Sie sind auf Seite 1von 16

Bypass switches

Type B-1 and type B-2

Answers for energy.

Eliminate voltage regulator bypass switch problems with type B-1 and type B-2

Overview

Type B-1 The Bridges Electric type B-1 regulator bypass switch is a simple and rugged three-bladed disconnect switch. Each blade is independently operated and is readily visible to the operator. The major safety feature of the type B-1 is that the bypass blade can be visually checked to ensure that it is open. This helps eliminate the possibility of the regulator being shortcircuited when it is restored to service. Many available options and accessories make the type B-1 a flexible solution for regulator bypass schemes.

Type B-2 The Bridges Electric type B-2 oil circuit recloser (O.C.R.) (or regulator) bypass switch utilizes the same blade and contact material as the type B-1. Its design provides clearance for an O.C.R. bypass scheme, but can be used as a regulator bypass. Versatility is provided with optional backplate sets for underhung mounting or an angled pole bracket for mounting directly to the pole. Many available options and accessories make the type B-2 a flexible solution for O.C.R. and regulator bypass schemes.

Details

Type B-1 regulator bypass: 600 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C D E F G Dimensions - inches H J K L M N P Q Insulators

610 710 615 715 815

14.4 23 14.4 23 34.5

15 25 15 25 38

110 150 110 150 200

600 600 600 600 600

40,000 40,000 40,000 40,000 40,000

4 4 4 4 6

2 2 2 2 2

28 31 31 34 40

30 33 33 36 42

5 5 5 5 5

8 10 10 14 18

12 15 15 18 24

8 10 10 14 18

10.8 12.8 12.8 16.8 20.8

11.8 13.8 13.8 17.8 21.8

14.3 16.3 16.3 20.3 20.3

15.3 17.3 17.3 21.3 21.3

11.5 14.5 14.5 17.5 23.5

19.7 22.7 22.7 25.7 31.7

29.7 32.7 32.7 35.7 41.7

2 1/4 D.B.C. 3 D.B.C.

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator H = Loadbreak hooks K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper

P = Pole mount bracket QB = Quick break T = Tinned terminal pads X = Backplate set Example: 610CQBT = type B-1, 15 kV, 110 kV BIL, 600 A, polymer insulators, quick break, tinned terminal pads

Details

Type B-1 regulator bypass: 900 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C D E F G Dimensions - inches H J K L M N P Q Insulators

630 730 635 735 835

14.4 23 14.4 23 34.5

15 25 15 25 38

110 150 110 150 200

900 900 900 900 900

40,000 40,000 40,000 40,000 40,000

4 4 4 4 6

2 2 2 2 2

28 31 31 34 40

30 33 33 36 42

5 5 5 5 5

8 10 10 14 18

12 15 15 18 24

8 10 10 14 18

10.8 12.8 12.8 16.8 20.8

11.8 13.8 13.8 17.8 21.8

14.3 16.3 16.3 20.3 20.3

15.3 17.3 17.3 21.3 21.3

11.5 14.5 14.5 17.5 23.5

19.7 22.7 22.7 25.7 31.7

29.7 32.7 32.7 35.7 41.7

2 1/4 D.B.C. 3 D.B.C.

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator H = Loadbreak hooks K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket QB = Quick break

T = Tinned terminal pads X = Backplate set Example: 630CQBT = Type B-1, 15 kV, 110 kV BIL, 900 A, polymer insulators, quick break, tinned terminal pads

Details

Type B-1 regulator bypass: 1,200 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C D E Dimensions - inches F G H J K L M Insulators

625 725 825

14.4 23 34.5

15 25 38

110 150 200

1,200 1,200 1,200

61,000 61,000 61,000

6 6 6

3 3 3

37 40 46

39 42 48

19 22 28

10 10 10

10 14 18

13.3 17.3 21.3

14.8 18.8 22.8

17.4 20.4 26.4

31 34 40

41 44 50 3 D.B.C.

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator P = Pole mount bracket

QB = Quick break T = Tinned terminal pads X = Backplate set Example: 625CQBT = Type B-1, 15 kV, 110 kV BIL, 1,200 A, polymer insulators, quick break, tinned terminal pads

Details

Type B-1 regulator bypass: 600 A with Saf-T-Gap interrupter (600 A loadbreak)

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C D E Dimensions - inches F G H J K L M Insulators

675 775 875

14.4 23 34.5

15 25 38

110 150 200

600 600 600

40,000 40,000 40,000

4 4 6

2 2 3

31 34 40

33 36 42

15 18 24

8 8 12

10 14 18

13.8 16.8 20.8

16.3 17.5 21.3

14.5 17.5 23.5

23.25 26.25 32.25

33.4 36.4 42.4 3 D.B.C.

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket

T = Tinned terminal pads X = Backplate set Example: 675CT = Type B-1, 15 kV, 110 kV BIL, 600 A, polymer insulators, tinned terminal pads

Details

Type B-1 regulator bypass: 900 A with Saf-T-Gap interrupter (600 A loadbreak)

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C D E Dimensions - inches F G H J K L M Insulators

695 795 895

14.4 23 34.5

15 25 38

110 150 200

900 900 900

40,000 40,000 40,000

4 4 6

2 2 3

31 34 40

33 36 42

15 18 24

8 8 12

10 14 18

13.8 16.8 20.8

16.3 17.5 21.3

14.5 17.5 23.5

23.25 26.25 32.25

33.4 36.4 42.4 3 D.B.C.

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket

T = Tinned terminal pads X = Backplate set Example: 695CT = Type B-1, 15 kV, 110 kV BIL, 900 A, polymer insulators, tinned terminal pads

Details

Type B-1 regulator bypass: 1,200 A with Saf-T-Gap interrupter (600 A loadbreak)

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C D E Dimensions - inches F G H J K L M Insulators

685 785 885

14.4 23 34.5

15 25 38

110 150 200

1,200 61,000 1,200 61,000 1,200 61,000

5 5 6

2 2 3

37 40 46

39 42 48

19 22 28

10 10 10

10 14 18

13.3 17.3 21.3

14.8 18.8 22.8

17.4 20.4 26.4

31.6 34.6 40.6

41.6 44.6 50.6 3 D.B.C.

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator P = Pole mount bracket

T = Tinned terminal pads X = Backplate set Example: 685CT = Type B-1, 15 kV, 110 kV BIL, 1,200 A, polymer insulators, tinned terminal pads

Options

The Type B-1 regulator bypass disconnects are available with quick break and pole bracket options.

Quick break option

Pole bracket option


9

Details

Type B-2: O.C.R. (or regulator) bypass 600 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C Dimensions - inches D E F G

603 703 803

14.4 23 34.5

15 25 38*

110 150 150

600 600 600

40,000 40,000 40,000

15.8 18.8 21.8

12 15 18

8 10 10

12.97 14.97 14.97

12 15 18

22.5 25.5 30

12 15 18

* Grounded wye system only

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator H = Loadbreak hooks K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket

T = Tinned terminal pads X = Backplate set L = Bypass blade in left hand position 01 = Angled bypass blade Example: 603-01CPT = Type B-2, 15 kV, 110 kV BIL, 600 A, angled bypass blade, polymer insulators, pole mount bracket, tinned terminal pads

10

Details

Type B-2: O.C.R. (or regulator) bypass 900 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C Dimensions - inches D E F G

604 704 804

14.4 23 34.5

15 25 38*

110 150 150

900 900 900

40,000 40,000 40,000

15.8 18.8 21.8

12 15 18

8 10 10

12.97 14.97 14.97

12 15 18

22.5 25.5 30

12 15 18

* Grounded wye system only

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator H = Loadbreak hooks K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket

T = Tinned terminal pads X = Backplate set L = Bypass blade in left hand position 01 = Angled bypass blade Example: 604-01CPT = Type B-2, 15 kV, 110 kV BIL, 900 A, angled bypass blade, polymer insulators, pole mount bracket, tinned terminal pads

11 1

Details

Type B-2: O.C.R. (or regulator) bypass substation style 600 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C Dimensions - inches D E F G

605 705 805

14.4 23 34.5

15 25 38

110 150 200

600 600 600

40,000 40,000 40,000

19.3 22.3 28.5

15 18 24

10 14 18

15.6 19.6 23.6

15 18 24

27.25 30.25 36.25

15 18 24

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator H = Loadbreak hooks K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket

T = Tinned terminal pads X = Backplate set L = Bypass blade in left hand position Example: 605CPT = Type B-2, 15 kV, 110 kV BIL, 600 A, polymer insulators, pole mount bracket, tinned terminal pads

12

Details

Type B-2: O.C.R. (or regulator) bypass substation style 900 A

Rating data Cat. no. NOM kV MAX kV kV BIL Amps Cont. Mom. A B C Dimensions - inches D E F G

606 706 806

14.4 23 34.5

15 25 38

110 150 200

900 900 900

40,000 40,000 40,000

19.3 22.3 28.5

15 18 24

10 14 18

15.6 19.6 23.6

15 18 24

27.25 30.25 36.25

15 18 24

Note: Add these suffixes to catalog numbers for the option described C = Polymer insulator H = Loadbreak hooks K = Cable connector #6 - 397.5 MCM ACSR #6 - 500 MCM copper P = Pole mount bracket

T = Tinned terminal pads X = Backplate set L = Bypass blade in left hand position Example: 606CPT = Type B-2, 15 kV, 110 kV BIL, 900 A, polymer insulators, pole mount bracket, tinned terminal pads

13

Options

Mounting bracket options

14

Three-phase recloser bypass assembly


n Three type B-2 recloser bypass switches factory installed on an aluminum or fiberglass arm n Aluminum or fiberglass arm mounted on adjustable pole gain, which provides the option of angling assembly based upon field conditions n Single-point lift bracket n Stable switching action while allowing for a visible indication of a break in the circuit n Easy identification of the load and source sides in equipment while the circuit is in its normal configuration n Bypass blades can be easily recognized as open or closed

Contact factory for application information

15

Published by and copyright 2010: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens Energy, Inc. 99 Bolton Sullivan Drive Heber Springs, AR 72543 Phone: +1 (501) 362-8296 Toll-free: +1 (800) 347-6659 Order No. E50001-F630-A117-X-4A00 Printed in USA
BU 2010115153054664F BR 0710.5 All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.

www.usa.siemens.com/energy

Das könnte Ihnen auch gefallen