Sie sind auf Seite 1von 23

Undergraduate Lecture Notes on

Robust Control

Joo P. Hespanha a

April 1, 2007

Disclaimer: This is a draft and probably contains several typos. Comments and information about typos are welcome. Please contact the author at (hespanha@ ece.ucsb.edu).

c Copyright to Joo Hespanha. Please do not distribute this document without the authors a consent.

Contents
1 Robust stability 1.1 Model uncertainty . . . . . . . . 1.1.1 Additive uncertainty . . . 1.1.2 Multiplicative uncertainty 1.2 Nyquist stability criteria . . . . . 1.2.1 The Nyquist Plot . . . . . 1.2.2 The Nyquist criterion . . 1.3 Small-Gain . . . . . . . . . . . . 1.4 MATLAB hints . . . . . . . . . . 1.5 Exercises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . 3 . 4 . 5 . 6 . 7 . 7 . 8 . 11 . 12 13 13 14 16

2 Control design by loop-shaping 2.1 The loop-shaping design method . . . . . . . . . . . . . . . . . . . . . . . . . 2.2 Open-loop vs. closed-loop specications . . . . . . . . . . . . . . . . . . . . . 2.3 Exercises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Attention! When a margin sidebar nishes with . . . , more information about the topic can be found at the end of the lecture in the To probe further section.

ii

Joo P. Hespanha a

Introduction to Robust Control


For controller design purposes it is convenient to imagine that we know an accurate model for the process, e.g., its transfer function. In practice, this is hardly ever the case: 1. When process models are derived from rst principles, they always exhibit constants that can only be determined up to some error. E.g., the precise values of masses, moments of inertia, and friction coecients in models derived from Newtons laws; or resistances, capacitances, and gains, in electrical circuits. 2. When one identies a model experimentally, noise and disturbances generally lead to dierent results as the identication experiment is repeated multiple times. Which experiment gave the true model? The short answer is none, all models obtained have some error. 3. Processes change due to wear and tear so even if a process was perfectly identied before starting operation, its model will soon exhibit some mismatch with respect to the real process. The goal of this chapter is to learn how to take process model uncertainty into account, while designing a feedback controller. Pre-requisites 1. Laplace transform, continuous-time transfer functions, frequency responses, and stability. 2. Classical continuous-time feedback control design using loop-shaping. 3. Knowledge of MATLAB/Simulink.

Joo P. Hespanha a

Lecture #1

Robust stability
Contents 1.1 1.2 1.3 1.4 1.5 Model uncertainty . . . Nyquist stability criteria Small-Gain . . . . . . . MATLAB hints . . . . . Exercises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 . 6 . 8 . 11 . 12

1.1

Model uncertainty

k b m u

Suppose we want to control the spring-mass-damper system in Figure 1.1, which has the
Measuring the mass vertical position y with respect to the rest position of the spring, we obtain from Newtons law: m = by ky + u y

Figure 1.1. Spring-mass-damper system.

following transfer function from the applied force u to the spring position y P (s) = ms2 1 . + bs + k (1.1)

Typically, the mass m, the friction coecient b, and the spring constant k would be measured experimentally (or taken from some specications sheet) leading to condence intervals for these parameters and not just a single value: m [m0 1 , m0 + 1 ], b [b0 2 , b0 + 2 ], 3 k [k0 3 , k0 + 3 ].

PSfrag replacements

Joo P. Hespanha a

The values with subscript 0 are called the nominal values for the parameters and the i are called the maximum deviations from the nominal value.
Matlab hint 1. bode(sys) draws the Bode plot of the system sys. . .

In practice, this means that there are many admissible transfer functions for the processone for each possible combination of m, b, and k in the given intervals. Figure 1.2 shows the Bode plot of (1.1) for dierent values of the parameters m, b, and k. The idea
20 10 0 Magnitude (dB) 10 20 30 40 50 60 0 45 Phase (deg) 90 135 180 1 10 Bode Diagram

10 Frequency (rad/sec)

10

Figure 1.2. Bode plot of P (s) = k [2, 3].

1 , ms2 +bs+k

for dierent values of m [.9, 1.1], b [.1, .2], and

behind robust control is to design a single controllers that achieves acceptable performance (or at least stability) for every admissible process transfer function.

1.1.1

Additive uncertainty

In robust control one starts by characterizing the uncertainty in terms of the process frequency response. To this eect on selects a nominal process transfer function P 0 (s) and, for each admissible process transfer function P (s), one denes: a (s) := P (s) P0 (s), (1.2)

which measures how much P (s) deviates from P0 (s). This allows us to express any admissible transfer function P (s) as in Figure 1.3. Motivated by the diagram in Figure 1.3, a (s) is called an additive uncertainty block. P0 (s) should correspond to the most likely transfer function, so that the additive uncertainty block is as small as possible. In the example above, one would typically choose P0 (s) = m0 s2 1 . + b0 s + k 0

To obtain a characterization of the uncertainty purely in the frequency domain, one needs to specify how large a (j) may be for each frequency . This is done by determining a

Robust Control
P (s) a (s) := P (s) P0 (s)
+

PSfrag replacements u

a (s) P0 (s)

y P (s) = P0 (s) + a (s)

Figure 1.3. Additive uncertainty

function we have

a ()

suciently large so that for every admissible process transfer function P (s) |a (j)| = |P (j) P0 (j)|
a (),

When one has available all the admissible P (s) (or a representative set of themsuch as in Figure 1.2), one can determine a () by simply plotting |P (j) P0 (j)| vs. for all the P (s) and choosing for a () a function larger than all the plots. Since in general it is not feasible to plot all |P (j) P0 (j)|, one should provide some safety-cushion when selecting a (). Figure 1.4 shows a () for the Bode plots in Figure 1.2.
20

20

Frequency (rad/sec)

40

60

80

100 1 10

10 Magnitude (dB)

10

Figure 1.4. Additive uncertainty bounds for the process Bode plots in Figure 1.2 with P 0 (s) := 1 , m0 = 1, b0 = 1.5, k0 = 2.5. The solid lines represent possible plots for |P (j)P0 (j)| m0 s2 +b0 s+k0 and the dashed one represents the uncertainty bound a ().

1.1.2

Multiplicative uncertainty

The additive uncertainty in (1.2) measures the dierence between P (s) and P0 (s) in absolute terms and may seem misleadingly large when both P (s) and P0 (s) are largee.g., at low frequencies when the process has a pole at the origin. To overcome this diculty one often denes instead m (s) := P (s) P0 (s) , P0 (s) (1.3)

which measures how much P (s) deviates from P0 (s), relative to the size of Po (s). We can now express any admissible transfer function P (s) as in Figure 1.5, which motivates calling

Joo P. Hespanha a

PSfrag replacements u

m (s)
+ +

P (s) y

m (s) :=

P (s) P0 (s) P0 (s)

P0 (s)

` P (s) = P0 (s) 1 + m (s)

Figure 1.5. Multiplicative uncertainty

m (s) a multiplicative uncertainty block. To characterize a multiplicative uncertainty one determines a function m () suciently large so that for every admissible process transfer function P (s) we have |m (j)| = |P (s) P0 (s)| |P0 (s)|
m (),

One can determine m () by plotting |P (s)P0 (s)| vs. for all admissible P (s) (or a repre|P0 (s)| sentative set of them) and choosing m () to be larger than all the plots. Figure 1.6 shows m () for the Bode plots in Figure 1.2.
20

20

Frequency (rad/sec)

40

60

80

100 1 10

10 Magnitude (dB)

10

Figure 1.6. Multiplicative uncertainty bounds for the process Bode plots in Figure 1.2 with 1 P0 (s) := m0 s2 +b0 s+k0 , m0 = 1, b0 = 1.5, k0 = 2.5. The solid lines represent possible plots for
|P (j)P0 (j)| |P0 (j)|

and the dashed one represents the uncertainty bound

m ().

1.2

Nyquist stability criteria

The rst question we address is: Given a specic feedback controller C(s), how can we verify that it stabilizes every admissible process P (s). When the admissible processes are described in terms of a multiplicative uncertainty block, this amounts to verifying that the closed-loop system in Figure 1.7 is stable for every m (j) with norm smaller than m (). This can be done using the Nyquist stability criterion, which we review next.
Sidebar 1. Figure 1.8 can represent the closed-loop system in Figure 1.7 if we choose G(s):= ` 1 + m (s) P (s)C(s).

The Nyquist criterion is used to investigate the stability of the negative feedback connection in Figure 1.8. We briey summarize it here. The textbook [1, Section 6.3] provides a more detailed description of it with several examples.

PSfrag replacements Robust Control m (s) r P (s)


+

7
|m (j)|
+ +
m (),

u C(s)

P0 (s)

Figure 1.7. Unity feedback conguration with multiplicative uncertainty PSfrag replacements + r y G(s) u

Figure 1.8. Negative feedback

1.2.1

The Nyquist Plot


Matlab hint 2. nyquist(sys) draws the Nyquist plot of the system sys. . .

The rst step consists of drawing the Nyquist plot, which is done by evaluating G(j) from = to = + and plotting it in the complex plane. This leads to a closed-curve that is always symmetric with respect to the real axis. This curve should be annotated with arrows indicating the direction corresponding to increasing . Attention! Any poles of G(s) on the imaginary axis should be moved slightly to the left of the axis to avoid divisions by zero. E.g., G(s) = s+1 s(s 3) s s G(s) = 2 = s +4 (s + 2j)(s 2j) G (s) s+1 (s + )(s 3) s s G (s) = , (s + + 2j)(s + 2j) (s + )2 + 4

for a small > 0. The criterion should then be applied to the perturbed transfer function G (s). If we conclude that the closed-loop is stable for G (s) with very small , then the closed-loop with G(s) will also be stable and vice-versa.

1.2.2

The Nyquist criterion

Count the number #ENC of clockwise encirclements by the Nyquist plot of the point 1. To do this, we draw a ray from 1 to in any direction and add one each time the Nyquist plot crosses the ray in the clockwise direction (with respect to the origin of the ray) and subtract one each time it crosses the ray in the counter-clockwise direction. The nal count gives #ENC. Nyquist Stability Criterion. The total number of unstable (i.e., in the right-hand-side plane) closed-loop poles (#CUP) is given by #CUP = #ENC + #OUP,

Joo P. Hespanha a

where #OUP denotes the number of unstable (open-loop) poles of G(s). To have a stable closed-loop one thus needs #ENC = #OUP. Figure 1.9 shows the Nyquist plot of G0 (s) = C(s)P0 (s), for the nominal process model P0 (s) := 1 , m0 s 2 + b 0 s + k 0 m0 = 1, b0 = 1.5, k0 = 2.5, (1.5) (1.4)

(used in Figures 1.4 and 1.6) and a PID controller C(s) := 10 + 15 + 5s. s (1.6)

Since the open loop system has no unstable poles (#OUP = 0) and there are no encirclements of 1 (#ENC = 0), we conclude that the closed-loop system is stable. This means that the given PID controller C(s) stabilizes, at least, the nominal process P0 (s). It remains to check if it also stabilizes every admissible process model with multiplicative uncertainty.
200 Nyquist Diagram

20

Nyquist plot for 1st controller

150

15

100

10

Imaginary Axis

Imaginary Axis

50

50

100

10

150

15

200 50

50

100

150 200 Real Axis

250

300

350

400

20 20

15

10

5 Real Axis

10

15

20

25

30

Figure 1.9. Nyquist plot for the (open-loop) transfer function in (1.4). The right gure shows a zoomed view of the origin. To avoid a pole over the imaginary axis, in these plots we moved the pole of the controller from 0 to .01.

1.3

Small-Gain

Consider the closed-loop system in Figure 1.7 and suppose that we are given a controller C(s) that stabilizes the nominal process P0 (s), i.e., the closed-loop is stable when m (s) = 0. Our goal is to nd out if the closed-loop remains stable for every m (j) with norm smaller than m ().

Robust Control

Since C(s) stabilizes P0 (s), we know that the Nyquist plot of the nominal (open-loop) transfer function G0 (s) = C(s)P0 (s), has the right number of encirclements (#ENC = #OUP, where #OUP is the number of unstable poles of G0 (s). To check is the closed-loop is stable from some admissible process transfer function P (s) = P0 (s) 1 + m (s) , we need to draw the Nyquist plot of G(s) = C(s)P (s) = C(s)P0 (s) 1 + m (s) = G0 (s) + G0 (s)m (s) and verify that we still get the same number of encirclements.
|1 + G0 (j)| 1 G(j) PSfrag replacements(j)| |G(j) G0 G0 (j)
Sidebar 2. We are assuming that G(s) and G0 (s) have the same number of unstable poles #OUP and therefore stability is achieved for the same number of encirclements #ENC = #OUP. In practice this means that the uncertainty should not change the stability of any pole.

Figure 1.10. Nyquist plot derivation of the small-gain conditions

The Nyquist plots of G(s) and G0 (s) dier by |G(j) G0 (j)| = |G0 (j)m (j)| |G0 (j)|
m (),

A simple way to make sure that G(j) and G0 (j) have the same number of encirclements is to ask that the maximum dierence between the two be smaller than the distance from G0 (j) to the point 1, i.e., |1 + G0 (j)| > |G0 (j)|
m ()

|G0 (j)| < |1 + G0 (j)|

1 m ()

This leads to the so called small-gain condition: Small-gain Condition. The closed-loop system in Figure 1.7 is stable for every m (j) with norm smaller than m (), provided that C(j)P0 (j) < 1 + C(j)P0 (j) 1 , m () . (1.7)
Matlab hint 3. To check if (1.7) holds, draw 20 log 10 1 = m () 20 log10 m () on the magnitude Bode plot of the complementary sensitivity function and see if the latter always lies below the former.

10

Joo P. Hespanha a

Sidebar 3. Recall that the complementary sensitivity function is also the closed-loop transfer function for the reference r to the output y. Sidebar 4. A mnemonic that can be used to remember (1.7) is that the transfer function whose norm needs to be small is precisely the transfer function seen be the m block in Figure 1.7.

The transfer function on the left-hand-side of (1.7) is precisely the complementary sensitivity function: T0 (s) := 1 S0 (s), S0 (s) := 1 1 + C(s)P0 (s)

for the nominal process. So (1.7) can be interpreted as requiring the norm of the nominal complementary sensitivity function to be smaller than 1/ m(), . For this reason (1.7) is called a small-gain condition. Figure 1.11 shows the Bode plot of the complementary sensitivity function for the nominal process in (1.5) and the PID controller in (1.6). In the same plot we can see the 20 log10 m1 = 20 log10 m (), for the m () in Figure 1.6. Since the magnitude plot of () T0 (j) is not always below that of m1 , we conclude that the system may be unstable for () some admissible processes. However, if we redesign our controller to consist of an integrator with two lags C(s) = .005(s + 5)2 , s(s + .5)2 (1.8)

the magnitude plot of T0 (j) is now always below that of m1 and we conclude that we have () stability for every admissible process. In this case, the price to pay was a low bandwidth. This example illustrates a common problem in the control of systems with uncertainty: it is not possible to get good reference tracking over ranges of frequencies for which there is large uncertainty.
Bode Diagram 10 5 Magnitude (dB) Phase (deg) 0 5 10 15 20 25 30 0

45

90 1 10

10

Frequency (rad/sec)

10

10

Figure 1.11. Verication of the small gain condition for the nominal process (1.5), multiplicative uncertainty in Figure 1.6, and the PID controller (1.6). The solid line corresponds to the Bode plot of the complementary sensitivity function T0 (s) and the dashed line to m1 (both in dB). ()

Robust Control
Bode Diagram 40 20 0 20 40 60 0 90 Phase (deg) 180 270 360 450 2 10

11

Magnitude (dB)

10

10 10 Frequency (rad/sec)

10

10

Figure 1.12. Verication of the small gain condition for the nominal process (1.5), multiplicative uncertainty in Figure 1.6, and the integrator with 2 lags controller (1.8). The solid line corresponds to the Bode plot of the complementary sensitivity function T0 (s) and the dashed line to m1 (both () in dBs).

1.4

MATLAB hints

Matlab Hint 1 (bode). The command bode(sys) draws the Bode plot of the system sys. To specify the system one can use: 1. sys=tf(num,den), where num is a vector with the coecients of the numerator of the systems transfer function and den a vector with the coecients of the denominator. 2s The last coecient must always be the zero-order one. E.g., to get s2 +3 one should use num=[2 0];den=[1 0 3]; 2. sys=zpk(z,p,k), where z is a vector with the zeros of the system, p a vector with its 2s poles, and k the gain. E.g., to get (s+1)(s+3) one should use z=0;p=[1,3];k=2; 3. sys=ss(A,B,C,D), where A,B,C,D are a realization of the system. Matlab Hint 2 (nyquist). The command nyquist(sys) draws the Nyquist plot of the system sys. To specify the system you can use any of the commands in Matlab hint 1. Especially when there are poles very close to the imaginary axis (e.g., because they were actually on the axis and you moved them slightly to the left), the automatic scale may not be very good because it may be hard to distinguish the point 1 from the origin. In this case, you can use then zoom features of MATLAB to see what is going on near 1: Try clicking on the magnifying glass and selecting a region of interest; or try left-clicking on the mouse and selecting zoom on (-1,0) (without the magnifying glass selected.)

12

Joo P. Hespanha a

1.5

Exercises

Exercise 1 (Unknown parameters). Suppose one want to control the orientation of a satellite with respect to its orbital plane by applying a thrusters generated torque. The systems transfer function is give by P (s) := 10(bs + k) , s2 (s2 + 11(bs + k))

where the values of the parameters b and k are not exactly known, but it is known that .09 k .4 .006 b .03.

Find a nominal model and compute the corresponding additive and multiplicative uncertainty bounds. Exercise 2 (Noisy identication). The Simulink block provided corresponds to a discretetime system with transfer function H(z) = 1 z + 0 . z 2 + 1 z + 0

1. Use least-squares to estimate the 4 coecients of the transfer function. Repeat the identication experiment 25 times to obtain 25 estimates of the systems transfer functions. 2. Convert the discrete-time transfer functions so obtained to continuous-time using the Tustin transformation. Hint: Use the MATLAB command d2c. 3. Select a nominal model and compute the corresponding additive and multiplicative uncertainty bounds. Exercise 3 (Small-gain). For the nominal process model and multiplicative uncertainty that you obtained in Exercise 2, use the small gain condition to verify if the following controllers achieve stability for all admissible process models: C1 (s) = .3 C2 (s) = 2 s + .1 C3 (s) = 20 s 30 C4 (s) = 5(s + 1) (s + 2)(s + 3) C5 (s) = 2(s + 1) (s + .3)2

Justify your answers with appropriate Bode plots. Exercise 4 (Robustness vs. performance). Justify the statement: It is not possible to get good reference tracking over ranges of frequencies for which there is large uncertainty. Exercise 5 (Additive uncertainty). Derive a small-gain condition similar to (1.7) for additive uncertainty. Check if the mnemonic in Sidebar 4 still applies. Hint: With additive uncertainty, the open-loop gain is given by G(s) = C(s)P (s) = C(s) P0 (s) + a (s) = G0 (s) + C(s)a (s), which diers from G0 (s) by C(s)a (s).

Lecture #2

Control design by loop-shaping


Contents 2.1 The loop-shaping design method . . . . . . . . . . . . . . . . . . . . . . . . . 13 2.2 Open-loop vs. closed-loop specications . . . . . . . . . . . . . . . . . . . . . 14 2.3 Exercises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.1

The loop-shaping design method


d
+ e

PSfrag replacements

u C(s) P0 (s)
+ +

Figure 2.1. Closed-loop system

The basic idea behind control design by loop-shaping is to convert the desired specications on the closed-loop system in Figure 2.1 into constraints on the open-loop gain G0 (s) := C(s)P0 (s). The controller C(s) is then designed so that the open-loop gain G0 (s) satises the appropriate constraints. The shaping of G0 (s) to satisfy the appropriate constraints can be done using the classical methods described in [1, Chapter 6.7], such as PID, Lead, or Lag compensation. We will see later that loop-shaping can also be done using LQR/LQG. 13

14

Joo P. Hespanha a

2.2

Open-loop vs. closed-loop specications

In the remaining of this section we discuss how several closed-loop specications can be converted to constraints on the open-loop gain G0 (s). Stability Assuming that the open-loop gain has not unstable poles, stability of the closedloop is guaranteed as long as the phase of the open loop gain is above 180 degrees at the cross-over frequency c , i.e., at the frequency for which |G0 (jc )| = 1. The distance between the phase of G0 (jc ) and 180 degrees is the phase margin. Larger phase margins generally corresponds to a smaller overshoot for the step response of the closed-loop system. Reference tracking Suppose that one wants the tracking error to be at least k T 1 times smaller than the reference, over the range of frequencies [0, T ]. In the frequency domain, this can be expressed by |E(j)| kT , |R(j)| [0, T ], (2.1)

where E(s) and R(s) denote the Laplace transforms of the tracking error e := r y and the reference signal r, in the absence of noise and disturbances. For the closed-loop system in Figure 2.1, E(s) = and therefore (2.1) is equivalent to 1 kT , |1 + G0 (j)| [0, T ] |1 + G0 (j)| 1 , kT [0, T ]. 1 R(s), 1 + G0 (s)

This condition is guaranteed to hold by requiring that |G0 (j)| 1 + 1, kT [0, T ].

Disturbance rejection Suppose that one wants measurement input disturbances to appear in the output attenuated at least kD 1 times, over the range of frequencies [0, D ]. In the frequency domain, this can be expressed by |Y (j)| kD , |D(j)| [0, D ], (2.2)

Robust Control

15

where Y (s) and D(s) denote the Laplace transforms of the output y and the input disturbance d, in the absence of reference and measurement noise. For the closed-loop system in Figure 2.1, Y (s) = and therefore (2.2) is equivalent to |P0 (j)| kD , |1 + G0 (j)| [0, D ] |1 + G0 (j)| |P0 (j)| , kD [0, D ]. P0 (s) D(s), 1 + G0 (s)

This condition is guaranteed to hold by requiring that |G0 (j)| |P0 (j)| + 1, kD [0, D ].

Noise rejection Suppose that one wants measurement noise to appear in the output attenuated at least kN 1 times, over the range of frequencies [N , ). In the frequency domain, this can be expressed by |Y (j)| kN , |N (j)| [N , ), (2.3)

where Y (s) and N (s) denote the Laplace transforms of the output y and the measurement noise n, in the absence of reference and disturbances. For the closed-loop system in Figure 2.1, Y (s) = and therefore (2.3) is equivalent to |G0 (j)| kN , |1 + G0 (j)| [N , ) 1+ 1 1 , G0 (j) kN [N , ). G0 (s) N (s), 1 + G0 (s)

This condition is guaranteed to hold by requiring that 1 1 + 1, G0 (j) kN [N , ) |G0 (j)| kN , 1 + kN [N , ).

Robustness with respect to multiplicative uncertainty Suppose that one wants the closed-loop to remain stable for every multiplicative uncertainty m (j) with norm smaller than m (). This can be expressed by |G0 (j)| |1 + G0 (j)| 1 , m () , (2.4)

16 which is equivalent to 1+
Sidebar 5. Typically, (2.5) will hold for high-frequencies (for which |G0 (j)| is small), whereas (2.6) will hold for low-frequencies (for which |G0 (j)| is large).

Joo P. Hespanha a

1 G0 (j)

m (),

This condition is guaranteed to hold if for every either one of the following conditions holds
1 1. | G0 (j) | 1 and

1 1 G0 (j)
1 2. | G0 (j) | 1, m ()

m ()

|G0 (j)|

1 1+
m ()

(2.5)

< 1 and 1 G0 (j)


m ()

|G0 (j)|

1 1
m ()

(2.6)

Attention! None of the conditions derived above for the open-loop gain G0 (j) is necessary for the original closed-loop specications to hold. When the open-loop gain almost veries the conditions derived, it may be worth it to check directly if it veries the original closedloop conditions. This is actually necessary for the conditions (2.5)(2.6) that arise from robustness with respect to multiplicative uncertainty, because around the crossover frequency |G 0 (jc )| 1 will not satisfy either of these conditions, but it will generally satisfy the original condition (2.4) (as long as m () is not too large).

2.3

Exercises

Exercise 6 (Loop-shape 1). Consider again the nominal process model and multiplicative uncertainty that you obtained in Exercise 2. Design a controller for this process that achieves stability for all admissible process models and that exhibits: 1. zero steady-state error to a step input, 2. Phase Margin no smaller then 60degrees, 3. steady-state error for sinusoidal inputs with frequencies < 0.1rad/sec smaller than 1/50 (34dB), and 4. Rise time no slower than .3sec. Exercise 7 (Loop-shape 2). Consider the following nominal transfer function ans uncertainty bound: P0 (s) = 1 , s(1 + s/5)(1 + s/20)
m ()

= |L(j)|,

Robust Control where L(s) := 2.5 . (1 + s/20)2

17

Use loop-shaping to design a controller that achieves stability for all admissible process models and that exhibits: 1. steady-state error to a ramp input no larger than .01, 2. Phase Margin no smaller then 45degrees, 3. steady-state error for sinusoidal inputs with frequencies < 0.2rad/sec smaller than 1/250 (50dB), and 4. attenuation of measurement noise by at least a factor of 100 (40dB) for frequencies greater than 200rad/sec.

18

Joo P. Hespanha a

Bibliography
[1] G. F. Franklin, J. D. Powell, and A. Emami-Naeini. Feedback Control of Dynamic Systems. Prentice Hall, Upper Saddle River, NJ, 4th edition, 2002.

19

Das könnte Ihnen auch gefallen