Section 15854 Air Handling Units & Fan Coil Units Specifications

HVAC Specification

15854-1

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Air Handling Units & Fan Coil Units Specifications Table of Contents Contents 1. Air Handling & Fan Coil Units.......................................................................................................... 3 1.1 1.2 Codes and Standards ............................................................................................................ 3 Air Handling & Treatment Equipment ..................................................................................... 4

1.2.1 General Description........................................................................................................... 4 1.2.2 Type 1: Constant air Volume, Re circulating, Variable ventilation ...................................... 4 1.2.3 Type 2: Variable air Volume, Recirculating, Variable ventilation ....................................... 6 1.2.4 Type 3: Variable air Volume, All fresh air........................................................................... 7 1.2.5 Type 4: Constant air Volume, All fresh air with Energy Wheel Heat recovery ................... 9 1.2.6 Type 5: Constant air Volume, All fresh air with Liquid coupled run round coil .................. 10 1.3 Air Handling Equipment ....................................................................................................... 12 1.3.1 General ........................................................................................................................... 12 1.3.2 Air Handling Plant Construction....................................................................................... 13 1.3.3 Air Handling Plant Casing................................................................................................ 13 1.3.4 Filters .............................................................................................................................. 15 1.3.5 Air Handling Units Dampers ............................................................................................ 17 1.3.6 Air Cooling and Heating Coils.......................................................................................... 18 1.3.7 Heat recovery coils.......................................................................................................... 19 1.3.8 Energy Recovery Wheels................................................................................................ 19 1.3.9 Cross Flow Plate Heat Exchanger Section ...................................................................... 19 1.3.10 1.3.11 1.3.12 1.3.13 1.3.14 1.3.15 1.3.16 1.4 Dehumidifier Section .............................................................................................. 20 Humidifier Section.................................................................................................. 21 Air Handling Units Fans.......................................................................................... 21 Test Holes.............................................................................................................. 25 Drain Pans ............................................................................................................. 25 Manometers........................................................................................................... 25 Dehumidifier Section .............................................................................................. 25

Air Cooled Split System Unit - Ducted Type ......................................................................... 27

1.4.1 General ........................................................................................................................... 27 1.4.2 Room Thermostat ........................................................................................................... 27 1.5 1.6 Fan Coil Units ...................................................................................................................... 28 Guest Room Fan Coil Units ................................................................................................. 30

1.6.1 General ........................................................................................................................... 30 1.6.2 Card Access Panel.......................................................................................................... 31 1.6.3 Drawings ......................................................................................................................... 31 1.7 Schedule:............................................................................................................................. 32

HVAC Specification

15854-2

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

1. 1.1

Air Handling & Fan Coil Units Codes and Standards Work and materials shall conform to the British Standards and Codes of Practice, and with all prevailing rules and regulations pertaining to adequate protection of all moving parts, or otherwise hazardous conditions. Nothing in this Specification shall be construed to permit work not conforming to the most stringent of the applicable codes. ASHRAE: IHVE: ASME: ARI: ASTM: AWS: UL: SMACNA: BSI: NFPA: CIBSE: HVCA: American Society of Heating Refrigeration and Air conditioning (U.S.A.) Engineers The Institute of Heating and Ventilation Engineers (U.K.) American Society of Mechanical Engineers Air Conditioning Refrigeration Institute (U.S.A.) American Society for Testing and Materials American Welding Society Underwriter Laboratories (U.S.A.) Sheet Metal and Air conditioning Contractors National Association, Vienna British Standard Institute CP: Code of Practice National Fire Protection Association The Chartered Institute of Building Services Engineers - UK Heating and Ventilation Contractors Association, U.K.

Other International Standards may be considered provided they meet with the above standards as a minimum. The Codes and Standards mentioned above are hereby made part of the Contract Specification for the project, and the Contactor accepts full liability for ensuring compliance with the same.

HVAC Specification

15854-3

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

1.2

Air Handling & Treatment Equipment 1.2.1 General Description

Various type of air handling equipment will be utilised to air condition and ventilate the equipment. This includes:-

AHU type 1. CV-RC-VV 2. VV-RC-VV 3. VV-FA 4. CV-FA-HR-R

Description Constant Air volume, recirculating, variable ventilation Variable Air volume, re circulating, variable ventilation Variable Air volume, All fresh air Constant Air volume, All fresh air with rotary wheel heat recovery Constant Air volume, All fresh air with run round coil heat recovery

AHU ref. in drawings AHU-1, AHU-2, AHU-3, AHU7, AHU-8(type2), AHU-15. AHU-(type1), AHU-(type2). AHU-04,AHU-6(type1), AHU9, AHU-10, AHU-11, AHU-12, AHU-16, AHU-17.

5. CV-FA-HR-LC

1.2.2

Type 1: Constant air Volume, Re circulating, Variable ventilation

System Function This type of air handling unit system shall provide air conditioning and fresh air ventilation to their served area. Constant air flow equivalent to the maximum load requirement of all served areas shall be utilized. Ventilation air flow shall vary based on occupation as well as the indoor air quality. Ventilation airflow shall be under the control of the indoor air quality sensors. Indoor Air quality shall be determined by the return air CO2 sensors, which shall maintain CO2 concentration below 1000 PPM. System Arrangement
TYPE(1):

Each air-handling unit shall comprise of: Mixing box with return air, exhaust air and fresh air motorized dampers Panel filters to EU3 Bag filters to EU7 Hot water Heating coil Access Section Chilled water cooling coil

HVAC Specification

15854-4

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Constant speed Centrifugal supply fan Connection section with motorized damper Bag filters to EU7 Constant speed Centrifugal return fan
TYPE(2):

(AHU-8) air-handling unit shall comprise of: Mixing box with return air, exhaust air and fresh air motorized dampers Panel filters to EU3 Bag filters to EU7 Hot water Heating coil Access Section Chilled water cooling coil Variable speed Centrifugal supply fan Connection section with motorized damper Bag filters to EU7 Variable speed Centrifugal return fan

Basic Logic Control The return air duct mounted temperature sensor shall control supply Air temperature. This shall sequence the operation of the mixing dampers cooling coil and heating coil control valves. Supply air temperature sensor shall indicate the proper sequence of operation of the control valves and dampers Ventilation airflow shall be under the control of the indoor air quality sensor, which shall also be installed in the return air ducts. The sensor shall measure the concentration of the CO2 Levels as it shall modulate the fresh air and return air dampers However; a minimum fresh air flow rate shall be maintained to compensate for the exhausted air flow rates and to maintain the building positively pressurized to outside, Early morning warm up and cool down mode shall set the system for complete recirculation mode as to boost the heating and cooling mode. Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. The supply and return air fans shall be monitored by differential pressure detectors installed across the fan, the sensor shall report the fans failure to BMS All supply and exhaust air fans shall be connected to the essential power supply. During main power failure, all recirculating air dampers shall shut off, all fresh and exhaust air dampers shall open completely. Air handling units shall run in all fresh air mode,

HVAC Specification

15854-5

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Smoke detectors shall be installed on the return air duct of each air-handling unit. The detector shall be relayed to the fire alarm system and shall shut off the air handling units fans as well as all unit dampers. 1.2.3 Type 2: Variable air Volume, Recirculating, Variable ventilation

System Function This type of air handling unit system shall provide air conditioning and fresh air ventilation to their served area Variable air supply and return shall be supplied depending on the actual demand of each served area. Variable air volume system shall be utilized. The system shall utilize variable ventilation airflow; this is to respond to the variation of the occupations. Accordingly; Ventilation airflow shall be under the control of the indoor air quality sensors. The return air CO2 sensors, which shall maintain CO2 concentration below 1000 PPM, shall determine indoor Air quality. System Arrangement Air handling unit shall comprise of: Mixing box with return air and fresh air motorized damper. Fresh air sand trap louver Exhaust louver Panel filters to EU3 Bag filters to EU7 Chilled water cooling coil Electric heating coil Centrifugal supply fan Centrifugal return fan Attenuators Access sections Supply air ducts shall run at high level of the ceiling void of the ground floor offices. The layout of the offices may be altered and modified, in order to provide flexibility in the system operation, flexible duct outlets shall stem out of the main duct to serve all offices via VAV terminals. Return air shall be carried out through the ceiling void of the corridors before returning back to the air-handling unit via duct work. Cross talk attenuators shall be installed between the offices and the corridors. Basic Logic Control

HVAC Specification

15854-6

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

The return air duct mounted temperature sensor shall control supply Air temperature. This shall sequence the operation of the mixing dampers cooling coil control valve and the unit electric heater. Relative humidity of the zone shall be under the control of the return air duct mounted humidity sensor. This shall sequence the operation of the cooling coil control valve and electric heaters. Supply airflow shall be under the control of the pressure sensor installed at 70% of the supply air duct. The sensor shall modulate the fan speed via frequency invertor A high limit pressure switch shall be installed at the main supply air duct . This shall protect the installio n against any excessive pressure. Return airflow shall be tracked with supply airflow to maintain the zone positive to outside. Frequency invertor shall control fan speed. Ventilation airflow shall be under the control of the indoor air quality sensor, which shall also be installed in the return air ducts. All VAV terminals shall be of pressure independent type. Each VAV shall be under the control of the room thermostat. The sensor shall measure the concentration of the CO2 Levels as it shall modulate the fresh air and return air dampers. However; a minimum fresh air flow rate shall be maintained to compensate for the exhausted air flow rates and to maintain the building positively pressurized to outside, Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. Differential pressure detectors installed across the fan shall monitor the supply and return air fans. The sensor shall report the fans failure to BMS All supply and exhaust air fans shall be connected to the essential power supply. During main power failure, all recirculating air dampers shall be maintained on, all fresh and exhaust air dampers shall shut off or minimal fresh air shall be maintained. Air handling units shall run in recirculation mode Smoke detectors shall be installed on the return air duct of each air-handling unit. The detector shall be relayed to the fire alarm system and shall shut off the air handling units fans as well as all unit dampers. 1.2.4 Type 3: Variable air Volume, All fresh air

This type of air handling unit system shall provide air conditioning and fresh air ventilation to their served area Variable air supply turn shall be supplied depending on the actual demand of each served area. The system shall utilize variable ventilation airflow; this is to respond to the variation of the occupations, room pressurization ,and replenish air lost from fume cupboard and safety cabinet isolator .

HVAC Specification

15854-7

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Type(1) :AHU-13

System Arrangement The Fresh air-handling unit shall be comprised of: Connection section with motorized damper Panel filters to EU3 Bag filters to EU9 Hot water Heating coil Access Section Chilled water cooling coil Humidifier Variable speed Centrifugal supply fan Access Section HEPA filter to H13 Access Section
Type(2) :AHU-14

System Arrangement The Fresh air-handling unit shall be comprised of: Connection section with motorized damper Panel filters to EU3 Bag filters to EU7 Hot water Heating coil Access Section Chilled water cooling coil Variable speed Centrifugal supply fan Basic Logic Control. The supply air duct mounted temperature sensor shall control supply Air temperature. This shall sequence the operation of the mixing dampers cooling coil and heating coil control valves. Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. During main power failure, the fresh dampers shall open completely. Air handling units shall run in all fresh air modes, Smoke detectors shall be installed on the supply air duct of each air-handling unit. The detector shall be relayed to the fire alarm system and shall shut off the air handling units fans as well as all unit dampers.

HVAC Specification

15854-8

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. The condition of the supply and exhaust air fans shall be monitored by differential pressure detectors installed across the fan. The sensor shall report the fans failure to BMS 1.2.5 Type 4: Constant air Volume, All fresh air with Energy Wheel Heat recovery

System Function Fresh air handling units, shall be provided with rotating heat recovery wheels systems and exhaust air fan shall be utilized Heat recovery wheels shall make use of the energy of the exhaust fans The Fresh air-handling unit shall be comprised of: Connection section with motorized damper Fresh air louver Pre filters to EU3 Bag filters to EU7 Energy recovery wheel Chilled water cooling coil Heating water coil Centrifugal supply fan Mixing section with motorised damper Attenuators Access sections The Exhaust Air section unit shall comprise of: Exhaust air section motorized damper Exhaust Air louver Pre filters to EU3 Basic Logic Control. The supply air duct mounted temperature sensor shall control supply Air temperature. This shall sequence the operation of the mixing dampers cooling coil and heating coil control valves. The exhaust air duct mounted temperature sensor shall control the sequence of the operation of the mixing dampers and the operation of the energy recovery wheels. A Minimum fresh air and exhaust air flow rate shall be set at early morning warm up and cool down mode as to boost the heating and cooling mode. Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. The supply and exhaust air fans shall be monitored by differential pressure detectors installed across the fan, the sensor shall report the fans failure to BMS

HVAC Specification

15854-9

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

A trigger switch shall monitor the operation of the energy recovery wheels During main power failure, all recirculating air dampers shall shut off, all fresh and exhaust air dampers shall open completely. Air handling units shall run in all fresh air modes, Smoke detectors shall be installed on the supply air duct of each air-handling unit. The detector shall be relayed to the fire alarm system and shall shut off the air handling units fans as well as all unit dampers. Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. The condition of the supply and exhaust air fans shall be monitored by differential pressure detectors installed across the fan. The sensor shall report the fans failure to BMS 1.2.6 Type 5: Constant air Volume, All fresh air with Liquid coupled run round coil

System Function Fresh air handling units, with liquid coupled heat recovery systems and exhaust air fan shall be utilized
Type(1) :AHU-6

System Arrangement: The Fresh air-handling unit shall comprise of: Intake air section with motorized damper Panel filters to EU3 Bag filters to EU7 Liquid coupled Heat recovery coil with recirculating pump and expansion vessel Access Section Hot water heating coil Access Section Chilled water cooling coil Centrifugal supply fan The Exhaust Air section unit shall comprise of: Intake air section with motorized damper Bag filters to EU7 Liquid coupled Heat recovery coil Centrifugal exhaust fan.
Type(2) :AHU-(04-9-10-11-12-16)

System Arrangement: The Fresh air-handling unit shall comprise of: Intake air section with motorized damper Panel filters to EU3

HVAC Specification

15854-10

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Bag filters to EU9 Liquid coupled Heat recovery coil with recirculating pump and expansion vessel Access Section Hot water heating coil Access Section Chilled water cooling coil Humidifier Centrifugal supply fan Access Section HEPA filter to H13 Access Section The Exhaust Air section unit shall comprise of: Intake air section with motorized damper Panel filters to EU3 Bag filters to EU7 Liquid coupled Heat recovery coil Centrifugal exhaust fan.
Type(3) :AHU-(17)

System Arrangement: The Fresh air-handling unit shall comprise of: Intake air section with motorized damper Panel filters to EU3 Bag filters to EU9 Liquid coupled Heat recovery coil with recirculating pump and expansion vessel Access Section Hot water heating coil Access Section Chilled water cooling coil Humidifier Dual Centrifugal supply fan(1on duty,1stand by) Access Section HEPA filter to H13 Access Section The Exhaust Air section unit shall comprise of: Intake air section with motorized damper Panel filters to EU3

HVAC Specification

15854-11

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Bag filters to EU7 Liquid coupled Heat recovery coil Dual Centrifugal exhaust fan(1on duty,1stand by).

Basic Logic Control The air handling unit shall provide dehumidified air at constant temperature. This shall be controlled by the supply air duct mounted and temperature sensor. The sensor shall sequence the operation of cooling coil control valve and the heating coils. Differential pressure detectors reporting the pressure drop on the BMS shall monitor the conditions of the filters. The condition of the supply and exhaust air fans shall be monitored by differential pressure detectors installed across the fan. The sensor shall report the fans failure to BMS All supply and exhaust air fans shall be connected to the essential power supply. Smoke detectors shall be installed on the supply air duct of the air-handling unit. The detector shall be relayed to the fire alarm system and shall shut off the air handling unit fans as well as all unit dampers. Fan coil units shall be controlled by return air duct sensors. On/Off switch as well as fan speed selector shall be under control of the BMS system. Temperature sensor shall modulate the fan coil unit control valves. 1.3 Air Handling Equipment 1.3.1 General

A. This Section of the Specifications covers air-handling units. Air handling units shall be completely factory assembled by a reputable manufacturer. B. Each unit shall be of suitable size as shown on equipment schedule C. Each unit shall incorporate the following:A nameplate shall be permanently affixed to every unit listing air volume, fan static pressure, coil duties and heat recovery equipment ratings. Lifting rings shall be provided on all individual components of 35 kg mass and above for maintenance removal. All bearings shall be supplied fully lubricated. Spare drive belts shall be provided, in sets where applicable, for each drive in the assembly to a total of one complete change per drive. Air Handling Units shall not exceed the overall maximum dimensions specified by 15%.

HVAC Specification

15854-12

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

The automatic control equipment required shall be supplied by the controls manufacturer and fitted by the equipment manufacturer, unless otherwise instructed. All access doors shall be insulated to the same standard as the unit casing open towards the high-pressure side. All construction and applications shall comply with the requirements of BS 8313 or NFPA 90A and NFPA 90B requirements with respect of fire precautions against fire. All components shall be inherently non-flammable or be made permanently so by suitable treatment. Any viscous liquid used shall have a flash point in excess of 177C. All components shall be tested and certified in accordance with the appropriate ARI or Eurovent . Fans shall be tested and certified in accordance to AMCA. All electrical items of equipment cabling, wiring, and works shall comply with the latest edition of IEC or IEE Wiring Regulations & Electricity at Work Regulations 1989 or equivalent approved. Test Points shall be provided to enable comprehensive airside and waterside tests to be made on each air-handling unit. 1.3.2 Air Handling Plant Construction

The air conditioning plants for the different areas in the plant shall comprise the individual components as shown in attachments, given at end of this section. 1.3.3 Air Handling Plant Casing

A. The unit casings shall be made of insulated double panels built into a post frame. B. Each section of a unit shall have a post framework constructed of multi angle formed members measuring 50 mm. x 50 mm with 50 mm. deep return edge and 50 mm. seating flange fabricated from insulated aluminium for units, . Corners shall be formed from metered joints welded to form a rigid strong joint cleaned off smooth. C. Frame posts and cross members shall be constructed to incorporate 50 mm. nominal thickness thermal insulation which shall be sealed in position with an additional angle member riveted or spot\welded in place. D. All framework shall protected against corrosion after manufacture. Lifting eyebolts shall be provided on the corners of the sections and shall be removed after installation, the holes being plugged off with suitably sized flush fitting brass plugs. E. Insulation materials shall be tested to and shall comply with EN 1886 class T3 and achieve class 1 ratings. F. Insulation panels shall have a thermal conductivity not greater than 0.03 W/mC and have a minimum thickness of 50mm. G. Insulates incorporating CFCs in their manufacture, woodwool slabs, polystyrene and urea formaldehyde shall not be used.

HVAC Specification

15854-13

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

H. If mineral fibers material is used the density shall not be less than 48 kg/m3 and provisions shall be made to ensure that no settling in materials occurs I. Panels shall be formed from two sheets of the external sheet shall be of 1.2 mm. thick electronic plated steel having 25 mm. returned edges riveted or spot welded together. Internal shall be of galvanized steel sheet of minimum 0. 7mm

J. The insulated top and bottom panels of the units shall be designed to withstand the weight of a man and the necessary equipment for maintenance purposes, by forming the inner metal surface in a number of tray pieces, which fit inside the complete outer panel section. K. Panels shall be adequately stiffened and braced to prevent flexing and drumming and as necessary to maintain rigidity. L. All panels shall be of the bolted in removable type: panels fitting flush into frames and corner posts to give smooth external faces. M. Joints between panels and framework shall be sealed airtight with non-hardening plastic ribbon seal seating strip. N. The completed air handling unit casings shall be designed and installed to reduce the fans sound power level radiated into the plant room, or roof level, by the amounts as specified in Schedule S3.01. The density and type of thermal and acoustic insulation to be sandwiched within the panels shall be selected to achieve the panel attenuation specified in Schedule S3.01. __________________________________________________________________ Schedule S3.01 ___________________________________________________________________ Frequency HZ 63 125 250 500 1K 27 30 35 2K 4K

Power Loss dB

22.5 28

27.5 29

___________________________________________________________________ A. Framework and panels shall be constructed so that bare metal bridges linking inside to outside will not occur. The units shall be designed to prevent condensation from occurring from any cool surface of the unit. B. Individual panel sizes shall not be greater than 3.5m by 1.75 m. where sections are dimensionally larger; more than one panel shall be used. C. All panels and section framework shall be of manageable proportions for transportation and shipment. D. The air handling plants shall be painted at the manufacturer's works before dispatch and shipment internally with a complete corrosion resistant paint finish. E. The air handling plants shall be decoratively painted externally in accordance with the painting and decorating Clause of the Specifications. F. Air handling units, which are installed externally, shall be provided with rainwater hood completely extended above the air-handling unit. The unit shall be decoratively painted with final two coats suitable for the weather conditions that prevail in the region (see design conditions in specification).

HVAC Specification

15854-14

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

G. All units intake and exhaust shall be provided with rainwater hood as well as birds screen. H. Doors in access (empty) sections and fan sections shall be suitably sized for man access into and for easy maintenance of the equipment. Each door shall be of double skin construction with an infill of thermal and acoustic insulation to provide acoustic properties equivalent to the unit panels. I. Doors shall be designed to be an airtight fit and match the unit panels. The doors shall be double hinged to ensure a good seal onto the gaskets and shall include chromium plated handles, seals and fasteners to hold the neoprene seals in compression.

J. All doors shall be openable from outside and inside the section and shall be provided with door locks, which can be locked from outside the unit but which can still be opened from the inside. K. Access doors shall be provided on both sides of each unit in access sections and fan sections. 1.3.4 Filters

1.3.4.1 Bag Filters

A. Where indicated in the Equipment schedules sheets, bag filter sections shall be incorporated. B. These can comprise a composite section of the air-handling unit, which shall be arranged to enable side withdrawal of the filter media from the unit. C. Holding frames shall be constructed from galvanized sheet steel with suitable seals provided to prevent air bypass around the filters. D. The filter media shall consist of high-density glass micro fibre media with individual dust holding compartments, reinforced with a backing to form a lofted filter blanket. The filter media shall have an average arrestance efficiency of not less than 95 % and atmospheric dust spot efficiency 80-90 % on ASHRAE test Standard 52-76 or to EU grade (EU-7)/EU-9. E. The configuration of the dust holding compartments shall be controlled by means of progressive link stitching. The stitching shall be such that it forms a supported compartment resulting in uniform velocities in the passages of the air exit side of the filter. F. The dust holding compartments shall be equipped with a minimum of 516 support points per square meter of the filter media. G. All stitching points shall be sealed with a hot melt adhesive. H. Each filter bank shall be fitted with an inclined tube manometer connected at the works by the manufacturer.
1.3.4.2 Panel Filters (Pre Filters)

A. The filter media shall be natural, synthetic or glass fiber or fabric fibrous material shall be covered with a final scrim backing. They shall be replaceable filter elements in either mat or pad form, suitable for attachment to the upstream face of the bag filter banks.

HVAC Specification

15854-15

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

B. They shall be fixed in permanent holding frames, and clips to ensure quick and easy removal of pre filters. The arrangement of the pre-filters shall not impair access to and serviceability of the bag filters. All frames and clips shall be galvanized steel or other acceptable corrosion resistant material. C. All filter elements shall be bedded firmly into permanent frame seals and pressed firmly and continuously onto face of bag filter frame by a cam operated mechanism or a series of accessible clips for front withdrawal type to prevent air by passing. D. Panel filter assemblies shall be 50 mm. thick unless otherwise specified and have efficiencies of not less than those given below for various types of media when tested, to BS 2831 Test Dust No. 2, or ASHRAE 52-76 test. Typical performance requirements: Media Volume Type 3 Media No. 1. 2. Nominal face Velocity m/s 2.0 Typical Construction Initial PD Pa Efficiency BS 2831 96 At Design ASHARE 5276 86

80

Laminated two stage glass filament media. As type 1. followed with a synthetic scrim.

E. The filter media shall provide a normal servicing frequency of 4 months with a rise in pressure drop from clean to dirty of not more than twice the initial pressure drop. F. Each filter bank shall be fitted with an inclined tube manometer connected at the works by the manufacturer.
1.3.4.3 Panel Washable Type Filters

The filter media shall be combined of expanded and slit aluminium, bonded together in various patterns to form a unique baffle design. This rustproof aluminium should be easily washed.
1.3.4.4 HEPA Filters

The filter casing shall be constructed form stove-enameled sheet steel with a secure, central, sealing and clamping device for the particulate air filter cell. Shall be provide and pre-assembled pressure measuring points, with tubes run to immediately across the filters. The filter cell shall be accessible from the ceiling void. The air velocity across the filter shall not exceed 2.5 m/s. The particulate air filter frame shall be constructed from a moisture proof fire resistant impregnated board, with fixed neoprene rubber sealing on one side.

HVAC Specification

15854-16

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

The filter media shall be moisture proof glassfibre paper with aluminum corrugated spacers. The filter unit shall be H13 (99.95%) efficient when tested in accordance with BS. 3928 (sodium flame) to meet the Class (1) Clean Room Requirements of BS. 5295. The assembly of filters shall be tested on site by a DOP testing rig. The filter shall be suitable for operation in maximum conditions of 60 deg.C and 100% R.H. 1.3.5 Air Handling Units Dampers

A. Air regulating dampers in air handling plant sections shall be assembled from individual dampers bolted together to form a multiple unit. The dampers shall be manufactured of extruded aluminium multi leaf opposed blade type. The assembled unit shall be bolted to angle and channel framework built into the unit casings. B. The multiple damper units shall be sized for the full air handling unit area, without blanking plates. The face velocities shall be not greater than 5.08 m/sec. (1000 f.p.m.). Closed blade leakage should be <10 m3/h.m2 with a 100 Pa pressure differential. C. Complete damper assemblies shall be operated in vertical banks across the width of the unit. or the adjustment of vertical banks damper regulators with locking quadrants shall be installed inside the unit casing integral with the vertical bank. D. Damper regulators shall be marked to indicate the damper position. E. Dampers shall be designed, selected and installed such that they do not whistle, whine or produce any recognizable pure tone. The regenerated noise from dampers shall not exceed the induct sound power level at that point of the ductwork system, also the regenerated noise when combined with the induct sound power level at that point must not exceed the criterion in any room over which the duct passes subsequently or in a room which is subsequently served by that ductwork system. F. Damper frames shall be fabricated from galvanized steel channel with all four corners of the frame braced, and shall be electro galvanized after manufacture. G. Damper blades shall not be greater than 250 mm. in width. Blades made from aluminiumextruded sections. The blades shall have interlocking edges and cross-connecting brackets. Each blade shall have neoprene edging inserted along its length to ensure an airtight seal and whistle free operation. H. Damper sections shall be built to size using the lowest practicable number of equal width blades inter-connected on every other blade. Any resulting small air gap top and bottom between blades and channel frame shall be blanked off. Damper blade side stops shall be overlapped and designed to contact blade edges and reach the blade axles. I. Damper blade axles and push rods shall be of the blind end type with the bearings mounted flush with the inside face of the damper frame. The bearing shall be pre packed with grease and the open end sealed with a rubber '0' ring seal to prevent air leakage. The opposed blades action only, via gears, made from special anti-static plastic (ABS), temperature resistant to 100 C. Bearing seal achieved using a plastic elastomer on rear of gears between case and gear. Material: Perbunan.

HVAC Specification

15854-17

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

J.

Multizone air handling units shall include mixing dampers for each individual zone. The dampers shall provide optimum control of temperature by modulating the mixing air dampers. The damper sexton shall be extended to full width of the units. The dampers blades shall securely mounted on a common steel rod and positioned at 90-degree angles in relation to each other. 1.3.6 Air Cooling and Heating Coils

A. Air cooler/heaters batteries contained within air handling plants shall be sectionalised. The whole air cooler battery shall be made up of individual cooler batteries having an overall area not greater than 2.0 square meters. B. The Air cooler/heaters batteries shall be bolted onto a steel channel and angle iron framework built inside, and bolted to the unit. The framework shall be protected against corrosion and all nuts and bolts shall be cadmium plated. C. Airtight blanking plates shall be provided to seal the remaining portions of the cross sectional area of the air handling unit when the cooler battery is less than the cross sectional area of the unit. Sufficient space shall be left between the battery assembly and the top and bottom of the units for bolting the individual batteries in position in situ. D. Each Air cooler/heaters batteries flow and return connection shall be extended through the unit side casings with puddle type black steel extension flanges ending to match flange pipe joints within the units. Where two cooler battery sections are mounted end to end across the width of the unit, the primary flow and return connections shall be handed so that the coil can be connected to the service mains at each side of the unit. E. Each air cooler/heaters batteries battery shall be manufactured in accordance with the following Specification. Cooling battery coils shall be constructed from 20 mm. 0/D solid drawn copper tube mechanically expanded into collar spaced ribbed and punched aluminium fins of maximum density 320 fin/meter (8fins/inch). The fin and tube matrix shall be treated after manufacturing with corrosion protective layers such as acrylic coatings or other approved materials. Coils in all AHUs should not contain more than six rows. F. Each air cooler battery shall be provided with a galvanized steel drip tray at the base of each section of the battery. Each drip tray shall be tanked and sealed into the assembly. Each drip tray shall be fitted with air deflectors and 25-mm. pipe drain. Each intermediate drain pan shall be connected with a drain pipe feeding into the main air handling unit drain pan as specified in this Section G. Drain pans shall be designed to minimize the risk of legionella. H. The air velocity across the cooling coil shall not exceed 2.75 m/sec. Accessories Each coil shall be provided with the following accessories: Isolating valve Balancing valve with by-Pass globe at the main return. Modulating control Valve Self Seating Plugs Strainer

HVAC Specification

15854-18

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

Air Vent 1.3.7 Heat recovery coils

Heat recovery units shall be designed for a maximum air speed of 2.5 m/sec. and a pressure drop at the air side not higher than 200 Pa. hey shall be operated with a water and ethylene or propylene glycol solution able to working at outside air temperature as mentioned in the relevant data sheet. he maximum pressure drop shall be 30 kPa at solution side. Circulating pump shall be to circulate flow between heat recovery coil ,pumps shall be complete with expansion tank , check valve ,strainer ,isolating valve .all related pipes between heat recovery coils .

1.3.8

Energy Recovery Wheels

Wheels shall be of the enthalpy or sensible type as shown on drawings, the wheel shall be designed for laminar flow. Energy transfer rating must be ARI certified to standards 1060. Wheel segments shall be of removable segments for ease of service and cleaning. Enthalpy recovery wheels shall be of silica gel for maximum latent energy transfer. Wheels shall be constructed of lightweight polymer media or to minimize shaft and bearing loads. Polymer media shall be mounted in a stainless steel rotor for corrosion resistance. Silica gel shall permanently bonded to wheels media to retain latent heat capacity after cleaning. Energy recovery device shall transfer moisture entirely in vapour phase. Alternatively enthalpy wheels shall be made of aluminium materials coated by 3A molecular sieve desiccant substrates, with a non masking porous binder adhesive Face velocity shall not exceed 3.0 m/s Sensible recovery wheels shall be of aluminium mesh for maximum sensible energy transfer. Energy recovery drive belt material shall be strength urethane and shall be factory installed on a pre stretched state; to eliminate the need for field belt tension adjustment link style belts are not acceptable. Energy wheels shall be mounted on a slide out track for ease of inspection, removal and cleaning 1.3.9 Cross Flow Plate Heat Exchanger Section

The plate heat exchanger shall be manufactured by Greenbox or equal and approved. The heat exchanger matrix shall consist of several specially thermoformed plates, connected together via aerodynamic folded leading edges, which are permanently bonded and sealed. The complete heat exchanger matrix shall be mounted and sealed into a heavy duty PVC casework, comprising extruded PVC box section framework and thermoformed PVC end trays stiffened with L section PVC extrusion. The heat exchanger manufacture shall provide a 5 year anti-corrosion warranty.

HVAC Specification

15854-19

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

A side or middle bypass suited to the exchanger package shall be built into the casing and shall be complete with opposed blade dampers fitted within the frame and fastened directly on the casing and be complete with all necessary linkages for motorised operation. The cross flow plate heat exchanger section shall be complete with Galvanised sloping drain pans. An option for a corrosion-protected exchanger and stainless steel drain pans provided where units are designed to operate in condition 1.3.10 Dehumidifier Section shall be

The Dehumidifier section shall include a- Regeneration Filtration b- Desiccant Rotor c- Reactivation Section d- Steam coils e- Regeneration Fans A- Regeneration Filtration The Regeneration filtration section shall be containing Bag Filters and HEPA filters. Final HEPA Filters shall be H13 according to EN 1822 efficiency. All filters should be supplied magnehelic gauges B- Desiccant Rotor The rotor shall be washable in industrial alcohol. The desiccant rotor is the moisture absorbing part of the dehumidifier and consists of a special composite matrix of heat resistant material which houses the silica gel or Lithium Chloride desiccant. Adsorbents shall be synthesized silica gel and metal silicates. The adsorbents shall be bounded to a base of ceramic paper though a temperature process, assuring that all materials shall be strongly bounded to the rotor and no dust will leave the rotor. The rotor shall be contains no LiCI or any other absorbents. The rotor shall be fixing to stainless steel shaft. E- Desiccant Rotor Microprocessor - based direct digital control (BMS) which supervises the operation of the dehumidifier and provides display messages of system parameters and faults. Analogue signals or digital or through web access. Temperature and RH control using two sensors or more Weather proof control panel. Safety mechanical electronic thermostat. E- Reactivation Section Steam coils complete with steam isolating valves, steam relay points steam control and reducing valves steam condensate accumulators and temperature sensor and control panel,

HVAC Specification

15854-20

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

1.3.11

Humidifier Section

Humidifiers shall be of the self-contained, electronically controlled, self generative type. The Air handling unit manufacturer shall mount the humidifier onto the outside of the humidifier section. The steam shall be generated in a polypropylene cylinder of the disposable type for ease of maintenance. Stainless steel steam lances shall be sized in accordance with humidifier manufactures recommendations and installed within the humidifier section by the Air Handling Unit manufacture, condensate pipework and separators shall also be provided if required. The humidifier shall have a microprocessor-based control able to detect abnormal operation and respond to it by corrective action, the internal control circuit shall operate at 24 VAC The humidifier shall shut-down and provide local indication in the event of: a. high current b. blocked drain pump and c. fault on feed water supply. When connected to a mains water supply and appropriate humidity controller, the humidifier shall be totally automatic in operation. The boiled water condition shall be automatically and continuously monitored to ensure operation with minimum energy wastage. The humidifier section shall be complete with stainless sloping drain pans, Where the Air Handling Unit is located externally the AHU manufacturer shall provide a weatherproof enclosure to house the humidifier. The enclosure shall be manufactured from the same casing construction as the Air Handling Unit and shall be sized to allow maintenance of the humidifier, in accordance with the humidifier manufacturers 1.3.12 Air Handling Units Fans

A. Supply air fans , exhaust air fans and re-circulation air fans mounted within air handling unit sections shall be centrifugal casing type designed and manufactured as specified herein. B. Fans shall be double inlet, double width centrifugal plug, forward , air foil or backward curved, with high efficiency. C. Fans shall be suitable for indirect drive by matched vee belts and pulleys. Where the system allows low flow, multi vane forward curved bladed fans may be used. D. Fans shall be selected for low sound level and highest efficiency. All fans shall be selected to be operated by at least 10% in capacity over the design volume specified. E. The fan performance shall be tested and certified to ANSI / ASHRAE Standard 51Laboratory Method of Testing Fans for Rating and AMCA 300 Reverberant Room Method for sound Testing of Fans. (FC & BC 315 and above). F. Fan wheels and shafts shall be statically balanced prior to assembly and dynamically

HVAC Specification

15854-21

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

balanced as an assembly in the factory at design speed prior to delivery. G. Fan casings and scrolls shall be fabricated from heavy gauge mild steel plate adequately stiffened and supported. Fan casings shall be rigid and completely free from vibration and drumming and capable of with standing the pressures involved without leakage or distortion. Fan casings shall be continuously welded construction split as required to pass through available unit access doors. H. Fan casings shall be bolted construction for ease of installation, the number of sections being dependent upon the size of the fan and access available for future removal and replacement. I. Bearing blocks shall be carried on opposite sides of the fan casing on bearer bars forming a part of a rigid fabricated steel structure integral wit h the casing.

1.3.12.1 Fan Drives and Guards

A. Fan drives for centrifugal fans shall be multiple vee belts and variable pitch pulleys. B. Pulleys of the taper lock type may be used for drives up to 30 KW output. The pulleys shall be keyed to the shafts after commissioning. C. Alternatively and where drives are above 30 KW out-put, the pulleys shall be secured to the fan and motor shafts by fitting into machined keyways. Keys shall be easily accessible so that they can be withdrawn or tightened and shall be accurately fitted so that the gib head does not protrude beyond the end of the shaft. D. Each fan set shall be supplied with initial sets of pulleys and drives to give the duties as designed. E. Fans with standby motors if require shall be provided with two sets of pulleys, one on each side of the fan. F. Vee belt drives shall comply with BS 3790 and shall be capable of transmitting not less than the rated wattage output of the motor with one belt removed. G. Machined bolts, nuts and washers shall be used for the assembly of fans: all bearing surfaces for the heads of bolts of washers shall be counter-faced. H. All fan casings shall be fitted with bolted on airtight inspection door and a drain plug. I. Fan casing shall be fitted with flanged outlets for duct connections and shall have rigid spigot inlets truly circular and free from dents.

J. Inlet cones shall be manufactured to close tolerances to avoid turbulence at the air entry to the impeller. All internal and external exposed casing surfaces shall be zinc sprayed for protection against corrosion. K. The fan impeller wheel and blades shall be robustly constructed from mild steel sheet with fabricated steel or cast iron boss with back plate when required. The boss shall be bored and key wayed for the shaft. Impellers shall be zinc sprayed against corrosion. L. Impellers shall be rigidly braced to ensure concentricity and eliminate vibration and shall be certified as being statically and dynamically balanced on their shafts at the manufacturers works.

HVAC Specification

15854-22

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

M. Fan driving shafts, of ample section for the loading, shall be of high tensile mild steel, precision turned ground and polished. N. Keyways shall be provided for securing the impeller and riving pulley. O. All fans shall be fitted with grease lubricated ball or roller bearings mounted in cast iron plumer blocks. No fan drive shall be fitted with less than two belts. P. All vee belts shall be of the anti static type suitable for operation in temperatures likely to prevail in the plant rooms. Q. Guards shall be provided for all open unprotected air inlets to centrifugal fans, for vee belt drives and pulleys whether within unit casings or not R. For vee belt drives the guards shall be of galvanized steel wire not less than 2.5 mm. diameter formed into a mesh not greater than 25 mm. attached to a rigid galvanized steel framework of rods not less than 10 mm. diameter. S. Drive and pulley guards shall be made to be readily removable to permit belts to be changed. T. Adequate access panels shall be provided in the guard to allow tachometer readings of the shafts to be taken and the belt tension to be tested. Allowance shall be made in the dimensions of the guard and the size and position of access panels for the adjustment of the motor on its side rails. Fans with standby motors shall be provided with two guards one on each side of the fan.
1.3.12.2 Fan Motor

A. Electric motors shall be continuously rated of metric frame construction and shall comply with BS. 5000 and BS .2048. B. IP54 protection and class F insulation with class B temperature rise complying with BS2757. motors comply with AS1360 on physical dimensions and to AS1359 on performance. Motors should be rated for operation up to an ambient temperature of 54C C. Each motor shall be rated at 130 percent (%) of the fan's rating when running at the duties as designed. Fan motors shall be squirrel cage, total enclosed, fan cooled type wound for 415 volts, 3 phase, 4 wire, 50 hertz electrical supply. Thermistor type overheating cut outs shall be provided in the motor windings. D. All motors shall be suitable for horizontal foot mounting and be complete with slide rails and belt adjusting bolts. E. Standby motors, when required, shall be complete as for duty driving motors with slide rails and shall be permanently mounted and wired within the air handling units so that in the event of failure of the duty motor the standby motor can be started without any belt changing, etc. F. Each fan and motor assembly including standby motors shall be mounted on a fabricated and welded rolled steel channel iron base frame, suitably drilled for mounting upon antivibration mountings within the air handling unit fan section casing.
1.3.12.3 Anti Vibration Treatment

A. All equipment containing moving parts generating noise or vibration shall be mounted or placed upon specially designed isolators. All connections to such equipment shall be fitted

HVAC Specification

15854-23

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

with flexible connectors to prevent transmission of such noise and vibration to the structure or to other areas of the Building or to other pieces of equipment. B. Each centrifugal fan and motor channel base frame shall be mounted on anti vibration mountings as specified herein. C. The resilient material of the anti vibration mounting shall be rubber or neoprene for static deflections of less than 12 mm. and steel for deflection of greater than 12 mm. Steel springs shall contain a series of rubber or neoprene pads to contain and isolate the structural borne noise component. Anti vibration mounting shall be adjustable in height to level the machine foundation except where the static deflection of the mount is less than 6 mm. D. Where practicable, anti vibration mountings shall be removed for shipment. Where impracticable anti vibration mountings must be provided with transit bolts and nuts to hold them rigid to the frame of the machine. E. Flexible joints shall be provided on fan inlet and outlet connections as required. F. Flexible joints and material shall be of, or be protected by, material having a fire penetration time of not less than fifteen minutes when tested in accordance with BS476, Part 1, Section 3.00. The material shall be of the glass fiber cloth type and waterproof. Canvas material will not be permitted. G. The width of the joints from metal edge to metal edge shall not be less than 100 mm. and not greater than 250 mm. H. All flexible joints shall be between flanged ends. The flexible material flange shall be backed by an angle or flat iron flange and the flexible material held securely between the metal faces of the steel section. I. All electrical conduits and connections in contact with fans, bases, motors or supports shall be fitted with flexible sections to avoid nullification of the anti-vibration treatment provided.

J. Flexible conduit shall be watertight, PVC sheathed, spiralled metal type. The conduit shall be terminated at boxes and equipment with compression glands. Additional PVC insulated stranded tinned copper earthing conductor not less than 6 mm. diameters shall be drawn into flexible conduits and connected to the earth terminals at each end of the flexible run.
1.3.12.4 Tests and Performance Certificates

The Contractor shall submit for approval before placing his order for the AHU's the following information: a) b) c) A description of the actual test procedures used by the fan manufacturers. A laboratory test sheet showing results of a test for fans typical of the types that will be ordered. A fully documented list of total sound power levels in each of the second octave bands between the frequencies of 63 Hz and 4 KHz for each fan.

J. The fan performance shall be tested and certified to ANSI / ASHRAE Standard 51Laboratory Method of Testing Fans for Rating and AMCA 300 Reverberant Room Method for sound Testing of Fans. (FC & BC 315 and above).

HVAC Specification

15854-24

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

The characteristics of each fan's performance shall include curve relationships of volume, pressure, efficiency and power absorbed at constant speed. The Contractor shall provide for approval with performance certificates showing the induct sound power level in the seven octave bands as specified above for each fan before placing his order with the manufacturer. 1.3.13 Test Holes

A. Tapped holes for testing purposes and for permanent instrumentation shall be provided as indicated on the drawings and Schedule. Suitably sized holes shall be formed in the inner and outer panel skins and steel hank bushes welded onto the inner faces. B. Recesses hexagon brass plugs, threaded 15 mm. male shall be supplied and fitted into the female thread of the instrument ferrule. C. The panel insulation shall be suitably cut to give a clear way for the instrument ferrule. 1.3.14 Drain Pans

A 50 mm. deep drain pan complete with trap and clean out plug shall be fitted below all cooling coils , humidifiers and recovery coils as a continuous unit . The drain shall be constructed of ( 1.00 mm ) thick stainless steel SS 304. The drain outlet shall be fitted with deep trap for extension via a tundish to the nearest floor drain gully. 1.3.15 Manometers

Manometers shall be installed across each and every filter, cooler battery, etc., to indicate the differential pressure. These shall be the inclined type with scale calibrated 0 to 50 millibars in millibars divisions. The gauge fluid shall have a zero adjustment facility and a spirit level incorporate in the casing. 1.3.16 Dehumidifier Section

The Dehumidifier section shall include f-Regeneration Filtration g- Desiccant Rotor h- Reactivation Section i- Steam coils j- Regeneration Fans C- Regeneration Filtration The Regeneration filtration section shall be containing Bag Filters and HEPA filters. Final HEPA Filters shall be H13 according to EN 1822 efficiency. All filters should be supplied magnehelic gauges D- Desiccant Rotor The rotor shall be washable in industrial alcohol.

HVAC Specification

15854-25

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

The desiccant rotor is the moisture absorbing part of the dehumidifier and consists of a special composite matrix of heat resistant material which houses the silica gel or Lithium Chloride desiccant. Adsorbents shall be synthesized silica gel and metal silicates. The adsorbents shall be bounded to a base of ceramic paper though a temperature process, assuring that all materials shall be strongly bounded to the rotor and no dust will leave the rotor. The rotor shall be contains no LiCI or any other absorbents. The rotor shall be fixing to stainless steel shaft. E- Desiccant Rotor Microprocessor - based direct digital control (BMS) which supervises the operation of the dehumidifier and provides display messages of system parameters and faults. Analogue signals or digital or through web access. Temperature and RH control using two sensors or more Weather proof control panel. Safety mechanical electronic thermostat. E- Reactivation Section Two steam coils

HVAC Specification

15854-26

Mechanical Specification

Dar Al-Dawa Company Non Betalactam Factory- Plant # 4 Nau'r Jordan

1.4

Air Cooled Split System Unit - Ducted Type 1.4.1 General

Casing construction shall be acoustically lined sheet steel finished externally with baked enamel and sufficiently stiffened to eliminate vibration. Readily removable panels shall be provided and internal equipment shall be laid out so that all internal equipment is easily accessible for maintenance or replacement. Access panel location shall be compatible with the plant layout to maintain adequate working clearances not less than those published in the manufacturers data. The refrigeration circuits shall include a liquid line filter drier and a thermostatic expansion valve or capillary tube. A condensate drain pan treated to resist corrosion and suitable to catch all condensate and any moisture carry over from the coil shall be provided. Fans shall be forward curve, double inlet, and centrifugal type. Motor design, marking, rating, performance and testing shall be in accordance with Relevant British Standards. Motors shall be designed to have a winding temperature rise to class B requirements and be provided with class F insulation. The unit shall be pre-wired to relevant British Standards complete with contactors, overloads and control circuit fuses and shall have a terminal including an earth connection for field wiring of both power and controls. Units shall incorporate thermal overloads for fan motors and compressors, manually reset high pressure cut outs, thermistors with lockout circuiting, low pressure controls with lock out provision, start to start timers (5-10 mins). The protection shall be arranged so that an alarm will shut down the affected compressor and trigger an alarm light on the unit but will permit the fan and any other compressors to continue to operate. Unit casing shall be insulated throughout including the condensate tray, with a minimum 13mm fiber glass with scrim finish, bonded to the casting. The air-cooled split unit shall be a single zone type with fan and coil capacities as indicated in the table of performance. 1.4.2 Room Thermostat

A wall-mounted sensor with recessed housing and over lapping cover plate shall control the ducted split indoor unit. The housing shall have conduit entry provision and shall be handed to the electrical Sub Contractor with instructions for fixing at the time that conduits are installed. Interconnecting cables shall terminate at a fixed terminal strip within the housing and all connections to the components mounted on the fascia. Facilities on the sensor shall include:

HVAC Specification

15854-27

Mechanical Specification

-fan high, medium and low speed selector. -ON/off /auto switch. -Temperature set point.

-Transformer from 240V to 24V.

NOTES
1 The design is based upon the equipment listed in the equipment.2 The tender pricing shall be based on any of the above listed acceptable manufacturers for each type. 3 The contractor must submit the base tender complying with the listed manufacturers equipment. An alternative offer from alternative manufacturers may be submitted in addition to the base tender, provided that full substantiating data of the equipment, and noting the non-compliant features of the alternative equipment together with the cost implications, is submitted 4 All alternative equipment offers may be accepted or rejected at the sole discretion of the Engineer as it shall be to the approval and final acceptance of the Engineer . 4 Submit the compliance form with the Tender indicating the proposed manufacturers for major equipment. Treat all equipment for which data submissions are required as major equipment for this purpose. Changes from the equipment offered at Tender will not normally be permitted unless the Engineer is satisfied that there is significant advantage in Principle.