DESIGN CRITERIA
y Roof Slab
y DEAD LOAD G.I. corrugated sheets Steel purlins Lighting and electrical Concrete (unit weight)
0.0766 kpa (1.6psf) ....... 0.08 kPa (1.65 psf) ...0.10kpa(2psf) ..24KN/m3 (150pcf)
y ALLOWABLE DESIGN STRESSES Concrete Compressive stress @ 28 days curing f c = 21 MPa f c = 27.5 MPa Reinforcing Steel Bars Fy = 275Mpa & Fy = 414 Mpa Structural Steel (ASTM A36) Fy = 36ksi or 3600 psi E = 29.0x106
q=39.63psf 40psf from fig.1.5-2(Carillo) C1= 1.3sin 0.5 ; =11.31 C1 = -0.25 C2 = 0.5 (governs!) P= Cx q ; P= wind force P= 0.5 x 40psf P= 20psf
Where: Z = seismic zone factor table 2.2A (2.46) Z =Zone 4, coefficient = 0.75 I = importance factor table 2.2D (2.50) = using earthquake importance factor I = 1.00 (standard occupancy structures) S = 1.0 C= ; S = site coefficient for soil characteristics direction under consideration, S = 1.0 T= T = elastic fundamental period of vibration, in seconds of the structure in the direction under consideration.