ALTV248UL Series

CCTV Power Supplies Installation Guide


Models Include:

ALTV248UL
- 24VAC @ 3.5 amp (85VA) or 28VAC @ 3 amp (85VA). - Eight (8) Fuse Protected Outputs.

ALTV248ULCB
- 24VAC @ 3.5 amp (85VA) or 28VAC @ 3 amp (85VA). - Eight (8) PTC Protected Outputs.

ALTV248175UL
- 24VAC @ 7 amp (175VA) or 28VAC @ 6.25 amp (175VA). - Eight (8) Fuse Protected Outputs.

ALTV248175ULCB
- 24VAC @ 7 amp (175VA) or 28VAC @ 6.25 amp (175VA). - Eight (8) PTC Protected Outputs.

ALTV248300UL
- 24VAC @ 12.5 amp (300VA) or 28VAC @ 10 amp (280VA). - Eight (8) Fuse Protected Outputs.

ALTV248300ULCB
- 24VAC @ 12.5 amp (300VA) or 28VAC @ 10 amp (280VA). - Eight (8) PTC Protected Outputs.

ALTV248300ULM
- 24VAC @ 12.5 amp (300VA) or 28VAC @ 10 amp (280VA). - Eight (8) Fuse Protected Outputs.

ALTV248300ULCBM
- 24VAC @ 12.5 amp (300VA) or 28VAC @ 10 amp (280VA). - Eight (8) PTC Protected Outputs.

ALTV248600UL
- 24VAC @ 25 amp (600VA) or 28VAC @ 20 amp (560VA). - Eight (8) Fuse Protected Outputs.

ALTV248600ULCB
- 24VAC @ 25 amp (600VA) or 28VAC @ 20 amp (560VA) - Eight (8) PTC Protected Outputs.
Rev. 040506X

Overview:
These Altronix CCTV Power Supplies provide 24VAC or 28VAC distributed via eight (8) fuse or PTC protected outputs for powering CCTV Cameras, heaters and other video accessories.

Eight (8) Output ALTV248UL Reference Chart:


Cu rre Nu nt m be ro PT f C po Pr Out w o p (C er l tect uts las im ed s it O Fu 3 fo ed f utp se r W or uts Pr et Dry (Cl ot lo l a ec In ted cati ocat ss 2 div on io Cl s) ns no idu as t t al s 1 . ). Fu o ex Out Ou ce pu se tp ut Ra ed t C s tin tot urr M gs al en ain ou t ( tpu ma Fu tc xp se ur er Ra ren o tin Pr t) utp gs im ut Fu ary se In Ra -li tin ne 11 gs 5V In AC pu 5 Ag t Cu 0/60 r H e Li ncy rent z sti ng s

Altronix Model Number ALTV248UL ALTV248ULCB ALTV248175UL ALTV248175ULCB ALTV248300UL ALTV248300ULCB ALTV248300ULM ALTV248300ULCBM ALTV248600UL ALTV248600ULCB

24VAC 3.5 amp 28VAC 28VAC 24VAC 24VAC 3 amp 3 amp 7 amp 8 8 8 8 8 8 8 8 -Yes -7 amp Yes -8 8 -Yes -Yes -Yes 24VAC 3.5 amp

To ta (P l Ou ow tp er) ut

Ou tp ut

Vo lta ge

3.5 amp 2.5 amp 3.5 amp 3.5 amp 3.5 amp 2.5 amp 3.5 amp 2.5 amp 3.5 amp 2.5 amp

3.5 amp --

5 amp/ 3.5 amp/ 250V 250V 5 amp/ 3.5 amp/ 250V 250V ---------

.9 amp .9 amp 1.73 amp 1.73 amp 2.7 amp 2.7 amp 2.7 amp 2.7 amp 5.4 amp 5.4 amp

28VAC 6.25 amp 28VAC 6.25 amp 24VAC 12.5 amp 28VAC 10 amp 24VAC 12.5 amp 28VAC 10 amp 24VAC 12.5 amp 28VAC 10 amp 24VAC 12.5 amp 28VAC 10 amp 24VAC 25 amp 28VAC 20 amp 24VAC 25 amp 28VAC 20 amp

3.5 10 amp/ amp 250V -10 amp/ 250V

Yes --

3.5 15 amp/ amp 32V -15 amp/ 32V

Yes --

Yes --

3.5 15 amp/ amp 32V -15 amp/ 32V

Yes --

Yes --

3.5 15 amp/ amp 32V -15 amp/ 32V

Yes

-2-

Specifications: UL Listed for Commercial CCTV Equipment (UL 2044). Enclosure Dimensions:
CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment. Surge suppression. AC power LED indicator. Power ON/OFF switch (ALTV248UL, ALTV248ULCB). Illuminated power disconnect circuit breaker with manual reset (all other models). Unit maintains camera synchronization. Ease of installation saves time & eliminates costly labor. Spare fuses included (on fuse protected models). ALTV248UL, ALTV248ULCB, ALTV248300ULM, and ALTV248300ULCBM: 8.5"H x 7.5"W x 3.5"D ALTV248175UL, ALTV248175ULCB, ALTV248300UL and ALTV248300ULCB: 12"H x 7.75"W x 4.5"D ALTV248600UL and ALTV248600ULCB: 13"H x 13.5"W x 3.5"D

Installation Instructions:
1. Mount unit in desired location. 2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL or ALTV248ULCB (Figs. 1, 2, pg. 5). Set power disconnect circuit breaker to OFF position for all other models (Figs. 3A-10A, pgs. 6-10). 3. All units are factory set for 24VAC operation. For 28VAC operation adjust unit prior to mounting and applying power as follows: Change the wire position so that the wire marked [28V] is connected to the terminal marked [P] and the wire marked [24V] is connected to the terminal marked [S]. Note: ALTV248ULCB set for 28VAC operation is not Class 2 Rated, not power limited. 4. Connect AC power to the black and white flying leads of the transformer(s) (Figs. 1-10, pgs. 5-10), secure green lead to earth ground. Use 18 AWG or larger for all power connections. Keep power limited (PTC protected outputs only) wiring separate from non-power limited wiring. Minimum .25 spacing must be provided. Use separate knockouts. 5. Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL or ALTV248ULCB (Figs. 1, 2, pg. 5). Set power disconnect circuit breaker to RESET (ON) position for all other models (Figs. 3A-10A, pgs. 6-10). 6. Measure output voltage before connecting devices. This helps avoid potential damage. Terminals marked [1P - 8P] are of the same polarity. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage. 7. Set power switch on power distribution board marked [PD] to OFF position for models ALTV248UL or ALTV248ULCB (Figs. 1, 2, pg. 5). Set power disconnect circuit breaker to OFF position for all other models (Figs. 3A-10A, pgs. 6-10). 8. Connect devices to terminals marked [1P - 1N through 4P - 4N] on PD4/PD4CB board (Figs. 9, 10, pgs. 9, 10) or terminals marked [1P - 1N through 8P - 8N] on PD8/PD8CB board (Figs. 1-8, pgs. 5-8), carefully observing polarity. 9. Set power switch on power distribution board marked [PD] to ON position for models ALTV248UL or ALTV248ULCB (Figs. 1, 2, pg. 5). Set power disconnect circuit breaker to RESET (ON) position for all other models (Figs. 3A-10A, pgs. 6-10) 10. Green LED will illuminate when power is present. 11. Upon completion of wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional. Caution: Equipment to be installed/serviced by authorized/trained personnel only. Shut branch circuit power before installing/servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to all local codes and in accordance with the National Electrical Code. Use 75 C or higher rated UL insulated wiring for connecting the unit to the mains. Replace fuses with the same type and rating (refer to Eight (8) Output ALTV248UL Reference Chart, pg. 2)

-3-

Terminal Identification:
PD4 - Power Distribution Module 1P - 4P AC output. 1N - 4N AC output.

PD8 - Power Distribution Module 1P - 8P AC output. 1N - 8N AC output.

The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the products enclosure that may be of sufficient magnitude to constitute an electric shock. The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions - 3 -the literature accompanying the appliance. in CAUTION: To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.

-4-

Fig. 1 ALTV248UL
MAIN FUSE
24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 8P & N outputs 2 through 8)
FUSED POWER OUTPUTS COMMON POWER OUTPUTS N P S

Primary In-line Fuse

Class 1 Outputs

non-power limited non-power limited


Black Lead

ON

OFF

Black Lead

115VAC Input 50/60 Hz.

XFMR
White Lead

Green Lead (Ground)

Back Panel of Enclosure Fig. 2 ALTV248ULCB

F1

F2

F3

F4

F5

F6

F7

F8

MAIN FUSE
LED INPUT S

24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 8P & N outputs 2 through 8)

D1

FUSED

POWER

OUTPUTS

R1

N
COMMON POWER OUTPUTS N P

Primary In-line Fuse

24VAC configuration Class 2 Not Wet/Class 3 Wet 28VAC configuration Class 1

non-power limited non-power limited


Black Lead

ON

OFF

Black Lead

115VAC Input 50/60 Hz.

XFMR
White Lead

Green Lead (Ground)

Back Panel of Enclosure


-5-

Fig. 3 ALTV248175UL

MAIN FUSE

24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 8P & N outputs 2 through 8)

Fig. 3A

FUSED

POWER

OUTPUTS

COMMON

POWER

OUTPUTS

Class 1 Outputs

non-power limited

Illuminated Power Disconnect Circuit Breaker with manual reset

Black Lead

115VAC input 50/60 Hz


White Lead

XFMR
Green Lead (ground)

Fig. 4 ALTV248175ULCB

F1

F2

F3

F4

F5

F6

F7

F8

MAIN FUSE

Fig. 4A
24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 8P & N outputs 2 through 8)

P
D1

FUSED

POWER

OUTPUTS

R1

LED

N
COMMON POWER OUTPUTS N P S

INPUT

24VAC configuration Class 2 Not Wet/Class 3 Wet

non-power limited

Illuminated Power Disconnect Circuit Breaker with manual reset

Black Lead

115VAC input 50/60 Hz


White Lead

XFMR
Green Lead (ground)

-6-

Fig. 5 ALTV248300UL

24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 8P & N outputs 2 through 8)

P
D1

MAIN FUSE

FUSED

POWER

OUTPUTS

R1

LED

Fig. 5A
INPUT

N
COMMON POWER OUTPUTS

Class 1 Outputs

non-power limited

Illuminated Power Disconnect Circuit Breaker with manual reset

115VAC input 50/60 Hz

White Lead
XFMR*
Green Lead (ground)

Fig. 6 ALTV248300ULCB

24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 8P & N outputs 2 through 8)

Fig. 6A
non-power limited

24VAC configuration Class 2 Not Wet/Class 3 Wet

Illuminated Power Disconnect Circuit Breaker with manual reset

115VAC input 50/60 Hz

White Lead
XFMR*
Green Lead (ground)

-7-

Fig. 7 ALTV248300ULM

Fig. 7A

Illuminated Power Disconnect Circuit Breaker with manual reset

LED

INPUT
D1
R1

OUTPUTS

POWER

POWER COMMON

OUTPUTS
Black Lead 115VAC Input, 50/60 Hz.
White Lead

Transformer underneath power supply board

XFMR*

FUSED

Fig. 8 ALTV248300ULCBM

LED

INPUT

F8

D1

F7

R1

OUTPUTS

POWER

POWER

F3

OUTPUTS

F4

Transformer underneath power supply board

F5

F6

F2

COMMON

FUSED

F1

-8-

MAIN FUSE

MAIN FUSE

Fig. 8A

Illuminated Power Disconnect Circuit Breaker with manual reset

Black Lead 115VAC Input, 50/60 Hz.


White Lead

XFMR*

Fig. 9 ALTV248600UL

24VAC or 28VAC fused ( Follow same procedure using terminals 2P & N thru 4P & N outputs 2 thru 4).
MAIN FUSE

Connected to Door

INPUT N P S

Class 1 outputs

non-power limited

Green Lead (Ground)

115VAC input, 50/60 Hz.

XFMR*

Black Lead White Lead


non-power limited

MAIN FUSE

Fig. 9A
INPUT

P S

Illuminated Power Disconnect Circuit Breaker with manual reset

non-power limited

XFMR*

-9-

Fig. 10 ALTV248600ULCB

24VAC or 28VAC output 1 (Follow same procedure using terminals 2P & N through 4P & N outputs 2 through 4)
INPUT

Connected to Door

24VAC configuration Class 2 Not Wet/Class 3 Wet

N N

Fig. 10A
INPUT

non-power limited

P S

Illuminated Power Disconnect Circuit Breaker with manual reset

non-power limited

Green Lead (Ground)

115VAC input, 50/60 Hz.

XFMR*

XFMR*

Black Lead White Lead


non-power limited

- 10 -

Enclosure Dimensions for: ALTV248UL ALTV248ULCB


8.5"H x 7.5"W x 3.5"D

7.25

3.625 1.25 3.50

1.25

0.60 1.125

6.05

0.60 1.125

2.00

2.00

8.125

1.00 0.60 6.05

1.00 0.60 1.25

3.50

3.50

1.00 1.00 5.25 1.00

Enclosure Dimensions for: ALTV248300ULM ALTV248300ULCBM


8.5"H x 7.5"W x 3.5"D
3.63"

1.25"

3.85"

7.25" 1.25" 0.60" 0.60" 1.25"

1.00"

0.90"

0.90"

1.00"

8.13"

8.13"

8.13"

1.75"

1.00"

1.00"

1.25" 3.85"

0.60" 7.25"

0.60"

3.85"

1.00"

1.00" 7.25"

1.00"

- 11 -

Enclosure Dimensions for: ALTV248175UL ALTV248175ULCB ALTV248300UL ALTV248300ULCB


12"H x 7.25"W x 4.5"D
1.50" 1.25" 0.50" 1.11"

7.50"

4.50"

0.50" 1.11"

1.25"

1.50"

3.50"

3.50"

12"

2.50"

12"

12"

5.88"

3.50"

1.00"

1.13"

4.50"

7.50"

4.50"

4.50"

1.00" 0.88" 5.75" 7.50" 0.88"

1.00"

Enclosure Dimensions for: ALTV248600UL ALTV248600ULCB


13"H x 13.5"W x 3.5"D

1.40

4.85

4.85

1.40

1.20

3.25

1.20

12.50 11.00 0.75 0.9375

1.40

5.10

5.10

5.10 6.5625

0.9375

3.25

3.25

3.25

1.00

1.00

1.00

10.50

1.00

Altronix is not responsible for any typographical errors.


Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. II1ALTV248ULSeries D05F

MEMBER

- 12 -

Das könnte Ihnen auch gefallen