Sie sind auf Seite 1von 2

1/4

I DT LD: Offer:

Customer: Project: Offer-no.: Date: BEC project 376202 Feb 03 2012

Technical and ordering data are subject to change. There may be discrepancies between calculated and rating plate values.

Version: 2010.02.18 generiert / generated Fri Feb 03 12:26:07 CET

Datasheet for three-phase Squirrel-Cage-Motors / Squirrel cage


null Ordering data:
Client-order-no.: Order-no.: Offer-no.: Remarks:

1LA43506AN70
A42+A65+C20+D12+G50+K09+L55+M13+M52 Item-no.: Consignment-no.: Project: 31559 BEC project

Electrical data: Ratings:


Rated motor power P
N

Mechanical data:
Starting-/rated motor current I /I
A N

5,30
K N

250 kW 6.6 kV 10 % (IEC 60034-1) 50 Hz 2 989 1/min 6


N

Breakdown-/rated motor torque M /M Starting-/rated motor torque M /M


A N

2,30 1,10 11 kg*m

Rated motor voltage U D/Y Voltage fluctuations Frequency f Frequency fluctuations Rated motor speed n Number of poles Rated motor torque M Rated motor current I Partial load P/P Efficiency %
N N

Moment of inertia J

mot

Ext. moment of inertia (max.) J

fremd

Perm. no. of consecutive starts, cold/warm Service factor Stator circuit Rotor winding material Dyn. foundation load, downward/upward Dynamic foundation load

3/ 2 Star / Al 50 kN / 26 kN

2414 Nm 28 A

5/4 94,2 % 0,83


r

4/4 94,7 % 0,82

3/4 94,9 % 0,79

2/4 94,5 %

Bearing design Bearing cooling D.E./N.D.E bearing design Oil content, D.E./N.D.E. bearing

Rolling-contact bearing

6224 C3 / 6220 C3

Power factor cos Locked-rotor voltage U Rated rotor current I Rotor winding Brush lifting device
r

0,71

Oil throughput, D.E./N.D.E. bearing Direction of rotation 1m-sound pressure level L (Tol.+3dB(A))
pA

Both directions of rotation 71 dB(A) 16 dB Standard coating RAL 7030 2400 kg Acc. to IEC/EN/ISO 0.0

Bar winding

Measuring surface level L Coating Colour Total weight Standards / specifications Total weight

General data:
Type of ex-protection Rate of purging compressed-air flow Temp. rise time const. t for thermal cl. T1/T2/T3 Degree of protection
e

without 500 - / - / IP55

Special configurations and tests:


A42 A65 2 double resistance thermometers Pt 100 for 4-wire connection from terminals, rollingcontact bearing / 2 Doppel-Widerstandsthermometer PT100 fr 4-Leiterschaltung ab Klemmenkasten bei Wlzlagern 6 embedded resistance thermometers Pt 100 without lightning arresters for 3- or 4-wire connection from terminals / 6 Nut-Widerstandsthermometer PT100, ohne berspannungsschutz, fr 3- und 4-Leiterschaltung ab Klemmenkasten Special winding / Anormale Wicklung Cooling air temperature 50 C / Khllufttemperatur 50 C Shock pulse measurement (SPM), measuring nipple at D.E. and N.D.E. / Stoimpulsmessung (SPM), Menippel auf AS und BS Terminal box on right-hand side, view from D.E. / Klemmenkasten seitlich, rechts von AS gesehen Neutral-point terminal box 6kV, 3 terminals / Sternpunkt-Klemmenkasten 6kV, 3 Klemmen Anti-condensation heater 220-240 V (min 200 V, max. 264V) / StillstandsheizungsBemessungsspannungsbereich 220 - 240V (min. 200V, max. 264V) Separate auxiliary terminal box for anti-condensation heating / Separater Hilfsklemmenkasten fr die Stillstandsheizung

Slipring degree of protection Type of construction Type of operating


IM B3 IC 411

C20 D12 G50 K09 L55

Site conditions:
Coolant temperature K Cooling requirement Altitude above sea level Thermal class / utilisation Stator thermal class Rotor thermal class
1000 m 155(F) utilized acc. to thermal class 130(B)
T

50 C

M13 M52

Technical and ordering data are subject to change. There may be discrepancies between calculated and rating plate values.

2/4

Version: 2010.08.16 generiert / generated Fri Feb 03 12:26:07 CET

Das könnte Ihnen auch gefallen