Beruflich Dokumente
Kultur Dokumente
Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB Inc. Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Toll-free: 1 (800) 523-2620 Phone: +1 954-752-6700 Fax: +1 954 345-5329 http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN 60255-27 for the low voltage directive. The IED is designed in accordance with the international standards of the IEC 60255 series and ANSI C37.90.
Table of contents
Table of contents
Section 1 Introduction............................................................................5
This manual..............................................................................................5 Intended audience....................................................................................5 Product documentation.............................................................................6 Product documentation set..................................................................6 Document revision history...................................................................7 Related documentation........................................................................8 Symbols and conventions.........................................................................8 Safety indication symbols....................................................................8 Manual conventions.............................................................................9 Functions, codes and symbols............................................................9
Section 2
REF615 overview................................................................13
Overview.................................................................................................13 Product version history......................................................................14 PCM600 and IED connectivity package version................................14 Operation functionality............................................................................15 Optional features...............................................................................15 Physical hardware..................................................................................15 Local HMI................................................................................................17 LCD....................................................................................................18 LEDs..................................................................................................18 Keypad..............................................................................................19 Web HMI.................................................................................................19 Authorization...........................................................................................20 Communication.......................................................................................21
Section 3
REF615 variants..................................................................23
REF615 variant list.................................................................................23 Presentation of standard configurations.................................................23 Standard configurations ....................................................................24 Connection diagrams.........................................................................27 Standard Configuration FA01: Current inputs only.................................29 Applications.......................................................................................29 Functions...........................................................................................29 Default I/O connections................................................................31
Table of contents
Functional diagrams..........................................................................33 Functional diagrams for protection...............................................34 Functional diagrams for digital fault recorder and trip circuit monitoring.....................................................................................40 Functional diagrams for control and interlocking..........................44 Functional diagram for optional ARC flash detection and autoreclosing................................................................................48 Functional diagram for optional additional ground overcurrent protection...................................................................50 Optional sensitive earth fault and high impedance fault detection.......................................................................................52 Standard configuration FA02: Current and voltage inputs......................53 Applications.......................................................................................53 Functions...........................................................................................54 Default I/O connections................................................................56 Functional diagrams..........................................................................58 Functional diagrams for protection...............................................58 Functional diagrams for digital fault recorder and trip circuit monitoring.....................................................................................64 Functional diagrams for control and interlocking..........................67 Functional diagram for voltage protections...................................72 Functional diagram for optional ARC flash detection and autoreclosing................................................................................73 Functional diagram for optional additional ground overcurrent protection...................................................................75 Optional sensitive earth fault and high impedance fault detection.......................................................................................76
Section 4
Section 5
Table of contents
Phase voltages.............................................................................83 Ground voltage.............................................................................84 Auxiliary supply voltage input............................................................84 Binary inputs......................................................................................84 Optional light sensor inputs...............................................................86 Outputs...................................................................................................86 Outputs for tripping and controlling....................................................86 Outputs for signalling.........................................................................87 IRF.....................................................................................................88
Section 6
Glossary..............................................................................89
1MAC109554 C
Section 1 Introduction
Section 1
Introduction
1.1
This manual
The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings.
1.2
Intended audience
This manual addresses the protection and control engineer responsible for planning, preengineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as communication and protocols.
Section 1 Introduction
1MAC109554 C
1.3
1.3.1
Product documentation
Product documentation set
Decommissioning deinstalling & disposal Planning & purchase
Commissioning
Engineering
Engineering manual Installation manual Commissioning manual Operation manual Service manual Application manual Technical manual Communication protocol manual en07000220.vsd
IEC07000220 V1 EN
Figure 1:
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and DNP3. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. The commissioning manual contains instructions on how to commission the IED. The manual can also be used by system engineers and maintenance personnel for assistance
6 REF615 ANSI Application Manual
Operation
Installing
Maintenance
1MAC109554 C
Section 1 Introduction
during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service. The chapters are organized in chronological order in which the IED should be commissioned. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The service manual contains instructions on how to service and maintain the IED. The manual also provides procedures for de-energizing, de-commissioning and disposal of the IED. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Some of the manuals are not available yet.
1.3.2
Section 1 Introduction
1MAC109554 C
Download the latest documents from the ABB web site http:// www.abb.com/substationautomation.
1.3.3
Related documentation
Name of the document Modbus Communication Protocol Manual DNP3 Communication Protocol Manual IEC 61850 Engineering Guide Installation Manual Operation Manual Technical Manual Document ID 1MAC052634-MB 1MAC052460-MB 1MAC106231-MB 1MAC051065-MB 1MAC050592-MB 1MAC050144-MB
1.4
1.4.1
The warning icon indicates the presence of a hazard which could result in personal injury.
The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
The information icon alerts the reader to important facts and conditions.
1MAC109554 C
Section 1 Introduction
The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it should be understood that operation of damaged equipment could, under certain operational conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this manual. Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the push button icons, for example: To navigate between the options, use and . HMI menu paths are presented in bold, for example: Select Main menu/Settings. LHMI messages are shown in Courier font, for example: To save the changes in non-volatile memory, select Yes and press . Parameter names are shown in italics, for example: The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks, for example: The corresponding parameter values are "Enabled" and "Disabled". IED input/output messages and monitored data names are shown in Courier font, for example: When the function picks up, the PICKUP output is set to TRUE. Dimensions are provided both in inches and mm. If it is not specifically mentioned then the dimension is in mm.
1.4.3
Section 1 Introduction
Function Three-phase non-directional time overcurrent protection, low stage Three-phase non-directional instantaneous overcurrent protection Three-phase non-directional time overcurrent protection, high stage 1 Three-phase non-directional time overcurrent protection, high stage 2 Three-phase non-directional long time overcurrent protection Ground non-directional time overcurrent protection, low stage (Calculated) Ground non-directional instantaneous overcurrent protection, (Calculated) Ground non-directional time overcurrent protection, high stage 1 (Calculated) Ground non-directional time overcurrent protection, high stage 2 (Calculated) Ground non-directional time overcurrent protection, high stage 1 (Measured) Ground non-directional time overcurrent protection, high stage 2 (Measured) Negative sequence non-directional time overcurrent protection 1 Negative sequence non-directional time overcurrent protection 2 Phase discontinuity protection Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Loss of load protection Three phase overvoltage protection, stage 1 Three phase overvoltage protection, stage 2 Three-phase undervoltage protection, stage 1 Three-phase undervoltage protection, stage 2 Ground overvoltage protection Negative sequence overvoltage protection Directional ground-fault protection, low stage Directional ground-fault protection, high stage 1 Directional ground-fault protection, high stage 2 Three-phase directional overcurrent protection, low stage Table continues on next page 10 IEC 61850 PHLPTOC1 PHIPTOC1 PHHPTOC1 PHHPTOC2 PHLTPTOC1 EFLPTOC2 EFIPTOC2 EFHPTOC3 EFHPTOC4 EFHPTOC1 EFHPTOC2 NSPTOC1 NSPTOC2 PDNSPTOC1 T1PTTR1 CCBRBRF1 LOFLPTUC1 PHPTOV1 PHPTOV2 PHPTUV1 PHPTUV2 ROVPTOV1 NSPTOV1 DEFLPDEF1 DEFLPDEF2 DEFHPDEF1 DPHLPDOC1 IEC 60617 3I>(1) 3I>>>(1) 3I>>(1) 3I>>(2) 3I>(3) I0>(2) I0>>> (2) I0>> (3) I0>> (4) I0>> (1) I0>> (2) I2>(1) I2>(2) I2/I1> 3Ith>F 3I>/IoBF(1) 3I< 3U>(1) 3U>(2) 3U<(1) 3U<(2) U0>(1) U2> I0>->(1) I0>->(2) I0>>->(1) 3I>->(1)
1MAC109554 C
ANSI 51P 50P-3 50P-1 50P-2 51LT 51N 50N-3 50N-1 50N-2 50G-1 50G-2 46-1 46-2 46PD 49F 50BF 37 59-1 59-2 27-1 27-2 59G 47 67/51N 67/50N -1 67/50N -2 67/51P
1MAC109554 C
Section 1 Introduction
Function Three-phase directional overcurrent protection, high stage 1 Three-phase directional overcurrent protection, high stage 2 Ground non-directional time overcurrent protection, low stage (Measured) Ground non-directional instantaneous overcurrent protection, (Measured) Non-directional sensitive earth-fault protection Arc flash detector 1 Arc flash detector 2 Arc flash detector 3 Low impedance restricted ground fault protection High impedance fault detector Control Autoreclosing Circuit Breaker Control Supervision and monitoring Circuit breaker condition monitoring Trip circuit monitoring 1 Trip circuit monitoring 2 Current circuit supervision Fuse failure supervision Measurement Three-phase current measurement Three-phase voltage measurement Sequence current measurement Sequence voltage measurement Three-phase power and energy measurement Ground current measurement Ground voltage measurement Digital fault recorder Sequence of events recorder Fault recorder Electrically latched/self resetting trip output 1 Electrically latched/self resetting trip output 2 CMMXU1 VMMXU1 CSMSQI1 VSMSQI1 PEMMXU1 RESCMMXU1 RESVMMXU1 RDRE1 SER FLTMSTA TRPPTRC1 TRPPTRC2 3I 3U I1,I2,I0 U1,U2,U0 P,E I0 U0 DR SER FR Trip(1) Trip(2) IA, IB, IC VA,VB,VC I1, I2, I0 V1,V2,V0 P,E IG VG DFR SER FLR 86/94-1 86/94-2 SSCBR1 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 CBCM TCS(1) TCS(2) MCS 3I FUSEF 52CM TCM-1 TCM-2 CCM 60 DARREC1 CBXCBR1 O->I I<->O CB 79 52-1 IEC 61850 DPHLPDOC2 DPHHPDOC1 EFLPTOC1 EFIPTOC1 EFLPTOC3 ARCSARC1 ARCSARC2 ARCSARC3 LREFPNDF1 PHIZ1 IEC 60617 3I>->(2) 3I>>->(1) I0>(1) I0>>> (1) I0>(3) ARC(1) ARC(2) ARC(3) dIoLo> PHIZ1 ANSI 67/50P-1 67/50P-2 51G 50G-3 50SEF AFD-1 AFD-2 AFD-3 87LOZREF HIZ
11
12
1MAC109554 C
Section 2
REF615 overview
2.1
Overview
REF615 is a dedicated feeder IED (intelligent electronic device) designed for the protection, control, measurement and supervision of utility substations and industrial power systems. REF615 is a member of ABBs Relion product family and part of its 615 protection and control product series. The 615 series IEDs are characterized by their compactness and withdrawable design. Re-engineered from the ground up, the 615 series has been designed to unleash the full potential of the IEC 61850 standard for communication and interoperability between substation automation devices. The IED provides main protection for overhead lines and cable feeders in distribution networks. The IED is also used as back-up protection in applications, where an independent and redundant protection system is required. Depending on the chosen standard configuration, the IED is adapted for the protection of overhead line and cable feeders in isolated neutral, resistance earthed, compensated and solidly earthed networks. Once the standard configuration IED has been given the application-specific settings, it can directly be put into service. The 615 series IEDs support a range of communication protocols including IEC 61850 with GOOSE messaging, Modbus and DNP3.
13
1MAC109554 C
Circuit breaker condition monitoring Replaced EFIPTOC3 with EFLPTOC3 New communication modules COMB11A, COMB12A, COMB13A and COMB14A IRIG-B CB interlocking functionality enhanced TCS functionality in HW enhanced Non-volatile memory added Serial communications Support for DNP3 serial or TCP/IP Voltage measurement and protection Power and energy measurement Disturbance recorder upload via WHMI Fuse failure supervision
2.1.2
Download connectivity packages from the ABB web site http:// www.abb.com/substationautomation
14
1MAC109554 C
2.2
2.2.1
Operation functionality
Optional features
Arc flash detector with three sensors Optional arc flash detectors can be added to all standard configurations. Optional BIO (7 BI + 3 BO) can be added to all standard configurations. Additional BIOs: 7BI+3BO Autorecloser
2.3
Physical hardware
The IED consists of two main parts: plug-in unit and case. The plug-in unit content depends on the ordered functionality.
Table 2:
Main unit Plug-in unit X100
X110
BI/O module
X120
AI/BI module
Case
X130
X000
15
1MAC109554 C
The rated input levels are selected in the IED software for phase current and ground current. The binary input thresholds 18...176 V DC are selected by adjusting the IED's parameter settings. The optional BIO module can be added in the IED to all standard configurations. The connection diagrams of different hardware modules are presented in this manual. See the installation manual for more information about the case and the plug-in unit.
Table 3:
Conf. FA01 FA02
3 or 4
16
1MAC109554 C
2.4
Local HMI
A070704-ANSI V1 EN
Figure 2:
LHMI
The LHMI of the IED contains the following elements: Display Buttons LED indicators Communication port
17
1MAC109554 C
The LHMI includes a graphical LCD that supports two character sizes. The character size depends on the selected language.
Table 4:
Character size Large, variable width (13x14 pixels)
A070705-ANSI V2 EN
Figure 3:
1 Header 2 Icon 3 Content
Display layout
2.4.2
LEDs
The LHMI includes three protection indicators above the display: Normal, Pickup and Trip. There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the operation mode can be selected with the LHMI, WHMI or PCM600.
18
1MAC109554 C
There are two additional LEDs which are embedded into the control buttons . They represent the status of the circuit breaker.
and
2.4.3
Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views or menus. With the push-buttons you can give open or close commands to one primary object, for example, a circuit breaker, disconnector or switch. The push-buttons are also used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.
A071176-ANSI V1 EN
Figure 4:
LHMI keypad with object control, navigation and command pushbuttons and RJ-45 communication port
2.5
Web HMI
The WHMI enables the user to access the IED via a web browser. The supported web browser version is Internet Explorer 7.0 or later. WHMI is enabled by default.
WHMI offers several functions. Alarm indications and event lists System supervision Parameter settings
19
1MAC109554 C
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
A070754-ANSI V2 EN
Figure 5:
The WHMI can be accessed locally and remotely. Locally by connecting your laptop to the IED via the front communication port. Remotely over LAN/WAN.
2.6
Authorization
The user categories have been predefined for the LHMI and the WHMI, each with different rights and default passwords. The default passwords can be changed with Administrator user rights.
20
1MAC109554 C
Table 5:
Username VIEWER OPERATOR
ENGINEER
ADMINISTRATOR
2.7
Communication
The IED supports different communication protocols: IEC 61850, Modbus and DNP 3.0 Level 2 - all using TCP/IP. DNP3 and Modbus also support serial communication. Operational information and controls are available through these protocols. However, some communication functionality, for example, horizontal peer-to-peer communication between the IEDs and parameters setting, is only enabled by the IEC 61850 communication protocol. The IEC 61850 communication implementation supports all monitoring and control functions. Additionally, parameter setting and DFR records can be accessed using the IEC 61850 protocol. Oscillographic files are available to any Ethernet-based application in the standard COMTRADE format. Further, the IED can send and receive binary signals from other IEDs (so called horizontal communication) using the IEC61850-8-1 GOOSE profile, where the highest performance class with a total
21
1MAC109554 C
transmission time of 3 ms is supported. The IED meets the GOOSE performance requirements for tripping applications in distribution substations, as defined by the IEC 61850 standard. The IED can simultaneously report events to five different clients on the station bus. All communication connectors, except for the front port connector, are placed on integrated optional communication modules. The IED can be connected to Ethernetbased communication systems via the RJ-45 connector (100BASE-TX) or the fiberoptic LC connector (100BASE-FX). An optional serial interface is available for RS-232/RS-485 communication.
22
1MAC109554 C
Section 3
REF615 variants
3.1
3.2
23
1MAC109554 C
With Signal Matrix in PCM600 the user can modify the standard configuration according to the actual needs. The IED is delivered from the factory with default connections described in the functional diagrams for BI's, BO's, function to function connections and alarm LEDs. Signal Matrix has a number of different page views, designated as follows: Binary input Binary output Functions
There are four IED variant-specific setting groups. Parameters can be set independently for each setting group. The active setting group (1...4) can be changed with a parameter. The active setting group can also be changed via a binary input if the binary input is enabled for this. To enable the change of the active setting group via a binary input, connect a free binary input with PCM600 to the ActSG input of the SGCB-block.
Table 6:
BI state OFF ON
The active setting group defined by a parameter is overridden when a binary input is enabled for changing the active setting group.
3.2.1
Standard configurations
The feeder protection IED REF615 is available with two alternative standard configurations.
Table 7:
Description Current inputs only Current and voltage inputs
Standard configurations
Std conf. FA01 FA02
24
1MAC109554 C
Table 8:
Supported functions
Std config. FA01 Std config. FA02
Protection Three-phase transformer inrush detector Three-phase non-directional time overcurrent protection, low stage Three-phase non-directional time overcurrent protection, high stage 1 Three-phase non-directional time overcurrent protection, high stage 2 Three-phase non-directional instantaneous overcurrent protection Three-phase non-directional long time overcurrent protection Ground non-directional time overcurrent protection, low stage (Measured) Non-directional sensitive earth-fault protection Ground non-directional time overcurrent protection, high stage 1 (Measured) Ground non-directional time overcurrent protection, high stage 2 (Measured) Ground non-directional instantaneous overcurrent protection (Measured) Ground non-directional time overcurrent protection, low stage (Calculated) Ground non-directional time overcurrent protection, high stage 1 (Calculated) Ground non-directional time overcurrent protection, high stage 2 (Calculated) Ground non-directional instantaneous overcurrent protection (Calculated) Three phase overvoltage protection, stage 1 Three phase overvoltage protection, stage 2 Three-phase undervoltage protection, stage 1 Three-phase undervoltage protection, stage 2 Ground overvoltage protection Negative sequence overvoltage protection Directional ground-fault protection, low stage Directional ground-fault protection, high stage 1 Directional ground-fault protection, high stage 2 Three-phase directional overcurrent protection, low stage Three-phase directional overcurrent protection, high stage 1 Three-phase directional overcurrent protection, high stage 2 Negative sequence non-directional time overcurrent protection 1 Negative sequence non-directional time overcurrent protection 2 Phase discontinuity protection Three-phase thermal protection for feeders, cables and distribution transformers Loss of load protection Low impedance restricted ground-fault protection Table continues on next page REF615 ANSI Application Manual 25
1MAC109554 C
Cold load timer 1 (Seconds) Cold load timer 2 (Minutes) Arc flash detection with three sensors High impedance fault detector Circuit breaker failure protection Control Autoreclosing Circuit breaker control Supervision and monitoring Circuit breaker condition monitoring Trip-circuit monitoring of two trip circuits Current circuit supervision Fuse failure supervision Measurement Three-phase current measurement Three-phase voltage measurement Sequence current measurement Sequence voltage measurement Ground current measurement Ground voltage measurement Three-phase power and energy measurement Disturbance recorder Sequence of events recorder Fault recorder Electrically latched/self resetting trip output 1 and 2 = Included, = Optional at the time of the order
26
1MAC109554 C
3.2.2
REF615
X120 1 2 3 X100
+
BI 1 Vaux
1 2 3
BI 2
IRF 4 5 PO1
4
P1
BI 3
S1 S2
5 6 7 8 9
BI 4 IA
BREAKER CLOSE 6 7 PO2 BREAKER FAILURE 8 9 10 SO1 COMMON PICKUP 11 12 13 SO2 COMMON TRIP 14
P2
IB 10 11 IC 12 13 IG 14
52 A B C
BI 2
TCM-1
MASTER TRIP 2
7 8 9
10 11 12
BI 6 SO1 BI 7 SO2
13
BI 8
X130 1 2 BI 1
1)
3 4 5
BI 2
BI 3
1)
6 7 8
BI 4
BI 5
BI 6
X1 LAN
1) 2)
X13 Light sensor input 1 X14 Light sensor input 2 X15 Light sensor input 3 1) Optional 2) 100BaseFX / LC or 100BaseTX / RJ-45
1) 1) 1)
GUID-A7A9B265-EF15-4220-8319-7337B50977D0 V1 EN
Figure 6:
REF615 ANSI Application Manual
1MAC109554 C
A B C A N n a da dn X120 1 2 3 4
P1 S1 S2
REF615
BI 1 BI 2 BI 3 PO1 BI 4 IA IB IC IG SO2 14 BI 1 BI 2 BI 3 BI 4 TCM-2 Not in use VA VB VC VG SO2 PO3 16 17 15 19 18 20 22 21 23 24 X110 14 SO1 16 15 17 19 18 20 22 21 23 SO4 BI 1 BI 2 BI 3 BI 4 BI 5 BI 6 BI 7 BI 8 24 MASTER TRIP 1 SO1 11 12 13 6 7 PO2 8 9 10 Vaux
IRF
5 6 7 8 9 10 11 12 13 14 X13 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
BREAKER CLOSE
P2
BREAKER FAILURE
52 A B C
COMMON PICKUP
COMMON TRIP
TCM-1
PO4
MASTER TRIP 2
SO3
X110 1 2 3 4 5 6 7 8 9 10 11 12 13 X1 LAN X5 1 2 3 4 5 6 7 8 9 10 X13 X14 X15 GND GNDC IRIG-BIRIG-B+ AGND B/- TX A/+ TX B/- RX A/+ RX
1)
1) 2)
1)
1)
1)
GUID-E3D5CE1A-5EB8-4D7B-B52F-CD420869B354 V1 EN
Figure 7:
28
1MAC109554 C
3.3
3.3.1
3.3.2
Functions
Table 9:
Function Included functions Three-phase current measurement Sequence current measurement Three-phase transformer inrush detector Cold load timer 1 (Seconds) Cold load timer 2 (Minutes) Three-phase non-directional time overcurrent protection, low stage Three-phase non-directional time overcurrent protection, high stage 1 Three-phase non-directional time overcurrent protection, high stage 2 Three-phase non-directional instantaneous overcurrent protection Three-phase non-directional long time overcurrent protection Ground non-directional time overcurrent protection, low stage (Calculated) Ground non-directional time overcurrent protection, high stage 1 (Calculated) Ground non-directional time overcurrent protection, high stage 2 (Calculated) Table continues on next page CMMXU1 CSMSQI1 INRPHAR1 TPSGAPC1 TPMGAPC1 PHLPTOC1 PHHPTOC1 PHHPTOC2 PHIPTOC1 PHLTPTOC1 EFLPTOC2 EFHPTOC3 EFHPTOC4 3I I1,I2,I0 3I2f> TPS(1) TPM(1) 3I>(1) 3I>>(1) 3I>>(2) 3I>>>(1) 3I>(3) I0>(2) I0>> (3) I0>> (4) IA, IB, IC I1, I2, I0 INR 62CLD-1 62CLD-2 51P 50P-1 50P-2 50P-3 51LT 51N 50N-1 50N-2
29
1MAC109554 C
ANSI 50N-3 46-1 46-2 46PD 49F 50BF TCM-1 TCM-2 86/94-1 86/94-2 DFR SER FLR 52-1 37 52CM CCM
IG 51G 50G-1 50G-2 50G-3 50SEF 79 AFD-1 AFD-2 AFD-3 87LOZREF HIZ
30
1MAC109554 C
3.3.2.1
Table 11:
Binary output X100-PO1 X100-PO2 X100-PO3 X100-PO4 X100-SO1 X100-SO2
Table 12:
LED label LED label 1
Order codes
Order code options HAFAAAAxxAE1BNNxXC HAFAAAAxxBE1BNNxXC HAFAAAAxx3E1BNNxXC
LED label 2
LED label 3
HAFAAAAxxFE1BNNxXC HAFAAAAxxGE1BNNxXC
LED label 4
HAFAAAAxxFE1BANxXC HAFAAAAxxGE1BANxXC
LED label 5
LED label 6
31
1MAC109554 C
Table 13:
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11
Table 14:
LED1 LED2 LED3
32
1MAC109554 C
Table 15:
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11
3.3.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function to function connections. The default connections can be viewed with the Signal Matrix tool and changed according to the application requirements, if necessary. The analog channels, measurements from CTs, have fixed connections to the different function blocks inside the IEDs standard configuration. The analog channels are assigned to different functions as shown in the functional diagrams. The common signal marked with IA, IB, IC represents the three phase currents. The signal IG represents the measured ground current.
33
1MAC109554 C
The following functional diagrams describe the IEDs protection functionality in detail and according to the factory set default connections in the Signal Matrix tool. Five overcurrent stages are offered for phase overcurrent and short-circuit protection. The inrush detection blocks (INR) output BLK2H provides the possibility to either block the function or multiply the active settings for any of the shown protection function blocks.
PHASE OVERCURRENT PROTECTION INDICATION
ANSI Device/Function Number/Acronym IEC60617 symbol IEC61850 identification 51P
NOTE 1
TRIP_PhA TRIP_PhB TRIP_PhC
OR
86/94 LED
TRIP_PhA TRIP_PhA
PHASE A TRIP
LED1
3I>(1) PHLPTOC1
PICKUP TRIP
Trip1 LEDPTRC
ENA_MULT
50P-1
NOTE 1
TRIP_PhA TRIP_PhB
OR
86/94 LED
TRIP_PhB TRIP_PhB
IA, IB, IC
3I>>(1) PHHPTOC1
TRIP_PhC
PHASE B TRIP
LED2
PICKUP TRIP
INR
3I2f> INRPHAR1
IA, IB, IC BLOCK BLK2H
BLOCK ENA_MULT
Trip1 LEDPTRC
50P-2
NOTE 1
TRIP_PhA TRIP_PhB
OR
86/94 LED
TRIP_PhC TRIP_PhC
PHASE C TRIP
LED3
IA, IB, IC BLOCK AVAILABLE FOR MAPPING USING SMT TOOL IN PCM TO ANY PROTECTION, DEPENDING ON APPLICATION.
3I>>(2) PHHPTOC2
TRIP_PhC
PICKUP TRIP
Trip1 LEDPTRC
ENA_MULT
50P-3
NOTE 1
OR
TIME TRIP
LED 5
TRIP_PhA TRIP_PhB
3I>>>(1) PHIPTOC1
TRIP_PhC
PICKUP TRIP
ENA_MULT
OR
INSTANTANEOUS TRIP
LED6
51LT
NOTE 1
TRIP_PhA TRIP_PhB
3I>(3) PHLTPTOC1
TRIP_PhC
PICKUP TRIP
ENA_MULT
GUID-E42BE42B-7540-48EF-88D3-F3EA495494E0 V1 EN
Figure 8:
The neutral overcurrent protections 51N, 50N-1/2 can be blocked by energizing the binary input 1 (X120:1-2). Two negative sequence overcurrent stages (46-1 and 46-2) are included for phase unbalance protection along with a separate phase discontinuity protection. The phase discontinuity protection (46PD) provides protection for interruptions in the normal three-phase load supply, like in downed conductor situations. Two separate cold load timers are provided with seconds and minutes
34 REF615 ANSI Application Manual
1MAC109554 C
ranges to provide utmost flexibility in cold-load inrush protection. Any functions can be selected to be blocked during the cold load timers pickup duration using the Signal Matrix tool.
NEUTRAL OVERCURRENT PROTECTION
51N
I0>(2) EFLPTOC2
IA, IB, IC BLOCK ENA_MULT
TRIP_NEUT TRIP_NEUT
PICKUP TRIP
OR
86/94 LED
NEUTRAL TRIP
LED4
50N-1
I0>>(3) EFHPTOC3
IA, IB, IC PICKUP TRIP
Trip 1 LEDPTRC
TIME TRIP
LED 5
BI 1 (Blocking)
BLOCK ENA_MULT
OR
INSTANTANEOUS TRIP
LED 6
50N-2
I0>>(4) EFHPTOC4
IA, IB, IC BLOCK ENA_MULT PICKUP TRIP
50N-3
I0>>>(2) EFIPTOC2
IA, IB, IC BLOCK ENA_MULT PICKUP TRIP
GUID-5D3E8AF3-F761-44A7-9C32-5895506023CE V1 EN
Figure 9:
35
1MAC109554 C
46-1
I2>(1) NSPTOC1
I1, I2, I0 BLOCK ENA_MULT PICKUP TRIP
46-2
I2>(2) NSPTOC2
I1, I2, I0 BLOCK ENA_MULT PICKUP TRIP
46PD
I2/I1> PDNSPTOC1
I1, I2, I0 BLOCK ENA_MULT PICKUP TRIP
GUID-5A283316-A594-476E-9D4E-679F733DD128 V1 EN
Figure 10:
36
1MAC109554 C
50P-1
3I>>(1) PHHPTOC1
PICKUP
OR
TRIP BLOCK
62CLD-2
TPM(1) TPMGAPC1
TRIP TRIP
50G-1
I0>>(1) EFHPTOC1
PICKUP TRIP BLOCK
50N-1
I0>>(3) EFHPTOC3
PICKUP TRIP BLOCK NOTE: COLD LOAD INRUSH PROTECTION LOGIC MAY BE MODIFIED USING SMT IN PCM TOOL, AS REQUIRED.
GUID-20863AAD-BFF9-4B2C-84AF-E104ABA00DB2 V1 EN
Figure 11:
The thermal overload protection (49F) provides indication for overload situations.
37
1MAC109554 C
3Ith>F T1PTTR1
IA, IB, IC TRIP ALARM BLK_OPR ENA_MULT BLK_CLOSE PICKUP
OVERLOAD ALARM
OR
LED9
GUID-CAE27F81-EBCE-4CAC-A59D-3D644A9AB54A V1 EN
Figure 12:
All trip signals are connected to the Master Trip Logic and also to the alarm LEDs. The breaker failure protection (50BF) is initiated via the pickup input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET output is used for retripping its own breaker through the Master Trip. The TRBU output is used to give a back-up trip to the breakers associated with the faulty breaker. For this purpose the TRBU trip output signal is connected to output PO2 (X100: 8-9).
38
1MAC109554 C
OR
CCBRBRF1
PO2
X100 8 9
Figure 13:
Restricted earth-fault protection is used in applications where the IED is used as a backup for transformer protection.
39
1MAC109554 C
87LOZREF
dIoLo> LREFPNDF1
3I IG
PICKUP TRIP
REF_PICKUP REF_TRIP
LED4
GUID-2B403B4C-8BB3-464F-B483-E69D7FE072F3 V1 EN
Figure 14:
3.3.3.2
Functional diagrams for digital fault recorder and trip circuit monitoring
The digital fault recorder has 64 digital inputs. All pickup and trip signals from the protection stages are routed to trigger the digital fault recorder or alternatively only to be recorded by the digital fault recorder depending on the parameter settings.
40
1MAC109554 C
DR DREC
GUID-5117344E-F9D8-4A21-8C94-A1D76A904FA0 V1 EN
Figure 15:
41
1MAC109554 C
DR DREC
OR
OR
OR
OR
GUID-AB84979D-9313-4A32-846A-1EB9E5EADAD0 V1 EN
Figure 16:
42
1MAC109554 C
DR DREC
X120-1
X120-3
X110-1
X110-3
X110-5
X110-7
X130-1
X130-3
X130-5
X120-2
X120-4
X110-2
X110-4
X110-6
X110-8
X130-2
X130-4
X130-6
GUID-1A93270E-B5A8-4E23-AD71-8BE3A5A3C547 V1 EN
Figure 17:
Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) and TCM-2 for PO4 (X100:20-23). Both functions are indicated in LED 8.
43
1MAC109554 C
TCM-2
TCS(2) TCSSCBR2
BLOCK ALARM
GUID-5B908A59-702C-4BD4-8DFA-85B6A1A7E18F V1 EN
Figure 18:
3.3.3.3
X100 16 17 15 19 18
OR
TRIP
BLOCK
Trip(1) TRPPTRC1
86/94-1
TRIP
CL_LKOUT
OR
PO3
RST_LKOUT
TCM-1
NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION. 79 OPEN_CB 52 EXE_OP
GUID-095D3F46-D13E-4826-AAE6-0797F7D401FE V1 EN
Figure 19:
Master trip 1
44
1MAC109554 C
OR
Trip(2) TRPPTRC2
BLOCK TRIP RST_LKOUT TRIP CL_LKOUT
86/94-2
+
OR
PO4
TCM-2
79 OPEN_CB 52 EXE_OP
NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION. 2) NON-LATCHED MODE AS DEFAULT.
GUID-57A77F68-3DCA-4471-9F83-6E77DD010693 V1 EN
Figure 20:
Master trip 2
The blocks 86/94-1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be reassigned to the RST_LKOUT input of the Master Trip Logics to enable external reset with a push button.
45
1MAC109554 C
52
52-1 EXE_OP
Always True
+ OR PO1
X100 6 7
Close Breaker
52CM
SSCBR1 TRV_T_OP_ALM BLOCK POSOPEN TRV_T_CL_ALM POSCLOSE DIFTRVTOPALM PRES_ALM_IN DIFTRVTCLALM PRES_LO_IN SPR_CHR_ALM SPR_CHR_ST SPR_CHR RST_IPOW RST_CB_WEAR OPR_ALM OPR_LO IPOW_ALM IPOW_LO CB_LIFE_ALM MON_ALM PRES_ALM PRES_LO OPENPOS INTERMPOS CLOSEPOS CBCM
5 6
BI 3 BI 4
OR
(CB COND MONITOR)
LED8
CB Spring Charged
GUID-F6999B37-F933-43D0-967B-3FE127FE7811 V1 EN
Figure 21:
The ENA_CLOSE input, which enables closing the circuit breaker, in the breaker control function block 52-1, is a combination of the status of the Master Trip Logics. The open operation is always enabled. If the ENA_CLOSE signal is completely removed from the breaker control function block 52-1 with the Signal Matrix tool, the function assumes that the breaker close commands are allowed continuously. The circuit-breaker condition monitoring function (52CM) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8. The signal outputs from the IED are connected to give dedicated information on pickups and trips. Pickup of any protection function SO1 (X100:10-12) Trip of any protection function SO2 (X100:13-15)
46
1MAC109554 C
TP-1
1)
TP-1 TPGAPC1
PICKUP PICKUP TRIP
NOTE: 1) THERE ARE FOUR PULSE TIMERS AVAILABLE -ONE OF THEM IS USED FOR DEFAULT CONFIGURATIONS. ALL PULSE TIMERS INCLUDING TP-1 CAN BE MAPPED FOR SPECIFIC APPLICATIONS USING SMT IN PCM TOOLS.
GUID-17F7E87F-230E-496D-94C4-B188BA549CE9 V1 EN
Figure 22:
The TP-1 is a timer and used for setting the minimum pulse length for the outputs.
47
1MAC109554 C
Trip(1) TRPPTRC1
PICKUP TRIP PICKUP TRIP
Trip(2) TRPPTRC2
PICKUP TRIP PICKUP TRIP
GUID-7E976C74-3F94-4023-89FD-0E62CC5766C6 V1 EN
Figure 23:
3.3.3.4
48
1MAC109554 C
ARC(1) ARCSARC1
IA, IB, IC IG BLOCK REM_FLT_ARC OPR_MODE TRIP ARC_FLT_DET
LED10
ARC(2) ARCSARC2
IA, IB, IC IG BLOCK REM_FLT_ARC OPR_MODE TRIP ARC_FLT_DET
ARC(3) ARCSARC3
IA, IB, IC IG BLOCK REM_FLT_ARC OPR_MODE TRIP ARC_FLT_DET
GUID-19A57C71-5055-4521-AA56-C8BD5F51EDA3 V1 EN
Figure 24:
Trip signals from the ARC protection function blocks are connected to the Master Trip Logic and also to the alarm LED 10 as a common arc flash detection. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1-5 inputs. It is possible to create individual autoreclosing sequences for each input.
49
1MAC109554 C
AUTORECLOSING (Optional)
79 OR
O->I DARREC1
PROT_CRD INIT_1 INIT_2 INIT_3 INIT_4 OPEN CB CLOSE CB INPRO UNSUC_RECL AR_ON LOCKED
50P-1 -trip 50P-2 -trip 50N-1 -trip 50N-2 -trip 50G-1 -trip 50G-2 -trip 51P -trip 51N -trip 51G -trip 46-1 -trip 46-2 -trip 50P-3 -trip 50N-3 -trip 50G-3 -trip 52 -selected AFD-1 -trip AFD-2 -trip AFD-3 -trip External AR Blocking X120 BI 4 49F -InhRec X120 BI 3 (CB Open)
GUID-9E712054-3ECA-4AAB-8756-F157B5ACDB2C V1 EN
OR
RECLOSER LOCKOUT
LED 7
OR
OR
Notes: Map PROT_CRD signal to Block 50P-1, 50P-2, 50N-1 and 50N-2 using SMT.
DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION.
Figure 25:
Autoreclosing
The autoreclosing function can be blocked with the INHIBIT_RECL input. As a default, the operation of some selected protection functions are connected to this input. A control command to the circuit breaker, either local or remote, will also block the autoreclose function via the 52-1-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_RDY input in 79. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time.
3.3.3.5
50
1MAC109554 C
PICKUP TRIP
OR
86/94LED
50G-1
I0>>(1) EFHPTOC1
IG PICKUP TRIP
TRIP(1) LEDPTRC
TIME TRIP
LED5
BI 1 (Blocking)
BLOCK ENA_MULT
OR
INSTANTANEOUS TRIP
LED 6
50G-2
I0>>(2) EFHPTOC2
IG BLOCK ENA_MULT PICKUP TRIP
50G-3
I0>>>(1) EFIPTOC1
IG BLOCK ENA_MULT PICKUP TRIP
GUID-A251AB3C-8465-441C-8E2E-55335AA2A332 V1 EN
Figure 26:
51
1MAC109554 C
OR
I0>(3) EFLPTOC3
PICKUP TRIP
50N-1
I0>>(3) EFHPTOC3
PICKUP BLOCK TRIP
50N-2
I0>>(4) EFHPTOC4
PICKUP BLOCK TRIP
50N-3
I0>>>(2) EFIPTOC2
PICKUP BLOCK TRIP
GUID-7B5D6C4F-BC2D-4BD4-A659-5F9329A1C20F V1 EN
Figure 27:
52
1MAC109554 C
PHIZ1 PHIZ1
HIZ DETECTION
BLOCK
TRIP
LED11
GUID-81DC07F7-4A53-4918-8FDD-66BD24B6A191 V1 EN
Figure 28:
The sensitive earth-fault protection (50SEF) and high impedance fault detection (HIZ) provide protection against high impedance faults. If the load unbalance is high, 50SEF needs to be set high to avoid misoperations which renders 50SEF ineffective for such applications. In those cases, HIZ can provide detection which would otherwise be undetected.
3.4
3.4.1
53
1MAC109554 C
3.4.2
Functions
Table 16:
Function Included functions Three-phase current measurement Three-phase voltage measurement Sequence current measurement Sequence voltage measurement Three-phase power and energy measurement Three-phase transformer inrush detector Cold load timer 1 (Seconds) Cold load timer 2 (Minutes) Three-phase non-directional time overcurrent protection, low stage Three-phase non-directional instantaneous overcurrent protection Ground non-directional time overcurrent protection, low stage (Calculated) Ground non-directional instantaneous overcurrent protection, (Calculated) Negative sequence non-directional time overcurrent protection 1 Negative sequence non-directional time overcurrent protection 2 Phase discontinuity protection Three-phase thermal protection for feeders, cables and distribution transformers Circuit breaker failure protection Trip circuit monitoring 1 Trip circuit monitoring 2 Electrically latched/self resetting trip output 1 Electrically latched/self resetting trip output 2 Disturbance recorder Sequence of events recorder Fault recorder Circuit breaker control Loss of load protection Table continues on next page CMMXU1 VMMXU1 CSMSQI1 VSMSQI1 PEMMXU1 INRPHAR1 TPSGAPC1 TPMGAPC1 PHLPTOC1 PHIPTOC1 EFLPTOC2 EFIPTOC2 NSPTOC1 NSPTOC2 PDNSPTOC1 T1PTTR1 CCBRBRF1 TCSSCBR1 TCSSCBR2 TRPPTRC1 TRPPTRC2 RDRE1 SER FLTMSTA CBXCBR1 LOFLPTUC1 3I 3U I1,I2,I0 U1,U2,U0 P,E 3I2f> TPS(1) TPM(1) 3I>(1) 3I>>>(1) I0>(2) I0>>> (2) I2>(1) I2>(2) I2/I1> 3Ith>F 3I>/IoBF(1) TCS(1) TCS(2) Trip(1) Trip(2) DR SER FR I<->O CB 3I< IA, IB, IC VA,VB,VC I1, I2, I0 V1,V2,V0 P,E INR 62CLD-1 62CLD-2 51P 50P-3 51N 50N-3 46-1 46-2 46PD 49F 50BF TCM-1 TCM-2 86/94-1 86/94-2 DFR SER FLR 52-1 37
54
1MAC109554 C
55
1MAC109554 C
Table 18:
Binary output X100-PO1 X100-PO2 X100-PO3 X100-PO4 X100-SO1 X100-SO2
Table 19:
LED label LED label 1
Order codes
Order code options HAFDDADAxAE1BNNxXC HAFDDADAxBE1BNNxXC HAFDDADAx3E1BNNxXC
LED label 2
HAFDDADAxFE1BNNxXC HAFDDADAxGE1BNNxXC
LED label 3
LED label 4
HAFDDADAxFE1BANxXC HAFDDADAxGE1BANxXC
LED label 5
LED label 6
HAFDDBDAxFE1BNNxXC HAFDDBDAxGE1BNNxXC
56
1MAC109554 C
Table 20:
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11
Table 21:
LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 LED9 LED10 LED11
57
1MAC109554 C
The functional diagrams describe the default input, output, alarm LED and function to function connections. The default connections can be viewed with the Signal Matrix tool and changed according to the application requirements, if necessary. The analog channels, measurements from CTs, have fixed connections to the different function blocks inside the IEDs standard configuration. The analog channels are assigned to different functions as shown in the functional diagrams. The common signal marked with IA, IB, IC represents the three phase currents. The signal IG represents the measured ground current.
3.4.3.1
58
1MAC109554 C
TRIP_PhA TRIP_PhB
OR
86/94 LED
TRIP_PhA TRIP_PhA
PHASE A TRIP
LED1
TRIP_PhC
3I>(1) PHLPTOC1
PICKUP TRIP
Trip1 LEDPTRC
ENA_MULT
67/51P
3I>->(1)
VA,VB,VC IA, IB, IC
NOTE 1
TRIP_PhA TRIP_PhB
OR
86/94 LED
TRIP_PhB TRIP_PhB
PHASE B TRIP
LED2
DPHLPDOC1
TRIP_PhC
PICKUP TRIP
INR
3I2f> INRPHAR1
IA, IB, IC BLOCK BLK2H
BLOCK ENA_MULT
Trip1 LEDPTRC
50P-3
NOTE 1
TRIP_PhA
OR
86/94 LED
TRIP_PhC TRIP_PhC
PHASE C TRIP
LED3
PICKUP TRIP
Trip1 LEDPTRC
AVAILABLE FOR MAPPING USING SMT TOOL IN PCM TO ANY PROTECTION, DEPENDING ON APPLICATION.
ENA_MULT
OR
67/50P-1
DPHLPDOC2
NOTE 1
TIME TRIP
LED 5
TRIP_PhA
3I>>->(1) TRIP_PhB
TRIP_PhC
PICKUP TRIP
OR
ENA_MULT
INSTANTANEOUS TRIP
LED6
67/50P-2
NOTE 1
TRIP_PhA
PICKUP TRIP
GUID-7014C373-CE58-4086-85E6-384051F9E999 V1 EN
Figure 29:
The neutral overcurrent protection 51N can be blocked by energizing the binary input 1 (X120:1-2). In addition, there are three more directional protection for ground faults. Two negative sequence overcurrent stages (46-1 and 46-2) are included for phase unbalance protection along with a separate phase discontinuity protection. The phase discontinuity protection (46PD) provides protection for interruptions in the normal threephase load supply, like in downed conductor situations. Two separate cold load timers are provided with seconds and minutes ranges to provide utmost flexibility in cold-load inrush protection. Any functions can be selected to be blocked during the cold load timers pickup duration using the Signal Matrix tool. The thermal overload protection (49F) provides indication of overload situations.
59
1MAC109554 C
BI 1 (Blocking)
PICKUP TRIP
OR
86/94 LED
TRIP_NEUT TRIP_NEUT
NEUTRAL TRIP
LED4
Trip 1 LEDPTRC
50N-3
I0>>>(2) EFIPTOC2
IA, IB, IC BLOCK ENA_MULT PICKUP TRIP
TIME TRIP
LED 5
OR
INSTANTANEOUS TRIP
LED 6
GUID-25B47047-EB9A-4262-AEFE-2C3FECC2BAD6 V1 EN
Figure 30:
TIME TRIP
67/50N-1
I0>>(2) DEFLPDEF2
IG VG BLOCK ENA_MULT RCA_CTL PICKUP TRIP
86/94LED
OR
TRIP_NEUT TRIP_NEUT
67/50N-2
I0>>->(1) DEFHPDEF1
IG VG BLOCK ENA_MULT RCA_CTL PICKUP TRIP
TRIP(1) LEDPTRC
GUID-70E9F754-FE31-4F4A-BC58-191B4217C6D7 V1 EN
Figure 31:
60
1MAC109554 C
46-1
I2>(1) NSPTOC1
I1, I2, I0 BLOCK ENA_MULT PICKUP TRIP
46-2
I2>(2) NSPTOC2
I1, I2, I0 BLOCK ENA_MULT PICKUP TRIP
46PD
I2/I1> PDNSPTOC1
I1, I2, I0 BLOCK ENA_MULT PICKUP TRIP
GUID-5A283316-A594-476E-9D4E-679F733DD128 V1 EN
Figure 32:
61
1MAC109554 C
67/50P-1
3I>>->(1) DPHLPDOC2
PICKUP
OR
TRIP BREAKER CLOSE SIGNAL
TRIP BLOCK
62CLD-2 67/50N-1
TPM(1) TPMGAPC1
Mappable Signal External or internal TRIP BLOCK TRIP
I0>>(2) DEFLPDEF2
PICKUP TRIP
NOTE: COLD LOAD INRUSH PROTECTION LOGIC MAY BE MODIFIED USING SMT IN PCM TOOL, AS REQUIRED.
GUID-E8E78F22-20B2-4D87-91F4-1D7E4FC83E41 V1 EN
Figure 33:
3Ith>F T1PTTR1
IA, IB, IC TRIP ALARM BLK_OPR ENA_MULT BLK_CLOSE PICKUP
OVERLOAD ALARM
OR
LED9
GUID-CAE27F81-EBCE-4CAC-A59D-3D644A9AB54A V1 EN
Figure 34:
All trip signals are connected to the Master Trip Logic and also to the alarm LEDs.
62
1MAC109554 C
The breaker failure protection (50BF) is initiated via the pickup input by a number of different protection stages in the IED. The breaker failure protection function offers different operating modes associated with circuit breaker position and the measured phase and residual currents. The breaker failure protection has two operating outputs: TRRET and TRBU. The TRRET output is used for retripping its own breaker through the Master Trip. The TRBU output is used to give a back-up trip to the breakers associated with the faulty breaker. For this purpose the TRBU trip output signal is connected to output PO2 (X100: 8-9).
BREAKER FAILURE PROTECTION
50BF
3I>/Io>BF(1)
51P Trip 67/50P-1 Trip 67/50P-2 Trip 50P-3 Trip 67/51P Trip 46-1 Trip 46-2 Trip 51N Trip 67/50N-1 Trip 67/50N-2 Trip 50N-3 Trip 46PD Trip 49F Trip 50BF Retrip AFD-1 Trip AFD-2 Trip AFD-3 Trip 51G Trip 50G-3 Trip 50SEF Trip 67/51N Trip 87LOZREF Trip
1)
OR
CCBRBRF1
PO2
X100 8 9
Figure 35:
Restricted earth-fault protection is used in applications where the IED is used as a backup for transformer protection.
63
1MAC109554 C
87LOZREF
dIoLo> LREFPNDF1
3I IG
PICKUP TRIP
REF_PICKUP REF_TRIP
LED4
GUID-2B403B4C-8BB3-464F-B483-E69D7FE072F3 V1 EN
Figure 36:
3.4.3.2
Functional diagrams for digital fault recorder and trip circuit monitoring
The digital fault recorder has 64 digital inputs. All pickup and trip signals from the protection stages are routed to trigger the digital fault recorder or alternatively only to be recorded by the digital fault recorder depending on the parameter settings.
DIGITAL FAULT RECORDER
DFR
IA-A IB-A IC-A IG-A I1-A I2-A I0-A VA-kV VB-kV VC-kV VG-kV Disabled AI#1 AI#2 AI#3 AI#4 AI#5 AI#6 AI#7 AI#8 AI#9 AI#10 AI#11 AI#12
DR DREC
GUID-478D7109-29FA-4702-8CF8-40EAFCA81206 V1 EN
Figure 37:
64
1MAC109554 C
OR
BI#1 BI#2 BI#3 BI#4 BI#5 BI#6 67/50N-1 Trip 67/50N-2 Trip 50N-3 Trip 46-1 Trip 46-2 Trip 46PD Pickup 49F AlmThm 49F Trip 50BF Retrip 50BF Backup Trip INR Pickup AFD-11 FADet AFD-21 FADet AFD-31 FADet AFD-11 Trip AFD-21 Trip AFD-31 Trip 79 PrgRec 79 Trip 79 UnsRec HIZ TCM-1 Alarm TCM-2 Alarm Spare 50G-3 50SEF BI#7 BI#8 BI#9 BI#10 BI#11 BI#12 BI#13 BI#14 BI#15 BI#16 BI#17 BI#18 BI#19 BI#20 BI#21 BI#22 BI#23 BI#24 BI#25 BI#26 BI#27 BI#28 BI#29 BI#30 BI#31 BI#32
DR DREC
OR
51G
GUID-14BE59BC-34F1-4AC8-A94C-DAC1790C2343 V1 EN
Figure 38:
65
1MAC109554 C
DR DREC
X120-1
X120-3
X110-1
X110-3
X110-5
X110-7
XA130-1
XA130-3
X120-2
X120-4
X110-2
X110-4
X110-6
X110-8
XA130-2
XA130-4
Figure 39:
Two separate TCM functions have been included: TCM-1 for PO3 (X100:16-19) and TCM-2 for PO4 (X100:20-23). Both functions are indicated in LED 9 or 8.
66
1MAC109554 C
TCM-2
TCS(2) TCSSCBR2
BLOCK ALARM
GUID-1B534756-98AC-408A-92F1-91ABA66E3A1C V1 EN
Figure 40:
3.4.3.3
67
1MAC109554 C
X100 16 17 15 19 18
OR
TRIP
BLOCK
Trip(1) TRPPTRC1
86/94-1
TRIP
CL_LKOUT
OR
PO3
RST_LKOUT
TCM-1
NOTES: 1) DASHED LINE INDICATES OPTIONAL INPUT BASED ON CONFIGURATION. 2) NON-LATCHED MODE AS DEFAULT.
79 OPEN_CB 52 EXE_OP
GUID-280A62F0-6D51-4BA4-BFB9-B373E670AADD V1 EN
Figure 41:
Master trip 1
68
1MAC109554 C
OR
TRIP
BLOCK
Trip(2) TRPPTRC2
86/94-2
+
TRIP
CL_LKOUT
OR
PO4
RST_LKOUT
TCM-2
1)
79 OPEN_CB 52 EXE_OP
GUID-F8A675E1-1C31-4C83-9569-CCB85F9ABC0E V1 EN
Figure 42:
Master trip 2
The 86/94-1 and 2 blocks provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binary input can be re-assigned to the RST_LKOUT input of the Master Trip Logics to enable external reset with a push button.
69
1MAC109554 C
52
52-1 EXE_OP
Always True
+ OR PO1
X100 6 7
Close Breaker
52CM
SSCBR1 TRV_T_OP_ALM BLOCK POSOPEN TRV_T_CL_ALM POSCLOSE DIFTRVTOPALM PRES_ALM_IN DIFTRVTCLALM PRES_LO_IN SPR_CHR_ALM SPR_CHR_ST SPR_CHR RST_IPOW RST_CB_WEAR OPR_ALM OPR_LO IPOW_ALM IPOW_LO CB_LIFE_ALM MON_ALM PRES_ALM PRES_LO OPENPOS INTERMPOS CLOSEPOS CBCM
5 6
BI 3 BI 4
OR
(CB COND MONITOR)
LED8
CB Spring Charged
GUID-F6999B37-F933-43D0-967B-3FE127FE7811 V1 EN
Figure 43:
The ENA_CLOSE input, which enables closing the circuit breaker, in the breaker control function block 52-1, is a combination of the status of the Master Trip Logics. The open operation is always enabled. If the ENA_CLOSE signal is completely removed from the breaker control function block 52-1 with the Signal Matrix tool, the function assumes that the breaker close commands are allowed continuously. The circuit-breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 8. The signal outputs from the IED are connected to give dedicated information on pickups and trips. Pickup of any protection function SO1 (X100:10-12) Trip of any protection function SO2 (X100:13-15)
70
1MAC109554 C
TP-1
1)
TP-1 TPGAPC1
PICKUP PICKUP TRIP
NOTE: 1) THERE ARE FOUR PULSE TIMERS AVAILABLE -ONE OF THEM IS USED FOR DEFAULT CONFIGURATIONS. ALL PULSE TIMERS INCLUDING TP-1 CAN BE MAPPED FOR SPECIFIC APPLICATIONS USING SMT IN PCM TOOLS.
GUID-17F7E87F-230E-496D-94C4-B188BA549CE9 V1 EN
Figure 44:
The TP-1 is a timer and used for setting the minimum pulse length for the outputs.
71
1MAC109554 C
Trip(1) TRPPTRC1
PICKUP TRIP PICKUP TRIP
Trip(2) TRPPTRC2
PICKUP TRIP PICKUP TRIP
GUID-7E976C74-3F94-4023-89FD-0E62CC5766C6 V1 EN
Figure 45:
3.4.3.4
72
1MAC109554 C
59-2
3U>(2) PHPTOV2
VA,VB,VC PICKUP BLOCK TRIP
59G
U0>(1) ROVPTOV1
VG BLOCK
PICKUP TRIP
27-1
3U<(1) PHPTUV1
VA,VB,VC PICKUP BLOCK TRIP
60-Pickup
27-2
VA,VB,VC PICKUP BLOCK TRIP
3U<(2) PHPTUV2
47
VA,VB,VC PICKUP BLOCK TRIP
U2> NSPTOV1
GUID-B8A1B7D7-4F8F-46CE-B2E2-D5AAD79D2219 V1 EN
Figure 46:
3.4.3.5
73
1MAC109554 C
ARC(1) ARCSARC1
IA, IB, IC IG BLOCK REM_FLT_ARC OPR_MODE TRIP ARC_FLT_DET
LED10
ARC(2) ARCSARC2
IA, IB, IC IG BLOCK REM_FLT_ARC OPR_MODE TRIP ARC_FLT_DET
ARC(3) ARCSARC3
IA, IB, IC IG BLOCK REM_FLT_ARC OPR_MODE TRIP ARC_FLT_DET
GUID-19A57C71-5055-4521-AA56-C8BD5F51EDA3 V1 EN
Figure 47:
Trip signals from the ARC protection function blocks are connected to the Master Trip Logic and also to the alarm LED 10 as a common arc flash detection. The autorecloser is configured to be initiated by operate signals from a number of protection stages through the INIT1-5 inputs. It is possible to create individual autoreclosing sequences for each input.
74
1MAC109554 C
AUTORECLOSING (Optional)
79 51P -trip 51N -trip 51G -trip 46-1 -trip 46-2 -trip 67/50P-1 -trip 67/50P-2 -trip 67/50N-1 -trip 67/50N-2 -trip 67/51P -trip 67/51N -trip 50P-3 -trip 50N-3 -trip 50G-3 -trip 52 -selected AFD-1 -trip AFD-2 -trip AFD-3 -trip External AR Blocking X120 BI 4 49F -InhRec X120 BI 3 (CB Open)
GUID-FE025888-1CCB-4B71-9BB5-2F188592AE62 V1 EN
OR
O->I DARREC1
PROT_CRD INIT_1 INIT_2 OPEN CB CLOSE CB INPRO UNSUC_RECL AR_ON LOCKED
OR
RECLOSER LOCKOUT
LED 7
OR OR
OR
Figure 48:
Autoreclosing
The autoreclosing function can be blocked with the INHIBIT_RECL input. As a default, the operation of some selected protection functions is connected to this input. A control command to the circuit breaker, either local or remote, will also block the autoreclose function via the 52-1-selected signal. The circuit breaker availability for the autoreclosure sequence is expressed with the CB_RDY input in 79. In the configuration, this signal is not connected to any of the binary inputs. As a result, the function assumes that the breaker is available all the time.
3.4.3.6
75
1MAC109554 C
BI 1 (Blocking)
BLOCK ENA_MULT
OR
86/94LED
TRIP_NEUT TRIP_NEUT
TRIP(1) LEDPTRC
50G-3
I0>>>(1) EFIPTOC1
IG BLOCK ENA_MULT PICKUP TRIP
TIME TRIP
LED5
OR
INSTANTANEOUS TRIP
LED 6
GUID-C91BD513-143F-4154-A045-399457B2D796 V1 EN
Figure 49:
3.4.3.7
OR
I0>(3) EFLPTOC3
PICKUP TRIP
50N-3
I0>>>(2) EFIPTOC2
PICKUP BLOCK TRIP
GUID-D9DBE355-6C7A-4D42-A679-CF3C2FAD22B9 V1 EN
Figure 50:
76
1MAC109554 C
PHIZ1 PHIZ1
HIZ DETECTION
BLOCK
TRIP
LED11
GUID-81DC07F7-4A53-4918-8FDD-66BD24B6A191 V1 EN
Figure 51:
The sensitive earth-fault protection (50SEF) and high impedance fault detection (HIZ) provide protection against high impedance faults. If the load unbalance is high, 50SEF needs to be set high to avoid misoperations which renders 50SEF ineffective for such applications. In those cases, HIZ can provide detection which would otherwise be undetected.
77
78
1MAC109554 C
Section 4
4.1
4.1.1
Current transformers
Current transformer requirements for non-directional overcurrent protection
For reliable and correct operation of the overcurrent protection, the CT has to be chosen carefully. The distortion of the secondary current of a saturated CT may endanger the operation, selectivity, and co-ordination of protection. However, when the CT is correctly selected, a fast and reliable short circuit protection can be enabled. The selection of a CT depends not only on the CT specifications but also on the network fault current magnitude, desired protection objectives, and the actual CT burden. The protection settings of the IED should be defined in accordance with the CT performance as well as other factors. Appropriate 'C' class CT should be used based on the total resistances of the CT secondary circuit. If other accuracy class CTs are used then refer the following discussions.
4.1.1.1
5P 10P
79
1MAC109554 C
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent protection. The 5P class provides a better accuracy. This should be noted also if there are accuracy requirements for the metering functions (current metering, power metering, and so on) of the IED. The CT accuracy primary limit current describes the highest fault current magnitude at which the CT fulfils the specified accuracy. Beyond this level, the secondary current of the CT is distorted and it might have severe effects on the performance of the protection IED. In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy limit factor (Fn) and is proportional to the ratio of the rated CT burden and the actual CT burden. The actual accuracy limit factor is calculated using the formula:
Fa Fn
A071141 V1 EN
Sin + Sn Sin + S
Fn Sin S
the accuracy limit factor with the nominal external burden Sn the internal secondary burden of the CT the actual external burden
4.1.1.2
80
1MAC109554 C
81
1MAC109554 C
The following figure describes a typical medium voltage feeder. The protection is implemented as three-stage definite time non-directional overcurrent protection.
A071142-ANSI V2 EN
Figure 52:
The maximum three-phase fault current is 41.7 kA and the minimum three-phase short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is calculated to be 59. The pickup current setting for low-set stage (51P) is selected to be about twice the nominal current of the cable. The trip time is selected so that it is selective with the next IED (not visible in the figure above). The settings for the high-set stage and instantaneous stage are defined also so that grading is ensured with the downstream protection. In addition, the pickup current settings have to be defined so that the IED operates with the minimum fault current and it does not trip with the maximum load current. The settings for all three stages are as in the figure above. For the application point of view, the suitable setting for instantaneous stage (50P-3) in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the criteria given by the current transformer selection formula is fulfilled and also the IED setting is considerably below the Fa. In this application, the CT rated burden could have been selected much lower than 10 VA for economical reasons.
82
1MAC109554 C
Section 5
5.1
5.1.1
5.1.1.1
Inputs
Energizing inputs
Phase currents
The IED can also be used in single or two-phase applications by leaving one or two energizing inputs unoccupied. However, at least terminals X120/7-8 must be connected.
Table 23:
Terminal X120-7, 8 X120-9, 10 X120-11, 12
5.1.1.2
Ground current
Table 24:
Terminal X120-13, 14
5.1.1.3
Phase voltages
Table 25:
Terminal X130-11, 12 X130-13, 14 X130-15, 16
83
1MAC109554 C
5.1.2
5.1.3
Binary inputs
The binary inputs can be used, for example, to generate a blocking signal, to unlatch output contacts, to trigger the digital fault recorder or for remote control of IED settings. Terminals X120/1-6 are binary input terminals. An additional BIO module can be included in slot 110.
Table 28:
Terminal X110-1 X110-2 X110-3 X110-4 X110-5 X110-6 X110-6 X110-7 X110-8 X110-9 X110-9 Table continues on next page
84
1MAC109554 C
Table 29:
Terminal X120-1 X120-2 X120-3 X120-2 X120-4 X120-2 X120-5 X120-6
Table 30:
Terminal X130-1 X130-2 X130-2 X130-3 X130-4 X130-5 X130-5 X130-6 X130-7 X130-8 X130-8 X130-9
85
1MAC109554 C
If the IED is provided with the optional communication module with light sensor inputs, the pre-manufactured lens-sensor fibers are connected to inputs X13, X14 and X15, see the terminal diagrams.For further information, see arc flash detector. The IED is provided with connection sockets X13, X14 and X15 only if the optional communication module with light sensor inputs has been installed. If the arc flash detector option is selected when ordering an IED, the light sensor inputs are included in the communication module.
Table 31:
Terminal X13 X14 X15
5.2
5.2.1
Outputs
Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. On delivery from the factory, the trip signals from all the protection stages are routed to PO3 and PO4.
Table 32:
Terminal X100-6 X100-7 X100-8 X100-9 X100-15 X100-16 X100-17 X100-18 X100-19 X100-20 X100-21 Table continues on next page
Output contacts
Description PO1, NO PO1, NO PO2, NO PO2, NO PO3, NO (TCM resistor) PO3, NO PO3, NO PO3 (TCM1 input), NO PO3 (TCM1 inputr), NO PO4, NO (TCM resistor) PO4, NO
86
1MAC109554 C
5.2.2
Table 34:
Terminal X110-14 X110-15 X110-16 X110-17 X110-18 X110-19 X110-20 X110-21 X110-22 X110-23 X110-24
87
1MAC109554 C
Table 35:
Terminal X130-10 X130-11 X130-12 X130-13 X130-14 X130-15 X130-16 X130-17 X130-18
5.2.3
IRF
The IRF contact functions as an output contact for the self-supervision system of the protection IED. Under normal operating conditions, the IED is energized and the contact is closed (X100/3-5). When a fault is detected by the self-supervision system or the auxiliary voltage is disconnected, the output contact drops off and the contact closes (X100/3-4).
Table 36:
Terminal X100-3 X100-4 X100-5
IRF contact
Description IRF, common Closed; IRF, or Vaux disconnected Closed; no IRF, and Vaux connected
88
1MAC109554 C
Section 6 Glossary
Section 6
Glossary
100BASE-FX A physical media defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses fibre-optic cabling 100BASE-TX A physical media defined in the IEEE 802.3 Ethernet standard for local area networks (LANs) that uses twisted-pair cabling category 5 or higher with RJ-45 connectors ANSI BI BI/O BO CB CT DFR DNP3 American National Standards Institute Binary input Binary input/output Binary output Circuit breaker Current transformer Digital fault recorder A distributed network protocol originally developed by Westronic. The DNP3 Users Group has the ownership of the protocol and assumes responsibility for its evolution. Electromagnetic compatibility Generic Object Oriented Substation Event Human-machine interface Hardware International standard for substation communication and modelling Intelligent electronic device A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol. Inter-Range Instrumentation Group's time code format B Local area network Connector type for glass fiber cable Liquid crystal display
89
Section 6 Glossary
1MAC109554 C
Light-emitting diode Local human-machine interface A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. Medium voltage Protection and Control IED Manager Power output Galvanic connector type Serial interface standard Serial link according to EIA standard RS485 Signal output Transmission Control Protocol/Internet Protocol Trip-circuit supervision Wide area network Web human-machine interface
90
91
Contact us
ABB Inc. Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Phone +1 (800) 523-2620 Phone +1 954-752-6700 Fax +1 954 345-5329 www.abb.com/substationautomation