Bill of Material
MILPO
All Net prices in US$
WIN Proposal #: 652-0733B
Alternative Bid Proposal/Quote Type:

Valued GE Customer,
We are pleased to offer this proposal for your review. Thank you for allowing GE Industrial Solutions - Electrical Distribution the
opportunity to participate on this project. Please do not hesitate to contact us with any questions.
_____
Item# Total Price Description Unit Price Qty Inches
___
1 Evolution Series MCC (GO100) 1
TAG 6151-201C
Linetype E9000
Modified NEMA I-A Wiring Class - MCC Express
UL TYPE 12 Enclosure
6" Bottom Mounted Wireway
MCC is Front Mounting Only
480 Volts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 600 AmpsRating 65000 AIC
Min. Vertical Bus 600 Amps
Miscellaneous
Enclosure and Bus (2 Vertical Sections)
2 Built to UL Type 12 standards
Enclosure Modifications
(2) Seismic Bracing Zone 4
(2) Low Voltage Wireway Barrier
Bus System
(2) 600 Amp CU Main Bus
(2) 300 Amp CU Ground Bus
(2) 600 Amp CU Front Vertical Bus
(2) Vertical Unit Ground Bus
(2) Vertical Unit Ground Lug
Bus Modifications
(2) 65000 AIC SC Bus Bracing
(2) Double Bolted Construction for Main Bus
Main device
1 SGL4T Type 400Amps Frame 250 Amps Trip Main C/B
With (1) #2/0 AWG-500 kcmil Cables Per Phase, TOP
Feed
42
Accessories
(3) Current Transf - <=600:5A
(1) LSIG
Sub Total : 42
Feeders
3 Feeder C/B SELT Type 150 Amps Frame 15 Amps Trip 18
3 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 18
1 Feeder C/B SELT Type 150 Amps Frame 100 Amps Trip 6
1 Feeder C/B SELT Type 100 Amps Frame 100 Amps Trip 12
Page: 1
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
.
Inches Description Qty Item#
.
Accessories
(1) Shunt trip
Sub Total : 54
Combination Starter Devices
1 Size 1 FVNR Starter 10 Hp 20 Amps Trip SEL C/B Disc. 18
Accessories
(1) CPT-150 VA
(1) Full-voltage indicating light -RUN-GREEN
(1) Full-voltage indicating light -STOP-RED
(1) Full-voltage indicating light -TRIP-AMBER
(4) Intlks + 1(No Charge)= 5 Total
(1) Shunt trip
(1) Solid state OL relay
(1) Standard 3pos selector switch
(1) Std reset pushbutton
(2) Std start/stop pushbutton
1 Size 2 FVNR Starter 25 Hp 50 Amps Trip SEL C/B Disc. 18
Accessories
(1) CPT-150 VA
(1) Full-voltage indicating light -RUN-GREEN
(1) Full-voltage indicating light -STOP-RED
(1) Full-voltage indicating light -TRIP-AMBER
(4) Intlks + 1(No Charge)= 5 Total
(1) Shunt trip
(1) Solid state OL relay
(1) Standard 3pos selector switch
(1) Std reset pushbutton
(2) Std start/stop pushbutton
Sub Total : 36
Miscellaneous
1 12" undrilled device mounting plate 12
1 12" Section of Future space available 12
Sub Total : 24
Units supplied with the following options
2 NONE control wire
2 Control wire terminals - NONE
6 High density control terminal board
10 MTW VW1 (STD) power type
10 Stripped Wire (STD) power wire terminal
Wiring Class
1 Wiring Class : Express
Order Information
(3) Standard Instruction Books
(3) Standard Catalog Renewal Parts Books
(3) 8 1/2 by 11 Print Customer Prints
7,590.32 7,590.32 Item Sell Price:
1 Evolution Series MCC (GO100) 2
Page: 2
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
.
Inches Description Qty Item#
.
TAG 6150-215
Linetype E9000
Modified NEMA I-A Wiring Class - MCC Express
UL TYPE 12 Enclosure
6" Bottom Mounted Wireway
MCC is Front Mounting Only
480 Volts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 1200 AmpsRating 65000 AIC
Min. Vertical Bus 600 Amps
Miscellaneous
Enclosure and Bus (1 Vertical Sections)
1 Built to UL Type 12 standards
Enclosure Modifications
(1) Seismic Bracing Zone 4
(1) Low Voltage Wireway Barrier
Bus System
(1) 1200 Amp CU Main Bus
(1) 300 Amp CU Ground Bus
(1) 600 Amp CU Front Vertical Bus
(1) Vertical Unit Ground Bus
(1) Vertical Unit Ground Lug
Bus Modifications
(1) 65000 AIC SC Bus Bracing
(1) Double Bolted Construction for Main Bus
Main device
1 SKL12T Type 1200Amps Frame 1200 Amps Trip Main
C/B With (3) 300-750 kcmil Cables Per Phase, BOTTOM
Feed
42
Accessories
(3) Current Transf - 1200:5A
(1) LI Trip Unit
Sub Total : 42
Feeders
2 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 12
Sub Total : 12
Miscellaneous
1 12" undrilled device mounting plate 12
1 12" Section of Future space available 12
Sub Total : 24
Units supplied with the following options
2 MTW VW1 (STD) power type
2 Stripped Wire (STD) power wire terminal
Wiring Class
1 Wiring Class : Express
Order Information
(3) Standard Instruction Books
(3) Standard Catalog Renewal Parts Books
(3) 8 1/2 by 11 Print Customer Prints
4,358.49 4,358.49 Item Sell Price:
Page: 3
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
.
Inches Description Qty Item#
.
1 Evolution Series MCC (GO100) 3
TAG 6150-293
Linetype E9000
Modified NEMA I-A Wiring Class - MCC Express
UL TYPE 12 Enclosure
6" Bottom Mounted Wireway
MCC is Front Mounting Only
480 Volts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 1200 AmpsRating 65000 AIC
Min. Vertical Bus 600 Amps
Miscellaneous
Enclosure and Bus (1 Vertical Sections)
1 Built to UL Type 12 standards
Enclosure Modifications
(1) Seismic Bracing Zone 4
(1) Low Voltage Wireway Barrier
Bus System
(1) 1200 Amp CU Main Bus
(1) 300 Amp CU Ground Bus
(1) 600 Amp CU Front Vertical Bus
(1) Vertical Unit Ground Bus
(1) Vertical Unit Ground Lug
Bus Modifications
(1) 65000 AIC SC Bus Bracing
(1) Double Bolted Construction for Main Bus
Incoming Power
1 1200Amp Terminal Board With (3) #2 AWG-600 kcmil
Lugs Per Phase, BOTTOM Feed Cu/Al Lug
30
Accessories
(3) Current Transf - 1200:5A
Sub Total : 30
Feeders
2 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 12
Sub Total : 12
Miscellaneous
1 12" undrilled device mounting plate 12
2 12" Section of Future space available 24
Sub Total : 36
Units supplied with the following options
2 MTW VW1 (STD) power type
2 Stripped Wire (STD) power wire terminal
Wiring Class
1 Wiring Class : Express
Order Information
(3) Standard Instruction Books
(3) Standard Catalog Renewal Parts Books
(3) 8 1/2 by 11 Print Customer Prints
3,713.86 3,713.86 Item Sell Price:
1 Evolution Series MCC (GO100) 4
Page: 4
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
.
Inches Description Qty Item#
.
TAG 6151-201B
Linetype E9000
Modified NEMA I-A Wiring Class - MCC Express
UL TYPE 12 Enclosure
6" Bottom Mounted Wireway
MCC is Front Mounting Only
480 Volts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 600 AmpsRating 65000 AIC
Min. Vertical Bus 600 Amps
Miscellaneous
Enclosure and Bus (2 Vertical Sections)
2 Built to UL Type 12 standards
Enclosure Modifications
(2) Seismic Bracing Zone 4
(2) Low Voltage Wireway Barrier
Bus System
(2) 600 Amp CU Main Bus
(2) 300 Amp CU Ground Bus
(2) 600 Amp CU Front Vertical Bus
(2) Vertical Unit Ground Bus
(2) Vertical Unit Ground Lug
Bus Modifications
(2) 65000 AIC SC Bus Bracing
(2) Double Bolted Construction for Main Bus
Main device
1 SGL4T Type 400Amps Frame 250 Amps Trip Main C/B
With (1) #2/0 AWG-500 kcmil Cables Per Phase, TOP
Feed
42
Accessories
(3) Current Transf - <=600:5A
(1) LSIG
Sub Total : 42
Feeders
3 Feeder C/B SELT Type 150 Amps Frame 15 Amps Trip 18
3 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 18
1 Feeder C/B SELT Type 150 Amps Frame 100 Amps Trip 6
1 Feeder C/B SELT Type 100 Amps Frame 100 Amps Trip 12
Accessories
(1) Shunt trip
Sub Total : 54
Combination Starter Devices
1 Size 1 FVNR Starter 10 Hp 20 Amps Trip SEL C/B Disc. 18
Accessories
(1) CPT-150 VA
(1) Full-voltage indicating light -RUN-GREEN
(1) Full-voltage indicating light -STOP-RED
(1) Full-voltage indicating light -TRIP-AMBER
(4) Intlks + 1(No Charge)= 5 Total
(1) Shunt trip
(1) Solid state OL relay
(1) Standard 3pos selector switch
Page: 5
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
.
Inches Description Qty Item#
.
(1) Std reset pushbutton
(2) Std start/stop pushbutton
1 Size 2 FVNR Starter 25 Hp 50 Amps Trip SEL C/B Disc. 18
Accessories
(1) CPT-150 VA
(1) Full-voltage indicating light -RUN-GREEN
(1) Full-voltage indicating light -STOP-RED
(1) Full-voltage indicating light -TRIP-AMBER
(4) Intlks + 1(No Charge)= 5 Total
(1) Shunt trip
(1) Solid state OL relay
(1) Standard 3pos selector switch
(1) Std reset pushbutton
(2) Std start/stop pushbutton
Sub Total : 36
Miscellaneous
1 12" undrilled device mounting plate 12
1 12" Section of Future space available 12
Sub Total : 24
Units supplied with the following options
2 NONE control wire
2 Control wire terminals - NONE
6 High density control terminal board
10 MTW VW1 (STD) power type
10 Stripped Wire (STD) power wire terminal
Wiring Class
1 Wiring Class : Express
Order Information
(3) Standard Instruction Books
(3) Standard Catalog Renewal Parts Books
(3) 8 1/2 by 11 Print Customer Prints
7,590.32 7,590.32 Item Sell Price:
Total Lot Price $__________ Price to follow
Page: 6
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
FACTORY TESTS:
WARRANTY:
1. Sales to Authorized GE Distributor: 12 months from GE ship date, or for shipments from Distributors stock 12 months
from Distributor ship date, but not exceeding 18 months from shipment by GE. Sales to Direct-Served Accounts: See Form
ES104 (Rev. 4) for warranty terms.
2. Additional 12 months available for 2% adder, 24 months for 4% adder.
3. Warranty covers Equipment only, to be repaired or replaced at Manufacturers discretion. Contact GE Post Sales Service for
warranty assistance at (888) GE RESOLVE
Limited Warranty for all Core/Standard and Stand-Alone Drive Panels (excluding DV300 DC Drives and 18 Pulse
Panel products): 36 months from date of shipment. An additional 12 months (a total of 48 months) are available for 10% Net
Price adder, or an additional 24 months (the maximum of 60 months) for 20% Net Price adder. Contact GE 1 Stop when order
is placed to include extended warranty on item(s). DV300 DC Drives have a warranty period of 18 months after shipment only
18 Pulse Drive panels have a warranty of 12 months after shipment.
For GE Zenith Controls and Power Quality product limited warranty, please refer to GETCPQ, which can be found at
http://www.gedigitalenergy.com/PowerQuality/GETCPQ.pdf.
Post Sales Service for GE Zenith Products (Automatic Transfer Switches and UPS products)
Contact GE Post Sales Service at 800 637 1738 Select Option 3.
TERMS OF PAYMENT:
1.
3.
4.
5.
Sales to Authorized GE Distributor: This quotation is offered subject to the Apparatus Distributor Agreement between
This quotation expires in 30 calendar days unless terminated sooner by notice.
ORDER CANCELLATION - SCHEDULE OF CHARGES:
POLICIES AND CONDITIONS OF SALE:
specifically noted herein and GE Zenith Controls/Power Quality products shown on GETCPQ, which can be found at
http://www.gedigitalenergy.com/PowerQuality/GETCPQ.pdf.
GE and Distributor. Sales to Direct-Served Accounts: See Form ES104 (Rev. 4), except as
Standard factory test procedures will be performed. Field testing, customer inspections, customer witness tests and any other
non-standard test procedures are not included unless specifically noted herein.
All projects are:
10% - Order received and entered on factory, work not started, material not ordered.
30% - Drawings for approval submitted.
60% - Approved drawings returned. Job released for manufacture and shipment.
80% - Material accumulated and production started.
100% - Manufacturing completed.
Price(s) quoted are for estimated lead-times givenexpedited schedule may require additional charges.
Order must be released for manufacture within 90 days. If drawings are required they must be returned approved for
release within 60 days of mailing. If not, and/or shipment is delayed for any reason, the price will increase 1.5% for each
partial/full month that shipment is delayed after the 90-day period.
Net 30 days
Price Clause 1Q
For projects up to $250,000 terms of payment are 100% net 30 days from invoice date.

If project value exceeds $250,000 net, progress payments are required payable at the following milestones:
-20% upon delivery of drawings -30% upon release of equipment -Balance due upon shipment
DELIVERY AND TRANSPORTATION:
2. To the extent the Buy American Act, Trade Agreements Act, or other domestic preference requirements are applicable to
this Contract, the country of origin of Products is unknown unless otherwise specifically stated by Seller in this Contract.
The customer (distributor or direct-served customer, as applicable) warrants that there are no governmental contracting
requirements or regulations that apply to this transaction (including without limitation any Federal Acquisition
Regulations), other than such terms as have been disclosed to Seller and agreed to by Seller in writing prior to Seller
agreeing to this transaction.
Page: 7
Date: 02/13/2012 Name: MILPO
Prop: 652-0733B
1.
2.
3.
4.
5.
Unless otherwise noted in this quotation, normal transportation and handling, is allowed on orders of $1000 net or more
to common-carrier point nearest destination within the Continental US (excluding Alaska and Hawaii). Freight and
handling will be prepaid and billed on orders less than $1000 net.
Special Instruction - The Receiving Associate is required to sign, date and note specific visible or concealed damage on
Bill of Lading at time of delivery. Freight Company Associate is required to witness Receiver's signature, date and
damage claim annotations. GE's Post Sales Service Department must be provided with copy of annotated BOL within
five (5) days of delivery or Shipper's responsibility ends.
Exception-GE Zenith ATS and UPS are not shipped freight allowed. Freight charges will be included on Invoice (3.0% of
sale for ATS LTL carrier shipments with minimum $70.00 shipping charge on all ATS products).
6.
GE will assume the risk of loss or damage to the destination for a 2% adder (but not less than $500 net) applied to the
total price of the equipment. "Destination" is defined as GE's common carrier's delivery point nearest first destination or
point of export within the continental U.S.
EXW GEs facility, place of manufacture or warehouse (Incoterms 2000). Title passes upon shipment.
Shipment via Air or Open -Top/Flatbed/Lift gate truck not included unless specifically listed herein.
The lead-times quoted are for Estimating Purposes Only. Actual drawing and shipping schedules will be based on factory
load, receipt of order with complete technical information, and the date GE receives authorized release to manufacture.
The accompanying Bill of Material is our interpretation of what is required to meet the intent of the listed Drawings and
Specifications. Please review thoroughly for accuracy and completeness, and advise immediately if any revisions are required.
This proposal is limited to the attached Bill of Material only. Start-up Services and Training are not included unless specifically
noted herein. Changes to scope will require a revised proposal.
The devices listed on this bill of material may have selective coordination over the long time, short time and instantaneous
range. GE's selective capabilities are listed in publication DET-537. It is recommended that a qualified engineer be employed to
determine selective coordination as required for the project and in accordance with applicable local codes and acceptable
engineering practices. Selective coordination may require significant changes to the system design, equipment sizing and cost.
MANUFACTURAS ELECTRICAS S.A.
Page: 8
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 600 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 1 Pg: 1
TAG 6151-201C
Date : 02-13-2012
Plan View - Top
A = 3.31"
AA AB
B=
C=
F=
17.63"
5.12"
5.12"
17.63"
5.12"
5.12"
D = 3.13" , E = 1.25"
B - width of top removable cover plate.
C,F - depths of top removable cover plates.
Note:
For UL TYPE 12 Enclosures with Powerbreak & HPC
switch devices rated 800/1000/1200/1600 or 2000A, allow
minimum 5 space in front of door for hinged cover
Elevation - Front View
Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note :
1. Drawings not to be used for installation.
Refer to factory for actual drawings.
2. Add 1.5"height for Channel Sill.
3. Top Mounted 4.4" high Fans required for 2500 Amp.
Bus and >= 40HP VFDs
4. Filler, if shown allows door swing
when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area
10.66" - Vert wiring trough Depth
AA AB
A=
C=
D=
4.63"
14.19"
6.8"
4.63"
14.19"
6.8"
A - width of vertical wiring trough
C - width\depth of Conduit Entrance
D- depth is Ground only , no neutral
or space heater.
E = 3.13" , H = 1.25"
B
C
A
D
E
AA
600 amps
Grnd & BUS
C D
E
H
AA
20"X20"
AAG
MAINCB
AAI
MTG
AAK
SPACE
AAN
FVNR
Size:1
AB
600 amps
Grnd & BUS
AB
20"X20"
ABE
FVNR
Size:2
ABF FDRCB
ABG FDRCB
ABH FDRCB
ABI FDRCB
ABJ FDRCB
ABK FDRCB
ABL FDRCB
ABN
FDRCB
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 600 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 1 Pg: 2
TAG 6151-201C
Date : 02-13-2012
Unit
Loc
Cust
Unit#
Circuit Name Function Size
HP, KW,
KVA
KVAR
CB Or
FSW
Trip
Fuse
Clip
FLA SF RPM Ht PB Sw IL
Cont.
Rly
Prot/
Mtrg
Total
Intlk
NO
Total
Intlk
NC
AAG BLANK NP MAINCB SGL(T) 250 42 X
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAI BLANK NP MTG 12
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAK BLANK NP SPACE 12
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAN BLANK NP FVNR 1
10HP SEL(M) 20 11.9 1.25 1800 18 2 1 3 3 2
Push Button: 1 START/STOP, 1 RESET Selector Switch : 1 H-O-A
Indicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABE BLANK NP FVNR 2
25HP SEL(M) 50 28 1.15 1800 18 2 1 3 3 2
Push Button: 1 RESET, 1 START/STOP Selector Switch : 1 H-O-A
Indicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABF BLANK NP FDRCB SEL(T) 100 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABG BLANK NP FDRCB SEL(T) 50 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABH BLANK NP FDRCB SEL(T) 50 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABI BLANK NP FDRCB SEL(T) 50 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABJ BLANK NP FDRCB SEL(T) 15 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABK BLANK NP FDRCB SEL(T) 15 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABL BLANK NP FDRCB SEL(T) 15 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABN BLANK NP FDRCB SEL(T) 100 12
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 1200 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 2 Pg: 1
TAG 6150-215
Date : 02-13-2012
Plan View - Top
A = 3.31"
AA
B=
C=
F=
17.63"
5.12"
5.12"
D = 3.13" , E = 1.25"
B - width of top removable cover plate.
C,F - depths of top removable cover plates.
Note:
For UL TYPE 12 Enclosures with Powerbreak & HPC
switch devices rated 800/1000/1200/1600 or 2000A, allow
minimum 5 space in front of door for hinged cover
Elevation - Front View
Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note :
1. Drawings not to be used for installation.
Refer to factory for actual drawings.
2. Add 1.5"height for Channel Sill.
3. Top Mounted 4.4" high Fans required for 2500 Amp.
Bus and >= 40HP VFDs
4. Filler, if shown allows door swing
when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area
10.66" - Vert wiring trough Depth
AA
A=
C=
D=
4.63"
14.19"
6.8"
A - width of vertical wiring trough
C - width\depth of Conduit Entrance
D- depth is Ground only , no neutral
or space heater.
E = 3.13" , H = 1.25"
B
C
A
D
E
AA
600 amps
Grnd & BUS
C D
E
H
AA
20"X20"
AAD
SPACE
AAF
MTG
AAG FDRCB
AAH FDRCB
AAO
MAINCB
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 1200 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 2 Pg: 2
TAG 6150-215
Date : 02-13-2012
Unit
Loc
Cust
Unit#
Circuit Name Function Size
HP, KW,
KVA
KVAR
CB Or
FSW
Trip
Fuse
Clip
FLA SF RPM Ht PB Sw IL
Cont.
Rly
Prot/
Mtrg
Total
Intlk
NO
Total
Intlk
NC
AAD BLANK NP SPACE 12
AAF BLANK NP MTG 12
AAG BLANK NP FDRCB SEL(T) 50 6
AAH BLANK NP FDRCB SEL(T) 50 6
AAO BLANK NP MAINCB SKL(T) 1200 42 X
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 1200 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 3 Pg: 1
TAG 6150-293
Date : 02-13-2012
Plan View - Top
A = 3.31"
AA
B=
C=
F=
17.63"
5.12"
5.12"
D = 3.13" , E = 1.25"
B - width of top removable cover plate.
C,F - depths of top removable cover plates.
Note:
For UL TYPE 12 Enclosures with Powerbreak & HPC
switch devices rated 800/1000/1200/1600 or 2000A, allow
minimum 5 space in front of door for hinged cover
Elevation - Front View
Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note :
1. Drawings not to be used for installation.
Refer to factory for actual drawings.
2. Add 1.5"height for Channel Sill.
3. Top Mounted 4.4" high Fans required for 2500 Amp.
Bus and >= 40HP VFDs
4. Filler, if shown allows door swing
when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area
10.66" - Vert wiring trough Depth
AA
A=
C=
D=
4.63"
14.19"
6.8"
A - width of vertical wiring trough
C - width\depth of Conduit Entrance
D- depth is Ground only , no neutral
or space heater.
E = 3.13" , H = 1.25"
B
C
A
D
E
AA
600 amps
Grnd & BUS
C D
E
H
AA
20"X20"
AAD
SPACE
AAF
SPACE
AAH
MTG
AAI FDRCB
AAJ FDRCB
AAO
INCLINE
Amps:1200
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 1200 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 3 Pg: 2
TAG 6150-293
Date : 02-13-2012
Unit
Loc
Cust
Unit#
Circuit Name Function Size
HP, KW,
KVA
KVAR
CB Or
FSW
Trip
Fuse
Clip
FLA SF RPM Ht PB Sw IL
Cont.
Rly
Prot/
Mtrg
Total
Intlk
NO
Total
Intlk
NC
AAD BLANK NP SPACE 12
AAF BLANK NP SPACE 12
AAH BLANK NP MTG 12
AAI BLANK NP FDRCB SEL(T) 50 6
AAJ BLANK NP FDRCB SEL(T) 50 6
AAO BLANK NP INCLINE 30 X
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 600 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 4 Pg: 1
TAG 6151-201B
Date : 02-13-2012
Plan View - Top
A = 3.31"
AA AB
B=
C=
F=
17.63"
5.12"
5.12"
17.63"
5.12"
5.12"
D = 3.13" , E = 1.25"
B - width of top removable cover plate.
C,F - depths of top removable cover plates.
Note:
For UL TYPE 12 Enclosures with Powerbreak & HPC
switch devices rated 800/1000/1200/1600 or 2000A, allow
minimum 5 space in front of door for hinged cover
Elevation - Front View
Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note :
1. Drawings not to be used for installation.
Refer to factory for actual drawings.
2. Add 1.5"height for Channel Sill.
3. Top Mounted 4.4" high Fans required for 2500 Amp.
Bus and >= 40HP VFDs
4. Filler, if shown allows door swing
when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area
10.66" - Vert wiring trough Depth
AA AB
A=
C=
D=
4.63"
14.19"
6.8"
4.63"
14.19"
6.8"
A - width of vertical wiring trough
C - width\depth of Conduit Entrance
D- depth is Ground only , no neutral
or space heater.
E = 3.13" , H = 1.25"
B
C
A
D
E
AA
600 amps
Grnd & BUS
C D
E
H
AA
20"X20"
AAG
MAINCB
AAI
MTG
AAK
SPACE
AAN
FVNR
Size:1
AB
600 amps
Grnd & BUS
AB
20"X20"
ABE
FVNR
Size:2
ABF FDRCB
ABG FDRCB
ABH FDRCB
ABI FDRCB
ABJ FDRCB
ABK FDRCB
ABL FDRCB
ABN
FDRCB
GE Motor Control Centers
Proposal Nbr : 652-0733B Job: MILPO
Requisition Nbr : Linetype E9000; Modified NEMA I-A Wiring CIass - MCC Express;
Section ht 90" UL TYPE 12 EncIosure; 6" Bottom Mounted Wireway
MCC is Front Mounting OnIy; 480 VoIts 3 Phase 3 Wire 60 Hz
Main Horz. Bus 600 Amps; Rating 65000 AIC; Min. VerticaI Bus 600 Amps
Item No 4 Pg: 2
TAG 6151-201B
Date : 02-13-2012
Unit
Loc
Cust
Unit#
Circuit Name Function Size
HP, KW,
KVA
KVAR
CB Or
FSW
Trip
Fuse
Clip
FLA SF RPM Ht PB Sw IL
Cont.
Rly
Prot/
Mtrg
Total
Intlk
NO
Total
Intlk
NC
AAG BLANK NP MAINCB SGL(T) 250 42 X
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAI BLANK NP MTG 12
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAK BLANK NP SPACE 12
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAN BLANK NP FVNR 1
10HP SEL(M) 20 11.9 1.25 1800 18 2 1 3 3 2
Push Button: 1 START/STOP, 1 RESET Selector Switch : 1 H-O-A
Indicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABE BLANK NP FVNR 2
25HP SEL(M) 50 28 1.15 1800 18 2 1 3 3 2
Push Button: 1 RESET, 1 START/STOP Selector Switch : 1 H-O-A
Indicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABF BLANK NP FDRCB SEL(T) 100 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABG BLANK NP FDRCB SEL(T) 50 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABH BLANK NP FDRCB SEL(T) 50 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABI BLANK NP FDRCB SEL(T) 50 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABJ BLANK NP FDRCB SEL(T) 15 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABK BLANK NP FDRCB SEL(T) 15 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABL BLANK NP FDRCB SEL(T) 15 6
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABN BLANK NP FDRCB SEL(T) 100 12
Legend :
Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit
Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry