"ASCE702W" --- ASCE 7-02 CODE WIND ANALYSIS PROGRAM

Program Description:
"ASCE702W" is a spreadsheet program written in MS-Excel for the purpose of wind loading analysis for buildings and structures per the ASCE 7-02 Code. Specifically, wind pressure coefficients and related and required parameters are selected or calculated in order to compute the net design wind pressures. This program is a workbook consisting of eight (8) worksheets, described as follows:

Worksheet Name
Doc Simplified MWFRS (Low-Rise) MWFRS (Any Ht.) Wall C&C Roof C&C Stacks & Tanks Wind Map

Description
This documentation sheet Analysis using simplified method for low-rise buildings with h <= 60 Main Wind-Force Resisting System for low-rise buildings with h <= 60 Main Wind-Force Resisting System for buildings of any height Analysis of wall Components and Cladding Analysis of roof Components and Cladding Analysis of cantilevered chimneys, stacks, and vertical tanks Basic wind speed map (Figure 6-1 of ASCE 7-02 Code)

Program Assumptions and Limitations:


1. This program assumes only enclosed or partially enclosed buildings. Open buildings are NOT considered. 2. Worksheet for Simplified analysis is applicable for low-rise buildings meeting the criteria of Section 6.4.1. 3. In the worksheet for Simplified analysis, the design MWFRS wind load is calculated for each direction. The design MWFRS load is assumed to be the total wind load on either the width or the length of the building respectively. 4. Worksheet for MWFRS (Low-Rise) is applicable for low-rise buildings as defined in Section 6.2. 5. Worksheets for MWFRS (Any Ht.), Wall C&C, and Roof C&C are applicable for buildings with mean roof heights of up to 500 feet. 6. In worksheets for MWFRS (Any Ht.), Wall C&C, and Roof C&C the user may opt to utilize user designated "steps" in height, "z", in determining the wind pressure distribution. 7. Worksheet for Stacks & Tanks is applicable for cantilevered structures up to 600 feet tall. 8. Worksheets for Wall C&C and Roof C&C are applicable for flat roof buildings, gable roof buildings with roof angles <= 45 degrees, and monoslope roof buildings with roof angles <= 3 degrees. 9. Worksheets for MWFRS (Any Ht.) and for Stacks & Tanks can handle rigid as well as flexible buildings and structures. For rigid buildings or structures, this program uses the smaller value of either 0.85 or the calculated value from Section 6.5.8.1 of the Code for the gust effect factor, 'G'. For flexible buildings or structures, this program calculates the gust effect factor, Gf, per Section 6.5.8 of the Code based on the assumed formula for the fundamental period of vibration from Section 9.5.5.3 of the Code. 10. This program uses the equations listed in the reference, Guide to the Use of the Wind Load Provisions of ASCE 7-02 for determining the external wind pressure coefficients, GCp, used in the Wall C&C and Roof C&C worksheets. 11. This program contains numerous comment boxes which contain a wide variety of information including explanations of input or output items, equations used, data tables, etc. (Note: presence of a comment box is denoted by a red triangle in the upper right-hand corner of a cell. Merely move the mouse pointer to the desired cell to view the contents of that particular "comment box".)

NALYSIS PROGRAM

analysis for buildings

"ASCE702W" es una hoja de clculo escrita en MS-Excel con el propsi de viento para edificios y estructuras con el cdigo ASCE 7-02. Especific coeficientes de presiones de viento y relativos y parmetros, para calcul

Description

ocumentation sheet ethod for low-rise buildings with h <= 60 System for low-rise buildings with h <= 60 ing System for buildings of any height l Components and Cladding f Components and Cladding chimneys, stacks, and vertical tanks p (Figure 6-1 of ASCE 7-02 Code)

buildings with roof

Load Provisions of Wall C&C and Roof

of a comment box ouse pointer to the

crita en MS-Excel con el propsito de analizar las cargas n el cdigo ASCE 7-02. Especificamente, se seleccionan o calculan ativos y parmetros, para calcular las presiones de diseo del viento.

"ASCE702W.xls" Program Version 1.7

WIND LOADING ANALYSIS - MWFRS and Components/Cladding


Per ASCE 7-02 Code for Low-Rise, Enclosed Buildings with h <= 60' and Roof q <= 45o Using Method 1: Simplified Procedure (Section 6.4) Job Name: Subject: Job Number: Originator: Checker: Input Data: Wind Speed, V = 90 mph (Wind Map, Figure 6-1) Bldg. Classification = II (Table 1-1) Exposure Category = B (Sect. 6.5.6) Ridge Height, hr = 19.00 ft. (hr >= he) Eave Height, he = 15.00 ft. (he <= hr) Building Width, W = 41.00 ft. (Normal to Building Ridge) Building Length, L = 61.00 ft. (Parallel to Building Ridge) Roof Type = Monoslope (Gable or Monoslope) Wall C&C Name = Wall (Girt, Siding, Wall, or Fastener) Wall C&C Eff. Area = 75.00 ft.^2 (for Component/Cladding) Roof C&C Name = Joist (Purlin, Joist, Decking, or Fastener) Roof C&C Eff. Area = 205.00 ft.^2 (for Component/Cladding) Overhang Eff. Area = 0.00 ft.^2 (for Component/Cladding) Resulting Parameters and Net Design Pressures: For Transverse Direction: Roof Angle, q = 5.57 Mean Roof Ht., h = 15.00 Adjustment Factor, l = 1.000 Importance Factor, I = 1.00 Wall & Roof End Zone Width, a = 4.100 (wind perpendicular to ridge) W deg. Elevation ft. (h = he for q < 10 deg.) (adjusts for height and exposure) (Table 6-1) ft. (use: "2*a" for MWFRS, "a" for C&C)

Plan

hr

qo
h<=60'
he

Transverse MWFRS Net Pressures (psf) Location Direction Zone Load Case 1 Load Case 2 A = end zone of wall Horizontal A 12.99 --B = end zone of roof Horizontal B 0.00 --C = interior zone of wall Horizontal C 8.63 --D = interior zone of roof Horizontal D 0.00 --E = end zone of windward roof Vertical E -15.40 --F = end zone of leeward roof Vertical F -8.87 --G = interior zone of windward roof Vertical G -10.70 --H = interior zone of leeward roof Vertical H -6.85 --For Longitudinal Direction: Roof Angle, q = 0.00 Mean Roof Ht., h = 17.00 Adjustment Factor, l = 1.000 (wind parallel to ridge) deg. (assumed) ft. (h = (hr+he)/2) (adjusts for height and exposure)

Longitudinal MWFRS Net Pressures (psf) Location Direction Zone Load Case 1 Load Case 2 A = end zone of wall Horizontal A 12.80 --B = end zone of roof Horizontal B 0.00 --C = interior zone of wall Horizontal C 8.50 --D = interior zone of roof Horizontal D 0.00 --E = end zone of windward roof Vertical E -15.40 --F = end zone of leeward roof Vertical F -8.80 --G = interior zone of windward roof Vertical G -10.70 --H = interior zone of leeward roof Vertical H -6.80 ---

4 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7


(continued)

5 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Total Design MWFRS Horizontal Load (kips) Transverse Longitudinal


Load Case 1 Load Case 2 Min. Load Load Case 1 Load Case 2 Min. Load

8.97 --11.59 7.12 --6.97 Formulas: Ph(Trans) = ((Pc*(L-4*a)+Pa*4*a)*he+(Pd*(L-4*a)+Pb*4*a)*(hr-he))/1000 Ph(Trans)(min) = P(min)*L*hr/1000 , where: P(min) = 10.0 psf on projected area Ph(Long) = (Pa*(hr+he)/2*4*a+Pc*((hr+he)/2*W-(hr+he)/2*4*a))/1000 Ph(Long)(min) = P(min)*W*(hr+he)/2/1000 , where: P(min) = 10.0 psf on full area Components & Cladding Net Pressures (psf) Location Zone Pos. (+) Wall 4 = interior zone of wall 4 12.70 5 = end zone of wall 5 12.70 1 = interior zone of roof 1 4.70 Roof Joist 2 = end zone of roof 2 4.70 3 = corner zone of roof 3 4.70 Roof Overhang 2 = end zone of o.h. 2 --3 = corner zone of o.h. 3 --Item

Neg. (-) -13.95 -15.80 -13.30 -15.80 -15.80 -----

Notes: 1. For Method 1: Simplified Procedure of Section 6.4 to be used for an enclosed low-rise building to determine the design wind loads, all of the following nine conditions of 6.4.1.1 must be met: a. Building is a simple diaphragm building, in which wind loads are transmitted through floor and roof diaphragms to the vertical Main Wind-Force Resisting System (MWFRS). b. Building is a low-rise building where mean roof height, h <= 60 ft., and h <= min. of L or W. c. Building is enclosed and conforms to wind-borne debris provisions of Section 6.5.9.3. d. Building is a regular shaped building, having no unusual geometrical irregularity. f. Building is not classified as a flexible building so it is considered "rigid". g. Building is not subject to across-wind loading, vortex shedding, etc. h. Building has no expansion joints or separations. i. Building is not subject to topographic effects, no abrupt topographic changes. j. Building has an approximately symmetrical cross section in each direction with either a flat roof, or gable roof with q <= 45 degrees. 2. Wind pressures (ps30) in Figures 6-2 and 6-3 were prepared based on following assumptions: a. Mean roof height, h = 30 ft. , Exposure category = B , Importance factor, I =1.0 b. Velocity pressure exposure coefficient, Kz = 0.70 c. Directionality factor, Kd = 0.85 , Topographic factor, Kzt = 1.0 d. Internal pressure coefficients, GCpi = +0.18, -0.18 (enclosed building) e. MWFRS pressure coeff's. from Figure 6-10, and C&C pressure coeff's. from Figure 6-11. f. Design wind pressure, Ps = l*I*ps30, in psf. 3. Design wind pressures are net pressures (sum of external and internal pressures). 4. Wall net pressure for MWFRS is total for both windward and leeward walls. 5. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. 6. If pressures for Zones "B" and "D" < 0, assume = 0. 7. For the design of the longitudinal MWFRS use roof angle, q = 0 degrees. 8. Both load cases 1 and 2 are be checked for roof angle, 25 degrees < q <= 45 degrees. 9. The total design MWFRS horizontal load is the total horizontal wind load on either the length (L) or the width (W) of the building respectively assuming one end zone of a width = 2*a. 10. Minimum wind load for MWFRS design shall be 10 psf applied on projected vertical plane. Minimum wind load for C&C shall be 10 psf acting in either direction normal to surface. 11. References: a. ASCE 7-02 Standard, "Minimum Design Loads for Buildings and Other Structures". b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004).
(continued)

6 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

MWFRS - Wind Zones

Components and Cladding - Wind Zones

7 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

WIND LOADING ANALYSIS - Main Wind-Force Resisting System


Job Name: Job Number: Input Data: Wind Speed, V = Bldg. Classification = Exposure Category = Ridge Height, hr = Eave Height, he = Building Width = Building Length = Roof Type = Topo. Factor, Kzt = Direct. Factor, Kd = Enclosed? (Y/N) 90 II C 53.33 20.00 200.00 250.00
Gable

Per ASCE 7-02 Code for Enclosed or Partially Enclosed Buildings Using Method 2: Analytical Procedure (Section 6.5) for Low-Rise Buildings Subject: Originator: Checker:

1.00 0.85 Y

mph (Wind Map, Figure 6-1) (Table 1-1) (Sect. 6.5.6) ft. (hr >= he) ft. (he <= hr) ft. (Normal to Building Ridge) ft. (Parallel to Building Ridge) (Gable or Monoslope) (Sect. 6.5.7 & Figure 6-4) (Table 6-4) (Sect. 6.2 & Figure 6-5)

Wind

Plan

hr

qo
h<=60'

Resulting Parameters and Coefficients: Roof Angle, q = Mean Roof Ht., h = 18.43 36.67 deg. ft. (h = (hr+he)/2, for angle >10 deg.)
L

Elevation

Check Criteria for a Low-Rise Building: 1. Is h <= 60' ? Yes, O.K.

2. Is h <= Lesser of L or B?

Yes, O.K.

External Pressure Coeff's., GCpf (Fig. 6-10): (For values, see following wind load tabulations.) Positive & Negative Internal Pressure Coefficients, GCpi (Figure 6-5): +GCpi Coef. = 0.18 (positive internal pressure) -GCpi Coef. = -0.18 (negative internal pressure) If h < 15 then: Kh = 2.01*(15/zg)^(2/a) (Table 6-3, Case 1b) If h >= 15 then: Kh = 2.01*(z/zg)^(2/a) (Table 6-3, Case 1b) a= 9.50 (Table 6-2) zg = 900 (Table 6-2) Kh = 1.02 (Kh = Kz evaluated at z = h) I= 1.00 (Table 6-1) (Importance factor) Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15) qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h) qh = 18.06 psf Design Net External Wind Pressures (Sect. 6.5.12.2.2): p = qh*[(GCpf) - (+/-GCpi)] (psf, Eq. 6-18) Wall and Roof End Zone Widths 'a' and '2*a' (Fig. 6-10): a= 14.67 ft. 2*a = 29.33 ft.

8 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7 MWFRS Wind Load for Transverse Direction Surface GCpf p = Net Pressures (psf) (w/ +GCpi) (w/ -GCpi) Zone 1 0.52 6.08 12.58 Zone 2 -0.69 -15.71 -9.21 Zone 3 -0.47 -11.71 -5.21 Zone 4 -0.42 -10.75 -4.25 Zone 5 -0.45 -11.38 -4.88 Zone 6 -0.45 -11.38 -4.88 Zone 1E 0.78 10.84 17.34 Zone 2E -1.07 -22.57 -16.07 Zone 3E -0.67 -15.41 -8.91 Zone 4E -0.62 -14.41 -7.91 MWFRS Wind Load for Longitudinal Direction Surface *GCpf p = Net Pressures (psf) (w/ +GCpi) Zone 1 0.40 3.97 Zone 2 -0.69 -15.71 Zone 3 -0.37 -9.93 Zone 4 -0.29 -8.49 Zone 5 -0.45 -11.38 Zone 6 -0.45 -11.38 Zone 1E 0.61 7.77 Zone 2E -1.07 -22.57 Zone 3E -0.53 -12.82 Zone 4E -0.43 -11.02

*Note: Use roof angle q = 0 degrees for Longitudinal Direction. For Transverse when GCpf is neg. in Zone 2: For Longitudinal when GCpf is neg. in Zone 2: Zone 2 distance = 91.66 ft. Zone 2 distance = 91.66 Remainder of roof Zone 2 to have roof Zone 3 pressures. MWFRS Wind Load for Transverse, Torsional Case Surface GCpf p = Net Pressure (psf) (w/ +GCpi) (w/ -GCpi) Zone 1T --1.52 3.14 Zone 2T ---3.93 -2.30 Zone 3T ---2.93 -1.30 Zone 4T ---2.69 -1.06 MWFRS Wind Load for Long., Torsional Case Surface GCpf p = Net Pressure (psf) (w/ +GCpi) Zone 1T --0.99 Zone 2T ---3.93 Zone 3T ---2.48 Zone 4T ---2.12

Notes: 1. For Transverse, Longitudinal, and Torsional Cases: Zone 1 is windward wall for interior zone. Zone 1E is windward wall for end zone. Zone 2 is windward roof for interior zone. Zone 2E is windward roof for end zone. Zone 3 is leeward roof for interior zone. Zone 3E is leeward roof for end zone. Zone 4 is leeward wall for interior zone. Zone 4E is leeward wall for end zone. Zones 5 and 6 are sidewalls. Zone 1T is windward wall for torsional case Zone 2T is windward roof for torsional case. Zone 3T is leeward roof for torsional case Zone 4T is leeward wall for torsional case. 2. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. 3. Building must be designed for all wind directions using the 8 load cases shown below. The load cases are applied to each building corner in turn as the reference corner. 4. Wind loads for torsional cases are 25% of respective transverse or longitudinal zone load values. Torsional loading shall apply to all 8 basic load cases applied at each reference corner. Exception: One-story buildings with "h" <= 30', buildings <= 2 stories framed with light frame construction, and buildings <=2 stories designed with flexible diaphragms need not be designed for torsional load cases. 5. Per Code Section 6.1.4.1, the minimum wind load for MWFRS shall not be less than 10 psf. 6. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures". b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004).

9 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7 Low-Rise Buildings h <= 60'

10 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

ng System

ldings e Buildings

h<=60'

he

11 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

for Longitudinal Direction p = Net Pressures (psf) (w/ -GCpi) 10.47 -9.21 -3.43 -1.99 -4.88 -4.88 14.27 -16.07 -6.32 -4.51

pf is neg. in Zone 2: ft.

for Long., Torsional Case p = Net Pressure (psf) (w/ -GCpi) 2.62 -2.30 -0.86 -0.50

for torsional case.

l zone load values.

12 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

13 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

WIND LOADING ANALYSIS - Main Wind-Force Resisting System


Per ASCE 7-02 Code for Enclosed or Partially Enclosed Buildings Using Method 2: Analytical Procedure (Section 6.5) for Buildings of Any Height Job Name: Subject: Job Number: Originator: Checker: Input Data: Wind Direction = Wind Speed, V = Bldg. Classification = Exposure Category = Ridge Height, hr = Eave Height, he = Building Width = Building Length = Roof Type = Topo. Factor, Kzt = Direct. Factor, Kd = Enclosed? (Y/N) Damping Ratio, b = Period Coef., Ct = Normal 120 II B 157.00 157.00 100.00 200.00 Monoslope 1.00 0.85 Y 0.030 0.0200 (Normal or Parallel to building ridge)
mph (Wind Map, Figure 6-1)

Wind

(Table 1-1) (Sect. 6.5.6) ft. (hr >= he) ft. (he <= hr) ft. (Normal to Building Ridge) ft. (Parallel to Building Ridge) (Gable or Monoslope) (Sect. 6.5.7 & Figure 6-4) (Table 6-4) (Sect. 6.2 & Figure 6-5) (Suggested Range = 0.010-0.070) (Suggested Range = 0.020-0.035) hr
(Assume: T = Ct*h^(3/4) , and f = 1/T)

Plan

qo
h he

Resulting Parameters and Coefficients: Roof Angle, q = Mean Roof Ht., h = Windward Wall Cp = Leeward Wall Cp = Side Walls Cp = Roof Cp (zone #1) = Roof Cp (zone #2) = Roof Cp (zone #3) = Roof Cp (zone #4) = +GCpi Coef. = -GCpi Coef. = 0.00 157.00 0.80 -0.50 -0.70 -1.04 -0.70 N.A. N.A. 0.18 -0.18 deg. ft. (h = he, for roof angle <=10 deg.) (Fig. 6-6) (Fig. 6-6) (Fig. 6-6) -0.18 (Fig. 6-6) (zone #1 for 0 to h/2) -0.18 (Fig. 6-6) (zone #2 for h/2 to h) N.A. (Fig. 6-6) (zone #3 for h to 2*h) N.A. (Fig. 6-6) (zone #4 for > 2*h) (Figure 6-5) (positive internal pressure) (Figure 6-5) (negative internal pressure)

Elevation

L = 100 ft. B = 200 ft.

If z <= 15 then: Kz = 2.01*(15/zg)^(2/a) , If z > 15 then: Kz = 2.01*(z/zg)^(2/a) (Table 6-3, Case 2a) a= 7.00 zg = 1200 (Table 6-2) Kh = 1.12 (Kh = Kz evaluated at z = h) I= 1.00 (Table 6-1) (Importance factor) Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15) qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h) qh = 35.23 psf Ratio h/L = 1.570 freq., f = 1.127 hz. (f >= 1, Rigid structure) Gust Factor, G = 0.818 (Sect. 6.5.8) Design Net External Wind Pressures (Sect. 6.5.12.2): p = qz*G*Cp - qi*(+/-GCpi) for windward wall (psf), where: qi =qh (Eq. 6-17, Sect. 6.5.12.2.1) p = qh*G*Cp - qi*(+/-GCpi) for leeward wall, sidewalls, and roof (psf), where: qi = qh (Sect. 6.5.12.2.1)

14 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7 Normal to Ridge Wind Load Tabulation for MWFRS - Buildings of Any Height z Kz qz Cp p = Net Design Press. (psf) (ft.) (psf) (w/ +GCpi) (w/ -GCpi) Windward Wall 0 0.57 18.01 0.80 5.45 18.13 15.00 0.57 18.01 0.80 5.45 18.13 20.00 0.62 19.55 0.80 6.46 19.14 25.00 0.67 20.84 0.80 7.30 19.98 30.00 0.70 21.95 0.80 8.03 20.71 35.00 0.73 22.94 0.80 8.68 21.36 40.00 0.76 23.83 0.80 9.26 21.94 45.00 0.79 24.65 0.80 9.80 22.48 50.00 0.81 25.40 0.80 10.29 22.97 55.00 0.83 26.10 0.80 10.75 23.43 60.00 0.85 26.76 0.80 11.18 23.86 70.00 0.89 27.97 0.80 11.97 24.65 80.00 0.93 29.05 0.80 12.68 25.36 90.00 0.96 30.05 0.80 13.33 26.01 100.00 0.99 30.97 0.80 13.93 26.61 120.00 1.04 32.62 0.80 15.01 27.70 140.00 1.09 34.09 0.80 15.98 28.66 For z = hr: 157.00 1.12 35.23 0.80 16.72 29.40 Surface

For z = he: For z = h: Leeward Wall Side Walls


Roof (zone #1) cond. 1 Roof (zone #1) cond. 2 Roof (zone #2) cond. 1 Roof (zone #2) cond. 2

157.00 157.00 All All -

1.12 1.12 -

35.23 35.23 -

0.80 0.80 -0.50 -0.70 -1.04 -0.18 -0.70 -0.18

16.72 16.72 -20.75 -26.52 -36.32 -11.53 -26.52 -11.53

29.40 29.40 -8.07 -13.84 -23.64 1.15 -13.84 1.15

Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. 2. Per Code Section 6.1.4.1, the minimum wind load for MWFRS shall not be less than 10 psf. 3. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures". b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004). 4. Roof zone #1 is applied for horizontal distance of 0 to h/2 from windward edge. 5. Roof zone #2 is applied for horizontal distance of h/2 to h from windward edge.

15 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Determination of Gust Effect Factor, G: Is Building Flexible? No f >=1 Hz.

1: Simplified Method for Rigid Building G= 0.850 Parameters Used in Both Item #2 and Item #3 Calculations (from Table 6-2): a^ = 0.143 b^ = 0.84 a(bar) = 0.250 b(bar) = 0.45 c= 0.30 l= 320 ft. e(bar) = 0.333 z(min) = 30 ft. Calculated Parameters Used in Both Rigid and/or Flexible Building Calculations: z(bar) = 94.20 = 0.6*h , but not < z(min) , ft. Iz(bar) = 0.252 = c*(33/z(bar))^(1/6) , Eq. 6-5 = l*(z(bar)/33)^(e(bar)) , Eq. 6-7 Lz(bar) = 453.94 gq = 3.4 (3.4, per Sect. 6.5.8.1) gv = 3.4 (3.4, per Sect. 6.5.8.1) gr = 4.218 = (2*(LN(3600*f)))^(1/2)+0.577/(2*LN(3600*f))^(1/2) , Eq. 6-9 Q= 0.805 = (1/(1+0.63*((B+h)/Lz(bar))^0.63))^(1/2) , Eq. 6-6 2: Calculation of G for Rigid Building G= 0.818 = 0.925*((1+1.7*gq*Iz(bar)*Q)/(1+1.7*gv*Iz(bar))) , Eq. 6-4 3: Calculation of Gf for Flexible Building b= 0.030 Damping Ratio Ct = 0.020 Period Coefficient T= 0.887 = Ct*h^(3/4) , sec. (Period) f= 1.127 = 1/T , Hz. (Natural Frequency) V(fps) = N.A. = V(mph)*(88/60) , ft./sec. = b(bar)*(z(bar)/33)^(a(bar))*V*(88/60) , ft./sec. , Eq. 6-14 V(bar,zbar) = N.A. N1 = N.A. = f*Lz(bar)/(V(bar,zbar)) , Eq. 6-12 Rn = N.A. = 7.47*N1/(1+10.3*N1)^(5/3) , Eq. 6-11 hh = N.A. = 4.6*f*h/(V(bar,zbar)) = (1/hh)-1/(2*hh^2)*(1-e^(-2*hh)) for hh > 0, or = 1 for hh = 0 ,Eq. 6-13 Rh = N.A. hB = N.A. = 4.6*f*B/(V(bar,zbar)) = (1/hB)-1/(2*hB^2)*(1-e^(-2*hB)) for hB > 0, or = 1 for hB = 0,Eq. 6-13 RB = N.A. hL = N.A. = 15.4*f*L/(V(bar,zbar)) = (1/hL)-1/(2*hL^2)*(1-e^(-2*hL)) for hL > 0, or = 1 for hL = 0 ,Eq. 6-13 RL = N.A. = ((1/b)*Rn*Rh*RB*(0.53+0.47*RL))^(1/2) , Eq. 6-10 R= N.A. Gf = N.A. = 0.925*(1+1.7*Iz(bar)*(gq^2*Q^2+gr^2*R^2)^(1/2))/(1+1.7*gv*Iz(bar)) , Use: G = 0.818 Eq. 6-8

16 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Figure 6-9 - Design Wind Load Cases of MWFRS for Buildings of All Heights

Case 1: Full design wind pressure acting on the projected area perpendicular to each principal axis of the structure, considered separately along each principal axis. Case 2: Three quarters of the design wind pressure acting on the projected area perpendicular to each principal axis of the structure in conjunction with a torsional moment as shown, considered separately for each principal axis. Case 3: Wind pressure as defined in Case 1, but considered to act simultaneously at 75% of the specified value. Case 4: Wind pressure as defined in Case 2, but considered to act simultaneously at 75% of the specified value. Notes: 1. Design wind pressures for windward (Pw) and leeward (PL) faces shall be determined in accordance with the provisions of Section 6.5.12.2.1 and 6.5.12.2.3 as applicable for buildings of all heights. 2. Above diagrams show plan views of building. 3. Notation: Pwx, Pwy = Windward face pressure acting in the X, Y principal axis, respectively. PLx, PLy = Leeward face pressure acting in the X, Y principal axis, respectively. e (ex, ey) = Eccentricity for the X, Y principal axis of the structure, respectively. MT = Torsional moment per unit height acting about a vertical axis of the building.

17 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

WIND LOADING ANALYSIS - Wall Components and Cladding


Job Name: Job Number: Input Data: Wind Speed, V = Bldg. Classification = Exposure Category = Ridge Height, hr = Eave Height, he = Building Width = Building Length = Roof Type = Topo. Factor, Kzt = Direct. Factor, Kd = Enclosed? (Y/N) Component Name = Effective Area, Ae = 90 II C 53.33 20.00 200.00 250.00
Gable

Per ASCE 7-02 Code for Buildings of Any Height Using Method 2: Analytical Procedure (Section 6.5) Subject: Originator:

Checker:

1.00 0.85 Y Girt 208

mph (Wind Map, Figure 6-1) (Table 1-1) (Sect. 6.5.6) ft. (hr >= he) ft. (he <= hr) ft. (Normal to Building Ridge) ft. (Parallel to Building Ridge) (Gable or Monoslope) (Sect. 6.5.7 & Figure 6-4) (Table 6-4) (Sect. 6.2 & Figure 6-5) (Girt, Siding, Wall, or Fastener) ft.^2 (Area Tributary to C&C)

Plan

hr

qo
h

Resulting Parameters and Coefficients: Roof Angle, q = Mean Roof Ht., h = 18.43 36.67 deg. ft. (h = (hr+he)/2, for roof angle >10 deg.)

Elevation

Wall External Pressure Coefficients, GCp: GCp Zone 4 Pos. = 0.77 (Fig. 6-11A) GCp Zone 5 Pos. = 0.77 (Fig. 6-11A) GCp Zone 4 Neg. = -0.87 (Fig. 6-11A) GCp Zone 5 Neg. = -0.93 (Fig. 6-11A) Positive & Negative Internal Pressure Coefficients, GCpi (Figure 6-5): +GCpi Coef. = 0.18 (positive internal pressure) -GCpi Coef. = -0.18 (negative internal pressure) If z <= 15 then: Kz = 2.01*(15/zg)^(2/a) , If z > 15 then: Kz = 2.01*(z/zg)^(2/a) (Table 6-3, Case 1a) a= 9.50 (Table 6-2) zg = 900 (Table 6-2) Kh = 1.02 (Kh = Kz evaluated at z = h) I= 1.00 (Table 6-1) (Importance factor) Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15) qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h) qh = 18.06 psf Design Net External Wind Pressures (Sect. 6.5.12.4): For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf) For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf) where: q = qz for windward walls, q = qh for leeward walls and side walls qi = qh for all walls (conservatively assumed per Sect. 6.5.12.4.2)

18 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7 Wind Load Tabulation for Wall Components & Cladding z Kh qh p = Net Design Pressures (psf) (ft.) (psf) Zone 4 (+) Zone 4 (-) Zone 5 (+) 0 1.02 18.06 17.11 -18.91 17.11 15.00 1.02 18.06 17.11 -18.91 17.11 20.00 1.02 18.06 17.11 -18.91 17.11 25.00 1.02 18.06 17.11 -18.91 17.11 30.00 1.02 18.06 17.11 -18.91 17.11 35.00 1.02 18.06 17.11 -18.91 17.11 40.00 1.02 18.06 17.11 -18.91 17.11 45.00 1.02 18.06 17.11 -18.91 17.11 50.00 1.02 18.06 17.11 -18.91 17.11 53.33 1.02 18.06 17.11 -18.91 17.11

Component Girt

For z = hr:

For z = he: For z = h:

20.00 36.67

1.02 1.02

18.06 18.06

17.11 17.11

-18.91 -18.91

17.11 17.11

Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. 2. Width of Zone 5 (end zones), 'a' = 14.67 ft. 3. Per Code Section 6.1.4.2, the minimum wind load for C&C shall not be less than 10 psf. 4. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures". b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004).

19 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Wall Components and Cladding:

Wall Zones for Buildings with h <= 60 ft.

Wall Zones for Buildings with h > 60 ft.

20 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Cladding

he

Elevation

ble 6-3, Case 1a)

z evaluated at z = h)

21 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

ng sign Pressures (psf) Zone 5 (-) -20.13 -20.13 -20.13 -20.13 -20.13 -20.13 -20.13 -20.13 -20.13 -20.13

-20.13 -20.13

22 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

23 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

WIND LOADING ANALYSIS - Roof Components and Cladding


Per ASCE 7-02 Code for Bldgs. of Any Height with Gable Roof q <= 45o or Monoslope Roof q <= 3o Using Method 2: Analytical Procedure (Section 6.5) Job Name: Subject: Job Number: Originator: Checker: Input Data: Wind Speed, V = Bldg. Classification = Exposure Category = Ridge Height, hr = Eave Height, he = Building Width = Building Length = Roof Type = Topo. Factor, Kzt = Direct. Factor, Kd = Enclosed? (Y/N) Component Name = Effective Area, Ae = Overhangs? (Y/N) 90 II C 53.33 20.00 200.00 250.00
Gable

1.00 0.85 Y Joist 208 N

mph (Wind Map, Figure 6-1) (Table 1-1) (Sect. 6.5.6) ft. (hr >= he) ft. (he <= hr) ft. (Normal to Building Ridge) ft. (Parallel to Building Ridge) (Gable or Monoslope) (Sect. 6.5.7 & Figure 6-4) (Table 6-4) (Sect. 6.2 & Figure 6-5) (Purlin, Joist, Decking, or Fastener) ft.^2 (Area Tributary to C&C) (if used, overhangs on all sides)

Plan

hr

qo
h

Resulting Parameters and Coefficients: Roof Angle, q = Mean Roof Ht., h = 18.43 36.67 deg. ft. (h = (hr+he)/2, for roof angle >10 deg.)

Elevation

Roof External Pressure Coefficients, GCp: GCp Zone 1-3 Pos. = 0.30 (Fig. 6-11B thru 6-11D) GCp Zone 1 Neg. = -0.80 (Fig. 6-11B thru 6-11D) GCp Zone 2 Neg. = -1.20 (Fig. 6-11B thru 6-11D) GCp Zone 3 Neg. = -2.00 (Fig. 6-11B thru 6-11D) Positive & Negative Internal Pressure Coefficients, GCpi (Figure 6-5): +GCpi Coef. = 0.18 (positive internal pressure) -GCpi Coef. = -0.18 (negative internal pressure) If z <= 15 then: Kz = 2.01*(15/zg)^(2/a) , If z > 15 then: Kz = 2.01*(z/zg)^(2/a) (Table 6-3, Case 1a) a= 9.50 zg = 900 (Table 6-2) Kh = 1.02 (Kh = Kz evaluated at z = h) I= 1.00 (Table 6-1) (Importance factor) Velocity Pressure: qz = 0.00256*Kz*Kzt*Kd*V^2*I (Sect. 6.5.10, Eq. 6-15) qh = 0.00256*Kh*Kzt*Kd*V^2*I (qz evaluated at z = h) qh = 18.06 psf Design Net External Wind Pressures (Sect. 6.5.12.4): For h <= 60 ft.: p = qh*((GCp) - (+/-GCpi)) (psf) For h > 60 ft.: p = q*(GCp) - qi*(+/-GCpi) (psf) where: q = qh for roof qi = qh for roof (conservatively assumed per Sect. 6.5.12.4.2)

24 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7 Wind Load Tabulation for Roof Components & Cladding z Kh qh p = Net Design Pressures (psf) (ft.) (psf) Zone 1,2,3 (+) Zone 1 (-) Zone 2 (-) 0 1.02 18.06 8.67 -17.70 -24.92 15.00 1.02 18.06 8.67 -17.70 -24.92 20.00 1.02 18.06 8.67 -17.70 -24.92 25.00 1.02 18.06 8.67 -17.70 -24.92 30.00 1.02 18.06 8.67 -17.70 -24.92 35.00 1.02 18.06 8.67 -17.70 -24.92 40.00 1.02 18.06 8.67 -17.70 -24.92 45.00 1.02 18.06 8.67 -17.70 -24.92 50.00 1.02 18.06 8.67 -17.70 -24.92 53.33 1.02 18.06 8.67 -17.70 -24.92

Component Joist

For z = hr:

For z = he: For z = h:

20.00 36.67

1.02 1.02

18.06 18.06

8.67 8.67

-17.70 -17.70

-24.92 -24.92

Notes: 1. (+) and (-) signs signify wind pressures acting toward & away from respective surfaces. 2. Width of Zone 2 (edge), 'a' = 14.67 ft. 3. Width of Zone 3 (corner), 'a' = 14.67 ft. 4. For monoslope roofs with q <= 3 degrees, use Fig. 6-5B for 'GCp' values with 'qh'. 5. For buildings with h > 60' and q > 10 degrees, use Fig. 6-5B for 'GCpi' values with 'qh'. 6. For all buildings with overhangs, use Fig. 6-5B for 'GCp' values per Sect. 6.5.11.4.2. 7. If a parapet >= 3' in height is provided around perimeter of roof with q <= 10 degrees, Zone 3 shall be treated as Zone 2. 8. Per Code Section 6.1.4.2, the minimum wind load for C&C shall not be less than 10 psf. 9. References : a. ASCE 7-02, "Minimum Design Loads for Buildings and Other Structures". b. "Guide to the Use of the Wind Load Provisions of ASCE 7-02" by: Kishor C. Mehta and James M. Delahay (2004).

25 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Roof Components and Cladding:

Roof Zones for Buildings with h <= 60 ft. (for Gable Roofs <= 45o and Monoslope Roofs <= 3o)

Roof Zones for Buildings with h > 60 ft. (for Gable Roofs <= 10o and Monoslope Roofs <= 3o)

26 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Cladding

Monoslope Roof q <= 3o

he

Elevation

ble 6-3, Case 1a)

z evaluated at z = h)

27 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

ng sign Pressures (psf) Zone 3 (-) -39.37 -39.37 -39.37 -39.37 -39.37 -39.37 -39.37 -39.37 -39.37 -39.37

-39.37 -39.37

28 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

29 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

WIND LOADING ANALYSIS - Chimneys, Stacks, and Vertical Tanks


Per ASCE 7-02 Code for Cantilevered Structures Classified as Other Structures Job Name: Job Number: Input Data: V= Class. = Exposure = Kzt = h= Hb = D= Shape? b= Ct = Kd = 90 II B 1.00 80.00 50.00 3.00 Round 0.010 0.0412 0.95 Subject: Originator:

Checker:
D

mph (Wind Map, Figure 6-1) (Structure Classification from Table 1-1) (Exposure Category from Sect. 6.5.6) Wind (Topographic Factor from Sect. 6.5.7) ft. (Height of Stack/Tank itself) ft. (Ht. of Stack/Tank Base Above Ground) ft. (Diameter or Width of Surface Normal to Wind) Ground (Round, Hexagonal, or Square) Elevation (Damping Ratio = 0.010-0.070) (Period Coefficient = 0.020-0.035) (Direct. Factor, Table 6-4) Wind Load Tabulation for Stack / Tank z Kz qz p=qz*G*Cf (ft.) (psf) (psf) Resulting Parameters and Coefficients: 50.00 0.81 15.97 12.54 55.00 0.83 16.41 12.88 If z < 15 then: Kz = 2.01*(15/zg)^(2/a) 60.00 0.85 16.82 13.21 If z >= 15 then: Kz = 2.01*(z/zg)^(2/a) 65.00 0.87 17.21 13.51 a= 7.00 (Table 6-2) 70.00 0.89 17.58 13.80 zg = 1200 (Table 6-2) 75.00 0.91 17.93 14.08 I= 1.00 (Table 6-1) (Import. Factor) 80.00 0.93 18.26 14.34 h/D = 26.667 85.00 0.94 18.58 14.59 freq., f = 0.907 Hz. (f < 1) Flexible 90.00 0.96 18.89 14.83 G= 1.122 (Gust Factor, Sect. 6.5.8) 95.00 0.97 19.18 15.06 Cf = 0.700 (Figure 6-19)(Press. Coef.) 100.00 0.99 19.47 15.28 (for Mod. Smooth Surface) 105.00 1.00 19.74 15.50 110.00 1.02 20.00 15.71 Velocity Pressure (Sect. 6.5.10, Eq. 6-15): 120.00 1.04 20.51 16.10 qz = 0.00256*Kz*Kzt*Kd*V^2*I 130.00 1.07 20.98 16.47 Net Design Wind Pressures (Sect. 6.5.13): p = qz*G*Cf (psf) Net Design Wind Forces (Sect. 6.5.13, Eq. 6-25): F = qz*G*Cf*D (lb/ft) Resulting Total Base Shear & Moment: SV(total) = SM(total) = 3.53 324.23 kips ft-kips

30 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

Determination of Gust Effect Factor, G: Flexible? Yes f < 1 Hz.

1: Simplified Method for Rigid Structure G= N.A. Parameters Used in Both Item #2 and Item #3 Calculations (from Table 6-2): a^ = 0.143 b^ = 0.84 a(bar) = 0.250 b(bar) = 0.45 c= 0.30 l= 320 ft. e(bar) = 0.333 z(min) = 30 ft. Calculated Parameters Used in Both Rigid and/or Flexible Structure Calculations: z(bar) = 48.00 = 0.6*h , but not < z(min) , ft. Iz(bar) = 0.282 = c*(33/z(bar))^(1/6) , Eq. 6-5 Lz(bar) = 362.57 = l*(z(bar)/33)^(e(bar)) , Eq. 6-7 gq = 3.4 (3.4, per Sect. 6.5.8.1) gv = 3.4 (3.4, per Sect. 6.5.8.1) gr = 4.166 = (2*(LN(3600*f)))^(1/2)+0.577/(2*LN(3600*f))^(1/2) , Eq. 6-9 Q= 0.895 = (1/(1+0.63*((B+h)/Lz(bar))^0.63))^(1/2) , Eq. 6-6 2: Calculation of G for Rigid Structure G= N.A. = 0.925*((1+1.7*gq*Iz(bar)*Q)/(1+1.7*gv*Iz(bar))) , Eq. 6-4 3: Calculation of Gf for Flexible Structure b= 0.010 Damping Ratio Ct = 0.041 Period Coefficient T= 1.102 = Ct*h^(3/4) , sec. (Period) f= 0.907 = 1/T , Hz. (Natural Frequency) V(fps) = 132.00 = V(mph)*(88/60) , ft./sec. = b(bar)*(z(bar)/33)^(a(bar))*V*(88/60) , ft./sec. , Eq. 6-14 V(bar,zbar) = 65.23 N1 = 5.043 = f*Lz(bar)/(V(bar,zbar)) , Eq. 6-12 Rn = 0.050 = 7.47*N1/(1+10.3*N1)^(5/3) , Eq. 6-11 hh = 5.119 = 4.6*f*h/(V(bar,zbar)) = (1/hh)-1/(2*hh^2)*(1-e^(-2*hh)) for hh > 0, or = 1 for hh = 0 , Eq. 6-13a,b Rh = 0.176 hB = 0.192 = 4.6*f*b/(V(bar,zbar)) = (1/hB)-1/(2*hB^2)*(1-e^(-2*hB)) for hB > 0, or = 1 for hB = 0 , Eq. 6-13a,b RB = 0.883 hd = 0.643 = 15.4*f*L/(V(bar,zbar)) = (1/hL)-1/(2*hL^2)*(1-e^(-2*hL)) for hL > 0, or = 1 for hL = 0 , Eq. 6-13a,b RL = 0.680 = ((1/b)*Rn*Rh*RB*(0.53+0.47*RL))^(1/2) , Eq. 6-10 R= 0.817 Gf = 1.122 = 0.925*(1+1.7*Iz(bar)*(gq^2*Q^2+gr^2*R^2)^(1/2))/(1+1.7*gv*Iz(bar)) , Eq. 6-8 Use: G = 1.122

31 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

ertical Tanks

her Structures

Hb >= 0

lation for Stack / Tank F=qz*G*Cf*D (lb/ft) 37.61 38.65 39.62 40.54 41.41 42.23 43.02 43.77 44.49 45.18 45.85 46.49 47.12 48.30 49.42

32 of 41

5/3/2012 4:43 AM

"ASCE702W.xls" Program Version 1.7

h = 0 , Eq. 6-13a,b

hB = 0 , Eq. 6-13a,b

L = 0 , Eq. 6-13a,b

*gv*Iz(bar)) , Eq. 6-8