Product Overview
DR. STRAUSS
Impulse Measurement Calibration - Diagnosis www.strauss.de
Impulse Voltage
Test -Technique
Measurement Calibration Diagnosis
Measuring Rack MIRA 25 19 TFT Display Keyboard with trackball in drawer Color Laser Printer in drawer Measuring rack mount with 1 to 4 channels Direct input 100 mV to 10 V on front Input 10 V to 2000 V on front Measuring line bushings to the rear suitable for i.v. tests and calibrations in the test field with high electromagnetic distortions
www.strauss.de
1 DR. STRAUSS SYSTEM-ELEKTRONIK GMBH D-96163 Gundelsheim/Bamberg Phone +49 951-43063 Fax +49 951-43858 INFO www.strauss.de email dr.strauss@ strauss.de
DR. STRAUSS
Impulse Measurement Calibration - Diagnosis www.strauss.de
Product Overview
MS/s, MHz 220 200 180 160 140 120 100 80 60 40 20 HIAS 743 1997 TR-AS 100 1987 PowerPro TR-AS 100 1989 TR-AS 200 1997 TR-AS 200 1997 IEC 1083-1 Requirem. 1991 TR-AS 200 2003 HIAS 742 0 Bandwidth MHz Resolution Bit SampleRate MS/s Performance progress of Digital Recorder in the last 16 years Bit 22 20 18 16 14 12 10 8 6 4 2 0
Highest performance with 60 up to 200 MS/s sampling rate and 8 to 14 Bit resolution
Already in 1987, the first TR-AS 100-8 Digital Recorder was delivered to customers for h.v. impulse tests and was therefore the first system with 100 MS/s sampling rate, which fulfilled all requirements of the IEC 1083-1, published later in 1991. A short time later in 1989 followed the TR-AS 100-10 Digital Recorder as the leading systems with 100 MS/s sampling rate at 10 Bit resolution which fulfilled all requirements of IEC 1083-1 in all respects for comparative measurements, too. The first competitor system with a sampling rate of 100 MS/s as required in IEC 1083-1 followed with 120 MS/s and 12 Bit resolution years later in 1997, when we finished the design of the TR-AS 200-12 Digital Recorder with 200 MS/s sampling rate and 12 Bit resolution. End of 2002 we presented a new designed system with 200 MS/s and 14 Bit resolution and further significantly reduced noice.
200 MS/s reduces measuring uncertainty 12 to 14 Bit show details of measured waves
The higher sampling rate of 200 MS/s (5ns sampling intervall instead of 8 or 10 ns) show increased accuracy and reduced standard deviations for the front time of full impulses as also for the peak and the time-to-chopping at front chopped impulses during calibration. The influence of the increased resolution from 10 Bit (0.1%) to 12 or 14 Bit (0.006 %) to the resulting overall measuring uncertainty of approx. 0.5% to 0.7% is hereby negligible. Desktop-Housing DERA 6 12 TFT Color Display Keyboard with trackball in drawer Measuring rack mount with 1 to 4 channels Direct input 100 mV to 10 V on rear Input 10 V to 1600/2000 V on rear suitable for i.v. tests and calibrations in the test field and on site The well-established Impulse Voltage Measuring Systems TR-AS, including the digital recorders from our own development and manufacturing, were consequently further developed and now feature improved sampling rates up to 200 MS/s in real-time with 14 Bit resolution simultaneously in up to 16 measuring channels. The new developed composit A/D-converter hardware system generates raw data with upto 14 Bit resolution together with the highest available sampling rate of 200 MS/ s today and optionally 400 MS/s with 10 to 12 Bit resolution is available for steep i.v. tests.
+0,5% Limit IEC 1083
TR-AS 200-14: The static integral nonlinearity INL referred to 14 Bit resolution shows at 200 MS/s an excellent lapse and stays signifikant inside the required limits of 0,5% in IEC 1083-1. The INL influences
directly the measuring accuracy as also the calibration results.The INL influences directly the measuring accuracy as also the calibration results.
A careful design using sophisticated programmable logic controllers and SMT optimizes the demanding requirements like high sampling rate, small risetime, minimized noise, short settling time, small measuring uncertainty and Working Desk with 19 good long-term accuracy. TFT-Display, KeyThis results in nearly smooth waveshapes without visible board, Mouse, Laser quantization steps and significantly improves the accuracy Printer and a separate of diagnosis using difference method or transfer function. Measuring Rack with The patented multi-timebase allows setting of up to 8 indiTR-AS RC System vidual sampling rates each with a selectable number of with 1 to 4 channels samples, so individual time profiles can be generated, e.g. Direct input 100 mV to a profile similar to an exponential timebase. 10 V As an option, for multichannel applications in the high poMeasuring Input 12 V wer test field, the sampling rate of each individual channel to 2000 V Input Connection Unit can be indepently selected. With this option fast tranFor easy connection of sients and slow events can be recorded with reference to measuring cables and a common trigger event and displayed together on the Terminating Resisstors monitor. Industrial PC Control Computer connected to the TR-AS digital recorder via Application: Precise Measurements in large High Voltage glassfibre LAN and High Power Testfields, Monitoring in Substations, Onfor use in test fields with suitable shielding Site-Measurements and Diagnosis
DR. STRAUSS
Impulse Measurement Calibration - Diagnosis www.strauss.de
The Frequency Response Analysis (FRA) on power transformers is used for diagnosis at works, after putting into operation and for maintenance on site. The frequency-dependent admittance is determined and recorded as fingerprint. The test object is connected as a 2pole to the connection unit with inbuilt step voltage impulse generator with up to 350 V peak voltage and sufficient energy without additional measuring lines and shunts.
1175 MVA Short Circuit Transformer winding 3.1-GND calibration test: 1 mS / 1 kOhm no load test:
The phase-synchronous averaging 1 MOhm || 30 pF technique improves the signal to noise ratio of the recorded data significant corresponding to 16 to 24 and more Bit. Because the instant of the step voltage excitation is not correlated to external electromagnetic fields, e.g. caused by power transformers, switchgear or radio stations, their influence is reduced corresponding to the number of accumulations applied.
Application: The generator is placed on the floor or wall in the h. for determination of the impulse scale factor and v. test field and connected to the h.v. divider. Meathe response parameters of the impulse measusurement and determination of response paramering system including h.v. divider according to IEC ters is automatically performed with calibration soft60060-2 / IEEE 4. ware TRAS-TEIL together with TRAS digital recorders.
DR. STRAUSS
Impulse Measurement Calibration - Diagnosis www.strauss.de
ISO-VER 2.2
2 or 4 kv a.c. isolation 1 to 8 channels input 1 to 1000 V 1 MOhm / 30 pF output 1 V A floating current input from mA to kA can bandwidth 0,1 / 2 MHz be realized using a suitable measuring accuracy 1%
shunt at the input.
ISO-VER 12
7 kv a.c. isolation 1 to 8 channels input 0.1 to 10 V 1 MOhm / 30 pF programmable output 2 V bandwidth 2.5 MHz accuracy 1%
Technical data and design subject to change without notice. Alternative design on request.