Murali Krishnan T and Kaustubh Deshpande K t bh D h d Emerson Process Management, Asia Pacific
Agenda
Typical project organization Implementation Process Modular concept System hardware design, delivery and installation y g , y flexibility Software standards for FPSO automation Use of bus technologies
Experienced personnel in Project Management Application knowledge Asset Management Safety and Automation System Instrumentation / Valves Power Systems Fieldbus Technology
Integrated Engineering Team during FEED, follow-up engineering and site integration coordination
( Customer / Contractor / Suppliers / End-user ) Customer/End-User/Contractor experts availability Co-design Co design on solutions Prepare and train customer organization and yard-teams for utilization of new designs/techniques and maximize the yield Prepare and distribute project design specifications and f perform FEED Empowered participation in the preparation of tender documents and package procurement to enforce standards and improve data from package units
Project Execution
Design phase Implementation phase FAT Metering Skid FAT Top Sides Site work on yard Site work on Offshore location
Engineering Phase
Fieldbus Technical Training
Design / Segmentation
FEED Phase
FEED Phase
Fieldbus Deployment Assessment
Example of Physical Design: Hazardous Area Easier live maintenance: -Exi - ExnL What device and component hazardous area certification is required? -FISCO devices for FNICO -Entity Exi devices for Entity ExnL
Engineering Phases
FEED Phase
Fieldbus Deployment Assessment
Engineering Phase
Fieldbus Technical Training
Design / Segmentation
EPC defines philosophy (rules) by which Fieldbus devices are allocated to the bus to achieve desired control availability
Workshop topics for discussion: Control Loop / Valve Criticality Ranking Application Scope of Foundation Fieldbus Cable Selection A Arrangement of JB, Grounding t f JB G di Redundant Philosophy Macro-cycle philosophy Function Block Requirement Controller Location (CIC/CIF) Zone Application
Consists of: - Definition of control loop criticality level - Restrictions for allocation for control criticality level - Analysis and ranking of control loops/valves Impacts: - Number of devices per bus - Number of loops per bus
Functional Design Specification (FDS) Generated by the Project Team Common design philosophy document for all parties Appendix content: Hazardous area concept Components Wi i Wiring Design considerations Control strategy gy Etc.
12
(EPC)
EPC will load the segment based on process plot plan and results from Segment Design Tool, risk assessment, process criticality and equipment unit.
Segment Allocation = assigning devices to bus Segment Loading = block and communication timing Segment Design = calculate current and voltage S tD i l l t t d lt
Singapore FPSO Seminar - 21 August 2009
13
EPC will load the segment based on process plot plan and results from Segment Design Tool risk assessment process criticality and plant unit Tool, assessment, unit. MIV will then validate for any software constraint and provide Fieldbus Segment Software Analysis to EPC.
16
Engineering Phase
Fieldbus Technical Training
Design / Segmentation
M45
M60
M41 - MCC
Pump
H1
Profibus
Fieldbus I/O
Singapore FPSO Seminar - 21 August 2009
22
Safety
Data Acquisition
Electrical
23
Digital system architecture that uses the power of field intelligence to improve FPSO performance
Singapore FPSO Seminar - 21 August 2009
23
Summary