VERSION 3.00
Table of Contents
HPC301 Introduction
Software Up dates
A1
HPC301 Introduction
The HPC301 (HART Pocket Configurator) is a Palm OS based software that runs in the Palm Operating System version 3.5 and later. The HPC301 Package is comprised of three parts: 1. 2. 3. The communication interface, specifically the HPI311 (HART Pocket Interface), the Palm OS based handheld, and the configuration software, specifically the HPC301 (HART Pocket Configurator).
The HPC301 software is compatible with most Palm handheld versions, this gives the user the flexibility to choose which handheld would be best suited for their purposes. Listed below are the three communication interfaces supported (refer to the HPI311 Reference Guide): HPI311-V - Compatible with Palm V/Vx. HPI311-III - Compatible with Palm IIIc, and VIIx. (Palm VIIx is available only in the USA.) HPI311-M5 - Compatible with Palm m125/130, m500/505/515 and i705. (Palm i705 is available only in the USA.) NOTE The configuration software is always the same independently of the interface or Palm handheld model chosen.
The HPC301 setup program, HPC301.EXE, may be obtained from the Internet at http://www.smarresearch.com/hpc301.html or from your local Smar distributor. To Install/Upgrade the HPC301 software: 1. 2. 3. 4. 5. 6. Ensure the cradle is connected to your computer and the Palm Desktop software is installed. Exit all open programs. Start the setup program by double clicking on the HPC301.EXE file. When the HPC301 Installer menu appears, click the Next button to begin the installation procedure and follow the on screen instructions. Start the Hotsync Manager, if not already started. Insert your handheld in its cradle and press the HotSync button. The HPC301 application will automatically be installed into your Palm handheld.
Now you should be able to see the HPC301 icon in the Palm Handheld (Figure 1).
Figure 1
Figure 2 2. Now select the device polling address by choosing an address from 0 to 15. Select a particular device address, a particular device tag, or a range of addresses. NOTE Please refer to the field devices operation manual for connection of the Configurator to the HART Network.
3.
Tap the Poll button and the HPC301 will poll the network for the desired device. After execution of the Poll function, the list of polled devices found on the bus will be available (Figure 3).
Figure 3 4. Select a device from the list by taping on it. The HPC301 will provide acces s to all functions available for this device. For instance, if the selected device is a LD301, the next screen shown would be Figure 4, but if instead the device is a TT301 Figure 5 would be shown.
Figure 4 5.
Figure 5
For further explanation of specific field device procedures, please refer to the instructions provided in the Appendix. If no instructions for the specific device are available, refer to the Generic device section.
State: Fax:
Zip Code:
NOTE Registered users receive technical support, early notification of product upgrades, and new product announcements.
Software updates
Software updates are available at http://www.smarresearch.com/hpc301.html.
A3
A5
A7
A8
A9
A10
Table Points
A11
Totalization Configuration
A12
A13
Equipment Configuration
A15
Equipment Maintenance
A17
A1
Introduction
NOTE: Refer to the LD301's Operation and Maintenance Instruction/Manual for detailed information of the topics described below. By means of the HART Configurator, the LD301 firmware allows the following configuration features to be accessed:
Transmitter Identification and Manufacturing Data. Primary Variable Trim - Pressure. Primary Variable Trim - Current. Transmitter Adjustment to the Working Range. Engineering Unit Selection. Transference Function for Flow rates Measurement. Linearization Table. Totalizer Configuration. PID Controller Configuration. Device Configuration. Equipment Maintenance.
The operations, which take place between the configurator and the transmitter do not interrupt the Pressure measurement, and do not disturb the output signal. The configurator can be connected on the same pair of wires as the 4-20 mA signal, up to 2 km away from the transmitter.
NOTE: All HPC301 button sequences provided in this Appendix assume that you are starting from the main LD301 menu (Figure 1). Refer to Starting the Software section of this manual to get to this position.
Figure 1
A2
Figure 2 To configure the FLANGE TYPE, FLANGE MATERIAL, O-RING MATERIAL and DRAIN/VENT MATERIAL (Figure 3): 1. 2. 3. From the main LD301 menu, click the Maint -> Advanced -> Sensor Info -> Flange Info buttons. Select the desired value(s). Click the Send button.
Figure 3 To configure the REMOTE SEAL TYPE, FLUID, DIAPHRAGM, and QUANTITY (Figure 4): 1. 2. 3. From the main LD301 menu, click the Maint -> Advanced -> Sensor Info ->Remote Seal buttons. Select the desired value(s). Click the Send button.
A3
Figure 4 To read the SENSOR TYPE, RANGE, FLUID and ISOLATING DIAPHRAGM (Figure 5): , 1. From the main LD301 menu, click the Maint -> Advanced -> Sensor Info buttons (Note: These variables are Read Only).
Figure 5
A4
Figure 6 To execute the UPPER TRIM (Figure 7): 1. 2. 3. From the main LD301 menu, click the Trim -> Upper button. Enter the correct reading for the applied pressure. Click the Send button.
Figure 7 To execute the ZERO TRIM (Figure 8): 1. 2. From the main LD301 menu, click the Trim -> Zero button. Click the Send button when the pressure is stabilized.
Figure 8 A5
To execute the CHAR TRIM (Figure 9): 1. 2. 3. 4. 5. 6. From the main LD301 menu, click the Trim -> Char button. Enter the desired value for Point 1 (Type the correct reading for the applied pressure). Click the Send button. Enter the desired value for Point 2 (Type the correct reading for the applied pressure). Click the Send button. You will be prompted for additional points, if more points are desired, repeat steps 2 and 3 (maximum 5 points). You will be prompted to activate the Characterization Trim, click Yes to activate, or No to cancel.
Figure 9
A6
Figure 10
A7
Figure 11 To execute the CALIBRATION WITH REFERENCE (Figure 12): 1. 2. 3. From the main LD301 menu, click the Range button. Click the Lower or Upper button. Click the Send button when the pressure is stabilized.
Figure 12
A8
Figure 13 To configure the USER UNIT (Figure 14): 1. From the main LD301 menu, click the User Unit button.
To configure the 0%, 100%, and/or User Unit: 2. 3. Enter the desired value(s) in the corresponding field(s). Click the Send button. (Note: If the User Unit is on, the changes will take effect right away.)
To Enable/Disable the User Unit: 2. Click the On button to enable, or click the Off button to disable the User Unit.
Figure 14
A9
Figure 15
A10
Table Points
To configure the TABLE POINTS (Figure 16): 1. 2. 3. 4. From the main LD301 menu, click the Conf -> Table button. Select the desired Number of points (minimum 2, maximum 16). Enter the desired X(s) and Y(s) values. Click the Send button.
Figure 16
A11
Totalization Configuration
To configure the TOTALIZATION (Figure 17): 1. From the main LD301 menu, click the Total button.
To configure Max Flow, Factor (Totalization Increment), and Total Unit: 2. 3. Enter the desired value(s) in the corresponding field(s). Note: Totalization should be Off. Click the Send button.
To Enable/Disable the Totalization: 2. Click the On button to enable or click the Off button to disable the Totalization.
To Initialize the Totalization from value "0". 2. Click the Reset tot. button.
Figure 17
A12
To configure the Safety Out, Out Rate_Chng, Low Limit, and High Limit: 2. 3. Enter the desired value(s) in the corresponding field(s). Click the Send button.
To configure the SP Power On: 2. Click the A button to set the SP Power On mode to automatic, click the M button to set it to manual, or click the Last Mode button to set it to the last mode prior to a power failure.
Figure 18 To configure all other PID parameters (Figure 19): 1. From the main LD301 menu, click the PID button.
To Enable/Disable the Controller: 2. Click the On button to enable or click the Off button to disable the Controller.
To configure the TUNING parameters: 2. 3. Enter the desired value(s) in to the Kp, Tr, and/or Td field(s). Click the Send button.
To change the read out of the PV and SP: 2. Check the (E.U.) check box to change the read out to engineering unit or uncheck it to change the read out to percentage.
To Enable/Disable the Setpoint Tracking: 2. Check the SP Track. check box to enable the setpoint tracking or uncheck it to disable the setpoint tracking.
To configure the Control Action: 2. Click the D button to set the Control Action to direct or click the R button to set it to reverse.
A13
To configure the Control Mode : 2. Click the A button to set the Control Mode to automatic or click the M button to set it to manual.
To configure the Manipulated Variable (MV): 2. 3. Enter the desired value in the MV field (Note: The Control Mode must be in manual). Click the Send button.
To configure the Setpoint (SP): 2. 3. Enter the desired value in the SP field (Note: The Setpoint Tracking must be disabled). Click the Send button. Note that when the Setpoint is changed, it is only the current operating Setpoint that is changed. After a power-off it will be lost unless you desire to save the Setpoint in EEPROM. Click the Yes button to save the Setpoint in EEPROM, or click the No otherwise. This is done to reduce the number of times this memory location of the EEPROM is written; the maximum number of changes is somewhere above ten thousand.
4.
Figure 19
A14
Equipment Configuration
To configure the Damping (Input Filter): 1. 2. 3. From the main LD301 menu, click the Range button. Enter the desired value in the Damping field. Click the Send button.
To configure the BURN OUT (Fail Safe): 1. 2. 3. From the main LD301 menu, click the Conf button. Select the desired value. Click the Send button.
To configure the ADDRESSING (Polling Address): 1. 2. 3. From the main LD301 menu, click the Multidrop button. Select the desired value. Click the Change Polling Address button.
To configure the DISPLAY INDICATION (Figure 20): 1. 2. 3. From the main LD301 menu, click the Conf -> LCD button. Select the desired value(s). Click the Send button.
Figure 20 To Enable/Disable the WRITING PROTECTION: 1. 2. From the main LD301 menu, click the Conf button. Click the Enabled button to enable the write protection, or click the Disabled button to disable it.
To configure the Level of password for each menu (Figure 21): 1. 2. 3. From the m LD301 menu, click the Maint -> Passwords button. ain Select the desired value(s). Click the Send button.
A15
Figure 21 To configure the operation passwords (Figure 22): 1. 2. 3. 4. 5. From the main LD301 menu, click the Maint -> Passwords -> Change Passwords button. Select the password level to be changed. Enter the new password in the corresponding field. Click the Send button. Repeat steps 2, 3, and 4 to change other passwords.
Figure 22
A16
Equipment Maintenance
To configure the ORDER CODE: 1. 2. 3. From the main LD301 menu, click the Maint -> Ordering Code button. Enter the desired value in the Ordering Code field. Click the Send button.
To read/configure the SERIAL NUMBER: 1. 2. 3. From the main LD301 menu, click the Info -> Dev. Info button. Enter the desired value in the De vice Ser. # (Transmitter Number) field. Click the Send button.
To view the OP_COUNT: 1. From the main LD301 menu, click the Maint -> Operations Counter button.
To execute the BACKUP: 1. From the main LD301 menu, click the Maint -> Advanced -> Write To Sensor button.
To execute the RESTORE: 2. From the main LD301 menu, click the Maint -> Advanced -> Read From Sensor button.
A17