01-SAMSS-005 Shop Applied, Internal Cement Mortar Lining of Steel Pipe Paints and Coatings Standards Committee Members
Khashram, Maher Saud, Chairman Hammad, Bakr Sulaiman, Vice Chairman Seba, Zaki Ahmed Mansour, Mana Hamad Nujaim, Salah Ahmed Homayed, Mohammed Ali Suller, Abraham A

30 May 2009

Saudi Aramco DeskTop Standards


Table of Contents I II III IV Scope............................................................. 2 Conflicts and Deviations................................. 2 References..................................................... 2 Modifications to AWWA C205........................ 3

Previous Issue: 31 October 2004 Next Planned Update: 30 May 2014 Page 1 of 5 Primary contact: Khashram, Maher S (Saud) on 966-3-876-0261
CopyrightSaudi Aramco 2009. All rights reserved.

Document Responsibility: Paints and Coatings Issue Date: 30 May 2009 Next Planned Update: 30 May 2014

01-SAMSS-005 Shop Applied, Internal Cement Mortar Lining of Steel Pipe

Scope A. This specification defines the requirements for shop applications of cement mortar lining to the internal surfaces of steel pipe. It includes materials, surface preparation, application and testing. Only shop applied, internal, lining shall be required by this specification. It does not address coating external pipe surfaces or field application of lining.

B.

II

Conflicts and Deviations A. Any conflicts between this specification and other applicable Saudi Aramco Materials System Specifications (SAMSSs), Engineering Standards (SAESs), Standard Drawings (SASDs), or industry standards, codes, and forms shall be resolved in writing by the Company or Buyer Representative through the Manager, Consulting Services Department of Saudi Aramco, Dhahran. Direct all requests to deviate from this specification in writing to the Company or Buyer Representative, who shall follow internal company procedure SAEP-302 and forward such requests to the Manager, Consulting Services Department of Saudi Aramco, Dhahran.

B.

III

References All referenced Specifications, Standards, Codes, Forms, Drawings, and similar material shall be considered part of this Specification to the extent specified herein and shall be the latest issue (including all revisions, addenda, and supplements) unless stated otherwise. A. Saudi Aramco References Saudi Aramco Engineering Procedure SAEP-302 Instructions for Obtaining a Waiver of a Mandatory Saudi Aramco Engineering Requirement

Saudi Aramco Material System Specification 01-SAMSS-024 Pipe Handling and Nesting

Saudi Aramco Inspection Requirements Form 175-012500 Concrete Mortar Lining for Internal Surfaces of Line Pipe and Fittings
Page 2 of 5

Document Responsibility: Paints and Coatings Issue Date: 30 May 2009 Next Planned Update: 30 May 2014

01-SAMSS-005 Shop Applied, Internal Cement Mortar Lining of Steel Pipe

B.

Industry Codes and Standards American Water Works Association AWWA C205 Cement Mortar Protective Lining and Coating for Steel Water Pipe-4 inch and Larger Shop Applied

American Society for Testing and Materials ASTM C136 ASTM C142 ASTM C150 ASTM D1888 British Standards Institution BS 812 Part 117 BS 812 Part 118 Swedish Institute of Standard SIS-05-59-00 IV Modifications to AWWA C205 The following paragraph numbers refer to AWWA C205 - 95, which is part of this Specification. The text in each paragraph below is an addition, exception, modification, or deletion to AWWA C205 - 95 as noted. Paragraph numbers not appearing in AWWA C205 - 95 are new paragraphs to be inserted in numerical order. 4.1.4 Quality Program (Addition) The Vendor shall implement and maintain a Quality Program which shall include clearly defined and documented procedures for the relevant Quality Systems functions. The Quality Program documents shall be made available to the Purchaser's Representative for review and audit. 4.2.1 4.2.2.1 (Exception) - Not applicable. (Exception) Portland Cement - Delete in entirety. (Addition) Portland Cement - Portland Cement shall conform to the requirements of ASTM C150, Type V including the optional chemical requirements of Table 1A and the optional physical requirements of Table 2A.
Page 3 of 5

Sieve Analysis of Fine and Coarse Aggregates Clay Lumps and Friable Particles in Aggregates Standard Specification for Portland Cement Particulate and Dissolved Matter, Solids, or Residue in Water

Water Soluble Chloride Salts Sulfate Content

Pictorial Surface Preparation Standards

Document Responsibility: Paints and Coatings Issue Date: 30 May 2009 Next Planned Update: 30 May 2014

01-SAMSS-005 Shop Applied, Internal Cement Mortar Lining of Steel Pipe

4.2.3

Fine Aggregate (Exception) Sand shall be fine aggregate as defined in ASTM C136. Deleterious substances shall not exceed the following limits: Clay Lumps and Friable Particles Acid Soluble Chlorides {Cl} Acid Soluble Sulfates {SO3} 3.00% by weight 0.06% by weight 0.40% by weight

4.2.4

Mixing Water (Exception) Mixing water shall not contain more than 500 ppm of total dissolved solids.

4.3.1

(Exception) Cleaning Surfaces - Delete in entirety. (Addition) Cleaning Surfaces - All surfaces to be cement mortar lined shall be cleaned in accordance with St2 of SIS-05-59-00 at the time of application of the cement mortar.

4.4.2

Thickness (Exception) Delete "... or as specified by the Purchaser " and "... and the lining holdback shall be as specified by the Purchaser for the type of joint required."

4.4.2.1 4.4.2.2

(Addition) For sleeved pipe, there shall be no cutback. The cement mortar lining shall be flush with the end of the pipe. (Addition) For pipe that has been specifically designated for butt welding, the cement mortar lining shall be cut back a minimum of 10 mm to a maximum of 25 mm from the end of the pipe. (Addition) The thickness of the cement lining shall be checked within 0.6m of the end of the pipe at the 3, 6, 9, and 12 o'clock positions. (Exception) Mortar Coating - Not applicable. (Exception) Field Joints - Not applicable. (Exception) Delete in Entirety. (Addition) Testing Requirements.

4.4.2.3 4.5 4.6 5

5.1

(Addition) The following tests shall be performed prior to and during lining. This table shows the properties to be tested, the test method, the frequency
Page 4 of 5

Document Responsibility: Paints and Coatings Issue Date: 30 May 2009 Next Planned Update: 30 May 2014

01-SAMSS-005 Shop Applied, Internal Cement Mortar Lining of Steel Pipe

for testing and the acceptance criteria. The Buyer reserves the right to require more frequent or additional test if these criteria are not met. Table 1 - Testing and Acceptance Criteria
Material Sand Gradation Deleterious Substances Acid Soluble Chloride Acid Soluble Sulfates Water Total Dissolved Solids Cement Mortar Soluble Chloride Content Test Method ASTM C136 ASTM C142 BS 812 Part 117 BS 812 Part 118 ASTM D1888 BS 812 Part 117 Frequency Weekly Monthly Monthly Monthly Monthly Monthly Acceptable Criteria Fine Aggregate Max. 3.0 wet % Clay Max. 0.06 wet % Max. 0.40% Max. 500 ppm Max. 0.15%

B C

5.2

(Addition) Buyer reserves the right to obtain samples, of either the delivered product or its constituent components, which ever the Buyer deems necessary to verify compliance to any of the quality requirements stated in this Specification. Inspection (Addition) The Vendor shall furnish all equipment and instruments needed to perform inspections. The items manufactured to this Specification are subject to verification by the Purchaser's Inspection Representative, per Saudi Aramco Inspection Requirements Form 175-012500, attached to the Purchase Order. (Exception) Loading, and stacking during storage, transportation and handling shall conform to 01-SAMSS-024. Calculations for static load stress shall be based on the force caused by the mass of the pipe, W (lb/in or N/M) including the weight of the cement mortar lining.

5.3.1

30 May 2009

Revision Summary Revised the Next Planned Update. Reaffirmed the contents of the document and reissued with no other changes.