Beruflich Dokumente
Kultur Dokumente
Section 3
Circuit Breaker Selection
Page INTRODUCTION .............................................................................................. 3-2 CIRCUIT BREAKER RATINGS ........................................................................ 3-2 SELECTION CONSIDERATIONS .................................................................... 3-2 Circuit Voltage .............................................................................................. 3-2 System Frequency ........................................................................................ 3-5 Short-circuit Current ...................................................................................... 3-5 Closing and Latching Current ....................................................................... 3-5 Continuous Current ....................................................................................... 3-5 Rated Interrupting Time ................................................................................ 3-5 SPECIAL SWITCHING APPLICATIONS .......................................................... 3-6 Repetitive Switching ..................................................................................... 3-6 Arc Furnace Switching ................................................................................. 3-6 Reactor Switching ......................................................................................... 3-6 Capacitor Switching ...................................................................................... 3-8 Automatic Transfer ....................................................................................... 3-9 Fast Bus Transfer ....................................................................................... 3-10 SERVICE CONDITIONS ................................................................................. 3-12 Usual Service Conditions ........................................................................... 3-12 Unusual Service Conditions ....................................................................... 3-13 Temperature ..................................................................................... 3-12 High Altitude ..................................................................................... 3-13 BREAKER-MOUNTED ACCESSORIES ........................................................ 3-15 LIFT TRUCK ................................................................................................... 3-15 REFERENCES .............................................................................................. 3-17
Revised 8-2009
3-1
CIRCUIT VOLTAGE The nominal voltage classes of medium-voltage metalclad switchgear based on ANSI standards are 4.16 kV, 7.2 kV and 13.8 kV. Power/Vac switchgear may be applied at operating voltages from 2400 volts through 15,000 volts, provided the maximum circuit operating voltage does not exceed the Power/Vac rated maximum voltage, see Table 3-1.1 or Table 3-1.2 .
3-2
Table 3-1.1 Power/Vac Power Circuit Breaker Characteristics, K = 1.0 Power/Vac PowerPower Circuit Breaker Characteristics GE POWER/VAC Circuit Breaker Characteristics Symetrical Ratings Basis per ANSI C37.06 -- 2000 Symetrical Ratings Basis per ANSI C37.06 2000
AVAILABLE RATINGS Rated Withstand Test Voltage Rated Voltage Range Factor, K Low Frequency rms Voltage (kV) Crest Impulse Voltage (kV) Rated Interrupting Time (Cycles) Rated Permissible Tripping Delay, Y (Seconds) Continuous rms Current Rating at 60Hz (amperes) (2) Rated Short Circuit Current (Maximum Interrupting Capability) (kA) (3) 2 Sec Short time Current Carrying Capability (kA)
Peak Close and Latch (2.6K x short circuit current rating) (kA) 31.5 82
2400 1.0 19 1200-4000 1200-4000 1200-4000 1.0 36 1200-4000 1200-4000 1200-4000 1200-4000 1.0 36 1200-4000 1200-4000 1200-4000 95 1200-4000 31.5 40 50 63 25 20 63 * 50 * 95 40 5 or 3 5 or 3 5 5 or 3 5 or 3 5 or 3 5 or 3 5 or 3 5 2 2 63 * 5 50 5 or 3 60 1200-4000 40 5 or 3 2
1200-4000
31.5
5 or 3
4.76
4.16
4160
40 50 63 40 50 63 20 25 31.5 40 50 63
4200
6600
8.25
7.2
6900
7200
12000
12470
15
13.8
13200
13800
14400
Notes: Notes: 1 Maximum voltage voltage for which the breaker limitdesigned and upper limit of operation. 1 Maximum for which the breaker is designed and upper is of operation. 2 Available current ratings are 1200A, 2000A, 3000A, 3500A and 4000A. 4000A rating is forced-air cooled, indoor construction only. 2 Available current ratings are 1200A, 2000A, 3000A, 3500A and 4000A. 4000A rating is forced-air cooled, indoor constrcution only. 3500A is available in outdoor construction, but must be derated to 3250A. 3 3500A system in outdoor construction, but must be derated to 3250A. At is available operating voltages equal to or less than rated maximum voltage. * AtRatings offered in additionless than rated maximum voltage. values 3 system operating voltages equal to or to the ANSI preferred
Section 3
3-3
4.16 1.19 1.00 1.25 36 1200-4000 1200-4000 36 1200-4000 1200-4000 63 37 95 1200-4000 28 18 11.5 11.5 11.5 15 63 5 8.25 2 95 1.00 1.30 1.30 1.30 1.00 1200-4000 33 6.6 1200-4000 63 4.76 19 1200-4000 41 4.0 60 49 63 41 63 23 36 48 63
250
1.24
1200-4000
29
3-4
Rated Values Insulation Level Current Related Required Capabilities Rated Withstand Test Voltage Rated Maximum rms Voltage Divided by K (kV) K times Related Short circuit rms Current Rated Voltage Range Factor, K (2) (kA) 3.85 36 (kA) 36 49 63 41 63 23 36 48 63 58 78 101 66 101 37 58 77 101 97 132 164 111 164 62 98 130 164 Continuous rms Current Rating at 60Hz (amperes) (7) & (8) Short Circuit rms Current Rating (at Rated Max. kV) (kA) (3) (4) Maximum Symmetrical Interrupting Capability (5) 3 Sec Short time Current Carrying Capability (5) Closing and Latching Capability rms Current (kA) (10) Peak Close and Latch (2.7K x max S/C rating) (kA) (6)
Power/Vac Power Circuit Breaker Characteristics POWER/VAC Power Circuit Breaker Characteristics Symmetrical Ratings Basis ANSI C37.06 (1987)
Identification
Voltage
350
4.76
450 (6)
7.2
500
8.25
785 (6)
500
13.8
750
15
1000
1500 (6)
Notes: Notes: (1) Maximum voltagefor which the breaker breaker anddesigned and the upper limit for operation. (1) Maximum voltage for which the is designed is the upper limit for operation. (2) K is the ratio of themaximum voltage to the lower limit of lower limit of the rangewhich the required symmetrical in which the interrupting symmetrical and maximum voltage to the the range of operating voltage in of operating voltage and asymmetrical required (2) K is the ratio of the asymmetrical interruptingcapabilities vary in inverse proportion to the operating voltage. capabilities vary in inverse proportion to the operating voltage. (3) To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated (3) To obtain the required symmetrical maximum voltage and rated interrupting capability of a circuit breaker at an operating voltage between 1/K times rated maximum voltage and rated maximum voltage, maximum voltage, the following formula shall be used: the following formula shall be used: Required Symmetrical = Rated Short-Circuit Current Current X (Rated Maximum Voltage) Required Symmetrical Interrupting Capability Interrupting Capability = Rated Short-Circuit X (Rated MaximumVoltage) (Operating Voltage) (Operating Voltage) For operating voltages below 1/K times rated maximum voltage, the required symmetrical interrupting capability of the circuit breaker shall be equal to K times of the circuit For operating voltages below 1/K times rated maximum voltage, the required symmetrical interrupting capabilitythe rated short-circuit current. breaker the limitation equal to K times the rated short-circuit current. line-to-line faults. For single phase-to-phase faults, the specific conditions (4) With shall be stated in 5.10 of ANSI-C37.04-1991, all values apply for polyphase and (4) With the limitationofstated in 5.10 apply. of ANSI-C37.04-1991, all values apply for polyphase and line-to-line faults. For single phasestated in 5.10.2.3 ANSI-C37.04-1991 to-phase faults, thespecific conditions stated in 5.10.2.3 of ANSI-C37.04-1991 apply. (5) Current values in this column are not to be exceeded even for operating voltages below 1/K times maximum voltage. (5) Current values in this column are not to be exceeded even for operating voltages below 1/K times maximum voltage. (6) (6) MVA MVA Class listed for reference only. Note 4160V-450MVA, 7.2KV-785MVA and 13.8KV-1500MVA are not listed as preferred ratings according to tablelistedANSI-C37.06-1987. Class listed for reference only. Note 4160V-450MVA, 7.2KV-785MVA and 13.8KV-1500MVA are not 2.1 of as preferred For these ratings to table 2.1 of ANSI-C37.06-1987. For these X S/C rating. ratings accordingthe Short Time current is on a 2 sec basis, and the peak C&L is 2.6ratings the Short Time current is on a 2 sec basis, and the peak C&L AvailableX S/Cratings are 1200A, 2000A, 3000A, 3500A and 4000A. 3500A is indoor construction only. is 2.6 current rating. (7) (7) Available current forced-air cooled,1200A, 2000A, 3000A, 3500A and 4000A. 3500A and 4000A are indoor construction only. ratings are and indoor construction only. (8) 4000A breaker is (8) 4000A breaker is forced-air cooled, and indoor construction only. (9) 3 cycle interruping ratings may be available, consult Factory. (9) 3 cycle interruping ratings may be available, consult Factory. (10) Non-standard, high (10) Non-standard, highClose & Latch ratings may be available, consult available, consult Factory. Close & Latch ratings may be Factory.
Section 3
SYSTEM FREQUENCY The frequency rating of Power/Vac metalclad switchgear should coincide with the nominal frequency of the power system. Standard Power/ Vac is rated at 60-Hz (Tables 3-1.1 and 3-1.2) per ANSI standards, however can typically be applied at 50-Hz as well. Special frequency applications should be referred to the nearest GE Office. SHORT-CIRCUIT CURRENT Quick interruption of short-circuit current is usually considered the primary function of a circuit breaker. The fault-current interrupting capability of Power/Vac circuit breakers is stated in threephase, symmetrical, rms AC amperes. Accordingly, calculation of the maximum available fault duty of a circuit breaker assumes a threephase bolted fault. After calculation of short-circuit current duty, choose a Power/Vac breaker of the proper voltage class and which has a short-circuit current capability that equals or exceeds the expected duty. If applying breakers with K factors > 1.0, remember to consider the circuit operating voltage when evaluating the circuit breakers interrupting capability. For example: a 4.16 kV- 350 MVAclass circuit breaker has a rated short-circuit current of 41 kA at a maximum rated voltage of 4.76 kV, but has a short-circuit capability of 47 kA symmetrical rms current at 4.16 kV. However when applied on a 2.4 kV system, the interrupting capability increases to 49 kA, which is the maximum symmetrical interrupting capability listed in the rating tables, because 2.4 kV is less than 4.76 kV divided by k, or 4.76/1.19 = 4.0 kV. (See footnote No. 5, Table 3-1.2). CLOSING AND LATCHING CURRENT Circuit breakers are designed to stay latched, or to close and latch, against a first-cycle maximum asymmetrical rms current which is approximately 1 1/2 times the maximum symmetrical rms interrupting capability of the circuit breaker. This close and latch capability is satisfactory for most applications (Table 3-1.1 and 3-1.2). However there are some applications in which the calculated rms value of first-cycle asymmetrical short-circuit current, exceeds the closing and latching capability of the otherwise suitable circuit breaker. Applications which include large motor loads may generate these higher firstcycle currents. In these cases, breaker selection may depend on closing and latching capability rather than symmetrical short-circuit capability. The breaker selected may have the next higher short-circuit current capability. For circuit breakers with K factor =1.0, the closing and latching capability (kA, rms) of the circuit breaker is equal to 1.55 K times rated short-circuit current. If close & latch is expressed in peak amperes, the value is equal to 2.6 K times rated short-circuit current. For circuit breakers with K > 1.0, closing and latching capability (kA, rms) of the circuit breaker is equal to 1.6 K times rated short-circuit current and if expressed in peak amperes, the value is equal to 2.7 K times rated short-circuit current (see ANSI C37.06-2000 for details) CONTINUOUS CURRENT Feeder and main breaker loading determines the required continuous current duty. For continuous loads, select a Power/Vac breaker with rated continuous current (defined at 60-Hz) equal to or greater than load current. Note that Power/Vac circuit breakers are 100% rated, and have no continuous overload rating. When considering circuit breaker applications with a generator, a motor, a transformer, or other apparatus having a long-time overload rating, the circuit breaker (and switchgear equipment) must have a continuous-current rating at least equal to the overload rating of the served apparatus. When applied with a forced-air cooled transformer, the switchgear continuous-current rating must equal or exceed the transformer forcedair cooled current rating. Circuit breakers may be operated for short periods, in excess of their rated continuous current. This covers such operations as starting motors or energizing cold loads. Consult ANSI C37.20.2 for overload current capability guidelines. RATED INTERRUPTING TIME Power/Vac circuit breakers are available with interrupting ratings of 5-cycles or 3-cycles, as stated in Tables 3-1.1 and 3-1.2. For additional information contact your GE Sales Engineer.
3-5
Section 3
Table 3-2 Repetitive Duty and Normal Maintenance for Power/Vac Breakers used in Mild Environments other than for Arc Furnace Switching
BREAKER KA Rating CONTINUO US RATING - AMPS COLUMN 1 MAXIMUM NO. OF OPERATIONS BEFORE SERVICING COLUMN 2 A. Servicing consists of adjusting, cleaning, lubrication, changing parts, as recommended by the Company. The operations listed are on the basis of service in a mild environment. NUMBER OF OPERATION S (EACH = 1 CLOSE PLUS 1 OPEN OPERATION) NO-LOAD MECHANICAL CONTINUOUS CURRENT INRUSH-CURRENT SWITCHING SWITCHING COLUMN 3 B. Close and trip, no-load. E. F. Rated control voltage. Frequency of operation not more than 20 in 10 minutes or not more than 30 in 1 hour. COLUMN 4 Close and trip within rated current, rated maximum voltage and 80% PF or greater. Applies Applies COLUMN 5 Closing 600% of rated current or less at no less than 30% PF. Otherwise, same as C. Applies Applies
C.
D.
E. F.
E. F.
G. Servicing at intervals given in Column 2. H. I. No parts replacement. Breaker meets all current, voltage, interrupting current ratings.
G. H. I.
G. H. I.
J.
At the first servicing interval, the amount of vacuum interrupter contact erosion should be used to estimate the additional life at that continued duty. After 15 full short circuit faults check the contact erosion.
J.
Applies
K. Applies
K.
All All
10,000 5,000
10,000 5,000
Table 3-3Repetitive Duty and Maintenance Requirements for Power/Vac Circuit Breakers Applied to Arc Furnace Switching
BREAKER CONTINUOUS RATING (AMPERES) COLUMN 2 NUMBER OF OPERATIONS NO-LOAD MECHANICAL SWITCHING AND INTERRUPTING COLUMN 5 COLUMN 6
TYPE
COLUMN 1
A.
Servicing consists of adjusting, cleaning, lubrication, tightening, changing parts, as recommended by the Company. The operations listed are on the basis of service in a mild environment. If the weighted average of the currents interrupted during load and secondary furnace cave-ins is equal to the breaker continuous current, this column applies. After 15 full short circuit faults check the contact erosion.
B. C. D.
When closing and opening no-load. Within 90 to 100% of rated control voltage.
C. D. E.
Applies Applies
H.
Frequency of operation not more than 20 in 10 minutes or not more than 30 in 1 hour. Servicing at no greater interval than shown in Column 4. No parts replacement. Breaker meets all current, voltage, interrupting current ratings.
F. G. I. J.
E.
Applies At the first servicing interval, the amount of vacuum interrupter contact erosion should be used to estimate the additional life at that continued duty.
F. G.
I.
All All
All All
3-7
CAPACITOR SWITCHING Capacitor banks are generally applied on both utility and industrial power systems to improve voltage regulation and system stability. Power/ Vac circuit breakers properly equipped are applicable as General Purpose circuit breakers for shunt-capacitor-bank switching, or as Definite Purpose Circuit Breakers with back-to-back capacitor switching capabilities as listed in Table 3-4. Shunt-bank capacitor switching means one breaker feeding one 3-phase capacitor bank. If this circuit is closely paralleled by another switched capacitor bank, the duty is considered back-toback. These situations require evaluation of such factors as local high-frequency equalizing currents flowing between the separated, switched capacitor banks.
Isolated-Capacitor Bank or Back-toBack Switching Amps 1200 1200 1200 1200 1200 1200 1200 1200 1850 1200 1850 1200 1200 1850
29 - 50 63 33 - 40 50 - 63 18 & 20 25 - 40 50 - 63
rev 8/2009
rev 8/2009
rev 8/2009
Footnote The capacitor bank rating is subject to the following conditions: 1. The transient voltage from line-to-ground, shall not exceed 3 times the maximum design line-to-ground crest voltage measured at the breaker terminals. 2. The number of re-strikes or re-ignitions shall not be limited as long as the transient voltage to ground does not exceed the value given in footnote 1. 3. Interrupting time shall be in accordance with the rated interrupting time of the circuit breaker. 4. Maximum Capacitor Bank KVAR rating is calculated as follows: System Voltage (kV) x Cap. Switching Current (A) x 1.25 (for ungrounded banks) or 1.35 (for grounded banks) 5. For Back-to-Back switching, the bank inrush currents are limited to 15KA at 2000hz. 6. For capacitor switching requirements other than shown above, consult GE.
3
3-8
Section 3
AUTOMATIC TRANSFER To improve system reliability and ensure supply to critical loads, primary or secondary selective system designs are often utilized. In these configurations, two or more otherwise typical radial buses are connected together via tie breakers. In normal operating mode, each bus is served by its own source through normally closed main breakers, with the bus tie breaker open. If an outage occurs on one of the incoming supplies, the incoming breaker connected to that supply is opened, and then the bus is re-energized by closing the bus tie breaker to transfer the dead bus to the live (alternate) source. To protect against damage to motors connected to the dead bus, the bus tie breaker is typically not allowed to close until the residual voltage on the effected bus has decayed to a safe level. After the lost source has been reestablished, the scheme provides two methods (auto and manual) to restore the system to normal configuration. If the sources cannot be synchronized, the bus tie breaker must be manually opened before the open incomer can be manually closed. In this procedure the incomer will only be allowed to close if the incoming source (line VT) voltage is above a live threshold and the load (bus VT) voltage is below a dead threshold value. If the sources are synchronized, it is possible to manually close the open incomer with synchcheck supervision to parallel all three breakers; the scheme will then automatically open a breaker which had been previously selected to trip if all breakers become closed, in this instance the bus tie breaker. Note that if momentary paralleling is utilized, the equipment and breakers must be rated for the total available fault current from the combined sources. The detection of a undervoltage event and the resulting transfer logic can be accomplished using either discrete protective relays, auxiliary relays and timers, or with a PLC and programming, or by using the various protective relay and logic features contained in todays multifunction relays, such as the GE Multilin SR750. In addition to a protective relay required for each of the three circuit breakers (both mains and the tie), it is required to connect one contact from a three-position switch to each breaker. This switch (device 43/10) is used to select the breaker that will trip after all breakers are closed. It is generally recommended that a twoposition switch (device 43/83) with three contacts, be connected to each relay as an Auto-Off transfer scheme selector. Because a relay is required for each the three circuit breakers, it allows bus-splitting operation. This is accomplished by setting the time overcurrent elements in the relay on the bus tie breaker to trip faster than the incomers, opening the bus tie before an incomer when operating from only one source. FAST BUS TRANSFER Fast bus transfer (FBT) is an option used when there is a need for transferring from a normal power source bus to an emergency or alternate power source upon failure of the normal source of power or vice-versa, as quickly as possible without paralleling, typically within a maximum of 3 cycles (50 milliseconds). It is utilized when serving essential loads such as motors and pump applications. During this transfer, it is essential that bus dead time be as short as possible to prevent loss of downstream critical auxiliary functions, such as contactors and relays. It is important that the main and alternate breakers are not closed at the same time since the sources may not be synchronous or even if they are, some short circuit conditions may result in the loss of both sources, if they are both closed at the same time. Also, when both are closed at the same time, system short circuit currents can exceed the feeder breaker rating.
3-9
Table 3-5Typical Dead-Times for Fast Transfer Using Power/Vac Circuit Breakers Nominal Dead Bus Times (Milliseconds) Trip then close using: Power/Vac Breakers Mechanism Control Voltage (volts) (1) Early b contact & Special closing coil No Arcing (2) 62 N/A With Arcing (3) 50 N/A Standard b contact Special closing coil No Arcing (2) N/A 60 Standard b contact Standard closing coil
ML-17 ML-18
125/250 DC 125/250 DC
Footnotes: (1) Control voltage at rated value. (2) Main contact parting to main contact making. (3) End of arcing to main contact making. Dead bus times noted include allowable + operational tolerances.
3-10
Section 3
Figure 3-1 ML-18/18H Transfer Timing Sequence - 5 Cycle Interrupting - Standard Close Coil
Aux "b" Contact Makes Outgoing Breaker Clears Transfer Initiation Energize Trip Coil of Outgoing Breaker
10
20
30
40
50
60
70
80
90
100
110
Dead Bus Time - No Arching (70ms*) Arching (12ms) (10ms) Dead Bus Time - With Arching (58ms*) Closing Time (60ms*)
*Dead Bus and Closing Times can Vary Based on Allowable Tolerances. Opening - 32-45 ms. Closing 60 +/- 15 ms.
Figure 3-2 ML-18/18H Fast Bus Transfer Timing Sequence - 5 Cycle Interrupting FBT Breaker with Special Close Coil
Aux "b" Contact Makes Outgoing Breaker Clears
Milliseconds
100
10
20
30
40
50
60
70
80
90
Dead Bus Time - No Arching (55ms*) Arching (12ms) (10ms) Dead Bus Time - With Arching (43ms*) Closing Time (45ms*)
*Dead Bus and Closing Times can Vary Based on Allowable Tolerances. Opening: 32-45 ms. Closing: 22-55 ms.
3-11
Milliseconds
3-12
Section 3
High Altitude Medium voltage metal-clad switchgear is designed and tested in conformance to ANSI Standards. Inherent is these standards is the use of air as a heat transfer and dielectric medium. In the application of metalclad switchgear at high altitudes, there are two characteristics which degrade above 1000 meters (3300ft). They are the continuous current rating and the dielectric withstand capability, which may result in excessive corona at operating voltages and an inability to operate due to the dielectric breakdown of the air insulation due to the reduced air density. Power/Vac circuit breakers and switchgear assemblies utilize air for an insulating and cooling medium. Operation at altitudes above 1000 meters (3300 ft) will result in a higher temperature rise and lower dielectric withstand capability because the air is thinner at the higher altitudes. For applications at higher altitudes, the rated 1 minute power-frequency withstand voltage, the impulse withstand voltage, and continuous current rating of the switchgear should be multiplied by the correction factors listed in Table 3-6 to obtain the modified or derated ratings. When the Voltage Correction Factor is applied to the maximum designed voltage rating of 15 kV, 8.25kV or 4.76 kV for metal-clad switchgear, the derating may not permit the equipment to be installed at altitudes above 1000 meters, at their respective typical nominal system voltages. Since it is more realistic to apply these correction factors to the BIL rating (impulse withstand voltage) of the switchgear, an industry accepted option is to apply the equipment at their rated nominal voltages, with no change in clearances, by the addition of lighting arresters to protect the equipment. The recommended practice is to apply the Voltage Correction Factor to the rated BIL level of the equipment, and provide surge protection on the load side of the switchgear using station type lightning arresters (Tranquell arresters), selected such that the maximum discharge voltage of the arrester is about 20% less than the modified impulse voltage rating of the switchgear. (See ANSI C37.010-1999, 4.2.2) The Current Correction Factor is applied to the continuous current rating of the equipment only. It is necessary to derate the continuous current rating, because switchgear assemblies depend on the air for cooling and will have a higher temperature rise when operated at altitudes above 1000 meters. The short-time and interrupting current ratings on vacuum breakers are not affected by altitude. Since the Current Correction Factor is small and the actual continuous current duty is usually less than the equipment rating, current correction is typically not as serious a consideration as the voltage correction. An additional consideration is that often at higher altitude, the ambient is reduced, which can offset the higher altitude continuous current derating effect. NOTE: The recommendations are subject to modification depending on the actual system conditions.
3-13
Application of metal-clad switchgear above 1000 meters (3300 ft) should be referred to GE. It should be cautioned that the correction factors of power transformers are different than those for switchgear. Besides abnormal temperature and high altitude there are other unusual service conditions, which may require special protecting features or affect construction. Some of these are: Exposure to corrosive atmosphere, explosive fumes, excessive dust (e.g., coal dust, paper fibers) or particulate contamination, salt spray, steam, dripping water, and other similar conditions. Exposure to abnormal vibration, shock, unusual transportation, or special storage conditions. Installations accessible to the general public. Special duty/operating requirements of equipment.
BREAKER MOUNTED ACCESSORIES Each Power/Vac breaker has two a and three b breaker auxiliary contacts wired from the breaker-mounted auxiliary switch for the Purchasers use. Additional breaker contacts from optional compartment mounted switches are available, see Section 7. A redundant tripping circuit on Power/Vac circuit breakers can also be furnished via an optional second or dual trip coil. This option was 3-14 designed specifically for use on utility breakers and on breakers applied in power-station switchgear applications. This feature is seldom used in industrial or commercial applications since the standard Power/Vac trip circuit is extremely reliable. Power/Vac circuit breakers can be provided with an optional direct-acting undervoltage trip device. The undervoltage trip device is a factory
Section 3
installed unit, which is an integral part of the breaker mechanism. Its function is to monitor the trip circuit control voltage and to mechanically trip the breaker if that control power drops below a preset value. (See page 4-5.) Refer to Instruction Book GEK-105393 for additional details. Note that the options for a dual trip coil and the undervoltage trip device are mutually exclusive. Both cannot be utilized on the same breaker. Standard Power/Vac design uses a lift truck, for lifting and inserting/removing the circuit breakers from the breaker cells. For designs using only 1high breaker arrangements, with the breakers located in the bottom compartments, GE offers an option for roll-in breakers. Roll-in breakers have a wheeled undercarriage bolted to the bottom of the breaker frame, which raises the breaker to the proper height to interface with the breaker cell connections. The breaker cell floor frame is modified to allow the breaker to roll directly from the finished floor into the cell, without the need for the lift truck described in the following section. Note roll-in breakers cannot be inserted into a standard breaker cell without removing the bolton undercarriage, and using the lift truck. BREAKER LIFT TRUCKS GE offers two basic styles of lift trucks for handling Power/Vac circuit breakers, ground and test devices, roll-out transformer trays and fuse roll-outs. The first is a double masted truck that is available with two swivel casters in the rear and two straight wheels in the front. This truck is compatible with indoor switchgear and provided as a standard with every order. However, to reach the top rollout drawer in an upper compartment, a different single masted truck is required. The dimensions of the double masted truck carriage are width of 47 inches and a total width of 50 inches with the winch handle installed. The depth with arms extended is 46 inches, and the standing height is 86 inches. This style of truck cannot be used with outdoor aisle-less switchgear. See Figure 3-3. The second style is a single-masted truck that is available with all swivel casters. As shown in Figure 3-4. This truck is compatible with outdoor switchgear and is required to reach the upper compartment rollout on indoor equipment. The maximum handle load is 15 lb. with a 850 lb. load. The typical dimensions of the single masted truck are width 36.5 inches, depth is 47 inches (with arms extended 55.5 inches), and the standing height is 79.5 inches extendible to 137.5 inches. The legs at the base of the lift truck are adjustable in width from 31.5 inches to 58 inches. This allows the legs to be narrowed to the width of the breaker for moving through doorways. Caution; while lowering the breaker from the cubicle to the floor the width of the legs must maintain a minimum width of 44 inches. The single-mast lift truck can be collapsed for storage. The width is 39 inches with arms and legs collapsed, the depth is 29 inches and the height is 77 inches.
Figure 3-3
3-15
REFERENCES 1. ANSI Standard C37.06-2000, Schedules of Preferred Ratings and Related Required Capabilities for AC High Voltage Circuit Breakers Rated on a Symmetrical CurrentBasis. 2. ANSI Standard C37.010-1999, Application Guide for AC High Voltage Circuit Breakers. 3. ANSI Standard C37.04-1999, Circuit Breaker Rating Structure. 4. ANSI Standard C37.20.2-1999, Metalclad Switchgear Assemblies. 5. ANSI Standard C37.24-1986, Guide for Evaluating the Effect of Solar Radiation on Outdoor Metalclad Switchgear. 6. ANSI Standard C37.100-1992 Definitions for Power Switchgear. 7. Power/Vac Manual Ground and Test Device Instruction Book, GEK-39686. 8. Power/Vac Electrical Ground and Test Device Instruction Book, GEK-39684. 9. Power/Vac Circuit Breakers using ML-17 Mechanism, GEK-39671. 10. Power/Vac Circuit Breakers using ML-18/ 18HMechanism, GEK-86132. 11. Power/Vac Breaker Lift Truck, GEK-90214
Figure 3-4
3-16