Beruflich Dokumente
Kultur Dokumente
ENGLISH
2-0
Lexium 05 A
2.1
Overview
The simplified manual only contains selected information. The complete manual is on the included CD or at http://www.telemecanique.com
2.2 Steps 2.3 Mechanical installation 2.4 Electrical installation 2.6 Operation with installed HMI 2.7 "first setup" (FSU) via HMI 2.8 Jog 2.9 Duplicate existing device settings 2.10 Error numbers 2.11 Technical Data 2.11 Technical Data
Page2-2 Page2-3 Page2-4 Page2-16 Page2-18 Page2-19 Page2-20 Page2-20 Page2-26 Page2-26
@ WARNING
Injury from unexpected movements Drives may execute unexpected movements because of incorrect wiring, incorrect settings, incorrect data or other errors. Malfunctions (EMC) may cause unpredictable responses in the system.
00198441113252, V0.16, 08.2005
Install the wiring carefully in accordance with the EMC requirements. Disable the inputs PWRR_A and PWRR_B (status 0) to prevent unexpected movements before switching on and configuring the drive system. Do not operate a drive system with unknown settings or data. Carry out a comprehensive commissioning test.
Lexium 05 A
2-1
ENGLISH
2.1 Overview
Page2-1
2.2
Steps
1 Receive product
Open the packaging and check the device for transport damage Check that the information on the nameplate matches that on the order form
ENGLISH
Make sure that the mains voltage matches the permissible voltage range of the device
3 Install product
Check that the specified installation clearances correspond to the operating conditions Fasten the device in place in accordance with the EMC specifications and the recommendations included in this document
5 Basic settings
"First Setup" (FSU menu)
6 Start
Conduct jog to check the drive function
2-2
Lexium 05 A
2.3
Mechanical installation
$ DANGER
Electric shock from foreign bodies or damage. Conductive foreign bodies in the product or serious damage can cause accidental energisation. Do not use damaged products. Prevent foreign bodies such as chips, screws or wire clippings from entering the product. Do not use products that contain foreign bodies.
Failure to follow these instructions will result in death or serious injury. Installation spacing;ventilation When selecting the position of the device in the switching cabinet, note the following instructions:
d d
Adequate cooling of the device must be ensured by complying with the minimum installation distances. Prevent heat accumulation. The device must not be installed close to heat sources or mounted on flammable materials. The warm airflow from other devices and components must not heat the air used for cooling the device.
Measures with protective foil in place None d > 10 mm (d > 0.39 in.) Reduce nominal current and continuous current 3) Operation not possible
Distance 1)
d > 50mm None (d > 1.97 in.) d < 50mm None (d < 1.97 in.)
d > 50mm None (d > 1.97 in.) d < 50mm Reduce nominal current and continuous (d < 1.97 in.) current 3)
1) Distance in front of the device: 10mm (0.39 in.), above: 50mm (1.97 in.), below: 200 mm (7.87 in.) 2) Recommendation: remove protective foil on completion of the installation 3) by 2.2% per C above 40C (by 1.22% per F above 104 F)
Installing the device Painted surfaces have an insulating effect. Remove the paint from the attachment points over a wide area (bright metal) before attaching the device to a painted mounting plate.
Lexium 05 A
2-3
ENGLISH
Note the layout of the components, see also 2.5 Electromagnetic compatibility, EMC Install the device in a vertical position (10). This is particularly important for cooling the device. Attach the EMC plate included with the device at the bottom of the device, or use alternative base elements (comb bars, shield clamps, busbars). Attach plate with safety instructions Attach the plate with safety instructions included with the device in a visible position on the front panel as specified by the national regulations.
Remove the protective foil only after completion of all installation work. The protective foil must be removed if required by the thermal conditions.
ENGLISH
2.4
Electrical installation
@ WARNING
Danger of injury by loss of control! Observe the accident prevention regulations. (For USA see also NEMA ICS1.1 and NEMA ICS7.1) The system manufacturer must take the potential error possibilities of the signals and the critical functions into account to ensure a safe state during and after errors. Some examples are: emergency stop, final position limitation, power failure and restart. The assessment of error possibilities must also include unexpected delays and the failure of signals or functions. Suitable redundant control paths must be in place for dangerous functions. Check that measures taken are effective.
2-4
Lexium 05 A
T1
T2
R/L1 S/L2 T/L3 PA/+ PBi PBe PC/- U/T1 V/T2 W/T3
T3
Prepared motor cable [mm] ([in.]) Dimension A (T1) (T1) (T2) (T4) (T3) (T4) (T4) (T4) (T3) (T4) (T4) (T4) (T5) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) 130 (5.12) Dimension B 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) 120 (4.72) Dimension C 75 (2.95) 75 (2.95) 75 (2.95) 85 (3.35) 85 (3.35) 85 (3.35) 85 (3.35) 90 (3.54) 90 (3.54) 90 (3.54) 90 (3.54) 90 (3.54) 90 (3.54)
T4
R/L1 S/L2 T/L3 PA/+ PBi PBe PC/- U/T1 V/T2 W/T3
T5
2
BK L1 BK L2 BK L3 GN/YE WH GR
LXM05 D57N4
L3
3a
GN/YE WH GR
L1
L2
Preparing the motor cable (1) Strip the motor cable to length A, see table.
B A C
BK BK L
(2) Slide the shield braiding back over the cable sheath. During mounting it must be spread over the EMC plate. (3) Shortening cables: motor cables (BK) to length C, protective conductor remains length A. (3a) For motors with holding brake: brakes cables to length B (3b) Without holding brake: insulate brake cables individually. Use fork-type cable lugs or wire end ferrules. The braided wire must fill the ferrule over its complete length.
2 L3
3b
GN/YE
L1
WH GR
Lexium 05 A
BK
2-5
ENGLISH
2.4.1
$ DANGER
Electric shock High voltages can occur unexpectedly at the motor connection. The motor generates voltage when the shaft is rotated. Lock the shaft of the motor to prevent rotation before starting work on the drive system. AC voltages may jump over unused wires in the motor cable. Isolate unused wires at both ends of the motor cable. The system manufacturer is responsible for compliance with all applicable regulations relevant to earthing the drive system. Extend the earth through the motor cable with an additional earth at the motor housing.
ENGLISH
Wiring diagram for motor cable and holding brake controller HBC
Description Colour
LXM05
R/ U/ L1 T V/T 1 2 S/L W/ 2 T3 T/L 3 CN 3 CN .44 3.4 2 CN 1.3 2
HBC: 32 1) HBC: 34
34 32 11 / 12 21 /2 14 2 / 13 24 /2 3
Connecting external braking resistor 2): Remove jumper between PA/+ and PBi. If this is not done the internal braking resistor may be destroyed during operation. Connect external braking resistor to PA/+ and PBe
M
3~
HBC
1) If the holding brake option is used 2) If the external braking resistor option is used; for dimensioning see product manual
2-6
Lexium 05 A
2.4.2
Mains connection
$ DANGER
Electric shock because of insufficient earthing This drive system has an increased leakage current > 3.5mA. Use a protective conductor at least 10 mm (AWG 6) or two protective conductors with the same cross section as the power supply conductors. Observe the local regulations for earthing.
@ WARNING
This product can cause a direct current in the protective earth conductor! If a residual current device (FI protection switch, RCD) is used then peripheral conditions are to be observed. Failure to follow these instructions can result in death or serious injury.
@ WARNING
Inadequate overcurrent protection Use the external fuses specified in the "Technical Data" chapter. Do not connect the product to mains if the short-circuit capacity exceeds the maximum short-circuit current specified in the "Technical Data" chapter.
Failure to follow these instructions can result in death, serious injury or equipment damage.
00198441113252, V0.16, 08.2005
CAUTION
Destruction by incorrect mains voltage! The incorrect mains voltage may destroy the product. Before switching on and configuring the product, make sure that the type is approved for the mains voltage.
Failure to follow these instructions can result in equipment damage. Lexium 05 A 2-7
ENGLISH
3-phase devices must only be connected and operated on 3-phase. For devices with external mains filter the power cable must be shielded from 200 mm length between the external mains filter and the device and earthed at both ends. Observe the requirements for UL and EMC. The cable cross section must be sufficient to trip the fuse in the event of a short circuit. See also page 2-26.
ENGLISH
Information about the use of residual-current-operated protective devices can be found in the product manual.
2.4.3
Operation in an IT mains
An IT mains is characterised by a neutral conductor that is insulated or earthed through a high impedance. The Y-capacitors can be disabled if required on devices with integrated mains filter. Use a permanent insulation monitor compatible with non-linear loads: a Merlin Gerin type XM200 or equivalent.
1a
2a
1b
PE
2b
(1a): Y-capacitors of the internal filter effective (standard) (1b): Y-capacitors of the internal filter disabled (IT mains)
(2a): Y-capacitors of the internal filter effective (standard) (2b): Y-capacitors of the internal filter disabled (IT mains)
2-8
Lexium 05 A
2.4.4
CN1
CN 3 CN 2
S1 OFF
41 42 43 44
24V controller supply voltage PC, decentralised control terminal, Modbus, CANopen (fieldbus: see product manual) ESIM (A/B/I out), PULSE/DIR in, A/B/I encoder signals in 2) Switch for fieldbus terminating resistor
CN 4 CN 5
S1
1) max. 0.75mm cable cross section, max. 2A terminal current 2) depending on first setup FSU
2.4.5
2.4.6
$ DANGER
Electric shock from incorrect power supply.
00198441113252, V0.16, 08.2005
The +24VDC supply voltage is connected with many exposed signals in the drive system. Use a power supply that meets the requirements for PELV (Protective Extra Low Voltage) Connect the negative output of the power supply to PE.
Lexium 05 A
2-9
ENGLISH
CN2
@ CAUTION
Destruction of unit components and loss of control! Excessive currents can be created at the signal connections if the negative connection to the controller supply voltage is interrupted. Do not interrupt the negative connection between power supply unit and load with a fuse or switch Check for correct connection before switching on. Never connect the controller supply voltage or change its wiring while there is supply voltage present.
ENGLISH
Description Reference potential for 24V voltage Reference potential for 24V voltage 24V controller supply voltage 24V controller supply voltage
I/O I O I O
42 43 44
HBC
24V = 0V
+24V
2-10
Lexium 05 A
2.4.7
A
10 9 8 7 6
1 6 2 7 3 8 4 9
5 4 3 2 1
CN5
A
Figure 2.1 Wiring diagram CN5
Meaning of A/B/I PULSE signal Meaning of PULSE Encoder signal channel A PULSE Motor step "Pulse" Motor step "Pulse", inverted direction of rotation "DIR"
Meaning of ESIM Channel A Channel A, inverted Channel B Channel B, inverted Index pulse index pulse, negated
1 6 2 7 3 8
00198441113252, V0.16, 08.2005
Channel B, inver- DIR ted Channel index pulse Channel index pulse, inverted ENABLE ENABLE
direction of rota- ESIM_B tion "Dir", inverted Enable signal Enable signal, inverted ESIM_I ESIM_I
4 9 5 10
not assigned
Lexium 05 A
2-11
ENGLISH
SHLD 5
2.4.8
ENGLISH
CN1
11 12 13 14 21 22 23 31 32 33 34 35 36 37 38 39
Pin 11 12 13 14
Description Analogue input signal, 10V, e.g. for current or setpoint speed value Reference potential forANA1+, pin 11 Analogue input signal, 10V, e.g. for current or speed limiting Reference potential for ANA2+, pin 13
31 32
Output for error detection 0: motor without current, 1: motor with current, e.g. HBC control signal, max. 400mA
33 34 35 36 37 38
not assigned in local control mode Fault reset Enable power amplifier STOP function, interruption of movement / continue without error Safety function channel A Safety function channel B
I digital 24V I digital 24V 1) I digital 24V 1) I digital 24V 1) I digital 24V
00198441113252, V0.16, 08.2005
I digital 24V
1) Signal logic (logic level) can be specified with first setup, see Seite 13
39
24VDC
O 24V
2-12
Lexium 05 A
2.4.9
Logictype
This product can switch the 24V inputs and outputs as follows (DRC- / iolt). Exception: the safety signals PWRR_A and PWRR_B are always logic type "Source".
Logic type "Source" "Sink" active status output sends current current flows to the input
@ WARNING
Unintended equipment operation Use of the logic type setting "Sink" allows the earth fault of a signal to be recognised as an On condition. Take extra care with the wiring to exclude any possibility of an earth fault.
Failure to follow these instructions can result in death, serious injury or equipment damage. Logictype "Source"
CN1
11 12 13 14 33 34 35 36 31 32 41 42 43 44
PE
24V=
10V
Logictype "Sink"
00198441113252, V0.16, 08.2005
CN1
11 12 13 14 33 34 35 36 31 32 41 42 43 44
PE
24V=
10V
Lexium 05 A
2-13
ENGLISH
ENGLISH
1) if the signal is not required, the input must be wired corresponding to the logic level 2) if the safety function is not required, these inputs must be wired with +24V
@ WARNING
Loss of the safety function Incorrect usage may cause a safety hazard by loss of the safety function. Observe the requirements for the safety function.
Failure to follow these instructions can result in death or serious injury. For more information see the product manual.
PC connection
VW3A31101
ESC ENT
stop reset FWO REV
RUN
CN4
2-14
Lexium 05 A
2.5
@ WARNING
In a domestic environment, this product may cause radio interference, in which case supplementary mitigation measures may be required.
Control cabinet
Mains filter (optional)
System earth
Machine bed
M~
Encoder cable
Field bus
Position
Lexium 05 A
2-15
ENGLISH
2.6
@ WARNING
Unexpected motion may cause injury and damage to the system When the drive is operated for the first time there is a high risk of unexpected motion because of possible wiring faults or unsuitable parameters. If possible, run the first test movement without coupled loads. Make sure that a functioning button for EMERGENCY STOP is within reach. Also anticipate a movement in the incorrect direction or oscillation of the drive. Make sure that the system is free and ready for the motion before starting the function.
ENGLISH
Failure to follow these instructions can result in death, serious injury or equipment damage.
(1) Red LED on: voltage applied at DC bus Status display LEDs for fieldbus
ENT
(2) (3)
RUN
8.8.8.8
BUS ERR
ESC
Leaving a menu or parameter Return from displayed to last saved value Calling a menu or parameter Store the displayed value in the EEPROM Switch to previous menu or parameter Increase the displayed value Switch to next menu or parameter Reduce the displayed value
00198441113252, V0.16, 08.2005
ESC
ENT
2-16
Lexium 05 A
2.6.1
ENT
FSUSave
ENT
First Setup
ESC
rdy
ENT
ENT ESC
SEtENT ESC
Settings
ESC
drCESC
Drive Configuration
ESC ENT
tUnENT ESC
Autotuning
ESC
JoGMenus
ESC
JOG Mode
ESC ENT
(OmENT ESC
Communication
ESC
Fault
InFENT ESC
Information / Identification
ESC
STAESC
Status Information
Menu
Value
The adjacent figure shows an example for calling a parameter (second level) and the input or selection of a parameter value (third level).
ESC
SetESC
IMAX
ESC
8.49 8.48
ENT
NMAX
(next parameter)
Store (flashing)
8.48
ESC
When you press ENT, the selected value is accepted. Confirmation is indicated by the display flashing once. The modified value is saved in the EEPROM immediately.
Lexium 05 A
2-17
ENGLISH
2.7
FSU-
ENGLISH
ENT
DevC
ESC
CURR sped
IO-M
ESC
gear
ENT
ENT
IOLt
ESC
PoS NEG
Save settings.
SAVE Save settings in device.
SaVe
ENT
The device saves all set values in the EEPROM and displays the status nRDY, RDY or DIs on the HMI. Switch controller power supply off and on again. Restore factory setting with HMI Proceed as follows to restore the factory settings: Set DRC and then FCS on the HMI and confirm your selection with yes. All parameter values are reset to the default values. The new settings only become effective after switching off and switching on the device again.
00198441113252, V0.16, 08.2005
2-18
Lexium 05 A
2.8
Jog
For a simple initial commissioning the motor should not be connected to the system. If the motor is connected to the system, all limiting parameters must be checked and an EMERGENCY STOP button must be within reach before the first motor movement, see product manual. If the inertia ratio of Jext/Jmotor > 10 (external load on motor), the initial setting of the controller parameter may result in an unstable controller Start the jog operating mode. (HMI: Jog_ / Strt) HMI display: JG
ENT ENT
JoG
ESC
Strt ...
JG
Start a movement in clockwise rotation (1) (HMI: "Up arrow") The motor rotates in clockwise rotation. HMI display JGStart a movement in anti-clockwise rotation (2) (HMI: "down arrow")
1
ENT
2
ENT
+ fast
JG-
slow
-JG
+ fast
You can change from slow to fast movement by simultaneously pushing the ENT-button.
Is the device in status rdy? For more information see the product manual. Is the controller power supply switched on? Is the power amplifier supply voltage switched on? Has "first setup" been conducted or have device settings been imported? Was the controller power supply switched off and on after that? Is the safety function correctly wired? Was the safety function triggered? Have the limit switches been correctly wired for fieldbus control mode or is a limit switch actuated?
00198441113252, V0.16, 08.2005
Lexium 05 A
2-19
ENGLISH
2.9
Device type, motor type and device firmware must be identical. The tool is the Windows-based commissioning software PowerSuite. The controller power supply must be switched on at the device. The commissioning software installed on a PC can apply the settings of a device as configuration. Load the configuration if the device into the commissioning software with "Action Transfers". Highlight the configuration and select "File - Export".
ENGLISH
A stored configuration can be imported into a device of the same type. In the commissioning software select the menu item "File - Import" and load the desired configuration. Highlight the configuration and select "Action - Configure".
2.10
Error numbers
Errors are shown on the display of the HMI (without "I"). In the "local" control mode an error can be acknowledged with Fault_Reset.
Error number E 1xxx E 2xxx E 3xxx E 4xxx E 5xxx E 6xxx E 7xxx E 8xxx E Axxx E Bxxx Error in area General error Excess current error Voltage error Temperature error Hardware error Software error Interface error, wiring error Fieldbus error CANopen Drive error, movement error Communication error
00198441113252, V0.16, 08.2005
For detailed information on error classes and error bits see the product manual. Class par. = configurable
2-20
Lexium 05 A
Error number E 1100 E 1101 E 1102 E 1103 E 1104 E 1106 E 1107 E 1108 E 1109 E 110A E 110B E 1300 E 1301 E 1310 E 1603 E 1606 E 1607 E 1608 E 1609 E 160A E 160B E 160C E 160D E 160E E 160F E 1610 E 1611
00198441113252, V0.16, 08.2005
Class 0 0 0 0 0 0 0 0 1 0 3 3 4 3 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 1 1 1
Bit 0 0 0 0 0 0 0 0 0 0 30 4 24 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Description Parameter out of the setting range Parameter does not exist Parameter does not exist Parameter write not permissible (READ only) Write access denied (no access authorisations) Command not allowed when the power amplifier is activ
Parameter not readable (Block transfer in progress) Data stored after power failure are not consistent System error: boot loader not present Initialisation error (at the indicated modbus address) Power Removal activated (PWRR_A, PWRR_B) PWRR_A and PWRR_B different level Reference signal frequency too high Recording memory blocked by another function Recording still active Recording: no trigger defined Recording: trigger option not permissible Recording: no channel defined Recording: no data present Parameter not recordable Auto-tuning: moment of inertia out of permissible range Auto-tuning: The value of the parameter 'AT_n_tolerance' is probably too small for the identified mechanical system Auto-tuning: error when starting traverse attempt Power amplifier can not be enabled Auto-tuning: process stopped System error: Auto-tuning internal write System error: Auto-tuning internal read Auto-tuning: max. permissible positioning range exceeded Auto-tuning: already active Auto-tuning: This parameter cannot be changed as long as Auto-tuning is in progress Auto-tuning: Static friction for chosen speed jump magnitude 'AT_n_ref' too big Auto-tuning: friction or torque too high Auto-tuning: Optimization failed
Lexium 05 A
2-21
ENGLISH
Class 0 0 3 3 4 3 3 4 3 3 3 par. 3 3 2 4 0 3 0 0 3 3 0 0 0 4 4 4 4 3 4 4 3 4
Bit 0 0 19 19 31 30 30 30 30 18 18 16 15 14 14 19 11 21 1 4 21 21 2 5 6 19 19 19 19 19 19 29 29 29
Description Auto-tuning: Speed jump magnitude 'AT_n_ref' is too small compared to 'AT_n_tolerance' System error: FIFO memory overrun Motor has been replaced Motor has been replaced System error: Faulty parameter for the motor or the power amplifier User parameter max. speed too big User parameter max. current, holding current or Quick Stop current too big Encoder is not supported by current operating system ESIM resolution too high with selected n_max Overcurrent power amplifier Overcurrent in the braking resistor Mains phase loss Overvoltage DC bus Undervoltage DC bus (Switchoff threshold) Undervoltage DC bus (Quick Stop threshold) Supply voltage motor encoder Undervoltage DC bus, mains phase loss (warning) Power amplifier overtemperature Warning power amplifier overtemperature Warning power amplifier overload (It) Drive overtemperature Motor overtemperature Warning motor overtemperature Warning motor overload (It) Warning braking resistor overload (It) Motor encoder communication error Errors in communication motor encoder Motor encoder is not supported Motor encoder communication error Encoder communication lost Connected motor not supported (motor family) System error: EEPROM read error System error: EEPROM write error System error: EEPROM not formated
00198441113252, V0.16, 08.2005
ENGLISH
E 1B01 E 1B02 E 1B03 E 1B04 E 2300 E 2301 E 3100 E 3200 E 3201 E 3202 E 3203 E 3206 E 4100 E 4101 E 4102 E 4200 E 4300 E 4301 E 4302 E 4402 E 5200 E 5201 E 5202 E 5203 E 5204 E 5205 E 5430 E 5431 E 5435
2-22
Lexium 05 A
Error number E 5437 E 5438 E 5439 E 543A E 543B E 543C E 543D E 543E E 5600 E 5601 E 5602 E 5603 E 6107 E 6108 E 610D E 610F E 7120 E 7121 E 7122 E 7123 E 7124 E 7126 E 7200 E 7201 E 7327 E 7328 E 7329 E 7330
00198441113252, V0.16, 08.2005
Class 4 3 3 4 4 3 3 3 3 4 4 4 0 0 0 4 4 2 4 4 4 0 4 4 4 4 0 4 4 4 0 0 3 1 0
Bit 29 29 29 29 29 29 29 29 17 19 19 17 0 0 0 30 19 19 30 30 19 19 30 30 19 19 8 19 30 30 0 8 0 8 13
Description System error: EEPROM checksum manufacturer data System error: EEPROM checksum user parameter System error: EEPROM checksum CAN parameter System error: EEPROM Hardware information invalid System error: EEPROM manufacturer data invalid System error: EEPROM CAN data invalid
System error: EEPROM checksum error NoInit parameter Motor Phase connection fault Interruption or faulty encoder signals Interruption or faulty encoder signals Commutation error Parameter out of range (calculation error) Function not available Error in selection parameter System error: internal time base unusual (Timer0) Invalid motor data System error: faulty communication encoder Motor data not acceptable System error: motor current offset out of permissible range System error: encoder is faulty No answer has been received yet System error: calibration analogue/digital converter System error: motor encoder initialising (quadrant evaluation) System error: position sensor not ready Encoder reports: position capture errors Encoder reports: warning System error: motor encoder (Hiperface) System error: motor encoder initialising System error: Deviation at calibration analogue/digital transducer System error: Analogue/digital transducer offset too big Motor encoder not ready Offset of SinCos drift compensation too big Offset could not be successfully written No valid motor absolute position
Lexium 05 A
2-23
ENGLISH
Class 0 0 0 0 0 0 0 2 0 2 0 0 0 0 0 0 2 2 0 0 1 1 1 0 1 0 0 0 0 0 0 0 0 0 0
Bit 31 9 9 9 9 7 7 7 0 7 7 7 7 7 7 7 10 10 0 0 1 1 1 0 3 0 0 0 0 0 0 0 0 0 0
Description System error: illegal interrupt (XINT2) RS485/Modbus: overrun error RS485/Modbus: framing error RS485/Modbus: parity error RS485/Modbus: receive error CANopen: CAN overrun (message lost) CANopen: CAN controller in error passive CANopen: heartbeat or life guard error CANopen: CAN controller was in busoff, communication possible again CANopen: CAN controller in bus off CANopen: RxPDO1 could not be processed CANopen: RxPDO2 could not be processed CANopen: RxPDO3 could not be processed CANopen: RxPDO4 could not be processed CANopen: TxPDO could not be processed CANopen: overrun in internal queue message lost Calculation fault with electronic gear Reference signal change with electronic gear is too great Torque ramp with STOP current active Drive in state 'QuickStopActive' Interruption by LIMP Interruption by LIMN Interruption by REF Power amplifier cannot be activated in current operating status of status machine Interruption by user software stop Interruption by internal software stop Drive in state 'Fault' Drive not in state 'OperationEnable' Power amplifier not active Profile generation interrupted Position overflow (pos_over=1), reference point not defined by it any more (ref_ok=0) No reference position Homing active Overrun on acceleration calculation Drive not at standstill
00198441113252, V0.16, 08.2005
ENGLISH
E 8120 E 8130 E 8140 E 8141 E 8201 E 8202 E 8203 E 8204 E 8205 E 8206 E A060 E A061 E A300 E A301 E A302 E A303 E A304 E A305 E A306 E A307 E A308 E A309 E A310 E A312 E A313 E A314 E A315 E A316 E A317
2-24
Lexium 05 A
Error number E A318 E A319 E A31A E A31B E A31C E A31D E A31E E A31F E A320 E A321 E A324 E A325 E A326 E A327 E A328 E A329 E A32A E A32B E A32C E A32D E A32E E A32F E A330 E A331 E A332 E A334
00198441113252, V0.16, 08.2005
Class 0 1 0 0 0 0 1 1 par. 0 1 1 1 1 1 1 1 1 1 1 1 1 0 3 1 2 1 0 0 0 2 0 0 0
Bit 0 2 0 0 0 0 2 2 22 0 10 10 10 10 10 10 10 10 10 10 10 10 0 0 10 0 10 10 9 9 6 9 9 9
Description Operating mode active (x_end = 0) Manual-/ Auto-tuning: distance range overflow Manual-/Auto-tuning: amplitude/offset set too high STOP requested Illegal position setting at software limit switch Speed range overflow (CTRL_n_max)
Interruption by neg. software limit switch Tracking error RS422 position interface not defined as input signal Homing error (additional information = detailed fault number) Limit switch not enabled REF switch not found between LIMP and LIMN Reference movement to REF without direction reversal, improper activation of LIM limit switch Reference movement to REF without direction reversal, overrun of LIM or REF not permissible More than one LIMP/LIMN/REF signal active Ext. monitoring signal LIMP with neg. direction of rotation Ext. monitoring signal LIMN with pos. direction of rotation Error at REF (switch signal briefly activated or switch overshoot) Error at LIMP (switch signal briefly activated or switch overshoot) Error at LIMN (switch signal briefly activated or switch overshoot) Index pulse not found Reproducibility of index pulse motion uncertain, index pulse too close to switch Start-up operating mode at local control mode not selected Jog error (additional information = detailed fault number) Timeout in standstill window monitor Process only possible in fieldbus mode Operating mode cannot be continued RS485/Modbus: unknown service RS485/Modbus: protocol error RS485/Modbus: nodeguarding error RS485/Modbus: nodeguarding warning RS485/Modbus: number of monitor objects incorrect RS485/Modbus: service too long
Lexium 05 A
2-25
ENGLISH
2.11
LXM05 ...
Technical Data
D10F1 [V] 115 (1~) D17F1 115 (1~) 11 0.65 1 76 8 11.31 12 16.97 7 9.90 11 15.56 15/16 D28F1 115 (1~) 21.6 0.85 1 150 15 21.21 20 28.28 13 18.38 20 28.28 25 D10M2 230 (1~) 7 0.75 1 48 4 5.66 7 9.90 3.2 4.53 6 8.49 10 D17M2 230 (1~) 11 1.2 1 74 8 11.31 12 16.97 7 9.90 11 15.56 15/16 D28M2 230 (1~) 20 2.5 1 142 15 21.21 20 28.28 13 18.38 20 28.28 25
ENGLISH
max. permissible short circuit cur- [kA] rent of mains power loss [W]
continuous output current at 4kHz [Arms] 4 [Apk] peak output current at 4kHz [Apk] [Apk] peak output current at 8kHz [Apk] Primary fuse [A] 5.66 [Arms] 7 9.90
2-26
Lexium 05 A
D42M3X 230 (3~) 16.5 3.2 5 132 17 24.04 30 42.43 15 21.21 30 42.43 25
D34N4 400 (3~) 9.2 3.0 5 147 15 21.21 24 33.94 11 15.56 18 25.46 15/16
D57N4 400 (3~) 16.8 6.0 22 240 25 35.36 40 56.57 20 28.28 30 42.43 25
nominal power (device power out- [kW] put) max. permissible short circuit cur- [kA] rent of mains power loss 1) [W]
continuous output current at 4kHz [Arms] 4 [Apk] peak output current at 4kHz [Apk] [Apk] peak output current at 8kHz fuse 2) [Apk] Primary [A] 5.66 [Arms] 7 9.90
1) condition: internal braking resistor not active; value at nominal current, nominal voltage and nominal power 2) Fuses: fusible links of class CC or J as per UL 248-4, alternatively miniature circuit-breakers with B or C-characteristic. 15/16A specification: circuit breakers are available with 16A nominal current, UL fuses with 15A.
Lexium 05 A
2-27
ENGLISH
2.12
Wiring overview
CN1
ANA1+ ANA1-
11 12
+ 10V
CN2
ANA2+ 13 ANA2- 14 + 10V
ENGLISH
U/T1
NO_FAULT_OUT ACTIVE1_OUT *
Fault_Reset*
31 32 33 34 35 36 37 38 39 21 22 23 CANopen 24V
M 3~
V/T2 W/T3
1
R
HBC
CN4
RS485
PC
RS232
44 43 42 41 +
24VDC
CN3 CN5
PULSE/DIR A/B/I ESIM
L1 L2 L3
Figure 2.3
other signal assignment in fieldbus control mode, see product manual Optional: HBC, connection see Figure on page 2-6 Optional: external braking resistor, connection see Figure on page 2-6. If an external braking resistor is installed, the jumper between PA/+ and PBi must be removed.
2-28
Lexium 05 A
Lexium 05 A
2-29
ENGLISH
Lexium 05 A 00198441113252
0 0198441113252