SL.NO. DEVICE.

REF FUNCTION TECHNICAL SPECIFICATION MAKE QTY/PANEL REMARKS


1 CRP Enclosure
Simplex type, free standing,Double door, sheet steel cubicle; folded sheet
steel construction; having dimensions 2315mmx800mmx610mm(HxWxD);
(Inculding Base Frame)provided with AVP and 25x6mm tinned copper earth
bus.Comprising the following equipments.(Panel Details SH NO:3.4)
VOLTECH 1
2 DS Door limit switch Door limit switch for CFL ON/OFF KAYCEE 1
3 CFL Panel illumination Compact fluroscent lamp 230 V AC 18 W PASOLITE 1
4 PS Power socket Universal Socket, Rating: 5/15A, 230V AC ANCHOR 1
5 SW Space heater control Toggle Switch,ON/OFF: 1Pole,5/10A, 230V AC SWITRON 1
6 TH Temprature control Thermostat30 to 85 degree 15 A 230V AC for Space heater Auto ON/OFF GIRISH EGO 1
7 SR Stabilising resistor
Stabilising resistor for LV REF Protection relay,0-2000 ohms, 100watts.
REPUTED
1
8 SD Surge protection
Metrosil for REF Protection- CTR:1A.
AREVA
1
9 MCB-1 DC incoming ckt. control 2-pole,16A, 110V DC MCB for DC circuits SIEMENS 1
10 MCB-2 AC incoming ckt. Control 2-pole,16A, 2300V AC MCB for AC circuits SIEMENS 1
11 FS01 Protection circuits 20A fuse holder with 6A HRC fuse SIEMENS 1
12 FS02 Protection circuits 20A fuse holder with 6A HRC fuse SIEMENS 1
13 FS03 Protection ckt 20A fuse holder with 2A HRC fuse SIEMENS 1
14 FS04 Protection ckt 20A fuse holder with 2A HRC fuse SIEMENS 1
15 FS05 Protection ckt 20A fuse holder with 2A HRC fuse SIEMENS 1
16 LK01 Protection ckt 20A fuse holder with 16A Neutral link. SIEMENS 1
17 FS06 Protection ckt 20A fuse holder with 2A HRC fuse SIEMENS 1
18 LK02 Protection ckt 20A fuse holder with 16A Neutral link. SIEMENS 1
19 FS07 Rotor E/F Protection ckt 20A fuse holder with 2A HRC fuse SIEMENS 1
20 LK03 Rotor E/F Protection ckt 20A fuse holder with 16A Neutral link. SIEMENS 1
21 SH Space Heater Space Heater,100Watts, 230V AC SURYA 1
22
X01-X02-
X03-X13
Wire terminations
Disconnecting type terminals for CT,PT,DC,AC ckts and inter panel
wiring.
PHOENIX As Required
23
X04,X05,X16,
X19,XT,XXC,XX
T
Wire terminations Non-disconnecting type terminals for all other circuits PHOENIX As Required
24 D01 EARTH BUS Panel earth bus; 25mmx6mm, tinned copper strip. VOLTECH As Required
EQUIPMENT JOB REF: VCAPL/Y/1019
30MW GENERATOR RELAY PANEL DWG.NO. :VCAPL/D/1019/2
DRWG. TITLE : LIST OF APPARATUS DATE : 25.01.2011 Sheet:2.1
CUSTOMER : M/S: SPRAY ENGINEERING DEVICES LIMITED. APPD. BY : SM
1 16.08.2011
AS PER LETTER COMMENTS. DTD 10.08.11 USER : M/S: JAY MAHESH SUGAR INDUSTRIAL LIMITED. CHKD. BY : SM Contd:2.2
REV DATE DETAIL OF REVISION PROJECT : 30MW, 11/132KV SWITCHYARD PROJECT. PREP. BY : PS
MOUNTED INSIDE THE CUBICLE
25 ML Main label 30MW GENERATOR RELAY PANEL VOLTECH 2
26 87G Generator Differential Relay
Generator Differential Protection Relay,CTR:1A, (87,87N,64S,68,50/51)
Aux Supply 110V DC, Type:(MD32-G)
L & T 1
27 MFR Multifunctionl Relay
Generator Protection & Management Relay,CTR:1A,PTR:110 VAC,
(21,24,27/59,32,37,40,46,50/27,50V/51V,51BF,60FL,64S,68,81)
Aux Supply 110V DC, Type:(MG30) (Standard O/P)
L & T 1
28 64E Rotor earth fault protection
Rotor earth fault relay,Rotor voltage:110VDC,Bias voltage: 230V
AC,Contacts:2N/O S/R,Mounting Flush,1DV,type: VAEM 21AF101D
AREVA 1
29 86 TRIP RELAY
Electo mechanical High speed master trip relay, high burden, Double
element,110V DC, Per Element 3M & 1B, HR contacts, HR flag, size 1/2N,
non draw out flush mounting case, Type: VAJH232G8322BCH
AREVA 1
30 195 CB trip circuit supervision
Electro-mechanical, three element, auxillary relay for CB trip ckt.
supervision, pre & post close, Aux Supply110V DC,1 NO 2 NC SR contacts,
HR reverse flag, Size 1/2 N, non draw-out, horizantal flush mounting case,
Type VAX312G8074BCH
AREVA 1
EQUIPMENT JOB REF: VCAPL/Y/1019
30MW GENERATOR RELAY PANEL DWG.NO. :VCAPL/D/1019/2
DRWG. TITLE : LIST OF APPARATUS DATE : 25.01.2011 Sheet:2.2
CUSTOMER : M/S: SPRAY ENGINEERING DEVICES LIMITED. APPD. BY : SM
1 16.08.2011
AS PER LETTER COMMENTS. DTD 10.08.11 USER : M/S: JAY MAHESH SUGAR INDUSTRIAL LIMITED. CHKD. BY : SM Contd:3.1
REV DATE DETAIL OF REVISION PROJECT : 30MW, 11/132KV SWITCHYARD PROJECT. PREP. BY : PS
MOUNTED FRONT OF THE CUBICLE