E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
P R E -C O M M IS S IO N IN G T E S T R E P O R T
TRANSFORMER 01
Name of the Client Job Description Preference Standard Test Performed by Reviewed By
: DESH ENERGY LTD. : 35 MVA, 11/132 KV, 3-phase, 50Hz, Power Transformer : BS-171, IEC-76 : Engr. Rashiduzzaman Bulbul (Asstt. Engr., XFR, Testing) Engr. Mamun Biswas (Asstt. Engr., XFR, R&D) : Engr. Faruk Hannan Raju (Sr. Engr., R&D)
: 08/12/2010 - 09/12/2010 :
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
CONTENTS
PHYSICAL INSPECTIONS
1.1 1.2
Inspection for Transformer condition on arrival at site Inspection for Transformer Accessories
2.
TEST ITEMS 2.1 2.2 2.3 2.4 2.5 Magnetic Balance test Measurement of excitation current Vector group test Measurement of voltage ratio Measurement of winding insulation resistance
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
Note: for any serious damaged the matter should be immediately informed to Energypac Engineering Ltd. 2. Checking Result Check Item External Damage Rust Bolts & Nuts Oil leakage Date 08/12/2010 08/12/2010 08/12/2010 08/12/2010 Results None None Tightened none Remarks Good Good Good Good
RESULT
Satisfactory_______
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
Delta 11 1837 LI 650 kV, AC 275 kV LI 325 kV, AC 140 kV LI 75 kV, AC 28 kV 11000 Volts in all Tap Positions.
Rated Voltage (in kV) : Rated Current (in Ampere) : ONAF : Insulation level (in kV) HV Winding HV-N Winding LV W inding LV Voltage
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
TEST ITEMS
PROCEDURE: The following procedures are followed during magnetic balance check: 1) Single phase supply (220v) is applied across one phase. 2) Voltage is measured from the other two phase. For A-phase, when single phase voltage is applied in A-phase, flux A is produced. A will induce flux B and C phase and for this,voltage will be generated at B & C phase.
A So, A =B + C. OR, NIA/RA = NIB/RB + NIC/RC As Rc > RB , c < B. Prepared By Checked By Testing Engr. Mamun Biswas Faruk Hannan Rashiduzzaman Page 6 of 13 c
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
So voltage induced in the C phase must be less than the voltage induced in phase B. That is, VBN > VCN. Criteria 1. For a balance 3 phase circuit, VAN + VBN + VCN = 0 VAN = -( VBN + VCN)criteria 2. So the sum of the voltage induced on the two phases should be almost equal to the applied voltage on the 3rd phase.
PHASE C: THE SAME RESULT WILL BE OBTAINED WHILE APPLYING VOLTAGE IN THE CPHASE. For C-phase, VcN = -( VBN + VAN).
PHASE B: FOR B-phase, as B is the middle phase, the flux induced by B, will be equally divided and A & C phase will be induced equally. So, B =C + A. OR, NIB/RB = NIC/RC + NIA/RA Accordingly, VBN = -( VCN + VAN).
The above theory is verified in the test results given on the next page.
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
234 V = = 182 V 52 V
From the test data, the magnetic circuit is confirmed as a balanced circuit.
** **
Voltage measured by FLUKE-189 Digital Meter, manufactured by FLUKE,USA. Current measured by KYORITSU-2431 milli amps Meter, by kyoritsu, japan.
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
3-phase Supply from HV side Measured Voltage A-B : 407 V, Measured current : IA = 5.6 mA Measured Voltage B-C : 409 V, Measured current : IB = 2.4 mA Measured Voltage C-A : 409 V, Measured current : IC = 4.03 mA
** **
Voltage measured by FLUKE-189 Digital Meter, manufactured by FLUKE,USA Current measured by KYORITSU-2431 milli amps Meter, by kyoritsu, japan.
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
Step 2: C and c is shorted. Then the vector diagram turns into the following: A a c,C b Vectorially. Voltage of Aa=Bb=Ba And Ab is greater than all other voltage. So. Ab> Aa=Ba=Bb..(1) Step 3: measurement is performed to record the magnitude of Ab,Aa,Ba,Bb, comparison is done according to 1. The above procedures are followed below: B
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
DEPARTMENT OF RESEARCH & DEVELOPMENT REF : EELF/TR- DESH- 35 MVA REV : 00 TEST DATA: Terminals C and c shorted together. Voltage applied across the terminals A -B - C
410V, AC
= = = =
As the terminal voltage across B b = A a = B a and A-b > Voltage across All Other Terminals, The Vector Group Test is confirmed as YNd1. Result: _____________Vector group is ok____
**
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
HT Voltage 145200 143550 141900 140250 138600 136950 135300 133650 132000 130350 128700 127050 125400 123750 122100 120450 118800 117150 115500 113850 112200 110550 108900 107250 105600
LT Voltage 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000 11000
ACTUAL RATIO 7.621 7.534 7.447 7.361 7.274 7.188 7.101 7.014 6.928 6.841 6.754 6.668 6.581 6.495 6.408 6.321 6.235 6.148 6.062 5.975 5.888 5.802 5.715 5.629 5.542
Measured RATIO Phase-A Phase-B Phase-C 7.659 7.652 7.650 7.570 7.564 7.564 7.482 7.475 7.475 7.393 7.387 7.388 7.306 7.298 7.299 7.215 7.211 7.210 7.128 7.123 7.122 7.035 7.034 7.034 6.951 6.946 6.945 6.862 6.857 6.856 6.773 6.769 6.769 6.685 6.680 6.681 6.598 6.592 6.592 6.509 6.503 6.504 6.420 6.416 6.416 6.332 6.328 6.328 6.244 6.239 6.239 6.155 6.151 6.151 6.068 6.063 6.064 5.979 5.976 5.975 5.891 5.888 5.887 5.803 5.798 5.797 5.714 5.710 5.710 5.627 5.622 5.622 5.538 5.534 5.534
Remarks: ** **
The voltage ration between HT & LT side of the transformer for every TAP POSITION is OK. The vector group of this transformer is YNd1
Measured by Vanguard Turn Ratio Meter (Model: ATRT-03, S/N-18661) Manufactured by Vanguard Instrument Co., Inc. Calibrated by Cali-Labs Pv. Ltd., Bhopal, India Mamun Biswas Faruk Hannan Rashiduzzaman Page 12 of 13
ENERGYPAC
E N E R G Y P A C E N G I N E E R I N G L T D.
D A T E : 12/12/20 1 0
2.5
Test Voltage = Mean Transformer Oil Temperature = Measured After 15 Sec. 60 Sec. DAR
Insulation Resistance (Giga Ohms) HV E LV E HV LV 9.12 4.60 8.35 13.10 7.40 11.50 1.43 1.60 1.37
Result: ________Satisfactory_______
** Insulation Resistance measured by 5kV Electronic BM !4 Mega-ohm Meter & 5 kV Megger manufactured by Megger Industries Ltd., England.