INTRODUCTION
The conical tank process is designed to maintain the level of the tank for the desired value .To ensure the desired value in the tank PI controller law is normally used. In current practice the PI tuning process is performed manually by an engineering technician. However, for better and more consistent quality, it is desired to use automated PI tuning. The dynamics of the conical tank is dominated by the peristaltic pump. To protect the pump, the control signal is restricted to lie in the interval [0,5] volts .The pump also has significant friction, The sensor exhibit significant noise in addition ,the tank area will change due to the height change. Hence, the conical tank process exhibits nonlinear behavior in the parameters. Selftuning control is widely regarded as a method that can potentially become a major industrial control technique. The conical tank process is one of the highly non linear processes. So the difficulty that arises in the identification of this system can be broadly classified into three categories-complexities, non linearity and uncertainty. A selftuning controller is ideally suited to deal with the three classes of difficulties. Embedded based selftuning controller is designed to maintain the level of the tank with the change in area with respect to the change in height. To ensure the level of the conical tank process, a PI control law is designed and implemented in a normal way for a small bandwidth . The feedback control is to maintain the output at the set point while there have been unknown load disturbance and dynamic uncertainty, but if the constant gain controller loses its performance in conical tank because, if the set point largely deviated from the operating point leads to large overshoot in the process output, there is a need for self tuning controller.
Block diagram of self tuning controller 1.1 MATHEMATICAL MODEL FOR CONICAL TANK
The conical tank level process considered for simulation study is the level, the inflow rate and the outflow rate of the tank are considered as the controlled variable ( h ), manipulated variable ( Qin ) and disturbance variable ( Qout ) respectively. The inlet flow Qin , is the control input to the system and the output is the water level. It is assumed that Qin is controlled directly and that a commanded change of the flow takes immediately..
Where
R - Maximum radius in m. H - Maximum height in m. h Height at any timet. r Radius at any timet.
CONTROLLER THEORY
The process is controlled by a controller that has adjustable parameters. It is to determine a controller that satisfies some design criteria if the process and its environment are known. This is called underlying design problem. The adaptive control problem is then to find a method of adjusting the controller when the characteristics of the process and its environment are unknown or changing. In direct adaptive control the controller parameters are changed directly without the characteristics of the process and its disturbances.
PI CONTROLLER
The transfer function for the first order process is given by G(s) = Kp ( s + 1) The difference equation for the above process is y(k ) = a * y(k 1) + b * u(k 1) samp _ time a = exp( ) b = K p * (1 a) From the above equation we can find the value of system parameters by using the Kp = b RLS algorithm, now the system gain is 1 a
HARDWARE IMPLEMENTATION
INTRODUCTION
National Instruments Compact Reconfigurable I/O (RIO) is a small rugged industrial control and acquisition system powered by Reconfigurable I/O (RIO) FPGA technology for ultrahigh performance and customization. NI Compact RIO incorporates a
real-time processor and reconfigurable FPGA for reliable stand-alone embedded or distributed applications, and hot-swappable industrial I/O modules with built-in signal conditioning for direct connection to sensors and actuators. Compact RIO represents a low-cost architecture with open access to low-level hardware resources.
REAL-TIME PROCESSOR
The Compact RIO embedded system features an industrial 200 MHz Pentium class processor . which reliably and deterministically executes your Lab VIEW Real-Time applications. Choose from thousands of built-in Lab VIEW functions to build your multithreaded embedded system for real-time control, analysis, data logging, and communication.
PERFORMANCE
Using Lab VIEW FPGA software and reconfigurable hardware technology, you can create ultrahigh performance control and acquisition systems with Compact RIO. The FPGA circuitry is a 30
parallel processing reconfigurable computing engine that executes your Lab VIEW application in silicon circuitry on a chip. You can design your own custom control or acquisition circuitry in silicon with 25 nanosecond timing/triggering resolution.
HARDWARE IMPLEMENTATION
The physical setup for conical tank process interfaced with PC loaded with RLS algorithm through Lab VIEW and Compact Reconfigurable Input Output . The inflow of conical tank is controlled by peristaltic pump and outflow is through hand valve. The set point is given in terms of volts. The level in the tank is sensed by differential pressure transmitter. The output of DPT is current, converted to voltage by suitable signal conditioning circuit. (Connecting a 250 resistor across it) The level 0mm corresponds to 1v and the level 600mm corresponds to 5v. The voltage output 31
1-5v is then conditioned to 0-4v and it is fed to Compact RIO. The converted digital data is sent to the PC. The controller output is then fed to DAC. The converted analog value of range (1-5v) is then converted into 4-20mA using V-I converter. The current output from V to I converter (4-20mA) vary the frequency of peristaltic pump such that it regulate the flow in order to attain the desired level.
Front Panel
Block Diagram
32
33
CONCLUSION The industrial conical tank has high nonlinearity due to the area get changed with change in height. A self tuning regulator was designed for the conical tank which bounded the tank level from saturation while maintaining the correct level. This project detailed the indirect self tuning regulator design algorithm, which is a combination of the on-line recursive least-squares and controller, the algorithm was implemented for the conical tank. The initial values of the estimated plant parameter vector and the covariance matrix P affect the transient performance of the closed loop system and may possibly lead to tank level saturation. Hence they must be chosen carefully. REFERENCES 1. Yanan Zhao, Emmanuel G.Collins, Jr., and David A.Cartes, Indirect self tuning regulator design for an industrial weigh belt feeder, American Control Conference Anchorage, AK May 8-10, 2002. 2. M.Shangalov, H.M.Budman,online adaptive parameter estimator design and tuning, AACC, 2002. 3. Yasutoshi Mori, Masayoshi Doi and Yasuchika Mori,A self tuning controller for systems with varying time delays, ICE, 2002. 4. K.M.Vu, G.A.Dumont and P.Tessier,Recursive least determinant self tuning regulator, 34
IEEE, 2000. 5. Jinsiang Shaw, chive vibration isolation by adaptive control, IEEE, 1999.
35