Sie sind auf Seite 1von 36

Chapter 2

Reactive Power Compensation of Transmission Line


Index 2.1 General Introduction 2.2 Power control in Transmission line 2.2.1 Convectional Control Mechanism 2.2.1.1 Automatic Generation Control (AGC) 2.2.1.2 Excitation Control 2.2.1.3 Phase-Shifting Transformers 2.2.14 2.3 Uncompensated Transmission lines 2.3.1 Load Compensation. 2.3.2 System compensation. 2.3.3 Lossless Distributed Parameter of Lines. 2.4 Basic principal of power compensation in transmission system 2.4.1 Shunt Compensation. 2.4.2 Series Compensation. 2.4.3 Stability. 2.4.4 Transmission line Parameters. 2.4.4.1 Efficiency and regulation of lines. 2.4. 4.2 Length of transmission lines. 2.4.4.3 Surge impedance. 2.4.4.4 Ferranti-effect. 2.5 Experimental Transmission Line model 2.5.1 Transmission Line model of 750km ( /8) transmission line. 2.5.2 Design of scale down Artificial Transmission line. 2.5.3 Design of reactor for artificial line. 2.5.4 Design of capacitor for shunt compensator. 2.6 Flexible AC Transmission Systems (FACTS) Controllers 2.6.1Introduction 2.6.2 Shunt-connected controllers 2.6.21 Static Var Compensator (SVC) 2.6.1.2 Converter-based STATCOM Compensator 2.6.3 Series-connected controllers 2.6.4Combined Series-Series Controller 2.6.5 Combined Series-Shunt Controllers 2.6.6 Various other Types of FACTS Controllers 2.7 Conclusion
1|P a ge

Chapter 2
Reactive Power Compensation of Transmission Lines
2.1 General Introduction Modern civilization depends heavily on the consumption of electrical energy for industrial, agriculture, domestics, commercial and social purposes. The demand for low cost electrical energy has lead to the development of generation sites remotely located from the load centers. Remote generating stations include hydroelectric stations, fossil fuel stations, geothermal stations and tidal-power plants, wind power plant which are site bound; and nuclear Power plants built at distant from urban centers. Hence generation of bulk power at remote locations necessitates the use of transmission lines to connect generation sites to distant distribution network. Furthermore, to increase system reliability, multiple lines that connect load centers to several sources, led to the development of complex interconnected electrical transmission networks. An electrical power transmission network comprises mostly 3-phase alternating-current (ac) transmission lines operating at different transmission voltages (generally at 230 kV and higher). The choice of transmission voltage basically depends on distance of transmission (V= 1KV per km ) With increasing requirement of power-transmission capacity and/ or longer transmission distances, the transmission voltages continue to increase( as P V2); indeed, increases in transmission voltages are linked closely to decreasing transmission losses. For a system comprising multiple sources and numerous loads, line impedance and the voltages at its terminals determine the flow of active and reactive powers. The long-distance separation of a generating station from a load center requiring long transmission lines of high capacity and, active- and reactive-power control in ac transmission networks was exercised by carefully adjusting transmission line impedances, as well as regulating terminal voltages by generator excitation control and by transformer tap changers. During the past two decades, the increase in electrical energy demand has presented higher requirements from the power industry. More power plants, substations, and transmission lines need to be constructed. However, the most commonly used
2|P a ge

devices in present power grid are the mechanically-controlled circuit breakers. The long switching periods and discrete operation make them difficult to handle the frequently changed loads smoothly and damp out the transient oscillations quickly. In order to compensate these drawbacks, large operational margins and redundancies are maintained to protect the system from dynamic variation and recover from faults. This not only increases the cost and lowers the efficiency, but also increases the complexity of the system and augments the difficulty of operation and control. Severe black-outs happened recently in power grids worldwide and these have revealed that conventional transmission
systems are unable to manage the control requirements of the complicated interconnections and variable power flow.

Therefore, investment is necessary for the studies into the security and stability of the power grid, as well as the improved control schemes of the transmission system. Different approaches such as reactive power compensation and phase shifting have been applied to increase the stability and the security of the power systems. The demands of lower power losses, faster response to system parameter change, and higher stability of system have stimulated the development of the Flexible AC Transmission systems (FACTS) [1]. Based on the success of research in power electronics switching devices and advanced control technology, FACTS has become the technology of choice in voltage control, reactive/active power flow control, transient and steady-state stabilization that improves the operation and functionality of existing power transmission and distribution system [2], [3]. The achievement of these studies enlarge the efficiency of the existing generator units, reduce the overall generation capacity and fuel consumption, and minimize the operation cost.

2.11 CONVENTIONAL CONTROL MECHANISMS In the foregoing discussion, a lack of control on active- and reactive-power flow on a given line, embedded in an interconnected ac transmission network, was stated. Also, to maintain steady-state voltages and, in selected cases, to alter the power-transmission capacity of lines, traditional use of shunt and series impedances was hinted. In a conventional ac power system, however, most of the controllability exists at generating
3|P a ge

stations. For example, generators called spinning reserves maintain an instantaneous balance between power demand and power supply. These generators, in fact, are purposely operated at reduced power. Also, to regulate the system frequency and for maintaining the system at the rated voltage, controls are exercised on selected generators. 2.1.2 Automatic Generation Control (AGC) The megawatt (MW) output of a generator is regulated by controlling the driving torque, Tm, provided by a prime-mover turbine. In a conventional electromechanical system, it could be a steam or a hydraulic turbine. The needed change in the turbineoutput torque is achieved by controlling the steam/ water input into the turbine. Therefore, in situations where the output exceeds or falls below the input, a speedgoverning system senses the deviation in the generator speed because of the loadgeneration mismatch, adjusts the mechanical driving torque to restore the power balance, and returns the operating speed to its rated value. The speed-governor output is invariably taken through several stages of mechanical amplification for controlling the inlet (steam/ water) valve/ gate of the driving turbine. Figure 1.1 shows the basic speed-governing system of a generator supplying an isolated load. The operation of this basic feedbackcontrol system is enhanced by adding further control inputs to help control the frequency of a large interconnection. In that role, the control system becomes an automatic generation control (AGC) with supplementary signals.

4|P a ge

Figure A speed-governor system.


2.1.3 Excitation Control

The basic function of an exciter is to provide a dc source for field excitation of a synchronous generator. A control on exciter voltage results in controlling the field current, which, in turn, controls the generated voltage. When a synchronous generator is connected to a large system where the operating frequency and the terminal voltages are largely unaffected by a generator, its excitation control causes its reactive power output to change. In older power plants, a dc generator, also called an exciter, was mounted on the main generator shaft. A control of the field excitation of the dc generator provided a controlled excitation source for the main generator. In contrast, modern stations employ either a brushless exciter (an inverted 3-phase alternator with a solid-state rectifier connecting the resulting dc source directly through the shaft to the field windings of the main generator) or a static exciter (the use of a station supply with static rectifiers). An excitation-control system employs a voltage controller to control the excitation voltage. This operation is typically recognized as an automatic voltage regulator (AVR). However, because an excitation control operates quickly, several stabilizing and protective signals are invariably added to the basic voltage regulator. A power-system stabilizer (PSS) is implemented by adding auxiliary damping signals derived from the shaft speed, or the terminal frequency, or the poweran effective and frequently used technique for enhancing small-signal stability of the connected system. Figure 1.3 shows the functionality of an excitation-control system.

Figure A conceptual block diagram of a modern excitation controller.

2.1.4 Transformer Tap-Changer Control In addition to increasing and decreasing nominal voltages, many transformers are equipped with tap-changers to realize a limited range of voltage control. This tap control can be carried out manually or automatically. Two types of tap changers are usually available: offload tap changers, which perform adjustments when deenergized, and on5|P a ge

load tap changers, which are equipped with current-commutation capacity and are operated under load. Tap changers may be provided on one of the two transformer windings as well as on autotransformers. Because tap-changing transformers vary voltages and, therefore, the reactivepower flow, these transformers may be used as reactive-power-control devices. On-load tap-changing transformers are usually employed to correct voltage profiles on an hourly or daily basis to accommodate load variations. Their speed of operation is generally slow, and frequent operations result in electrical and mechanical wear and tear. 2.1.5 Phase-Shifting Transformers A special form of a 3-phaseregulating transformer is realized by combining a transformer that is connected in series with a line to a voltage transformer equipped with a tap changer. The windings of the voltage transformer are so connected that on its secondary side, phase-quadrature voltages are generated and fed into the secondary windings of the series transformer. Thus the addition of small, phase-quadrature voltage components to the phase voltages of the line creates phase-shifted output voltages without any appreciable change in magnitude. A phase-shifting transformer is therefore able to introduce a phase shift in a line. Figure 1.4 shows such an arrangement together with a phasor diagram. The phasor diagram shows the phase shift realized without an appreciable change in magnitude by the injection of phase-quadrature voltage components in a 3-phase system.

6|P a ge

Figure A phase-shifting transformer: (a) a schematic diagram and (b) a phasor diagram.

When a phase-shifting transformer employs an on-load tap changer, controllable phase-shifting is achieved. The interesting aspect of such phase shifters is that despite their low MVA capacity, by controlling the phase shift they exercise a significant realpower control. Therefore, they are used to mitigate circulating power flows in interconnected utilities. A promising application of these devices is in creating activepower regulation on selected lines and securing active-power damping through the incorporation of auxiliary signals in their feedback controllers. From this description, it is easy to visualize that an incremental in-phase component can also be added in lines to alter only their voltage magnitudes, not their phase.

It is found that reactive power Qr- is directly proportional to the magnitude of voltage drop. So, voltage and reactive power control are analogous to each other and their control is interrelated. For a good quality of power supply voltage at the consumer end must be kept constant irrespective of the type or magnitude of load. The maintenance of voltage is a complicated problem as system is supplied from various sources and is supplied to various consumers at various voltage levels. In order to maintain the voltage under prescribed limits, it is necessary to maintain the balance of reactive power in the system that is reactive power generation should be equal to reactive power consumption. Any discrepancy in these two quantities leads to voltage exceeding prescribed limits thereby damaging various appliances connected to the system. Also the presence of reactive power in the system leads to undesirable heating and lowering of the system stability. So, compensation of transmission lines is necessary. For this, various compensating techniques are adopted.es is necessary. For this, various compensating techniques are adopted. 2.1.6 Fixed or mechanically switched capacitors Shunt capacitors were first employed for power factor correction in the year 1914 [16]. The leading current drawn by the shunt capacitors compensates the lagging current drawn
7|P a ge

by the load. The selection of shunt capacitors depends on many factors, the most important of which is the amount of lagging reactive power taken by the load. In the case of widely fluctuating loads, the reactive power also varies over a wide range. Thus, a fixed capacitor bank may often lead to either over-compensation or under-compensation. Variable VAR compensation is achieved using switched capacitors [17]. Depending on the total VAR requirement, capacitor banks are switched into or switched out of the system. The smoothness of control is solely dependent on the number of capacitors switching units used. The switching is usually accomplished using relays and circuit breakers. However, these methods based on mechanical switches and relays have the disadvantage of being sluggish and unreliable. Also they generate high inrush currents, and require frequent maintenance [16].

2.1.7 Synchronous Condensers Synchronous condensers have played a major role in voltage and reactive power control for more than 50 years. Functionally, a synchronous condenser is simply a synchronous machine connected to the power system. After the unit is synchronized, the field current is adjusted to either generate or absorb reactive power as required by the ac system. The machine can provide continuous reactive power control when used with the proper automatic exciter circuit. Synchronous condensers have been used at both distribution and transmission voltage levels to improve stability and to maintain voltages within desired limits under varying load conditions and contingency situations. However, synchronous condensers are rarely used today because they require substantial foundations and a significant amount of starting and protective equipment. They also contribute to the short circuit current and they cannot be controlled fast enough to compensate for rapid load changes. Moreover, their losses are much higher than those associated with static compensators, and the cost is much higher compared with static compensators. Their advantage lies in their high temporary overload capability

8|P a ge

2.3 Uncompensated transmission lines To develop a good, qualitative understanding of the need for reactive-power control, let us consider a simple case of a lossless short-transmission line connecting a source Vs to a load Z J (For simplicity, the line is represented only by its inductive reactance XL) Figure 2.2 shows such a network with its parameters, as well as a phasor diagram showing the relationship between voltages and currents. From Fig. 2.2(b), it is clear that between the sending- and the receiving-end voltages, a magnitude variation, as well as a phase difference, is created. The most significant part of the voltage drop in the line reactance (DV1 c j IxXl) is due to the reactive component of the load current, Ix. To keep the voltages in the network at nearly the rated value, two control actions seem possible: 1. load compensation, and 2. system compensation. 2.3.1 Load Compensation It is possible to compensate for the reactive current Ix of the load by adding a parallel capacitive load so that Ic c Ix. Doing so causes the effective power factor of the combination to become unity. The absence of Ix eliminates the voltage drop DV1, bringing Vr closer in magnitude to Vs; this condition is called load compensation. Actually, by charging extra for

Figure 2.2 A short, lossless transmission line feeding a load.

9|P a ge

Figure 2.3 The reactive-power control for voltage regulations. supplying the reactive power, a power utility company makes it advantageous for customers to use load compensation on their premises. Loads compensated to the unity power factor reduce the line drop but do not eliminate it; they still experience a drop of V2 from jIrXL .

2.3.1.2 System Compensation To regulate the receiving-end voltage at the rated value, a power utility may install a reactive-power compensator as shown in Fig. 2.3. This compensator draws a reactive current to overcome both components of the voltage drop V1 and V2 as a consequence of the load current Il through the line reactance XL. To compensate for V2, an additional capacitive current, Ic, over and above Ic that compensates for Ix, is drawn by the compensator. When IcXlc V2, the receiving-end voltage, VR, equals the sendingend voltage, VS. Such compensators are employed by power utilities to ensure the quality of supply to their customers [1].

2.3.1.3 Lossless Distributed Parameter of Lines Most power-transmission lines are characterized by distributed parameters: series resistance, R ; series inductance, L; shunt conductance, G; and shunt capacitance, C- all per-unit (pu) length. These parameters all depend on the conductors size, spacing, clearance above the ground, and frequency and temperature of operation. In addition, these parameters depend on the bundling arrangement of the line conductors and the nearness to other parallel lines. The characteristic behavior of a transmission line is dominated by its L and C parameters. Parameters R and G account for the transmission
10 | P a g e

losses. The fundamental equations governing the propagation of energy along a line are the following wave equations:
d 2V ! zyI dx 2 d2I ! zyI dx 2

Where zy = (R + jQL) (G + jQC). For a lossless line, the general solutions are given as V ( x) ! VS cos F x  jZ 0 I s sin F x I ( x ) ! Is cos F x  j VS sin F x Z0

These equations are used to calculate voltage and current anywhere on line, at a distance x from the sending end, in terms of the sending-end voltage and current and the line parameters. In Eqs. (2.4) and (2.5), Z0 ! L C = the surge impedance or characteristic impedance

F ! [ LC

rad/km = the wave number = the electrical length of an a-km line

F a ! [ LCa rad

where L is the line inductance in henries per kilometer (H/ km), C is the line shunt capacitance in farads per kilometer (F/ km), and 1/ LC is the propagation velocity of electromagnetic effects on the transmission line. (It is less than the velocity of light.) From Eq. (2.5), we get IS ! V S cos F a  V R jZ 0 sin F a

If V S ! VS 0o and V R ! VR  H ! VR (cos H  j sin H ) then IS ! VR sin H  j (VR cos H  VS cos F a) Z 0 sin F a

Therefore, the power at the sending end is given as

S S ! PS  jQS ! VS I S

11 | P a g e

VSVR sin H V2 cos F a  VSVR cos H  Z 0 sin F a Z 0 sin F a (7) Likewise, power at the receiving end is given as VSVR sin H jVR 2 cos F a  VSVR cos H  Z 0 sin F a Z 0 sin F a (8)

S R ! PR  jQR ! 

Comparing Eqs. (2.7) and (2.8) and taking the directional notation of Fig. 2.4 into account, it is concluded that for a lossless line, PS =PR , as expected.However,

QS { QR because of the reactive-power absorption/ generation in theline. From Eqs. (2.7)


and (2.8), the power flow from the sending end to the receiving end is expressed as P! VS VR sin H Z 0 sin F a

In electrically short power lines, where F a is very small, it is possible to make a simplifying assumption that , sin F a ! F a or Z 0 sin F a ! Z 0 F a ! [ La where [ La ! X L is the total series reactance of a line. This substitution results in the following wellrecognized power equation: P! VS VR sin H XL (2.9)

Accordingly, the maximum power transfer is seen to depend on the line length.Then the power-transfer requirement for a given length of a line increases, higher transmission voltages of Vs and Vr must be selected. This chapter is not intended to provide a comprehensive analysis of transmission lines. Rather, its objective is to examine those aspects that enhance the understanding of the interplay between voltages on the line and the resulting reactive-power flows.

2.4 Basic principal of power compensation in transmission system.


12 | P a g e

Figure 2.2.1(a) shows the simplified model of a power transmission system. Two power grids are connected by a transmission line which is assumed lossless and represented by the reactance XL. V1 < 1 and V2 < 2 represent the voltage phasors of the two power grid buses with angle in Figure 2.1(b). = 12

between the two. The corresponding phasor diagram is shown

Figure 2.1 Power transmission system: (a) simplified model; (b) phase diagram The magnitude of the current in the transmission line is given by:

IL !

VL V1H1  V2 H 2 ! XL XL
V1  V2 cos H XL
V1 V1  V2 cos H XL

(2-1)

The active and reactive components of the current flow at bus 1 are given by

Id1 !

V2 SinH XL
V1V2 sin H XL

I q1 !

(2-2)

The active power and reactive power at bus 1 are given by: P! 1
,

Q1 !

(2-3)

Similarly, the active and reactive components of the current flow at bus 2 can be given by:

13 | P a g e

Id 2 !

V1 sin H XL

I q2 !

V2  V1 cos H XL

(2-4)

The active power and reactive power at bus 2 are given by:

P! 1

V1V2 sin H XL

Q2 !

V2 V2  V1 cos H XL

(2-5)

Equations (2-1) through (2-5) indicate that the active and reactive power/current flow can be regulated by controlling the voltages, phase angles and line impedance of the transmission system. From the power angle curve shown in Figure (c), the active power flow will reach the maximum when the phase angle is 90. In practice, a small angle is used to keep the system stable from the transient and dynamic oscillations [4]. Generally, the compensation of transmission systems can be divided into two main groups: shunt and series compensation.
2.4.1 Shunt compensation

Shunt compensation, especially shunt reactive compensation has been widely used in transmission system to regulate the voltage magnitude, improve the voltage quality, and enhance the system stability [5]. Shunt-connected reactors are used to reduce the line over-voltages, by consuming the reactive power, while shunt-connected capacitors are used to maintain the voltage levels by compensating the reactive power to transmission line. A simplified model of a transmission system with shunt compensation is shown in Figure 2.2(a). The voltage magnitudes of the two buses are assumed equal as V, and the phase angle between them is . The transmission line is assumed lossless and represented by the reactance XL. At the midpoint of the transmission line, a controlled capacitor C is shuntconnected. The voltage magnitude at the connection point is maintained as V.

14 | P a g e

Figure 2.2 Transmission system with shunt compensation: (a) simplified model; (b) phase diagram; (c) power-angle curve [2]

As discussed previously, the active powers at bus 1 and bus 2 are equal.

P ! P2 ! 2 1

H V2 sin XL 2

(2-6)

The injected reactive power by the capacitor to regulate the voltage at the mid-point of the transmission line is calculated as:

QC ! 4

H V2 (1  cos ) XL 2

(2-7)

From the power angle curve shown in Figure 2.2(c), the transmitted power can be significantly increased, and the peak point shifts from =90 to =180. The operation margin and the system stability are increased by the shunt compensation. The voltage support function of the midpoint compensation can easily be extended to the voltage support at the end of the radial transmission, which will be proven by the system
15 | P a g e

simplification analysis in a later section. The reactive power compensation at the end of the radial line is especially effective in enhancing voltage stabilit y
2.4.2 Series compensation

Series compensation aims to directly control the overall series line impedance of the transmission line. Tracking back to Equations (2-1) through (2-5), the AC power transmission is primarily limited by the series reactive impedance of the transmission line. A series-connected can add a voltage in opposition to the transmission line voltage drop, therefore reducing the series line impedance. A simplified model of a transmission system with series compensation is shown in Figure 2.3(a). The voltage magnitudes of the two buses are assumed equal as V, and the phase angle between them is . The transmission line is assumed lossless and represented by the reactance XL. A controlled capacitor is series-connected in the transmission line with voltage addition Ving. The phase diagram is shown in Figure 2.3(b)

Figure 2. 3 Transmission system with series compensation: (a) simplified model; (b) phase diagram; (c) power-angle curve [2]
16 | P a g e

Defining the capacitance of C as a portion of the line reactance,

X C ! kX L
The overall series inductance of the transmission line is,

(2-8)

X ! X L  X C ! (1  k ) X L
The active power transmitted is,

(2-9)

V2 sin H P! (1  k ) X L
The reactive power supplied by the capacitor is calculated as:

(2-10)

QC ! 2

V2 k (1  cos H ) X L (1  k ) 2

(2-11)

In Figure 2.3(c) shows the power angle curve from which it can be seen that the transmitted active power increases with k.

2.6 Transmission line Parameters


An Electrical transmission line can be represented by a series combination of resistance, inductance and shunt combination of conductance and capacitance. these parameters are symbolized as R,L,G and C respectively, of these R and G are least important in the sense that they do not effect much the total equivalent impedance of the line and hence the transmission capacity. They are of course very much importance when transmission efficiency and economy are to be evaluated as they completely determine the real transmission line losses The resistance of a conductor is given by R= power loss in conductor / I2ohms Where R is the effective resistance of the conductor and I the current flowing through the conductor. The effective resistance is equal to the D.C resistance of the conductor only if the current is uniformly distributed throughout the section of the conductor. Difference in the D.C resistance and effective resistance to frequencies less
17 | P a g e

than 50 Hz is less than 1 percent for copper conductors of section less than 350,000 circular mils. The loss on the overhead transmission line is due to 1. Ohmic loss in the power conductors 2. corona loss 3. leakage at the insulators which support the lines at the towers

2.6.1 Efficiency and regulation of lines The performance of lines is meant the determination of efficiency and regulation of lines  
         



(2-19)

Regulation of a line is defined as the change in the receiving end voltage, expressed in percent of full load voltage, from no load to full load, keeping the sending end voltage and frequency constant. Expressed mathematically    (2-20)

Where VR is the receiving end under no load condition and VR1 the receiving end voltage under full load condition. It is to be noted here that VR and VR1 are the magnitudes of voltage.

2.6.2 Length of transmission lines A transmission line is a set of conductors being run from one place to another supported on transmission towers. Such lines, therefore, have foure distributed parameters, series resistance and inductance and shunt capacitance and conductance. The voltage and current vary harmonically along the line with respect to the distance of the point under consideration. This observation is very important in representing the lines of different lengths. It is to be noted that the electrical power is being transmitted over the
18 | P a g e

overhead lines at approximately the speed of light .in order to get one full wave variation of voltage or current on the line, the length of the line for 50 Hz supply will be given by
f P !V

(2-21) is wavelength i.e the length of the in this case and v

where f is the frequency of supply ,

the velocity of the wave i.e the velocity of light


P! V ! 6000 Km f

(2-22)

This means that if the length of the line is 6000 Km the voltage or current wave at the two ends of the line. Transmission lines have been classified as lang and medium and short lines depending on the length of the lines. These are Upto 80km---short line 80 to 160km-----medium line Above 160km----long transmission line The transmission system selected for our study is a long transmission line with a 4 network representation. The resistance of a line has been neglected and the line is considered to be purely reactive. It means that I2R losses are neglected. This is because the project is mainly concerned with the reactive power control, and the resistance has no effect on the reactive power absorbed or generated by the system. The load is considered purely resistive.

2.6.3 Surge impedance The surge impedance of a typical overhead line is 400. The transmission network is so selected as to satisfy these conditions. Surge impedance: The surge impedance of a line is calculated from the formula

19 | P a g e

ZS !

L C

(2-23)

Where ZS=Surge Impedance, L=line Inductance/km and C=line capacitance./km Practical Considerations In general, the values of line parameters L and C remain reasonably independent of the transmission voltage. For example, typical values of L and C may lie in the following ranges: L= the line inductance/ km =0.780.98 mH/ km C= the line capacitance/ km =12.115.3 nF/ km On the basis of these parameters, the surge impedance, ZS, lies in the range of 225 to 285.

2.6.4 Ferranti-effect When a long line is operating under no load or light load condition, the receiving end voltage is greater than sending end voltage, this is known as Ferranti-effect. Ferrantieffect can be given by approximating the distributed parameters of the line by lumped impedance shown in figure below. Since usually the capacitive reactance of the line is quite large as compared to the inductive reactance, under no load or light loaded condition the line current is of leading p.f. The charging current produces drop in the reactance of the line which is in phase opposition to the receiving end voltage and hence the sending end voltage becomes smaller than the receiving end voltage. Ferranti-effect is based on the net reactive power flow on the line .it is shown that if the reactive power generated at a point is more than the reactive power absorbed, the voltage at that point becomes higher than the normal value and vice versa. The inductive reactance of the line is a sink for the reactive power where as the shunt capacitances generate reactive power. In fact, if the line loading corresponds to the surge impedance loading, the voltage is same everywhere as the reactive power absorbed than equals the reactive power generated by the lines. the SIL,therefore ,gives definite meaning to the terms lightly loaded or fully loaded lines. if the loading is less than SIL, the reactive power generated

20 | P a g e

is more than absorbed, therefore the receiving end voltage is greater than the sending end voltage. This explains, therefore, the phenomenon due to Ferranti-effect

Fig 3.2(a) Line representation under no load

Fig 3.2(b) phasor diagram

2.6.5 Transmission line model of 750km ( /8) transmission line

The implementation of the Reactive power compensation schemes are usually carried out on long lines (>250 km of length).A specific long line with its parameters as was chosen for this work. The specifications of the line are as follows: Power rating of the line: Voltage rating of the line: Resistance: Inductive reactance: Shunt admittance: works out to be: Series Inductance L: Shunt capacitance C: Propagation Constant : 1.525 x 10-5 H per km. 11.3 nF per km. 4.15 x 10-6. V2 Z base 100 MVA 220 kV. 0.073 0.4794 per km. per km.

3.35 mho per km.

Therefore at a frequency of 50 Hz, the values of series inductance and shunt capacitance

From equation Power !

21 | P a g e

Base Impedance of 220kv line Z base Therefore SIL is

400 v103 V2 = ! 100 v10 6 Power

= 484
2

V 2 nom Po ! Zo

(220 v 103 ) 2 = 484

=100MW

Symetrical Lines : When the voltage magnitudes at the two ends of line are equal , that is Vs=Vr, the line is said to be symmetrical .Because of power networks operate as voltage sources, attempts are made to hold almost all node voltage at nearly rated values From equation 7 and 8 following relationship are derived

V2 Ps ! - Pr ! sin H Z 0 sin F a
equation

and

QS !

V 2 cos F a  V 2 cos H Zo sin F a

Therefore for this line to operate as symmetrical line VS=Vr =220 kV We have from

(220 v103 )2 sin H Ps ! 484sin ([ lc)750

2.5.2 Scale down parameters of artificial transmission line This long line with the parameters obtained as above is scaled down for the fabrication of the Scale down model by choosing a base of 5 kVA and 400 V. The scale down model of the transmission line is obtained by maintaining the per unit values of the resistance and reactance the same as that of the actual long line. R p.u. = Actual Resistance*BaseMVA/(Base kV)2 = 1.508*10-4 p.u. er unit value of Reactance XL p.u. = Actual Reactance*Base MVA/(Base kV) 2
22 | P a g e

= 9.904*10-4 p.u Therefore the actual values of the resistance and reactance in the scaled down model work out to be:Actual value of Resistance RSD = Per unit value of resistance*Base impedance = 0.0048 per km. Actual value of Reactance XLSD = Per unit value of reactance*Base impedance = 0.0316 per km . Inductance LSD = 0.10089 mH per km. The value of the shunt capacitance is obtained by keeping the ratios of XL / R and constant. Actual value of shunt capacitance C s.d = / L s.d = 0.1625 x 10-6 F per km.

Using the above data the transmission line was fabricated to represent a 750 km line by as that of 50 km assembling six pi models comprising of series resistance and inductance and shunt capacitance with their values line model and the Six Pi models were connected in series . Thus in the scaled down model For long lines the reactance r mpensation can be evaluated as Phase constant, = 2* * f * (L*C) = 1.266*103 radians. Surge impedance, Zc = (L/C) = 24.81 Under no load conditions there is no real power transferred (Since IR=0). Therefore under ideal conditions VS =VR But practically, in most of the transmission lines the Ferranti Effect is predominant and the receiving end voltage is greater than that of the sending end voltage at light loads. Henceforth a shunt reactor is installed in the line for absorbing the excess VARs in the line. The value of the reactance required for this purpose was evaluated as follows

23 | P a g e

2.5.3 Reactor design for artificial line The reactor to be employed for shunt compensation is expected to have the following ratings: Voltage: 230V Current: 6A. The volt-ampere rating of the reactor is therefore 1370 VA. Henceforth an iron-core reactor with air gap in the core is selected

Linearity test

The reactor was fabricated and it was tested for its linearity. The average inductive reactance of the reactor was found to be 39.5 ohms. It was found that the Reactor responded linearly in the operating region with an average inductance of 0.127H . Under lagging load conditions, sometimes shunt capacitor compensation may be required .So, the amount of capacitive compensation required at different lengths of the transmission line are calculated and implemented as below

Calculation of the value of shunt compensator under loaded condition Specifications of the 3 Voltage : 400 V Power : 5 kVA, Calculation of capacitive reactance for a 1 750km long line x = Zc*sin l = 22.668 100% compensation is obtained by making the sending end voltage and the receiving end voltage equal .( VS = VR ). The reactive power in the line Q = VR * ( cos - cos l ) / x = 3.652* kVAR. The reactive power demanded by the load QL= Load kVA* sin ( )
24 | P a g e

load:

= 4.33 kVAR Therefore ,Net Reactive power to be injected, Qi = Q QL =0.677 kVAR The capacitive Reactance Xc = VR / Qi = 236.178 . The value of Capacitor to be installed ,C= 1 / (2* C = 13.47* 10-6 F. * f * Xc)

Calculation of capacitive reactance for a 3 300 km long line x = Zc*sin l = 8.4053 sin = PR * x / VR sin = 0.1313 = 0.1317 radians. 100% compensation is obtained by making the sending end voltage and the receiving end voltage equal .( VS = VR ). The reactive power in the line Q = VR * ( cos - cos l ) / x = 1.1943 kVAR. The reactive power demanded by the load QL = Load kVA* sin ( ) = 4.33 kVAR = 3.1357 kVAR The capacitive Reactance Xc = VR / Qi=51.0253 . The value of Capacitor to be installed , C= 1 / (2* = 62.36* 10-6 F. * f * Xc)

25 | P a g e

Design aspect for compensation of reactive power


In case of radial transmission line let sending end real power Flow is PS, sending end reactive power flow QS , receiving end real power flow PR and receiving end reactive power flow QR can be express as

Ps !
QS !

1 VS VR SinH X
1 VS 2  VS VR CosH X

(2-12)

(2-13) (2-14)

PR !
QR !

1 VS VR SinH X
1 VS  VS VR CosH  VR 2 X

(2-15)

From the above equations we can conclude that transfer of real power depends only on angle , the power angle and not on the relative magnitudes of sending end and receiving end voltage .More over the transmitted power varies approximately as the square of voltage level .The maximum power transfer takes place when = 900

PR ( max ) ! PS (max) !

VS VR X

(2-16)

From equations (2.13) and (2.15) it is clear that reactive power Q will flow in the direction of lower voltage. If the system operates with = 0, the average reactive power flow over the line is given as

26 | P a g e

Qavg !

QS  QR 1 2 VS  VR ! 2 2X

(2-17)

This equation (2.17) shows that the reactive power flow strongly depends on the difference in square of voltages. Line power loss is given as: ( P2  Q2 ) R PLoss ! 2 V Therefore, it important to reduce reactive power flow to reduce line losses. Referring equations (3) and (4) the voltage magnitudes VS and VR at sending end and receiving end of long lines are held within permissible limits by means of compensation of reactive power .Compensation of reactive power helps in improving steady state stability. For long line, if compensation of reactive power not made, will results in voltage instability. Stability of power system For achiving stable operating conditions ,both active power P and reactive power Q should be controlled under stesdy state and also under dynamic state (during disturbance ) the objective of reactive power flow control are twofold 1. Under study state condition: Optimization of voltage profile in the network, minimize losses and reduction of unnecessary VAr flow within the network. 2. Under dynamic condition: Control of under voltage, over voltage during disturbances, to provide voltage support , at intermediate points ,improves power transfer without losing stability ;improve dynamic stability. Hence it can conclude that 1. Active Power flow P determined by power angle. 2. Reactive Power VAr flow determines voltage magnitudes. (2-18)

Equation (2-18) shows that both real and reactive power contributes to line losses.

2.6 Flexible AC Transmission System (FACTS)


27 | P a g e

Introduction The history of FACTS controllers can be traced back to 1970s when Hingorani presented the idea of power electronic applications in power system compensation. From then on, various researches were conducted on the application of high power semiconductors in transmission systems. The shunt-connected Static VAR compensator (SVC) using solid-state switches and the series-connected controllers were proposed in AC transmission system application. In 1988, Hingorani defined the FACTS concept and described the wide prospects of the application in [6]. Nowadays, FACTS technology has shown strong potential. Many examples of FACTS devices and controllers are in operation As presented in [7], FACTS and FACTS controllers are defined in IEEE Terms and Definitions as: Flexible AC Transmission System (FACTS): Alternating current transmission systems incorporating power electronic-based and other static controllers to enhance controllability and increase power transfer capability. FACTS Controller: A power electronic-based system and other static equipment that provide control of one or more AC transmission system parameters. As new technology for power transmission system, FACTS and FACTS controllers not only provide the same benefits as conventional compensators with mechanicallycontrolled switches in steady state but also improve the dynamic and transient performance of the power system. The power electronics-based switches in the functional 7 blocks of FACTS can usually be operated repeatedly and the switching time is a portion of a periodic cycle, which is much shorter than the conventional mechanical switches. The advance of semiconductors increases the switching frequency and voltage-ampere ratings of the solid switches and facilitates the applications. For example, the switching frequencies of Insulated Gate Bipolar Transistors (IGBTs) are from 3 kHz to 10 kHz which is several hundred times the utility frequency of power system (50~60Hz). Gate turn-off thyristors (GTOs) have a switching frequency lower than 1 kHz, but the voltage and current rating can reach 5-8 kV and 6 kA respectively [8].

28 | P a g e

FACTS controllers have many configurations and broadly divided into four categories, which are 1. Shunt controllers. 2. Series controllers. 3. Combined series-series controllers. 4. Combined series-shunt controllers

2.6.1 Shunt-connected controllers FACTS controllers can be impedance type, based on thyristors without gate turn-off capability, which are called Static Var Compensator (SVC) for shunt-connected application. Another type of FACTS controllers is converter-based which is usually in the form of a Static Synchronous Compensator (STATCOM). 2.6.1.1 Static Var Compensator (SVC) Static Var Compensator is a shunt-connected static Var generator or absorber whose output is adjusted to exchange capacitive or inductive current so as to maintain or control specific parameters of the electrical power system (typically bus voltage) [5]. SVC is based on thyristors without gate turn-off capability. The operating principal and characteristics of thyristors realize SVC variable reactive impedance. SVC includes two main components and their combination: (1) Thyristor-controlled and Thyristor-switched Reactor (TCR and TSR); and (2) Thyristor-switched capacitor (TSC). In Figure 1.4 shows the diagram of SVC.

29 | P a g e

Figure 1. 4 Static VAR Compensators (SVC): TCR/TSR, TSC, FC and Mechanically Switched Resistor [2] TCR

TCR and TSR are both composed of a shunt-connected reactor controlled by two parallel, reverse-connected thyristors. TCR is controlled with proper firing angle input to operate in a continuous manner, while TSR is controlled without firing angle control which results in a step change in reactance. TSC shares similar composition and same operational mode as TSR, but the reactor is replaced by a capacitor. The reactance can only be either fully connected or fully disconnected zero due to the characteristic of capacitor. With different combinations of TCR/TSR, TSC and fixed capacitors, a SVC can meet various requirements to absorb/supply reactive power from/to the transmission line. 1.3.1.2 Converter-based STATCOM Compensator Static Synchronous Compensator (STATCOM) is one of the key Converter-based Compensators which are usually based on the voltage source inverter (VSI) or current source inverter (CSI), as shown in Figure 1.5(a). Unlike SVC, STATCOM controls the output current independently of the AC system voltage, while the DC side voltage is automatically maintained to serve as a voltage source. Mostly, STATCOM is designed based on the VSI.

30 | P a g e

Figure 1. 5 STATCOM topologies: (a) STATCOM based on VSI and CSI (b) STATCOM with storage [5]

Compared with SVC, the topology of a STATCOM is more complicated. The switching device of a VSI is usually a gate turn-off device paralleled by a reverse diode; this function endows the VSI advanced controllability. Various combinations of the switching devices and appropriate topology make it possible for a STATCOM to vary the AC output voltage in both magnitude and phase. Also, the combination of STATCOM with a different storage device or power source (as shown in Figure 1.5(b)) endows the STATCOM the ability to control the real power output. STATCOM has much better dynamic performance than conventional reactive power compensators like SVC. The gate turn-off ability shortens the dynamic response time from several utility period cycles to a portion of a period cycle. STATCOM is also much faster in improving the transient response than a SVC. This advantage also brings higher reliability larger operating range.

1.3.2 Series-connected controllers

As shunt-connected controllers, series-connected FACTS controllers can also be divided into either impedance type or converter type. The former includes Thyristor-Switched Series Capacitor (TSSC), Thyristor-Controlled Series Capacitor (TCSC), Thyristor31 | P a g e

Switched Series Reactor, and Thyristor-Controlled Series Reactor. The latter, based on VSI, is usually in the form of a Static Synchronous Series Compensator (SSSC). The composition and operation of different types are similar to the operation of the shuntconnected peers. Figure 1.7 shows the diagrams of various series-connected controllers.

Figure 1. 7 Series-connected FACTS controllers: (a) TCSR and TSSR; (b) TSSC; (c) SSSC [5]

2.2.3 Combined Series-Series Controllers


A combined series-series controller Fig 2.17 may have two configurations. One configuration consists of series controllers operating in a coordinated manner in a multiline transmission system. The other configuration provides independent reactive power control for each line of a multi-line transmission system and, at the same time, facilitates real power transfer through the power link.

32 | P a g e

Fig 2.17 series-series controller

Example: Interline power flow controllers (IPFC) Which helps in balancing both the real and reactive power flows on the lines?

2.2.4 Combined Series-Shunt Controllers


A combined series-shunt controller Fig 2.18 may have two configurations, one being two separate series and shunt controllers that operate in a coordinated manner and the other one being an interconnected series and shunt component. In each configuration, the shunt component injects a current into the system while the series component injects a series voltage. When these two elements are unified, a real power can be exchanged between them via the power link.

Fig 2.18 series-shunt controller. Example: Unified power flow controller (UPFC) These make use of the advantages of both series and shunt controllers and, hence, facilitate effective and independent power/current flow and line voltage control. Unified Power Flow Controller (UPFC)

33 | P a g e

A combination of static synchronous compensator (STATCOM) and a static series compensator (SSSC) which are coupled via a common dc link Fig 2.19, allow bidirectional flow of real power between the series out put terminals of the SSSC and the shunt output terminals of the STATCOM, and are controlled to provide concurrent real and reactive line compensation without an external electrical energy source. The UPFC, by means of angularly unconstrained series voltage injection, is able to control, concurrently, or selectively, the transmission line voltage, impedance, and angle or, alternatively, the real and reactive power flow in the line. The UPFC may also provide independently controllable shunt reactive compensation.

Fig 2.19 Unified power flow controller (UPFC)

In UPFC, which combines a STATCOM and an SSSC, the active power for the series unit (SSSC) is obtained from the line itself via the shunt unit STATCOM the latter one is also used for voltage control with control of its reactive power. This is a complete control for controlling active and reactive power through the line, as well as for the line voltage control.

34 | P a g e

As discussed in the previous section, STATCOM is a very popular FACTS controller application effective in transmission system voltage control. Since 1980 when the first STATCOM (rated at 20 Mvar) using force-commutated thyristor inverters was put into operation in Japan [10], many examples have been installed and the ratings have been increased considerably. In 1991, KEPCO and Mitsubish Motors installed a 80MVar STATCOM at Inuyama Switching Station [11]. In 1996, TVA, EPRI and Westinghouse installed a 100MVar STATCOM at Sullivan 500 kV Substation [12]. In 2001, EPRI and Siemens developed a 200MVar STATCOM at Marcy 345kV substation [13]. It is expected that more STATCOMs will be installed due to the advances in technology and commercial success. STATCOM could have many topologies, but in most practical applications it employs the DC to AC converter, which can also be called a Voltage Source Inverter (VSI) in 3-phase configuration as the primary block. The basic theory of VSI is to produce a set of controllable 3-phase output voltages/ currents at the fundamental frequency of the AC bus voltage from a DC input voltage source such as a charged capacitor or a DC energy supply device. By varying the magnitude and phase angle of the output voltage and current, the system can exchange active/reactive power between the DC and AC buses, and regulate the AC bus voltage. Various other Types of FACTS Controllers y y y y y y y Advanced SVC. NGH-SSR Damper. Thyrister Controlled Phase Angle Regulator (TCPAR). Thyrister Controlled Phase Shifter (TCPS). Dynamic Voltage Limiters. Fault Current Limiters. Load Tap Changer.

35 | P a g e

Ferro-Resonance Damper. Inter line power flow controllers (IPFC).

Conclusion

[1]N. G. Hingorani and L. Gyugyi, Understanding FACTS, IEEE Press, New York, 1999. [2 ]IEEE Power Engineering Society, FACTS Applications, Publication 96TP116-0, IEEE Press, New York, 1996. [3] R. Mohan Mathur; Rajiv K. Varma : Thyristor Based FACTS Controller for Electrical Transmission Systems 2002 Jons Wiley & Sons.

36 | P a g e

Das könnte Ihnen auch gefallen