Sie sind auf Seite 1von 4

Customer No.: Hilti AG FL-9494 Schaan HAP v3.3c Phone: Resp.

Anchor fastening design Location:

Page: Quotation: Project: List No.: Date: Project name:

1 of 4

Anchor fastening design for HST-M16


As per Hilti-CC method

Positioning
Anchoring plate:
lx=220 mm ly=200 mm s1=150 mm c1=100 mm c3=100 mm Anchor Anchor in slotted hole

c3

s1

c1

Loads (design values)


Shear Load:
Vyd=-32.0 kN

Vy

Concrete
Compressive class: C20/25 Compression zone / uncracked concrete Thickness of base material: 350 mm factor depth of embedment: 1.0 straight and close-mesh stirrup-type edge reinforcement (O >= 12mm) close reinforcement (close reinforcement (s <= 15 cm))

Data and results must be checked for agreement with the actual existing conditions and for plausibility! HAP v3.3c 2003 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Customer No.: Hilti AG FL-9494 Schaan HAP v3.3c Phone: Resp.:

Anchor fastening design Location:

Page: Quotation: Project: List No.: Date: Project name:

2 of 4

Tension Load N
Anchor Design value of tension load Design value of anchor group NSd,i
n

HST-M16
1 0.0 kN = 0.0 kN 2 0.0 kN

NSd = NSd,i
g i=1

Steel failure
Characteristic value for one anchor Partial safety factor NRk,s = -- Ms = 1.00 NRk,s Ms NSd = 0.00 NRd,s
h

Design value of resistance

NRd,s =

= ---

Check

Pullout failure
Characteristic value for one anchor Partial safety factor NRk,p = -- Mp = 1.00 NRk,p Mp NSd = 0.00 NRd,p
h

Design value of resistance

NRd,p =

= ---

Check

Concrete cone failure


Initial value of the anchor resistance Actual area of concrete cone Reference area of concrete cone Factor for disturbance of stressed distribution Shell spalling factor Eccentricity of the resulting tensile load Factors for eccentrical loading Influence concrete Influence depth Characteristic value for the anchor group NRk,c = NRk,c
0

NRk,c Ac,N A
0 c,N

= --= --= --= 1.00

s,N

re,N = 1.00 eN,x = 0 mm eN,y = 0 mm

ec,N,x = 1.00 fB,N T = 1.00 = 1.00

ec,N,y = 1.00

Ac,N A
0 c,N

s,N re,N ec,N,x ec,N,y T fB,N = -- Mc = 1.00 NRk,c Mc NSd = 0.00 NRd,c
g

Partial safety factor

Design value of resistance

NRd,c =

= ---

Check

Data and results must be checked for agreement with the actual existing conditions and for plausibility! HAP v3.3c 2003 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Customer No.: Hilti AG FL-9494 Schaan HAP v3.3c Phone: Resp.:

Anchor fastening design Location:

Page: Quotation: Project: List No.: Date: Project name:

3 of 4

Shear Load V
Anchor Design value of shear in x Design value of shear in y VSd,x,i VSd,y,i
n g Sd,x

HST-M16
1 0.0 kN -16.0 kN
g Sd,y

2 0.0 kN -16.0 kN
n

Design value of anchor group

= VSd,x,i = 0.0 kN
i=1

= VSd,y,i = -32.0 kN
i=1

Resulting design value of shear

VSd,i

16.0 kN

16.0 kN

Steel failure without lever arm


Characteristic value for one anchor Partial safety factor Design value of resistance VRd,s = VRk,s = 50.0 kN Ms = 1.25 VRk,s Ms = 40.0 kN Check VSd = 0.40 VRd,s
h

Concrete edge failure


Initial value of the anchor resistance Actual area of concrete cone Reference area of concrete cone Factor for disturbance of stressed distribution Factor for member thickness Factor for load direction Eccentricity of the resulting shear load Factors for eccentrical loading Factors for the position of the anchorage Characteristic value for the anchor group VRk,c = VRk,c
0

VRk,c Ac,V A
0 c,V

= --= 0 mm = 0 mm = 1.00 = 1.00 = 1.00 = 0 mm eV,y = 0 mm

s,V h,V ,V eV,x

ec,V,x = 1.00 ucr,V = 1.0

ec,V,y = 1.00

Ac,V Ac,V
0

s,V h,V ,V ec,V ucr,V VRk,c Mc

VRk,c,x = --g

Mc= 0.00 VSd = 0.00 VRd,c

Design value of resistance

VRd,c =

= ---

Check

Data and results must be checked for agreement with the actual existing conditions and for plausibility! HAP v3.3c 2003 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Customer No.: Hilti AG FL-9494 Schaan HAP v3.3c Phone: Resp.:

Anchor fastening design Location:

Page: Quotation: Project: List No.: Date: Project name:

4 of 4

Concrete pryout failure


Factor for short stiff anchors Characteristic value for the anchor group Characteristic value for the anchor group Partial safety factor Design value of resistance VRd,c = VRk,c Mc k= 2.0 NRk,c = 45.7 kN VRk,c = 91.5 kN Mc = 1.50 = 61.0 kN Check

HST-M16

VSd = 0.52 VRd,c

Data and results must be checked for agreement with the actual existing conditions and for plausibility! HAP v3.3c 2003 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

Das könnte Ihnen auch gefallen