Metasys Connectivity Technical Manual 629.

5 Metasys Integrator Section Application Note Issue Date 0900

APPLICATION NOTE

Metasys Integrator York Application

lntroduction
Application Details Component Requirements Vendor Contact Information Design Considerations

Page

*3
*3 *6 7 *7

Cable Connections
Cable Pinouts Connecting the Cable

9
9 9

Metasys Integrator Setup Point Mapping Tables


Translator and XL Login YT Centrifugal Dual or Mono Shell Chiller YK Centrifugal Super Chiller YS 125-400 Ton Rotary Screw Chiller LS 1000-1250 Ton Rotary Screw Chiller YP Absorption Chiller C1 U.S. Reciprocating Intelligent Chiller - Master C3 U.S. Reciprocating Intelligent Chiller - Slave B1 U.K. Basildon Reciprocating Intelligent Chiller - Master B3 U.K. Basildon Reciprocating Intelligent Chiller - Slave

*11 15
15 16 *18 20 21 22 24 27 29 31

*Indicates those sections where changes have occurred since the last printing.

2000 Johnson Controls, Inc. Code No. LIT-6295540

1
www.johnsoncontrols.com

YR Sunline 3000 Rooftop Chiller A1 Air-cooled Screw Chiller - Master A3 Air-cooled Screw Chiller - Slave YI Isoflow Absorption Chiller YG Gas Engine Drive Chiller

Page

33 35 37 *39 42

Metasys Network Setup


Mapping to a CS Object

*45
*45

Custom Integration

*47

*Indicates those sections where changes have occurred since the last printing.

Metasys IntegratorMetasys Integrator York Application

lntroduction
This document explains Metasys Integrator York applications. Use this document with the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5), which provide information on installing and commissioning the Metasys Integrator unit. For information on York equipment, see York documentation (obtainable from a York representative). Note: If you use a Universal Packaging Module (UPM) enclosure, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than the one high enclosure (EN-EWC13-0) as shown in the figures in this application note. Application Details The Metasys Integrator unit allows York Millennium chillers and Sunline 3000 rooftop units to become an integral part of the Metasys and Metasys Companion Networks. Once York controllers are connected to Metasys or Companion Networks via the Metasys Integrator unit, their data is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization. The York YorkTalk Translator and YorkTalk XL are the interfaces between York chiller controllers and non-York devices (such as the Metasys Integrator unit). Each Metasys Integrator vendor port can connect to one YorkTalk Translator. Each YorkTalk Translator can connect to up to four York chiller controllers. If you use reciprocating chillers, the maximum number of pairs in master/slave configuration (C1/C3 or B1/B3) is two. If you use only master reciprocating chillers (C1 or B1), the maximum number of chillers allowed is four. Also, with a YorkTalk Translator interface, reciprocating chillers may not be mixed with other types of chillers due to a difference in baud rates. Each Metasys Integrator vendor port can connect to one YorkTalk XL, which can then connect to 32 York controllers. Figure 1 shows York and Metasys System integration. Figure 2 shows York and Metasys Companion integration.

Metasys IntegratorMetasys Integrator York Application

N1 LAN A3 A1 Linc Chiller YS Linc Chiller YI Linc Chiller

RS-485 ISN Network Standard NCU YorkTalk XL RS-232 Metasys Integrator YorkTalk Translator

UNT N2 Bus

YK Chiller

YS Chiller

YP Chiller

YT Chiller

York1

Note:

If you use a UPM enclosure, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than the one high enclosure (EN-EWC13-0) as shown in the figures in this application note.

Figure 1: York and Metasys System Integration

Metasys IntegratorMetasys Integrator York Application

A3 Panel Unit Workstation A1 Linc Chiller YS Linc Chiller YI Linc Chiller

RS-485 ISN Network YorkTalk XL RS-232 Metasys Integrator YorkTalk Translator

UNT N2 Bus

YK Chiller

YS Chiller

YP Chiller

YT Chiller

Note: A PC version and converter may be substituted for the Panel unit.
york2

Note:

If you use a UPM enclosure, you must install the Metasys Integrator 300 Series in a two high enclosure (EN-EWC25-0) rather than the one high enclosure (EN-EWC13-0) as shown in the figures in this application note.

Figure 2: York and Metasys Companion Integration

Metasys IntegratorMetasys Integrator York Application

Component Requirements

To integrate York equipment, you need the following components: properly installed York YorkTalk Translator (Revision 1A, firmware Revision 5.00 or above) or YorkTalk XL version and York chiller controllers Note: The Metasys Integrator unit supports only the U.S. version of the translator, which has two Advanced Processor Cards. Versions with only one Advanced Processor Card (such as the U.K. version) are not supported. RS-232 cable (for connecting the YorkTalk Translator or YorkTalk XL to the Metasys Integrator unit) Metasys Integrator unit N2 Bus (for connecting the Metasys Integrator unit to the Metasys or Companion Networks) portable Personal Computer (PC) for downloading vendor communication tables (.VCT files) and network setup information into the Metasys Integrator unit, and for running diagnostics cable for connecting portable PC to the Metasys Integrator unit the correct vendor communication table (.VCT file) to download into the Metasys Integrator unit (supplied on Metasys Integrator CD-ROM)

Metasys Network Release Requirements

To integrate York equipment into the Metasys Network, you need: Metasys Operator Workstation (OWS) software Release 6.0 or higher Metasys Integrator software/firmware Release 8.0 or higher

Metasys Companion Release Requirements

To integrate York equipment into the Metasys Companion Network, you need: Metasys Companion Release 5.0 or higher Metasys Integrator software/firmware Release 8.0 or higher

Vendor Component Requirements

Integration between the Metasys Integrator unit and York has been tested with the YorkTalk Translator (Part Number 371-01415-100, Revision 1A) or the YorkTalk XL (Part Number 371-01457-101, Revision 77). Changes to this equipment or integration of York products not discussed in this document will require additional software development and testing by Systems Products. For information on integrating other products, refer to the Custom Integration section in this document.

Metasys IntegratorMetasys Integrator York Application

Vendor Contact Information

York International Corporation Applied Systems P.O. Box 1592-232Z York, PA 17405-1592 Phone: FAX: (717) 771-7890 (717) 771-7640

Design Considerations

When integrating York equipment, consider the following: Make sure all York equipment is set up and running properly before attempting to integrate with Metasys or Companion Network. (The York representative is responsible for operation of YorkTalk Translator, YorkTalk XL, and controllers.) Make sure the YorkTalk Translator or YorkTalk XL baud rate is set to 9600. (The York representative is responsible for setting the YorkTalk baud rate.) The York representative must configure the YorkTalk Translator or the YorkTalk XL to talk to the Metasys Integrator unit, provide passwords, and commission the chillers via YorkTalk. York must also configure the YorkTalk Translator and the YorkTalk XL to report BI statuses as Off and On. (The defaults in the Translator at this time are No and Yes.) The YorkTalk Translator or YorkTalk XL must be configured for: trm=4 (cr, prompt) txt=1 (field text) The YorkTalk Translator or the YorkTalk XL must have its logon password set to 1. Otherwise, the Metasys Integrator unit will not be able to bring it online. Make sure the YorkTalk Translator or YorkTalk XL table is defined as an N2 address so that the Metasys Integrator unit can establish the logon procedure. This will ensure the quickest recovery to online status of all York equipment.

IMPORTANT:

RS-232 cable distance between the Metasys Integrator unit and the YorkTalk Translator or YorkTalk XL can be a maximum of 50 feet. Cable distance between the YorkTalk Translator and the last controller can be a maximum of 5000 feet. The YorkTalk Translator does not provide offline notification when the chiller is disconnected from the Translator.
Metasys IntegratorMetasys Integrator York Application 7

IMPORTANT:

York must configure the YorkTalk XL failure output to report statuses as NOR, and FLT to allow the XL to report if the chiller is offline to the XL. Ensure battery backup is enabled to save baud rate settings on the YorkTalk Translator or YorkTalk XL. York chiller model names sometimes differ from the two character codes Johnson Controls uses (refer to Table 1). Table 1: Chiller Names
Standard Name
C1, C3 (B1, B3) A1, A3 YI YP

Also Known As:


YCA, YDA, YEA, YCW, YCR DYCAS YIA YPC

Metasys IntegratorMetasys Integrator York Application

Cable Connections
Cable Pinouts Use the following cable pinouts for the RS-232 connection between the Metasys Integrator unit and the YorkTalk Translator and XL:
Vendor Port A or B on Metasys Integrator DB-9 Female Signal RD TD GND Pin RS-232 2 3 5 (50 ft maximum) 15 14 16 TX1 RX1 GND1
york3

RS-232 Port on Translator or XL Screw Terminal Pin Signal

Figure 3: Cable Pinouts Connecting the Cable Connect the female end of the RS-232 cable to either Vendor Port A or Vendor Port B on the Metasys Integrator unit. Connect the male end to Port A on the YorkTalk Translator or YorkTalk XL.
Metasys Integrator YorkTalk Translator or XL

Vendor Port A or B

RS-232 Cable

RS-232 Terminal Block

york4

Figure 4: Port-to-Port Connection

Metasys IntegratorMetasys Integrator York Application

10

Metasys IntegratorMetasys Integrator York Application

Metasys Integrator Setup


To set up the Metasys Integrator unit, use a portable PC connected to the Metasys Integrator Terminal Port. Metasys Integrator setup involves: downloading the correct vendor communication table (.VCT file) setting up the ports assigning network addresses to the controllers

Table 2 provides information specific to York applications. For detailed procedures, see the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). Table 2: Metasys Integrator Setup for York Controllers
Vendor Communication Table (.VCT File) Login and Chillers Translator
Login YT Chiller (Centrifugal Dual Shell or Mono Shell) YK Chiller (Centrifugal Super Chiller) YS Chiller (125-400 Ton Rotary Screw) LS Chiller (1000-1250 Ton Rotary Screw) YP Chiller (Absorption Chiller) C1 Chiller (U.S. Reciprocating Intelligent Chiller-Master) C3 Chiller (U.S. Reciprocating Intelligent Chiller-Slave) B1 Chiller (U.K. Basildon Reciprocating Intelligent Chiller-Master) B3 Chiller (U.K. Basildon Reciprocating Intelligent Chiller-Slave) A1 Chiller (Air-cooled Screw ChillerMaster) A3 Chiller (Air-cooled Screw ChillerSlave) YI Chiller (Isoflow Absorption Chiller) YG Chiller (Gas Engine Drive Chiller) YK_TRAN.VCT YK_YTCH.VCT YK_YKCH.VCT YK_YSCH.VCT YK_LSCH.VCT YK_YPCH.VCT YK_C1CH.VCT YK_C3CH.VCT YK_B1CH.VCT YK_B3CH.VCT

XL
YK_XL.VCT YK_YTXL.VCT YK_YKXL.VCT YK_YSXL.VCT YK_LSXL.VCT YK_YPXL.VCT YK_C1XL.VCT YK_C3XL.VCT YK_B1XL.VCT YK_B3XL.VCT YK_S30XL.VCT YK_A1XL.VCT YK_A3XL.VCT YK_YIXL.VCT YK_YGXL.VCT

YR Chiller (Sunline 3000 Rooftop Chiller) YK_S3000.VCT N/A N/A N/A N/A 9600 8 1 None

Port Setup
Baud Rate Word Length Stop Bits Parity Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

11

Network Setup for Login of Translator or XL (Cont.)


Interface Vendor Address Timeout Value Poll Delay RS-232 0 4000 ms 550 ms 1-8 3000 ms 50 ms net, node 3000 ms 50 ms

Network Setup for Translator


Vendor Address Timeout Value Poll Delay

Network Setup for XL


Vendor Address* Timeout Value Poll Delay

Performance Guide Chillers


Approximate Scan Time (For a single N2 address) Login Table YT Chiller YK Chiller YS Chiller LS Chiller YP Chiller C1 Chiller C3 Chiller B1 Chiller B3 Chiller YR Chiller A1 Chiller XL A3 Chiller XL YI Chiller XL YG Chiller XL

Translator

XL

4 seconds 10 seconds 11 seconds 7 seconds 6 seconds 8 seconds 12 seconds 10 seconds 12 seconds 10 seconds 11 seconds N/A N/A N/A N/A

8 seconds 11 seconds 11 seconds 8 seconds 6 seconds 9 seconds 12 seconds 10 seconds 12 seconds 10 seconds 12 seconds 12 seconds 10 seconds 11 seconds 9 seconds

* Example: If network is 0 and node is 2, then enter 00,02 for the vendor address. The format is two digits each for the network address and the node address, with leading zeros if necessary.

12

Metasys IntegratorMetasys Integrator York Application

Network Modify/Add/Delete N2 Address 0 1 2 3 4 5 6 7 Poll Delay ] ] ] 550] 50] ] ] ]

Interface Type [ ] [ ] [ ] [YorkTalk Translator] [York C1 Chiller ] [ ] [ ] [ ]

Vendor Address [ [ [ [0 [1 [ [ [ ] ] ] ] ] ] ] ]

Port [A] [A] [A] [A] [A] [A] [A] [A]

Timeout [ ] [ [ ] [ [ ] [ [ 4000] [ [ 3000] [ [ ] [ [ ] [ [ ] [

Retry [ [ [ [ [ [ [ [ 3] 3] 3] 3] 3] 3] 3] 3]

Available Vendor Interface Types YorkTalk Translator York C1 Chiller

F1 Cancel F2 Save F3 More F4 Goto Select a vendor interface type from the list

Figure 5: Example--Proper Setup of York C1 Chiller on YorkTalk Translator


Network Modify/Add/Delete N2 Address 0 1 2 3 4 5 6 7 Poll Delay [ [ [ [ [ [ [ [ ] 550] 50] 50] 50] ] ] ] [ [ [ [ [ [ [ [

Interface Type [ ] [YorkTalk XL ] [York YT Chiller XL] [York YT Chiller XL] [York YT Chiller XL] [ ] [ ] [ ]

Vendor Address [ [0 [00,01 [00,02 [00,03 [ [ [ ] ] ] ] ] ] ] ]

Port [A] [A] [A] [A] [A] [A] [A] [A]

Timeout [ [ [ [ [ [ [ [ ] 4000] 3000] 3000] 3000] ] ] ]

Retry 3] 3] 3] 3] 3] 3] 3] 3]

Available Vendor Interface Types York Talk XL York YT Chiller XL

F1 Cancel F2 Save F3 More F4 Goto Select a vendor interface type from the list

Figure 6: Example--Proper Setup of Three York YT Chillers on ISN YorkTalk XL

Metasys IntegratorMetasys Integrator York Application

13

14

Metasys IntegratorMetasys Integrator York Application

Point Mapping Tables


The following tables (one for each application) show the points available for mapping in the York controllers: Translator and XL Login Table 3: YorkTalk Translator Login
NPT1
BI 1 2

NPA2
1

Unit

Description
Translator Ready 0-no, 1-yes

Network Point Type Network Point Address

Table 4: YorkTalk XL Login


NPT1
BI 1 2

NPA2
1

Unit

Description
XL Ready 0-no, 1-yes

Network Point Type Network Point Address

Metasys IntegratorMetasys Integrator York Application

15

YT Centrifugal Dual or Mono Shell Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Condenser Pressure point is AI10.

Table 5: YT Centrifugal Dual or Mono Shell Chiller (Translator and XL Configuration)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI6 BI7 BI8 AO AO AO BO 1 2 *

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 2 3 4 5 6 7 8 1* 2 3* 1

Unit
DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi psi % Amperes Amperes Amperes Volt Volt Volt DegF %

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Purge Pressure % Full Load Amperes Phase A Amperes Phase B Amperes Phase C Amperes Phase A-B Volts Phase B-C Volts Phase C-A Volts Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Compressor Vent Solenoid Chill Water Pump Start Switch Flow Switch ACC Valid Surge Map ACC New Surge Point VSD Cooling Pump Running 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

DegF %FLA DegC

Leaving Chill Water Setpoint (10 to 70) Current Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop 0-stop, 1-start

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

Continued on next page . . .

16

Metasys IntegratorMetasys Integrator York Application

NPT1 NPA2 (Cont.)


ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF BD BD 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2

Unit
Min Code Code Code Code Hour # # Volt kW MWh Volt Amps # Hz % % kVA Deg Deg # Hz

Description
Anti-Recycle Timer Operational Mode Code Operational Code Safety Code Cycling Code Runtime Hours Number Of Starts Adaptive Capacity Control Frozen Delta p/p VSD Output Voltage VSD Input kW VSD Input MWh VSD DC Link Voltage VSD DC Link Current VSD Surge Count VSD Output Frequency VSD Maximum Voltage THD VSD Maximum Current TDD VSD Input kVA VSD Internal Temperature VSD Converter Heatsink Temperature ACC PRV Position ACC Frozen Output Frequency VSD IEEE 519 Filter Present Surge Detection Type 0-Not Installed 0-Delta_p/p, 1-Current

Network Point Type Network Point Address

Metasys IntegratorMetasys Integrator York Application

17

YK Centrifugal Super Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Condenser Pressure point is AI10.

Table 6: YK Centrifugal Super Chiller (Translator and XL Configuration)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI AO AO AO BO 1 2 *

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 1 2 3 4 5 6 7 8 1* 2 3* 1

Unit
DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi % % Amperes Amperes Amperes Volt Volt Volt psi psi DegF %

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Refrigerant Level Full Load Amperes Phase A Amperes Phase B Amperes Phase C Amperes Phase A-B Volts Phase B-C Volts Phase C-A Volts Low Oil Pressure High Oil Pressure Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Compressor Vent Solenoid Chill Water Pump Start Switch Flow Switch ACC Valid Surge Map ACC New Surge Point VSD Cooling Pump Running 0-open, 0-open, 0-open, 0-open, 0-open, 0-open 0-open 0-open 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

DegF %FLA DegC

Leaving Chill Water Setpoint (10 to 70) Current Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop 0-stop, 1-start

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

Continued on next page . . .

18

Metasys IntegratorMetasys Integrator York Application

NPA2 NPT1 (Cont.)


ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF BD BD 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 1 2

Unit
Min Code Code Code Code Hour # # Volt kW MWh Volts Amps # Hz % % kVA Deg Deg # Hz %

Description
Anti-Recycle Timer Operational Mode Code Operational Code Safety Code Cycling Code Runtime Hours Number of Starts Adaptive Capacity Control Frozen Delta p/p VSD Output Voltage VSD Input kW VSD Input MWh VSD DC Link Voltage VSD DC link Current VSD Surge Count VSD Output Frequency VSD Maximum Voltage THD VSD Maximum Current TDD VSD Input kVA VSD Internal Temperature VSD Converter Heatsink Temperature ACC PRV Position ACC Frozen Output Frequency Refrigerant Level Setpoint VSD IEEE 519 Filter Present Surge Detection Type 0-Not Installed 0-Delta_p/p, 1-Current

Network Point Type Network Point Address

Metasys IntegratorMetasys Integrator York Application

19

YS 125-400 Ton Rotary Screw Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Discharge Temperature point is AI7.

Table 7: YS 125-400 Ton Rotary Screw Chiller (Translator and XL Configuration)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI AO AO AO BO ADF ADF ADF ADF ADF ADF ADF 1 2 *

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 2 3 4 5 6 7 1* 2 3* 1 1 2 3 4 5 6 7

Unit
DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi psi % Amperes Amperes Amperes Volt Volt Volt DegF %

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Filter Differential Pressure % Full Load Amperes Phase A Amperes Phase B Amperes Phase C Amperes Phase A-B Volts Phase B-C Volts Phase C-A Volts Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Compressor Oil Solenoid Chill Water Pump Start Switch Flow Switch Eductor Solenoid Separator Solenoid 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made

DegF %FLA DegC Min Code Code Code Code Hour #

Leaving Chill Water Setpoint (10 to 70) Current Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop Anti-Recycle Timer Operational Mode Code Operational Code Safety Code Cycling Code Runtime Hours Number of Starts 0-stop, 1-start

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

20

Metasys IntegratorMetasys Integrator York Application

LS 1000-1250 Ton Rotary Screw Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Discharge Temperature point is AI3.

Table 8: LS 1000-1250 Ton Rotary Screw Chiller (Translator and XL Configuration)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI AO AO AO BO ADF ADF ADF ADF ADF ADF 1 2 *

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 2 3 4 1* 2 3* 1 1 2 3 4 5 6

Unit
DegF DegF DegF DegF DegF psi psi psi psi % % % DegF %

Description
Leaving Chill Water Temperature Suction Temperature Discharge Temperature Oil Temperature Separator Temperature Evaporator Pressure Condenser Pressure Oil Pressure Filter Pressure % Full Load Amperes Slide Valve Liquid Level Vapor Pressure Ratio Leaving Water Temperature Actual Setpoint Current Actual Setpoint Feedback Heater Oil Pump Separator Switch Compressor 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made

DegF %FLA DegC Min Code Code Code Code Code

Leaving Chill Water Setpoint (38 to 70) Current Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (3 to 210) Chiller Start/Stop Anti-Recycle Timer Compressor Mode Slide Mode Operational Code Safety Code Cycling Code 0-stop, 1-start

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

Metasys IntegratorMetasys Integrator York Application

21

YP Absorption Chiller
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Purge Tank Pressure point is AI14.

Table 9: YP Absorption Chiller (Translator and XL Configuration)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI BI BI BI AO AO AO AO BO 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1 2 3 4 5 6 7 8 9 10 11 1* 2* 3* 4* 1

Unit
DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi psi DegF DegF %

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Leaving Hot Water Temperature Entering Hot Water Temperature First Gen 1 Temperature First Gen 2 Temperature Refrigerant Temperature Solution Temperature First Gen 1 Pressure First Gen 2 Pressure Purge Pump Pressure Purge Tank Pressure Leaving Water Temperature Actual Setpoint Leaving Hot Water Temperature Actual Setpoint Remote Loading Setpoint Feedback Refrigerant Pump Condenser Pump Chill Water Pump Start Switch Hot Water Pump Solution Pump 1 Solution Pump 2 Purge Pump Chill Water Flow Switch Hot Water Flow Switch Condenser Water Flow Switch 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

DegF DegF DegC DegC

Leaving Chill Water Setpoint (42 to 77) Hot Water Setpoint (90 to 175) Leaving Chill Water Setpoint (6 to 25) Hot Water Setpoint (32 to 79) Chiller Start/Stop 0-stop, 1-start

Network Point Type Network Point Address

Continued on next page . . .

22

Metasys IntegratorMetasys Integrator York Application

NPA2 NPT1 (Cont.)


ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2 * 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Unit
Mode Code Code Code Hour # # # # Min Min DegF DegF %

Description
Operational Mode Operational Code Safety Shutdown Code Cycling Shutdown Code Accumulated Operating Hours Accumulated System Starts Lifetime Purge Count Max Loading Seven Day Purge Total Pulldown Minutes Setpoint Pulldown Minutes Left Pulldown Loading Start Setpoint Pulldown Loading Stop Setpoint Present Calculated Pulldown Loading

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC. The same is true for points AO2 and AO4.

Metasys IntegratorMetasys Integrator York Application

23

C1 U.S. Reciprocating Intelligent Chiller - Master


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI5.

Table 10: C1 U.S. Reciprocating Intelligent Chiller - Master (Translator and XL Configuration)
NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

Unit
DegF DegF DegF DegF DegF psi psi psi %FLA psi psi psi %FLA DegF DegF DegF DegF psi psi DegF DegF DegF

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Outdoor Air Temperature Compressor 1 Suction Pressure Compressor 1 Discharge Pressure Compressor 1 Oil Pressure Compressor 1 Full Load Amperes Compressor 2 Suction Pressure Compressor 2 Discharge Pressure Compressor 2 Oil Pressure Compressor 2 Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low Pressure Cutout Feedback High Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint

Network Point Type Network Point Address

Continued on next page . . .

24

Metasys IntegratorMetasys Integrator York Application

NPA2 NPT1 (Cont.)


BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI AO AO AO BO 1 2 * 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1* 2 3* 1

Unit

Description
Chiller Run 0-open, 1-made Chiller Alarm 0-open, 1-made Evaporator Heater 0-open, 1-made Evaporator Pump Starter 0-open, 1-made Condenser Pump Starter 0-open, 1-made Load Permissive 0-open, 1-made Comp 1 Liquid Line Valve 0-open, 1-made Comp 1 Hot Gas Bypass Valve 0-open, 1-made Comp 1 Condenser Fan Reverse 0-open, 1-made Comp 2 Liquid Line Valve 0-open, 1-made Comp 2 Hot Gas Bypass Valve 0-open, 1-made Comp 2 Condenser Fan Reverse 0-open, 1-made Sw 1 (0-Comfort Cooling, 1-Brine) Sw 2 (0-Standard Ambient, 1-Low Ambient) Sw 3 (0-Local, 1-Remote) Sw 4 (0-RWT Control, 1-LWT Control) Sw 5 (0-English Units, 1-Metric Units) Sw 6 (0-Standard Fan Control, 1-Shared Fan Control) Sw 7 (0-Manual Lead/Lag, 1-Auto Lead/Lag) Sw 8 (0- Ambient Pressure Control, 1- Discharge Pressure Control)

DegF %FLA DegC

Leaving Chill Water Setpoint (10 to 70) % Load Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop 0-stop, 1-start

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

25

NPA2 NPT1 (Cont.)


ADF ADF ADF ADF ADF ADF ADF ADF 1 2 3 4 5 6 7 8

Unit

Description
Compressor 1: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor 2: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Master Anti-Coincidence Timer Load Steps Available Lead Compressor

Code Code # # Min Hour # Sec

ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2

9 10 11 12 13 14 15 16 17 18 19

Code Code # # Min Hour # Sec Min # #

Network Point Type Network Point Address

26

Metasys IntegratorMetasys Integrator York Application

C3 U.S. Reciprocating Intelligent Chiller - Slave


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Mixed Chill Water Temperature point is AI3.

Table 11: C3 U.S. Reciprocating Intelligent Chiller - Slave (Translator and XL Configuration)
NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Unit
DegF DegF DegF DegF psi psi psi %FLA psi psi psi %FLA DegF DegF DegF DegF psi psi DegF DegF DegF

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Mixed Chill Water Temperature Outdoor Air Temperature Compressor 3 Suction Pressure Compressor 3 Discharge Pressure Compressor 3 Oil Pressure Compressor 3 Full Load Amperes Compressor 4 Suction Pressure Compressor 4 Discharge Pressure Compressor 4 Oil Pressure Compressor 4 Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low-Pressure Cutout Feedback High-Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Chiller Run Chiller Alarm Evaporator Heater Evaporator Pump Starter Condenser Pump Starter Comp 3 Liquid Line Valve Comp 3 Hot Gas Bypass Valve Comp 3 Pressure Equalization Valve Comp 3 Condenser Reversing Valve Comp 4 Liquid Line Valve Comp 4 Hot Gas Bypass Valve Comp 4 Pressure Equalization Valve Comp 4 Condenser Reversing Valve Load Permissive 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

27

NPT1 (Cont.)
ADF ADF ADF ADF ADF ADF ADF ADF

NPA2

Unit

Description
Compressor 3: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor 4: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Slave Anti-Coincidence Timer Load Steps Available Lead Compressor

1 2 3 4 5 6 7 8

Code Code # # Min hrs # Sec

ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2

9 10 11 12 13 14 15 16 17 18 19

Code Code # # Min Hour # Sec Min # #

Network Point Type Network Point Address

28

Metasys IntegratorMetasys Integrator York Application

B1 U.K. Basildon Reciprocating Intelligent Chiller - Master


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI3.

Table 12: B1 U.K. Basildon Reciprocating Intelligent Chiller Master (Translator and XL Configuration)
NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Unit
DegF DegF DegF DegF psi psi psi %FLA DegF psi psi psi %FLA DegF DegF DegF DegF psi psi DegF DegF DegF

Description
Leaving Chill Water Temperature Leaving Condenser Water Temperature Outdoor Air Temperature Compressor 1 Oil Temperature Compressor 1 Oil Pressure Compressor 1 Suction Pressure Compressor 1 Discharge Pressure Compressor 1 Full Load Amperes Compressor 2 Oil Temperature Compressor 2 Oil Pressure Compressor 2 Suction Pressure Compressor 2 Discharge Pressure Compressor 2 Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low Pressure Cutout Feedback High Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Chiller Run 0-open, Chiller Alarm 0-open, Evaporator Heater 0-open, Evaporator Pump Starter 0-open, Condenser Pump Starter 0-open, Load Permissive 0-open, Comp 1 Liquid Line Valve 0-open, Comp 1 Hot Gas Bypass Valve 0-open, Comp 1 Pressure Equalization Valve 0-open, Comp 2 Liquid Line Valve 0-open, Comp 2 Hot Gas Bypass Valve 0-open, Comp 2 Pressure Equalization Valve 0-open, Sw 1 (0-Water Cooling, 1-Brine) Sw 2 (0-Stand Ambient, 1-Low Ambient) Sw 3 (0-Local, 1-Remote) Sw 4 (0-Star/Delta, 1-Part Wind) Sw 5 (0-English Units, 1-Metric units) Sw 6 (0-Comm Enable, 1-Comm Disable) Sw 7 (0-Manual Lead/Lag, 1-Auto Lead/Lag) Sw 8 (0-R134A Refrigerant, 1-R22) 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

29

NPT1 (Cont.)
AO AO AO BO ADF ADF ADF ADF ADF ADF ADF ADF

NPA2
1* 2 3* 1 1 2 3 4 5 6 7 8

Unit
DegF %FLA DegC

Description
Leaving Chill Water Setpoint (10 to 70) % Load Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop Compressor 1: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor 2: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Master Panel Anti-Coincidence Timer Load Steps Available Lead Compressor 0-stop, 1-start

Mode Code # # Min Hour # Sec

ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2 *

9 10 11 12 13 14 15 16 17 18 19

Code Code # # Min Hour # Sec Min # #

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

30

Metasys IntegratorMetasys Integrator York Application

B3 U.K. Basildon Reciprocating Intelligent Chiller - Slave


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI3.

Table 13: B3 U.K. Basildon Reciprocating Intelligent Chiller Slave (Translator and XL Configuration)
NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Unit
DegF DegF DegF DegF psi psi psi %FLA DegF psi psi psi %FLA DegF DegF DegF DegF psi psi DegF DegF DegF

Description
Leaving Chill Water Temperature Mixed Chill Water Temperature Outdoor Air Temperature Compressor 3 Oil Temperature Compressor 3 Oil Pressure Compressor 3 Suction Pressure Compressor 3 Discharge Pressure Compressor 3 Full Load Amperes Compressor 4 Oil Temperature Compressor 4 Oil Pressure Compressor 4 Suction Pressure Compressor 4 Discharge Pressure Compressor 4 Full Load Amperes Leaving Chill Water Setpoint Feedback Low Water Temperature Cutout Feedback Low Ambient Cutout Feedback High Ambient Cutout Feedback Low Pressure Cutout Feedback High Pressure Cutout Feedback Remote Temperature Setpoint Remote Cooling Range Local Barrel Setpoint Chiller Run Chiller Alarm Evaporator Heater Evaporator Pump Starter Condenser Pump Starter Comp 3 Liquid Line Valve Comp 3 Hot Gas Bypass Valve Comp 3 Pressure Equalization Valve Comp 3 Condenser Reversing Valve Comp 4 Liquid Line Valve Comp 4 Hot Gas Bypass Valve Comp 4 Pressure Equalization Valve Comp 4 Condenser Reversing Valve Load Permissive 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

31

NPT1 (Cont.)
ADF ADF ADF ADF ADF ADF ADF ADF

NPA2

Unit

Description
Compressor 3: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Compressor 4: Operational Code Fault Code Number of Operating Stages Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Runtime Seconds Slave Panel Anti-Coincidence Timer Load Steps Available Lead Compressor

1 2 3 4 5 6 7 8

Code Code # # Min Hour # Sec

ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2

9 10 11 12 13 14 15 16 17 18 19

Code Code # # Min Hour # Sec Min # #

Network Point Type Network Point Address

32

Metasys IntegratorMetasys Integrator York Application

YR Sunline 3000 Rooftop Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Building Air Pressure point is AI6.

Table 14: YR Sunline 3000 Rooftop Chiller (Translator and XL Configuration)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

Unit
DegF DegF DegF DegF psi psi % % Hour Hour % % psi psi psi psi psi psi DegF DegF psi psi DegF

Description
Space Temperature Discharge Air Temperature Return Air Temperature Outside Air Temperature Duct Static Pressure Building Air Pressure Outside Air Damper Position Heating Coil Valve Position Supply Fan Run Hours Exhaust Fan Run Hours Supply Fan Inlet Guide Vane Position Exhaust Fan Inlet Guide Vane Position Compressor 1 Oil Pressure Compressor 1 Suction Pressure Compressor 1 Discharge Pressure Compressor 2 Oil Pressure Compressor 2 Suction Pressure Compressor 2 Discharge Pressure Low Ambient Cutout High Ambient Cutout Low Pressure Cutout High Pressure Cutout Discharge Air Temperature Cutout Unit Run Permissive Air Handling Unit Alarm Local/Remote Selected Supply Fan Run Return (Exhaust) Fan Run OA/RA Selected Refrigeration System 1 Locked Out Compressor 1 Contractor System 1 Liquid Line Solenoid Valve Compressor 1 Unloader Solenoid Valve 1 Compressor 1 Unloader Solenoid Valve 2 Compressor 1 Hot Gas Bypass Sol. Valve Refrigeration System 2 Locked Out Compressor 2 Contractor System 2 Liquid Line Solenoid Valve Compressor 2 Unloader Solenoid Valve 1 Compressor 2 Unloader Solenoid Valve 2

0-100% 0-100%

0-100% 0-100%

0-open, 0-open, 0-local, 0-open, 0-open, 0-OA, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open,

1-made 1-made 1-remote 1-made 1-made 1-RA 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

33

NPA2 NPT1 (Cont.)


AO AO AO BO ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF 1 2 * 1* 2 3* 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Unit
DegF # DegC Min Hour Min # Hour Min # Code Code Code Code Code # # DegF DegF DegF psi psi

Description
Return Air Setpoint (10, 70) 0=Vent, 1=Heating, 2=Cooling, 3=Local Setpoints Return Air Setpoint (-12 to 21) Start/Stop Command Anti-Coincidence Timer Compressor 1 Run Hours Compressor 1 Anti-Recycle Timer Compressor 1 No. of Operating Stages Compressor 2 Run Hours Compressor 2 Anti-Recycle Timer Compressor 2 No. of Operating Stages Air Handling Unit Shutdown Code Compressor 1 Operational Code Compressor 1 Fault Code Compressor 2 Operational Code Compressor 2 Fault Code Number of Condenser Fans Running Cooling Load Steps Available Actual Heating Setpoint Actual Cooling Setpoint Actual Discharge Air Temperature Setpoint Actual Static Pressure Setpoint Actual Building Pressure Setpoint 0-stop, 1-start

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

34

Metasys IntegratorMetasys Integrator York Application

A1 Air-cooled Screw Chiller Master


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI14.

Table 15: A1 Air-cooled Screw Chiller - Master (XL Configuration only)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Unit
DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi %FLA psi psi psi %FLA % % DegF DegF DegF DegF psi psi DegF DegF

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Mixed Chill Water Temperature Compressor 1 Suction Temperature Compressor 1 Discharge Temperature Compressor 1 Saturated Suction Temperature Compressor 1 Saturated Discharge Temperature Compressor 1 Oil Temperature Compressor 2 Suction Temperature Compressor 2 Discharge Temperature Compressor 2 Saturated Suction Temperature Compressor 2 Saturated Discharge Temperature Compressor 2 Oil Temperature Outdoor Air Temperature Compressor 1 Suction Pressure Compressor 1 Discharge Pressure Compressor 1 Oil Pressure Compressor 1 Full Load Amperes Compressor 2 Suction Pressure Compressor 2 Discharge Pressure Compressor 2 Oil Pressure Compressor 2 Full Load Amperes Compressor 1 SVCALC % Compressor 2 SVCALC % Leaving Chill Water Setpoint Low Water Temperature Cutout Low Ambient Temperature Cutout High Ambient Temperature Cutout Low Pressure Cutout High Pressure Cutout Remote Temperature Setpoint Local Cooler Barrel Setpoint

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

35

NPA2 NPT1 (Cont.)


BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI AO AO AO BO ADF ADF ADF ADF ADF ADF 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 1* 2 3* 1 1 2 3 4 5 6

Unit

Description
Chiller Run 0-open, Chiller Alarm 0-open, Evaporator Heater 0-open, Evaporator Pump Starter 0-open, Comp 1 Liquid Line Solenoid Valve 0-open, Comp 1 Condenser Fan Reverse 0-open, Comp 2 Liquid Line Solenoid Valve 0-open, Comp 2 Condenser Fan Reverse 0-open, Switch 1 (0=Comfort Cooling, 1=Brine Cooling) Switch 2 (0=Standard Ambient, 1=Low Ambient) Switch 3 (0=Local, 1=Remote) Switch 4 (0=eev, 1=Thermal Expansion Valves) Switch 5 (0=English Units, 1=Metric Units) Switch 6 (0=x-Line Start, 1=wye delta start) Switch 7 (0=Manual Lead/Lag, 1=Auto Lead/Lag) Switch 8 (0=R134a, 1=R22) Load Permissive 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

1-made

DegF %FLA DegC

Leaving Chill Water Setpoint (10 to 70) Load Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop 0-stop, 1-start Compressor 1: Operational Code Fault Code Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Compressor 2: Operational Code Fault Code Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Master Anti-Coincidence Timer Lead Compressor

Code Code # Min Hour #

ADF ADF ADF ADF ADF ADF ADF ADF 1 2 *

7 8 9 10 11 12 13 14

Code Code # Min Hour # Min #

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

36

Metasys IntegratorMetasys Integrator York Application

A3 Air-cooled Screw Chiller Slave


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI14.

Table 16: A3 Air-cooled Screw Chiller - Slave (XL Configuration only)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI BI BI BI BI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 1 2 3 4 5 6 7 8 9

Unit
DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi %FLA psi psi psi %FLA % % DegF DegF DegF DegF psi psi DegF DegF

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Mixed Chill Water Temperature Compressor 3 Suction Temperature Compressor 3 Discharge Temperature Compressor 3 Saturated Suction Temperature Compressor 3 Saturated Discharge Temperature Compressor 3 Oil Temperature Compressor 4 Suction Temperature Compressor 4 Discharge Temperature Compressor 4 Saturated Suction Temperature Compressor 4 Saturated Discharge Temperature Compressor 4 Oil Temperature Outdoor Air Temperature Compressor 3 Suction Pressure Compressor 3 Discharge Pressure Compressor 3 Oil Pressure Compressor 3 Full Load Amperes Compressor 4 Suction Pressure Compressor 4 Discharge Pressure Compressor 4 Oil Pressure Compressor 4 Full Load Amperes Compressor 3 SVCALC % Compressor 4 SVCALC % Leaving Chill Water Setpoint Low Water Temperature Cutout Low Ambient Temperature Cutout High Ambient Temperature Cutout Low Pressure Cutout High Pressure Cutout Remote Temperature Setpoint Local Cooler Barrel Setpoint Chiller Run Chiller Alarm Evaporator Heater Evaporator Pump Starter Comp 3 Liquid Line Solenoid Valve Comp 3 Condenser Fan Reverse Comp 4 Liquid Line Solenoid Valve Comp 4 Condenser Fan Reverse Load Permissive 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made 1-made

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

37

NPA2 NPT1 (Cont.)


ADF ADF ADF ADF ADF ADF 1 2 3 4 5 6

Unit

Description
Compressor 3: Operational Code Fault Code Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Compressor 4: Operational Code Fault Code Condenser Fan Forward Anti-Recycle Timer Runtime Hours Number of Starts Master Anti-Coincidence Timer Lead Compressor

Code Code # Min Hour #

ADF ADF ADF ADF ADF ADF ADF ADF 1 2

7 8 9 10 11 12 13 14

Code Code # Min Hour # Min #

Network Point Type Network Point Address

38

Metasys IntegratorMetasys Integrator York Application

YI Isoflow Absorption Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Refrigerant Temperature point is AI8.

Table 17: YI Isoflow Absorption Chiller (XL Configuration only)


NPT1
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI 1 2

NPA2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

Unit
DegF DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi DegF DegF DegF DegF DegF DegF DegF DegF DegF DegF

Description
Leaving Chilled Water Temperature Entering Chilled Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Automatic Decrystallization Temperature Refrigerant Temperature Leaving the Condenser Steam/Hot Water Supply Temperature Refrigerant Temperature Strong Solution Temperature Generator Shell Pressure Steam Supply Pressure (Steam Units Only) Steam/Hot Water Actuator Value Position (0-100%) Local Leaving Chilled Water Setpoint Purge Pump Service Interval Setpoint - Hours Active Leaving Chilled Water Setpoint Remote Loading Setpoint Maximum Steam/Hot Water Valve Load Setpoint Pulldown Demand Setpoint - Minutes Pulldown Demand Setpoint -Start Load Limit Pulldown Demand Setpoint -Stop Load Limit Remote Temperature Range Setpoint Maximum Entering Condenser Water Temperature Setpoint

Network Point Type Network Point Address

Continued on next page . . .

Metasys IntegratorMetasys Integrator York Application

39

NPA2 NPT1 (Cont.)


BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI BI AO AO BO 1 2 * 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 1* 2* 1

Unit

Description
Chilled Water Pump Status 0-Off, 1-On Condenser Water Pump Status 0-Off, 1-On Refrigerant Pump Motor Status 0-Off, 1-On Solution/Absorber Pump Motor Status 0-Off, 1-On Purge Pump Motor Status 0-Off, 1-On Generator Pump Motor Status 0-Off, 1-On Refrigerant and Solution Pump Motor 0-Off, 1-On Coolant Solenoid Valve Status Refrigerant Stabilizer Solenoid Valve 0-Off, 1-On Status Refrigerant Level Solenoid Valve 0-Off, 1-On Status Chilled Water Flow Switch Status 0-Open, 1-Closed Condenser Water Flow Switch Status 0-Open, 1-Closed Refrigerant Level Float Switch Status 0-Open, 1-Closed Unit Switch Status 0-Stop, 1-Run J50 Status 0-AutoRe, 1-Manual J51 Status 0-LOA, 1-No_LOA J52 Status 0-Englsh, 1-Metric J54 Status 0-Limitd, 1-FullCn J55 Status 0-DiagEn, 1-DiaDis J57 Status 0-RTCDis, 1-RTCEnb J12 Status(Expansion I/O Board) 0-Englsh 1-German Dilution Cycle Status 0-Open, 1-Made Low Entering Condenser Water 0-No, 1-Yes Temp Limit Active Automatic Decrystallization Active 0-No, 1-Yes Remote Load Limiting Active 0-No, 1-Yes Pulldown Limiting Active 0-No, 1-Yes

DegF DegC

Leaving Chill Water Setpoint (10 to 70) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop 0-Stop, 1-Start

Network Point Type Network Point Address Points AO1 and AO2 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

Continued on next page . . .

40

Metasys IntegratorMetasys Integrator York Application

NPA2 NPT1 (Cont.)


ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF ADF BD BD BD 1 2 1 2 3 4 5 6 7 8 9 10 11 12 13 1 2 3

Unit
Mode Code Code Code Code Hour # # # Min # Code DegF

Description
Operational Mode (0-Service, 1-Local, 2-Remote) Operational Code Safety Shutdown Code Cycling Shutdown Code Warning Message Code Total Operating Hours Total System Starts Lifetime Purge Count Weekly Purge Counter Pulldown Demand - Minutes Left Pulldown Demand - Present Limit Dilution Cycle Code Maximum Steam/Hot Water Valve Unload Setpoint JP1 Status JP3 Status JP1 (Expansion I/O Board) 0-Steam, 0-Stndrd, 0-Rotary, 1-Hwater 1-50Hz 1-Cage

Network Point Type Network Point Address

Metasys IntegratorMetasys Integrator York Application

41

YG Gas Engine Drive Chiller


To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA (Network Point Address). For example, the hardware reference for the Engine Speed point is AI15.

Table 18: YG Gas Engine Drive Chiller (XL Configuration only)


NPT1 NPA2
AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI AI BI BI BI BI BI AO AO AO BO 1 2 * 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 1 2 3 4 5 1* 2 3* 1 DegF %FLA DegC

Unit
DegF DegF DegF DegF DegF DegF DegF DegF psi psi psi % % DegF rpm psi psi psi psi DegF % mils mils DegF rpm

Description
Leaving Chill Water Temperature Entering Chill Water Temperature Leaving Condenser Water Temperature Entering Condenser Water Temperature Evaporator Saturation Temperature Condenser Saturation Temperature Discharge Temperature Oil Temperature Evaporator Pressure Condenser Pressure Oil Differential Pressure Percent Engine Load Percent Vanes Open Engine Jacket Water Temperature Engine Speed Engine Oil Pressure Engine Manifold Pressure Low Oil Transducer Pressure High Oil Transducer Pressure Leaving Water Temperature Actual Setpoint Remote/Local Actual Engine Load Setpoint Proximity Sensor - Actual Position Proximity Sensor - Reference Position Drain Line Thermocouple Temperature Delta P over P Surface Speed Engine Panel Shutdown Status Vent Valve Status Chilled Water Pump Status Start Switch Status Chilled Water Flow Switch Status Leaving Chill Water Setpoint (10 to 70) Demand Limit Setpoint (50 to 100) Leaving Chill Water Setpoint (-12 to 21) Chiller Start/Stop 0-stop, 1-start 0-open, 0-open, 0-open, 0-open, 0-open, 1-made 1-made 1-made 1-made 1-made

Network Point Type Network Point Address Points AO1 and AO3 are the same point and will have the same value. Two points are provided because of the different ranges for DegF and DegC.

Continued on next page . . .

42

Metasys IntegratorMetasys Integrator York Application

NPA2 NPT1 (Cont.)


ADF ADF ADF ADF ADF ADF ADF ADI 1 2 3 4 5 6 7 1

Unit
Min Code Code Code Code Hour # Code

Description
Anti-Recycle Time Left Operating Mode Operation Code Safety Shutdown Code Cycling Shutdown Code Accumulated Operating Hours Accumulated System Starts Engine Type 0-G3408, 1-G3412, 2-G3508, 3-G3512, 4-G3516, 5-G3606

1 2

Network Point Type Network Point Address

Metasys IntegratorMetasys Integrator York Application

43

44

Metasys IntegratorMetasys Integrator York Application

Metasys Network Setup


Metasys Network setup is described in the Metasys Integrator technical bulletins in the Metasys Connectivity Technical Manual (FAN 629.5). This section contains details specific to York applications. Mapping to a CS Object Table 19: Software Model and CS Object Details
Application Software Model
(on Tables and Models CD-ROM) Login YT Chiller YK Chiller YS Chiller LS Chiller YP Chiller C1 Chiller C3 Chiller B1 Chiller B3 Chiller YR Chiller A1 Chiller A3 Chiller YI Chiller YG Chiller * YK_TRAN.DDL YK_YTCH.DDL YK_YKCH.DDL YK_YSCH.DDL YK_LSCH.DDL YK_YPCH.DDL YK_C1CH.DDL YK_C3CH.DDL YK_B1CH.DDL YK_B3CH.DDL YK_S3000.DDL YK_A1XL.DDL YK_A3XL.DDL YK_YIXL.DDL YK_YGXL.DDL

Display Attribute
(recommended) BI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1 AI1

NT Command Attribute
(recommended) BI1* BO1 BO1 BO1 BO1 BO1 BO1 BI1* BO1 BI1* BO1 BO1 BI1* BO1 BO1

The NT Command attribute must be defined; it cannot be null. However, since the points are not commandable, you will not be able to command the attribute.

Metasys IntegratorMetasys Integrator York Application

45

46

Metasys IntegratorMetasys Integrator York Application

Custom Integration
For information on integrating products that are not discussed in this document, first refer to the Metasys Compatible Global Catalog, an online list of released Connectivity products. If this list does not provide the information you require, consider using the System Integration Project Data Sheet to request a custom contract from the System Integration Team. Both the Metasys Compatible Global Catalog and the System Integration Project Data Sheet can be accessed from The Advisor by performing the following steps: 1. 2. 3. 4. 5. Click on the Systems Products button located on the left side of The Advisor home page. Click on the Product Literature link. Click on the Manuals-FANS link. Click on the 629.0 Metasys Connectivity Sales Resource Manual link. Find the System Integration Project Data Sheet link in the table of contents. Click on this link to view an online copy of the System Integration Project Data Sheet, or click on the Metasys Compatible Global Catalog link below it to view a list of released Connectivity products.

The System Integration Project Data Sheet (LIT-6290052) also can be found in the Metasys Connectivity Sales Resource Manual (FAN 629). If you need further assistance, contact Johnson Controls Field Support Center.

Metasys IntegratorMetasys Integrator York Application

47

Notes

Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201

www.johnsoncontrols.com FAN 629.5 Metasys Connectivity Technical Manual Metasys Integrator Release 9.0 Printed in U.S.A.