Power Isolation Transformers

Power Isolation Transformers

Typical High Voltage Transformer

Typical Low Voltage Transformer

FEATURES
Available for both high and low voltage generating systems. Designed for operation with Basler standard voltage regulators or
equivalent equipment. Terminals arranged for easy connection. Frequency range of 50-400 Hz on low voltage units. Fused primary windings on 5 kv class units. Multiple primary and secondary voltages on most types. Withstand underfrequency/overvoltage operation encountered in generating systems. Ruggedly constructed. CSA certified (selected models).

DESCRIPTION Page 1

APPLICATION and SPECIFICATIONS Page 2 CONNECTION INSTRUCTIONS Pages 2 through 8 ORDERING Page 8

DESCRIPTION
Basler Electric manufactures a series of power isolation transformers for use with the standard Basler Voltage Regulators or wherever power isolation or voltage matching requirements exist. These transformers outperform ordinary control transformers, particularly in the underfrequency and overvoltage conditions associated with generator operation. These transformers are available from stock with either low voltage (up to 600 VAC) or high voltage (more than 600 VAC) windings and ratings up to 4,000 VA maximum. The high voltage transformers feature low corona and high moisture resistance characteristics. The low voltage transformers operate from 50 to 400 Hz. All transformers are constructed to withstand the rigors of shock and vibration encountered in generating system applications. Conservative in design, these Basler transformers assure years of trouble-free operation.

SP-2 9-11
12570 STATE ROUTE 143, HIGHLAND, ILLINOIS 62249 USA PHONE 618-654-2341 FAX 618-654-2351

Power Isolation Transformers

APPLICATION
Basler SR, KR, and XR series of voltage regulators require a source of either 60, 120, 240 or 480 VAC power, depending upon which regulator is used. Since this power is normally obtained from generator terminal voltage, an isolation transformer must be used whenever the generator terminal voltage is not the same as that required by the regulator. An isolation transformer is also required to isolate the voltage regulator input from ground in installations where the exciter field or field flashing circuit is grounded.

SPECIFICATIONS
INSULATION TEMPERATURE DIELECTRIC TEST VOLTAGE Primary Secondary OPERATING FREQUENCY RANGE FINISH Notes:
1 2 3 BE 10647 001 - 130C BE 12819 001 - 4000 Vac BE 12819 001 - Varnish impregnated and epoxy coated 4 5 BE 12818 001, BE 13658 001 - 4 KVac BE 13658. BE 14014 - 19 KVac

Low Voltage Transformer 185C 1 2500 Vac 2 2500 Vac 2 50-400 Hz Varnish impregnated

High Voltage Transformer 185C 12000 Vac 5 2500 Vac 4 50/60 Hz Varnish impregnated and epoxy coated

CONNECTION INSTRUCTIONS
To determine proper winding connection, refer to Table 2 and locate primary and secondary code letters for the selected transformer. Then, in Table 1, locate the same code letters and select the required voltage. The necessary connections (jumpers) are indicated in the column headed Jump Terminals. Example: To connect BE 10317 001 for 240 V primary and 120 V secondary, refer to Table 2 and note that connection code letters for this transformer are A and W. Then refer to Table 1, code letter A. For 240 VAC at primary terminals Hl and H6, jump H3 to H6 and H4 to Hl. Referring to code letter W, 120 VAC is made available at secondary terminals Xl and X4 by jumping X2 to X4 and X3 to Xl.

Table 1

PRIMARY WINDINGS SECONDARY WINDINGS Code Voltage Code Voltage Jump Terminals Jump Terminals Letter VAC At terminals Letter VAC At terminals 208 H2-H6; H5-H1 3 and 4 Power Input U 240 240 H3-H6; H4-H1 E1 Voltage Sensing A H1 and H6 416 H2-H5 240 X2-X4; X3-X1 V X1 and X4 480 H3-H4 480 X2-X3 B 600 H1 and H2 None 120 X2-X4; X3-X1 W X1 and X4 240 H1 and H2 H2-H4; H3-H1 240 X2-X3 C 480 H1 and H4 H2-H3 60 X2-X4; X3-X1 Y X1 and X4 600 H1 and H5 H2-H3 120 X2-X3 2400 H1 and H2 None Z 139 X1 and X2 None D 4160 H1 and H3 None See Table 2 for connection code letters 6600 H1 and H3 None assigned to each transformer. E 3300 H1 and H2 None F 7200 H1 and H2 None
2

Power Isolation Transformers

CONNECTION INSTRUCTIONS, continued


Table 2
WHEN USING IN POWER ISOLATION BASLER APPLICATIONS REQUIRING: VOLTAGE REGULATOR PRIMARY PRIMARY SECONDARY MODEL VA (MAX.) VOLTS VOLTS SR4A SR6A SR4F SR8A SR9A SR8F SR63H SRN4 SR32A SR32H SR125H SRN8 SR250H KR2F KR2FF KR4F KR6F KR4FF KR7F KR7FF APR63-5 APR-125 VR63-4 XR2001 XR2001F XR2004,F SR2004,F DVR2004,F SR4A SR4F SR8A SR8F SR63H SRN4 SR125H SRN8 SR250H SR8A SR8F SR63H SRN4 SR8A SR8F SR125H SR250H 1000 1000 2000 2000 1200 4000 8000 640 500 500 1000 1000 208/240 x 416/480 600 208/240 x 416/480 600 208/240 x 416/480 208/240 x 416/480 208/240 x 416/480 208 x 240/ 600 208/240 x 416/480 600 208/240 x 416/480 600 120 x 240 120 x 240 120 x 240 120 x 240 60 x 120 240 x 480 240 x 480 139 120 x 240 120 x 240 120 x 240 120 x 240 SELECT BASLER TRANSFORMER PART NO. LOW BE 10493 002 BE 11049 002 BE 10494 002 BE 11050 002 BE 11304 002 BE 12819 001 BE 12819 001 (two in parallel) BE 10647 001 BE 10317 002 BE 11048 001 BE 10493 002 BE 11049 002 PER MAXIMUM UNIT WEIGHT IMP. IN POUNDS FIG. NET SHIP. NO. A VOLTAGE TRANSFORMERS .0414 .0418 .0339 .0299 .0327 .041 .041 .0193 .0670 .0640 .0414 .0418 36 36 67 67 48 87 38 38 71 71 50 91 1 3 1 3 1 4 4 2 1 3 1 3 6.50 6.50 6.50 6.50 6.50 8.25 8.25 6.37 6.50 0.65 6.50 6.50 OUTLINE DIMENSIONS INCHES C D 1/32 E 1/16 8.75 8.75 8.75 8.75 8.75 12.50 12.50 5.43 8.75 8.75 8.75 8.75 2.50 2.50 2.50 2.50 2.50 7.25 7.25 5.31 2.50 2.50 2.50 2.50 4.75 4.75 8.50 8.50 6.25 3.50 3.50 3.87 3.00 3.00 4.75 4.75 CONNECTIONS (TABLE 1) PRI SEC A B A B A A A C A B A B W W W W Y V V Z W W W W

B 7.00 6.87 10.75 10.75 8.50 9.25 9.25 6.50 5.25 5.25 7.00 6.87

F .37 x .75 .37 x .75 .37 x .75 .37 x .75 .37 x .75 .31 x .44 .31 x .44 .28 x .56 .37 x .75 .37 x .75 .37 x .75 .37 x .75

87 91 Each Each 28 19 19 36 36 30 21 21 38 38

1000

240/480 600 240/480 600

240 x 240

BE 18674 001

.0418

28

30

6.375

6.50

6.25

5.31

4.25

.563x.281

500

240 x 240

BE 18675 001

.0311

19

21

5.25

4.625

4.375

4.375

3.50

.243x.375

HIGH VOLTAGE TRANSFORMERS 1000 2400/4160 120 X 240 BE 13616 001 .033 40 42 6 9.00 10.00 9.75 5.00 8.50 .41 x .75 D W

1680

2400/4160

120 x 240

BE 13487 001

.0175

70

74

9.00

10.00

11.75

5.00

8.50

.41 x .75

4000 8000

2400/4160 2400/4160

240 x 480 240 x 480

BE 12818 001 BE 12818 001 (two in parallel) BE 14014 001

.064 .064

107 107 each 70

112 112 each 74

5 5

12.00 12.00

10.00 10.00

17.50 17.50

9.75 9.75

3.25 3.25

.31 x .44 .31 x .44

D D

V V

2000

3300/6600

120 x 240

.020

10.00

9.00

11.25

8.50

5.00

.31 x .44

4000 4000

13800 7200

240 x 480 240 x 480 BE 13658 001

.066 .066

107 107

112 112

10 10

10.00 10.00

13.75 13.75

16.25 16.25

10.75 10.75

3.25 3.25

.31 x .44 .31 x .44

F F

V V

Power Isolation Transformers

CONNECTION INSTRUCTIONS, continued

Figure 1

Figure 2 4

Power Isolation Transformers

CONNECTION INSTRUCTIONS, continued

Figure 3

Figure 4 5

Power Isolation Transformers

CONNECTION INSTRUCTIONS, continued

Figure 5

Figure 6

Power Isolation Transformers

CONNECTION INSTRUCTIONS, continued

Figure 7

Figure 8

Power Isolation Transformers

CONNECTION INSTRUCTIONS, continued

Figure 9

Figure 10

HOW TO ORDER
Specify by part number and description: Basler Part No. BE_____________________ Power Isolation Transformer. Select the proper part number by referring to transformer data in Table 1.

SAMPLE SPECIFICATIONS
A power isolation transformer is required to be capable of providing an output of 240 VAC, 60 Hz, 1680 VA with inputs of either 208/240 or 416/480 VAC, 60 Hz. It shall be capable of withstanding underfrequency and overvoltage conditions associated with generator operation and shall be constructed to withstand the shock and vibration encountered in such applications. The power isolation transformer shall be a Basler Electric Company BE10494001 or equivalent.

P .A.E. Les Pins, 67319 Wasselonne Cedex FRANCE Tel +33 3.88.87.1010 Fax +33 3.88.87.0808 e-mail: franceinfo@basler.com No. 59 Heshun Road Loufeng District (N), Suzhou Industrial Park, 215122, Suzhou, P .R.China Tel +86(0)512 8227 2888 Fax +86(0)512 8227 2887 e-mail: chinainfo@basler.com 111 North Bridge Road #15-06 Peninsula Plaza Singapore 179098 Tel +65 68.44.6445 Fax +65 65.68.44.8902 e-mail: singaporeinfo@basler.com Printed in U.S.A.

12570 State Route 143, Highland, Illinois 62249-1074 USA Tel +1 618.654.2341 Fax +1 618.654.2351 e-mail: info@basler.com

www.basler.com