Sie sind auf Seite 1von 4

Power Plant 2 x 25 MVA Transformer

LOAD LOSS CALCULATIONS


% LOAD

75

KVA

20,000

IL(HV)

251.02

IL(LV)

1312.16

LOAD LOSS CALCULATIONS @ 50 HZ


I2R loss @ 280C

31,659.78 watts

I2R loss @ 310C

32,020.92 watts

Observed losses @ 310C

44,326.92 watts

Stray losses @ 310C

12,306.00 watts

LOAD LOSS CALCULATIONS @ 60 HZ


I2R loss @ 310C

32,020.92 watts

Stray losses @ 310C

17,720.64 watts

I2R loss @ 660C

36,234.20 watts

Stray losses @ 660C

15,660.10 watts

Total load losses @ 660C

51,894.30 watts

No load loss for S/B Transformer

Losses for 1 X 20/25 MVA @ 75% load


+ 1 x 20/25MVA @ standby mode

12,306.00 watts

64,200.30

watts

Power Plant 2 x 25 MVA Transformer


LOAD LOSS CALCULATIONS
% LOAD
KVA

37.5
20000 /25000

IL(HV)

125.511

IL(LV)

656.080

LOAD LOSS CALCULATIONS @ 50 HZ


I2R loss @ 280C

7,914.95 watts

I2R loss @ 310C

8,005.23 watts

Observed losses @ 310C

20,311.23 watts

Stray losses @ 310C

12,306.00 watts

LOAD LOSS CALCULATIONS @ 60 HZ


I2R loss @ 310C
Stray losses @ 310C
I2R loss @ 500C

8,005.23 watts
17,720.64 watts
8,577.03 watts

Stray losses @ 500C

16,539.26 watts

Total load loss for 1 transformer @ 500C

25,116.30 watts

Losses for 2 X 20/25 MVA @ 37.5% load


per transformer unit

50,232.59

watts

Das könnte Ihnen auch gefallen