Sie sind auf Seite 1von 115

Q

The most reliable automatic controls in Refrigeration, Cooling, Air conditioning and Heating fields etc. We can answer any inquiries connect with our products. For any inquiries, contact the company at: SAGINOMIYA SEISAKUSHO, INC. 13-1,Ichibancho,Chiyoda-ku, Tokyo, 102-0082, Japan Tel : +81 3 5843 3341 Fax: +81 3 5843 3364 E-mail : inter@saginomiya.co.jp

Headquarters

Sales Headquarters

Tokorozawa Plant

Sayama Plant

OVERSEAS NETWORK

FOSHAN HUALU AUTOMATIC CONTROLS LIMITED (China) No.61 Wenhua Nanlu, Chancheng District, Foshan, Guangdong, China Sales & Manufacturing T e l: +86 757 8383 1558 Fax: +86 757 8383 1218

Saginomiya America, Inc. (USA) 655 Metro Place South suite 700, Dublin, Ohio 43017, U.S.A. Sales Tel: +1 614 766 7390 Fax: +1 614 766 7391

Danfoss Saginomiya Sp.z o.o. (Poland) ul. Chrzanowska 5, 05-825 Grodzisk Mazowiecki, Poland Sales & Manufacturing Tel: +48 22 7550 500 Fax: +48 22 7550 505

Saginomiya (Thailand) Co.,Ltd. (Thailand) 159 Serm-mit Tower 19th Fl., Room No.1903/1 Sukhumvit 21 Rd., Klongtoey-Nua, Wattana, Bangkok 10110, Thailand Sales Tel: +662 260 8364 Fax: +662 260 8366

SAGINOMIYA SINGAPORE PTE. LTD. (Singapore) 7500A Beach Road #07-322 The Plaza Singapore 199591, Singapore Sales Tel: +65 6273 7311 Fax: +65 6273 9611

RIMSA SAGINOMIYA, S.A.DE C.V. (Mexico) Av. Central No. 126, Parque Industrial Toluca 2000, Km. 52.8 Carretera Toluca Naucalpan, C. P. 50200, Toluca, Edo. de Mexico, Mexico Sales & Manufacturing Tel: +52 722 279 3680 Fax: +52 722 279 0234

AUTOMATIC CONTROLS
Catalog-edition-Q

REFERENCE APPROVAL

INFORMATION

STANDARD LIST CONTROLS

PRESSURE TEMPERATURE PRESSURE

& HUMIDITY CONTROLS

& TEMPERATURE CONTROLS INFORMATION


EXPANSION

VALVES

SOLENOID

VALVES & CONTROL VALVES VALVES

OTHER OTHER

CONTROL EQUIPMENT

This condensed catalog-Q is a revised edition of catalog-P

CONTENTS

REFERENCE INFORMATION
CONVERSION TABLES SATURATED VAPOUR PRESSURE CURVE APPLICATION EXAMPLES 13 4 56

APPROVAL STANDARD LIST


APPROVAL STANDARD LIST 7

PRESSURE CONTROLS
SMALL PRESSURE CONTROLS Type ACB, LCB, HCB, GCB & TCB SMALL PRESSURE CONTROLS Type LTB, ETB, HTB & FTB SINGLE FUNCTION PRESSURE CONTROLS Type SNS & HNS PRESSURE CONTROLS WITH NARROW DIFFERENTIAL Type FNS & ANS DUAL PRESSURE CONTROLS Type DNS OIL PROTECTION CONTROLS Type ONS DIFFERENTIAL PRESSURE CONTROLS Type WNS DIGITAL PRESSURE SWITCHES Type CFE PRESSURE SENSORS Type NSK & XSK 910 1112 1314 1516 1718 1920 21 22 2325

PROPORTIONAL TEMPERATURE CONTROLS Type PWS ROOM THERMOSTATS Type WRS ROOM THERMOSTATS Type LRS ROOM HUMIDISTATS Type AHS DIGITAL THERMOSTATS & DIGITAL HUMIDISTATS Type ULE & FLE DIGITAL THERMOSTATS Type TNE ELECTRONIC STEP THERMOSTATS Type DSE & FSE ELECTRONIC DEFROST CONTROLS Type DDE

32 3334 35 36 3739 40 4142 43

PRESSURE &TEMPERATURE CONTROLS INFORMATION


CONNECTION & ACCESSORIES DRIP PROOF & WATER PROOF CONTROLS Series NSW & NSP 4547 4849

EXPANSION VALVES
GENERAL INFORMATION EXPANSION VALVES Type BHX EXPANSION VALVES (BIFLOW) Type TCX EXPANSION VALVES Type ATX(R410A) EXPANSION VALVES Type ATX EXPANSION VALVES Type VPX & WPX EXPANSION VALVES Type WHX 5152 53 54 5556 5758 5960 6162

TEMPERATURE & HUMIDITY CONTROLS


TEMPERATURE CONTROLS Type LWS, FWS, RWS & EWS TEMPERATURE CONTROLS Type TNS, CNS & INS TEMPERATURE CONTROLS Type ALS & BLS 2728 2930 31

T Y P E
A ACB
ACV ADV AHS AKM AKV ALS ANS ATX ATX(R410A) AWR 910 85 95 36 100 6364 31 1516 5758 5556 8788 85 53 100 31 72

N U M B E R
106107 104105 22 2930 106107 8788 43 1718 4849 9394 4142 7980 97,106107 9192 1112 2728

I N D E X
3739 1516 98 4142 1112 2728 910 8788 910 108 106107 1314 4849 104105 104105 1112 HWR 8990 2930 73 104105 106107 910 65 35 1112 2728 99 7778 8788

C CAV
CCB CFE CNS CRV CWR

F FLE
FNS FQS FSE FTB FWS

INS IEV JKV JSK LCB LNE LRS LTB LWS

D DDE
DNS DNSW DPR DSE

G GCB
GWR

H HCB
HBL HEV HNS HNSW HPV HSK HTB

B BCV
BHX BKM BLS BPV

E EGK
ELK EPR ETB EWS

M MDP
MJV MWR

ELECTRONIC EXPANSION VALVES Type UKV, SKV, VKV, PKV & AKV PULSE CONVERTERS Type LNE

6364 65

SOLENOID VALVES & CONTROL VALVES


SOLENOID VALVES FOR REFRIGERANT Type NEV, TEV & VPV SOLENOID VALVES FOR REFRIGERANT Type SEV SOLENOID VALVES FOR REFRIGERANT Type REV & UEV SOLENOID VALVES FOR WATER (BRINE) Type WEV BIFLOW SOLENOID VALVES Type BPV 3-WAY SOLENOID VALVES Type IEV 4-WAY REVERSING VALVES Type STF & VHV MOTORIZED BALL VALVES Type MJV DAMPER & VALVE MOTOR ACTUATORS Type EGK & WGK 2WAY & 3-WAY CONTROL VALVES Type NVK 67

PRESSURE REGULATING VALVES Type EPR PRESSURE REGULATING VALVES Type SPR & DPR DIAPHRAGM TYPE STOP VALVES Type ADV

9192 9394 95

OTHER CONTROL EQUIPMENT


68 6970 71 72 73 7476 7778 7980 8183 FLOW SENSORS Type ELK FLOW SWITCHES Type FQS DRAIN PUMPS Type MDP TEMPERATURE RECORDERS Type AKM & BKM CONDENSER FAN SPEED CONTROLLERS Type RGE CONDENSER FAN SPEED CONTROLLERS Type XGE CONTROL APPLIANCES FOR HOT WATER SUPPLY UNITS BY CO2 REFRIGERANT Type CCB, HSK, HPV, UKV-J & JKV CONTROL APPLIANCES FOR HOT WATER SUPPLY UNITS Type CRV, VSV, WSV, HEV, XJV, TCV, CAV, JSK, ELK BELLOWS 108 109 Type HBL & WSL 85 86 8788 8990 OTHER CONTROLS Type RKV, SKM & Bi-METAL (No. 03, 05, 24) 106107 97 98 99 100 101102 103

104105

OTHER VALVES
CHECK VALVES Type ACV & BCV PRESSURE ACTUATED WATER REGULATING VALVES Type VWR PRESSURE ACTUATED WATER REGULATING VALVES Type CWR, AWR, GWR, MWR & SWR TEMPERATURE ACTUATED WATER REGULATING VALVES Type OWR, HWR & XWR

N NEV
NSK NSP NSW NVK

67 2325 4849 4849 8183 1920 4849 8990 6364 32 6970 101102 109 2728

S SEV
SKM SKV SNS SNSW SPR STF SWR

O ONS
ONSW OWR

68 109 6364 1314 4849 9394 7476 8788 910 54 106107 67 40 2930 4849

U UEV
UKV UKVJ ULE

6970 6364 104105 3739 7476 6364 67 5960 106107 86 71 7980 6162 21 4849 5960

WRS WSL WSV

3334 108 106107 103 106107 2325 8990 109 109 109

X XGE V VHV
VKV VPV VPX VSV VWR XJV XSK XWR No.03 No.05 No.24

T TCB P PKV
PWS TCX TCV TEV TNE TNS TNSW

W WEV
WGK WHX WNS WNSW WPX

R REV
RGE RKV RWS

REFERENCE INFORMATION
1. CONVERSION TABLES
1) Temperature conversion table (C F) The figures in the center column show the temperature to be converted. The figures on the left show conversion from Fahrenheit to Centigrade and the figures on the right from Centigrade to Fahrenheit.

Example : C 15.0

5C41.0F F 5 41.0

Temperature conversion formula : C5/9 (F32) F9/5C32

15.0C5F

C 37.2 35 36.7 34 36.1 33 35.6 32 35.0 31 34.4 30 33.9 29 33.3 28 32.8 27 32.2 26 31.7 25 31.1 24 30.6 23 30.0 22 29.4 21 28.9 20 28.3 19 27.8 18 27.2 17 26.7 16 26.1 15 25.6 14 25.0 13 24.4 12 23.9 11

F 31.0 29.2 27.4 25.6 23.8 22.0 20.2 18.4 16.6 14.8 13.0 11.2 9.4 7.6 5.8 4.0 2.2 0.4 1.4 3.2 5.0 6.8 8.6 10.4 12.2

C 23.3 10 22.8 22.2 21.7 21.1 20.6 20.0 19.4 18.9 18.3 17.8 17.2 16.7 16.1 15.6 15.0 14.4 13.9 13.3 12.8 12.2 11.7 11.1 10.6 10.0 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14

F 14.0 15.8 17.6 19.4 21.2 23.0 24.8 26.6 28.4 30.2 32.0 33.8 35.6 37.4 39.2 41.0 42.8 44.6 46.4 48.2 50.0 51.8 53.6 55.4 57.2

C 9.4 8.9 8.3 7.8 7.2 6.7 6.1 5.6 5.0 4.4 3.9 3.3 2.8 2.2 1.7 1.1 0.6 0 0.6 1.1 1.7 2.2 2.8 3.3 3.9 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

F 59.0 60.8 62.6 64.4 66.2 68.0 69.8 71.6 73.4 75.2 77.0 78.8 80.6 82.4 84.2 86.0 87.8 89.6 91.4 93.2 95.0 96.8 98.6 100.4 102.2

C 4.4 5.0 5.6 6.1 6.7 7.2 7.8 8.3 8.9 9.4 10.0 15.6 21.1 26.7 32.2 37.8 43.3 48.9 54.4 60.0 65.6 71.1 76.7 82.2 87.8 40 41 42 43 44 45 46 47 48 49 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190

F 104.0 105.8 107.6 109.4 111.2 113.0 114.8 116.6 118.4 120.2 122.0 140.0 158.0 176.0 194.0 212.0 230.0 248.0 266.0 284.0 302.0 320.0 338.0 356.0 374.0

101.1 150 238.0 95.6 140 220.0 90.0 130 202.0 84.4 120 184.0 78.9 110 166.0 73.3 100 148.0 67.8 90 130.0 62.2 80 112.0 56.7 70 51.1 60 45.6 50 45.0 49 44.4 48 43.8 47 43.3 46 42.8 45 42.2 44 41.7 43 41.1 42 40.6 41 40.0 40 39.4 39 38.9 38 38.3 37 37.8 36 94.0 76.0 58.0 56.2 54.4 52.6 50.8 49.0 47.2 45.4 43.6 41.8 40.0 38.2 36.4 34.6 32.8

2) Temperature difference conversion table (C C 0.056 0.111 0.278 0.56 1.11 1.67 2.22 2.78 0.1 0.2 0.5 1 2 3 4 5 F 0.18 0.36 0.90 1.8 3.6 5.4 7.2 9.0 C 3.33 3.89 4.44 5.00 5.56 6.11 6.67 8.33 6 7 8 9 10 11 12 15

F) This table is a comparison table of temperature difference. For F example, a 9F difference (77F68F) corresponds to a 5C difference (25C20C). 10.8 12.6 14.4 16.2

18.0 19.8 21.6 27.0 MPa)

3) Pressure conversion table (kgf/cm2

The figures in the center column show the pressure to be converted. The figures on the left show conversion from MPa to kgf/cm2 and the figures on the right from kgf/cm2 to MPa. Example : 1 MPa10.1972kgf/cm2, 1kgf/cm20.09807 MPa kgf/cm2 0 1.01972 2.03944 3.05916 4.07888 5.09860 6.11832 7.13804 8.15776 9.17748 10.1972 20.3944 30.5916 40.7888 50.9860 61.1832 71.3804 81.5776 91.7748 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 0 0.009806 0.019613 0.029420 0.039226 0.049033 0.058839 0.068646 0.078453 0.088259 0.09807 0.19613 0.29420 0.39227 0.49033 0.58840 0.68647 0.78453 0.88260 0.98066 1.07873 1.17680 1.27486 1.37293 1.47100 1.56906 1.66713 1.76520 1.96133 1.96133 MPa kgf/cm2 214.141 224.338 234.535 244.732 254.930 265.127 275.324 285.521 295.718 305.916 316.113 326.310 336.507 346.704 356.902 367.099 377.296 387.493 397.690 407.888 418.085 428.282 438.479 448.676 458.874 469.071 479.268 489.465 499.662 509.860 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 MPa 2.05940 2.15746 2.25553 2.35360 2.45166 2.54973 2.64780 2.74586 2.84393 2.94199 3.04006 3.18313 3.23619 3.33426 3.43233 3.53039 3.62846 3.72653 3.82459 3.92266 4.02073 4.11879 4.21686 4.31493 4.41299 4.51106 4.60913 4.70719 4.80526 4.90332 kgf/cm2 520.057 530.254 540.451 550.648 560.846 571.043 581.240 591.437 601.634 611.832 622.029 632.226 642.423 652.620 662.818 673.015 683.212 693.409 703.606 713.804 724.001 734.198 744.395 754.592 764.790 774.987 785.184 795.381 805.578 815.776 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 MPa 5.00139 5.09946 5.19752 5.29559 5.39366 5.49172 5.58279 5.68786 5.78592 5.88399 5.98206 6.08012 6.17819 6.27626 6.37432 6.47239 6.57046 6.66852 6.76659 6.86465 6.96272 7.06079 7.15885 7.25692 7.35499 7.45305 7.55112 7.64919 7.74725 7.84532 kgf/cm2 825.973 836.170 846.367 856.564 866.762 876.959 887.156 897.353 907.550 917.748 927.945 938.142 948.339 958.536 968.734 978.931 989.128 999.325 1000.52 1019.72 1529.58 2039.44 2549.30 3059.16 3569.02 4078.88 4588.74 5098.60 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 150 200 250 300 350 400 450 500 MPa 7.94339 8.04145 8.13952 8.23759 8.33565 8.43372 8.53179 8.62985 8.72792 8.82598 8.92405 9.02212 9.12018 9.21825 9.31632 9.41438 9.51245 9.61052 9.70858 9.80665 14.70997 19.6133 24.51662 29.41995 34.32327 39.2266 44.12992 49.03325

101.972 10 112.169 11 122.366 12 132.563 13 142.760 14 152.958 15 163.155 16 173.352 17 183.549 18 193.746 19 203.944 20

4) Pressure conversion table (kgf/cm2 kgf/cm 0 0.0070 0.0141 0.0211 0.0281 0.0352 0.0422 0.0492 0.0562 0.0633 0.0703 0.1406 0.2109 0.2812 0.3515 0.4218 0.4922 0.5625 0.6328 0.7031
2

psi) psi 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 156.5 170.8 184.9 199.1 213.4 227.6 241.8 256.0 270.2 284.5 298.7 312.9 327.1 341.4 355.6 369.8 384.0 398.3 412.5 426.7 kgf/cm2 2.180 2.250 2.320 2.390 2.461 2.531 2.601 2.672 2.742 2.812 2.883 2.953 3.023 3.094 3.164 3.234 3.304 3.375 3.445 3.515 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 psi 440.9 455.2 469.4 483.6 497.8 512.0 526.3 540.5 554.7 568.9 583.2 597.4 611.6 625.8 640.1 654.3 668.5 682.7 696.9 711.2 kgf/cm2 4.218 4.922 5.625 6.328 7.031 7.734 8.437 9.140 9.843 10.55 14.06 21.09 28.12 35.15 42.18 49.22 56.25 63.30 70.31 60 70 80 90 100 110 120 130 140 150 200 300 400 500 600 700 800 900 1000 psi 853.4 995.6 1137.9 1280.1 1422.3 1564.5 1706.8 1849.0 1991.2 2133.5 2844.6 4266.9 5689.2 7111.5 8533.8 9956.1 11378.4 12800.7 14223.0

psi 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10 0 1.422 2.845 4.267 5.689 7.112 8.534 9.956 11.379 12.801 14.22 28.45 42.67 56.89 71.12 85.34 99.56 113.79 128.01 142.22

kgf/cm2 0.773 0.844 0.914 0.984 1.055 1.125 1.195 1.266 1.336 1.406 1.477 1.547 1.617 1.687 1.758 1.828 1.898 1.969 2.039 2.109

5) Capacity conversion table (kW kW 0.116 0.232 0.348 0.465 0.581 0.697 0.813 0.930 1.046 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1000 kcal/h kW 0.086 1.162 0.172 2.325 0.258 3.488 0.344 4.651 0.430 5.813 0.516 6.976 0.602 8.139 0.688 9.302 0.774 10.46

kcal/h) 1kW 1000 kcal/h kW 8.6 116.2 17.2 232.5 25.8 348.8 34.4 465.1 43.3 581.3 51.6 697.6 60.2 813.9 68.8 930.2 77.4 104.6 860kcal/h 1000 kcal/h 100 86 200 172 300 258 400 344 500 433 600 516 700 602 800 688 900 774

6) Length conversion table (In In 1/8 1/4 3/8 1/2 5/8 3/4 7/8 1 1/16 3/16 5/16 7/16 9/16 11/16 13/16 15/16 1/32 3/32 5/32 7/32 9/32 11/32 13/32 15/32 17/32 19/32 21/32 23/32 25/32 27/32 29/32 31/32 mm 3.18 6.35 9.53 12.70 15.88 19.05 22.23 25.40 1.59 4.76 7.94 11.11 14.29 17.46 20.64 23.81 0.79 2.38 3.97 5.56 7.14 8.73 10.32 11.91 13.49 15.08 16.67 18.26 19.84 21.43 23.02 24.61 In 1/64 3/64 5/64 7/64 9/64 11/64 13/64 15/64 17/64 19/64 21/64 23/64 25/64 27/64 29/64 31/64 33/64 35/64 37/64 39/64 41/64 43/64 45/64 47/64 49/64 51/64 53/64 55/64 57/64 59/64 61/64 63/64

mm)

1 2 3 4 5 6 7 8 9

1000 kcal/h kW 0.86 11.62 1.72 23.25 2.58 34.88 3.44 46.51 4.33 58.13 5.16 69.76 6.02 81.39 6.88 93.02 7.74 104.6

10 20 30 40 50 60 70 80 90

7) Vacuum conversion table (MPa MPa 0.1013 0.0987 0.0960 0.0933 0.0907 0.0880 0.0853 0.0827 0.0800 0.0773 0.0747 0.0720 0.0693 0.0667 0.0640 0.0613 0.0587 0.0560 0.0533 0.0507 MPa cmHg kgf/cm2 (abs) v (abs) 76 0 0 0.0027 74 0.0272 0.0053 72 0.0544 0.0080 70 0.0816 0.0107 68 0.1088 0.0133 66 0.1360 0.0160 64 0.1631 0.0187 62 0.1903 0.0213 60 0.2175 0.0240 58 0.2447 0.0267 56 0.2719 0.0293 54 0.2991 0.0320 52 0.3263 0.0347 50 0.3535 0.0373 48 0.3806 0.0400 46 0.4078 0.0427 44 0.4350 0.0453 42 0.4622 0.0480 40 0.4894 0.0507 38 0.5166 MPa (abs) MPa 0.0480 0.0453 0.0427 0.0400 0.0373 0.0347 0.0320 0.0293 0.0267 0.0240 0.0213 0.0187 0.0160 0.0133 0.0107 0.0080 0.0053 0.0027 0 cmHgv kgf/cm2(abs)) MPa cmHg kgf/cm2 (abs) v (abs) 36 0.5438 0.0533 34 0.5710 0.0560 32 0.5981 0.0587 30 0.6254 0.0613 28 0.6526 0.0640 26 0.6798 0.0667 24 0.7069 0.0693 22 0.7341 0.0720 20 0.7613 0.0747 18 0.7885 0.0773 16 0.8157 0.0800 14 0.8429 0.0827 12 0.8700 0.0853 10 0.8972 0.0880 8 0.9245 0.0907 6 0.9517 0.0933 4 0.9788 0.0960 2 1.0060 0.0987 0 1.0332 0.1013

8) Other conversion values 1 kg2.20462 Ib, 1mm0.03937 inch 1 U.S. Refrigeration Ton12,000 Btu/h3,024 kcal/h 1 kgf/cm298.0667 kPa0.980667 bar

mm 0.40 1.19 1.98 2.78 3.57 4.39 5.16 5.95 6.75 7.54 8.33 9.13 9.92 10.72 11.51 12.30 13.10 13.89 14.68 15.48 16.27 17.07 17.86 18.65 19.45 20.24 21.04 21.83 22.62 23.42 24.21 25.00

2. SATURATED VAPOUR PRESSURE (C

MPa (abs), C

kgf/cm2 (abs))

3.0

30.0

2.0

20.0 15.0

1.5

1.0 0.9 0.8 0.7 0.6 0.5 0.4

R
10.0 9.0 8.0 7.0 6.0 5.0 4.0

23 R

41

0A

0.3 Absolute Pressure MPa abs 0.2

3.0


Li qu id
2.0

kgf/cm2 abs

40

4A

N H 3

40 7C

1.5

29

0.07 0.06 0.05 0.04 0.03

0.7 0.6 0.5 0.4

13

0.1 0.09 0.08

1.0 0.9 0.8

22

4a

50

0.15

7C

60

0a

0.3

0.02

0.2 60 50 40 30 20 10 0 10 20 30 40 50 60

Temperature

R 12 12 3 3

3. APPLICATION EXAMPLES
1). Refrigeration System with Hot Gas Defrosting

EVAPORATOR

ACCUMULATOR RECEIVER

D.P

O.P
CONDENSER

COMPRESSOR

NORMAL COOLING CYCLE COOLING CYCLE FOR LOW CONDENSER TEMP. DEFROST CYCLE

Dual Pressure Controls Type DNS

Pressure Controls Type SNS

Oil Protection Controls Type ONS

Differential Pressure Controls Type WNS

Temperature Controls Type TNS

Temperature Controls Type ALS

Electronic Step Thermostat Type DSE

Thermostatic Expansion Valve Type ATX

2). Heat Pump SystemChiller

T
INSIDE

HEAT EXCHANGER

RECEIVER

L.P D.P

OUTSIDE

HEAT EXCHANGER COMPRESSOR

FAN COOLING CYCLE HEATING CYCLE

Thermostatic Expansion Valve Type WPX

Thermostatic Expansion Valve Type WHX

Thermostatic Expansion Valve Type BHX

Solenoid Valve Type REVE

Solenoid Valve Type REVB

4-Way Reversing Valve Type STF

Solenoid Valve Type NEV

Check Valve Type BCV

APPROVAL STANDARD LIST


Our products are listed by type number. In some types of products, not all models are listed. Some approved items have special catalog number for the listing. Some approved items require extra charges. Please contact the company for details.
Standard for safety
Type Number Pressure Controls ANS(W), DNS(W), FNS(W), HNS(W), ONS(W), SNS(W), WNS(W), ETB, FTB, HTB, LTB, ACB, LCB, CFE, XSK, NSK Flow Switch FQS Pressure Controls DNS, HNS, SNS, WNS, ETB, FTB, HTB, LTB, ACB, XSK, NSK Flow Switch FQS Pressure Controls CSA DNS, SNS, ETB, FTB, HTB, LTB, ACB Temperature Controls Solenoid Valve GEV, IEV, JEV, NEV, REV, SEV, WEV, AMV, GMV, HMV, RMV, VHV, STF, BPV Fan Speed Controller RGE, XGE Solenoid Valve NV NEV, TEV, VPV VHV, STF BV Solenoid Valve NEV, REV, WEV Fan Speed Controller XGE Solenoid Valve NEV, VPV, STF Temperature Controls CNS, TNS NK ABS

Standard for marine


Type Number Pressure Switch FPS, SPS, WPS, YPS, ANS, DNS, FNS, HNS, ONS, SNS, WNS, YNS FPS, SPS, WPS, YPS, ANS, DNS, FNS, HNS, ONS, SNS, WNS, YNS FPS, SPS, WPS, YPS, ANS, DNS, FNS, HNS, ONS, SNS, WNS, YNS FPS, SPS, WPS, YPS, ANS, DNS, FNS, HNS, ONS, SNS, WNS, YNS ANS, DNS, FNS, HNS, ONS, SNS, WNS, YNS FPS, SPS, WPS, YPS, ANS, DNS, FNS, HNS, ONS, SNS, WNS, YNS Temperature Switch GPS, TPS, BNS, CNS, GNS, INS, TNS

CE

BNS(W), CNS(W), TNS(W), TNE

LR

Defrost Controls DDE Temperature Controls CNS, TNS, EWS, FWS, LWS, RWS Digital Thermostats TNE Fan Speed Controller RGE, XGE

GL

GPS, TPS, BNS, CNS, GNS, INS, TNS

GPS, TPS, BNS, CNS, GNS, INS, TNS

UL

GPS, TPS, BNS, CNS, GNS, INS, TNS

BNS, CNS, GNS, INS, TNS

Pressure Controls IECEE DNS, HNS, SNS,ETB, FTB, LTB, HTB, ACB DNS, SNS, ACB Pressure Controls VDE DNS, HNS, SNS, ETB, FTB, HTB, LTB, ACB Pressure Controls DNS, HNS, SNS

GPS, TPS, BNS, CNS, GNS, INS, TNS

TV

NEMKO

PRESSURE CONTROLS
SMALL PRESSURE CONTROLS 910 Type ACB, LCB, HCB, GCB & TCB SMALL PRESSURE CONTROLS 1112 Type LTB, ETB, HTB & FTB SINGLE FUNCTION PRESSURE CONTROLS 1314 Type SNS & HNS PRESSURE CONTROLS WITH NARROW DIFFERENTIAL 1516 Type FNS & ANS DUAL PRESSURE CONTROLS 1718 Type DNS OIL PROTECTION CONTROLS1920 Type ONS DIFFERENTIAL PRESSURE CONTROLS 21 Type WNS DIGITAL PRESSURE SWITCHES 22 Type CFE PRESSURE SENSORS 2325 Type NSK & XSK

PRESSURE CONTROLS

SMALL PRESSURE CONTROLS (DISC TYPE)


High Volume OEM Item Type ACB, LCB, HCB, GCB & TCB GENERAL DESCRIPTION
Pressure Control CB series are disc type small pressure controls featuring compact structure and field proven high quality. It is designed to suit modern designed application with its compact and various type of connection styles, such application as air conditioning, automobile industries and others. Type ACB High & medium pressure range Type LC B Low pressure range Type HCBHigh working pressure Type GCBDual pressure controls Type TCB Triple pressure controls mark applicable (available upon request)

Type ACB

Type ACB

UL recognized (available upon request)


STANDARD TYPE NUMBER SELECTION
Type ACB & LCB
Catalog No. Range Min. Max. Max. Pressure Contact Functions Pressure Connections Female Flare SPST (High Cut) 1/4" Solder ACB 0.7 {7} 4.5 {45} 4.5 {45} SPDT SPSTManual Reset SPDTManual Reset Female Flare Open LCB 0.1 {1} 0.7 {7} 1.5 {15} SPST (Low Cut) 1/4" Solder Water Proof Fan Control Low Pressure Cut Out Terminal Construction Open Water Proof Open Water Proof Open Water Proof High Pressure Cut Out Application

Type HCB

Unit: MPa {kgf/cm2} Dimension 0.03 0.06 0.06 Wt. (kg) 0.03 0.06 0.03 0.06 0.03

Type HCB
Catalog No. Setting Off 2.50.3 {25.53} On 2.00.3 {20.43} Max. Pressure 8.0 {80} Contact Functions Pressure Connections Male M10 Terminal Construction Direct Coupler Application High Working Pressure Wt. (kg) 0.044

HCB

SPST

Type GCB & TCB


Catalog No. Setting Off Low 0.20.02 {2.00.2} High 3.140.2 {322.0} Low 0.20.02 {2.00.2} 0.226 TCB Mid. 1.550.13 {15.81.3} High 3.140.2 {322.0} On 0.025 0.25 2.3 0.03 0.3 Differential Less Than 0.03 {0.3} 0.60.2 {6.12.0} Max. Pressure Contact Functions SPST (Low Cut) SPST (High Cut) 5.4 {54} SPST (Low Cut) SPST (Low Cut) SPST (High Cut) Male M11 Direct Coupler Pressure Terminal Connections Construction Application Wt. (kg)

GCB

Dual Pressure 0.024 Controls Triple Pressure Controls

More Than 0.02 {More Than 0.2} (0.29) {(3)} 0.590.2 {62}

1.230.15 {12.51.5} (2.55) {(26)}

0.031

ELECTRICAL RATINGS
Type ACB, LCB & HCB
Category of Ratings Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125V.AC 1 to 6 1 to 24 M Rating 250V.AC 1 to 4 1 to 16 12V.DC 1 to 4 125V.AC 0.02 to 2 0.02 to 8 L Rating 250V.AC 0.02 to 1 0.02 to 4 12V.DC 0.02 to 0.1 T Rating 12/24V.DC 0.01 to 0.025

Type GCB & TCB

24V. DC 2.5A (12V. DC 5A)

CONTACT FUNCTIONS
Type ACB, LCB & HCB
C RED PRESS. RISING Code A PRESS. RISING Code B L BLUE H BLACK M C H PRESS. RISING Code B w/Manual C RED M L BLUE H BLACK

PRESS. RISING Code C

PRESS. RISING Code C w/Manual

Type TCB
High Press. Middle Press. Low Press.

Type GCB
High Press. Low Press. Operating direction on press. increase at High Press.Side : M Operating direction on manual reset :

PRESSURE CONNECTIONS
1/4" Female Flare 1/4" Male Flare
7

Unit: mm Capillary 1/4" Copper Solder 1/8" Male PT

Hex. 12 7/16 20UNF

13.5

9.5

Schrader Depressor 9 10

5 I.D. 6.35

R 1/8"

Hex. 14 3/8 24UNF

2.4 1L 300mm 7.5

DIMENSIONS

14 21.6

Unit: mm
Reset Button

Hex. 14 7/16 20UNF

16.5

16.9 43.9

10.5

Hex. 14 7/16 20UNF 16.4 32 1000

24

22.6

13 39

L1000

Hex. 14 7/16 20UNF 16.4 33 1000

Hex. 14 7/16 20UNF 16.4 53.4 4 15 10 M40.7

8 14 21.7

Type HCB 68
6.35 25.6

49.4 12

58.2 85.5

16.8

10.5

8 22.6

Type GCB 139


29 18.6

41.5 20.5 7 14

6.35

59

33

1000

21.7

Type TCB 2
29 18.3 Hex. 14 7/16 20UNF 16.5 19.2 46.6 10.9

53 21.9 15.1

16

24

L1000

Hex. 14 7/16 20UNF

16.4 50.4

30

10

1/4" Female Flare

O Ring
L

57

10

SMALL PRESSURE CONTROLS


High Volume OEM Item Type LTB, ETB, HTB & FTB GENERAL DESCRIPTION
Factory set pressure switch designed for use in refrigeration units of quantity production such as room air conditioner (heat pump), packaged air conditioner (heat pump), water chiller etc. With SPDT contact mechanism. Models identified with electrical rating code L can be used for minimum 0.02A/125V.AC rating. Models with 0.78 to 1.96 MPa {8 to 20 kgf/cm2} range are also available for HTB and FTB. Models with 0.10 MPa {1 kgf/cm2} differential are also available for HTB (max. range limit: 1.27 MPa {13 kgf/ cm2}). mark applicable (available upon request)

Type HTB

UL recognized (available upon request)


Type FTB

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. LTBA301 LTBA302 LTBA303 LTBA304 LTBA305 LTBA306 ETBA301 ETBA302 ETBA303 ETBA304 ETBA305 ETBA306 HTBA301 HTBA302 HTBA303 HTBA304 HTBA305 HTBA306 FTBA301 FTBA302 FTBA303 FTBA304 FTBA305 FTBA306 Refer to Electrical Ratings Table in the list below. High Pressure 1.96 {20} 2.94 {30} Automatic operation on pressure increase and manual reset Lower Limit 0.29 to 0.49 {3 to 5} Upper Limit 0.29 to 0.69 {3 to 7} 0.098 {1} 0.245 {2.5} Low Pressure Automatic operation on pressure decrease and manual reset 1.5 {15} 0 0.392 {4} 0.059 to 0.147 {0.6 to 1.5} 0.294 {3} 0.196 {2} Application Range Min. Max. Differential Factory Setting On Off Max. Working Pressure

Unit: MPa {kgf/cm2} Pressure Electrical Wt. Connections Ratings (kg) H M L H M L H M L H M L H M L H M L H M L H M L 0.08

Manual Reset

0.098 {1}

0.1

1.96 {20}

0.09

2.45 {25}

3.3 {33}

Manual Reset

0.1

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Full Load Locked Rotor CH CL Terminal Power Factor (cos) 1 0.75 0.45 1 0.75 0.45 H Rating 125V.AC 1 to 10 1 to 6 1 to 24 1 to 16 1 to 64 250V.AC 1 to 10 1 to 6 1 to 24 1 to 16 1 to 64 1 to 3 1 to 2 1 to 8 1 to 6 1 to 24 M Rating 125V.AC 250V.AC 0.5 to 1.5 0.5 to 1 0.5 to 4 0.5 to 5 0.5 to 4 0.5 to 16 L Rating 125V.AC 0.02 to 2 0.02 to 8 0.02 to 2 0.02 to 8 250V.AC 0.02 to 1 0.02 to 4 0.02 to 1 0.02 to 4

Non-Inductive Current Inductive Current

11

CONTACT FUNCTIONS
Type LTB & HTB Type ETB (M2 : Manual Reset) Type FTB (M1 : Manual Reset)
M1 C H

C
L

Common Terminal Close on Pressure Increase Close on Pressure Decrease

L C H C M2

L H

L H

Operating direction on press. increase at High Press.Side : M1 M2 Operating direction on manual reset , :

PRESSURE CONNECTIONS
2.41000 Capillary Tube

2.41000 Capillary Tube

Dust Protection Cap 1/4" Flare Nut

1/4" Solder Connection is also available upon request.

DIMENSIONS
Type LTB
68 2 M40.7 36 24.5

Type ETB
64.5 36

18

2 M40.7

Max. 42 55

Max. 40 55 Faston Terminal 3 #250 Max. 47 Faston Terminal 3 #250 13.9

Reset Button

2.41000 2.41000

Type HTB
64.5 2 M40.7 36

Type FTB
64.5 36

Max. 50 Max. 42 55 13.5 Max. 50 18

18 18 26 2 M40.7 Max. 50 Faston Terminal 3 #250 2.41000

Max. 42 55 Faston Terminal 3 #250

2.41000

Unit: mm

26

26

12

SINGLE FUNCTION PRESSURE CONTROLS


Type SNS & HNS GENERAL DESCRIPTION
For use with fluorinated refrigerants as well as with air and water. (Allowable fluid temp.: 20 to 120C) Type SNS for universal application. Type HNS for high pressure safety cut out. Available drip proof enclosure for marine application or explosion proof enclosure for special application. Mounting bracket is supplied as standard. With SPDT contact mechanism. IP44 with upper lid (option). Ammonia Models: Available upon request. mark applicable (available upon request)

UL recognized (available upon request)


TYPE NUMBER SELECTION (SPECIFICATIONS)
Type SNSAutomatic Reset Type
Catalog No. SNSC101X SNSC102X SNSC103X SNSC104X SNSC106X SNSC110X SNSC120X SNSC130X SNSC135X Range Min. 0.06 {50cmHg} 0.02 {20cmHg} 0.06 {50cmHg} 0.06 {50cmHg} 0.06 {50cmHg} 0.1 {1} 0.5 {5} 1 {10} Max. 0.1 {1} 0.2 {2} 0.3 {3} 0.4 {4} 0.6 {6} 1 {10} 2 {20} 3 {30} 3.5 {35} Min. 0.015 {0.15} 0.025 {0.25} 0.035 {0.35} 0.04 {0.4} 0.06 {0.6} 0.1 {1} 0.2 {2} 0.3 {3} 0.5 {5} Differential Max. 0.05 {0.5} 0.15 {1.5} 0.2 {2} 0.4 {4} 0.3 {3} 0.5 {5} 1 {10} 1.5 {15}

Type SNS Type HNS

Unit: MPa {kgf/cm2} Factory Setting Off (On) 0.025 {0.25} 0.05 {0.5} 0.1 {1} 0.2 {2} 0.4 {4} 1.2 {12} 2 {20} 2.5 {25} On (Off) 0.05 {0.5} 0.15 {1.5} 0.2 {2} 0.3 {3} 0.6 {6} 1.5 {15} 2.5 {25} 3 {30} 3 {30} 3.3 {33} 3.8 {38} 1.5 {15} Diagram 1 0.33 Max. Working Contact Pressure Function 0.3 {3} 0.5 {5} 1 {10} Wt. (kg)

Type SNSManual Reset Type


Catalog No. Range Min. Max. 0.2 {2} 0.6 {6} 3 {30} Manual Reset Automatic operation on pressure decrease, and manual reset. Off 0.025 {0.25} 0.2 {2} 2 {20} manual reset Factory Setting On

Unit: MPa {kgf/cm2} Max. Working Contact Pressure Function 0.5 {5} 1.5 {15} 3.3 {33} Diagram 2 0.33 Wt. (kg)

SNSC102XM2 0.02 {20cmHg} SNSC106XM2 0.06 {50cmHg} SNSC130XM2 0.5 {5} Based on the 13 terminal connection.

Type HNSAutomatic Reset Type


Catalog No. Range Min. 0.8 {8} Max. 3 {30} Differential 0.3 to 0.5 fixed {3 to 5 fixed} Factory Setting Off 2 {20} On 1.6 {16} Max. Working Pressure 3.3 {33}

Unit: MPa {kgf/cm2} Contact Function Diagram 3 Wt. (kg) 0.24

HNSC130X

Based on the 13 terminal connection.

Type HNSManual Reset Type


Catalog No. Range Min. 0.8 {8} Max. 3 {30} Manual Reset Factory Setting Off 2 {20} On manual reset Max. Working Pressure 3.3 {33}

Unit: MPa {kgf/cm2} Contact Function Diagram 4 Wt. (kg) 0.24

HNSC130XM1

Automatic operation on pressure increase, and manual reset.

Based on the 13 terminal connection. Enclosure: IP20 Drip Proof Models: Available upon request. (Refer to Pages 48, 49.)

13

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125/250V. AC

CONTACT FUNCTIONS
3 1 1 5 M2 5 3

12 72 Diagram 1

Diagram 2

PRESSURE CONNECTIONS
1

5 1 3

M1

5 3

Diagram 3 Diagram 1 & 2 1 3


1/4" Flare 7/16 20 Thread

Diagram 4 Diagram 3 & 4 Common Terminal Open on Pressure Increase Open on Pressure Decrease

Common Terminal Close on Pressure Increase Close on Pressure Decrease

5 Refer to Pages 45, 46

Operating direction on press. increase at High Press. Side : M1, M2 Operating direction on manual reset :

Standard

DIMENSIONS
Standard Model Type SNS
4 M40.7 Thread Mounting Hole for Bracket Differential Adjusting Screw Range Adjusting Screw 80 9.4 54 50 36.4 22.4 17.3 250.5 20.8

Catalog No. SNSC101X SNSC102X SNSC103X SNSC104X SNSC106X SNSC110X SNSC120X SNSC130X SNSC135X SNSC102XM2 SNSC106XM2 SNSC130XM2

Unit: mm A 113.3 99.7 22.4 96.8 95.9 93.5 99.7 96.8 93.5 18.4 B

Reset Button 63.1 A

22.4 18.4

20.5

6 1/4" Flare Nut

Type HNS
4 M40.7 Thread Mounting Hole for Bracket Range Adjusting Screw 59 9.4 54 48.8 33.4 17.3 250.5 20.8

91

63.1

Reset Button

22

19

6 1/4" Flare Nut

17.4

Unit: mm

14

PRESSURE CONTROLS WITH NARROW DIFFERENTIAL


Type FNS & ANS GENERAL DESCRIPTION
For use with fluorinated refrigerants as well as with air and water. (Allowable fluid temp.: 20 to 120C) Type FNS with fixed narrow differential Type ANS with adjustable narrow differential Available drip proof enclosure for marine application or explosion proof enclosure for special application. Mounting bracket is supplied as standard. With SPDT contact mechanism. IP44 with upper lid (option). Type FNS Ammonia models: Available upon request. mark applicable (available upon request)
Type FNS

Type ANS

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type FNSFixed narrow differential
Catalog No. Range Min. 0.06 {50cmHg} 0.02 {20cmHg} 0.06 {50cmHg} 0.1 {1} 0.5 {5} Max. 0.1 {1} 0.2 {2} 0.6 {6} 1 {10} 3 {30} Differential Fixed 0.006 approx. {0.06 approx.} 0.008 approx. {0.08 approx.} 0.02 approx. {0.2 approx.} 0.025 approx. {0.25 approx.} 0.12 approx. {1.2 approx.} Off (0.019) {(0.19)} (0.042) {(0.42)} (0.28) {(2.8)} (0.575) {(5.75)} (2.38) {(23.8)} Factory Setting On 0.025 {0.25} 0.05 {0.5} 0.3 {3.0} 0.6 {6.0} 2.5 {25} Unit: MPa {kgf/cm2} Max. Working Pressure 0.3 {3} 0.5 {5} 0.32 1.5 {15} Wt. (kg)

FNSC101X FNSC102X FNSC106X FNSC110X FNSC130X

3.3 {33}

Type ANSAdjustable narrow differential


Catalog No. Min. ANSC101XB ANSC103XB ANSC106XB ANSC110XB ANSC130XB ANSC135XB 0.06 {50cmHg} 0.02 {20cmHg} 0.06 {50cmHg} 0.1 {1} 0.5 {5} 1 {10} Range Max. 0.1 {1} 0.3 {3} 0.6 {6} 1 {10} 3 {30} 3.5 {35} Bottom 0.007 {0.07} 0.008 {0.08} 0.015 {0.15} 0.02 {0.2} Differential Min. Top 0.007 {0.07} 0.01 {0.1} 0.018 {0.18} 0.03 {0.3} Bottom 0.014 {0.14} 0.018 {0.18} 0.03 {0.3} 0.045 {0.45} 0.23 {2.3} 0.24 {2.4} Max. Top 0.015 {0.15} 0.027 {0.27} 0.045 {0.45} 0.07 {0.7} 0.37 {3.7} 0.39 {3.9} Factory Setting Off 0.018 {0.18} 0.141 {1.41} 0.28 {2.84} 0.575 {5.75} 2.32 {23.2} 2.82 {28.2} On 0.025 {0.25} 0.15 {1.5} 0.3 {3.0} 0.6 {6.0} 2.5 {25} 3 {30}

Unit: MPa {kgf/cm2} Max. Working Pressure 0.3 {3} 1 {10} Wt. (kg)

1.5 {15}

0.32

0.12 {1.2}

0.2 {2.0}

3.3 {33} 3.8 {38}

Enclosure: IP20 Drip Proof Models: Available upon request. (Refer to Pages 48, 49.)

15

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125/250V. AC

CONTACT FUNCTIONS
3 1 5

12 72 1 3 5

Common Terminal Close on Pressure Increase Close on Pressure Decrease

Operating direction on press. increase at High Press. Side :

PRESSURE CONNECTIONS

1/4" Flare

Refer to Pages 45, 46 Standard

DIMENSIONS
Standard Model Type FNS
Range Adjusting Screw 80 4 M40.7 Thread Mounting Hole for Bracket 50 22.4 17.3 250.5 20.8

Catalog No. FNSC101X FNSC102X FNSC106X FNSC110X FNSC130X

Unit: mm A 113.3 99.7 96.8 93.5 18.4 22.4 B

20.5

6 1/4" Flare Nut

63.1

Type ANS
4 M40.7 Thread Mounting Hole for Bracket 80 21 Range Adjusting Dial 50 22.4 17.3 250.5 20.8 8

Catalog No. ANSC101XB ANSC103XB ANSC106XB ANSC110XB ANSC130XB ANSC135XB

Unit: mm A 113.3 99.7 96.8 93.5 18.4 22.4 B

20.5

6 1/4" Flare Nut

63.1

Unit: mm

16

DUAL PRESSURE CONTROLS


Type DNS GENERAL DESCRIPTION
For use with fluorinated refrigerants as well as with air and water. (Allowable Fluid Temp.: 20 to 120C) Various contact functions are available. Available drip proof enclosure for marine application or explosion proof enclosure for special application. Mounting bracket is supplied as standard. IP44 with upper lid (option). Ammonia models: Available upon request. mark applicable (available upon request)

UL recognized (available upon request)

TYPE NUMBER SELECTION (SPECIFICATIONS)


Automatic Reset Type
Catalog No. Pressure Side Low Side High Side Low Side High Side Low Side High Side Low Side High Side Range Min. 0.06 {50cmHg} 0.8 {8} 0.06 {50cmHg} 0.8 {8} 0.06 {50cmHg} 0.8 {8} 0.06 {50cmHg} 0.8 {8} Max. 0.4 {4} 3 {30} 0.6 {6} 3 {30} 0.4 {4} 3 {30} 0.6 {6} 3 {30} Min. 0.04 {0.4} 0.06 {0.6} 0.04 {0.4} 0.06 {0.6} Differential Max. 0.2 {2} 0.4 {4} 0.2 {2} 0.4 {4} Factory Setting Off 0.1 {1} 2 {20} 0.2 {2} 2 {20} 0.1 {1} 2 {20} 0.2 {2} 2 {20} On 0.2 {2} 1.6 {16} 0.3 {3} 1.6 {16} 0.2 {2} 1.6 {16} 0.3 {3} 1.6 {16} Unit: MPa {kgf/cm2} Max. Working Contact Pressure Function 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} Diagram 3 Diagram 1 0.49 Wt. (kg)

DNSD304X DNSD306X DNSD604X DNSD606X

Approx. 0.4 fixed {Approx. 4 fixed} Approx. 0.4 fixed {Approx. 4 fixed} Approx. 0.4 fixed {Approx. 4 fixed} Approx. 0.4 fixed {Approx. 4 fixed}

Manual Reset Type


Catalog No. Pressure Side Range Min. 0.8 {8} 0.8 {8} 0.8 {8} 0.8 {8} 0.8 {8} Max. 3 {30} 3 {30} 3 {30} 3 {30} 3 {30} Min. 0.04 {0.4} 0.06 {0.6} 0.04 {0.4} 0.06 {0.6} Differential Max. 0.2 {2} 0.4 {4} 0.2 {2} 0.4 {4} Factory Setting Off 0.1 {1} 2 {20} 0.2 {2} 2 {20} 0.1 {1} 2 {20} 0.2 {2} 2 {20} 0.2 {2} 2 {20} manual reset On 0.2 {2} manual reset 0.3 {3} manual reset 0.2 {2} manual reset 0.3 {3}

Unit: MPa {kgf/cm2} Max. Working Contact Wt. Pressure Function (kg) 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} 1.5 {15} 3.3 {33} Diagram 5 Diagram 4 0.49 Diagram 2

DNSD304XM DNSD306XM DNSD604XM DNSD606XM DNSD606XMM

Low Side 0.06 {50cmHg} 0.4 {4} High Side High Side High Side High Side High Side Low Side 0.06 {50cmHg} 0.6 {6} Low Side 0.06 {50cmHg} 0.4 {4} Low Side 0.06 {50cmHg} 0.6 {6} Low Side 0.06 {50cmHg} 0.6 {6}

Automatic operation on pressure rise, and manual reset. Automatic operation on pressure rise, and manual reset. Automatic operation on pressure rise, and manual reset. Automatic operation on pressure rise, and manual reset. Automatic operation on pressure decrease, and manual reset. Automatic operation on pressure rise, and manual reset.

Enclosure: IP20 Drip Proof Models: Available upon request. (Refer to Pages 48, 49.)

17

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125/250V. AC 12 72

CONTACT FUNCTIONS
L 1 2 H 4 3 1 2 H L 4 M 3

Diagram 1

Diagram 2

L 1

4 3 1

4 M 3 1 M L

4 M 3

6 H

6 H

6 H

L: Operating direction on press. increase at Low Press. Side H: Operating direction on press. increase at High Press. Side M: Operating direction on manual reset

Diagram 3

Diagram 4

Diagram 5

PRESSURE CONNECTIONS

1/4" Flare 7/1620 Thread

Refer to Pages 45, 46 Standard

DIMENSIONS
Standard Model
Low Range Differential Adjusting Screw Low Range Adjusting Screw High Range Adjusting Screw Reset Button 54 50 36.4 22.4 4 M40.7 Thread Mounting Hole for Bracket 20.8 17.4 22.4 17.3 250.5

106

34.4 22 20.5 20.5

6 1/4" Flare Nut 24 63

96.8 63.1

9.4

Unit: mm

18

OIL PROTECTION CONTROLS


Type ONS GENERAL DESCRIPTION
Provides dependable protection against major breakdown on pressure lubricated refrigeration compressors by guarding against low lubrication oil pressure. With manual reset. Built in time delay switch. Mounting bracket is supplied as standard. Ammonia models, drip proof models are available upon request. mark applicable (available upon request)

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No.
ONSC106XQ1 ONSC106XQ2 ONSC106XQ3 ONSC106XQ4 ONSC106XQ5 ONSC106XQ6 ONSC106XQ7 ONSC106XQ8 ONSC106XQ9 ONSC106XQ10 ONSC106XQ11 ONSC106XQ12 ONSC106XL1Q1 ONSC106XL1Q2 ONSC106XL1Q3 ONSC106XL1Q4 ONSC106XL1Q5 ONSC106XL1Q6 ONSC106XL1Q7 ONSC106XL1Q8 ONSC106XL1Q9 ONSC106XL1Q10 ONSC106XL1Q11 ONSC106XL1Q12 ONSC106XQ25 ONSC106XQ26 ONSC106XQ27 ONSC106XQ28 ONSC106XQ29 ONSC106XQ30 ONSC106XQ31 ONSC106XQ32 ONSC106XQ33 ONSC106XQ34 ONSC106XQ35 ONSC106XQ36 ONSC106XL1Q25 ONSC106XL1Q26 ONSC106XL1Q27 ONSC106XL1Q28 ONSC106XL1Q29 ONSC106XL1Q30 ONSC106XL1Q31 ONSC106XL1Q32 ONSC106XL1Q33 ONSC106XL1Q34 ONSC106XL1Q35 ONSC106XL1Q36

Unit: MPa {kgf/cm2} Timer Specification Connection Wt. (kg)

Range Min. Max.

Differential

Delay Time(sec.) 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110 45 90 110

Timer Voltage 100/200V. AC

Timer Circuit

110/220V. AC 1/4" Flare Nut 115/230V. AC Standard (SPST) without Alarm Contact 0.55

120/240V. AC

100/200V. AC

110/220V. AC

115/230V. AC

1000mm Capil. Tube with 1/4" Flare Nut

0.62

0.05 {0.5}

0.35 {3.5}

Approx. 0.05 fixed Approx. 0.5 fixed

120/240V. AC

100/200V. AC

110/220V. AC 1/4" Flare Nut 115/230V. AC 0.55

120/240V. AC

100/200V. AC

With Alarm Contact (SPDT)

110/220V. AC

115/230V. AC

1000mm Capil. Tube with 1/4" Flare Nut

0.62

120/240V. AC

Max. Working Pressure: 1.5 MPa {15 kgf/cm2} Limit of Pressure Diff. HpLp: 1.5 MPa {15 kgf/cm2}, Hp represents oil pump discharge pressure and Lp crank case pressure. Enclosure: IP20 Drip Proof Construction type is available upon request. Please, add W into the catalog number on ordering; for example, ONSC106XWQ30. Ammonia Application type ONSC106XN is also available upon request (Differential to be 0.06 MPa {0.6 kgf/cm2} fixed).

19

ELECTRICAL RATINGS
Rated Voltage. (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125/250 V. AC 3.5 3 10

CONTACT FUNCTIONS
Heater Circuit 1 Motor Circuit M L3 L2 100V Heater L1

PRESSURE CONNECTIONS

200V

: Operating direction of pressure increase c: Operating direction of timer when energized M: Operating direction of manual reset L3: Alarm Contact provided with a lead wire approx. 3.5100mm with a soldered terminal.

1/4" Flare 7/16 20 Thread

Standard

Refer to Pages 45, 46

1 100 200 L1 L2 L3 Motor Circuit Heater Circuit

Common Terminal 100V Power Supply Terminal 200V Power Supply Terminal Open on Decrease of Pressure Difference Main Contact Alarm Contact

110/220V. AC, 120/240V. AC etc. available

DIMENSIONS
Lead wire for Alarm Contact 18.9

20.5

34.4

62.8 142.2

20.5

6 1/4"Flare Nut

13 Reset Button

115.8 20.5 250.5 17.3 4M40.7 Thread Mounting Hole for Bracket 22.4

Unit: mm

49.1 51

20

DIFFERENTIAL PRESSURE CONTROLS


Type WNS GENERAL DESCRIPTION
For use on any application where the relationship between two pressure is critical to proper equipment operation. With SPDT contact mechanism. Available drip proof enclosure for marine application or explosion proof enclosure for special application. Mounting bracket is supplied as standard. Ammonia models are also available. mark applicable (available upon request)

UL recognized (available upon request)

TYPE NUMBER SELECTION (SPECIFICATIONS)


For water, air and fluorinated refrigerant.
Catalog No. WNSC102X WNSC106X Range Min. 0.03 {0.3} 0.05 {0.5} Max. 0.2 {2} 0.35 {3.5} Min. 0.03 {0.3} 0.05 {0.5} Differential Max. 0.15 {1.5} 0.25 {2.5} Factory Setting Off 0.05 {0.5} 0.1 {1.0} On 0.02 {0.2} 0.05 {0.5} Max. Working Pressure 0.5 {5} 1.5 {15} Unit: MPa {kgf/cm2} Limit of Wt. Press. Differential (kg) (HPLP) 0.5 {5} 0.43 1.5 {15} Allowable Fluid Temp.: 20 to 120C HP......High Side Press. LP......Low Side Press. Enclosure: IP20 Drip proof models: Available upon request. (Refer to Pages 48, 49.)

ELECTRICAL RATINGS
Rated Voltage. (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125/250 V. AC

CONTACT FUNCTIONS
1 Common Terminal Close on Pressure Increase Close on Pressure Decrease

3 1
12 72 Operating direction on press. increase at High Press. Side : 2

5
3

PRESSURE CONNECTIONS

DIMENSIONS

1/4" Flare 7/16 20 Thread 20.5

Refer to Pages 45, 46 Standard

20.5 B 63.1 D 6 1/4" Flare Nut C

Catalog No. WNSC102X WNSC106X

38.5 47.4 36.7 147.2 34.4 44.4 33.7 141.2

22.4

50

Unit: mm

20.8

250.5 17.3

4 M40.7 Thread Mounting Hole for Bracket

Unit: mm

21

24

80

DIGITAL PRESSURE SWITCHES


Type CFE GENERAL DESCRIPTION
All functions can be set by 3 push button switches. Independent ON/OFF setting. ON Delay Timer function. Pressure calibration mark applicable (available upon request)

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. CFESC10B001 CFESC35B001 CFESC10B101 CFESC35B102 Setting/Indication Range Min. 0.095 0 0.95 bar 0 bar Max. 0.995 3.5 9.95 bar 35 bar Setting resolution 0.005 0.02 0.05 bar 0.2 bar Calibration range 0.03 0.12 0.3 bar 1.2 bar Airtight Pressure 3.85

Unit: MPa Wt. (kg)

0.3 38.5 bar

COMMON SPECIFICATIONS
Supply voltage: 230V. AC10% 50/60Hz Output contact rating: 125/250V. AC 1A(cos1) SPST On delay timer: 0 to 240 sec (step1sec.) Ambient temp. range: 10 to 60C Storage temperature range: 20 to 70C Fluid: Refrigerants (excluding ammonia), water, air. Pressure connection: 1/4" male flare Enclosure: IPX2

WIRING
Pressure switch unit Power supply Load Output C Load power supply Power supply NO

OPERATION
OPERATION PATTERN
During Set Low (LoC)
Output Relay ON Output Relay OFF OFF Press. Increase ON ON

DIMENSIONS
90

During Set High (HiC)


Output Relay ON Output Relay OFF Press. Increase OFF

2 M40.7 Screw mounting pitch 25 65.8 1/4" Flare Nut Attached 29.2 32.5

DELAY TIMER OPERATION PATTERN


During Set Low (LoC)
OUTPUT Relay ON OFF

During Set High (HiC)


OUTPUT Relay ON OFF 25 12.8

Press ON OFF

Delay timer

Press OFF ON Time

Delay timer

Time

In case pressure decrease than the ON pressure during working of Delay timer, timer is reset, and dose not turn on.

In case pressure increase than the ON pressure during working of Delay timer, timer is reset, and dose not turn on.

Unit: mm

26.6

53.6

22

PRESSURE SENSORS
High Volume OEM Item (Type NSK) Type NSK & XSK GENERAL DESCRIPTION
High reliability and accuracy Double diaphragm structure Diffusion silicone chip pressure sensor

COMMON SPECIFICATIONS
Fluid temperature range: 30 to 120C (Type NSK) 20 to 70C (Type XSK) Ambient temperature range: 30 to 100C (Type NSK) 30 to 80C (Type NSK-BD) 20 to 70C (Type XSK) mark applicable (available upon request)

Type NSKBC

Type NSKBE

Type XSK

UL recognized (available upon request)


TYPE NUMBER SELECTION (SPECIFICATIONS)
Catalog No. NSKBC010I103 NSKBC020I103 NSKBC030I103 NSKBC035I103 NSKBC050I103 NSKBE010I103 NSKBE020I103 NSKBE030I103 NSKBE035I103 NSKBE050I103 NSKBD010D103 NSKBD020D103 NSKBD030D103 NSKBD035D103 NSKBD050D103 XSKAC10I194 XSKAC20I194 XSKAC30I194 XSKAC35I194 XSKAC50I194 Pressure Range 0 to 1 {0 to 10} 0 to 2 {0 to 20} 0 to 3 {0 to 30} 0 to 3.5 {0 to 35} 0 to 5 {0 to 50} 0 to 1 {0 to 10} 0 to 2 {0 to 20} 0 to 3 {0 to 30} 0 to 3.5 {0 to 35} 0 to 5 {0 to 50} 0 to 1 {0 to 10} 0 to 2 {0 to 20} 0 to 3 {0 to 30} 0 to 3.5 {0 to 35} 0 to 5 {0 to 50} 0.05 to 1 {0.5 to 10} 0 to 2 {0 to 20} 0 to 3 {0 to 30} 0 to 3.5 {0 to 35} 0 to 5 {0 to 50} Supply Voltage Output Accuracy Current Consumption Load Resistance Unit: MPa {bar} Airtight Pressure Wt. (kg)

2.5% F.S. 3.85 {38.5}

5V. DC 0.25V 0.5 to 4.5V. DC 2.0% F.S.

Max. 10mA

Min. 10 K

0.04

2.5% F.S.

5.5 {55}

2.5% F.S. 3.85 {38.5}

5V. DC 0.25V 0.5 to 4.5V. DC 2.0% F.S.

Max. 10mA

Min. 10 K

0.04

2.5% F.S.

5.5 {55}

2.5% F.S. 3.85 {38.5}

5V. DC 0.25V 0.5 to 4.5V. DC 2.0% F.S.

Max. 10mA

Min. 10 K

0.07

2.5% F.S.

5.5 {55}

Max. 100 at 12V. DC 10.5 to 28V. DC 4 to 20mA 3% F.S. Max. 500 at 24V. DC

3.85 {38.5}

0.09

5.5 {55}

Included non lineality hysteresis, and temperature drift Enclosure IP66

WIRING
1 Red 2 White Type NSK 3 Black Receiver Type XSK 1 Red Power Supply 5V. DC0.25V. Connector 3 White Connector Receiver Power Supply 10.5 to 28V.DC

23

DIMENSIONS
Type NSKBC (Molex connector)
1000 Vout 3 2 GND Vout 23.9 Housing Body 25.6 11.8 19.7 1 Vcc

Type NSKBE (Packard connector)


GND Vcc

23.9 17

PIN 1.6 0.1 1.5 0.1

49

54.9

16.8

13.5

7/16 20 UNF Flare 1/4"

Type NSKBD (Lead wire direct Connector)


20.5 10.5 Epoxide Resin 10000

10.5

Type XSK (Molex connector)

16.8

PIN

1.5

7/16 20 UNF Flare 1/4"

1000

3 COM. 23.9

26.6 21.4

1 Vcc Housing Body

(23.3)

56.3

66.3

(94.4)

13.5

7/16-20 UNF Flare 1/4"

Unit: mm

6.35 (8)

ACCESSORY
Lead wire with connector is supplied as standard accessory expect for NSKBE type.

OPTIONAL PARTS
Bracket
NSK Type No. NSKPP02
20 2 4.5 5

XSK Type No. YSKPP02


26 2 4.5

23

30 58 67

15

21 58 67

25

24 21

Unit: mm

24

PRESSURE CONNECTIONS
Connection Material Stainless steel pressure connection is available upon request. (R, NPT only) Connection Style Standard connection style is 7/1620UNF Female Flare with schrader depressor. The following connection styles are available upon request.
7/1620UNF Female Flare 1/4" with schrader depressor 7/1620UNF Female Flare 1/4" 7/1620UNF Male Flare 1/4"

R (NPT)

Capillary Tube (Type NSK)

2.4 1.0 A

A 1/8" 1/4" 3/8"

Type NSK XSK XSK XSK 1/4" Copper Solder (Type NSK-BD)
50

25

TEMPERATURE & HUMIDITY CONTROLS


TEMPERATURE CONTROLS 2728 Type LWS, FWS, RWS & EWS TEMPERATURE CONTROLS 2930 Type TNS, CNS & INS TEMPERATURE CONTROLS 31 Type ALS & BLS PROPORTIONAL TEMPERATURE CONTROLS 32 Type PWS ROOM THERMOSTATS 3334 Type WRS ROOM THERMOSTATS 35 Type LRS ROOM HUMIDISTATS 36 Type AHS DIGITAL THERMOSTATS & DIGITAL HUMIDISTATS 3739 Type ULE & FLE DIGITAL THERMOSTATS 40 Type TNE ELECTRONIC STEP THERMOSTATS 4142 Type DSE & FSE ELECTRONIC DEFROST CONTROLS 43 Type DDE

26

TEMPERATURE & HUMIDITY CONTROLS

TEMPERATURE CONTROLS
REMOTE / DIRECT SENSING Type LWS, FWS, RWS & EWS GENERAL DESCRIPTION
Most suitable model can be selected from the variations of wide temperature range with either adjustable or fixed differential. Narrow differential is further advantageous. Sensing elements are air sensed and liquid sensed type depending on control media. Also, sensing element can be selected from remote or direct type depending on application. Single pole double throw contacts allows use for either heating or cooling application, with large contact rating as well. Adjusting mechanism is driver adjusting type as standard on delivery, but a knob assembly and a concealed plate are also supplied as standard accessories.

Type LWS

UL listed (available upon request)

Type EWS

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type LWSSet high type with standard remote sensing element.
Catalog No. Designation Type Contact Model 030 060 090 120 160 200 LWS C1 240 030 060 090 120 160 200 240 Standard L1(L1m) Option L2 (L2m) F (Fixed) R Standard L1(L1m) Option L2 (L2m) L3 (L3m) L5 (L5m) Standard L1(L1m) Option L2 (L2m) A (Variable) G Standard L1(L1m) Option L2 (L2m) L3 (L3m) L5 (L5m) Differential Rating Capillary Length Temp. Adjusting Range Min. 35 5 25 40 95 135 175 35 5 25 40 95 135 175 Max. 30 60 90 120 160 200 240 30 60 90 120 160 200 240 2.5 (Fixed) 9.570 2 (Fixed) 9.5100 9.585 2.5 8 9.570 20 to 70 2 7 Differential Bulb Size (mm) Min. Max. 9.5100 9.585 Ambient Temp. Limit of Bulb Temp. 60 90 120 150 185 230 265 60 90 120 150 185 230 265 0.45 Unit: C Wt. (kg)

Manual Reset Models of LWSC1030F and LWSC1060F for low limit application are available upon request. Knob assembly and control plate are supplied as standard accessories.

Type FWSAir Sensed type with standard remote sensing element.


Catalog No. Designation Type Contact Model 030 060 090 FWS C1 120 030 060 090 120 F (Fixed) A (Variable) G R Option L2 (L2m) L3 (L3m) L5 (L5m) Standard L1 (L1m) Differential Rating Capillary Length Temp. Adjusting Range Min. 35 5 25 40 35 5 25 40 Max. 30 60 90 120 30 60 90 120 2.5 (Fixed) 2 (Fixed) 2.5 8 Max. 3758 20 to 70 2 7 Differential Bulb Size (mm) Min. Max. Ambient Temp. Limit of Bulb Temp. 60 90 120 150 60 90 120 150

Unit: C Wt. (kg)

0.52

27

Type RWSwith coiled capillary sensing element.


Catalog No. Type Designation Contact Model 060 034 RWS C1 054 060 034 054 A (Variable) F (Fixed) G R Differential Rating Temp. Adjusting Range Min. 5 10 10 5 10 10 Max. 60 35 55 60 35 55 2 1.4 Differential Min. Max. Sensing Element (mm) Ambient Temp. 20 to 70 Coiled Tube Max. 4240 20 to 60 20 to 70 20 to 60 20 to 70 Limit of Tube Temp. 70 60 70 60 70

Unit: C Wt. (kg)

2 (Fixed) 1.4(Fixed) 7 5

0.43

Type EWSwith direct immersion sensing element.


Catalog No. Type Designation Contact Model 080 120 EWS C1 160 080 120 160 A (Variable) F (Fixed) G R Differential Rating Temp. Adjusting Range Min. 0 40 95 0 40 95 Max. 80 120 160 80 120 160 2.5 8 2.5 (Fixed) 10.870 20 to 70 Differential Min. Max. Sensing Element (mm) Ambient Temp. Limit of Tube Temp. 110 150 185 110 150 185

Unit: C Wt. (kg)

0.51

ELECTRICAL RATINGS
Electrical Rating Code G Rated Voltage (V) Power Factor 125V. AC 250V. AC Rated Amps. (A) (cos) Non-Inductive Current 1.0 0.5 to 16 0.5 to 8 Full Load 0.75 Inductive Current Locked Rotor 0.45 96 48 Non-Inductive Current R Inductive Current Full Load Locked Rotor 1.0 0.75 0.45 0.05 to 8.5 0.05 to 4.5 51 27

CONTACT STYLE
L C H
Models set high The dial indicates the high switch point ( close, open). The low switch point ( open, close) is obtained by deducting the differential from the high switch point. Arrow mark indicates a direction of switch action on temperature increase.

DIMENSIONS
Type LWS
22.5

Type FWS
22.5 Max.58 Capillary Tube 2 Max.37 26.2 43.5 43.5 9.5 Capillary Tube2 16 114

51.5 37 21

54

21

Max.42

Type RWS

Type EWS
52.5 22.5 22.5

40

114

2Screws M510 R1/2" Bulb Well

16

43.5 42 108

70

10.8

74 86

Unit: mm

28

TEMPERATURE CONTROLS
GENERAL PURPOSE Type TNS, CNS & INS GENERAL DESCRIPTION
Type TNS is provided with a differential adjustable mechanism. Type CNS is provided with a fixed differential. Also manual reset models are available. Type INS provides automatic High-cut temp. control with manual reset. Narrow and adjustable temp. diff. for more accurate control model Type BNS is available. Available drip proof enclosure for marine application or explosion proof enclosure for special application. A mounting bracket is supplied as standard. With SPDT contact mechanism. IP44 with upper lid (option). mark applicable (available upon request)

UL recognized (available upon request)

Type TNS

Type INS

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type TNSAutomatic Reset Type
Catalog No. TNSC100X TNSC114X TNSC134X TNSC1070X TNSC1100X TNSC1120X TNSC1150X TNSC1010XC TNSC1034XC TNSC1070XC TNSC114XQ009 TNSC114XQ010 TNSC134XQ009 TNSC134XQ010 Range Min. 25 15 0 45 65 95 115 45 20 15 30 5 Max. 0 15 35 75 105 125 150 10 35 70 15 35 Bottom 5 15 Top 2 12 15 4 Top 3 4 5 Differential Min. Bottom 4.5 15 Max. Factory Setting Off (On) 18 3 17 61 71 110 20 140 4 16 36 8 On (Off) 15 0 20 65 75 115 145 0 20 40 5 120 115 140 160 180 45 70 115 Capillary Tube Type Capillary Coil Type Capillary Tube Type Capillary Coil Type TSTB TS TB 0.37 12.7 100 TSTB 70 6 80 TSTB 0.34 Limit Temp. Bulb Size (mm) A B Usage Condition Unit: C Wt. (kg)

Bottom...Differential when the switch is set at minimum of range. Top...Differential when the switch is set at maximum of range. TS...Ambient temp. of switch body. TB...Sensing bulb temp. Drip proof models: Available upon request. (Refer to pages 48, 49.) Enclosure: IP20

Type CNSAutomatic Reset Type


Catalog No. CNSC115X CNSC100X CNSC114X CNSC134X Range Min. 35 25 15 0 Max. 15 0 15 35 Bottom 4 Top 3 Differential Factory Setting Off 28 18 3 17 On 25 15 0 20 70 6 80 TSTB Limit Temp. Bulb Size (mm) A B Usage Condition

Unit: C Wt. (kg)

0.34

Bottom...Differential when the switch is set at minimum of range. Top...Differential when the switch is set at maximum of range. TS...Ambient temp. of switch body. TB...Sensing bulb temp. Enclosure: IP20

29

TYPE CNSManual Reset Type


Catalog No. CNSC115XM2 CNSC100XM2 CNSC114XM2 CNSC134XM2 Range Min. 35 25 15 0 Max. 15 0 15 35 Manual Reset Automatic operation on temperature decrease and manual reset Factory Setting Off 28 18 3 17 Manual Reset 70 6 80 TSTB On Limit Temp. Bulb Size (mm) A B Usage Condition

Unit: C Wt. (kg)

0.34

Based on the 13 terminal connection. TS...Ambient temp. of switch body. TB...Sensing bulb temp. Enclosure: IP20

TYPE INSManual Reset Type


Catalog No. INSC1070XM1 INSC1120XM1 INSC1150XM1 Range Min. 25 70 115 Max. 75 120 150 Manual Reset Automatic operation on temperature increase and manual reset. Factory Setting Off Manual Reset On 65 115 140 Limit Temp. 115 160 180 9.5 80 TSTB Bulb Size (mm) A B Usage Condition

Unit: C Wt. (kg)

0.26

Based on the 13 terminal connection. TS...Ambient temp. of switch body. TB...Sensing bulb temp. Enclosure: IP20

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor 125/250 V. AC (cos) 1 12 0.75 0.45 72

CONTACT FUNCTIONS
TNSC1, CNSC1 CNSC1M2 INSC1M1

3 1 1 5
M2

3 5 1

M1

5 3

TNS & CNS Automatic Reset Type 1 3 5 Common Terminal

CNS Manual Reset Type

INS Manual Reset Type

Close on Temperature Increase Close on Temperature Decrease

Operating direction on temp. increase at High : temp. side M1,M2: Operating direction on manual reset

SENSING ELEMENT STYLE


Sensing Bulb Type Capillary Tube Type Capillary Coil Type

2.42000 A B 16 more than 400 Feeler

42

Feeler

Standard: 1000mm Capillary tube. Other capillary length are available upon request.

DIMENSIONS
Type TNS, CNS
Differential Adjusting Screw Type TNS Range Adjusting Screw 80 4 M40.7 Thread Mounting Hole for Breacket 54 36.4 22.4 250.5 20.8 Range Adjusting Screw

Type INS

4M40.7 Thread Mounting Hole for Bracket 54 48.8 33.4 17.3 250.5 20.8

59

9.4

9.4

Reset Button 63.1

RESET BUTTON 63.1

17.3

22

19 2.4 Capillary Tube 24 2.4 Capillary Tube 22.4 17.4

16

16

Unit: mm

9.7

2.4 Capillary Tube

30

TEMPERATURE CONTROLS
Type ALS & BLS GENERAL DESCRIPTION
Wide temp. range and narrow fixed differential. One control can meet most of your refrigeration or heating applications. Easy and accurate setting with large external knob. Tin Plating of bulb and capillary for food. SUS of main body for anti-corrosion and high durability, ABS resin of cover for anti-static. With SPDT contact mechanism. Insert holder is available upon request. Can mount horizontal and vertical position.

Type ALS

Type BLS

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. BLSC1020L1 ALSC1011L1 ALSC1020L1 ALSC1050L1 ALSC1090L1 Range Min. 20 60 40 10 40 Max. 20 10 20 50 90 Approx. 2.5 (Fixed) Differential Approx. 2.0 (Fixed) Limit of Bulb Temp. 60 80 110 150 10100 2.41000 Blub Size (mm) Capillary Tube Length (mm)

Unit: C Wt. (kg)

0.3

When order model with earth terminal, add a suffix x to Catalog No. Other capillary length is available upon request.

ELECTRICAL RATINGS
Rated Voltage (V) Power Factor 125V. AC 250V. AC 450V. AC 24V. DC 125V. DC Rated Amps. (A) (cos) Non-Inductive Current 1 0.5 10 5 2 5 Inductive Current Full Load Locked Rotor 0.75 0.45 8.5 50 4.5 37 1 10 3 10 0.2 5

CONTACT FUNCTIONS
L C H
C Arrow Mark indicates direction of operation on temperature increase.

Common Terminal Close on Temperature Increase Close on Temperature Decrease

DIMMENSIONS
34.5

L H

66

43

ACCESSARY
Mounting Bracket
5 15 7.5 25 15 5 12 6 10 20 6 7 65 30 95 2 7 10 40

Capillary Tube 2.4100050 10

25

84.4

100 34.5 18

16

7.5

5 15

25

13

47.5

6 1
1.5

100

33

Part No.

ALSAE02

Unit: mm

31

45.5

PROPORTIONAL TEMPERATURE CONTROLS


Type PWS GENERAL DESCRIPTION
Designed for accurate control for air and liquid temperature in duct and boiler. Incorporates a potentiometer which produces a variable voltage signal to actuate AWK/EGK type damper motor or MJV/WGK type motor valve. Proportional band (throttling range) is adjustable. Electrical rating: 24V. AC, 50mA. Potentiometer resistance 0 to 135.

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. PWS7034 PWS7054 PWS7074 PWS7094 PWS7120 PWS7060 With One Potentiometer Construction Adjustable Temp. Range 10 to 35 10 to 55 30 to 75 50 to 95 40 to 120 5 to 60 4 35 20 15 2.5 14
< TS > TB =

Unit: C Max. Usage Condition Max. Ambient Temp. At Switch Body At Sensing Buld 60 80 20 to 70 100 120 150 90 0.68 0.52 Wt. (kg)

Proportional Band Min.

INTERNAL WIRINGS (POTENTIOMETER ARRANGEMENT)


Temp. Rise

R V B

Resistance variation at potentiometer with increase of temperature: Increase between R and B Decrease between R and V R...Common terminal

DIMENSIONS
22.5 22.5 154

154

Standard: 2000mm Capillary tube. 1000mm, 3000mm and 5000mm capillary tubes are available upon request. (Exception of Type PWS7060)

16 Capillary Tube 22000

Type PWS7060

Capillary Tube 22000

51.5

43.5

51.5

43.5

100

130

16

Unit: mm

16

9.5

R1/2

32

ROOM THERMOSTATS
Type WRS GENERAL DESCRIPTION
For fan coil units and air conditioners. Used for low or line voltage. Various models available with Fan Selector switch and/or Heat-Off-Cool change over switching. Using a diaphragm element, it assures high reliability and accurate control. Ambient temperature: 20 to 50C

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Type Contact & Temp. Range Special Application X1 WRS C130 X2 X7 Sub-Base Function Change over Switch ONOFF, HEATCOOL ONOFF ONOFF, HEATCOOL HIGHMEDLOW 10 30 Fan Switch Range Min. Max. Differential

Unit: C Wt. (kg)

Approx. 1.5 (Fixed)

0.25

Change over switch of HEATCOOL on WRSC130X1 is only for changing switch mechanism of room thermostat itself between HIGHCUT (HEATING) and LOWCUT (COOLING) according to system requirement. Please refer to the application sample and wiring diagram.

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125V. AC 6 24 250V. AC 3 12

Minimum contact capacity: 50mA

33

CONTACT FUNCTIONS
Type Internal Wiring

OFF

HIGH MED.

YELLOW BLACK BLUE TO FAN SPEED CONTROL

ON OFF L

LOW

WRSC130X1

ON

C H

TEMP. RISE HEAT COOL

GRAY ORANGE

TO MOTOR VALVE L1

OFF

HIGH MED.

YELLOW BLACK BLUE RED BROWN TO COOLING CONTROL TO HEATING CONTROL L1 TO FAN SPEED CONTROL

ON OFF

LOW L H

WRSC130X2
C TEMP. RISE

ORANGE

OFF

HIGH MED.

YELLOW BLACK BLUE TO FAN SPEED CONTROL

ON OFF L C ON H TEMP. RISE HEAT COOL HEAT COOL

LOW

WRSC130X7

GRAY WHITE ORANGE

TO COOLING CONTROL TO HEATING CONTROL L1

Arrow indicates temp. rise.

DIMENSIONS
133 42 15 19

OFF

ON

90

15

20

L M H
25

HEAT COOL

Base

System Switches

20

20

Unit: mm

34

ROOM THERMOSTATS
Type LRS GENERAL DESCRIPTION
High quality room thermostat for heating or cooling. Used for low or line voltage. Precise and narrow differential. Ambient temperature: 20 to 50C

SPECIFICATIONS
Catalog No. Type LRS Contact Type C1 Temp. 30 Min. 10 Range Max. 30 Differential Approx. 1.5 (Fixed)

Unit: C Ambient Temp. On Use.

20 to 50

ELECTRICAL RATINGS
Rated Voltage (V) Power Factor 125V.AC 250V. AC 24V. DC Rated Amps. (A) (cos) Non-Inductive Current 1 2 6 3 Full Load 0.75 1 Inductive Current Locked Rotor 0.45 24 10 12 Minimum contact capacity: 50mA

CONTACT FUNCTIONS
h

Standard SPDT
Arrow indicates temp. rise.

DIMENSIONS
40 15 19 80

APPLICATION SAMPLES
h C H L Cooling Unit Power Power C H h L Heating Unit

Cooling Control

Heating Control

Base

Cover Dial Knob Body 76 68

Unit: mm

35

34.2

90

15

20

25

Arrow indicates temp. rise.

ROOM HUMIDISTATS
Type AHS GENERAL DESCRIPTION
Accurate humidity control assured by nylon ribbon. Used for low or line voltage. Easy adjustment by dial knob. Dial stopper screw prevents unauthorized change of setting.

SPECIFICATIONS
Catalog No. AHSC1090 Contact SPDT Range Min. 30 Max. 90 Differential Approx. 5 Ambient Temp. on Use (C) 10 to 40

Unit: % RH Wt. (kg) 0.17

ELECTRICAL RATINGS
Rated Voltage (V) Rated Current (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor 125V. AC 250V. AC 24V. DC (cos) 1.0 4.5 2 1 0.75 0.45 3 12 1.5 6 0.4 2

CONTACT FUNCTIONS
Internal Wiring

Minimum Contact Capacity: 50mA

DIMENSIONS
80

Application and Wiring Examples

H C
90

H
Solenoid Valve, Relay etc. for Humidifying Equipment

Power

Relay etc. for Dehumidifying Equipment

Power

Dehumidifying Control

Humidifying Control

Arrow mark indicates humidity increase.


76 68

39.5

34

Cover Body Adjusting Dial Knob

Sub-Base

Unit: mm

36

DIGITAL THERMOSTATS & DIGITAL HUMIDISTAT


Type ULE & FLE GENERAL DESCRIPTION
Large LED, easy to see Back up memory on power failure Easy operation with a combination of setting knob and keypads Either for wall or panel mounting. Power source voltage: 85 to 264V. AC 50/60Hz Relay output: 250V. AC, 6A (cos0.7) Ambient temperature: Controller...10 to 50C Humidity sensor...0 to 50C
Type ULE
Type FLE

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type ULE Digital Thermostats
Catalog No. ULESD11011 ULESD12011 ULESD13011 ULESD21011 ULESD22011 ULESD23011 0 to 100 50 to 30 Min. 0.5 0 to 110 55 to 40 Temp. Set Range Differential Temp. Indication Standard 2 Step Hi/Lo Limit with time delay Standard 2 Step Hi/Lo Limit with time delay TEK83H601 with 2m lead TEK83H609 with 2m lead 0.2 Function Sensor Part No. (Standard) Unit: C Wt. (kg)

Temperature sensor type TEK83H609 or TEK83H601, sensor holder and panel mounting brackets are supplied as standard accessory.

Type FLE Digital Humidistat


Catalog No. Humidity Set Range Differential Humidity Indication Calibration Sensor Part No.

Unit: %RH Wt. (kg) 0.3

FLESD11011

30 to 90

Min. 3

20 to 99

10

HEKI1R001

MODE & SETTING


STANDARD MODEL
Set LED Position NO OPERATION "SEL" Key "SEL" Key 2sec. "" or "" Key "SEL" Key "" or "" Key "SEL" Key "SEL" Key 2sec. "" or "" Key "ENT" Key 7Seg.LED: "on" and "ON SET Point": Alternate Blink ON SET LED: On ON SET LED: Blink ON Set Point of Thermostat (Humidistat) "" or "" Key "SEL" Key "" or "" Key Indication Temp. OF1: OFF Set Point of Thermostat No.1 ON1: ON Set Point of Thermostat No.1 "" or "" Key SET2 OFF OF2: OFF Set Point of Thermostat No.2 ON2: ON Set Point of Thermostat No.2 "SEL" Key "" or "" Key "" or "" Key "SEL" Key SET1 ON "SEL" Key Indication 7Seg LED: Temp.(Humi.) COOL/HEAT LED: On (DEHUMI/HUMI LED: ON) 7Seg LED: "C" or "H" COOL/HEAT LED: Blink (DEHUMI/HUMI LED: Blink) 7Seg LED: "C" or "H" (7Seg LED: "dHU" or "HU" 7Seg.LED: "oFF" Blink OFF SET LED: Blink Confirm of COOLING/HEATING (DEHUMI/HUMI)

HI/LO LIMIT WITH TIME DELAY


Key Operation No OPERATION "SEL" Key "SEL" Key 2sec. Mode Set of COOLING/HEATING (DEHUMI/HUMI) OFF Set Point of Thermostat (Humidistat) "" or "" Key "SEL" Key "" or "" Key "SEL" Key "SEL" Key 2sec. Indication 7Seg LED:Temp. COOL/HEAT LED:On Confirm of 7Seg LED: "C" or "H" COOLING/HEATING COOL/HEAT LED: Blink Mode Set of 7Seg LED: "C" or "H" COOLING/HEATING 7Seg.LED: "oFF" Blink OFF SET LED: Blink OFF Set Point of Thermostat 7Seg.LED: "on" and "ON Confirm of ON Set Set Point"Alternate Blink Point ON SET LED: On 7Seg.LED: "on" Blink ON SET LED: Blink ON Set Point of Thermostat

2 STEP MODEL
Set LED Position No Blink SET1 OFF

7Seg.LED: "H" and "HIGH ALRM TEMP."Alternate Blink TEMP. HIGH ALARM LED: Blink ON Set Point of High Alarm Temp. 7Seg.LED: "Ht" and "HIGH ALRM DELAY"Alternate Blink DELAY HIGH ALARM LED: Blink High Alarm Delay Time Set 7Seg.LED: "L" and "LOW ALRM TEMP."Alternate Blink TEMP. LOW ALARM LED: Blink ON Set Point of Low Alarm Temp. 7Seg.LED: "Lt" and "LOW ALRM DELAY"Alternate Blink DELAY LOW ALARM LED: Blink Low Alarm Delay Time Set

SET2 ON

"ENT" Key

37

OPERATION
ULEDIGITAL THERMOSTAT
STANDARD MODEL
Cooling Mode Operation On Off Off Min. 0.5 Operation On Off On Off Temp. Set Point Heating Mode Min. 0.5

6 7 Terminal

6 7 Terminal On Temp. Set Point

Free to set On/Off set point independently within the range. When Off set point is changed, On set point automatically shifts. (Diff. remains same) When On set point is changed, Off set point remains unchanged. (Diff. changes) 2 STEP MODEL
Operation 6 7 or On 8 9 Off Terminal 8 9 On or 6 7 Off Terminal Cooling Mode Operation 6 7 or On 8 9 Off Terminal 8 9 On or 6 7 Off Heating Mode Operation 6 7 or On 8 9 Off Terminal 8 9 On or 6 7 Off Floating Mode

Off

Terminal On Off On Temp. Set Point

On

Terminal Off On Off Temp. Set Point

On

Off

Off

On Temp. Set Point

Hi/Lo LIMIT W/TIMER MODEL


Operation 8 9 Terminal On Off On 67 Terminal Off Lo Limit Off On Temp. Hi Limit Set Point 67 Terminal Lo limit Hi limit setting range Min. 0.5 setting range Lo Limit Time Set Lo limit Func starts after 0 to 120 min. ) Hi Limit Time Set Hi limit Func starts after 0 to 120 min. ) Operation 8 9 Terminal On Off On Off Lo Limit On Off Temp. Hi Limit Set Point Lo limit Hi limit setting range Min. 0.5 setting range Lo Limit Time Set Lo limit Func starts after 0 to 120 min. ) Hi Limit Time Set Hi limit Func starts after 0 to 120 min. )

Hi/Lo limit output is reset manualy (Push reset: Push ENT Key in 2 sec or power off) Delay Timer can be set in the time range from 0 to 120 min respectively.

FLEDIGITAL HUMIDISTAT
Dehumidity Mode 67 Terminal On Off Off On Min. 3% RH 67 Terminal On Off On Off Humidity Mode Min. 3% RH

Free to set On/Off set point independently within the range. When Off set point is changed, On set point automatically shifts. (Diff. remains same) When On set point is changed, Off set point remains unchanged. (Diff. changes)

WIRING DIAGRAM
Type ULE
Sensor 1 2 3 Power Supply 85 to 264V.AC 4 5 Relay Contact Relay Contact 6 7 8 9 Load Power Supply for Load Power Supply 85 to 264V.AC Load Power Supply for Load

Type FLE
Sensor 1 Type HEK 2 3 1 2 3 4 5 Load Relay Contact 6 7 8 9 Power Supply for Load

6 7 : STANDARD, 2 STEP & Hi/Lo Model Control Output 8 9 : 2 STEP Control Output Hi/Lo Limit Alarm Output

38

SENSORS
STANDARD
Sensor Part No. Applicable Model Dimension Remarks Ambient temp. on usage: 40 to 110C When the sensor is in use under the condition of dew, water dripping or outdoor, the sensor should be vertically installed with lead wire outlet downward. Sensor holder is supplied as standard.

TEK83H601 (Temperature)

ULESD21011 ULESD22011 ULESD23011

30 Sensor Holder 18 15 13 52 27

2000

Lead Wire:Black

TEK83H609 (Temperature)

ULESD11011 ULESD12011 ULESD13011

2-4.2

Ambient temp. on usage: 55 to 80C When the sensor is in use under the condition of dew, water dripping or outdoor, the sensor should be vertically installed with lead wire outlet downward. Sensor holder is supplied as standard.

Lead Wire:Blue Designed to accord room interior. Designed to be installed where certain air flow runs and the room humidity is represented. Depending on load or other conditions, humidity control may become difficult. Especially when the FLE is used under 10C or above 40C, contact manufacturer.

Sensor Mouting Bracket

102

HEKI1R001 (Humidity)

105

FLESD11011

71

33

Elliptic Holes 4.5

Following sensors are available as option. (Ambient temperature sensors are available upon request.) Direct immersion sensor with nipple.............................TEK83N Wall mounting sensor ...................................................TEK83R Surface temp. sensor ...................................................TEK83E Direct immersion sensor with terminal cover................TEK83B Bulb well .......................................................................TEK00N

DIMENSIONS
Type ULE, FLE
Wall Mounting Dimension

SEL

Panel Cutting Dimension


ENT

116

71

Unit: mm

PANEL MOUNTING BRACKET


In case of Panel Thickness : 1 to 1.6mm In case of Panel Thickness : 1.6 to 3.2mm

ULE/FLE body

ULE/FLE body

39

83.5

DIGITAL THERMOSTATS
Type TNE GENERAL DESCRIPTION
Compact digital temperature controller (48mm48mm) for many applications. High quality temperature control with platinum and thermo couple temperature sensor (option). Two kinds of output - current output and relay output are available. Various function such as PID Control, Auto/Manual Changeover and Lock Function are installed. Two points output for High/Low limit alarm. Power source voltage: 100 to 240 V.AC 50/60Hz Indicator: temp. 7Seg. Green LED 4 digit Temp. set point 7Seg. Red LED 4 digit Control output Red LED3

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. TNESNPRN21 Temp. Set Range Control Type On/Off PID (Self tuning) Control Output Relay (SPST 250V.AC 3A) Current (4 to 20 mA DC) Alarm Output (Relay) SPST 250V.AC 2A2 Wt. (kg) 0.18 based on a TNESNPAN21 connection sensor

WIRING DIAGRAM
Power Supply for Load Load

1
Current Output TNESNPAN21 TNESNPRN21 Fuse Power Supply Relay Output NO C

AL2

AL1

Load

11 12 13 14 15
b B A

2 3 4 5

Power Supply for Load

OUT1

Thermo Couple Temperature Sensor Platinum Temperature Sensor

DIMENSIONS
48 6 2 77

MOUNTING SIZE
Panel Cutout Size
48 or over
0.6

60 or over

48

45 0

0.6

Packing

Panel thickness under 5mm

ACCESSARY
Fixing Bracket

OPTIONAL PARTS
Platinum Temperature Sensor (Type: PEK02H001)
SUS Cap. 4.8 Lead Wire White White 50 Red A b B

50

3000

45 0

Unit: mm

40

ELECTRONIC STEP THERMOSTATS


Type DSE & FSE GENERAL DESCRIPTION
Series SE electronic step thermostats are designed for capacity control or other multistage control of cooling, heating or airconditioning equipment. Type SEK temperature sensor are available for series SE. Double constant voltage circuit and noise elimination circuit assure stable control. Model with heat-cool selector available. Type DSE...2 Step thermostat Type FSE...4 Step thermostat.
Type DSE

Type FSE

TYPE NUMBER SELECTION (SPECIFICATIONS)


Example for Complete Catalog No.: DSE 1 020A 2 1 DSE1020A21 (Type Code) (Power Source Code) (Temp. Code) (Diff. Code) (Step. Temp. Code)
Temp. Range (C) Differential Code Step Temp. Code Min. 20 See Note 3. See Note 4. 0 20 20 See Note 3. See Note 4. 0 20 Max. 20 40 60 20 40 60 Temp. Sensing Element SEK12 SEK14 SEK16 SEK12 SEK14 SEK16 Wt (kg)

Catalog No. Type Power Source Code Temp. Code 020A DSE See Note 1. 040A 060A 020A FSE See Note 1. 040A 060A

Mode Cooling Mode HeatCool Selector Heating Mode Cooling Mode HeatCool Selector Heating Mode

0.58

0.89

Note 1: Power Source Code Code 1 2 3 4 7 9 Power Source 100V. AC 200V. AC 110V. AC 220V. AC 240V. AC 230V. AC and Others

Note 2: Temperature Code Code 020A 040A 060A Range (C) 20 to 20 0 to 40 20 to 60

Note 3: Differential Code Code 1 2 3 4 5 6 7 8 Differential (C) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

Note 4: Step Temp. Code Code 1 2 3 4 5 6 Step Temp. (C) 0.5 1.0 1.5 2.0 2.5 3.0

When ordering, please specify complete catalog No. comprising type, power source, temperature, differential and step temp. codes.

TEMPERATURE SENSOR SELECTION


Basic models of sensor required for each temperature range are as specified in the table of TYPE NUMBER SELECTION. Depending on the application, various styles of element are available. Please specify model number from the table below when ordering.
Type SEK..H SEK..P SEK..R001 SEK..A SEK..K Application Air or water Temperature Control Air Temperature Control Room Temperature Control Liquid Immersion Application Duct Temperature Control Models available SEK12H, 14H, 16H SEK14P, 16P SEK12R001, 14R001, 16R001 SEK12A001, 14A001, 16A001 SEK14K001, 16K001

SEK..H with drip-proof construction

41

OPERATION
2 Step U L2 Terminal 1 Step U L1 Terminal Set Point Temp. Cooling Mode D On Off On Off S D Heating Mode 2 Step On H2 U L2 Off Terminal 1 Step U L1 H1 Terminal On Off Set Point Temp. D

S D

Cooling Mode D 4 Step C4 L4 Terminal 3 Step C3 L3 Terminal 2 Step C2 L2 Terminal 1 Step C1 L1 Terminal On Off On Off S D On Off On Off Set Point Temp. S D S D

Heating Mode 4 Step C4 L4 H4 On Terminal Off S D D

3 Step H3 On C3 L3 Terminal Off

2 Step H2 On C2 L2 Terminal Off

S D

1 Step H1 On C1 L1 Terminal Off

S D

Set Point

Temp.

WIRING DIAGRAM
Power Supply Sensor Sensor 1 Step Load U V T1 T2 2 Step Load

T1 T2 L1 C1 H1 L2 C2 H2

L1

H1

L2

H2

Load 1 Step

Load 2 Step

U Power Supply

L3 C3 H3 L4 C4 H4

Cooling Mode: Arrow marks indicate directions of switch action on temperature increase. Heating Mode: Arrow marks indicate directions of switch action on temperature decrease.

Load 3 Step

Load 4 Step Power Supply for Load

Terminal locations of L* and H* on type DSE060A and FSE060A are changed place each other.

DIMENSIONS
Temp. Adjusting Knob Heat-Cool Selector Only Temp. Code 040A Temp. Adjusting Knob Heat-Cool Selector Only Temp. Code 040A

60 110

5.6

5.6

60 110

64 74

15

69

110 120

15

69

Unit: mm

42

DEFROST CONTROLS
High Volume OEM Item Type DDE GENERAL DESCRIPTION
Microprocessor based defrost controls for heat pump air conditioner and various refrigeration units. Def. initiation temp. ... 15 to 5C (factory set) Def. termination temp. ... 5 to 15C (factory set) Time cycle ... 30, 40, 50, 60, 90, 120, 150, 180 min. (field adjustable ... heat pump model) 2, 2.5, 3, 4, 6, 8, 12, 24 hrs (field adjustable ... display case and cold room) Time safe ... 10, 15, 20, 30, 40, 50, 60, 80 min. (field adjustable for all models) Voltage ... 230 V. AC Contact capacity ... 5 Amp. at 250 V. AC (cos1)

mark applicable (available upon request)

TYPE NUMBER SELECTION (SPECIFICATIONS)


Application Heat Pump Heat Pump Display Case Cold Room Catalog No. DDEKBA1201 DDEKBA1202 DDEKBB1203 DDEKBB1204 3 5 Operating Temp. Def. Init. Def. Termi. 10 5 Time Cycle 60 min. 30 min. 12 Hr. 6 Hr. Time Safe Volt (V)

Unit: C Wt. (kg)

10 min. 50 min. 30 min. 230 0.2

WIRING DIAGRAM
Coil Sensor

U Power Supply

DEF

A Power Supply for Load

Manual Def.

Load

DIMENSIONS
2 4 self-tapping screw Max. screwed length: 10mm

SENSOR
4.2 25 2000

15 60 97.5 15 7 187 Faston terminal 70 30

Unit: mm

43

PRESSURE &TEMPERATURE CONTROLS INFORMATION

44

PRESSURE &TEMPERATURE CONTROLS INFORMATION

CONNECTION & ACCESSORIES 45-47 DRIP PROOF & WATER PROOF CONTROLS 48-49 Series NSW & NSP

CONNECTION & ACCESSORIES


NS PRESSURE CONTROLS NOMENCLATURE
Catalog No. is decided according to the specifications. Example: SNS C1 30 X M2 N W G Q

SUS Bellows for Ammonia Application WDrip Proof, PWater Proof Connection Style.... Refer to Connection Option....Special No Table Below

ONS PROTECTION CONTROLS NOMENCLATURE


Catalog No. is decided according to the specifications. Example: ONS C1 06 X N W G Q

SUS Bellows for Ammonia Application WDrip Proof Connection Style.... Refer to Connection Timer Specification.... Q1Q12Q25Q36 Table Below

Connection Table (for NS Series Pressure Controls )


Size Connection Style B U G Flare Union Rc Female Thread G NPT R Except Below M Male Thread ANS Direct Connector G NPT R G NPT K Flareless Except Below ANS 1/4" (Stand.) B U1 G (Stand.) G1 G2 M02 M03 M04 M1 M2 M3 K1 8 B1 B1 U2 K2 Copper 3/8" B2 B2 G3 G4 G5 M01 (Stand.) M05 M06 M (Stand.) M4 M5 10 B3 B3 U (Stand.) K (Stand.) 1/2" B4 B4 G6 G7 G8 M07 M08 M09 M6 M7 M8 Steel 10.5 U3 K3

Size Connection Style Capillary

1000 mm L1 (Stand.)

2000 mm L2

45

NS TEMPERATURE CONTROLS NOMENCLATURE


Catalog No. is decided according to the specifications. Example: TNS C1 100 X M2 W L1 Q1

WDrip Proof, PWater Proof Connection Style.... Refer to Connection Option....Special No Table Below

Capillary Length Table


Type Capillary Length 1m 2m 3m 5m 7m 10m Except Above LQ Except BNS Standard L2 L3 L5 L7 L0 LZ LQ012 Normal BNS L1 Q012 L2Q012 L3Q012 L5Q012 L7Q012 L0Q012 LZQ012 Nickel Plated Except BNS BNS L1Q012

TNSC1010XC to TNSC1070XC: Capillary length are 1m to 5m

Connection Dimension Table


(B) Flare (U) Union (G) Female
E Hex. C 5 Hex. 22

Unit: mm Pipe Thread (M) Male

40

27

Hex. 30

A Hex. B A

A Hex. B

A Hex.B

Size

B C

Size 6 Copper 8 Copper 10 Copper 10.5 Steel

A 6.5 8.5 10.5 11.0

Size 1/4"

1/4 6.5 17 12 8 8.2

7/1620 0 20.5 26 UNF 5/818 5 24.5 36 UNF 3/416 5 27.5 40 UNF

3/8 9.7 22 17 10 10.2 1/2 12.9 24 22

3/8"

1/2"

A Rc1/4 G1/4 1/4 NPT Rc3/8 G3/8 3/8 NPT Rc1/2 G1/2 1/2 NPT

Size 1/4"

19 23

22 23

3/8"

27 27

1/2"

A R1/4 G1/4 1/4 NPT R3/8 G3/8 3/8 NPT R1/2 G1/2 1/2 NPT

17 29

19 29

22 33

(K) Flareless Type Connection (L) Capillary Copper Pipe (Direct)


Hex.C G Connection F E D Thread 48.5 Hex.17 60.5

Steel Pipe (Connector Option)

M16 A Hex.B

1/4" Flare Nut 2.4 L Capillary Tube

Size 6 8 10

A 6.2 8.2 10.2

B 14 17 19

C 14 14 17

D M12 M14 M16

E 23 23 23

F 33 33 34

10.7 Hex.19

K3

Type L1 L2

L 1000 2000

46

ACCESSORIES
Mounting Brackets
Name Type FE, NS Series ALS, BLS Parts No. SNSAE01 (Standard Acce.) SNSAE11 ALSAE01 Type Body Bracket Parts No. SNSAE02 ALSAE02 Type LWS FWS RWS Parts No. Bulb Bracket Type Parts No. ALS, BLS ALSAE09 LWS PWS (Except PWS-7060) LWSAE12

NS Series ALS, BLS

LWSAE08

27 2 25 7.5 4 4.4

40 25 7.5 8 5

25

9 8 4.4 20 50 31 3 M30.5 16 20 20

25

65

25

82 120

95

Form

47 85

4 5.5 30

25

12.5 11.5

30 12 80 40

2 6.2

10 7 R3.5

20

20

10

2 7

6 20 40

15

65 74 86 10 M5 Distance Piece Protect Tube Bulb

75 8

55.2 60

2 4.4

) SNSAE11

Ambient temp.:40 to 90

Insert Holder, Protect Tube (For Temperature Controls)


Insert Holder Protect Tube

Size 1/2" 3/4"

Max Press.

Torque

Static 12Nm Press. 1MPa or less

A Hex. 24 Hex. 32

B Hex. 22 Hex. 30

D R1/2 R3/4

E (43) (54)

Size 1/2" 3/4"

Max Press.

Torque

Static 12Nm Press. 3MPa or less

A Hex. 24 Hex. 30

B R1/2 R3/4

D 10 10

E 20 22

Insert Holder
Controls Catalog No. TNSC100 to C134 CNSC115 (M2) to C134 (M2) TNSC1070 TNSC1010C to C1070C NS TNSC1100 to C1150 INSC1070M1 INSC1120M1, C1150M1 LWSC1030 to C1094 PWS7034 to 7094 LWSC1120 to C1240 PWS7120 ALSC1011 to C1050 BLSC1020 ALSC1090 Size 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" Parts No. TNSAB01 TNSAB09 TNSAB04 TNSAB07 TNSAB17 TNSAB18 TNSAB02 TNSAB05 TNSAB15 TNSAB16 LWSAB02 LWSAB05 LWSAB15 LWSAB16 ALSAB03 ALSAB06 ALSAB10 Size C 6 12.7 12.7 Heat Proof 9.5 9.5 Heat Proof 9.5 9.5 Heat Proof 10 10 Heat Proof

Protect Tube
Parts No. Copper SUS 1/2" TNSAC01 TNSAC46 TNSC100 to C134 CNSC115 (M2) to C134 (M2) 3/4" TNSAC35 TNSAC56 Controls Catalog No. Size TNSC1070 to C1150 TNSC1010C to C1070C 1/2" TNSAC05 TNSAC12 15115 3/4" TNSAC09 TNSAC14 TNSAC02 TNSAC06 LWSAC15 LWSAC17 LWSAC19 LWSAC20 LWSAC48 LWSAC49 LWSAC16 LWSAC18 EWSAC27 1/2" 1/2" ALSAC03 3/4" ALSAC07 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1/2" 3/4" TNSAC11 TNSAC13 LWSAC21 LWSAC23 LWSAC25 LWSAC26 LWSAC50 LWSAC51 LWSAC22 LWSAC24 EWSAC28 ALSAC36 1295 12110 1280 1280 Heat Proof 12140 10.870 1275 12105 Size CF 895

NS

INSC1070M1 to C1150M1 LWSC1030 to C1090 LWSC1120 to 1160 PWS7120 WS LWSC1200 to C1240 LWSC1034 to C1094 PWS7034 to 7094 EWSC1080 to C1160 LS ALSC1011 to C1090 BLSC1020

WS

LS

47

DRIP PROOF & WATER PROOF CONTROLS


SERIES NSW & NSP GENERAL DESCRIPTION
Approved by various marine standards such as Bureau Veritas, LIoyds Register, Germanischer LIoyd, Det Norske Veritas, Nippon Kaiji Kyokai, ABS etc. Suitable for indoor or outdoor applications where water drips and dusts are apt to enter, such as marine refrigeration units or industrial plants. External wiring is made by cabtyre cable connection with cable glands. Standard gland size:20mm Semi standard gland size:15mm To order, specify catalog No. with W or P. Example: Type SNSC106X Standard model Type SNSC106XW Drip proof model Type SNSC106XP Water proof model DNSW/P Drip proof model of dual pressure controls. for specifications, refer to page 17,18. Weight: Approx. 1.4kg
11.5 192 18 88 90 8 80 99 9 10 20.5 63 3 11 31 7.5 35 28 7.5 120 135 Conduit Gland Flare Nut 6 27.5 32.5 40 65 88 61 6 67 33 8 150 37.5 98 114 Conduit Gland Flare Nut 8 37.5 65.5 20

Type DNSW

51

Conduit Gland 18 24 28

23 63 28

DNSP
137 111 Reset Button

SNSW, FNSW, ANSW


51 Conduit Gland 20 18 11 9

11.5

Flare Nut

28 28 24 29 67

20 7

88 8 80 10

3 63

18

88

SNSW/P, FNSW/P, ANSW/P Drip proof model of single function pressure controls. For specifications, refer to Pages 1316. Weight: Approx. 1.1kg

SNSP, FNSP, ANSP


110

29

88

Unit: mm

48

HNSW Drip proof model of high pressure controls. For specifications, refer to pages 13,14. Weight: Approx. 1.0kg

Flare Nut
17 11.5 20 7 37

18 Reset Button 23 28 67 150 32 55 3


65 12

88

Conduit Gland
10

3 14 63

HNSW

80

ONSW Drip proof model of oil protection controls. For specifications, refer to pages 19,20. Weight: Approx. 1.3kg

51

Conduit Gland 18

11.5 20 7

Reset Button 32 28

18 3
65

67
20 18

Flare Nut

ONSW

8 20.5

88 101

10 20.5 51

WNSW

88 106 100

10 20.5

TNSW/P, CNSW/P, INSW Drip proof model of temperature controls. For specifications, refer to pages 29,30. Weight: Approx.1.3kg
20 7

Conduit Gland

18
11.5

36 Capillary Tube
88 8 80 10 101 97

63
16

TNSW

13 Capillary Tube 11.5 20 7 37 18 23 28 67 110 8 88 80 Conduit Gland 10 14 63 3 6 33 8 37.5 98 114 Conduit Gland 8 37.5 65.5 16 Capillary Tube 32.5 18 150

18 Reset Button

29

TNSP, CNSP

88

11

Unit: mm

49

67

67

150

28 28

67

100

WNSW Drip proof model of differential pressure controls. For specifications, refer to page 21. Weight: Approx. 1.3kg

Conduit Gland 18

20 7

Flare Nut

171

32 28

32 55

11.5

18

36

100

171

EXPANSION VALVES
GENERAL INFORMATION EXPANSION VALVES Type BHX EXPANSION VALVES (BIFLOW) Type TCX EXPANSION VALVES Type ATX(R410A) EXPANSION VALVES Type ATX EXPANSION VALVES Type VPX & WPX EXPANSION VALVES Type WHX ELECTRONIC EXPANSION VALVES Type UKV, SKV, VKV, PKV & AKV PULSE CONVERTERS Type LNE 5152 53 54 5556 5758 5960 6162 6364 65

50

EXPANSION VALVES

EXPANSION VALVES
GENERAL INFORMATION VALVE SELECTION
In order to properly select Expansion Valves, the following items should be considered. 1) Required valve capacity should be based on the actual system operating conditions rather than the normal valve capacity rating. 2) When there exists an appreciable pressure drop between the valve outlet and the evaporator outlet, i.e., above 0.02 MPa {0.2 kgf/cm2}, or when a pressure drop type of refrigerant distributor is used at the evaporator inlet, the valve should have the external equalizer feature for best performance. Otherwise, it will increase a static superheat (valve opening temp.), restricting the refrigerant flow and causing the reduction of system capacity. As for R134a, 0.01 MPa {0.1kgf/ cm2} pressure drop will increase the static superheat approximately 1C. 3) Internally equalized valve may be used with the evaporator which has a negligible pressure drop, i.e., below 0.02 MPa {0.2 kgf/cm2}

GUIDE FOR EQUALIZER (Internal or External)


An internal or external equalizer should be selected depending on pressure drop between valve outlet and evaporator outlet. Internal equalizer increases superheat in the refrigeration system of which evaporator has some pressure drop, and the increase of superheat decreases the effective area of evaporator. Select internal or external equalizer depending on refrigerant, pressure drop and evaporating temperature. The Guide Table for Equalizer indicates the pressure difference of refrigerant corresponding to 1C temperature. The external equalizer valves should be used when the pressure drop exceeds the value of pressure difference indicated in the Table.

GUIDE TABLE FOR EQUALIZER


Refrigerant R134a R22 R404A R407C Evaporating Temperature (C) 10 0.014 {0.14} 0.024 {0.24} 0.025 {0.25} 0.021 {0.21} 5 0.012 {0.12} 0.02 {0.20} 0.022 {0.22} 0.018 {0.18} 0 0.011 {0.11} 0.018 {0.18} 0.019 {0.19} 0.016 {0.16} 5 0.009 {0.09} 0.016 {0.16} 0.017 {0.17} 0.014 {0.14} 10 0.008 {0.08} 0.014 {0.14} 0.015 {0.15} 0.012 {0.12} 20 0.006 {0.06} 0.011 {0.11} 0.012 {0.12} 0.009 {0.09} 30 0.004 {0.04} 0.008 {0.08} 0.008 {0.08} 0.006 {0.06} 40 0.003 {0.03} 0.006 {0.06} 0.006 {0.06} 0.004 {0.04}

Unit: MPa {kgf/cm2} 50 0.004 {0.04} 0.004 {0.04} 0.003 {0.03} 60 0.003 {0.03} 0.003 {0.03} 0.002 {0.02}

Pressure Diff. corresponding to 1C temperature.

51

GUIDE FOR SETTING OF SUPERHEAT


Superheat Adjuster of Expansion Valve adjusts the superheat by which the valve begins to open from the fully closed condition, and this superheat is called Static Superheat. S.S.H.: Static Superheat O.S.H.: Operating Superheat (Superheat necessary for valve and refrigeration system operation) S.H.C.: Superheat Change (Superheat which keeps the valve opening at the optimum balance point for refrigeration systems) S.S.H. O.S.H. S.H.C. To change the adjustment, remove the seal cap and turn the adjusting spindle. Turning the spindle clockwise to compress the spring decreases flow and raises superheat and turning the spindle counter clockwise to loosen the spring increases flow and lowers superheat.

CHARGE & MOP (MAXIMUM OPERATING PRESSURE)


GCharge: Gas charge used generally on air conditioning gives pressure limiting, but loses control if valve body becomes colder than sensing bulb. A gas charged valve should be installed in a location where the valve body can be warmer than the bulb to prevent condensation of the charge in the powerhead. Liquid charge provides accurate control when valve body becomes colder than sensing bulb; hence a liquid charged valve may be installed in any location regardless of temperature. The charge, however, does not provide maximum operating pressure (pressure limiting) for motor overload protection.

LCharge:

CCharge: Cross charge and Cross Low Temp. charge used generally on low temperature range application will not lose CLCharge control even if valve body becomes colder than sensing bulb. A cross charged valve may be installed in any CYCharge location regardless of temperature. Cross charge (C) for normal refrigeration (higher than 40C temp. range) and Cross Low Temp. charge (CL and CY) for low temp. refrigeration (CY...70 to 40C with R22 for Type ATX valves). SCharge: SACharge SLCharge Saginomiya s all purpose special charge combines the best properties of gas and liquid charges. The charge provides accurate control even if valve boby becomes colder than sensing bulb and further it provides MOP (pressure limiting) for motor overload protection. Scharged valve may be installed in any location regardless of temperature.

ORDERING INFORMATION
1) Catalog Number ... On standard products, specify the Catalog No. only. 2) Special Specifications ... On special applications, specify the followings: g) Length of Capillary Tube a) Normal Pressure and Maximum Pressure h) External or Internal Evaporator b) Normal Temperature and Minimum Temperature i ) Pressure Drop at Evaporator c) Detailed Application j ) MOP (Maximum Operating Pressure) d) Refrigerant k) Two Stage Compressor System or not e) Valve Location f) Capacity (Condensing & Evaporating Temperature)

52

EXPANSION VALVES
Type BHX GENERAL DESCRIPTION
Application: General refrigeration and air conditioning system.
Note: This valve provides excellent control in unloading, heat pump application, or in a hot gas defrost system.

Charge: S (Special) charge for all purpose with 18C (standard) MOP. Max. allowable pressure: 2.8 MPa {28 kgf/cm2} Adjustable range of static superheat: 0 to 8C Superheat change: 4 to 5C

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications. Example: BHX 45030 B H S : Type...... BHXThermostatic expansion valve for general use : Model...... The last three figures indicate nominal capacity. The first and second figures indicate inlet and outlet pipe size respectively. : Connection...... BFlare Nut Connection, DSolder Connection : Kind of refrigerant...... MR134a, HR 22 : Kind of charge...... SScharge

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Type Model 45030 45040 45050 56070 56090 BHX 56110 56140 57070 57090 71110 71140 Capacity: Based on condensing temp. 38C and evaporating temp. 5C. D (Solder) H (R22) B (Flare) Connection B (Flare) or D (Solder) M (R134a) S (Special) Refrigerant Charge Capacity (U.S.R.T.) {kW} R134a 3.6 {12.7} 4.8 {16.9} 6.0 {21.1} 8.4 {29.5} 10.8 {38.0} 13.2 {46.4} 16.8 {59.1} 8.4 {29.5} 10.8 {38.0} 13.2 {46.4} 16.8 {59.1} R22 4.8 {16.9} 6.4 {22.6} 8.0 {28.1} 11.2 {39.4} 14.4 {50.6} 17.6 {61.9} 22.4 {78.7} 11.2 {39.4} 14.4 {50.6} 17.6 {61.9} 22.4 {78.7} 7/8" 5/8" 7/8" 11/8" Flare 3/4" 3 1500 1.04 1/2" 5/8" 1/4" 0.85 Inlet Connection Outlet Equalizer Capil. Tube Length (mm) Wt. (kg)

1/4" Solder

0.84 0.85

DIMENSIONS
3 150 0
61

3 150 0

61

44 43

31 30

120 122

45

10 100 12 15.9 124 62 61

100

15.9

49 54

50 51

Type BHX45030B to 45050B (BHX56070B to 56140B)

Type BHX57070D to 71140D Unit: mm

53

29

EXPANSION VALVES (BI-FLOW)


High Volume OEM Item Type TCX GENERAL DESCRIPTION
Application: Heat pump air conditioner
Note: This Bi-flow expansion valve features flow direction reversibility being suitable for heat pump application.

Charge: C (Cross) charge Max. allowable pressure: High pressure side: 2.8 MPa {28 kgf/cm2} Low pressure side: 1.4 MPa {14 kgf/cm2} Static superheat: Fixed (Factory setting) Superheat change: 5 to 6C

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications. Example: TCX 2307 D H C : Type...... TCX BiFlow Thermostatic expansion valve : Model...... The last two figures indicate nominal capacity. The first and second figures indicate inlet and outlet pipe size respectively. : Connection...... DSolder Connection : Kind of Refrigerant...... HR 22 : Kind of Charge...... CCcharge

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Type Model 2307 TCX 2310 2315 2320 Capacity: Based on condensing temp. 38C and evaporating temp. 5C. D (Solder) H (R22) C Connection Refrigerant Charge Capacity (U.S.R.T.) {kW} R22 1.0 {3.52} 1.6 {5.63} 2.4 {8.44} 3.2 {11.3} 6.34 8.13 3.3 2.4 500 0.13 Inlet Connection (mm) Outlet Equalizer Capil. Tube Length (mm) Wt. (kg)

DIMENSIONS
2. 45 00

39

3.3

14

6.34 45 42.5 8.13

80

9.53

Unit: mm

50

80

54

EXPANSION VALVES
Type ATX(R410A) GENERAL DESCRIPTION
Application: General refrigeration and air conditioning systems. Suitable for use in general refrigeration systems, and hot gas defrost systems. Charge: C, CLcharge for refrigeration Max. allowable pressure: 3.3 MPa {33 kgf/cm2} Max. temperature of body: 80C. Max. temperature of sensing bulb: 40C. Adjustable range of static superheat: 1 to 7C. Increase of approx. 0.007MPa / one rotation

Charge C CL

Evaporating Temp. (C) 10 to 20 10 to 40

MOP (C)

Temp. Condition Body Temp.: TS, Sensing Bulb Temp.: TB TS TB Type ATXD

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications. Example:

ATX 34006 B V C

: Type...... ATXThermostatic expansion valve for general use. : Model...... The last three figures indicate nominal capacity. The first and second figures indicate inlet and outlet pipe size respectively. : Connection...... BFlare Nut Connection, DSolder Connection : Kind of refrigerant...... VR410A : Kind of charge...... CCcharge, CLCLcharge

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Type Model 34006 34013 34023 34035 34045 57060 57080 ATX 71110 71140 71160 12220 12270 12330 12420 12500 Capacity: Based on condensing temp. 38C and evaporating temp. 5C. D (Solder) V (R410) C CL B (Flare) or D (Solder) Connection Refrigerant Charge Capacity (U.S.R.T.) {kW} CT38C ET5C 1.10 {3.85} 2.32 {8.14} 3.98 {14.0} 6.05 {21.3} 7.77 {27.3} 10.7 {37.6} 14.3 {50.3} 19.6 {69.0} 24.9 {87.4} 28.6 {101} 39.4 {139} 48.2 {170} 58.6 {206} 74.2 {261} 89.2 {314} 1"OD or 1-1/4"OD 1"OD or 1-1/4"OD 1.5 5/8"OD or 7/8"OD 7/8"OD or 1-1/8"OD 1/4" Flare 1.3 3/8" 1/2" 3/8"OD 1/2"OD 1.2 (B) 1.1 D Inlet Connection Outlet Equalizer Wt. (kg)

55

DIMENSIONS
Type ATXB

Type ATX-34006D 34045D ATX-57060D 71160D ATX-12220D 12500D

77 80 82

30 52 56

31 34

38

51 36

Type ATXD

ACCESSARY Sensing Bulb Mounting Band


14 6 7 12.6 116 16 116.6 267 126 5.4 t0.4

Type ATX34006 to 71160

Bolt

14

6 7

12.6

126 16

174 337

138.6

5.4 t0.4

Type ATX12220 to 12500

Heat Pump Chiller System


In case of using ATX in heat pump circuits, sensing bulb and external equalizer shall be mounted at a position between 4way reversing valve and accumulator.

Type ATX Thermostatic Expansion Valve

Air SIDE HEAT EXCHANGER

Check Valve

4-Way Reversing Valve COOLING CYCLE COMPRESSOR HEATING CYCLE

ACCUMULATOR

Outlet Inlet HEAT EXCHANGER Type ATX Thermostatic Expansion Valve

Check Valve

RECEIVER

56

EXPANSION VALVES
Type ATX GENERAL DESCRIPTION
Application: General refrigeration and air conditioning systems.
Note: Scharge valve for low temperature (40 to 10C,30 to 10C for R134a), unloading, heat pump applications, or hot gas defrost system. CYcharge valve for extreme low temp. (70 to 40C) application.

Charge: L (Liquid) charge for refrigeration application. G (Gas) charge for cooling application with 20C (standard) MOP. S (Special) charge for all purpose with 20C (standard) MOP. C (Cross) charge, CL (Cross low) charge and CY (Extreme low) charge for low temp application. SL (Special low) charge for low temp application with 20C (standard) MOP. Max. allowable pressure: 1.4 MPa {14kgf/cm2}.......... (G, L, C, CLcharge) 2.8 MPa {28kgf/cm2} ............ (S, CY, SLcharge) 3.3 MPa {33kgf/cm2} ........ (Scharge for R407C) Adjustable range of static superheat: 3 to 13C ........................... (G, L, C, CLcharge) 1 to 7C ..................... (S, SLcharge for R404A) 0 to 8C ..................... (Scharge except R404A) 0 to 13C ........................................ (CYcharge) Superheat change: 4 to 5C................................ (S, SL, CLcharge) 3 to 4C.................................... (G, L, Ccharge) 8 to 12C ........................................ (CYcharge) Rugged diaphragm element: Best for heat pump units.

Type ATXB

Type ATXD

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications. Example: : Type...... ATXThermostatic expansion valve for general use. : Model...... The last three figures indicate nominal capacity. The first and second figures indicate inlet and outlet pipe size respectively. : Connection...... BFlare Nut Connection, DSolder Connection : Kind of refrigerant...... MR134a, HR22, UR404A, PR407C, COther refrigerant : Kind of charge...... GGcharge, LLcharge, CCcharge, CLCLcharge, CYCYcharge, SScharge, SLSLcharge

ATX 34006 B H L

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Type Model 34006 34013 ATX 34023 34035 34045 B (Flare) Connection Refrigerant M (R134a) H (R22) U (R404A) P (R407C) C (Others) Charge R22 1.0 {3.51} 2.1 {7.39} 3.6 {12.7} 5.5 {19.3} 7.0 {24.8} Capacity (U.S.R.T.) {kW} R134a 0.7 {2.46} 1.6 {5.63} 2.8 {9.85} 4.2 {14.8} 5.4 {19.0} R404A 0.7 {2.46} 1.5 {5.27} 2.7 {9.49} 4.0 {14.1} 5.1 {17.9} R407C 1.0 {3.51} 2.2 {7.74} 3.7 {13.0} 5.7 {20.0} 7.2 {25.3} R404A(SL) 0.3 {1.16} 0.8 {2.90} 1.4 {4.78} 2.0 {7.19} 2.6 {9.23} 3/8" 1/2" 1/4" Flare 3 1500 1.2 Inlet Connection Capil. Wt. Tube Length (kg) Outlet Equalizer (mm)

S R134a R22 R404A R407C SL (R404A) GLC CL (R22)

Capillary tube length: 2000mm for Scharge valve as standard. Capacity: Based on condensing temp. 38C and evaporating temp. 5C.(-30C for SL-charge).

57

Catalog No. Type Model 34006 34013 34023 34035 34045 57060 57080 ATX 71110 71140 71160 12220 12270 12330 12420 12500 C (Others) P (R407C) D (Solder) U (R404A) H (R22) S R134a R22 R404A R407C SL (R404A) GLC CL (R22) M (R134a) Connection Refrigerant Charge R22

Capacity (U.S.R.T.) {kW} R134a R404A R407C R404A(SL)

Connection Inlet

Capil. Wt. Tube Length (kg) Outlet Equalizer (mm)

1.0 {3.51} 0.7 {2.46} 0.7 {2.46} 1.0 {3.51} 0.3 {1.16} 2.1 {7.39} 1.6 {5.63} 1.5 {5.27} 2.2 {7.74} 0.8 {2.90} 3.6 {12.7} 2.8 {9.85} 2.7 {9.49} 3.7 {13.0} 1.4 {4.78} 3/8" OD 1/2" OD 5.5 {19.3} 4.2 {14.8} 4.0 {14.1} 5.7 {20.0} 2.0 {7.19} 7.0 {24.8} 5.4 {19.0} 5.1 {17.9} 7.2 {25.3} 2.6 {9.23} 9.7 {34.1} 7.2 {25.4} 6.8 {23.9} 10.0 {35.1} 3.7 {12.9} 13.0 {45.7} 9.6 {33.7} 9.1 {32.0} 13.4 {47.1} 4.9 {17.3} 5/8" OD 7/8" OD 1/4" 17.8 {62.9} 13.2 {46.4} 12.5 {44.0} 18.3 {64.3} 6.9 {24.4} or or Flare 8.7 {30.7} 7/8" ID 11/8" ID 22.6 {79.4} 16.8 {59.1} 16.0 {56.3} 23.3 {81.9} 26.0 {91.6} 19.2 {67.5} 18.2 {64.0} 26.8 {94.2} 10.0 {35.0} 35.8 {126} 26.4 {92.8} 25.1 {88.3} 36.9 {130} 13.7 {48.2} 43.5 {154} 32.4 {114} 30.8 {108} 44.8 {158} 16.9 {59.3} 53.4 {187} 39.6 {140} 37.6 {132} 55.0 {193} 20.6 {72.4} 81.0 {285} 60.0 {211} 57.0 {200} 83.4 {293} 33.0 {116} 1" OD 1" OD or or 67.6 {237} 50.4 {177} 47.9 {168} 69.6 {245} 27.6 {97.1} 11/4" ID 11/4" ID 3 3000 1.5 3 2000 1.3 3 1500 1.1

Capillary tube length: 2000mm for Scharge valve as standard. Capacity: Based on condensing temp. 38C and evaporating temp. 5C.(-30C for SL-charge).

Extreme Low Temperature Model (70C to 40C)


Catalog No. Type Model 34006 34013 34023 ATX 34035 34045 57060 57080 D (Solder) B (Flare) or D (Solder) Connection Refrigerant Charge Capacity (U.S.R.T.) {kW} R22 1.39 {4.88} 3.21 {11.3} H (R22) CY Extreme Low 5.40 {19.0} 7.56 {26.6} 9.74 {34.3} 11.3 {39.8} 15.3 {53.7} 5/8" OD or 7/8" ID 7/8" OD or 11/8" ID 3/8" OD 1/2" OD 1/4" Flare 3 2000 1.2 (Flare) 1.1 (Solder) Inlet Connection Outlet Equalizer Capil. Tube Length (mm) Wt. (kg)

1.3

Capacity: Based on condensing temp. 40C and evaporating temp. 60C, subcooling 50C. Contact the company for more detailed information.

DIMENSIONS
Type ATXB
D 3 R

Catalog No. Type Model 34006 34013 34023 34035 34045 D (Solder) B (Flare) 38 77 31 Connection L H H1

Unit: mm h D R B

30

1500

57060 57080
H1

64

76

ATX
B 16

71110 71140 71160 12220 12270 D (Solder) 51

80

34

52

2000

12330 12420 12500

82

36

56

68

3000 100

Type ATXD
D 3 R

S,CY,SL-Charge : D=68,R=2000,B=100

ACCESSARY Sensing Bulb Mounting Band


14 6 7 12.6 116 16 116.6 126 267 16

H1

5.4 t0.4

Type ATX34006 to 71160


h

Bolt

14

6 7 L

12.6

126 16

174 337

138.6

5.4 t0.4

Unit: mm

Type ATX12220 to 12500

58

EXPANSION VALVES
Type VPX & WPX GENERAL DESCRIPTION
Application: Refrigeration display case, commercial refrigerator, freezer, air conditioning, reefer, etc. Suitable for use in general refrigeration systems, and hot gas defrost systems. Type VPX ... Internal equalizer type Type WPX ... External equalizer type With superheat external adjust device. Charge: SLcharge for freezer with 20C MOP. C, CLcharge for refrigeration SAcharge for air conditioner with 18C MOP. Max. allowable pressure: 2.2 MPa {22 kgf/cm2} Adjustable range of static superheat: 1 to 7C. Superheat change: 4 to 5C (C, SLcharge) 3 to 4C (SAcharge)
A Zone 10 to 20 R22 10 to 20 10 to 40 R404A 10 to 20 0 to 40 10 to 40 25 to 60 R Zone Evaporating Temp. (C) 0 to 30 10 to 40 0 to 30 25 to 60 F Zone

Type VPX

Type WPX Temp. Condition Body Temp.: TS, Sensing Bulb Temp.: TB TSTB TS TB TSTB TS TB TSTB TS TB TSTB TS TB

Charge SA C CL SL SA C SA C SL C CL R407C R134a

MOP (C) 18 20 18 18 20

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications. Example: VPX 3403 B H SA : Type...... VPXInternal equalizer type, WPXExternal equalizer type : Model...... The last two figures indicate nominal capacity. The first and second figures indicate inlet and outlet pipe size respectively. : Connection....... BFlare Connection DSolder Connection : Kind of refrigerant...... MR134a, HR22, UR404A, PR407C : Kind of charge...... SLSLcharge, CCcharge, SASAcharge, CLCLcharge

DIMENSIONS
Type VPXB
44.5 2.4 11200

Type WPXD
44.5 2.4 11200 20 1/4" Flare 8 F Zone 1/2 R Zone 3/8 A Zone 3/8 80 50 50 10 57

29.5

47.5

F Zone 1/2 R Zone 3/8 57 A Zone 3/8


50

44

41

80

29.5

Unit: mm

59

TYPE NUMBER SELECTION (SPECIFICATIONS)


Application VPX Freezing 25 to 60C (SL: R22, R404A) Catalog No. 3402B (D) SL 3403B (D) SL 3405B (D) SL VPX WPX 3408B (D) SL 3410B (D) SL 3415B (D) SL 3420B (D) SL 0 to 40C (C: R404A) VPX 3402B (D) C 3403B (D) C 3405B (D) C VPX WPX 3408B (D) C 3410B (D) C 3415B (D) C 3420B (D) C VPX 3402B (D) CL 3403B (D) CL 3405B (D) CL VPX WPX 3408B (D) CL 3410B (D) CL 3415B (D) CL 3420B (D) CL VPX 10 to 40C (SA: R404A) 3402B (D) SA 3403B (D) SA 3405B (D) SA VPX WPX 3408B (D) SA 3410B (D) SA 3415B (D) SA 3420B (D) SA VPX 3402B (D) PC 3403B (D) PC 3405B (D) PC VPX WPX 3408B (D) PC 3410B (D) PC 3415B (D) PC 3420B (D) PC Capacity (U.S.R.T.) {kW} R22 0.21 {0.74} 0.34 {1.20} 0.56 {1.97} 0.9 {3.16} 1.13 {3.97} 1.7 {5.98} 2.25 {7.91} R134a R404A 0.14 {0.48} 0.22 {0.78} 0.37 {1.29} 0.59 {2.08} 0.74 {2.59} 1.11 {3.90} 1.48 {5.20} 3/8" Flare 3/8" Solder 1/4" (3/8") Flare 3/8" Solder 3/8" (1/4") Flare 3/8" Solder R407C Connection Inlet 1/4" (3/8") Flare 3/8" Solder Capil. Tube Length Outlet (mm) Wt. (kg)

F Zone

0.30 {1.05} 0.23 {0.79} 0.21 {0.74} 0.48 {1.69} 0.36 {1.27} 0.34 {1.20} 0.80 {2.81} 0.60 {2.11} 0.57 {2.00} 1.28 {4.50} 0.96 {3.38} 0.91 {3.20} 1.60 {5.63} 1.20 {4.22} 1.14 {4.01} 2.40 {8.44} 1.80 {6.33} 1.71 {6.01} 3.20 {11.3} 2.40 {8.44} 2.28 {8.02} 0.30 {1.05} 0.48 {1.69} 0.80 {2.81} 1.28 {4.50} 1.60 {5.63} 2.40 {8.44} 3.20 {11.3} 0.30 {1.05} 0.23 {0.79} 0.21 {0.74} 0.48 {1.69} 0.36 {1.27} 0.34 {1.20} 0.80 {2.81} 0.60 {2.11} 0.57 {2.00} 1.28 {4.50} 0.96 {3.38} 0.91 {3.20} 1.60 {5.63} 1.20 {4.22} 1.14 {4.01} 2.40 {8.44} 1.80 {6.33} 1.71 {6.01} 3.20 {11.3} 2.40 {8.44} 2.28 {8.02}

3/8" (1/4") Flare 3/8" Solder

10 to 40C 0 to 30C (CL: R22, R407C) (C: R134a, R22)

Refrigeration

R Zone

3/8" Flare 3/8" Solder 0.31 {1.09} 1/4" (3/8") Flare 3/8" Solder 0.49 {1.74} 0.82 {2.89} 1.32 {4.64} 1.65 {5.79} 2.47 {8.68} 3.30 {11.6} 3/8" Flare 3/8" Solder 1/4" (3/8") Flare 3/8" Solder 3/8" (1/4") Flare 3/8" Solder 1/2" 2.4 1200 0.29 (VPXD) 0.47 (WPXB) 0.33 (WPXD) 0.43 (VPXB)

3/8" (1/4") Flare 3/8" Solder

Air conditioning

10 to 20C (C: R407C) (SA: R134a, R22)

A Zone

3/8" Flare 3/8" Solder 0.31 {1.09} 1/4" (3/8") Flare 3/8" Solder 0.49 {1.74} 0.82 {2.89} 1.32 {4.64} 1.65 {5.79} 2.47 {8.68} 3.30 {11.6} 3/8" Flare 3/8" Solder 3/8" (1/4") Flare 3/8" Solder

Capacity: Based on condensing temp. 38C and evaporating temp. 5C for R & A, 30C for F zone. External equalizer of WPX: 1/4" flare connection Connection: ( ) available upon request.

ACCESSARY
8.5 6 5.5

23

6
0.4

4.6

92

9.5 9.5 9.5 9.5 5.5

50 t3

M50.8 bolt

Sensing Bulb Mounting Band

Superheat Adjusting Handle

10

Flare Nut Unit: mm

60

EXPANSION VALVES
Type WHX GENERAL DESCRIPTION
Application: Refrigeration display case, commercial refrigerator, freezer, air conditioning, reefer, etc. Charge: SLcharge for freezer with 20C MOP. C,CLcharge for refrigeration SAcharge for air conditioner with 18C MOP. Max. allowable pressure: 1.9 MPa {19kgf/cm2} Adjustable range of superheat: 1 to 7C Superheat change: 5 to 6C (SL, C, CLcharge) 4 to 5C (SAcharge)

VALVE NOMENCLATURE
Catalog No. is decided according to the specifications. Example: WHX 3430 B H SL : Type ... WHXThermostatic expansion valve for general use : Model ... The last two figures indicate Nominal capacity. The first and second figures indicate inlet and outlet pipe size respectively. : Connection ... BFlare Nut Connection : Kind of refrigerant ... MR134a, HR22, UR404A, PR407C : Kind of charge ... CCcharge, CLCLcharge, SASAcharge, SLSLcharge

TYPE NUMBER SELECTION


Application Catalog No. 3430BHSL Freezing 25 to 60C 4540BHSL 4550BHSL 3430BUSL 4540BUSL 4550BUSL 3430BMC Refrigeration 0 to 30C(C: R134a, R22) 0 to 40C(C: R404A) 10 to 40C (CL: R22, R407C) 4540BMC 4550BMC 3430BHC (CL) 4540BHC (CL) 4550BHC (CL) 3430BUC WHX 4540BUC 4550BUC 3430BPCL 4540BPCL 4550BPCL 3430BMSA 4540BMSA Air conditioning 10 to 20C 4550BMSA 3430BMSA 4540BMSA 4550BMSA 3430BPC 4540BPC 4550BPC F Zone

(SPECIFICATIONS)
Capacity (U.S.R.T.) {kW} R22 3.4 {12.0} 4.5 {15.8} 5.6 {19.7} 2.21 {7.78} 2.95 {10.4} 3.69 {13.0} 3.6 {12.7} 4.8 {16.9} 6.0 {21.1} 4.8 {16.9} 6.4 {22.5} 8.0 {28.1} 3.4 {12.0} 4.6 {16.0} 5.7 {20.0} 4.94 {17.4} 6.57 {23.1} 8.24 {28.9} 4.8 {16.9} 6.4 {22.5} 8.0 {28.1} 3.6 {12.7} 4.8 {16.9} 6.0 {21.1} 4.94 {17.4} 6.57 {23.1} 8.24 {28.9} R134a R404A R407C Inlet 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" 3/8" 1/2" Connection Outlet 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/2" 5/8" 1/4" Flare 2.4 1500 Equalizer Capil. Tube Length (mm) Wt. (kg) 0.6 0.67 0.6 0.67 0.6 0.67 0.6 0.67 0.6 0.67 0.6 0.67 0.6 0.67 0.6 0.67 0.6 0.67

Capacity: Based on condensing temp. 38C and evaporating temp. 5C for R & A zone, 30C for F zone.

61

A Zone

R Zone

DIMENSIONS
2. 4 1 1 500 2. 4 1 1
55

500

55

33

43

99

43

33 48 44

80

12.7

80

12.7

45.5

43

Type WHX3430B

Type WHX4540B, 4550B

ACCESSARY
7 5 6 10 14

16

53 125

12.6 12.6 12.6

10.2 M525 bolt t0.4

6 50 t 3

Sensing Bulb Mounting Band

Superheat Adjusting Handle

99

Flare Nut Unit: mm

62

ELECTRONIC EXPANSION VALVES


High Volume OEM Item (Type UKV, SKV, VKV, AKV) Type UKV, SKV, VKV, PKV & AKV GENERAL DESCRIPTION
Application: Wide range of air conditioning and refrigeration equipment Refrigerant: R22, R134a, R404A, R407C, R410A High cool down capability. Quick response. Less energy consumption. Bi-Flow capability. (Type UKV, SKV, VKV, AKV)

COMMON SPECIFICATIONS

Type UKV

Type PKV

Max. working pressure: 4.2 MPa {42kgf/cm2} Valve operating pulse range: 0 to 480 pulse, 12 phase Excitation.

Type AKV

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type UKV
Catalog No. UKV18D UKV25D UKV30D UKV32D Port Size (mm) 1.8 2.5 3.0 3.2 Capacity (U.S.R.T.) {kW} R22 2.9 {10.3} R134a 2.3 {8.1} R404A 2.1 {7.3} R407C R410A Connection (Solder) (mm) B side A side Operating Pressure Differential (MPa) {kgf/cm2} 0 to 3.5 {0 to 35} 0 to 2.8 {0 to 28} Valve shut press on, A to B flow direction (MPa) {kgf/cm2} 2.8 {28} or less 2.2 {22} or less 1.5 {15} or less 1.2 {12} or less 0.05 Wt. (kg)

3.0 {10.6} 3.4 {12.1}

5.6 {19.6} 4.4 {15.3} 3.9 {13.8} 5.7 {20.1} 6.5 {23.0} 7.6 {26.8} 6.0 {20.9} 5.4 {18.9} 7.8 {27.5} 9.0 {31.5} 8.2 {28.8} 6.4 {22.5} 5.8 {20.3} 8.4 {29.6} 9.6 {33.9}

6.35 OD 6.35 OD 7.94 OD 7.94 OD

Capacity: Based on CT38C, ET5C, SC0C and SH0C

Type SKV
Catalog No. SKV16D SKV18D Port Size (mm) 1.6 1.8 Capacity (U.S.R.T.) {kW} R22 2.3 {8.2} 2.9 {10.3} R134a 1.8 {6.4} 2.3 {8.1} R404A 1.7 {5.8} 2.1 {7.3} R407C 2.4 {8.5} R410A 2.8 {9.7} Connection (Solder) (mm) B side A side Operating Pressure Differential (MPa) {kgf/cm2} 0 to 3.5 {0 to 35} Valve shut press on, A to B flow direction (MPa) {kgf/cm2} 2.5 {25} or less 2.4 {24} or less Wt. (kg)

3.0 {10.6} 3.4 {12.1}

7.94 OD 7.94 OD

0.09

Capacity: Based on CT38C, ET5C, SC0C and SH0C

Type VKV
Catalog No. VKV20D VKV25D VKV30D VKV32D Port Size (mm) 2.0 2.5 3.0 3.2 Capacity (U.S.R.T.) {kW} R22 3.5 {12.4} R134a 2.7 {9.7} R404A 2.5 {8.7} R407C R410A Connection (Solder) (mm) B side A side Operating Pressure Differential (MPa) {kgf/cm2} 0 to 3.5 {0 to 35} 0 to 2.5 {0 to 25} Valve shut press on, A to B flow direction (MPa) {kgf/cm2} 2.4 {24} or less 2.2 {22} or less 1.5 {15} or less 1.0 {10} or less 0.15 0.13 Wt. (kg)

3.6 {12.7} 4.1 {14.5}

5.3 {18.5} 4.1 {14.5} 3.7 {13.1} 5.4 {19.0} 6.2 {21.8} 7.94 OD 7.94 OD 7.0 {24.7} 5.5 {19.3} 5.0 {17.4} 7.2 {25.4} 8.3 {29.1} 8.2 {28.8} 6.4 {22.5} 5.8 {20.3} 8.4 {29.6} 9.6 {33.9} 9.52 OD 12.7 OD

Capacity: Based on CT38C, ET5C, SC0C and SH0C

Type PKV
Catalog No. PKV14BS PKV18BS PKV24BS PKV30BS Port Size (mm) 1.4 1.8 2.4 3.0 Capacity (U.S.R.T.) {kW} R22 1.5 {5.2} 2.9 {10.3} 5.0 {17.5} 7.9 {27.8} R134a 1.1 {4.0} 2.3 {8.1} 3.9 {13.7} 6.2 {21.7} R404A 1.0 {3.6} 2.1 {7.3} 3.5 {12.3} 5.6 {19.6} R407C 1.5 {5.3} 3.0 {10.6} 5.1 {18.0} 8.1 {28.5} R410A 1.7 {6.1} 3.4 {12.1} 5.9 {20.6} 9.3 {32.7} 3/8" 3/8" 1/2" 0 to 2.3 {0 to 23} 0 to 2.2 {0 to 22} 0.5 0.7 Connection (Flare) Inlet Outlet Operating Pressure Differential (MPa) {kgf/cm2} Wt. (kg)

Capacity: Based on CT38C, ET5C, SC0C and SH0C

Type AKV
Catalog No. AKV55D Port Size (mm) 5.5 Capacity (U.S.R.T.) {kW} R22 R134a R404A R407C R410A Connection (Solder) (mm) B side A side Operating Pressure Differential (MPa) {kgf/cm2} 0 to 2.5 {0 to 25} Valve shut press on, A to B flow direction (MPa) {kgf/cm2} 0.7 {7} or less Wt. (kg) 0.4

23.7 {83.4} 18.5 {65.2} 16.7 {58.8} 24.4 {85.6} 27.9 {98.1} 15.88 OD 15.88 OD

Capacity: Based on CT38C, ET5C, SC0C and SH0C

Coil
Valve Type Type UKV Type SKV Type VKV, PKV Type AKV 12V DC375mA/Phase 12V DC260mA/Phase Rated Voltage & Current Wt.(kg) 0.13 0.14 0.15 0.4

63

DIMENSIONS
Type UKV Type SKV
38 47 48

43

32

99

B Side Conn.

7.94

B Side Conn.

50

A Side Conn.

A Side Conn.

A 47 7.94 62

Catalog No. UKV18D UKV25D UKV30D UKV32D

A 6.35 7.94

Type VKV
37 48

Type AKV
67

A side Conn.

A side Conn.

E A

15.88 64.5

Catalog No. VKV20D VKV25D VKV30D VKV32D

64 66

49 64

112 130

7.94 9.52 12.7

Type PKV14BS to 24BS


55

Type PKV30BS
55

78 92

83

Inlet 500 11.5

Outlet 500 300 9 11

105

65.5

B side Conn.

Inlet

150

B side Conn.

15.88

49

103

Outlet

300

30

Strainer #100

5/818UNF

18 85

5/818UNF

2M40.7 Screw effective 3

5/818UNF M141 97

3/416UNF

36

Strainer #100

Flow direction

Flow direction

Unit: mm

64

PULSE CONVERTERS
Type LNE GENERAL DESCRIPTION
Can be used for all types of SKV, VKV, PKV and AKV electronic expansion valves. Current input is converted to driving pulse output to electronic expansion valve with the pulse converter. Convert 4 to 20mA. DC input to 0 to 480 pulse output.
Input Output Sampling time Start up input Current input 0 to 480 pulse No voltage contact signal 4 to 20mA. DC For SKV, VKV, PKV & AKV 0.1, 1, 5, and 10 sec.
U 1 V 2 3 C 4 A 5 B 6 A 7 B 8 9

WIRING
SIG 13 10 11 12 14 SIG 15 COM ST 16 17 18

SYSTEM EXAMPLE
Power Supply KV series Ele. Exp. Valve 24V. AC or 24V. DC Condensor Comp. Pulse Converter Hot gas bypass Type LNE Junction cable Type AKV KV Valve Temp. Sensor Type PEK Heat Exchanger Evaporator

Start up Signal

4 to 20mA. DC Current Input

DIMENSIONS
Receiver 106 Expansion Solenoid Valve Valve
PULSE CONVERTER

(Type: LNEZN20020)
58

(Wt. 0.25kg)

4 to 20mA. DC Temp. Controller Type TNE

Solenoid Valve
U V C A B A B COM ST

90

RUN

POWER: AC/DC 24V I N P U T : DC 420mA VALVE: 12V COIL ONLY

Unit: mm

65

SOLENOID VALVES & CONTROL VALVES


SOLENOID VALVES FOR REFRIGERANT Type NEV, TEV & VPV SOLENOID VALVES FOR REFRIGERANT Type SEV SOLENOID VALVES FOR REFRIGERANT Type REV & UEV SOLENOID VALVES FOR WATER (BRINE) Type WEV BIFLOW SOLENOID VALVES Type BPV 3-WAY SOLENOID VALVES Type IEV 4-WAY REVERSING VALVES Type STF & VHV MOTORIZED BALL VALVES Type MJV DAMPER & VALVE MOTOR ACTUATORS Type EGK & WGK 2WAY & 3-WAY CONTROL VALVES Type NVK 67 68 6970 71 72 73 7476 7778 7980 8183

64

SOLENOID VALVES & CONTROL VALVES

SOLENOID VALVES FOR REFRIGERANT


High Volume OEM Item Type NEV, TEV & VPV GENERAL DESCRIPTION
Direct-operated, pilot operated, 2-way, normally closed valve. Normally open type is available. For use with non-corrosive refrigerant. Compactly designed for use in small appliances produced in quantity such as room air conditioners, dehumidifiers and ice making machines. Various piping configuration available.
Type VPV Type TEV

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. NEVL202DXF NEV152DXF NEV202DXF NEV603DXF NEV803DXF NEV1204DXF TEV1220D TEV1620DQ2 TEV1920D VPVL202D VPV122D VPV152D VPV202DQ50 VPV603D VPV803DQ50 VPV1204DQ50 Port Size (mm) 1.8 1.5 1.9 5.8 7.8 11.0 1.2 1.6 1.9 1.8 1.2 1.5 1.9 5.8 7.8 11.0 Cv Value 0.06 0.07 0.09 0.65 1.5 3.0 0.037 0.07 0.1 0.06 0.04 0.07 0.09 0.65 1.5 3.0 5/16" 3/8" 1/2" 0.005 {0.05} 0.01 {0.1} 0.015 {0.15} 1/4" 0 1/4" Solder 0 5/16" 3/8" 1/2" 0.01 {0.1} 0.015 {0.15} 2.7 {27.6} 1.7 {17.3} 2.06 {21} 3.6 {36.7} 2.75 {28} 3.6 {36.7} 2.75 {28} 4.15 {42.3} 3.3 {33.7} 1/4" 0 2.06 {21} 3.3 {33.7} Connection Copper Tube O.D. Style Min. O.P.D. Max. Max. Working Pressure

Unit: MPa {kgf/cm2} Operation Normal Open Wt. (kg) 0.06 0.04 0.08 Normal Close 0.14 0.26 0.04 Normal Open 0.06 0.04 Normal Close 0.08 0.14 0.26

O.P.D.: Operating Pressure Differential (by air pressure) Ambient temperature: 20 to 50C Allowable fluid temperature: 30 to 120C (type NEV, VPV), 30 to 110C (type TEV)

ELECTRICAL RATING OF SOLENOID COILS


Type Rated Voltage Power Insulation Voltampere Tolerance Consumption (%) Class Running Inrush (W) Wt. (kg) 24V. AC 100V. AC 110V. AC 120V. AC NEV 50/60Hz 200V. AC 220V. AC 230V. AC 240V. AC 100V. AC 200V. AC 50/60Hz 220V. AC 240V. AC

DIMENSIONS
H l Inlet h H L h

10

11/9

33/27

7/6

Class B Molded

0.14

figure 2
47

TEV

10

9/7

22/16

5/4

Class B Molded

figure 1 0.1
18.5

Inlet 12.5

100V. AC 200V. AC VPV 220V. AC 50/60Hz 230V. AC 240V. AC

10

13/10

36/30

8/7

Class B Molded

0.14

figure 3

35

35

Unit: mm

Current (A)Voltampere / Rated Voltage

Catalog No.

Unit: mm L H 43 55 53.5 57.5 40 h 33 36 38.5 61.5 33 I

Form

VPV 122D 35 152D 202D 36.5 NEV 603D VPV 803D 41.5 61.5 1204D L202D 1220D TEV 1620DQ2 35 1920D

figure 1

22.5 28.5

figure 2 figure 3

figure 1

67

SOLENOID VALVES FOR REFRIGERANT


Type SEV GENERAL DESCRIPTION
Pilot operated, 2-way, normally closed valve. For non-corrosive refrigerant (liquid or gas) in refrigeration units. Also available for air application. Can operate under no pressure difference. (SEV502 and 603) Can install horizontally and vertically. (Coil should be located above the axis of pipe line.)
Type SEVB Type SEVD

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Port Size (mm) Cv Value Nominal Capacity (Refrigerants in Liquid) (U.S.R.T.) R134a 0.51 0.80 1.75 2.9 4.5 0.53 0.83 2.0 3.5 5.3 2.1 3.3 7.3 12.1 18.8 2.2 3.5 8.3 14.6 22.1 R22 2.3 3.6 7.8 13.0 20.1 2.4 3.8 8.9 15.6 23.7 Connection Copper pipe (O.D.) 1/4" 0 6 10 12 15 5 6 10 12 15 3/8" 1/2" 5/8" 3/4" 1/4" 0 3/8" 1/2" 5/8" 3/4" Solder 0.007 {0.07} Flare 0.007 {0.07} 2.45 {25} for AC Style O.P.D. Min. Max. Max. Working Press. Body Test Press. Fluid Temp. (C)

Unit: MPa {kgf/cm2} Ambient Temp. (C) Wt. (kg)

SEV502BXF SEV502BYF SEV603BXF SEV603BYF SEV1004BXF SEV1004BYF SEV1205BXF SEV1205BYF SEV1506BXF SEV1506BYF SEV502DXF SEV502DYF SEV603DXF SEV603DYF SEV1004DXF SEV1004DYF SEV1205DXF SEV1205DYF SEV1506DXF SEV1506DYF

0.4

0.7 1.0 X: 2.94 {30} Y: 4.2 {42} X: 4.41 {45} Y: 6.3 {63} 40 to 125 30 to 50 1.4 0.3 0.35 0.7 0.8 1.0

1.96 {20} for DC

Nominal capacities are based on P0.014710 MPa {0.15 kgf/cm2}, condensing temp. 38C and evaporating temp. 5C. Weight includes a coil

ELECTRICAL RATING OF SOLENOID COILS


Rated Voltage 24V.AC, 100V.AC, 110V.AC 50/60Hz 200V.AC, 220V.AC, 240V.AC 12V. DC, 24V. DC, 100V. DC Tolerance (%) Voltampere (VA) Running 15/11 Inrush 45/33 Power Consumption (W) 7/6 10 Insulation Class

10

Class B Molded

Current (A)Voltampere / Rated Voltage

DIMENSIONS
Type SEVD
39

Catalog No. 502B


H

Unit: mm L 85 105 115 135 270 160 180 190 H 58 85 88 95 58 85 88 95 h 11.5 20.5 22 25 10.5 20.5 22 25

Type SEVB
39

603B 1004B 1205B SEV


h

1506B 502D 603D 1004D 1205D 1506D

18 L Strainer

Unit: mm

68

SOLENOID VALVES FOR REFRIGERANT


Type REV & UEV GENERAL DESCRIPTION
Pilot operated, 2-way, normally closed valve (Type REV). and nomally opened valve (Type UEV). For non-corrosive refrigerant (liquid or gas) in refrigeration, cooling, air conditioning systems. Double plunger construction provides reliable On/Off action. Compact molded coil commonly fits all valve sizes. Operates in any position ... can be conveniently located in horizontal or vertical line with coil on top. Manual Opening Stem ... On Flange connection models, supplied as standard. On Flare or Solder connection models, supplied upon request.

Type UEVB

Type REVD

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. REV703BX F Y REV1004BX Y F REV1205BX Y F REV1506BX Y F REV1003GX Y F REV1204GX Y F REV1506GX Y F REV703DX F Y REV1004DX Y F REV1205DX Y F REV1506DX Y F REV2007DX Y F REV2010DX Y F REV2011DX Y F REV2511DXF REV2512DXF REV2513DXF REV3213DXF REV3214DXF REV3215DXF REV2006EXF REV2510EXF REV3212EXF REV4014EXF REV5020EXF REV6524EXF REV6530EXF UEV1004BXF UEV1205BXF UEV1506BXF UEV1003GXF UEV1204GXF UEV1506GXF UEV2010GXF UEV1004DXF UEV1205DXF UEV1506DXF UEV2007DXF UEV2010DXF UEV2011DXF 20 9.0 20 25 32 40 50 65 10 12 15 10 12 15 20 10 12 15 9.0 13.8 19.4 32.0 45.0 74.0 2.0 3.5 5.3 2.0 3.5 5.3 9.0 2.0 3.5 5.3 7/8" 1" 11/4" 11/2" 2" 21/2" 3" 1/2" 5/8" 3/4" 3/8" 1/2" 3/4" 1" 1/2" 5/8" 3/4" 7/8" 1" 11/8" Solder Rc 0.007 {0.07} 1.96 {20} Flare 32 19.4 25 13.8 20 9.0 Port Size (mm) 7 10 12 15 10 12 15 7 10 12 15 Cv Value 1.0 2.0 3.5 5.3 2.0 3.5 5.3 1.0 2.0 3.5 5.3 Connection Copper Tube O.D. 3/8" 1/2" 5/8" 3/4" 3/8" 1/2" 3/4" 3/8" 1/2" 5/8" 3/4" 7/8" 1" 11/8" 11/8" 11/4" 13/8" 13/8" 11/2" 15/8" 11/8" 11/2" 15/8" 2" 21/2" 3" 31/2" 3/4" 1" 11/4" 11/2" 2" 21/2" 3" Flange Solder 0.007 {0.07} 2.45 {25} Rc Flare Steel Tube O.D. Style O.P.D. Min. Max.

Unit: MPa {kgf/cm2} Max. Working Pressure Wt. (kg) 0.6 0.9 1.1 1.5 1.0 1.3 1.7 0.5 0.8 0.9 1.1 1.6 2.94 {30} 4.2{42} 2.2

3.2 5.1 7.7 8.9 10.8 16.3 23.2 26.6 0.9 1.1 1.5 1.0 1.3 1.7 2.94{30} 1.9 0.8 0.9 1.1 1.6

With companion flange, specify copper tube O.D. size when order. O.P.D.: Operating Pressure Differential (by air pressure) Ambient temperature: 30 to 40C, allowable fluid temperature: 40 to 125C (REV), 40 to 120C (UEV) Weight includes a coil

69

ELECTRICAL RATING OF SOLENOID COILS


Type Rated Voltage 24V.AC, 100V.AC, 110V.AC 50/60Hz 200V.AC, 220V.AC, 240V.AC REV 12V.DC, 24V.DC 48V.DC, 100V.DC UEV 10 10 15 17/14 43/35 10 8/7 Class B Molded Tolerance (%) 10 15 Voltampere (VA) Running 17/14 Inrush 43/35 Power Consumption (W) 8/7 Insulation Class

24V.AC, 100V.AC, 110V.AC 50/60Hz 200V.AC, 220V.AC, 240V.AC

Specify voltage & frequency when order. Current (A)Voltampere / Rated Voltage

DIMENSIONS
Type REVB, UEVBX Type REVG, UEVGX
Catalog No.
D K D K

Unit: mm L 90 105 115 135 65 75 85 150 160 180 190 230 H 70 73 88 90 90 92 96 99 89 91 94 96 99 102 70 73 88 90 90 92 96 99 112 116 h 19 21 22 25 20 21 24 19 21 22 25 29 10 13 16 19 20 48 240 123 31 23 44 E D K

703BX Y 1004BX Y 1205BX Y 1506BX Y 1003GX Y 1204GX Y 1506GX Y 703DX Y 1004DX Y

280 G1/2

280 H

M14 1 h

1205DX Y 1506DX Y 2007DX Y


L

2010DX Y REV 2011DX Y 2511DX 2512DX

Type REVD, UEVDX


D K

2513DX 3213DX 3214DX


280

260 95 110 120 130 170 200 210 105 115 135 65 75 85 100 160 180 190 230

126 112 123 126 133 149 169 108 110 116 109 112 119 133 108 110 116 132

35 73 78 87 92 115 129 21 22 25 20 21 24 33 21 22 25 29

26

3215DX 2006EX 2510EX 3212EX 4014EX 5020EX 6524EX


E

G1/2

6530EX 1004BX 1205BX 1506BX 1003GX 1204GX

M141 703D1506D L

M201 2007D3215D

Type REVEX
D K

1506GX UEV 2010GX 1004DX 1205DX


280

48 13 16 19 20

44

1506DX 2007DX 2010DX 2011DX

G1/2

Unit: mm

70

SOLENOID VALVES FOR WATER (BRINE)


Type WEV GENERAL DESCRIPTION
Pilot operated, 2-way, normally closed valve. For water in refrigeration, cooling, air conditioning systems, and general industrial plant. Valves for non-corrosive brine are available. To order, specify catalog No. with B Example: WEV1504GLW for water WEV1504GLB for brine, warm water Compact molded coil commonly fits all valve sizes. Operates in any position ... can be conveniently located in horizontal or vertical line with coil on top.

Type WEVG Type WEVF

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. WEV1504GL WEV2006GL WEV2510GL WEV3212GL WEV4014GL WEV5020GL WEV1504FL WEV2006FL WEV2510FL WEV3212FL WEV4014FL WEV5020FL WEV6524FL WEV8030FL B (Brine, Warm Water) W (Water) Fluid Port Size (mm) 15 20 25 32 40 50 15 20 25 32 40 50 65 80 Cv Value 4.3 7.8 10.4 17.6 26 42 4.3 7.8 10.4 17.6 26 42 65 100 Connection Steel Tube O.D. 1/2" 3/4" 1" 11/4" 11/2" 2" 1/2" 3/4" 1" 11/4" 11/2" 2" 21/2" 3" 0.03 {0.3} Flange (Round Type) 0.015 {0.15} 0.03 {0.3} 0.98 {10} Rc 0.015 {0.15} Style Min. O.P.D. Max.

Unit: MPa {kgf/cm2} Max. Wt. Working (kg) Pressure 0.6 0.8 1.1 1.6 2.4 3.6 0.98 {10} 2.0 2.6 3.7 5.0 5.7 7.7 12.8 16.5

Without companion flange (Weight without companion flange and bolts) O.P.D.: Operating Pressure Differential (by water pressure) Ambient temperature: 30 to 50C, allowable fluid temperature: 0 to 60C (Type W), 35 to 90C (Type B) Apparent power: 16VA Use of a strainer 80 to 100 mesh at the valve inlet is recommended. Weight includes a coil

ELECTRICAL RATING OF SOLENOID COILS


Rated Voltage 24V.AC, 100V.AC, 110V.AC 50/60Hz 200V.AC, 220V.AC, 240V.AC 10 12V.DC, 24V.DC 48V.DC, 100V.DC 11 Tolerance (%) Voltampere (VA) Running 18/14 Inrush 57/47 Power Consumption (W) 9/8 Class B Molded Specify voltage & frequency when order. Unit: mm L 65 80 90 105 120 140 105 115 125 140 150 160 200 240 H 82 86 91 97 103 126 82 86 91 97 103 126 138 152 h 19 25 29 36 47 55 48 50 63 68 70 78 88 93 48 44 D K Insulation Class

DIMENSIONS
Type WEVG
280 K D

Catalog No.

Type WEVF
280 K D

1504GL 2006GL 2510GL 3212GL 4014GL 5020GL WEV 1504FL 2006FL 2510FL 3212FL

G1/2

G1/2

4014FL 5020FL
L

6524FL Unit: mm 8030FL

71

BI-FLOW SOLENOID VALVES


Type BPV GENERAL DESCRIPTION
Bi-flow controlling applicable. Developed for the purpose of simplification of complicated refrigeration circuit. Not only for ordinary refrigeration circuit, suitable for flow change of heat exchanger on multi type heat pump air conditioner. Fluid temperature: 30 to 120C Ambient temperature: 20 to 60C

Type BPVA

Type BPVD

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. 803ADY 1204ADY BPV 1706ADY 1706D 2210D 2514D Gas line only Bleeding will be happen when pressure of B side is higher than A side. Weight includes a coil Refrigerant Fluid Port Size Cv Value (mm) 7.8 11 17 22 (25) 1.5 2.9 6.6 4.4 8.6 12 Bleed Cv Value BA Less Than 0.01 Less Than 0.013 Less Than 0.015 Less Than 0.02 Solder Style Connection Copper Tube O.D. 3/8" 1/2" 3/4" 1" 11/2" 0.015 Operation Pressure Differential (MPa) Min. 0.01 2 3.0 Max. Max. Working Pressure (MPa) Wt. (kg) 0.31 4.2 0.45 0.9 1.3 2.2 3.5

ELECTRICAL RATING OF SOLENOID COILS


Port Size (mm) 7.8, 11 17, 22, (25) Rated Voltage 100V.AC, 200V.AC 220V.AC, 240V.AC 50/60Hz Tolerance (%) 10 Voltampere (VA) Running 12/10 17/14 Inrush 36/30 51/42 Power Consumption (W) 6/5 7.5/6 Insulation Class Class B Molded

Current (A)Voltampere / Rated Voltage

Function of Bi-flow Solenoid Valve


Equivalent circuit of type BPV Bi-flow Solenoid Valve is as follow.
Standard Solenoid Valve Check Valve S Type BPV Solenoid Valve S A S B A B

DIMENSIONS
48 34 48 34

Catalog No. 803AD 1204AD


280 H

Unit: mm L 48 61 91 185 230 260 H 76 77 85 100 111.5 116.5 h 48 60 82 13 17.5 21.5

Form

figure 1

280 A

BPV

1706AD 1706D 2210D 2514D

figure 2

B h

B L L

figure 1

figure 2

Unit: mm

72

3WAY SOLENOID VALVES


Type IEV GENERAL DESCRIPTION
For non-corrosive refrigerant (gas) in refrigeration units or air. Pilot operated, 3-way Distributing valve and Selector valve. mark applicable (available upon request)

Type IEVB

Type IEVC Unit: MPa {kgf/cm2}

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Port Size (mm) Cv Value Nominal Capacity (Refrigerants in Liquid) (U.S.R.T.) R134a IEVB1505DX IEVB2007DX IEVB3211DX IEVB3212DX IEVB3213DX IEVC3211DX IEVC3212DX IEVC3213DX 30 25 42 36 65 79 18 20 6.3 9.0 16 23 R22 20 29 Connection Copper pipe (O.D.) 5/8" 7/8" 11/8" 11/4" 1-3/8" 11/8" 11/4" 13/8" Solder 0.29 {3.0} 2.06 {21} 2.94 {30} 4.41 {45} 20 to 125 20 to 50 O.P.D. Max. Working Press. Body Test Press. Fluid Temp. (C) Ambient Temp. (C)

Operation

Wt. (kg)

Style

Min. 0.49 {5.0}

Max. 2.25 {22.9}


20 to 120

0.95 1.0 branched

2.6 switched

Nominal capacities are based on P0.014710 MPa {0.15 kgf/cm2}, condensing temp. 38C and evaporating temp. 5C. O.P.D.: Operating Pressure Differential (by air pressure) Weight includes a coil

ELECTRICAL RATING OF SOLENOID COILS


Port Size (mm) 18, 20 100V.AC, 110V.AC 200V.AC, 220V.AC 30 Current (A)Voltampere / Rated Voltage 50/60Hz 10 16/13 40/33 8/7 Rated Voltage Tolerance (%) Voltampere (VA) Running 11/9 Inrush 33/27 Power Consumption (W) 6/5 Class B Molded Insulation Class

OPERATION
Type IEVB
Energized : AC non Energized : AB

Type IEVC
Energized : BA non Energized : AC

DIMENSIONS
Type IEVB1505DX (B2007DX)
109 116 600 16.13 22.47

Type IEVB3211DX B3213DX, C3211DX C3213DX


44 280 157

G1/2 22 2 M610 23

16 20 193 213

271

139 158

22

80 99

210

44

90 109

85 92

57

120

114

108

40

Unit: mm

73

4WAY REVERSING VALVES


High Volume OEM Item (Type STF) Type STF & VHV GENERAL DESCRIPTION
Pilot operated 4-way reversing valves are suitable for heat pump applications on unitary, split system and window type air conditioners, etc. 4-way pilot valve adoption has an advantage of reliable changeover operation. Unique device for short cycle prevention is provided. Designed for instantaneous reversing and operations under small minimum pressure differential between the high and low side. Pressure drop across the valve, and valve leakage are minimized. Provided with drip proof resin encapsulated solenoid coil. Coil voltage: 100V. AC, 110V. AC, 200V. AC, 220V. AC 230V. AC, 240V. AC 50/60 Hz mark applicable (available upon request)

Type STF01, 02 Type STF04, 07, 20

UL listed (available upon request)


TYPE NUMBER SELECTION (SPECIFICATIONS)
Max. working pressure: 3.3MPa {33.7kgf/cm2} (Type STFZ) 4.15MPa {42.3kgf/cm2} (Type VHV,STFG) Ambient temperature: 20 to 55C Allowable fluid temperature: 20 to 120C (STF0101 to 1511) 20 to 130C (STF2011 to 5001, VHV6001) Ambient humidity: Less than 95% R.H.
Type STF25, 30, 40, 50 VHV60

R22, R407C
Catalog No. STF0101Z STF0104Z STF0201Z STF0202Z STF0301Z STF0401Z STF0408Z STF0712Z STF1511Z STF2011Z Port Size (mm) 8 11.1 11.5 15.5 20 23 24 Nominal Capacity R22 (kW) 4.77 5.64 9.11 11.1 20.2 34.3 38.2 48.8 (U.S.R.T.) 1.36 1.60 2.59 3.16 5.75 9.76 10.9 13.9 0.3 {3.0} 2.5 {25} O.P.D. (MPa) {kgf/cm2} Max. Min. 0.25 {2.5} 0.35 {3.5} 0.25 {2.5} Connection (O.D.) Discharge 5/16" 3/8" Suction & Coils 3/8" 1/2" 5/8" 1/2" 3/4" 7/8" 3/4" 7/8" 1-1/8" 0.77 1.32 1.55 Wt. (kg) 0.25

0.37

Nominal capacities are based on P 0.015 MPa {0.153 kgf/cm2}, condensing temperature38C, evaporating temperature5C, superheat5C. (R22) O.P.D.: Operating Pressure Differential (with air)

74

R410A
Catalog No. STF0101G STF0104G STF0201G STF0202G STF0301G STF0401G STF0408G STF0712G STF1511G STF2011G STF2501G STF3001G STF4001G STF5001G VHV6001 Port Size (mm) 8 11.1 11.5 15.5 20 23 24 28 34 40 50 60 Nominal Capacity R410A (kW) 5.64 6.67 10.8 13.1 23.8 40.5 45.1 57.7 87.2 123.1 171.8 214.1 367.5 (U.S.R.T.) 1.60 1.90 3.07 3.73 6.77 11.5 12.8 16.4 24.8 35.0 48.9 60.9 104.5 3.1 {31.6} 0.3 {3.1} 1/2" 3/4" 7/8" 1" 11/4" 11/2" I.D. 15/8" O.P.D. (MPa) {kgf/cm2} Max. Min. 0.3 {3.1} 0.35 {3.6} Connection (O.D.) Discharge 5/16" 3/8" Suction & Coils 3/8" 1/2" 5/8" 3/4" 7/8" 11/8" 11/4" 11/2" 13/4" 21/8" 25/8" 0.77 1.32 1.55 3.4 4.7 9.1 9.4 20.0 Wt. (kg) 0.25

0.37

Nominal capacities are based on P 0.015 MPa {0.153 kgf/cm2}, condensing temperature38C, evaporating temperature5C, superheat5C. (R410A) O.P.D.: Operating Pressure Differential (with air)

DIMENSION
Type STF0101Z (0201Z, 0202Z), STF0101G (0201G, 0202G)
98 123 D 42.5 51 52

Type STF0301Z, STF0301G


123 16 30

22 28

50 59

62 71

62 68

28

62 E C D 42 52
15

E S 12 16

C 12 16 S 25
25 15

Type STF0401Z, 0408Z (0712), STF0401G, 0408G (0712G)


200 224 43.5 43.5 D 67 82 33.5 41.5

Type STF1511Z, STF1511G


43.5 D 100 E S 50 C 50 144 45

36 45

E 29 33.5 S

C 29 33.5

83 85.7

95 98.5

87

41.5

224

Type STF2011Z, 2011G


43.5 D 91

Type STF2501G

D 111 61 E C S 45 45 41.5 76 311

45

E 37 S 244

C 37

109

Unit: mm

75

117 131

96

Type STF3001G
39 D 121 120 66 142 40 76 E S 49 49 347 C 230

Type STF4001G, 5001G


81 D 136 200 166 88 30 E 63 C S 58 58 * STF 5001G: 202 414 226

Type VHV6001
195.5 82.5 103 33 158 184 240 40 75 75 526

300

116

260 220

149 169

120 145

Unit: mm

FLOW RATE (Capacity)


kW 500 USRt 100 Refrigerant: R22,R407C USRt 100 kW 500 Refrigerant: R410A

50 40 30 20 15 10 8 6 4 10 Capacity 2 5 1 50 100

50 40 30 100 20 15 10 8 6 4 10 Capacity 2 5 1 50

VH

V-6

001

1Z 01 F-2 ST 5 1Z -2 1 TF S Z 712 F-0 ST ST F-0 Z 401


Z

G 001 F-5 ST 4001G F ST G 001 F-3 ST 01G -25 F ST 11G -21 TF 11G S 5 F-1 ST G 712 F-0 ST G 712 F-0 ST 2 G 301 ,-020 G F-0 ST -0201 F ST G 104G F-0 ST -0101 TF S G

Flow Rate Conditions Condensing temp.: 38C Evaporator temp.: 5C Superheat temp.: 5C Nominal capacity shown in the table is based on pressure drop across the valve P0.015 MPa {0.153 kgf/cm2}

0.5 0.3 1

Z 2 301 020 F-0 Z,ST -0201 F ST Z 104 Z F-0 ST -0101 F ST

0.5 0.3 1

0.001

0.005 0.010 Suction Pressure Drop MPa

0.050

0.001

0.005 0.010 Suction Pressure Drop MPa

0.050

76

MOTORIZED BALL VALVES


Type MJV GENERAL DESCRIPTION
Proportional Control valve for hot or chilled water,indsutiral water and steam circuit. Compact & Light weight design,manual operation is also available. Various types of water supply Equipments Air Handling Units Ice Strage Units

Type MJV

COMMON SPECIFICATIONS
Valve Type Item Test Pressure Air Tight Pressure VALVE PART Max. Working Pressure Fluid Fluid Temperature Flow Characteristics Valve Leakage Material Power Supply Voltage Max. power Consumption Housing Construction MOTOR PART Ambient Temperature Timing INPUT SIGNAL Resistance Input Current Input Voltage Input 1.6MPa(0.2MPa for Steam) 0120C Equal Percentage Cv: 0.1% or less 24V.AC10%, 50/60Hz 12VA Rain-Proof (JIS C 0920 XXXXXX3) Operating Temp.:10 to 50C, Storage Temp.:20 to 70C Approx. 52 sec. 0135 DC 420mA(Input Impedance 250) DC 15V(Input Impedance 100k), DC 010V(Input Impedance 250k) Case: PPS Resin, Cover: ABS Resin Yes O: Open, S: Close Input Signal 1354mA1V0V:Close O: CA Open, S: CA Close Input Signal 1354mA1V0V: CA Close Two-way Valve Two-way Valve for Steam 1.6MPa 1.6MPa 1.6MPa(0.5MPa for Steam) 0160C 1.6MPa 090C Corrected Linear Non-corrosive water and Steam (Hot water and Three-way Valve are not available.) Three-way Valve

Body:Bronze Casting, Seat Ring:Fluoro-resin,O-ring:Fruoro rubber,Spindle:Stainless Steel,Plug:Stainless Steel

Material Manual Operation Flow Display Movement of Valve

TYPE NUMBER SELECTION (SPECIFICATIONS)


Two-way Valve
Catalog No. Type Model 1504GQ1 1504GQ2 1504G MJV 2006G 2510G 3212G 4014G 5020G 70 (Resistance 0 to 135) 71 (4 to 20 mA) 72 (1 to 5 VDC) 73 (0 to 10 VDC) 1/2 3/4 1 1-1/4 1-1/2 2 Model Connection Rc(O.D.) Cv Value 1 2 3.5 6.5 12 20 30 45 0.8 0.6 0.4 1 49 58.8 78.5 83.4 98.1 155 159 165 178 185 69 82 97 106 128 42 50 60 71 84 1.7 1.9 2.6 3.2 4.6 34.3 152 56 32 1.5 Max. Operation Press. Differential (MPa) Torque (N m) Dimension H L D Wt. (kg)

Two-way Valve for Steam


Catalog No. Type Model H1504GQ1 H1504GQ2 MJV H1504G H2006G H2510G 70(Resistance 0 to 135) 71(4 to 20 mA) 72(1 to 5 VDC) 73(0 to 10 VDC) 1/2 3/4 1 Model Connection Rc(O.D.) Cv Value 1 2 3.5 6.5 12 1 49 58.8 205 209 69 82 42 50 2.0 2.2 34.3 202 56 32 1.8 Max. Operation Press. Differential (MPa) Torque (N m) Dimension H L D Wt. (kg)

77

Three-way Valve
Catalog No. Type Model M1504G M2006G MJV M2510G M3212G M4014G M5020G Model 70 (Resistance 0 to 135) 71 (4 to 20 mA) 72 (1 to 5 VDC) 73 (0 to 10 VDC) Connection Rc(O.D.) 1/2 3/4 1 1-1/4 1-1/2 2 Cv Value 3.5 6.5 12 20 30 45 0.1 Max. Operation Press. Differential (MPa) Torque (N m) 34.3 49 58.8 78.5 83.4 98.1 Dimension H1 152 155 159 165 178 185 H2 30 37 44 51 57 67 H2 56 69 82 97 106 128 L 32 42 50 60 71 84 Wt. (kg) 1.6 1.8 2.1 2.8 3.5 5.0

Wiring
Resistance Input
(Blue)COM. Input (Brown)0 to 135 (Black) (Red) Supply Voltage AC24V (Brown)4 to 20mA (Black) (Red) Supply Voltage AC24V

Current Input
(Blue)COM. Input

Voltage Input
(Blue)COM. Input (Brown)1 to 5V , 0 to 10V (Black) (Red) Supply Voltage AC24V

DIMENSIONS
Two-way Valve
Opening Indicator

Two-way Valve for Steam


Opening Indicator

Clutch Release Button for Manual Operation Shaft for Manual Operation

Clutch Release Button for Manual Operation Shaft for Manual Operation

Label 0.3mm Cab tire code

Label 0.3mm Cab tire code

Flow Flow Direction display

Flow Flow Direction display

Three-way Valve
Opening Indicator

Manual Operation
Use a spanner at Manual Operation shaft(Torque:3N m), with pushing a Clutch Release button. Manual operation can be carried out by rotating the shoft. Don't operate in energized position for the safty. -- please do not operate it by any means.
Shaft for Manual Operation

Clutch Release Button for Manual Operation

Mounting Position
Mounting position should be in the below range.

Label 0.3mm Cab tire code Flow(NO) Flow Direction display Mixed(A) Flow(NC)

Opening Indicator : O...Open, S...Close

Unit: mm

78

DAMPER & VALVE MOTOR ACTUATORS


Type EGK & WGK GENERAL DESCRIPTION
Series GK motor actuator can provide On-Off, proportional or floating control of damper, valve or other controlling devices. Balancing relay without contact causes no burn-out. Type EGK is for damper. Type WGK is for valve. Type TAK1040 transformers (line volt. 24V. AC) available upon request.

TYPE NUMBER SELECTION (SPECIFICATIONS)


Power requirement: 24V. AC 10%, 50/60Hz
Type EGK

Max. power consumption: 21VA (without spring return action) 24VA (with spring return action) Input signal: resistance 0 to 135 Current 4 to 20mA. DC (Input Impedance 250) Voltage 1 to 5V. DC (Input Impedance 100k) Type: EGK Torque: Type: WGK Thrust:

Type WGK

12.2Nm {1.25 kgm} (without spring return action) 3.9Nm {0.4 kgm} (with spring return action) Rotation angle: 90 to 270 (without spring return action) 90 to 160 (with spring return action) Delivery Setting 90 Timing: 80 sec/160 Ambient temp.: 20 to 55C (without spring return action) 10 to 55C (with spring return action) Weight: 4.3kg (without spring return action) 6.1kg (with spring return action)

1220N {125 kgf} (without spring return action) 390N {40 kgf} (with spring return action) Stroke: 14 to 50mm (without spring return action) 14 to 30mm (with spring return action) Delivery Setting 20mm Timing: 80 sec/stroke 25mm Ambient temp.: 20 to 55C (without spring return action) 10 to 55C (with spring return action) Weight: 5kg (without spring return action) 6.7kg (with spring return action)

DAMPER MOTOR SELECTION


Function Model Standard With Auxiliary Potentiometer With Auxiliary Switch 1 OnOff/Floating Control OnOff/Floating EGKN500A EGKN520A Without Positioning Balance Relay With Positioning Balance Relay With Positioning Balance Relay 2 3 4 Current Input OnOff Servo Resistance Input Voltage Input EGKN600 A/S EGKN610 A/S EGKN620 A/S EGKN700 A/S EGKN710 A/S EGKN720 A/S EGKN701 A/S EGKN711 A/S EGKN721 A/S EGKN702 A/S EGKN712 A/S EGKN722 A/S

VALVE MOTOR SELECTION


Function Model Standard With Auxiliary Potentiometer With Auxiliary Switch 1 OnOff/Floating Control OnOff/Floating WGKN500A WGKN520A Without Positioning Balance Relay With Positioning Balance Relay With Positioning Balance Relay 2 3 4 Current Input OnOff Servo Resistance Input Voltage Input WGKN600 A/S WGKN610 A/S WGKN620 A/S WGKN700 A/S WGKN710 A/S WGKN720 A/S WGKN701 A/S WGKN702 A/S WGKN711 A/S WGKN712 A/S WGKN721 A/S WGKN722 A/S

1. The motor actuates with OnOff or floating signal from sensor. 2. The motor actuates with proportional signal from electronic sensor (Example: Type RBE Control Unit). 3. The motor actuates with the signal between 0 and 135 from electric sensor (Example: Type PWS Thermostat). 4. Spring Return Type is so designed that actuator shaft returns to safe side on current failure. Auxiliary potentiometer is to provide the signal between 0 and 135 in accordance with motor angular rotation for output. Auxiliary switch provides the contact signal of S.P.D.T. for output. Enclosure: IP62

79

INTERNAL WIRINGS
Check power supply to be 24V. AC 10%. Wiring is to be based on the technical standard of electrical installation. Be assured to use covered copper wire larger than 1.2 mm dia. Terminal wiring should be conducted with flexible wire of adequate length to prevent wire disconnection from slight move of the motor.
EGKN500A, WGKN500A
a d c b 9 8 On-Off or Floating Controller d f 24V. AC b e g 7 6 24V. AC

EGKN700A/S, WGKN700A/S
8 a c 9 1 3 Proportional Controller

7 6

EGKN600A/S, WGKN600A/S
a d b f e c 9 8 2 4 3 1 7 6 24V. AC Feedback Resistance On-Off Servo Signal

EGKN701A/S, N702A/S, WGKN701A/S, N702A/S


9 a d f b e V.I 4 7 6 24V. AC c R S 8 1 2 COM 4 to 20 mA. DC Input Signal g 1 to 5 V. DC

Auxiliary Potentiometer 10 11 5

Auxiliary Switch 10

Terminals
11 5

EGKN1A/S WGKN1A/S

EGKN2A/S WGKN2A/S

a: Upper Limit Switch e: Feedback Potentiometer b: Lower Limit Switch f: Spring Return Releasing Magnet Motor External Wiring c: Cam d: Condenser Motor g: Balance Relay Spring Return Type Only Motor Internal Wiring

DIMENSIONS
Type EGKNA
122 2 27 with Plastic Cap

Type EGKNS
122 2 27 with Plastic Cap Hole for adjusting Rotation Hole for adjusting Rotation 36

210

36

95

34

10

34

10

95

210

8.5 130 150

80.5 187

2 11 Mounting Hole 130 150

8.5

80.5

2 11 Mounting Hole 259

Type WGKNA
122 187 2 27 with Plastic Cap

Type WGKNS
122 187 2 27 with Plastic Cap

Hole for adjusting Stroke Valve Opening Position Indicator 95

210

210

Hole for adjusting Stroke Valve Opening Position Indicator

95

322

10

112

10

112

322

34.5 130 150

27

171 198

34.5 130 150

27 270

80

2WAY & 3WAY CONTROL VALVES


Type NVK GENERAL DESCRIPTION
Type NVK control valves are accompanied by Saginomiya type WGK motor for two position (On-Off), floating or proportional control. For use with low or high pressure hot and chilled water or non-corrosive fluid. NVK ... 2-way valve NVKM ... 3-way valve (mixing valve) Wide model selection available for various applications. V-port plug provides almost linear flow characteristic.

Type NVKG

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type NVK 2-way valve
Model Item Connection Fluid Max. Working Press. Fluid Temp. (C) Flow Characteristic Material of Body Material of Plug Material of Seat Ring Material of Stem CAC406 or CAC407 FC200 SCS14 SUS316 SUS304 0.98MPa {10 kgf/cm2} 0 to 200 Equal Percentage FCDS NVKGL Rc NVKFL Flange (JIS 10K) NVKFP Flange (JIS 20K) 1.96MPa {20 kgf/cm2} 0 to 250

Type NVKF

NVKWFL Flange (JIS 10K) 0.98MPa {10 kgf/cm2} 0 to 200 FC200

Non-corrosive Water and Steam

Type NVKM 3-way valve


Model Item Connection Fluid Max. Working Press. Fluid Temp. (C) Flow Characteristic Material of Body Material of Plug Material of Seat Ring Material of Stem CAC406 or CAC407 SCS14 SUS316 SUS304 NVKMGL Rc Non-corrosive Water for Air conditioning 0.98MPa {10 kgf/cm2} 0 to 200 Equal Percentage FC200 NVKMFL Flange (JIS 10K)

81

Type NVK 2-way valve


Catalog No. 1504GL@1 1504GL@2 1504GL 2006GL 2510GL 3212GL 4014GL 5020GL 6524FL 8030FL NVK 10040FL 1504FP@1 1504FP@2 1504FP 2006FP 2510FP 3212FP 4014FP 5020FP 6524FP 8030FP 10040FP 4014FL@1 4014FL 5020FL 6524FL NVKW 8030FL 10040FL 12550FL 15060FL 20080FL 250100FL 20 25 32 40 50 65 80 100 40 50 65 80 100 125 150 200 250 3/4" 1" 11/4" 11/2" 2" 21/2" 3" 4" 11/2" 2" 21/2" 3" 4" 5" 6" 8" 10" Flange (JIS 10K) Flange (JIS 20K) 15 1/2" 20 25 32 40 50 65 80 100 3/4" 1" 11/4" 11/2" 2" 21/2" 3" 4" Flange (JIS 10K) Rc 15 1/2" Port Size (mm) Connection Tube O.D. Style Cv 1 2.5 5 8 12 20 30 45 70 110 180 1 2.5 5 8 12 20 30 45 70 110 180 20 30 45 70 110 180 260 380 630 960 45 0.69 {7} 0.49 {5} 0.83 {8.5} 40 30 0.98 {10} 0.81 {8.3} 0.66 {6.7} 0.98 {10} 20 0.98 {10} 30 40 20 1.96 {20} 30 40 20 0.95 {9.7} 0.61 {6.2} 0.40 {4.1} 0.28 {2.9} 0.19 {1.9} 0.12 {1.2} 0.98 {10} Stroke (mm) Close off Rating WGKNA MPa {kgf/cm2} WGKNL Dimensions (mm) L H h (h2) WGKNS 0.98 {10} 0.66 {6.7} 0.38 {3.9} 0.24 {2.4} 0.14 {1.4} 0.09 {0.9} 0.05 {0.5} 0.044 {0.45} 0.028 {0.29} 1.76 {18} 0.66 {6.7} 0.38 {3.9} 1.57 {16} 0.95 {9.7} 0.61 {6.2} 0.40 {4.1} 0.28 {2.9} 0.19 {1.9} 0.12 {1.2} 0.24 {2.4} 0.14 {1.4} 0.09 {0.9} 0.062 {0.62} 0.044 {0.45} 0.028 {0.29} 0.98 {10} 0.67 {6.8} 0.48 {4.9} 0.31 {3.2} 0.2 {2} 1.96 {20} 194 197 210 235 267 292 317 368 222 254 276 298 352 403 451 543 673 50 53 61 72 125 149 169 110 114 129 156 187 208 225 278 319 0.67 {6.8} 0.48 {4.9} 0.31 {3.2} 0.2 {2} 0.98 {10} 90 105 120 140 276 298 352 190 48 50 60 68 125 149 169 29 30 35 46 87.5 92.5 105 47.5 50 62.5 67.5 70 77.5 87.5 100 112.5 70 (80) (96) (115) (150) (153) (170) (212) (232) 80 43 28 Wt. (kg)

0.9 0.95 1.2 1.6 2.4 3.6 19.9 25 36 3.5 4 5.7 7.3 8.6 12 20 28.5 39.5 10.5 13.5 18 28.5 46.5 63.3 90.6 167 251

45

Cv ... Flow (L/min) passing through the valve at full opening when water temperature is 15C and pressure difference across the valve is 0.00048 MPa {0.0049 kgf/cm2}

DIMENSIONS
M81 M81 Stroke 90 Stroke

90

Type NVKG

Type NVKF Unit: mm

h2

82

Type NVK, 3-way valve (used as a mixing valve)


Catalog No. 1504GL 2006GL 2510GL 3212GL 4014GL NVKM 5020GL 6524FL 8030FL 10040FL 12550FL 15060FL Port Size (mm) 15 20 25 32 40 50 65 80 100 125 150 Connection Tube O.D. 1/2" 3/4" 1" 11/4" 11/2" 2" 21/2" 3" 4" 5" 6" Flange (JIS 10K) Rc Style Cv 5 8 12 20 30 45 70 110 180 260 380 40 30 20 0.98 {10} 0.95 {9.7} 0.61 {6.2} 0.40 {4.1} 0.28 {2.9} 0.19 {1.9} 0.12 {1.2} 0.08 {0.8} 0.05 {0.5} Stroke (mm) Close off Rating WGKNA MPa {kgf/cm2} WGKNL L 80 0.98 {10} 90 105 120 0.67 {6.8} 0.48 {4.9} 0.31 {3.2} 0.2 {2} 0.13 {1.3} 0.09 {0.9} 140 276 298 352 403 451 Dimension (mm) H 29 32 38 43 51 92 106 131 149 173 h 72 73 77 80 84 97 185 215 238 263 288 WGKNS 0.38 {3.9} 0.23 {2.3} 0.14 {1.4} 0.09 {0.9} 0.061 {0.62} 0.044 {0.45} 0.028 {0.29} Wt. (kg) 1.1 1.12 1.45 1.95 2.7 4.17 24.5 31 42 64.5 92

Cv ... Flow (L/min) passing through the valve at full opening when water temperature is 15C and pressure difference across the valve is 0.00048 MPa {0.0049 kgf/cm2}

DIMENSIONS
M81 Stroke M81 Stroke 90 90 h H L L

Type NVKMG

Type NVKMF Unit: mm

83

OTHER VALVES
CHECK VALVES Type ACV & BCV PRESSURE ACTUATED WATER REGULATING VALVES Type VWR PRESSURE ACTUATED WATER REGULATING VALVES Type CWR, AWR, GWR, MWR & SWR TEMPERATURE ACTUATED WATER REGULATING VALVES Type OWR, HWR & XWR PRESSURE REGULATING VALVES Type EPR PRESSURE REGULATING VALVES Type SPR & DPR DIAPHRAGM TYPE STOP VALVES Type ADV 85 86 8788 8990 9192 9394 95

82

OTHER VALVES

CHECK VALVES
Type ACV & BCV GENERAL DESCRIPTION
Install in the liquid line of heat pump air conditioner to prevent the counter flow at change over of cycles from heating to cooling and vice versa. Also for prevention of reverse flow of high pressure gas when compressor stops. For use with Fluorinated Refrigerants, air or oil. Can be mounted in horizontal or vertical line.

Type ACVB

Type BCV

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type ACV
Catalog No. ACV2B (D) ACV3B (D) ACV4B (D) ACV5B (D) ACV6B (D) Inert Gas Fluid Fluorinated Refrigerants Air Port Size (mm) 4.8 7.5 10 12.5 16 Cv Value 0.55 1 2.4 4.2 6 Connection Copper Tube (O.D.) 1/4" 3/8" 1/2" 5/8" 3/4" B: Flare D: Solder 3 {30.6} 40 to 125 Style Max. Working Pressure (MPa) {kgf/cm2} Allowable Liquid Temp. (C) Wt. (kg) B 0.1 0.2 0.4 0.5 0.7 D 0.05 0.1 0.2 0.3 0.5

Type BCV
Catalog No. BCV302DY BCV603DY BCV804DY BCV1005DY BCV1306DY BCV1810DY Fluorinated Refrigerants Fluid Port Size (mm) 3 5.5 8 10 12.5 18 Cv Value 0.33 0.97 2 3.5 4.7 8 Connection Copper Tube (I.D.) 1/4" 3/8" 1/2" 5/8" 3/4" 1" Solder 4.15 {42.3} 30 to 120 Style Max. Working Pressure (MPa) {kgf/cm2} Allowable Liquid Temp. (C) Wt. (kg) 0.02 0.04 0.07 0.14 0.18 0.34

DIMENSIONS
D S d E L L L

Type ACVB

Type ACVD Unit: mm Unit: mm L 58 76 87 103 115 120 160 187 235 300 6.35 9.53 12.70 15.88 19.05 D S 14 19 24 30 36

Type BCV302DY to 804DY

Type ACV
Catalog No. ACV2B ACV3B ACV4B ACV5B ACV6B ACV2D ACV3D ACV4D ACV5D ACV6D

Type BCV1005DY to 1810DY

Type BCV
Catalog No. BCV302DY BCV603DY BCV804DY BCV1005DY BCV1306DY BCV1810DY Unit: mm L 112 120 140 160 180 200 d 6.55 9.70 12.92 16.09 19.30 25.7 E 8 13 16 19 20

85

PRESSURE ACTUATED WATER REGULATING VALVES


Type VWR GENERAL DESCRIPTION
Type VWR: 2-way press. actuated water regulating valves,open on pressure increase. Refrigerant: R410A, R407C, R404A Type VWR is applicable to the adjustment range which exceeds the applicable adjustment range of type AWR (Refer to next page). Pressure connection: 1/4" flare nut (Standard) Body material: Bronze for water and brine.
Type VWR

TYPE NUMBER SELECTION (SPECIFICATIONS)


PRESSURE ACTUATED VALVES 2-WAY
Catalog No. 1203G VWR 1504G 2006G Fluorinated Refrigerants Bronze Kind of Refrigerant Valve Body Material Connection Size 3/8" 1/2" 3/4" Rc 1.5 to 2.9 {15.3 to 29.6} 4.2 {42.8} 60 1 {10.2} 2.4 {24.5} Style Press. Range Max. Working Press. Max. Water Temp.(C) Max. Water Press. Unit: MPa {kgf/cm2} Factory Setting Wt. (kg) 0.68 0.9 1.0

Pressure at which valve starts opening. Adjust type VWR to a set value which is suitable for the refrigerant employed.

FLOW CAPACITY
Flow Capacity shows respectively refrigeration press. diff. at horizontal axis and flow rate of cooling water at vertical axis considering water press. diff. before and behind a valve with 0.1 MPa. (press. diff. between inlet and outlet of valve) In case of water press. diff. before and behind a valve is excepting for 0.1MPa, value is calculated multipling by coefficient in compensation table.
water pressure difference before and behind a valve: 0.1MPa
100 2006G 50 40 30 1203G 20 Flow volume L/min 10 1504G

ADJUSTMENT
One full turn of adjusting screw changes pressure setting as shown below.
Catalog No. 1203G VWR 1504G 2006G Approx. 0.2MPa Change in Press. Setting

COMPENSATION COEFFICIENTS
Press. Drop Across Valve:MPa {kgf/cm2} 0.2 {2} 0.1 {1} 0.03 {0.3} 0.05 {0.5} 0.07 {0.7} Coefficient 1.4 1 0.55 0.7 0.8

DIMENSIONS
Type VWR
C

0.1

0.2

0.3 0.4 0.5 0.6 Valve Opening Refrigeration Press.(MPa)

0.7

0.8 Inlet

Valve Opening Refrigerant Press. Diff. means difference between valve opening press.(Setting Press.) and actual working press.

D (Hex.Width across flats)

Please avoid to apply to this range constantly. Valve Opening Press.(Gas pressure when valve opening)

L 1/4" Flare Nut

Catalog No. 1203G VWR 1504G 2006G

Unit: mm D 22 27 32 L 55 70 80 H 91 100 104 h 72 83 87 C 40 42

86

PRESSURE ACTUATED WATER REGULATING VALVES


Type CWR, AWR, GWR, MWR & SWR GENERAL DESCRIPTION
Type CWR, AWR & MWR: 2-way press. actuated water regulating valves, open on pressure increase. Type GWR: 2-way press. actuated water regulating valves, open on pressure decrease. Type SWR: 3-way press. actuated water regulating valves. Pressure connection: 1/4" flare nut (Standard) Body material: Bronze for water and brine, cast iron for water only
Type AWR

TYPE NUMBER SELECTION (SPECIFICATIONS)


PRESSURE ACTUATED VALVES 2WAY
Catalog No. Kind of Refrigerant Valve Body Material Connection Size 3/8" 1/2" 3/8" Bronze 1/2" 3/4" 1" 11/4" 11/2" Fluorinated Refrigerants Cast Iron 2" 21/2" 11/2" Bronze 2" 21/2" Flange R: 0.59 to 1.18 {6.0 to 12.0} H: 1.08 to 1.77 {11.0 to 18.0} 0.59 to 1.18 {6.0 to 12.0} R: 0.59 to 1.18 {6.0 to 12.0} H: 1.08 to 1.77 {11.0 to 18.0} 1.96 {20} 60 Rc 0.59 to 1.77 {6.0 to 18.0} Style Rc Flare Press. Range 0.6 to 1.8 {6.0 to 18.0} Max. Working Press. 2 {20} Max. Water Temp. (C)

Type SWR Unit: MPa {kgf/cm2} Factory Setting 0.75 {7.5} 0.88 {9} Wt. (kg) 0.45 0.8 0.66 0.8 0.74 {7.5} 1.0 1.8 2.1 11.2 0.98 {10} R: 0.74 {7.5} H: 1.23 {12.5} 0.74 {7.5} R: 0.74 {7.5} H: 1.23 {12.5} 17.8 21.6 11.2 17.8 21.6

Max. Water Press. 1 {10}

CWR AWR

803GLWQ1 1204BLW 1203GLW 1504GLW 2006GLW 2510GLW 3212GLW

AWR GWR

4014FLW 5020FLWR 5020FLWH 6524FLWR 6524FLWH 4014FLW

MWR

5020FLWR 5020FLWH 6524FLWR 6524FLWH

Pressure at which valve starts opening. AWR, GWR & MWR with flange connection are supplied with JIS 10K (0.98 MPa) round companion flanges (JIS B2220 2239) and bolts/nuts.

PRESSURE ACTUATED VALVES 3WAY


Catalog No. Kind of Refrigerant Valve Body Material Connection Size 1/2" Fluorinated Refrigerants Bronze 3/4" 1" 11/4" Rc 0.59 to 1.77 {6 to 18} 1.96 {20} 60 0.98 {10} Style Press. Range Max. Working Press. Max. Water Temp. (C) Max. Water Press.

Unit: MPa {kgf/cm2} Factory Setting Wt. (kg) 1.1 0.74 {7.5} 1.5 2.5 3.0

1504GLW SWR 2006GLW 2510GLW 3212GLW Pressure at which main valve starts opening. Pressure range: Main line opening point

VALVE ACTION
Set Point is pressure for valve opening. Each cheractaristic of valves is different as follows.
Flow CWR AWR MWR Flow GWR Flow SWR

ADJUSTMENT
One full turn of adjusting screw changes pressure setting as shown below. Catalog No. AWR
e

Change in Press. Setting

1204 BLW 1203 GLW 1504 GLW 2006 GLW 2510 GLW 3212 GLW Approx. 0.075MPa 4014 FLW 5020 FLW 6524 FLW Approx. 0.09MPa Approx. 0.1MPa

By pa ss

Ma

in

Lin

Lin e

AWR GWR SWR AWR MWR GWR

Press. Set Point

Press. Set Point Set Point

Press.

87

FLOW CAPACITY
Flow Capacity shows respectively refrigeration press. diff. at horizontal axis and flow rate of cooling water at vertical axis considering water press. diff. before and behind a valve with 0.1 MPa. (press. diff. between inlet and outlet of valve) In case of water press. diff. before and behind a valve is excepting for 0.1MPa, value is calculated multipling by coefficient in compensation table. Type AWR, MWR, GWR water pressure difference before and behind a valve: 0.1MPa Type SWR water pressure difference before and behind a valve: 0.1MPa
bypass side bypass side bypass side bypass side main side main side main side main side

Flow volume

Flow volume

Valve Opening Refrigeration Press. (MPa)


Valve Opening Refrigerant Press. Diff. means difference between valve opening press.(Setting Press.) and actual working press.

Press. Diff. between Valve Opening Setting Press. (MPa) and Refrigerant Press.(Gas Press inside Bellows) Please avoid to apply to this range constantly. Setting Range(Point)(Valve Opening Press)

Please avoid to apply to this range constantly. Valve Opening Press.(Gas pressure when valve opening)

ACCESSORY
Pressure dampening capillary tube assembly only attached for AWR50, 65, MWR50 and 65. Please use these for safty.
Union

COMPENSATION COEFFICIENTS
1/4" Flare Nut
1 meter Capillary Tube.

Press. Drop Across Valve:MPa {kgf/cm2} 0.2 {2} 0.1 {1} 0.03 {0.3} 0.05 {0.5}

Coefficient 1.4 1 0.55 0.7 0.8

DIMENSIONS
Type CWR
23.9

0.07 {0.7}

Catalog No. 1204BLW 1203GLW 1504GLW AWR GWR 2006GLW 2510GLW 3212GLW AWR MWR GWR 4014FLW 5020FLW 6524FLW 1504GLW
22 Capillary Tube Approx. 1m 1/4" Flare Nut Shrader Connection

Unit: mm D 22 27 32 40 50 27 32 40 50 L 100 55 70 80 90 100 148 173 179 70 80 90 100 H 90 91 100 104 116 121 125 180 100 104 116 121 h 70 72 83 87 97 102 105 155 31 39 44 54 83 87 97 102 89 42 59 59 h1 C 40 42

Rc3/8

46

AWR
79
24 He x.

Inlet

21

33

50

SWR

2006GLW 2510GLW 3212GLW

Type AWR, GWRG


C

Type AWR, MWR, GWRF


C

Type SWR
C

D Hex. width across flats

D Hex. width across flats

H Outlet h Main Outlet Bypass h1

Inlet

Inlet h

Inlet

Blind Plug

L 1/4" Flare Nut

L 1/4" Flare Nut L 1/4" Flare Nut L

Unit: mm

88

TEMPERATURE ACTUATED WATER REGULATING VALVES


Type OWR, HWR & XWR GENERAL DESCRIPTION
Type OWR: 2-way temp. actuated water regulating valves, open on temperature rise. Type HWR: 2-way temp. actuated water regulating valves, open on temperature decrease. Type XWR: 3-way temp. actuated water regulating valves. Temperature sensing element (type OWR, HWR & XWR) Capil. tube: 1000mm2.4 Body material: Bronze for water and brine, cast iron for water only

Type OWR

TYPE NUMBER SELECTION (SPECIFICATIONS)


TEMPERATURE ACTUATED VALVES 2WAY
Catalog No. 5004 G 5006 G 5010 G 5012 G 5014 F 5020 F OWR HWR 5024 F 7504 G 7506 G 7510 G 7512 G 7514 F 7520 F 7524 F Cast Iron Bronze Cast Iron Bronze Valve Body Material Connection Size 1/2" 3/4" 1" 11/4" 11/2" 2" 21/2" 1/2" 3/4" 1" 11/4" 11/2" 2" 21/2" Flange 32350 Rc 50 to 75 100 19320 Flange 60 0.98 {10} 19150 32350 Rc 30 to 50 80 19320 Style Temp. Range (C) Max. Water Temp. (C) Max. Water Press. Max. Bulb Temp. (C) Bulb Size (mm) 19150

Type XWR Unit: MPa {kgf/cm2} Factory Wt. Setting (kg) (C) 1.0 1.2 2.0 40 2.2 11.5 18.3 22.2 1.0 1.2 2.0 60 2.2 11.5 18.3 22.2

Pressure at which valve starts opening. OWR & HWR with flange connection are supplied with JIS 10K (0.98 MPa) round companion flanges (JIS B2220 2239) and bolt/nuts. Capillary tube ... Standard 1 meter, optional 1.5, 2 and 3 meters

TEMPERATURE ACTUATED VALVES 3WAY


Catalog No. 5004 G 5006 G 5010 G XWR 5012 G 7504 G 7506 G 7510 G 7512 G Pressure at which valve starts opening. Capillary tube ... Standard 1 meter, optional 1.5, 2 and 3 meters Bronze Rc Valve Body Material Connection Style Size 1/2" 3/4" 1" 11/4" 1/2" 3/4" 1" 11/4" 50 to 75 30 to 50 60 0.98 {10} 19150 100 19320 80 19320 Temp. Range (C) Max. Water Temp. (C) Max. Water Press. Max. Bulb Temp. (C) Bulb Size (mm) 19150

Unit: MPa {kgf/cm2} Factory Wt. Setting (kg) (C) 1.0 40 1.5 2.5 3.0 1.1 60 1.5 2.5 3.0

VALVE ACTION
Set Point is pressure for valve opening. Each cheractaristic of valves is different as follows.
Flow OWR Flow HWR Flow XWR

ADJUSTMENT
One full turn of adjusting screw changes pressure setting as shown below. Catalog No. 04G OWR HWR XWR 06G 10G 12G 14F OWR HWR 20F 24F Approx. 4.0C Approx. 3.0C
Bypa
ine

Change in Temp. Setting Approx. 4.0C

in L

ss Lin

Ma

Press. Set Point

Press. Set Point Set Point

Press.

89

FLOW CAPACITY
Flow Capacity shows respectively opening temp. diff. at horizontal axis and flow rate of cooling water at vertical axis considering water press. diff. before and behind a valve with 0.1 MPa. (press. diff. between inlet and outlet of valve) In case of water press. diff. before and behind a valve is excepting for 0.1MPa, value is calculated multipling by coefficient in compensation table. Type OWR, HWR water pressure difference before and behind a valve: 0.1MPa Type XWR water pressure difference before and behind a valve: 0.1MPa
(bypass side) (bypass side) (bypass side) (main side) (bypass side) (main side) (main side) (main side)

Flow volume

Flow volume

30
Valve Opening Temp. Diff. ()
Valve Opening Temp. Diff. means difference between valve opening temp.(Setting Temp.) and actual working temp..

Temp. diff. between operating temp. () and value opening tem. Please avoid to apply to this range constantly. Setting Range(Point)(Valve Opening Temp.)

Please avoid to apply to this range constantly. Valve Opening Temp.(Gas temperature when valve opening)

COMPENSATION COEFFICIENTS
Press. Drop Across Valve:MPa {kgf/cm2} 0.2 {2} 0.1 {1} 0.03 {0.3} 0.05 {0.5} Type OWRF, HWR
C

Coefficient 1.4 1 0.55 0.7 0.8

DIMENSIONS
Type OWR, HWRG
C

0.07 {0.7}

14F 20F, 24F H H D Hex. width across flats

Catalog No. 5004 G 5006 G 5010 G 5012 G 5014 F 5020 F OWR HWR 5024 F 7504 G 7506 G 7510 G 7512 G 7514 F 7520 F 7524 F

Unit: mm D 27 32 40 50 27 32 40 50 L 70 80 90 100 148 173 179 70 80 90 100 148 173 179 H 100 104 116 121 125 180 100 104 116 121 125 180 h 83 87 97 102 105 155 83 87 97 102 106 155 89 59 89 42 59 C 42

Inlet

Inlet

L Capillary Tube L Capillary Tube 2.41000 2.41000

Type XWR

Catalog No.
D Hex. width across flats H

Unit: mm D 27 32 40 50 27 32 40 50 L 70 80 90 100 70 80 90 100 H 100 104 116 121 100 104 116 121 h 31 39 44 54 31 39 44 54 h1 83 87 97 102 83 87 97 102 C 42 59 42 59

5004G 5006G
Outlet Blind Plug Outlet Bypass

Inlet

5010G XWR 5012G 7504G 7506G 7510G 7512G Unit: mm

Main

h1

2.41000 Capillary Tube

90

PRESSURE REGULATING VALVES


Type EPR GENERAL DESCRIPTION
Evaporating pressure regulating valves Direct operated, 2-way valves designed for maintaining suitable evaporating pressure in refrigeration. Fitted at the evaporator outlet to keep suitable set evaporating pressure.

Type EPRB

Type EPRD

COMMON SPECIFICATIONS
Operation Specifications Max. Working Pressure Max. Testing Pressure Fulid Temp. Pressure Adjustment Manual Open Direct Operation type 2.5MPa {25kgf/cm2} 3MPa {30kgf/cm2} to 100C Increase 1604 to 05: 0.08MPa {Approx.0.82kgf/cm2} /rotation 1905 to 07: 0.05MPa {Approx.0.51kgf/cm2} /rotation

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. Equalization Type Model 1604B 1605B 1905B 1906B EPR 1604D 1605D 1905D 1906D 1907D 20 5.5 {19} 3.5 {12} 4.1 {14} Internal Capacity (U.S.R.T.) {kW} Port size (mm) Valve Open 100% R22 15 20 15 2.6 {9.1} 5.5 {19} 2.6 {9.1} CT 38C P0.074MPa {0.75kgf/cm2} ET 5C Valve Open 70% R134a 1.5 {5.3} 3.5 {12} 1.5 {5.3} Valve Open 100% R404A 1.9 {6.7} Flare 4.1 {14} 1.9 {6.7} 0 to 0.6 {0 to 6} Solder Adjusting Range (MPa) {kgf/cm2} Connection Factory Setting Copper (MPa) Tube {kgf/cm2} (O.D.) 1/2" 5/8" 3/4" 12.7 15.88 19.05 22.23 0.4 0.3 {3} 0.5 0.2 Wt. (kg)

Style

0.3

91

APPLICATION EXAMPLE
Evaporating pressure regulating valve type EPR Fitted at the evaporator outlet to keep suitable set evaporating pressure. At multi evaporator system, evaporating pressure regulating valves are used to control each different pressure (temperature) of evaporators. Compressor operates based on the lowest pressure (temperature) of evaporators, pressure regulating valves keep pressure (temperature) of each evaporator at their setting pressure. In this case, a check valve is required at the outlet of lowest pressure evaporator. Also, evaporating pressure regulating valve is used at water chiller for prevent form congelation of cool water and vegetable warehouse for prevents form over dehumidification.
Compressor

Equalizer Check Valve


EPR

Low Temperature Evaporator Expansion Valve Equalizer Medium Temperature Evaporator Expansion Valve High Temperature Evaporator Expansion Valve Condenser

Evaporating Pressure Regulating Valve


EPR

Equalizer Receiver

Evaporating Pressure Regulating Valve

DIMENSIONS
Type EPRB Type EPRD Direct Operation Type Catalog No. Type
H H

Unit: mm L 45 53 56 60 71 H 82 109 82 h 91 94 100 105 78

Model 1604B 1605B 1905B 1906B

Hex. 27

EPR
Hex. 27 h h

1604D 1605D 1905D 1906D

100

109

120

L L

1907D

Unit: mm

92

PRESSURE REGULATING VALVES


High Volume OEM Item (Type DPR) Type SPR & DPR GENERAL DESCRIPTION
Type SPR Direct operated, 2-way valves, designed for maintaining suitable compressor suction pressure in refrigeration or air conditioning units. Fitted in suction line after the evaporator to prevent compressor overload. Type DPR Fitted in by-pass line between compressor discharge and suction line in refrigeration or air conditioning units. (Quantity order only.) Senses excessive compressor discharge pressure and releases it through the bypass line to the low pressure side to protect the compressor from overloading. Reduces frequency of cut-in and cut-out of high pressure switch to keep the compressor operating. A typical advantage is in the heating cycle of heat pump systems during spring or autumn, or at the time when filter is clogged with foreign materials.

Type SPRB

Type SPRD

Type DPR

COMMON SPECIFICATIONS (Type SPR)


Operation Specifications Max. Working Pressure Max. Testing Pressure Fluid Temp. Pressure Adjustment Manual Open Direct Operation type 2.5MPa {25kgf/cm2} 3MPa {30kgf/cm2} to 100C Increase 1604 to 05: Approx. 0.08MPa {0.82kgf/cm2} /rotation 1905 to 07: Approx. 0.05MPa {0.51kgf/cm2} /rotation 3011 to 13: Approx. 0.03MPa {0.31kgf/cm2} /rotation

TYPE NUMBER SELECTION (SPECIFICATIONS)


Type SPR
Catalog No. Fluid Type Model 1604B 1605B 1905B 1906B 1604D SPR 1605D 1905D 1906D 1907D 3011D 3013D 29 5.0 {17.6} 2.7 {9.5} 4.5 {15.8} 20 3.0 {10.5} 1.8 {6.3} 2.5 {8.8} Fluorinated Refrigerants Capacity (U.S.R.T.) {kW} Port Size (mm) CT38C P0.049MPa {0.5kgf/cm2} ET10C Valve Open 40% R22 15 20 15 1.4 {4.9} 3.0 {10.5} 1.4 {4.9} Valve Open 70% R134a 0.9 {3.2} 1.8 {6.3} 0.9 {3.2} Valve Open 70% R404A 1.1 {3.9} 2.5 {8.8} 1.1 {3.9} Copper Tube (O.D.) 1/2" 5/8" 3/4" 1/2" 5/8" 3/4" 7/8" 11/8" 13/8" 1.3 Solder 0.4 Style Connection Wt. (kg)

0.3 Flare 0.5 0.2

Nominal capacity is based on condensing temp. 38C, evaporating temp. 10C, pressure drop across the valve 0.049 MPa {0.5kgf/cm2}, and Set Pressure R134a0.2MPa {2kgf/cm2}, R220.4MPa {4kgf/cm2}. R404A...0.5MPa {5kgf/cm2}

93

Type DPR
Catalog No. Type DPR Model 343D Fluid Fluorinated Refrigerants Port Size (mm) 3.4 Factory Adjustable Range (MPa) 0.98 to 2.45 Connection (mm) Tube (I.D.) 7.94 Style Solder Max. Working Press. (MPa) {kgf/cm2} 2.9 {29} Wt. (kg) 0.11

Working pressure is factory set, please specify working pressure when order.

APPLICATION EXAMPLE
Suction pressure regulating valve type SPR Suction pressure regulating valve is installed between compressor and evaporator in order to keep outlet pressure (suction pressure) under it's setting. In case of rapid increase of load, suction pressure regulating valve could be used to prevent from overload of electric motor for compressor.
Suction Pressure Regulating Valve SPR Compressor Compressor

Discharge pressure regulating valve type DPR Discharge pressure regulating valve is mounted in the lowpressure side bypass piping from the discharge piping of a compressor as a control valve to control the discharge pressure to be lower than the specified pressure for the purpose of preventing the compressor from being an abnormal high pressure.

Evaporator Condenser

Evaporator DPR Condenser Discharge Pressure Regulating Valve

Expansion Valve

Expansion Valve

DIMENSIONS
Type SPRB Type SPRD Catalog No. Type Model 1604B 1605B
H H

Unit: mm L 45 53 56 60 71 H 82 109 82 h 91 94 100 105 78

1905B 1906B 1604D SPR 1605D 1905D 1906D

100

109

120

1907D 3011D 3013D


L

140

147

170

Type DPR
23 19

114

64.2 7.94

63.2

7.94

Unit: mm

94

DIAPHRAGM TYPE STOP VALVES


Type ADV GENERAL DESCRIPTION
The valve can be used on the lines of delivery gas, liquid, suction gas and hot gas, etc. The valve is applicable to not only Fluorinated refrigerants, but also air. In spite of its compactness and light weight, the port diameter is comparatively large to enable to flow a large amount. The large diameter handle makes easy and smooth rotation even in vacuum condition. Carefully processed valve with selected material provides long trouble free service and dependable operation. Type ADV cannot be used in a reverse flow.

Type ADVB

Type ADVD

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. 902BY 903BY 1404BY 1605BY 1606BY ADV 902DY 903DY 1404DY 1605DY 1606DY 1607DY 16 Port Size (mm) 9 14 16 9 14 Flow Coefficient 0.35 0.79 1.61 2.82 3.46 0.35 0.79 1.61 2.82 3.46 Connection Copper Tube (O.D.) 1/4" 3/8" 1/2" 5/8" 3/4" 1/4" (6.35) 3/8" (9.53) 1/2" (12.7) 5/8" (15.88) 3/4" (19.05) 7/8" (22.23) Solder 3.6 {36} Flare Style Max. Working Pressure

Unit: MPa {kgf/cm2} Fluid Temp. (C) Wt. (kg) 0.26 0.32 0.51 0.85 1.13 40 to 120 0.24 0.28 0.46 0.76 0.91

DIMENSIONS
D

Catalog No. 902BY 903BY


(H)

Unit: mm L 80 85 101 128 135 165 190 200 H 75 75.5 87.5 98 102 75 75.5 87.5 98 102 h 20 19.5 23 25 20 19.5 23 25 70 70 6.5 52 9.65 12.95 16.15 19.3 22.45 8 10 12 14 D 52 d E

1404BY 1605BY 1606BY ADV


h L

902DY 903DY 1404DY 1605DY 1606DY 1607DY

Type ADVBY
D

(H)

E L

Type ADVDY Unit: mm

95

OTHER CONTROL EQUIPMENT


FLOW SENSORS 97 Type ELK FLOW SWITCHES 98 Type FQS DRAIN PUMPS 99 Type MDP TEMPERATURE RECORDERS 100 Type AKM & BKM CONDENSER FAN SPEED CONTROLLERS 101102 Type RGE CONDENSER FAN SPEED CONTROLLERS 103 Type XGE CONTROL APPLIANCES FOR HOT WATER SUPPLY UNITS BY CO2 REFRIGERANT 104105 Type CCB, HSK, HPV, UKV-J & JKV CONTROL APPLIANCES FOR HOT WATER SUPPLY UNITS 106107 Type CRV, VSV, WSV, HEV, XJV, TCV, CAV, JSK, ELK BELLOWS 108 Type HBL & WSL OTHER CONTROLS & VALVES 109 Type RKV, SKM & Bi-METAL (No. 03, 05 & 24)

94

OTHER CONTROL EQUIPMENT

FLOW SENSORS
High Volume OEM Item Type ELK GENERAL DESCRIPTION
Turbine type flow sensor having an impeller to rotate in proportion to flow rate. For burner On-Off of hot water supply system, accumulation of automatic hot water supply. Pulse output corresponding flow rate. Max. working pressure: 1MPa Fluid temperature: 0 to 80C (No frozen) Rated voltage: 4.5 to 13.2 V. DC Housing body material: PPS Installation is vertical riser piping or horizontal piping.

SPECIFICATIONS
Flow RateOutput Pulse Characteristics Catalog No. Range of Flow Rate (L/min) Based Flow Rate (L/min) 1.5 ELK0508 1.5 to 25 10 15 Vertical riser piping (pps) 9.62 68.76 102.912 Horizontal piping (pps) 7.72 69.26 104.112 Open Collector 15 0.025 Output Mode Max. Output Current (mA) Wt. (kg)

FLOW RATEOUTPUT PULSE CHARACTERISTICS


100 Horizontal piping Output Pulse pps Vertical riser piping 150 Terminal Cable Color No.1 Red: Vcc No.2 No.3 Yellow: Vout Black: GND

DIMENSIONS

50

30

30

190.06 0.1

200.06 0.1

30

25

25

10 0 Inlet

1.5

10

15 Flow rateL/min

50

30

Unit: mm

97

FLOW SWITCHES
Type FQS GENERAL DESCRIPTION
For use on liquid lines such as water, ethylene glycol, or any non-corrosive fluid in chillers, pumps, condensers, boilers, etc. With S.P.D.T. contact mechanism. Paddle consists of three segments that can be removed or trimmed for use in 1 to 6" pipe. Drip proof models: Available upon request. mark applicable (available upon request)

UL listed (available upon request)

SPECIFICATIONS
Catalog No. Paddle Size Connection Size Style Max. Working Pressure MPa{kgf/cm2} 0.98 {10} Fluid Temp. (C) Max. Flow Velocity (m/s) Wt. (kg)

FQSU30G

3"

1"

580

0.6

Enclosure:IP20 (IP62 model:available upon request.)

ELECTRICAL RATINGS
Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 125V. AC 15 3.5 21 250V. AC 15 2.5 15

OPERATION ADJUSTMENT RANGE TABLE


When the operating value is not specified, the flow switch is shipped with the operating value set around the minimum flow rate. When you turn the flow adjusting screw clockwise, the operating point goes up. When you turn it counterclockwise, the operating point goes down. When more than two paddles is attached, you can change the flow rate adjustment range by removing the paddles one by one in order of the longer paddle first.
Paddle Pipe Size Size Adjustment range (L/min) Min. Max.

DIMENSIONS
29 50 64

Flow Decrease Flow Increase Flow Decrease Flow Increase


98.5

1" 1-1/4" 1-1/2"


1.5 121.2

18 1" 1"+2" 1" 1"+2" 1" 1"+2"+3" 1"+2" 1" 1"+2"+3" 43 63 50 151 105 356 100 226 481 200 386 821 350 595 1266 530 837 1781

28 53 78 65 181 126 427 120 271 577 240 463 985 420 714 1519 636 1004 2137

45 100 135 150 220 355 360 225 480 510 385 820 870 594 1265 1342 836 1780 1890

55 120 162 180 264 426 432 270 576 612 462 984 1044 713 1518 1610 1003 2136 2268

Earth Mark 189

Hex.36

2" 2-1/2"

R1" 59 35

1" Paddle

3"

89

Flow

2" Paddle

4"
3" Paddle 28

1"+2" 1" 1"+2"+3"

5" Unit: mm 6"

1"+2" 1" 1"+2"+3" 1"+2" 1"

Flow decrease ... Flow amount at which the switch operates on flow decrease. Flow increase ... Flow amount at which the switch operates on flow increase.

98

DRAIN PUMPS
High Volume OEM Item Type MDP GENERAL DESCRIPTION
Drain pump which can exhaust drain water in accumlating at indoor unit. By adopting DC motor, this realizes more energy saving, much higher durability,compact and light weight. Fluid: Drain water Fluid temp.: 0 to 35C (No frozen water) Ambient temperature: 10 to 45C Motor coil insulation: Class E

SPECIFICATIONS
Catalg No. Rated Voltage Tolerance (%) 10 Power Consumption (Pump head:850mm) 3.1W Max. Flow 400cm3 /min or more at Rated Voltage Pump Head (mm) 150 to 850 Sound Level Wt. (kg) 0.19

MDP14

DC12V

36dB (A) or less on no drain

Please contact us for the AC motor types.

DIMENSIONS
Type MDP14
115

NOTE FOR USE

115

73 .2

Water Level

outlet

13

3-4.6

Inlet It must be 8mm or more the distance from drain pan to the bottom of pump.

95

3 17

(20)

15.5 52
55

Unit: mm

99

27

Pump Head

20

TEMPERATURE RECORDERS
Type AKM & BKM GENERAL DESCRIPTION
Portable temperature recorder widely applicable for use in refrigeration, air conditioning and medical fields. High recording accuracy with quartz driving motor. Recording paper feeding speed: 3.3mm per hour Motor driven by dry cell battery: 1.5V. DC, Ctype Life 1 year Type BKM is a temperature sensitive recording paper which is supplied as standard for use 12 month period. Specify catalog No. when order additional papers. Higher and lower alarm pointers can be set within the range.

Type AKM

TYPE NUMBER SELECTION (SPECIFICATIONS)


Catalog No. AKM4014LH1X AKM4014LH2X AKM0054LH1X AKM0054LH2X AKM1044LH1X AKM1044LH2X AKM0620LH1X For Air-conditioning 10 44 Application Examples For Refrigeration & Freezing Temp. Range Min. 40 0 Max. 14 54 2 0.5 plus Indicating Accuracy Indicating Accuracy Recording Accuracy Alarm Accuracy Alarm Power Source 100 to 120V. AC 200 to 240V. AC 100 to 120V. AC Temp. Scale 2 200 to 240V. AC 100 to 120V. AC 200 to 240V. AC 100 to 120V. AC 200 to 240V. AC Catalog No, of Recording Paper BKM4044X BKM0054X

Unit: C Wt. (kg)

1.6 BKM4044X BKM0620X

28 : 0.8 28 : 0.8 For Medical Use 20 6 62 : 2 62 : 2 AKM0620LH2X 820 820 Alarm Contact: Each one on upper and lower limit pointer, 100V. AC1A, 200V. AC 0.5A.

WIRINGS
Higher Alarm Pointer Lower Alarm Pointer

DIMENSIONS
162 149 140.4 Capillary Tube 22000 60 Sensing Bulb 183.7 Capillary Tube

Alarm Power Source Lower Alarm Terminal Higher Alarm Terminal

Standard capillary tube length: 2.02000mm (Plastic covering on capillary tube available.) Alarm lamp or buzzer can be connected to the contacts on higher and lower alarm terminals.

111

Unit: mm

Less than 15

100(170)

12.7( 15.9) ( ): Type 0620

100

CONDENSER FAN SPEED CONTROLLERS


Type RGE GENERAL DESCRIPTION
The most suitable for controlling the speed of a condenser fan of freezing and refrigeration condensing unit, package air conditioner and other units which are operated throughout a year. Keep condensing pressure constant in winter and intermediate seasons for stable operation. One of the following operation models is selectable when low speed. Minimum Speed Operation Cut off Operation Excellent noise-resisting design. Applicable to the external forced operation switch. mark applicable
Single-phase type

listed (available upon request)

COMMON SPECIFICATIONS
Max.working pressure : 4.7MPa Control method : Phase control Enclosure : IP54
Three-phase type

TYPE NUMBER SELECTION (SPECIFICATIONS)


1

F.V.S. Setting (MPa) Adjusting Range Min. 0.8 1.6 0.8 1.6 0.8 1.6 0.8 1.6 0.8 1.6 0.8 1.6 0.8 1.6 Max. 2.8 3.9 2.8 3.9 2.8 3.9 2.8 3.9 2.8 3.9 2.8 3.9 2.8 3.9

2 E.P.B. (MPa) Refrigerants Electrical Ratings Ampere Fixed 0.6 R22, R404A, R407C Fixed 0.9 R410A Fixed 0.4 R22, R404A, R407C Fixed 0.8 R410A Fixed 0.4 R22, R404A, R407C Fixed 0.8 R410A Fixed 0.4 R22, R404A, R407C Fixed 0.8 R410A Fixed 0.4 R22, R404A, R407C Fixed 0.8 R410A Fixed 0.6 R22, R404A, R407C Fixed 0.8 R410A Fixed 0.4 R22, R404A, R407C Fixed 0.8 R410A 0.2 to 3A At approx. 45% (50Hz) at approx. 35% (60Hz) Cut Off or Minimum 0.2 to 4A Speed function is Single phase 220 to 240V. AC selectable with 50/60Hz 0.2 to 6A changeover switch. Default setting: 0.2 to 8A Cut Off 0.2 to 5A Three phase 220 to 240V. AC 50/60Hz 0.2 to 7A At approximately 35%, Cut Off or Minimum Speed function is selectable with changeover switch. Three phase Default setting: 380 to 415V. AC 0.2 to 5A Min. Speed
50/60Hz

Catalog No.

Factory Set 1.9 3.2 1.9 3.2 1.9 3.2 1.9 3.2 1.6 3.2 1.6 3.2 1.6 3.2

Function

Ambient Temp. (C)

Operation

Wt. (kg)

RGEZ1L47 RGEZ1L67 RGEZ1N47 RGEZ1N67 RGEZ1P47 RGEZ1P67 RGEZ1Q47 RGEZ1Q67 RGEZ3R47 RGEZ3R67 RGEZ3T47 RGEZ3T67 RGEX3R47 RGEX3R67

0.36 0.5 20 to 55 0.54 0.58 1.4 20 to 50 15 to 50 1.53 1.4

1: The pressure at which the control delivers 95% output effective voltage (VRMS). 2: Pressure width where effective voltage corresponds to the minimum speed or causes cut off operation Min. speed: Fan motor will be kept running at the specific value (V%) when pressure band increase more than E.P.B. Cut off: Fan motor will be stopped when pressure decrease to the specific value (V%) for R.M.S. For other pressure set values or min. speed/cut off set values, please contact us.

OPERATION
Singlephase type
Effective Voltage R.M.SV% . 100 95 Max. Speed F.V.S. Adjustable

Threephase type
Effective Voltage R.M.SV% . 100 95 Max. Speed F.V.S. Adjustable

50 Hz
45 35 Cut Off Min. Speed

60

Hz

at

at 23 0 23 V 0V

35

Min. Speed Cut Off

E.P.B. Fixed

E.P.B. Fixed

Pressure

Pressure

The operating characteristic may vary according to the voltage, frequency, and fan motor characteristics.

101

WIRING
Single-phase type
for 2A (RGEZ1)
External Forced Operation Switch On: Full speed Off: Auto speed

Three-phase type
for 4A, 6A, 8A (RGEZ1)

Ground

Ground Circuit Breaker or Fuse

External Forced Operation Switch On: Max. speed Off: Auto speed

Circuit Breaker or Fuse

Ground

Circuit Breaker or Fuse

Fan Motor Switch

Switch Power Supply

Switch

External Forced Operation Switch

Fan Motor

Fan Motor

Apply external forced operation switches that afford to cut consumption curret of fan motors.

Use a forced operation switch with non-voltage contact signal.

DIMENSIONS
Single-phase type
104 95 44.4 105 95 45.4

Three-phase type
185 175 160 45.4

(125)

75

100

150

900100 900100 1/4" Female Flare with Schrader Copper Packing 1/4" Female Flare with Schrader Copper Packing 900100

(102)

22.5 Conduit Gland

12

36 (55)

22.5 Conduit Gland

130

200

1/4" Female Flare with Schrader 58 67

Copper Packing

for 4A 22.5 Conduit Gland 98

36

for 2A

58

22.5 Conduit Gland 76 for 5A (REG-Z3,X3) 67 25

for 6A 36 22.5 Conduit Gland 98

58 76

22.5 Conduit Gland 25 for 7A (REG-Z3)

for 8A

Unit: mm

16

16

102

CONDENSER FAN SPEED CONTROLLERS


Type XGE GENERAL DESCRIPTION
The most suitable for controlling the speed of a condenser fan of freezing and refrigeration condensing unit, package air conditioner and other units which are operated throughout a year. Keep condensing pressure constant in winter and intermediate seasons for stable operation. mark applicable listed (available upon request)

COMMON SPECIFICATIONS
Control method : Phase control Max. working pressure : 4.7MPa Power supply : [Rated Voltage] 230V.AC 15 % single phase [Frequency] 50/60Hz [Rated Amp.] 0.2 to 3A 20 Pressure connection : 1/4 Female flare with Schrader (7/16-20 UNF) Enclosure : IP65

TYPE NUMBER SELECTION (SPECIFICATIONS)


*1 Catalog No. Factory Set XGE-4CC-7 XGE-4MC-7 XGE-6CC-7 XGE-6MC-7 Cut off 1.9 F.V.S. Setting(MPa) Adjusting Range Min. 1.0 Max. 2.5 0.6 R22,R407C,R404A R410A Cut off type Min. speed type Cut off type Min. speed type 20 to 55 20 to 70 0.19 *2 E.P.B (MPa) Refrigerants Function Ambient temp. (C) Fluid temp. (C) Wt. (kg)

2.8

2.2

3.9

0.7

: Fan motor will be stopped when pressure decrease to the specific value(V%) for R.M.S. Min. speed : Fan motor will be kept running at the specific value(V%) when pressure band increase

OPERATION
XGE-4CC-7 and XGE-6CC-7 (Cut off type)
F.V.S. (Adjustable)

*1 F.V.S. : FULL VOLTAGE SET POINT The pressure at which the control delivers 95% output effective voltage. *2 E.P.B. : EFFECTIVE PROPORTIONAL BAND Pressure width where effective voltage corresponds to the min. speed or causes cut off operation.

XGE-4MC-7 and XGE-6MC-7 (Min. speed type)


F.V.S. (Adjustable)

Effective voltage(V%)

0V

Hz

60

(35)
Cut off

(35)

E.P.B. (Fixed)

Pressure

60

Hz

50 (45)

50 (45)

Min. speed

23 0V

H 50

23

0V

Effective voltage(V%)

100 (95)

Max. speed

100 (95)

Max. speed

H 50

23

0V

23

*The operating characteristic may vary according to the voltage, frequency, and fan motor characteristics.

E.P.B. (Fixed)

Pressure

DIMENSIONS

64.2
9

WIRINGS
Connector Fan motor

(48.4)

8.8 9.2 18

Range adjusting screw

(8)

2
Circuit breaker or Fuse

Switch
12.5

Power supply
Supplied with a gasket. Cable exit in 4 directions possible.

63.2

PIN 1.60.1 1.50.1

ACCESSORIES (XGE-1 Plug parts set)


Plug Gasket Plug fixing screw Plastic bag

1.5
Heat sink

(15.9)

Pressure admission port Schrader

Copper packing

103

Unit: mm

10.5

(7)

CONTROL APPLIANCES FOR HOT WATER SUPPLY UNITS BY CO2 REFRIGERANT


High Volume OEM Item Type CCB, HSK, HPV, UKV-J & JKV GENERAL DESCRIPTION
Used for CO2 refrigerant applications. Available for extreme high pressure.

Type CCB

Type HSK

Type HPV

Type UKV-J

PRESSURE CONTROL for High Pressure [Type CCB ]


SPECIFICATIONS
Catalog No. CCBAA01 Setting on 10 {100} off 15 {150} Max. Pressure 15 {150} Contact Function SPST (High Cut) Pressure Connection 1/4" Solder Terminal Construction Open Unit: MPa {kgf/cm2} Application High Pressure Cut Out Wt. (kg) 0.07

Allowable fluid temperature: 30 to 100 C Enclosure: IP20 (IP66 model: available upon request)

ELECTRICAL RATINGS
Category of Ratings Rated Voltage (V) Rated Amps. (A) Non-Inductive Current Inductive Current Full Load Locked Rotor Power Factor (cos) 1 0.75 0.45 T Rating 24V. DC 12V. DC

DIMENSIONS
Type CCB
10.5 Faston#250 26.2 57.7 6.35 8

0.01 to 0.05
28 14

CONTACT FUNCTION

PRESS. RISING

PRESSURE SENSOR for High Pressure [Type HSK ]


SPECIFICATIONS
Catalog No. HSKBC150D Pressure Range {0 to 150} 0 to 15 Supply Voltage 5V. DC0.25V Output 0.5 to 4.5V. DC Accuracy 2.5% F.S. Current Consumption Max. 10mA Load Resistance Min. 10k Airtight Pressure 15 {150} Unit: MPa {kgf/cm2} Pressure Connection 1/4" Solder Wt. (kg) 0.07

Allowable fluid temperature: 30 to 120 C Enclosure: IP66 Ambient temperature: 30 to 100 C

WIRING
1 2 Type HSK 3 Receiver Power Supply

DIMENSIONS
Type HSK
Contact pin No.

26

11.8

5V. DC0.25V. Connector

321

19.7 55 92.3

10.5

7.5

104

SOLENOID VALVE for High Pressure [Type HPV ]


TYPE NUMBER SELECTION (SPECIFICATIONS)
Catalog No. HPV102D HPV122D Port Size (mm) 1.0 1.2 Cv Value 0.028 0.038 Connection Copper Tube O.D. 1/4" Style Solder Min. 0 O.P.D. Max. 10.0 {100} Max. Working Pressure 13.0 {130} 13.8 {138} Unit: MPa {kgf/cm2} Operation Normal close Wt. (kg) 0.05 0.09

O.P.D.: Operating Pressure Differential (by air pressure) Ambient temperature: 20 to 50 C Allowable fluid temperature: 30 to 120 C

DIMENSIONS
Type HPV102D {HPV122D}
39

ELECTRICAL RATING OF SOLENOID COILS


Valve Type HPV102D HPV122D Rated Voltage 100V. AC 50/60Hz 200V. AC Voltampere Tolerance (%) Running Inrush 10 11/8 16/13 32/27 52/38 Power Insulation Wt. Consumption Class (kg) (W) 6/4.5 Class B 0.13 Molded 0.16 9/8

O.D. 6.35 88 107 O.D. 6.35 47

ELECTRONIC EXPANSION VALVE for High Pressure [Type UKV-J, JKV ]


TYPE NUMBER SELECTION (SPECIFICATIONS)
Catalog No. UKVJ14D JKV20D JKV24D Port Size (mm) 1.4 2.0 2.4 Cv Value 0.065 0.12 0.17 Capacity (U.S.R.T) {kW} 1 2 R744 CO2 R744 CO2 2.3 {8.1} 4.2 {14.8} 5.9 {20.7} 3.4 {11.8} 6.1 {21.6} 8.6 {30.4} 15 {150} 010 {0100} Max. Working Pressure Operating Pressure Differential B side 6.35 OD 7.94 OD Unit: MPa {kgf/cm2} Connection (Solder) (mm) A side 6.35 OD 7.94 OD 0.05 0.2 Wt. (kg)

1: CT=5 C, ET=25 C, SH=0 C, SC=0 C 2: Gas cooler inlet temp.=70 C, Gas cooler outlet temp.=22 C, ET=6 C, SH=0 C Allowable fluid temperature: 30 to 70 C Ambient temperature: 30 to 70 C Enclosure:IP66

SPECIFICATIONS OF COIL
Valve Type Type UKVJ Type JKV-20D 1-2 Phase excitation Type JKV-24D Excitation method Rated Voltage & Current 12V. DC.260mA/Phase 12V. DC.380mA/Phase Insulation Class Wt. (kg) 0.13 Class E Molded 0.14 0.19

DIMENSIONS
Type UKV-J
(47)

Type JKV-20D
37 48

Type JKV-24D
48

(43)

7.94

(32)

6.35

56

119

(100)

A side Conn.

A side Conn.

A side Conn. 7.94 6.35 47 54 54 7.94

50

56

Unit: mm

105

119

B side Conn.

7.94

B side Conn.

B side Conn.

45

Unit: mm

CONTROL APPLIANCES FOR HOT WATER SUPPLY UNITS


Type CRV, VSV, WSV, HEV, XJV, TCV, CAV, JSK, ELK GENERAL DESCRIPTION
Control appliances for hot water supply unit

Pressure Reducing Valve


Type CRV This water valve can be connected directly to a water conduit. This valve is provided with a check device, a negative pressure operating device, and a strainer. A bronze casting type and a resin type are prepared as the body material.

Type CRV

Type CRV

Relief Valve
Type WSV, VSV This valve being provided with a diaphragm is highly reliable and the most suitable for the maintenance of a hot water supply unit. (WSV type) This valve is provided with a negative pressure operating device. If the hot water supply unit or piping becomes a negative pressure internally, this device introduces the atmospheric pressure to prevent the damage of the unit and a reverse flow. (VSV type)

Type WSV

Type VSV

Solenoid Valve
Type HEV This small solenoid valve is used for feed water, cooling water, and hot water circuits of the hot water supply unit. A bronze casting type are prepared as the body material.
Type HEV

Electric Complex valve


Type XJV This three-way mixed proportional valve applies to the cold and hot water of a fully automatic hot water supply unit. It controls the mixing ratio of cold water and hot water to produce an optimum mixed water temperature.

Type XJV

106

Check Valve
Type TCV This is a resin type check valve for water.

Type TCV

Automatic Air Vent Valve


Type CAV This valve automatically releases the air generated in the hot water circuit outside. Since the unit and joint each being made of stainless steel material (SUS) are assembled together, it has excellent corrosion resistance, and also, it is safe and sanitary. This valve is characterized with a large exhaust volume and an excellent air exhaust performance.
Type CAV

Water Level Sensor


Type JSK This water level sensor adopts the semiconductor pressure sensor system. It is used for controlling the water level of a fully automatic bath.
Type JSK

Flow Sensor
Type ELK This turbine system flow sensor is provided with an impeller which rotates in proportion to the flow. This sensor is used for starting and stopping the burner of an instantaneous hot water supply unit and also integrating the automatic hot water feeding. It outputs pulses according to the flow.

Type ELK

107

BELLOWS
High Volume OEM Item Type HBL & WSL HydraulicallyFormed Bellows Type HBL etc...

Hydraulically corrugated bellows made from a tin wall metal pipe. Material and specifications are selectable for applications. Match for mass production and quality are very stable. Material example: Phosphor bronze, beryllium copper, stainless steel, hastelloy, inconel, etc

Welding Bellows

Type WSL etc ...

Bellows made from precision-made tin wall metal rings. Suitable for extremely precision use. Material is selectable for applications. Material example: Stainless steel, hastelloy, inconel, etc

Welding Bellows for vacuum useS seris


Welding bellows for low pressure and long stroke use Main Characteristics: Using anticorrosion material SUS316L Long stroke structure With End Fittings for easy to install Low price and fast delivery

Applications
Aerospace, marine, chemical, refrigeration, air conditioning, electric, construction, medical, and other various kinds of industrys. Bellows assembled with fittings are also available.

108

OTHER CONTROLS & VALVES


Type RKV, SKM, 03, 05 & 24 GENERAL DESCRIPTION
Various controls and valves are available by Saginomiya. The following are some examples.

3WAY CHANGE-OVER VALVE


Type RKV Control appliance for changing over flow direction in two evaporator type household retrigerator.

Type RKV

TEMPERATURE RECORDER FOR REFRIGERATION


CONTAINER Type SKM For marine container and truck refrigeration Open type without enclosure or drip proof type with enclosure 31 days recording or 7 days recording mark applicable (available upon request)

Type SKM

BI-METAL DISC THERMOSTATS


Type 03, 05, 24 For various applications, wide available temperature range: 20 to 260C Auto reset or manual reset

Please contact the company for detail information on the above controls.

109