. MINIMONO/485 . MINIMONO/IP
User Manual
MINIMONO
THANK
YOU
& CONGRATULATIONS:
Thank you for purchasing the modular controller MINIMONO. This device is a Media Bus Control automation controller that can be configured according to your needs. This manual is meant for helping you in its installation.
The information in this manual is copyright protected. No part of this manual may be copied or reproduced in any form without prior written consent of VITY Technology Headquarters France. VITY Technology is not responsible for operational, technical or editorial errors/omissions made in this manual. All the information in this manual may be subject to change without prior notice. MINIMONO and Media Bus Control are registered trademarks of VITY Technology. All other brand or product names are trademarks of their respective companies or organizations.
NUMRO
DE RVISION DU MANUEL:
MINIMONO_EN_0001
2/49
MINIMONO INDEX
1 About this manual.........................................................................................................4 2 Controller presentation.................................................................................................4 3 Material description......................................................................................................5 3.1 Visualization (frontside of the controller).....................................................................5 3.2 Connections (backside of the controller).....................................................................6 3.3 External dimensions.................................................................................................7 4 Installation and Configuration......................................................................................8 4.1 4.2 4.3 4.4 4.5 5.1 5.2 5.3 5.4 5.5 5.6 Configuration of MBC Bus address...........................................................................8 MBC Bus communication port.................................................................................9 Ethernet network port (only with MINIMONO/IP)........................................................10 Power supply.........................................................................................................12 InfraRed learning and internal IR sensor...................................................................13 External InfraRed sensors.......................................................................................14 Logic inputs...........................................................................................................15 Relays outputs.......................................................................................................16 InfraRed outputs....................................................................................................18 X10......................................................................................................................19 RS232 Serial ports.................................................................................................20 (MINIMONO/485 & MINIMONO/IP)..........................................22 (MINIMONO/IP ONLY).....................................25
6 Update by RS232
7.1 Software view........................................................................................................26 7.2 Basics Functions....................................................................................................27 7.2.1 Devices upgrade............................................................................................27 7.2.2 Upgrade Web Server files...............................................................................30 7.2.3 Change device parameters.............................................................................31 7.2.4 Change Web Server secure access...................................................................33 7.3 Advanced Functions...............................................................................................34 7.3.1 Restore factory settings..................................................................................34 7.3.2 MBC Architecture...........................................................................................36 7.3.3 Tests of devices.............................................................................................37 7.3.4 View Ethernet traffic......................................................................................38 7.4 Others possibilities and functions.............................................................................39 7.4.1 Watch the configuration Web site of LAN configuration.......................................39 7.5 Open firewall in Windows XP.................................................................................42 7.6 Frequency Asked Questions.....................................................................................44 7.7 Installation of Ethernet/MBC Bus gateways and Webserver.........................................45 7.8 Create a WebServer...............................................................................................46 7.9 Create PctoMaty applications and upload new files.....................................................46 7.10 Launch the WebServer across the Internet..............................................................47 8 Technical specifications..............................................................................................48 9 Compatible brands with MediaBus Control automation system..................................49 10 Warranty...................................................................................................................50
3/49
MINIMONO
1 ABOUT
THIS MANUAL
Please read this manual carefully before installing the MINIMONO. The manufacturer will not be responsible for any damage or accidents caused by the use, even correct of its products. The data and features of the product may change without prior notice.
Used signs : Notes : These parts contents information about materials and important warnings.
Technical tips : These parts are treating about material installation and method for devices use.
2 CONTROLLER
PRESENTATION
MINIMONO is a home automation controller that enables to control many devices using buses and varied protocols. This controller receives and emits data via the MBC Bus proprietary bus or a LAN connection. Thanks to the ZIG ACCESS or Wifi access points, it can also be controlled by Zigbee (VIMATY70ZR screen) or WiFi (Tactum CE screen). MINIMONO can also work with some limitations, in stand-alone mode. In that case, no remote control (touch pannel, keyboard, computer, ...) is necessary. Actions are triggered by dry contacts or infrared codes.
MINIMONO exists in 2 versions : Minimono/485 : the device has a MBC Bus proprietary bus and a RS232 port for the upgrades. Minimono/IP : the device has a LAN connection and a MBC Bus proprietary bus. The upgrade is made by LAN.
4/49
MINIMONO
3 MATERIAL
DESCRIPTION
Status led and Media Bus activity (Bus/Learn) Reset button IR Sensor
5/49
MINIMONO
2 RS232 ports X10 4 GPI inputs 6 Infra Red outputs 6 relays outputs 2 Infra Red inputs 2 Media Bus connectors 1 power supply connector
The backside of the controller have an integrated tab, which allows cables support.
6/49
MINIMONO
44 mm
326 mm 120 mm
7/49
MINIMONO
4 INSTALLATION
AND
CONFIGURATION
It is possible to connect up to 16 MINIMONO on the MBC Bus at the same time. Selection of the address according to the dipswitches :
Adresse 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Dipswitch 1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF Dipswitch 2 ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF Dipswitch 3 ON ON ON ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF Dipswitch 4 ON ON ON ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF
When all switches are OFF, the controller is in emergency upgrade mode. The status led must blink quick. MINIMONO default address is 1.
8/49
MINIMONO
Communication features: Speed : 115200 Bauds Data length : 8 bits Parity : aucune Stop bit length : 1 maximal physical length : 1000 meters. Connector : Reference : MC1,5/3-ST-3,81 (Phoenix Contact) Cable section : 0,08 -1,5 mm2 (AWG : 28 -16). Quantity : 2 Connector wiring :
Terminal 1 2 3 Signal Tx/Rx+ Tx/RxGND
3 2 1
The "Bus/Learn" Led indicates the transit of the MBC Bus command.
Respect the polarity of the bus. In most of cases, the ground signal (GND) is not needed to ensure the communication. If there is problem of communication (such as parasites), wire the shield of the cable only in one of its side.
9/49
MINIMONO
Communication features : Speed : 10/100 MBits/s UDP/IP and TCP/IP protocols on port 12000 Connector : RJ45 female Connector wiring :
Terminal 1 2 3 4 5 6 7 8 Rx 87654321
Signal Tx + Tx Rx +
10/49
MINIMONO
Donk link 2 Minimono/IP at the same time to the same MBC Bus bus and to the same Ethernet network.
Tactum Switch/Hub Ethernet MBC Bus
MINIMONO 1
MINIMONO 2
Tactum
Switch/Hub
MINIMONO 1
MINIMONO 2
Tactum
Switch/Hub
MINIMONO 1
MINIMONO 2
To connect a Minimono/IP to a Switch/Hub, you have to use a straight cable. To connect a Minimono/IP directly to a PC, you have to use a cross cable (see following pictures). The cable used must be a 4-CAT5 twisted pair cable.
MINIMONO/IP and SWITCH/HUB (straight cable) Side A 1 2 3 4 5 6 7 8 Side B 1 2 3 4 5 6 7 8 MINIMONO/IP and PC (cross cable) Side A 1 2 3 4 5 6 7 8 Side B 3 6 1 4 5 2 7 8
11/49
MINIMONO
Connector : Cable section : 0,08 -1,5 mm2 (AWG : 28 -16) Reference : MC1,5/2-ST-3,81 (Phoenix Contact) Connector wiring :
Terminal 1 2 Signal GND +12Vdc
2 1
When the controller is power on, the "status" led blinks continuously, to indicate good working of the controller. If the led fixes (ON or OFF), there is a problem on the controller. Please reboot it.
12/49
MINIMONO
The integrated IR sensor (IR Sensor) is on the left in the frontside of the controller. Range : From 10 to 40 cm between the remote control and the sensor. Angle : 60 The internal IR sensor (Sensor) or the external sensor n2 works in the same way as the infrared sensor of the basic box. You can use either for the infrared codes learning. So the led "IR IN 2" blinks when an InfraRed code is capted by the IR sensor. When a RC5 code is received, either Minimono sends the information to the MBC Bus. bus, or it triggers an action associated to the code if it is in stand-alone mode. Learning procedure : 1. Set the device in learning mode by using the free downloadable IRDump software on our website www.vity.com 2. For a correct learning of the infrared codes, it is preferable to use the Normal learning mode. This mode makes it possible to control the measurements taken before validating them. This learning mode is more protected than the Forced mode which accepts all taken measurements. 3. In learning mode, the led "Bus/Learn" lights. From this moment, you can send the infrared codes by placing the remote control at between 10cm and 40 cm from the IR Sensor . 4. If you are in normal learning mode, press the remote button until the led goes down. In forced learning mode, press quickly the button. 5. The end of the learning is indicated by 5 flickering of the led Bus/Learn of the MINIMONO.
13/49
MINIMONO
5 EXTERNAL
DEVICES CONNECTION
The led "IR IN" n1 blinks when an infrared code is received on the port n1. The led "IR IN" n2 blinks when an infrared code is received on the port n2. The infrared input sensor number 2 is in parallel with the internal sensor. One can thus also learn the infrared codes by the external sensor number 2 via an external infrared receiver.
14/49
MINIMONO
Features of a logic input : Max. voltage: 30 V Min. voltage : 0 V Max. VIL = 0,5V Minimum delay of a state modification : 50 ms Connector : Cable section : 0,08 -1,5 mm2 (AWG : 28 -16) Reference : MC1,5/2-ST-3,81 (Phoenix Contact) Connector wiring :
Terminal 1 2 Signal GND In
2 1
15/49
MINIMONO
These outputs are isolated from the power supply of the MINIMONO.
Three types of actions can be done: the opening of the relay the closing of the relay the generation of a click of 100ms (Closing during 100ms then opening of the relay). Caractristiques de la sortie contact sec : SPST relay, contact normally open Contact impedance : 100 mOhm Max. voltage : 36V Max. intensity : 1A Connector : Cable section : 0,08 -1,5 mm2 (AWG : 28 -16) Reference : MC1,5/2-ST-3,81 (Phoenix Contact) Connector wiring :
Terminal 1 2 Signal C1 C2
2 1
16/49
MINIMONO
Use for higher voltages than 36V : The voltage commutation of sector by the dry contacts outputs of the MINIMONO implies the use of the KRT power relay. In this case, it is necessary to use these outputs as on the diagram below.
Neutre
220V 220V
The12V is is supplied by an power The 12V supplied by an extern external power supply supply
+12V COM
KRT relay Relais de puissance de type KRT Dry contact output of the Relay output minimono MINIMONO MINIMONO
Relay
NC
NO
COM NC NO
Lamp Lampe
Relais
17/49
MINIMONO
Characteristics : Output impedance of each channel : 100 ohms. Connector : jack 3,5mm stereo or mono Connector wiring :
Terminal 1 2 3 Signal GND GND IR OUT
1 2 3
18/49
The controller Minimono enables to control device by X10 powerline bus. Need X10 interface (ref : XM10E)
Characteristics : Output impedance of each channel : 100 ohms. Connector : RJ12 connector 6 pins socket. The crossed cable RJ12 is delivered with the interface.
19/49
MINIMONO
Port 1 allows the programming of the standalone mode as well as the updates of the firmware. We advise to reserve this port for this function. However if this port is used by the customer application, the programming mode can be forced using the switches located under the MINIMONO (For that, set all the switches to OFF).
Communication features : Rate : Baudrate Port 1 Port 2 300 600 1200 2400 4800 9600 19200 38400 57600 115200
Parity : none pair - odd Bit number / character : 5 bits 6 bits 7 bits - 8 bits Stop bit length: 1 bit 1,5 bit 2 bits
20/49
MINIMONO
Connector wiring :
Terminal 1 2 3 4 5 6 7 8 9 RTS CTS GND
9 6
Signal (RS232)
Rx Tx
5 1
When datas are received or emitted on serial port, the led "RS232" blinks.
21/49
MINIMONO
The "setup" window allows you to choose the RS232 port (generally called serial port) of the computer which should be use for the upgrade.
Click on the "Update" button. The software asks you for the file of update. This file type is ".mno".
The software asks you for the configuration which should be use for the update.
By default, the configuration is : 115200 Bauds / 8bits / None / 1. If it does not work, try : speed = 9600 Bauds.
22/49
MINIMONO
The software converts the file then sends it to the controller Minimono.
23/49
MINIMONO
The firmware update is done by the searching and updating software called : "PCtoLAN". This software allows you to : find VITY TECHNOLOGY's devices like VITYLAN, MINIMONO/IP MAXIMONO/IP and MULTICUSTOM/IP and watch all their parameters (network, firmware, connected controllers ...) update the firmware of these devices change network configuration, name and switch between Ethernet/MediaBus gateway mode and WebServer mode modify the password for the WebServer Connection restore factory settings watch all VITY's controllers connected to the IP devices test the controllers communication see the Ethernet traffic generated by the devices Warning : This software needs an other network configuration than the one used in the first version of VITYLAN/LAN option. To provide weel working, and upload all the new files (including the JAVA Webserver core), you must do a factory restoration on the olds materials, before doing a firmware update (see chapiter 1.2.5. for more information) All these functions (except firmware update) are activated only with firmware 2.0.0 or greater of the VITYLAN/LAN option. Update a firmware from 1.x.x version to 2.x.x need a BIOS upgrade. If the software detect this requirement, it will do that automatically before the 2.x.x upgrade. The BIOS upgrade is a critical operation. BE CAREFUL ! If power supply is disconnected during this operation, the device will be definitely damaged. The MINIMONO LAN upgrade by network is possible only from 1.0.6 MINIMONO firmware version. Please update first the device with this firmware by RS232 before using this feature (see MINIMONO update software documentation for more information). All operations accessible with this software are accessible only across the local network (Ethernet).
24/49
MINIMONO
25/49
MINIMONO
BE CAREFUL : Update a firmware from 1.x.x version to 2.x.x need a BIOS upgrade. If the software detect this requirement, it will do that automatically before the 2.x.x upgrade. The BIOS upgrade is a critical operation. If power supply is deconnected during this operation, the device will be definitly damaged.
Note : The MINIMONO/IP upgrade by network is possible only from 1.0.6 MINIMONO firmware version. Please update first the device with this firmware by RS232 before using this feature (see MINIMONO update software documentation for more information).
If you have set the controller in forced upgrade mode, you need to check "Forced mode" and to choose the kind of controller you want to upgrade.
26/49
MINIMONO
Select the file which contains the firmwares (PCtoLAN_firmwares_x.x.x. upg in this case) then click on "Open". If the device is a VITY TECHNOLOGY controller, it is upgraded first. Else, the software goes directly to step 9.
4 5 6 7 8 9 10
Note : If the firmware of the Vitylan / MinimonoLAN / MulticustomLAN is older than 2.0.0, the BIOS of the device will be upgraded first. The software extract and converts the firmware file of the controller.
Click on "Yes" or "No" depending to the current version and the upgrade version of the controller.
If you have click on "Yes", the firmware is uploaded onto the controller, else the software goes directly to step 9.
Click on "Yes" or "No" depending to the current version and the upgrade version of the VITYLAN/LAN option.
27/49
MINIMONO
11 12 13
If you have click on "Yes", the firmware is uploaded onto the VITYLAN/LAN option, else the software ends.
28/49
MINIMONO
2 2 3 4 5
This operation needs the same files as the parameters restoration. This file is called PctoLAN_factory_settings_ x.x.x.fact. Select it and click on open.
29/49
MINIMONO
30/49
MINIMONO
Network configuration : Change "New IP address", "New subnet mask" and "New gateway" The SerialPort is the IP address which will be used to send VITY Technology communications. The software will automatically fill this address, but if you need you can enter manually this parameter. Change name : Check "New device name" Enter the new name. Switch working mode : Check the right "Working mode" Click on "OK". case on
3 4 5 6
If you have changed the name of the device, you need to open the file which contains the configuration files ("PCtoLAN_factory_settings_x. x.x.fact" in this case). Select it and click on open.
The software upload the new file and set the new parameters on the device.
31/49
MINIMONO
On the window appearing, enter the current security access codes and the new ones. The minimal length of the username and password is 4 caracters. Click on "OK".
3 4 5
The software upload the new file and set the new parameters on the device.
32/49
MINIMONO
After that, you must re-parameter your device. This manipulation activate the TCP protocol too, which allows you to use the WebServer mode and provides a better security when firmwares are updated. So it is necessary to execute this task on old device before the first firmware update, else all others tasks will not be accessible. Moreover, this task will upload the JAVA WebServer core files.
2 3
This operation needs a file called PctoLAN_factory_settings_ x.x.x.fact. Select it and click on open.
The software upload the new file. This operation may take 10 minutes.
33/49
MINIMONO
4 5
34/49
MINIMONO
A window appears.
All VITY's controllers and remotes are listed in a treeview. On each node, you can see the IP device, and all devices connected to it.
35/49
MINIMONO
A window appears. On this window, you need to indicate the MBC address. If the device is a Multicustom/IP, you need to indicate the slot for the Relays card and the Digital feedback card too.
36/49
MINIMONO
A window appears.
Click on "Stop capture" if you want to suspend the scan of Ethernet communications. Click on "OK" to quit.
37/49
MINIMONO
Open a WEB browser. Enter the IP address of the device. Exemple : Http://192.168.0.142/home.htm
open
Enter the current username and password (by default admin and 1234).
38/49
MINIMONO
link
"Update
Go in the folder where you have installed the PctoLAN software (by default C:\program files\vity\PCtoLAN\) and select :
- if you have a LAN card with 2Mo of memory : 82000867_G_post_2mb.bin - if you have a LAN card with 4Mo of memory : 82001229_c_post_4mb.bin then click on "OK".
39/49
MINIMONO
Do this operation a second time but : - if you have a LAN card with 2Mo of memory select : 82001116_h_firmware_2mb_ .bin - if you have a LAN card with 4Mo of memory select : 82001120_h1_firmware_4mb .bin
40/49
MINIMONO
Open the Advanced tab and click on Parameters, then in the new window open the Exceptions tab and click on Adding a port :
41/49
MINIMONO
In the window appearing, enter the following parameters : Name : VityLAN Number of port : 12000 Notch UDP
Do the same but notch TCP instead of UDP. Finally click on OK.
42/49
MINIMONO
The device does not appear in - The device is configured on a subnet totally different to the the list. computer one. The only way to know its IP address is to scan Ethernet communication (with "Ethereal" for example) during clicking on "Refresh view" button of the updating software. The device will answer, then take its IP address and configure the computer on the same subnet to make a full restoration. - The network materials (such as routers, switch and hub) blocks Multicast communications. Configure these materials to accept these communications. - The device is not correctly plug to the network or to the power supply. Check connections. The device appears in the list - The device firmware is down to 2.0.0. Update it but the line is red and the - The device is not well configure on its "serial port". See firmware version is "x.x.x" chapiter 1.4. - The device is on WebServer mode and a session is active. Shut it down. - The device is configured on a subnet a little different from the computer one. This blocks the communication but not the detection. Modify the network configuration of the computer or the device. - Two devices have the same IP address. Change one of these. - An other software uses the same Ethernet protocol on the computer. Shut it down (IRDump, PC2Maty ...). - The network materials (such as routers, switch and hub) blocks Multicast communications. Configure these materials and all firewalls to accept these communications. The device appears in the list - The last uploaded firmware is more recent than the one in but the line is red. the device. Upgrade the device. The software print "Socket - The device is on WebServer mode and a session is active. error" when a firmware upgrade. Shut it down. - The MediaBus is saturated by communications. Try several times to do establish the connection. If it does not work, unplug all devices except the one you want to update then try again to update. The device does not accept a - The device automatically checks if the IP address is accorded new IP address. to the subnet mask and the gateway. Be careful about all parameters. - If the software seems to have problem to comunicate with the device, try to do this operation by the Website of configuration. See chapter 1.3.1 for more details.
43/49
MINIMONO
Gateway 1
Ethernet IP 1
Group of products 2
MBC Bus 2
Gateway 2
Ethernet IP 2
Group of products x
MBC Bus x
Ethernet IP x
Gateway x
2 - WebServer only
Ethernet Local network
Group of products
MBC Bus
WebServer
Ethernet IP 1
Router + Modem
Internet IP
Internet
44/49
MINIMONO
3 - WebServer + Passerelles
Group of products 1
MBC Bus 1
Gateway 1
Ethernet IP 1 Ethernet Local network
Group of products 2
MBC Bus 2
Gateway 2
Ethernet IP 2
Internet IP
Router + Modem
WebServer
Ethernet IP 3
Internet
Group of products x
MBC Bus x
Ethernet IP x
Gateway x
The application upload to Minimono/IP WebServer is a Vitmay 35 application with restrictions : special options depending of the Vimaty hardware cannot be used (JPI input, IR receiver, ect...). The file upload to Websever cannot have a size bigger than 200ko (avois to use background for screen because picture take lot of memory space).
45/49
MINIMONO
Create a Vimaty 35 application and take in count the restriction... Compile your project as you did with Vimay's and check the VityLAN Websever options into the dialog box.
When compilation is finished, Pctomaty ask you to select the VityLAN Webserver you want to upload... It's possible to enter a specific address if you VityLAN don't appear into the list (attention it's possible that your VityLAN is not into because of network mismatch between your computer network configuration and the VityLAN configuration. You can refresh the list with Refresh button or reboot a VityLAN Webserver by clicking the reboot button to unlock a bad situation. Click OK and wait during upload...
46/49
MINIMONO
8 TECHNICAL
SPECIFICATIONS
General characteristic : Power supply : 12 Volts DC / 4A delivered with the device. Size : 326,00 mm x 44,00 mm (1U) x 120,00 mm (without corner plates). External connector power supply: MC1,5/2-G-3,81 (Manufacturer : Phoenix Contact) Protection by polyswitch. 19" rack mounting kit inclued. Standalone working mode possible. Interfaces : 6 InfraRed outputs on female stereo or mono 3.5mm jack. 2 InfraRed inputs on female stereo 3.5mm jack. 2 RS232 ports (2 compatibles with RS485 and RS422). 6 relays SPST NO (1A 36V max). 4 logical inputs. Media Bus communication bus : Half duplex Bus (RS485). Communication rate : 115200 bauds. Communication parameters : 8 data bits / character, 1 stop bit ,no parity Maximal physical bus length : 1000 meters. Connector : MC1,5/3-G-3,81 (Manufacturer : Phoenix Contact) Ethernet (MINIMONO/IP only) : 10/100 Mbps. UDP ans TCP protocol. Port used : 12000 in emission and reception. connector : RJ45.
47/49
MINIMONO
9 COMPATIBLE
BRANDS WITH
MEDIABUS CONTROL
AUTOMATION SYSTEM
The MEDIA BUS CONTROL automation systems are compatible with many audiovisual equipment, lighting and EIB-KNX manufacturers. You will find below the main compatible major brands, but Media Bus Control obviously doesn't restrict itself to them...
3M, ABB, Adtec, Akg, AllenHeath, Analogway, Ask, Autopatch, Barco, Behringer, Biamp, Canon, Clipsal, CommTec, DIS, Epson, Extron, Faroudja, Fostex, Gyra, Hager, Imerge, Jung, JVC, Kenwwod, Knox, Kodak, Kramer, Legrand, Lexicon, Lightec, Lite Touch, Lutron, Meridian, Merten, Mitsubishi, Nec, Niko, Onkyo, Panasonic, Phillips, Pioneer, Pixelmagics, Proxima, RGB Spectrum, Samsung, Sennheiser, Siemens, Sharp, Sony, Tasca, Theben, Vigatec, Vity, Xantech, Yamaha, Zumtobel... and more
48/49
MINIMONO
10 WARRANTY
1. VITY warranty. VITY Technology France, headquarters, 180 Rue Pierre Landais, 56850 CAUDAN - France, and its subsidiaries VITY China and Vity USA warrant that MINIMONO will be free of defects in materials and manufacture at the time of sale and will remain in good working order for a period of 2 years following the date of the original sales invoice from VITY. This warranty refers to the products manufactured by VITY. A return materials authorization is necessary before reshipping a product. This authorization is available via the Internet site of VITY http://www.vity.com/ and must be sent by fax to VITY : 02 97 89 20 10. On the other hand, if it's a product distributed by VITY, the applying warranty is that of the constructor.Its term may vary according to the present warranty and may therefore last more or less than 2 years. This waranty will be clearly specified during the sale. Minimono is warranted for 2 years. 2. What the warranty doesn't cover.
This warranty does not apply to (a) any VITY product that has been modified, altered or repaired by an unauthorized agent or improperly transported, stored, installed, used, or maintained; (b) damage caused by acts of nature, including flood, erosion, or earthquake; (c) damage caused by a sustained low or high voltage situation or by a low or high voltage disturbance, including brownouts, sags, spikes, or power outages; or (d) damage caused by war, vandalism, theft, depletion, or obsolescence. 3. Disclaimer and other warranties.
The warranties contained in Section 1 are the exclusive warranties given by VITY and supersede any prior, contrary or additional representations, whether oral or written. Vity disclaims and excludes all other warranties whether express, implied, or statutory. 4. Buyer's exclusive remedies for any nonconformity.
If a VITY product fails to conform to the warranties in Section 1, Buyer must notify VITY within a reasonable time and in no event more than thirty (30) days after the discovery of the nonconformity, and VITY will repair any nonconforming products or components. 5. Application of the warranty.
During the period of warranty, VITY Technology will repair the defective units free. The defective products must be sent to your expenses to the Vity Technology's buildings at Caudan with a note of accompaniment. The repaired units will be turned over to our expenses with the recipient. Apart from the period of warranty, VITY Technology will repair the defective units in its buildings at Caudan, and the cost of repair will be the responsibility of the customer. In the case of the product was bought to a Vity subsidiary or a Vity distributor, it must be returned to the subsidiary or the distributor before. 6. Exclusion of consequential and incidental damages.
Vity shall be not liable under any circumstances for consequential or incidental damages including, but not limited to, labour costs or loss of profits arising in connection with the use of or the inability to use Vity products. 7. Transport damage.
VITY will not be responsible for items damaged during shipment to or from VITY. The shipping carrier is responsible for items damaged during shipment. 8. No Modifications.
This warranty may not be modified except in writing by an authorized VITY officer. 9. Other notice.
VITY reserves the right to modify or discontinue designs, specifications, warranties, prices and polices without prior notice.