Custom Toroid and Bobbin Wound Transformers - - - - - - - - - - - - - - - - - - - - - - - - - -Contact Factory Excitation Curves - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Contact Factory Other CR Magnetics Catalogs 3-Phase Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 3 Rectangular Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 4 Split-Core Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 5 Breaker Type Current Transformer - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 6 Wound Primary Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 7 Bushing Type Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 8 Ground Fault Sensors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 9 Current & Voltage Transformers, IEC Rated, 50 Hz - - - - - - - - - - - - - - - - - - - - - - - -Section 10 Low Voltage, Voltage Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 11 Low Voltage, Control Power Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 12 Medium Voltage, Current Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 13 Medium Voltage, Current Transformers, IEC Rated, 50 Hz - - - - - - - - - - - - - - - - - - -Section 14 Medium Voltage, Voltage Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 15 Medium Voltage, Voltage Transformers, IEC Rated, 50 Hz - - - - - - - - - - - - - - - - - - -Section 16 Medium Voltage, Control Power Transformers - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 17 Ground Fault Systems - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 18 Instrumentation Switches - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -Section 19
2000 CR Magnetics, Inc. All rights reserved.
Selection Guide
Part Number
Description
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
50/60 Hz
60/400 Hz
50/400Hz .
Input Range
0.350 Aac
Output
5/10 Volts DC
4-20 mA
4-20 mA
4-20 mA
Solid State
Accuracy
0.5% F.S.
0.5% F.S.
0.5% F.S.
Dimensions (H)x(W)x(D)
2.75x2.69x2.36 (69.9x68.3x59.9)
2.75x2.69x2.36 (69.9x68.3x60)
4.50x2.68x2.37 (114.3x68x60.1)
3.63x4.19x4.38 (92.2x106.4x111.3)
1.50x1.0x.75 (38.1x25.4x19.1)
Power Source
Self-Powered
Loop-Powered
120 Vac
Loop-Powered
Self Powered
Agency Approval
UL
UL
UL
UL
Page Number
10
12
14
16
Selection Guide
CURRENT TRANSFORMERS
Current Transformers
CR8750 Horizontal Mount Commercial & ANSI Class Split Core Medium Voltage
50-400 Hz
50-400 Hz
50-400 Hz
50-400 Hz
50-400 Hz
50-400 Hz
Up to 60 Aac
Up to 100 Aac
Up to 60 Aac
Up to 4,000 Aac
Up to 10,000 Aac
Up to 3,000 Aac
5.0 Aac
Up to 0.3%
Up to 0.3%
Up to 0.3%
.250 (6.4)
See Catalog
See Catalog
See Catalog
UL/CSA
UL/CSA
UL
18
20
22
25
26
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
Selection Guide
Part Number
Description
Model 18 & 19
CR2550 Remote Current Indicator Low Voltage V/T Medium Voltage V/T
Frequency
50/60 Hz
50/60 Hz
50/400 Hz
60 Hz
60 Hz
Input Range
Up to 600 Vac
Up to 34.5 kV
Output
Visual
Visual
Visual
120 Vac
120 Vac
Accuracy
Up to 0.3%
Up to 0.3%
Dimensions (H)x(W)x(D)
1.04x.95x.46 (26.4x24.1x11.7)
See Page 32
See Page 34
See Catalog
See Catalog
Power Source
Self-Powered
Self-Powered
Self-Powered
---
Agency Approval
UL/CSA
UL/CSA
Page Number
32
34
36
The actual current ratio may be changed from the nameplate ratio by wrapping the primary and/or secondary leads through the window opening.
ACTUAL TURNS RATIO
NAMEPLATE RATIO
Wire from X1 terminal is routed through the H1 side Wire from X1 terminal is routed through the side opposite the H1 side (H2 side)
Examples This illustration shows how a current transformer with a nameplate turns ratio of 125:5 can be rescaled to operate as a non-standard 55:5 ratio transformer.
WHERE:
Nameplate ratio = 125 (125/5) Number of secondary turns through window = - 3 Use -3 because the secondary wire is routed from the X1 terminal first through the H1 side. Use + if the wire was routed first through the side opposite the H1 side. Number of primary turns through window = 2
125 5
SECONDARY (5 AAC) PRIMARY (55 AAC)
X2 Black H1
=
2
11
X1 White
This illustration shows the internal construction of a current transformer. The outside face of the transformer is identified as H1. The opposite face is identified as H2. The secondary leads are identified as X1 and X2. Current flowing out of terminal X1 will have the same polarity as current flowing into terminal H1.
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
Features
Permanently calibrated Output overload protected Fully isolated 10 different ranges Self-powered, requires no external power source
E154235
Specifications
Accuracy: Depends on the range and load resistance, see Part Numbers table Ripple: 1% Max. peak ripple on output Calibrated Signal Out: 0-5 Vdc for CR4310 0-10 Vdc for CR4311 Response Time: 250 ms max., 10-90% FS Max. Signal Out: 16 Vdc for CR4310 33 Vdc for CR4311 Frequency: 50/60 Hz Continuous Thermal Current Rating Factor: 2.50 @ 30C Short Time Thermal Current Rating Factor: 60 x Full Scale (For 1 Second) Insulation Class: 600 V, BIL 10 kV Full Wave Operating Temperature Range: -30C to +60C Storage Temperature Range: -55C to +85 C Shipping Weight: 1.5 pounds (.68 kg.) 5 10 15 20 30 50 75 100 150 200
0-5 0-10 0-15 0-20 0-30 0-50 0-75 0-100 0-150 0-200
1.0 0.75 0.75 0.5 0.5 0.5 0.5 0.5 0.5 0.5
0 0-5 Vdc Out 1 0-10 Vdc Out * For total load resistance of: 1.0 megohm or higher for CR4310 150 K ohm or higher for CR4311 Internet Resources http://www.crmagnetics.com/
Transducer Selection Guide: transducer.html Application Sheet: pdf/ancr4310.pdf, pdf/ancr4310-2 Pricing: pricing/4310.html External Current Transformers: cts.html
35
1.69 (42.9) .50 (12.7)
30 25 20 15 10 5 0 0 50 100 150
Output Volts, DC
CR4311 CR4310
200
250
300
350
400
2.75 (69.9)
0-5 Vdc for CR4310 0-10 Vdc for CR4311 .15 (3.8)
OUTLINE DRAWING
INTERCONNECT RESISTANCE
I INPUT
INSTRUMENTATION RESISTANCE
TYPICAL CONNECTIONS
in (mm)
Typical Applications
EXTERNAL CURRENT TRANSFORMER An external current transformer may be used with the transducer by routing the secondary leads through the window opening. Use the CR4310-5 or CR4311-5 current transducer with a 5 Amp secondary instrument grade current transformer. For additional details on current transformers, see page 25.
3-PHASE SYSTEMS Three-phase systems may be monitored by attaching three transducers in series. The total output voltage will be the sum of each individual transducer. If each transducer is sized for the full-scale current, the output voltage will be 0-15 Vdc for the CR4310 Series (0-30 Vdc for the CR4311 Series) at 0 to 100% full-scale. As an alternate, each transducer may be sized for three times the full-scale current, then the output voltage for the CR4310 will be 0-5 Vdc for 0 to 100% full-scale.
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
Features
Permanently calibrated Loop-powered Fully isolated E154235 12 different ranges 2 case styles, .93 (23.6 mm) and 1.25 (31.8 mm) window opening Output overload protected
Specifications
Accuracy: 0.5% Full-Scale (FS) Repeatability: Less than 0.1% Ripple & Noise: 1% Max., peak to peak Calibrated Signal Out: 4-20 mA DC Response Time: 200 ms max., 10-90% FS Max. Signal Out: 30 mA DC Temperature Coefficient: 0.04%/C Supply Voltage: 24 Vdc 10% Frequency: 50/60 Hz Continuous Thermal Current Rating Factor: 1.33 @ 30C Short Time Thermal Current Rating Factor (For 30 Seconds): 6.0 x Full Scale for AC ranges up to 200 Amp. 4.0 x Full Scale for ranges 300 and 400 Amp. Output Load: 0 to 600 ohms Insulation Class: 600 V, BIL 10 kV Full Wave Reverse Polarity Protection: Yes Operating Temperature Range: -30C to +60C Storage Temperature Range: -55C to +85C Approximate Weight: 1.5 pounds (.68 kg)
0-5 0-10 0-15 0-20 0-30 0-50 0-75 0-100 0-150 0-200 0-300 0-400
1 1 1 1 1 1 1 1 1 1 2 2
Transducer Selection Guide: transducer.html Application Sheet: pdf/ancr4320-1.pdf Pricing: pricing/4320.html Motor Loads: mot_ld_a.pdf
Loop Current DC MA
20 16 12 8 4
50
75
100
4.88 (124.0)
Case Style 2
1.5 (38)
.15 (3.8)
0 to 600 ohms
+
INTERCONNECT RESISTANCE
INSTRUMENTATION RESISTANCE
I PRIMARY
FS
X 16 + 4
24 Vdc
FS = FULL-SCALE CURRENT IN AMPS RMS
Typical Applications
0-15
Cr4 320
Aac
-30
An external current transformer may be used with the transmitter by routing the secondary leads through the window opening. Use the CR4320-5 current transmitter when using a 5 Amp secondary instrument grade current transformer. For additional details on current transformers, see page 25.
The scaling factor may be changed by threading the primary currentcarrying wire several times through the window opening. The "actual" measurement range will be the name plate range divided by the number of wire passes. For example, the CR4320-30 has the name plate range of 0-30 Aac. Two passes of the wire through the window opening will then provide an effective range of 0-15 Aac (302).
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
Features
Permanently calibrated Fully isolated Output overload protected 13 different ranges - 6 field selectable Internal current generator 2 case styles, .94 (23.9) and 2.13 (54.1) window opening Monitors over long distances
Case Style 2
Case Style 1
Specifications
Accuracy: 0.5% Full-Scale (FS) Ripple & Noise: 1% Max., peak to peak E154235 Calibrated Signal Out: 4-20 mA DC Response Time: 150 ms max., 10-90% FS Max. Signal Out: 30 mA DC Temperature Coefficient: 0.02%/C Supply Voltage: 120 10% Vac Frequency: 50/60 Hz Continuous Thermal Current Rating Factor: 1.50 @ 30C for ranges-All Ranges up to75 Amp. 1.33 @ 30C for ranges100 Amp. and over Short Time Thermal Current Rating Factor (For 30 Seconds): 15.0 x Full Scale for AC ranges up to 75 Amp. 4.0 x Full Scale for ranges 400 Amp. and over Output Load: 0-1000 ohms Insulation Class: 600 V, BIL 10 kV Full Wave Operating Temperature Range: -30C to +60C Storage Temperature Range: -55C to +85C
5 20
75
0-5 0-10* 0-15* 0-20* 0-25* 0-50* 0-75* 0-100 0-150 0-200 0-300 0-400 0-600
1 1
2 2 2 2 2 2
10
1.70
24 20 16 12 8 4
2.37 4.68 4.12 .23 .44 TYP. 2.13 DIA. #6-32 TERMINALS 4 PLACES RANGE SWITCH 1.97
AC AC
AC AC +
25 4.88 4.50
50
75
100
.06
.94 DIA.
Case Style 1
+
INTERCONNECT RESISTANCE
I CONTROL
I PRIMARY
INSTRUMENTATION RESISTANCE
I CONTROL
in (mm)
FS
X 16 + 4
Typical Applications
An external current transformer may be used with the transmitter by routing the secondary leads through the window opening. Use the CR4340-5 current transmitter when using 5-Amp secondary instrument grade current transformer. For additional details on current transformers, see page 22.
The scaling factor may be changed by threading the primary currentcarrying wire several times through the window opening. The "actual" measurement range will be the name plate range divided by the number of wire passes. For example, the CR4340-30 has the name plate range of 0-30 ACA. Two passes of the wire through the window opening will then provide an effective range of 0-15 ACA (302).
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
11
Features
Permanently calibrated Fully isolated ANSI/ISO 50.1 Class L3
Internet Resources http://www.crmagnetics.com/
E154235
Specifications
Nominal Input Voltages: 120, 240, 277 & 480 Vac Accuracy: 0.5% Full-Scale (FS) Ripple On Output: Less than 1% Calibrated Signal Out: 4-20 mA DC Response Time: 1.50 sec. max., 10-90% FS Temperature Coefficient: 0.03%/C Supply Voltage: 24 Vdc 10% PART NUMBERS CR4730-120 CR4730-480 (Dual Range) CR4731-120 CR4731-277 NOMINAL VOLTAGE RANGE 120 V 240 V Line-to-line 480 V Phase-to-neutral Phase-to-neutral 120 V 277 V 360 V to 600 V 0.1 VA @ 530 V 90 V to 150 V 0.1 VA @ 150 V Load Resistance: 0-600 ohms Frequency: 50/60 Hz Max. Continuous Input Voltage: 600 V Operating Temperature Range: -30C to +60C Storage Temperature Range: -50C to +85C Shipping Weight: Approx. 1.3 Pounds (.59 kg) Reverse Polarity Protection: Yes INPUT VOLTAGE RANGE 90 V to 150 V INPUT BURDEN (MAX) 0.1 VA @ 240 V TRANSFER FUNCTION ILOOP MA DC
EIN - 75 3.75 EIN - 150 7.5 EIN - 300 15 EIN - 75 3.75 EIN - 150 7.5
Ein=Volts RMS
APPLICATION Line-to-line
12
3.44 (87.4) 1 2 3 4 5 6 3.94 (100) 4.38 (111.3) #6-32 (Use M3.5 terminals) 7 8 9 10 11 12
in (mm)
4 10 5 11 6 12
NEUTRAL TOTAL LOAD RESISTANCE 0-600 OHMS, EACH PHASE 1 L1 L2 L3 2 3 7 8 9 L1 - N OUTPUT L2 - N OUTPUT L3 - N OUTPUT + 24 Vdc
I LOOP I LOOP I LOOP
4 10 5 11 6 12
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
13
Applications
Monitor electrical heater elements Sense motor over/under loads Detect lamp burn-out Indicate phase loss
Output Options
The Relay is available with three different output configurations, electromechanical relay, optoisolated NPN transistor or optoisolated triac. Specify desired selection in part number. Relay Arrangement: 1 Form C (SPDT) Contact Material: Silver-cadmium oxide Terminals: 3 - 1/4 Male Q C Mechanical Life: 10 million operations, typ.@ rated load Electrical Life: 100,000 operations, typ. @ rated load Initial Contact resistance: 50 milliohms max. @ 500 mA, 12 Vdc Contact Rating: UL508/873 & CSA VOLTAGE 240 Vac 240 Vac 125 Vac 28 Vdc
LOAD TYPE N.O. CONTACT N.C. CONTACT
Features
Variable trip point and time delay Monitors currents from 10 mA to 100 AC Amps Electrical isolation between circuits Output relay rated up to 20 Amps LED trip status indicator Dead band prevents relay chatter Calibrated dial option available External current transformers available
Specifications *
Mounting: 3/16 dia. clearance holes on 1 15/16 by 2 15/16 centers Environmental: Operating Temperature: -30C to +60C Storage Temperature: -55C to +85C Power-On Delay: 100 ms max Hysteresis: 5% Max. Input Supply Power: Terminals: 2 - 1/4 Male Q C Sensed Current: Max. Continuous: 200% Full Scale Frequency: 60-400 Hz Internet Resources http://www.crmagnetics.com/ Relay Selection Guide: relays.html Application Sheets : pdf/ancr4395-1.pdf, pdf/ancr4395-2.pdf, pdf/ancr4395-3 Pricing: pricing/4395.html External Current Transformers: cts.html
DC Switching (-NPN) Vce (full off): 30 Vdc max. Isink (full on): 120 mAdc max.@ rated full-on Vce (full on): 1.5 Vdc @ 120 mAdc Isink Off state leakage current: 5ua @ 30 Vdc (typical) AC Switching (-AAC) Off state voltage: 240 Vac RMS max. Minimum switch voltage: 24 Vac RMS On state current: 0.5 Aac RMS max. continuous Switching mode: Zero crossing Off state leakage: 60 ua @ 240 Vac max.
14
Timing Drawing
NC NO COM
3 1/2 (88.9)
MAX
2 15/16 (74.6)
25 20
MIN
30
TRIP POINT
INDICATING LED "ON" WHEN RELAY IS TRIPPED 9/32 (7.14)
15
10
SENSED CURRENT
EH - version
SENSED CURRENT TRIP POINT
EL - version
Part Numbers
SUPPLY VOLTAGE
AC 120 - 120 Vac 240 - 240 Vac DC 24D - 24 Vdc
All supply voltage tolerances are 10 %
TIME ON DELAY
A - .5 to 6 Sec. B - 2 to 25 Sec. X - none
Time-on delay is the time from when the relay trips to when the output energizes. The ranges are guaranteed minimum, actual range may be slightly greater.
OUTPUT OPTIONS ELR - Electromechanical Relay NPN - Optoisolated NPN Transistor TRC - Optoisolated Triac., zero crossing
NC NO COM
_ +
- ELR
- NPN
TRIP STATUS
EH - Energized on High, trips when sense current is above trip point and returns to non-trip status when sense current is below the trip point. EL - Energized on Low, trips when sense current is below trip point and returns to non-trip status when sense current is above trip point. LH - Latch on High, trips when sense current is above trip point and remains tripped until supply power is removed. LL - Latch on Low, trips when sense current is below trip point and remains tripped until supply power is removed.
TRIP RANGE
.01.1 -.01 to 0.1 AAC .11 - 0.1 to 1.0 AAC 110 - 1.0 to 10 AAC 330 - 3.0 to 30 AAC 660 - 6.0 to 60 AAC 101 - 10 to 100 AAC
The trip ranges shown are for one wire pass through the window opening. The trip range may be proportionally lowered with additional wire passes through the window.
- TRC
TRIP POINT DIAL NC - Non-calibrated Dial CD - Calibrated Dial FP - Fixed Trip Point (Specify value of
fixed trip point with order)
CURRENT TRIP CURRENT TRIP
25
10
MAX
MIN
15
20
30
- NC
- CD
-330 trip range shown
- FP
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
15
The CR9321-LC series is a low cost, self powered, fixed set-point Current Switch designed for applications that require an on-off indication of current flow. Current levels above the guaranteed full-on level will turn the output to full on. The Current Switch is recommended only for applications where the continuous operating current is above the rated full on level of 350 mA. Operation below this point will not drive the output device full-on and derate the output ratings. The unit is available with a NPN or PNP output transistor for switching DC and a SCR output for switching AC. Connections can be made directly to items such as a PLC or electromechanical relay. Note that connections made directly to an inductive device such as an electromechanical relay will require a customer supplied clamping diode for DC operation or a snubber network for AC operation.
Features
Low cost Low fixed trip point Fully isolated Reverse output polarity protected Self-powered
Specifications *
Rated full-on: 0.350 Aac RMS Turn-on time: 100 ms max. @ rated full-on Turn-off time: 250 ms. max. to 80% of Vce Maximum sense current: Continuous: 100 Aac 1 Second: 500 Aac Frequency: * 50 to 400 Hz Operating Temperature: -30 C to +60 C Storage Temperature: -55 C to +85 C DC Switching (-NPN or -PNP) Vce (full off): 30 Vdc max. Isink (full on): 120 mAdc max.@ rated full-on Vce (reverse polarity voltage): 1.2 Vdc @ 100 mA dc Vce (full on):1.5 Vdc @ 120 mAdc Isink Off state leakage current: 5ua @ 30 Vdc (typical) AC Switching (-ACA) Off state voltage: 240 Vac RMS max. Minimum switch voltage: 24 Vac RMS On state current: 1.0 Aac RMS max. continuous Off state leakage: 50 ua @ 240 Vac max. Peak Non-Repetitive Surge Current: 8 Aac RMS (1 cycle, 60 Hz.) *All specifications for operation at 60 Hz only
Outline Drawing
.27 Dia. (6.8) AWG # 22
1.50 (38.1)
.75 (19.1)
in (mm)
1.00 (25.4)
12 (304)
.75 (19.1)
Electrical Connections
V+
ORANGE +
V+
VAC
Vce
I sink
BLACK -
RED +
BLACK
-PNP
Vce
I source
BLACK
-ACA -NPN
16
Relay Applications
Typical Relay Applications
CR CR
CR CR
20
15
15
20 25
10
10 5 3 5 3
25 30
30
M M
MOTOR OVER UNDER MONITOR MOTOR OVER / /UNDER MONITOR The relay may be used to monitor the operational load of motor. One The relay may be used to monitor the operational load of aamotor. One leg of the motor wiring is routed through the window opening. With the leg of the motor wiring is routed through the window opening. With the "EH" (Energized on High) option, when the motor current draw exceeds "EH" (Energized on High) option, when the motor current draw exceeds the trip point, the relay will energize and open the motor starter. The time the trip point, the relay will energize and open the motor starter. The time delay would be set long enough to inhibit tripping during high inrush delay would be set long enough to inhibit tripping during high inrush starting current. Note that an electrical fuse and other overload devices starting current. Note that an electrical fuse and other overload devices will still be required for complete motor protection. will still be required for complete motor protection. CONNECTION TO INDICATOR LAMP CONNECTION TO INDICATOR LAMP The current switch may be used to drive directly an indicating lamp. The current switch may be used to drive directly an indicating lamp. When using the AC output version, either of the two black leads may be When using the AC output version, either of the two black leads may be attached to the power source. snubber network is required when attached to the power source. AAsnubber network is required when connecting to an indictive device such as an electromechanical relay. connecting to an indictive device such as an electromechanical relay.
20
15
15
20 25
10
10 5 3 5 3
25 30
30
EXTERNAL CURRENT TRANSFORMERS EXTERNAL CURRENT TRANSFORMERS The relay may be used with an external split or solid-core current The relay may be used with an external split or solid-core current transformer. The external transformer can be used to access remote transformer. The external transformer can be used to access remote loads or where the current-carrying wire is too large to fit through the loads or where the current-carrying wire is too large to fit through the window opening in the relay. standard, Amp secondary, commercial window opening in the relay. AAstandard, 55Amp secondary, commercial grade current transformer (see page 25) would be attached with the grade current transformer (see page 25) would be attached with the secondary leads threaded twice through the window opening, as secondary leads threaded twice through the window opening, as illustrated. The trip range option "110" (1.0 to 10 ACA) would then illustrated. The trip range option "110" (1.0 to 10 ACA) would then provide full-scale adjustment for the transformer. provide full-scale adjustment for the transformer.
CONNECTION TO PLC CONNECTION TO PLC The current switch may be connected directly to PLC. Supply power The current switch may be connected directly to aaPLC. Supply power may be provided from the PLC, as shown, or from an external power may be provided from the PLC, as shown, or from an external power source. When using transistor output, the negative or black lead from source. When using aatransistor output, the negative or black lead from the switch is attached to the negative side of the supply. the switch is attached to the negative side of the supply.
"A" "A"
15 15
"B" "B"
20
20 25
The trip ranges shown on page 15 represent one wire pass through the The trip ranges shown on page 15 represent one wire pass through the window opening. The trip range may be changed by threading the window opening. The trip range may be changed by threading the current-carrying wire through the window opening several times, as current-carrying wire through the window opening several times, as shown above. The "actual" trip range would be the relay name plate shown above. The "actual" trip range would be the relay name plate range divided by the number of wire passes through the opening. For range divided by the number of wire passes through the opening. For example, name plate range of 6.0 to 60 ACA with three wire passes example, aaname plate range of 6.0 to 60 ACA with three wire passes would provide an actual range of 2.0 to 20 ACA (63=2.0 603=20). would provide an actual range of 2.0 to 20 ACA (63=2.0 &&603=20).
OPEN HEATER LAMP DETECTOR OPEN HEATER / /LAMP DETECTOR The relay may be used to provide an alarm signal to indicate an open The relay may be used to provide an alarm signal to indicate an open heater element. The current-carrying wire is routed through the window heater element. The current-carrying wire is routed through the window opening. With the"EL" (Energized on Low current) option, when the opening. With the"EL" (Energized on Low current) option, when the heater element draws current above the trip point, the relay remains deheater element draws current above the trip point, the relay remains deenergized. the element becomes open, the current level will be energized. IfIfthe element becomes open, the current level will be reduced, causing the relay to become energized. Supply power is reduced, causing the relay to become energized. Supply power is constantly supplied to the relay with the "A" connection and the relay will constantly supplied to the relay with the "A" connection and the relay will cycle every time the temperature controller cycles. Using the alternate cycle every time the temperature controller cycles. Using the alternate connection with line "B", power is provided to the relay only when the connection with line "B", power is provided to the relay only when the temperature controller is cycled on. With this connection, the relay will temperature controller is cycled on. With this connection, the relay will energize only when the element is open. energize only when the element is open.
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
17
10
10 5 3 5 3
25 30
30
CR Magnetics offers a versatile line of rugged wire lead current transformers. Installed around a currentcarrying wire, the sensor provides a current output relative to the AC input current (within specification limits). With the output connected across a resistive load (burden), the voltage developed is proportional to the input current.
Applications
Remote monitoring of electrical loads Input to electrical control system Detect open heater elements Indicate phase loss Monitor motor operation
Features
Low cost Non-contact, isolated current measurement Surface mounting bracket available for Model 17
and Model 18 2 case sizes, 3 different standard ratios
Model 19
Specifications
Frequency: 50-60 Hz Working Class: 600 Vac Case Material: Black thermoplastic
Part Numbers
Model 17-2000 Model 17-1000 Model 18-600 MB-18 Model 19 Current Transformer with wire leads, .55 dia. opening, 2000 turns Current Transformer with wire leads, .55 dia. opening, 1000 turns Current Transformer with wire leads, .55 dia. opening, 600 turns Surface Mounting Bracket for Model 17 or Model 18 Current Transformer with .29 dia. opening, 230 turns Internet Resources http://www.crmagnetics.com/ Model 17 & 18 Shown with optional mounting bracket MB-18
18
20 W
. .95
10 W
.29 DIA.
0.5
1.0 W
0 0 5 10 15 20 25 30
1.04
12 NTS
200 W
5 4
100 W
47 W 20 W
0 0 5 10 15 20 25 30
1.48 .79
10 9
1000 W
510 W
8 7 6 5 4 3 2 1 0 0 5 10 15 20 25 30
200 W 100 W 47 W 20 W 10 W
35 40 45 50 55 60
.95 1.33
.19
.50
24 NTS
1000 W
.105
max. (2.7)
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 5 10 15 20 25 30 35 40 45
510 W
200 W 100 W 47 W 20 W
50 55 60
.875 1.37
10 W
.25
.25
.750 1.25
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
19
Applications
Silicon Steel cores provide moderate accuracy and lower cost for applications such as current measurement and current relaying. Nickel Alloy cores are for applications that require highest accuracy with minimal phase angle error and are higher in cost. Applications would include power and energy monitoring devices.
CR8351
Specifications
Case Material: Polypropylene Resin Construction: Epoxy Encapsulated Operating Temperature: -25C to +66C Insulation Resistance: 100 M ohm @ 500 Vdc High Potential: 1500 volts x 1 minute Frequency: 50 to 400 Hz
CR8348 CR8349
CR8350
A
min. .265 (6.7) .354 (9) .504 (12.8) .772 (19.6)
B
max. .925 (23.5) 1.024 (26) 1.476 (37.5) 1.969 (50)
C
max. .433 (11) .669 (17) .551 (14) .748 (19)
D
.04 (1.0) .118 (3) .118 (3) .118 (3) .137 (3.5)
E
max. .984 (25) 1.102 (28) 1.535 (39) 2.204 (56)
Fig.
.075 .60 .75 .374 (1.905) (15.24) (19.05) (9.5) .075 .60 .75 .60 (1.905) (15.24) (19.05) (15.24) .15 1.00 1.30 .50 (3.81) (25.4) (33.02) (12.7) .591 1.181 2.362 .394 (15) (30) (60) (10)
Part Numbers CR - -
Number of Secondary Turns
Standard Configurations
The following are standard configurations that are stocked. CR8348-2000 CR8348-2500-N-0.2 CR8349-1500 CR8349-2500-N-0.2 CR8350-2000 CR8350-2500-N-0.2 CR8351-2000-N-0.2 CONTACT FACTORY FOR ADDITIONAL ELECTRICAL SPECIFICATIONS
8300a.
- .272 Window Opening - .354 Window Opening - .504 Window Opening - .772 Window Opening
Leave blank for Silicon Steel Core N 0.2 - Nickel Alloy Core, 0.2 Accuracy Class N 0.1 - Nickel Alloy Core, 0.1 Accuracy Class
1000 W 1000 W
510510 W W
6 4
200 20 W
200 W
2
100 W 10
2
100 W 51 W
0 0 5 10 15 20 25 30
51 W 5
10
10 W
10 W
10
20
30
40
50
1000 W 1000 W
510 W 510 W
I
10
20 200
W
R
10 100
51 W
5 0 10
10 W
20
40
60
80
100
CR Magnetics, Inc. 544 Axminister Dr. Fenton, MO 63026 (314) 343-8518 FAX (314) 343-5119
21
Features
Low cost 5 standard sizes Non-contact, isolated measurement
Applications
Over/under current sensing Ground Faults Current measurements Power monitoring
CR8459 CR8460
Specifications
Case Material: Polypropylene Resin Construction: Epoxy Encapsulated Operating Temperature: -25C to +66C Insulation Resistance: 100 M ohm @ 500 Vdc High Potential: 1500 volts x 1 minute Frequency: 50 to 400 Hz
CR8401
CR8410
CR8420
A
min. .232 (5.9) .350 (8.9) .610 (15.5) .760 (19.3) 1.181 (30)
B
max. .827 (21.0) .984 (25.0) 1.299 (33.0) 1.862 (47.3) 2.401 (61)
C
max. .315 (8.0) .355 (9.0) .355 (9.0) 748 (19) .826 (21)
D
.12 (3.0) 2.75 (70.0) 2.87 (73.0) 2.75 (70.0)
E
max. .709 (18.0) .866 (22.0) 1.181 (30.0)
Fig.
NOTES
NICKEL ALLOY CORE WITH MAGNETIC SHIELDS FOR GROUND FAULT APPLICATIONS SILICON STEEL CORE FOR GENERAL PURPOSE CURRENT MONITORING NICKEL ALLOY CORE WITH MAGNETIC SHIELDS FOR GROUND FAULT APPLICATIONS NICKEL ALLOY CORE FOR POWER MONITORING APPLICATIONS NICKEL ALLOY CORE FOR POWER MONITORING APPLICATIONS
3 3 3 4
3.464 (88)
Part Numbers CR u u u u - u u u u
Number of Secondary Turns
- .232 Window Opening - .350 Window Opening - .610 Window Opening - .760 Window Opening
- 1.181 Window Opening
Standard Configurations
The following are standard configurations that are normally stocked.
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Email: sales@crmagnetics.com
22
0.1 3
2 0.01 1
200 W
100 W 51 W
10 W 0 2 4 6 8 10
I R V
0.1
0.01
0.001 0.001
0.01
0.1
10
23
I G H X1 K J Top View
L B C
E H1 M F (Typ.4 Places) M
H1
D F (Typ. 4 Places) D
Front View
Side View
Front View
Side View
Figure 1
Figure 2
A DIA.
Figure 3
Figure 4
D B A DIA. C
H1
Figure 5
24
The CR8750 series, PCB Current Transformer provides a low cost method for monitoring electrical current. The transformer is intended to be mounted on a Printed Circuit Board with the current-carrying wire routed through the center window opening. A five-pin, non-symmetrical mounting pattern ensures correct orientation on the PCB. Two different winding ratios are available to accommodate various applications. The graph below illustrates how different values of burden resistors attached to the output terminal will provide a number of different output voltage ranges.
Specifications
Frequency: 60-400 Hz Insulation Level: 600 V Internet Resources http://www.crmagnetics.com/
Application Notes
1.125 MIN.
.850 0.280"
.90 MAX.
.425
H1 X1 X2
.250 MIN.
.47 MAX.
.140
0.187"
Outline Drawing
Typical Response
7
1000 W
6
510 W
200 W
100 W
47 W
2
20 W
1
10 W
0 0 5 10 15 20 25 30 35 40 45 50
CR8750-1000
25
RL
SFT
Applications
Ammeters Energy Management Watt/VAR/Watthour Transducers, Current Sensing Relays, see pages 14 & 16 Internet Resources http://www.crmagnetics.com/
SFL
SHT
SHL
RT
RBT Specifications
RBL
SERIES
CR1A CR2 CR2DA CR5 CR5A CR6A CR7 CR7A CR8 CR56 CR76 CR170
WINDOW DIAMETER
0.64 1.13 1.00 1.56 1.56 2.06 2.50 2.50 3.25 2.06 3.00 4.25
(16.2) (28.7) (35.4) (39.6) (39.6) (52.3) (63.5) (63.5) (72.5) (52.3) (76.2) (107.9)
XXX
x10 MULTIPLIER
Specials
FIRST TWO NUMBERS OF PRIMARY CURRENT RATING
*Example: 50 AMP primary current rating would read 500, 300 AMP would read 301 and 4000 AMP would read 402.
Ultra low frequency to 20 Hz Water Proof High volume, low cost styles 1.0, 0.2 & 0.1 AAC secondary ratios available
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
26
G F A
B A
RL
D F
RBL
G E
A B A B
RT
G F A D
C
D F
SFT
G E
A B B
RBT
UL1015 #16AWG 24" (610) LONG
SFL
#8-32 (Use M4 terminal)
A B
A B
SHL
SHT
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
27
B
2.46 (62.5) 2.68 (68.1) 2.68 (68.1) 2.71 (68.8) 2.71 (68.8)
C
1.05 (26.7) 2.00 (50.8) 2.00 (50.8) 0.95 (24.1) 0.95 (24.1)
D
1.05 (26.7) 1.75 (44.5) 1.75 (44.5) 0.95 (24.1) 0.95 (24.1)
E
1.05 (26.7) 1.60 (40.6) 1.60 (40.6) 0.95 (24.1) 0.95 (24.1
F
1.05 (26.7) .27 (6.9) .27 (6.9) 0.95 (24.1) 0.95 (24.1
G
1.05 (26.7) .31 (7.9) .31 (7.9) 0.95 (24.1) 0.95 (24.1
ACCURACY AT 60 Hz
3% 2% 2% 2% 1% 1% 1% 1% 1% 1% 1% 2% 2% 2% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 2% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 3% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 1% 2% 1% 1% 1% 1% 1% 1% 1% 1% 1%
BURDEN VA AT 60 Hz
2.0 2.0 2.0 2.0 2.0 2.5 2.5 4.0 4.0 6.0 8.0 1.0 1.5 2.0 5.0 5.0 10.0 12.5 12.5 20.0 25.0 25.0 25.0 25.0 30.0 2.5 5.0 5.0 5.0 12.0 15.0 25.0 30.0 30.0 35.0 30.0 35.0 40.0 45.0 0.5 0.5 1.0 2.5 4.0 6.0 7.5 10.0 12.5 15.0 7.0 8.0 10.0 12.5 5.0 5.0 6.0 10.0 10.0 10.0 10.0 12.5 10.0 10.0 12.5 12.5 15.0 1.0 2.0 2.0 2.0 2.5 3.0 3.0 4.0 5.0 7.5
1.13 (28.7)
CR2
1.56 (39.6)
CR5
RL SFT SFL SHT SHL RT RBT * RBL * RL SFT SFL SHT SHL RT RBT RBL RL SFT SFL RT RBT RBL RL SFT SFL RT RBT RBL
3.56 (90.4) 3.78 (96.0) 3.78 (96.0) 3.83 (97.3) 3.83 (97.3) 3.62 (91.9) 3.90 (99.1) 3.70 (94.0) 4.70 (919.4) 4.85 (123.2) 4.85 (123.2) 4.70 (119.4) 4.70 (119.4) 4.61 (117.1) 4.94 (125.5) 4.70 (125.5)
1.10 (27.9) 2.15 (54.6) 2.15 (54.6) 1.09 (27.7) 1.09 (27.7) 1.13 (28.7) 1.25 (31.8) 1.25 (31.8) 1.10 (27.4) 2.13 (54.1) 2.13 (54.1) 1.10 (27.9) 1.10 (27.9) 1.10 (27.9) 1.25 (31.8) 1.25 (31.8)
1.10 (27.9) 2.75 (69.9) 2.75 (69.9) 1.09 (27.7) 1.09 (27.7) 1.13 (28.7) 3.88 (98.6) 3.88 (98.6) 1.10 (27.4) 3.78 (96.0) 3.78 (96.0) 1.10 (27.9) 1.10 (27.9) 1.10 (27.9) 5.75 (146.1) 5.75 (146.1)
1.10 (27.9) 1.77 (45.0) 1.77 (45.0) 1.09 (27.7) 1.09 (27.7) 1.13 (28.7) 1.25 (31.8) 1.25 (31.8) 1.10 (27.4) 1.75 (44.5) 1.75 (44.5) 1.10 (27.9) 1.10 (27.9) 1.10 (27.9) 6.5 (7.1) 6.5 (16.5)
1.10 (27.9) .21 (5.3) .21 (5.3) 1.09 (27.7) 1.09 (27.7) 1.13 (28.7) .44 (11.2) .44 (11.2) 1.10 (27.4) .25 (6.4) .25 (6.4) 1.10 (27.9) 1.10 (27.9) 1.10 (27.9) .28 (16.5) .28 (7.1)
1.10 (27.9) .31 (7.9) .31 (7.9) 1.09 (27.7) 1.09 (27.7) 1.13 (28.7) .27 (6.9) .27 (6.9) 1.10 (27.4) .31 (7.9) .31 (7.9) 1.10 (27.9) 1.10 (27.9) 1.10 (27.9) .28 (7.1) .28 (7.1)
50:5 75:5 100:5 150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 100:5 150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 1500:5 1600:5 50:5 75:5 100:5 150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 1500:5 1600:5 2000:5 50:5 60:5
2.50 (63.5)
CR7
2.06 (52.3)
CR56
3.50 (88.9) 3.63 (92.2) 3.63 (92.2) 3.62 (91.9) 3.90 (99.1) 3.70 (94.0)
1.09 (27.7) 2.15 (54.6) 2.15 (54.6) 1.10 (27.9) 1.25 (31.8) 1.25 (31.8)
1.09 (27.7) 2.70 (68.6) 2.70 (68.6) 1.10 (27.9) 3.88 (98.6) 3.88 (98.6)
1.09 (27.7) 1.70 (43.2) 1.70 (43.2) 1.10 (27.9) 4.50 (114.3) 4.50 (114.3)
1.09 (27.7) .21 (5.3) .21 (5.3) 1.10 (27.9) .27 (6.9) .27 (6.9)
1.09 (27.7) .31 (7.9) .31 (7.9) 1.10 (27.9) .44 (11.2) .44 (11.2)
3.00 (76.2)
CR76
4.50 (114.3) 4.68 (128.9) 4.68 (118.9) 4.62 (117.3) 4.94 (125.5) 4.70 (119.4)
1.09 (27.7) 2.08 (52.8) 2.08 (52.8) 1.10 (27.9) 1.25 (31.8) 1.25 (31.8)
1.09 (27.7) 3.70 (44.0) 3.70 (44.0) 1.10 (27.9) 5.75 (146.1) 5.75 (146.1)
1.09 (27.7) 1.75 (44.5) 1.75 (44.5) 1.10 (27.9) 6.50 (165.1) 6.50 (165.1)
1.09 (27.7) .25 (6.4) .25 (6.4) 1.10 (27.9) .28 (7.1) .28 (7.1)
1.09 (27.7) .31 (7.9) .31 (7.9) 1.10 (27.9) .28 (7.1) .28 (7.1)
RBT and RBL mounting styles in the CR5 series are not available in current ratios of 750:5 thru 1200:5
200:5 250:5
28
SERIES
MOUNTING STYLE
DIMENSIONS
1.0 (25.4)
CR2DA
RL
3.56 (90.4)
1.10 (27.9) 2.15 (54.6) 2.15 (54.6) 1.10 (27.9) 1.10 (27.9) 2.75 (69.9) 2.75 (69.9) 1.77 (45.0) 1.77 (45.0) .21 (5.3) .21 (5.3) .31 (7.9) .31 (7.9)
150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 100:5
1.56 (39.6)
CR5A
150:5 200:5 3.34 (84.8) 3.34 (84.8) 1.75 (44.5) 1.75 (44.5) .25 (6.4) .25 (6.4) .31 (7.9) .31 (7.9) 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 1500:5 100:5 150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 800:5 1000:5 1200:5 1500:5 1600:5
2.06 (52.3)
CR6A
2.12 4.21 (106.9) (53.8) 2.12 4.21 (106.9) (53.8) 1.10 4.22 (107.2) (27.9) 1.10 4.22 (107.2) (27.9)
2.50 (63.5)
CR7A
2.13 4.85 (123.2) (54.1) 2.13 4.85 (123.2) (54.1) 1.10 4.70 (119.4) (27.9) 1.10 4.70 (119.4) (27.9)
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
29
SERIES
MOUNTING STYLE
DIMENSIONS
200:5 250:5 300:5 400:5 500:5 600:5 1.15 5.73 (145.5) (29.2) 1.15 5.73 (145.5) (29.2) 1.15 5.73 (145.5) (29.2)
3.25 (82.6)
CR8
RL SHT SHL
750:5 800:5 1000:5 1200:5 1500:5 1600:5 2000:5 2500:5 3000:5 3200:5 4000:5 200:5 250:5 300:5 400:5 500:5
4.25 (108)
CR170
RL SHT SHL
1.25 6.73 (170.9) (31.8) 1.28 6.73 (170.9) (32.5) 1.28 6.73 (170.9) (32.5)
600:5 750:5 800:5 1000:5 1200:5 1500:5 1600:5 2000:5 2500:5 3000:5 3500:5 4000:5
30
3-Phase WYE
IL E L-L
IL
A
Z Z
IL
E L-N
E L-N
E L-L
E L-L
Z
E L-N
IL
P = 3 EL-N IL cos 0 = 1.73 EL-L IL cos 0 IL= EL-N = EL-L Z 1.73 Z Z = EL-L EL-L 1.73 IP EL-N = 1.73
The current in each element is equal to the line current I . The voltage across each element E L-N is equal to the line voltage EL-L divided by 3 The impedance of each element is equal to line voltage EL-L divided by 3 times the line current. The voltages across the elements are 120 out of phase. The currents in the elements are 120 out of phase. The power is equal to 3 times line voltage E L-N times line current times COS O. For a balanced load the current in the neutral is equal to zero.
Z Z
E L-L IB B IC
E L-L
E L-L
A
Z Z
E L-L B IL
I C-B
EE = E L-L 2
E L-L
E L-L
I L= 0
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
31
The CR-45 series, Wire-Mounted Electrical Current Indicators provides an effective method of monitoring electrical current. The indicator is attached directly to a current-carrying wire. When the current exceeds the turn-on point, the LED will illuminate to indicate the presence of current.
Applications
Monitor status of heater elements Observe remote loads Indicate phase loss Monitor motor operation
Features
Self powered Red or green indicator Easy to install Supplied with plastic tie Bright yellow case for easy identification Panel mounting bracket available
Specifications
Min. Turn-on Point 2 Amps for CR-45-R 2.5 Amps for CR-45-G Indicating Range: 2 to 100 Amps (for CR-45-R) 2.5 to 100 Amps (for CR-45-G) Max. Continuous Current: 100 Amps LED Type: T 13/4 Diffused LED Color: Red or Green Case Material: Thermoplastic Case Color: Bright Safety Yellow Weight: .5 oz. (14.2 g) Frequency: 50-60 Hz Mounting Bracket Material: Non-Magnetic Aluminum
WIRE PASSES RED TURN-ON POINT GREEN MAX. WIRE DIAMETER
1 2 3 4 N
2 1 .66 .5 2N
Part Numbers
Internet Resources http://www.crmagnetics.com/
CR45 -
Current Indicator with (Red or Green) LED R-Red Indicator G-Green Indicator Panel Mounting Bracket for CR-45
MB-45
32
One-Wire Pass
Two-Wire Passes
Three-Wire Passes
Outline Drawings
.144 DIA. .005 (3.7 DIA.) 2 PLACES
1.562 DIA. .005 (39.7 DIA.) .203 DIA. .005 (5.2 DIA.)
RUBBER WASHER FURNISHED
.95 (24.1)
.46 (11.7)
CR-45
MB-45
Typical Application
Load Center
Control Panel
Process Heating
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
33
The CR Magnetics line of Remote Electrical Current Indicators provides an effective method for remote monitoring of electrical current. The remote current sensing transformer is installed around the currentcarrying wire and is connected directly to the LED panel indicator. When the current exceeds the turnon point of the sensing transformer, the LED illuminates to indicate the presence of current. Two sizes of remote current sensing transformers are available for use with either one of two types of LED indicators. The panel indicators are available with either red or green LED.
Applications
Indicate open heater elements Observe remote loads Indicate phase loss Monitor motor operation
Indicating Range: 2 to 100 Amps (1-Wire Pass) Minimum turn-on point: 2 Amps Max. Cont. Current: 100 Amps Max.Transient Current: 150 Amps for 5 Sec. Working Class: 600 Volts, 50-60 Hz
WIRE PASSES 1 2 3 N TURN-ON POINT 2 1 .66 2N MAX. WIRE DIAMETER .29 (7.4) .14 (3.6) .13 (3.3)
Indicating Range: 2.5 to 100 Amps (1-Wire Pass) Minimum turn-on point: 2.5 Amps Max. Cont. Current: 100 Amps Max.Transient Current: 150 Amps for 5 Sec. Working Class: 600 Volts, 50-60 Hz
WIRE PASSES 1 2 3 N TURN-ON POINT 2.5 1.25 .83 2.5 N MAX. WIRE DIAMETER .55 (14) .27 (6.9) .25 (6.4)
LED type: Bi-Polar, Red or Green Mounting Hole: .250 (6.4) .002 Dia. Mounting Hardware: Use either one-piece press-in red lens or two-piece mounting clip
T-13/4,
LED type: T-13/4, Bi-Polar, Red or Green Housing Material: Chrome Plated Brass Mounting Hole: .312 .005 (7.9) Dia.
34
Model 19
PH-25
PH-31
. .95 (24.1)
1.48 (37.6) .29 (7.4)DIA. 12 (304.8) NTS .95 (24.1) 1.33 (33.8) #4-40 INSERT-.17 DEEP .19 (4.8) .50 (12.7) .25 (6.4) 24 (609.6) NTS .79 (28.1) #20 AWG UL STYLE 1015
1.04 (26.4)
.46 (11.7)
12 (304.8) NTS
.25 (6.4)
.250 (6.4) .002 Dia. Hole ONE PIECE RED LENS TWO PIECE MOUNTING CLIP
Part Numbers
Current Transformer with .29 dia. opening Current Transformer with .55 dia. opening Surface Mounting Bracket for Model 18 Press-In Panel Indicator with red LED Press-In Panel Indicator with green LED Splash Proof Panel Indicator with red LED Splash-Proof Panel Indicator with green LED
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
35
Features
Low cost for high volume OEM installations Low fixed trip point Fully isolated Easy to install Self-powered
Applications
Indicate open heater element Observe remote loads Indicate phase loss Monitor motor operation
Specifications
Turn-on point: 0.75 Aac RMS for Red LED 1.5 Aac RMS for Green LED Maximum Continuous Rating: 20 Aac RMS Frequency: 50 to 400 HZ Operating Temperature: -30 C to +60 C Storage Temperature: -55 C to +85 C LED Indicator type: T-13/4, Bipolar, Red/Red or Green/Green Diffused, Indicator is supplied with LED attached to current sensing transformer LED Mounting Hardware: Supplied with both one-piece press-in lens and twopiece mounting clip
Part Numbers
CR2550-11-.75 R CURRENT INDICATOR WITH
RED LED
Installation
Outline Drawing
.062 (1.6) MIN. .125 (3.2) MAX.
36
200 V 2.3 3.2 4.15 6 7.8 11 17.5 25 32 48 62 78 92 120 150 177 221 285 358 415 550
230 V 2 2.8 3.6 5.2 6.8 9.6 15.2 22 28 42 54 68 80 104 130 154 192 248 312 360 480
460 V 1 1.4 1.8 2.6 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 180 240
575 V .8 1.1 1.4 2.1 2.7 3.9 6.1 9 11 17 22 27 32 41 52 62 77 99 125 144 192
2300 V 4160 V 200 V 23 29 34.5 46 57.5 73.5 106 146 186 267 334 420 500 667 834 16 8.9 1000 20 11 1250 26 14.4 1670 31 17 2085 37 20.5 2500 49 27 3340
220/230 V 440/460 V 550/575 V 2300 V 20 10 8 25 12.5 10 30 15 12 40 20 16 50 25 20 64 32 25 92 46 37 127 63 51 162 81 65 232 116 93 290 145 116 365 182 146 35 435 217 174 41 580 290 232 55 725 362 290 69 870 435 348 83 1085 592 435 104 1450 725 580 139 1815 907 726 173 2170 1085 870 208 2900 1450 1160 278
4160 V
19 23 30 38 46 57 76 96 115 153
2.75
2.40
1.20
.96
.24
.133
*This information provided as reference only. Consult motor manufacturer and related standards for additional information.
POLYPHASE
A A
240 (480) 120 (240) [480] 208 (416)
N GROUND B LINE
C
120 (240) [480]
B
120 (240) 120 (240) 240 (480)
LINE
B
120 (240) [480]
A N
208 (480)
GROUND
CR Magnetics, Inc. 544 Axminister Dr. Fenton MO USA 63026 V: 636.343.8518 F: 636.343.5119
Web: http://www.crmagnetics.com Email: sales@crmagnetics.com
37
Manufacturers & Designers Of Electrical Current Monitoring Products For Industrial Market Applications Throughout The World
CR MAGNETICS, INC.
544 Axminister Drive Fenton, MO 63026 USA PHONE: 636-343-8518 FAX: 636-343-5119 E-MAIL: sales@crmagnetics.com WEB SITE: www.crmagnetics.com
Code M2000A