UNIVERSITY OF UKUROVA

INSTITUTE OF NATURAL AND APPLIED SCIENCE









PhD THESIS







Ahmet TEKE






UNIFIED POWER QUALITY CONDITIONER: DESIGN, SIMULATION
AND EXPERIMENTAL ANALYSIS






DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING










ADANA, 2011




UKUROVA UNIVERSITY
INSTITUTE OF NATURAL AND APPLIED SCIENCES


Ahmet TEKE

PhD THESIS

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

We certify that the thesis titled above was reviewed and approved for the award of
degree of the Doctor of Philosophy by the board of jury on 25/05/2011.


.................... .. ................................
Prof. Dr. Mehmet TMAY Prof. Dr. Tankut YALINZ Assoc. Prof. Dr. lyas EKER
SUPERVISOR MEMBER MEMBER


.................... ..
Assoc. Prof. Dr. Ulus EVK Assist. Prof. Dr. K. aatay BAYINDIR
MEMBER MEMBER



This PhD Thesis is written at the Department of Electrical and Electronics
Engineering of Institute of Natural and Applied Sciences of ukurova University.
Registration Number:


Prof. Dr. lhami YENGL
Director
Institute of Natural and Applied Sciences


This thesis was supported by the Scientific Research Project Unit of ukurova University for
my thesis (Project Number: MMF2009D3).

Note: The usage of the presented specific declarations, tables, figures and photographs either in
this thesis or in any other reference without citation is subject to "The law of Arts and
Intellectual Products" number of 5846 of Turkish Republic.
UNIFIED POWER QUALITY CONDITIONER:
DESIGN, SIMULATION AND EXPERIMENTAL ANALYSIS


I
ABSTRACT

PhD THESIS


Ahmet TEKE

UKUROVA UNIVERSITY
INSTITUTE OF NATURAL AND APPLIED SCIENCES
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING

Supervisor:Prof. Dr. Mehmet TMAY
Year: 2011, Pages: 204
Jury :Prof. Dr. Mehmet TMAY
Prof. Dr. Tankut YALINZ
Assoc. Prof. Dr. lyas EKER
Assoc. Prof. Dr. Ulus EVK
Asst. Prof. Dr. K. aatay BAYINDIR

Power quality (PQ) problem can be defined as the deviations of the voltage
and/or current from the nominal sine wave. PQ problems generally concern with voltage
sags/swells and harmonic currents. Custom Power (CP) devices that mitigate these
power quality problems have gained more attention in the recent decades. Unified Power
Quality Conditioner (UPQC) is one of the CP devices and it mitigates both load current
and supply voltage problems, simultaneously.
In this study, UPQC and a new topology of UPQC namely OPEN UPQC are
designed, modeled and setup experimentally to mitigate voltage sag/swells and harmonic
currents. UPQC consists of Dynamic Voltage Restorer (DVR) and Active Power Filter
(APF). An improved voltage compensation controller and new sag/swell detection
method based on Enhanced Phase Locked Loop (E-PLL) are presented for DVR.
Traditional Instantaneous Reactive Power Theory (IRPT) is optimized for APF control
algorithm to compensate harmonic load current under unbalanced and distorted supply
voltages. Digital Signal Processor based 6 kVA, 230V
line-line
UPQC and OPEN UPQC
prototypes have been developed for laboratory tests. UPQC and OPEN UPQC with
proposed controller algorithms effectively compensates the sag/swell in supply voltage
by keeping the load voltage amplitude at 0.9-1 per unit and eliminates the load current
harmonics by keeping supply current at 5%<THD (Total Harmonic Distortion),
simultaneously.
This experimental study was conducted in Power Quality Laboratory at Electrical
and Electronics Engineering Department, ukurova University, Adana, Turkey.

Key Words: Unified Power Quality Conditioner, OPEN UPQC, Custom Power, Active
Power Filter, Dynamic Voltage Restorer.
UNIFIED POWER QUALITY CONDITIONER:
DESIGN, SIMULATION AND EXPERIMENTAL ANALYSIS


II
Z

DOKTORA TEZ


Ahmet TEKE

UKUROVA NVERSTES
FEN BLMLER ENSTTS
ELEKTRK ELEKTRONK MHENDSL ANABLM DALI

Danman : Prof. Dr. Mehmet TMAY
Yl: 2011, Sayfa: 204
Jri : Prof. Dr. Mehmet TMAY
Prof. Dr. Tankut YALINZ
Do. Dr. lyas EKER
Do. Dr. Ulus EVK
Yrd. Do. Dr. K. aatay BAYINDIR

G kalitesi problemi gerilim ve/veya akmn nominal sins dalga formundan
sapmas olarak tanmlanabilir. G kalitesi problemleri genellikle gerilim
dmleri/ykselmeleri ve harmonikli akmlar ile ilgilidir. G kalitesi problemlerine
zm getiren zel G Donanmlar son yllarda byk bir nem kazanmtr.
Birletirilmi G Kalitesi Dzenleyici (BGKD) bu donanmlardan biridir ve hem
akm hem de gerilim kalitesi problemlerini e zamanl olarak azaltr.
Bu almada, gerilim dm/ykselimi ve akm harmoniklerini azaltmak
amacyla BGKD ve yeni bir BGKD topolojisi olan Ak BGKD tasarlanm,
modellenmi ve deneysel olarak kurulmutur. BGKD, Dinamik Gerilim yiletiricisi
(DG) ve Aktif G Filtresinden (AGF) olumaktadr. DG iin Gelimi-Faz
Kilitlemeli Dng yntemi tabanl bir gerilim kompanzasyon yntemi ve gerilim
dm/ykselmesini tespit etmek amacyla yeni bir hata tespit yntemi
sunulmutur. AGF kontrolcsnde, Anlk Reaktif G Teorisi dengesiz ve harmonikli
besleme gerilimlerinde en iyi alacak ekilde iyiletirilmitir. Laboratuvar testleri
iin Saysal Sinyal lemci tabanl 6 kVA, 230V
faz-faz
BGKD ve Ak BGKD
prototipleri gelitirilmitir. Amalanan BGKD ve Ak BGKD, kaynak geriliminde
meydana gelen gerilim dm/ykselimini dengeler ve hassas yk gerilimini 0.9-1
birim deerde ve ayrca harmonikli yk akmlarn yok ederek kaynak akmn
(Toplam Harmonik Bozulma, THB), THB<%5deerinde ezamanl olarak tutar.
Bu deneysel alma ukurova niversitesi Elektrik Elektronik Mhendislii
Blm G Kalitesi Laboratuvarnda gerekletirilmitir, Adana, Trkiye.

Anahtar Kelimeler: Birletirilmi G Kalitesi Dzenleyicisi, Ak BGKD, zel
G, Aktif G Filtresi, Dinamik Gerilim yiletiricisi.
BRLETRLM G KALTES DZENLEYC:
TASARIM, SMLASYON VE DENEYSEL ANALZ


III
ACKNOWLEDGEMENTS

It is a pleasure to thank my supervisor Prof. Dr. Mehmet TMAY who made
this thesis possible for his esteemed guidance, encouragement, friendship and
support during my studies.
I am grateful to Prof. Dr. Sleyman GNGR for his encouragement and
good wishes for my work. I also thank to my co-supervisor Assist. Prof. Dr. K.
aatay BAYINDIR for his valuable comments on my study. I am especially
indebted to my thesis committee members, Prof. Dr. Tankut YALINZ, Assoc.
Prof. Dr. lyas EKER and Assoc. Prof. Dr. Ulus EVK. I also wish to thank Assist.
Prof. Dr. M. Emin MERAL, Ph.D. M. Ura CUMA, Rsch. Asst. Ltf
SARIBULUT, Rsch. Asst. Adnan TAN, Rsch. Asst. Murat FURAT, Rsch. Asst.
Tahsin KROLU and Ph.D. Alper TERCYANLI for their technical helps and
useful suggestions during the study. I am also grateful to the members of the
Electrical and Electronics Engineering Department, ukurova University.
I would like to thank and acknowledge the financial supported by Electrical,
Electronics and Informatics Research Group of Scientific and Technological
Research Council of Turkey (Project Number: 106E188) for our research project.
This thesis is a part of the research project entitled as Modeling and Implementation
of Custom Power Park (106E188). This project also supports two other Ph.D.
studies namely Voltage Quality Enhancement with Custom Power Park and
Digital Signal Processor based Implementation of Custom Power Device
Controllers.
I would like also to thank and acknowledge the financial supported by
Scientific Research Project Unit of ukurova University for my thesis (Project
Number: MMF2009D3).
Finally, I also wish to express my deepest gratitude to my parents and
extended family for their endless support, encouragement and patience.






IV
CONTENTS PAGE

ABSTRACT I
Z.. II
ACKNOWLEDGEMENTS III
CONTENTS. IV
LIST OF TABLES. X
LIST OF FIGURES.XII
LIST OF SYMBOLS. XVIII
LIST OF ABBREVATIONSXX
1. INTRODUCTION.. 1
1.1. Background and Research Motivation...1
1.2. Objectives and Organization of Thesis..3
1.3. Contributions of Thesis. 5
2. ELECTRIC POWER QUALITY... 7
2.1. Power Quality Terminology.. 7
2.2. Classification of Power Quality Problems and Their Impacts...8
2.2.1. Current Harmonic Distortion..10
2.2.2. Voltage Sags11
2.2.3. Voltage Swells 12
2.3. Power Quality Standards. 12
2.3.1. Standards Related with Voltage Characteristics. 13
2.3.1.1. IEEE Standards...13
2.3.1.2. IEC Electromagnetic Compatibility Standards...13
2.3.1.3. The European Voltage Characteristics Standard.14
2.3.2. Standards Related with Current Harmonics... 15
2.3.2.1. IEEE Standards...16
2.3.2.2. The International Electrotechnical Commission 17
2.3.2.3. Energy Networks Association Engineering
Recommendation G5/4... 18
2.4. Custom Power Devices to Mitigate Power Quality Problems.19


V
2.4.1. Custom Power Devices...20
2.4.2. Comparisons of Power Quality Mitigation Devices...23
2.4.3. Cost Range of Custom Power Devices.. 27
2.5. Summary..28
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES... 29
3.1. Literature Review of Active Power Filter29
3.1.1. Power Circuit Topologies of APF...30
3.1.2. Control Techniques of APF 34
3.1.3. Active Power Filter in Service36
3.2. Literature Review of Dynamic Voltage Restorer 37
3.2.1. Power Circuit Topologies of DVR. 38
3.2.2. Control Techniques of DVR... 42
3.2.3. Field Applications of DVR. 45
3.3. Literature Review of Unified Power Quality Conditioner.. 46
3.3.1. Power Circuit Topologies of UPQC... 48
3.3.2. Control Techniques of UPQC Topologies.. 50
3.3.3. UPQC in Service and Future Trends.. 53
3.4. Summary..53
4. CONTROL STRATEGY OF UPQC AND OPEN UPQC 55
4.1. Control Algorithms for APF 55
4.1.1. Proposed APF Controller56
4.1.2. Reference Current Generation 58
4.1.3. Hysteresis Current Controller.59
4.2. Control Algorithms for DVR...60
4.2.1. Proposed Reference Voltage Generation 61
4.2.2. PWM Gate Signal Generation 65
4.2.3. Proposed Sag/Swell Detection... 66
4.3. Summary..69
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER...71
5.1. Power Circuit Design of Proposed APF.. 71
5.1.1. Design of DC Link Capacitor.73


VI
5.1.2. Design of Inverter Circuit...74
5.1.3. Design of Filter Units. 75
5.2. Components of Proposed APF.77
5.2.1. Voltage and Current Measurements78
5.2.2. Signal Conditioner/Interface Board79
5.2.3. Firing and Fault Protection Board..79
5.2.4. IGBT Driver Circuit...81
5.2.5. Three-Phase Bridge IGBT Inverter with DC Link Capacitor.81
5.2.6. Smoothing Inductor and Choke Reactors...82
5.2.7. Three-Phase Bridge Rectifier with a Resistive Load. 83
5.3. Power Circuit Design of Proposed DVR.84
5.3.1. Design of DC Supply..86
5.3.2. Design of Inverter Circuit.. 86
5.3.3. Design of LC Filter.87
5.3.4. Design of Series Injection Transformer. 89
5.4. Components of Proposed DVR... 90
5.4.1. Disturbance (Sag/Swell) Generator 91
5.4.2. Voltage Transducers93
5.4.3. Signal Conditioner/Interface Board93
5.4.4. H-Bridge PWM Inverters... 94
5.4.5. Passive LC Output Filter 95
5.4.6. Injection Transformer. 96
5.5. Practical Recommendations for Experimental Study.. 97
5.6. Summary..99
6. SIMULATION STUDY OF UPQC TOPOLOGIES...101
6.1. Controller of Proposed APF...102
6.2. Controller of Proposed DVR. 103
6.3. Simulation Verification of Proposed UPQC.. 104
6.3.1. Simulation Results for Standby Operation of DVR. 106
6.3.2. Simulation Results for Reference Current Extraction.. 107


VII
6.3.3. Simulation Results for Voltage Sag Compensation and Current Harmonic
Elimination with Proposed UPQC... 107
6.3.3.1. Case Study 1: No Voltage Sag, Current Harmonic
Elimination... 108
6.3.3.2. Case Study 2: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination... 112
6.3.3.3. Case Study 3: 20% Double Phase Voltage Sag, Current Harmonic
Elimination... 117
6.4. Simulation Verification of Proposed OPEN UPQC.. 122
6.4.1. Case Study 4: No Voltage Sag, Current Harmonic Elimination.. 124
6.4.2. Case Study 5: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination...127
6.4.3. Case Study 6: 20% Double Phase Voltage Sag, Current Harmonic
Elimination...132
6.5. Summary137
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES...139
7.1. Experimental Results for Standby Operation of DVR.. 140
7.2. Experimental Results for Reference Current Extraction....141
7.3. Experimental Results for Voltage Sag Compensation and
Current Harmonic Elimination with Proposed UPQC. 143
7.3.1. Case Study 1: No Voltage Sag, Current Harmonic Elimination...143
7.3.2. Case Study 2: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination...146
7.3.3. Case Study 3: 20% Double Phase Voltage Sag, Current Harmonic
Elimination...150
7.4. Experimental Results for Voltage Sag Compensation and
Current Harmonic Elimination with Proposed OPEN UPQC.. 154
7.4.1. Case Study 4: No Voltage Sag, Current Harmonic Elimination..155
7.4.2. Case Study 5: 25% Single-Phase Voltage Sag,
Current Harmonic Elimination158


VIII
7.4.3. Case Study 6: 20% Double Phase Voltage Sag, Current Harmonic
Elimination.. 162
7.5. Summary166
8. CONCLUSIONS AND FUTURE WORK. 169
REFERENCES.. 173
BIOGRAPHICAL INFORMATION. 199
APPENDIX A: Most Common Power Quality Problems.. 200
APPENDIX B: Fundamentals of Instantaneous Reactive Power Theory.. 202


























IX

































X
LIST OF TABLES PAGE

Table 2.1. Financial loss per voltage sag for some types of industries ................... 12
Table 2.2. IEEE-519 current harmonic distortion limits ......................................... 17
Table 2.3. Custom power device application matrix............................................... 27
Table 5.1. The filter design parameters of DVR ..................................................... 88
Table 5.2. The ratings and components of disturbance generator........................... 92
Table 6.1. Data of the simulated UPQC system ................................................... 101
Table 6.2. THD contents of load and supply currents of Phase_A for Case 1 ...... 111
Table 6.3. THD contents of load and supply currents of Phase_A for Case 2 ...... 115
Table 6.4. THD contents of supply and filtered currents of Phase_A for Case 3 . 120
Table 6.5. THD contents of load and supply currents of Phase_A for Case 4 ...... 126
Table 6.6. THD contents of load and supply currents of Phase_A for Case 5 ...... 130
Table 6.7. THD contents of supply and filtered currents of Phase_A for Case 6 . 135
Table 7.1. Data of the experimental UPQC system .............................................. 139
Table 7.2. THD contents of load and supply currents of Phase_A for Case 1 ...... 145
Table 7.3. THD contents of load and supply currents of Phase_A for Case 2 ...... 148
Table 7.4. THD contents of supply and filtered currents of Phase_A for Case 3 . 152
Table 7.5. THD contents of load and supply currents of Phase_A for Case 4 ...... 157
Table 7.6. THD contents of load and supply currents of Phase_A for Case 5 ...... 160
Table 7.7. THD contents of supply and filtered currents of Phase_A for Case 6 . 164
Table A.1. Most common PQ problems ................................................................ 200











XI

































XII
LIST OF FIGURES PAGE

Figure 2.1. Basic disturbances: (a) Causes at customer side, (b) Causes at utility
side and (c) Affected equipment ......................................................... 9
Figure 2.2. Percentage occurrences of PQ disturbances in equipment
interruptions ........................................................................................ 9
Figure 2.3. Most common types of power quality problems .............................. 10
Figure 2.4. Single line diagrams of a real system with/without CP devices ....... 21
Figure 2.5. Circuit diagram of a shunt APF ........................................................ 21
Figure 2.6. Circuit diagram of a DVR ................................................................ 22
Figure 2.7. Circuit diagram of (a) UPQC and (b) OPEN UPQC ........................ 23
Figure 2.8. The topologies of DVR and STS ...................................................... 24
Figure 2.9. The topology of UPS ........................................................................ 24
Figure 3.1. Basic representation of APF ............................................................. 30
Figure 3.2. Various power circuit topologies of APF: (a) Three-phase 3/4 wire
based, (b) Three-phase with uncontrolled rectifier and(c) Cascaded
multilevel inverter based .................................................................. 31
Figure 3.3. Control unit of APF with a specified power circuit topology .......... 34
Figure 3.4. Basic representation of DVR ............................................................ 37
Figure 3.5. Various power circuit topologies of DVR ........................................ 39
Figure 3.6. Control unit of a DVR with a specified power circuit topology ...... 43
Figure 3.7. Basic representation of UPQC.......................................................... 47
Figure 3.8. Various power circuit topologies: (a) Left shunt-UPQC, (b) Right
shunt-UPQC, (c) OPEN UPQC, (d) Interline UPQC and
(e) Multilevel UPQC ........................................................................ 48
Figure 3.9. Control unit of UPQC with a specified power circuit topology ....... 51
Figure 4.1. The control system of traditional APF .............................................. 56
Figure 4.2. Proposed APF controller................................................................... 57
Figure 4.3. Voltage and current waveforms of hysteresis band controller .......... 59
Figure 4.4. Structure of series inverter control ................................................... 60
Figure 4.5. Reference signal generation for the series controller ....................... 61


XIII
Figure 4.6. Supply voltage and its extracted components .................................. 65
Figure 4.7. Generation of PWM gate signals ...................................................... 66
Figure 4.8. Structures of conventional and proposed sag detection methods ..... 67
Figure 4.9. The depth values of sag with conventional and proposed methods . 68
Figure 5.1. Power diagram of the (a) Proposed UPQC and (b) OPEN UPQC ... 71
Figure 5.2. Power circuit and control system of APF ......................................... 72
Figure 5.3. The single-phase equivalent circuit of APF...................................... 72
Figure 5.4. Experimental block diagram of APF ................................................ 78
Figure 5.5. The current transformers and voltage transducers ............................ 78
Figure 5.6. Picture of signal conditioning board of APF .................................... 79
Figure 5.7. Picture of firing and fault protection board ...................................... 80
Figure 5.8. APF control board ............................................................................ 80
Figure 5.9. IGBT driver cards for one of H-bridge inverters .............................. 81
Figure 5.10. APF inverter with DC link capacitors .............................................. 82
Figure 5.11. Choke reactors (on the top) and interface reactors (on the bottom) . 83
Figure 5.12. Harmonic polluting load ................................................................... 84
Figure 5.13. DVR system connected with energy storage .................................... 85
Figure 5.14. The single-phase equivalent circuit of DVR .................................... 85
Figure 5.15. Experimental block diagram of DVR ............................................... 91
Figure 5.16. View of disturbance generator system .............................................. 92
Figure 5.17. LEM LV25-400 voltage transducer cards ........................................ 93
Figure 5.18. Picture of signal conditioner/interface board ................................... 94
Figure 5.19. Three base VSI with IBGT modules and IGBT driver boards ......... 95
Figure 5.20. Passive LC filters for three-phases of DVR ..................................... 96
Figure 5.21. Single-phase injection transformers ................................................. 97
Figure 6.1. Simulation model of proposed APF control system ...................... 102
Figure 6.2a. PSCAD/EMTDC model of DVR control system: Reference signal
generation ...................................................................................... 103
Figure 6.2b. PSCAD/EMTDC model of DVR control system: Sag/swell
detection ......................................................................................... 104
Figure 6.3. PSCAD/EMTDC model of UPQC ................................................. 105


XIV
Figure 6.4. Sag detection signals for H-bridge inverters of supply voltages .... 106
Figure 6.5. The load current and generated reference currents ......................... 107
Figure 6.6. The waveforms of supply and load voltages for Case 1 ................. 109
Figure 6.7. RMS trends of supply and load voltages ........................................ 109
Figure 6.8. Waveforms of supply voltages and supply currents during Case 1 110
Figure 6.9. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 1................................... 111
Figure 6.10. The waveforms of supply and load voltages for Case 2 ................. 112
Figure 6.11. RMS trends of supply and load voltages ........................................ 113
Figure 6.12. Waveforms of supply voltages and currents during Case 2 ............ 114
Figure 6.13. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 2................................... 114
Figure 6.14. Three-phase voltage and current waveforms at starting of
single-phase 25% voltage sag for Case 2 ....................................... 116
Figure 6.15. Three-phase voltage and current waveforms at ending of
single-phase 25% voltage sag for Case 2 ....................................... 116
Figure 6.16. The waveforms of supply and load voltages for Case 3 ................. 117
Figure 6.17. RMS trends of supply and load voltages ........................................ 118
Figure 6.18. The waveforms of supply voltages and currents during Case 3 ..... 119
Figure 6.19. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 3................................... 119
Figure 6.20. Three-phase voltage and current waveforms at starting of double
phase 20% voltage sag for Case 3 .................................................. 121
Figure 6.21. Three-phase voltage and current waveforms at ending of double
phase 20% voltage sag for Case 3 .................................................. 122
Figure 6.22. PSCAD/EMTDC model of OPEN UPQC ...................................... 123
Figure 6.23. The waveforms of supply and load voltages for Case 4 ................. 124
Figure 6.24. RMS trends of supply and load voltages ........................................ 125
Figure 6.25. Waveforms of supply voltages and supply currents during Case 4 125
Figure 6.26. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 4................................... 126


XV
Figure 6.27. The waveforms of supply and load voltages for Case 5 ................. 127
Figure 6.28. RMS trends of supply and load voltages ........................................ 128
Figure 6.29. Waveforms of supply voltages and currents during Case 5 ............ 129
Figure 6.30. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 5................................... 129
Figure 6.31. Three-phase voltage and current waveforms at starting of
single-phase 25% voltage sag for Case 5 ....................................... 131
Figure 6.32. Three-phase voltage and current waveforms at ending of
single-phase 25% voltage sag for Case 5 ....................................... 132
Figure 6.33. The waveforms of supply and load voltages for Case 6 ................. 133
Figure 6.34. RMS trends of supply and load voltages ........................................ 133
Figure 6.35. Waveforms of supply voltages and currents during Case 6 ............ 134
Figure 6.36. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 6................................... 135
Figure 6.37. Three-phase voltage and current waveforms at starting of double
phase 20% voltage sag for Case 6 .................................................. 136
Figure 6.38. Three-phase voltage and current waveforms at ending of double
phase 20% voltage sag for Case 6 .................................................. 137
Figure 7.1. PWM signals for H-bridge inverters of Phase_A and Phase_B ..... 141
Figure 7.2. Reference currents using traditional and improved IRPT methods 142
Figure 7.3. Experimental diagram of UPQC system with measurement points 143
Figure 7.4. RMS trends of supply and load voltages ........................................ 144
Figure 7.5. Waveforms of supply voltages and supply currents during Case 1 144
Figure 7.6. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 1................................... 145
Figure 7.7. RMS trends of supply and load voltages ........................................ 146
Figure 7.8. Waveforms of supply voltages and currents during Case 2 ............ 147
Figure 7.9. Waveforms of Phase_A supply/injected/load voltages;
supply/filter/load currents during Case 2 ....................................... 148
Figure 7.10. Three-phase voltage and current waveforms at starting of
single-phase 25% voltage sag for Case 2 ....................................... 149


XVI
Figure 7.11. Three-phase voltage and current waveforms at ending of
single-phase 25% voltage sag for Case 2 ....................................... 150
Figure 7.12. RMS trends of supply and load voltages ........................................ 150
Figure 7.13. Waveforms of supply voltages and currents during Case 3 ............ 151
Figure 7.14. Waveforms of Phase_A supply/injected/load voltages;
supply/filter/load currents during Case 3 ....................................... 152
Figure 7.15. Three-phase voltage and current waveforms at starting of double
phase 20% voltage sag for Case 3 .................................................. 153
Figure 7.16. Three-phase voltage and current waveforms at ending of double
phase 20% voltage sag for Case 3 .................................................. 154
Figure 7.17. Experimental diagram of OPEN UPQC with measurement points 155
Figure 7.18. RMS trends of supply and load voltages ........................................ 155
Figure 7.19. Waveforms of supply voltages and supply currents during Case 4 156
Figure 7.20. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 4................................... 157
Figure 7.21. RMS trends of supply and load voltages ........................................ 158
Figure 7.22. Waveforms of supply voltages and currents during Case 5 ............ 159
Figure 7.23. Waveforms of Phase_A supply/injected/load voltages;
supply/filter/load currents during Case 5 ....................................... 160
Figure 7.24. Three-phase voltage and current waveforms at starting of
single-phase 25% voltage sag for Case 5 ....................................... 161
Figure 7.25. Three-phase voltage and current waveforms at ending of
single-phase 25% voltage sag for Case 5 ....................................... 162
Figure 7.26. RMS trends of supply and load voltages ........................................ 162
Figure 7.27. Waveforms of supply voltages and currents during Case 6 ............ 163
Figure 7.28. Waveforms of Phase_A supply/injected/load voltages;
supply/filter/load currents during Case 6 ....................................... 164
Figure 7.29. Three-phase voltage and current waveforms at starting of double
phase 20% voltage sag for Case 6 .................................................. 165
Figure 7.30. Three-phase voltage and current waveforms at ending of double
phase 20% voltage sag for Case 6 .................................................. 166


XVII



XVIII
LIST OF SYMBOLS

C
DC
: DC link capacitor
C
f
: Filter capacitance
e(t) : The error signal
E
d
: Nominal DC supply voltage
F : Farad
f
o
: Cutoff frequency
f
r
: Fundamental frequency
f
s
: Switching frequency
h : Harmonic order
H : Henry
I
aRef
: Active filter reference current
I
c
: Capacitor current
I
h
: h
th
harmonic current
I
inj
: Injected current
I
L
: Load current
I
LH
: Maximum demand load current (at fundamental frequency) at PCC
I
o
: Load current
I
s
: Supply current
I
SC
: Maximum short circuit current at point of common coupling
K : Filter factor
k : Modulation index
L
f
: Filter inductance
M : Mega
Mag(t) : Amplitude
ms : Milliseconds
p : Instantaneous real power
q : Instantaneous imaginary power
s : Seconds
Tr_A : Injection transformer for phase_A
u(t) : Input signal to the PLL


XIX
U
n
: Nominal voltage
V
a
: Phase_A voltage
V
b
: Phase_B voltage
V
c
: Phase_C voltage
V
d
: D component of voltage
V
DC
: DC link voltage
V
error
: Ideal reference voltage value for the PLL
V
inj
: Injected voltage
V
L
: Load voltage
V
o
: Nominal load voltage
V
oav
:Total harmonic of the load V
o

V
p
: Voltage phasor
V
peak
: Peak value of voltage
V
phase
: Phase voltage
V
q
: q component of voltage
V
rms
: RMS value of voltage
V
s
: Supply voltage
w
o
: Angular frequency
x(t) : Per unit sinusoidal voltage output of the PLL
y(t) : Output of the PLL
: Alpha component
: Beta component
(t) : Phase angle of the tracked signal
: Micro
: Ohm


XX
LIST OF ABBREVIATIONS


AC : Alternating Current
APF : Active Power Filter
ASD : Adjustable Speed Drive
CP : Custom Power
DC : Direct Current
DSP : Digital Signal Processor
DSTATCOM : Distribution Static Compensator
DVR : Dynamic Voltage Restorer
EMC : Electromagnetic Compatibility
EMI : Electromagnetic Interference
ET AL : And Others
FFT : Fast Fourier Transform
FPGA : Field Programmable Gate Array
GTO : Gate Turn-Off Thyristor
IEC : International Electrotechnical Commission
IEEE : Institute of Electrical and Electronics Engineers
IGBT : Insulated Gate Bipolar Transistor
IHD : Individual Harmonic Distortion
IRPT : Instantaneous Reactive Power Theory
KVA : Kilovolt Ampere
MC-UPQC : Multiconverter Unified Power Quality Conditioner
MVA : Megavolt Ampere
OPEN UPQC : OPEN Unified Power Quality Conditioner
PCC : Point of Common Coupling
PFC : Power Factor Correction
PI : Proportional Integral
PLC : Programmable Logic Controller
PLL : Phase Lock Loop
PQ : Power Quality


XXI
PSCAD/EMTDC : Power System Computer Aided Design/Electromagnetic
Transient DC Program
PU : Per Unit
PWM : Pulse Width Modulation
RMS : Root Mean Square
SARFIx : System Average RMS Frequency Index
SPWM : Sinusoidal Pulse Width Modulation
STS : Static Transfer Switch
TDD : Total Demand Distortion
THD : Total Harmonic Distortion
UPQC : Unified Power Quality Conditioner
UPS : Uninterruptible Power Supply
VSI : Voltage Source Inverter











1. INTRODUCTION Ahmet TEKE
1
1. INTRODUCTION

1.1.Background and Research Motivation

Power quality is defined as the concept of powering and grounding electronic
equipment in a manner that is suitable to the operation of that equipment and
compatible with the premise wiring system and other connected equipment in
Institute of Electrical and Electronics Engineers (IEEE) Standard 1159-1995 (IEEE
Std 519, 1995). International Electrotechnical Commission (IEC) defined power
quality as set of parameters defining the properties of power quality as delivered to
the user in normal operating conditions in terms of continuity of supply and
characteristics of voltage (frequency, magnitude, waveform and symmetry) (Meral,
2009).
There are two classes of power quality problems: phenomena due to low
quality of current drawn by the load caused by nonlinear loads and voltage
disturbances that cause faults in the power system (Sannino et al., 2003). The most
significant and critical power quality problems are voltage sags, voltage swells and
current harmonics. These problems may cause tripping of sensitive electronic
equipment with disastrous consequences in industrial plants where tripping of critical
equipment can bear the stoppage of the whole production with high costs associated
(Chen, 2005).
Custom Power devices also called as power quality compensator employ
power electronic or static controllers in medium or low voltage distribution systems
for the purpose of supplying a level of power quality that is needed by electric power
customers that are sensitive to root mean square (RMS) voltage variations and
voltage transients. CP devices include static switches, power converters, injection
transformers, master control modules and/or energy storage modules that have the
ability to perform current interruption and voltage regulation functions in a
distribution system to improve power quality (Sabin et al., 2003). CP devices are
generally used for voltage regulation, active filtering, load balancing or power factor
correction (Ghosh, 2002).
1. INTRODUCTION Ahmet TEKE
2
Active Power Filter is a shunt connected compensating device. The main
purpose of this device is to protect supply currents from current harmonics in the
load side (downstream). This is accomplished by rapid shunt current injection to
compensate for the harmonics in the load current. Dynamic Voltage Restorer is a
series connected compensating device that protects sensitive loads from sag/swell
disturbances in the supply side (upstream). This is performed by rapid series voltage
injection to compensate for the drop/rise in the supply voltage.
In recent years, Unified Power Quality Conditioner which offers customers
high quality of power has become an increased concern of engineers. UPQC is a
combination of a shunt (APF) and a series compensator (DVR) connected together
via a common direct current (DC) link capacitor. These devices compensate the
power quality disturbances such as current harmonics and voltage sag/swell to
protect sensitive process loads as well as improve service reliability. However, these
devices do not allow local distributors to guarantee different quality demand levels to
the final customers, because they improve power quality for all the supplied end
users. The installation investments are also quite high relative to the power quality
level obtained.
A solution that has similar performances and advantages, but also makes cost
reduction possible, is OPEN UPQC. This new solution, analyzed in (Morris et al.,
2009) as a simulation study, starts from UPQC configuration and removes the
common DC connection. Therefore, the control strategy is different than the
traditional combined series and shunt converters. Above all, OPEN UPQC can
stabilize load voltage, keep load voltage and supply current sinusoidal and balanced
as well.
The combination of APF and DVR concept being relatively new is still being
researched. It is considered that this will be a universal solution to all power quality
issues because of its voltage and current compensating capability (Jayanti, 2008). In
order to achieve the mitigation of PQ disturbances, new circuit topologies for UPQC
and new control techniques to detect and extract the PQ disturbances should be
examined.

1. INTRODUCTION Ahmet TEKE
3
1.2. Objectives and Organization of Thesis

The main objectives of this thesis are as follows.
1- To describe the power quality definitions, types of the PQ problems,
main sources of the PQ problems, negative influences of the PQ problems, PQ
standards, solutions to PQ problems and Custom Power concept.
2- To present literature survey of APF, DVR and UPQC with their control
algorithms and power circuit topologies.
3- To find/develop control methods for reference current extraction for APF,
To describe the modeling of APF,
To evaluate the performance of the APF with simulation studies,
To describe the experimental setup of APF,
To evaluate the performance of APF with experimental analysis.
4- To find/develop control methods for reference voltage generation and
sag/swell detection for DVR,
To describe the modeling of DVR,
To evaluate the performance of the DVR with simulation studies,
To describe the experimental setup of DVR,
To evaluate the performance of DVR with experimental analysis.
5- To describe the modeling of UPQC,
To evaluate the performance of the UPQC with simulation studies,
To describe the experimental setup of UPQC,
To evaluate the performance of UPQC (6 kVA, 220 V
l-l
) with experimental
analysis.
6- To describe the modeling of OPEN UPQC,
To evaluate the performance of the OPEN UPQC with simulation studies,
To describe the experimental setup of OPEN UPQC,
To evaluate the performance of OPEN UPQC (6 kVA, 220 V
l-l
) with
experimental analysis.
7- To present specific and practical recommendations on software and
hardware of the laboratory prototype implementations.
1. INTRODUCTION Ahmet TEKE
4
A small scale, simple and low cost UPQC and OPEN UPQC circuits are
designed, simulated and experimentally implemented. The power circuits of UPQC
topologies consist of DVR and APF and the control circuit employs new algorithms.
The results of the proposed UPQC and OPEN UPQC systems meet the international
standards for power quality.
After an introductory section where the background and research motivation
of the study are introduced, the structure of this thesis is as follows:
Chapter 2, power quality terms and definitions, types of the power quality
problems, overview of sources of the power quality problems, negative impacts of
the power quality problems and power quality standards are described. The
overviews of Custom Power devices namely Active Power Filter, Dynamic Voltage
Restorer and Unified Power Quality Conditioner are presented.
Chapter 3, after wide literature survey, the control algorithms and power
circuit configurations of each CP device are classified. The advantages and
disadvantages of both the controller methods and circuit topologies are clearly
emphasized.
Chapter 4, the controller algorithms of APF and DVR are presented. The
drawbacks associated with the conventional control technique are presented. The
reference current extraction algorithm of APF is based Instantaneous Reactive Power
Theory. The drawback associated with the conventional IRPT technique is presented
and the modified IRPT method is proposed. DVR with a new compensation method
and a new sag/swell detection method is presented. Both the reference voltage
extraction and sag detection algorithms are based Enhanced Phase Locked Loop and
nonlinear adaptive filter.
Chapter 5, the power circuit design procedure of APF and DVR are
presented. The power circuit of DVR is optimized to perform minimum power
injection and reduce the inverter losses. The designed APF protection board protects
the overall system by preventing the firing pulses going to Insulated Gate Bipolar
Transistor (IGBT) drivers. The laboratory design procedures of 6 kVA, 220 V
l-l

UPQC topologies are presented.
1. INTRODUCTION Ahmet TEKE
5
Chapter 6, modeling and simulation of UPQC and OPEN UPQC that are the
combination of APF and DVR are presented. Several case studies are performed to
show the validity of proposed UPQC and OPEN UPQC. APF is always on line and
eliminates the load current harmonics keeping the supply current almost sinusoidal.
DVR becomes online when a voltage sag is detected otherwise it is in off state.
Chapter 7, several laboratory tests are performed to show the performance of
proposed UPQC topologies experimentally. The capabilities of UPQC and OPEN
UPQC are deeply analyzed during steady state, transients and faults. The results of
experimental case studies are discussed. The advantages and disadvantages of UPQC
topologies are presented.
Chapter 8, the conclusions, contributions of the thesis and authors
recommendations for future work are explained.
Finally, all the references used in the thesis, biographical information of the
author and sections of the Appendix are presented.

1.3. Contributions of Thesis

The main differences and important contributions of this thesis can be
summarized as follows:
(i) OPEN UPQC is investigated as experimentally in UPQC literature for the
first time. OPEN UPQC is a relatively new device and not much work has yet been
reported on its theoretical, design procedure and experimental analysis. The
publications made as a result of this thesis will contribute to scientific literature. This
thesis will also contribute to the concept finding solutions to the electric power
quality problems and this will also pioneer the using of related devices in the world.
(ii) APF control algorithm is optimized for harmonic compensation of load
current under unbalanced supply voltages. The disadvantage of IRPT theory under
unbalanced supply voltages is eliminated by creating virtual alpha and beta
components. The number of voltage measurement points has been reduced using this
control approach.
1. INTRODUCTION Ahmet TEKE
6
(iii) An algorithm for unbalanced voltage sag detection is presented. A passive
filter with a low cut-off frequency is not used in the sag detection. The proposed
method can detect the single-phase voltage sags correctly. The extraction and tracking
of disturbances are fast and accurate when compared with the traditional detection
methods. Each phase of DVR is controlled independently thus minimum voltage
injection is obtained during unbalanced faults. During the standby operation of DVR,
two lower IGBTs in each phase remain turned on while the two upper IGBTs remain
turned off.
(iv) A reference voltage generation method is presented which is used in a
voltage compensation of DVR. Most of the methods in literature have drawbacks to
generate compensation signals experimentally when the supply voltage is distorted
and unbalanced. With this approach, distortions in the supply line are perfectly
filtered and a purely sinusoidal reference voltage is obtained.
(v) The wide literature survey for APF, DVR and UPQC has been
accomplished and 6 kVA DSP based laboratory prototypes of UPQC and OPEN
UPQC have been constructed.
(vi) Practical recommendations and suggestions for experimental study are
presented.

2. ELECTRIC POWER QUALITY Ahmet TEKE
7
2. ELECTRIC POWER QUALITY

Power quality has gained more importance in the power industry since the
last two decades 1980s (Dugan et al., 2003). Everybody does not agree with the use
of the term power quality, but they do agree that it has become a very important
aspect of power delivery especially in the second half of the 1990s. There is a lot of
disagreement about what power quality actually incorporates. Various sources use the
term power quality with different meanings. Other sources use similar but slightly
different terminology like quality of power supply or voltage quality (Bollen, 2001).

2.1. Power Quality Terminology

The term power quality has gained some official status already within the
IEEE, e.g., through the name of Standards Coordinating Committee 22: Power
Quality. But the international standards setting organization in electrical engineering
(IEC) does not yet use the term PQ in any of its standard documents. Instead it uses
the term Electromagnetic Compatibility, which is not the same as power quality
but there is a strong overlap between the two terms. Below, a number of different
terms will be discussed (Bollen, 2001). The definition of power quality given in the
IEEE dictionary originates in IEEE Std. 1100: Power quality is the concept of
powering and grounding sensitive equipment in a matter that is suitable to the
operation of that equipment. However, the following definition is given in IEC
61000-1-1: Electromagnetic compatibility is the ability of an equipment or system to
function satisfactorily in its electromagnetic environment without introducing
intolerable electromagnetic disturbances to anything in that environment. The most
common terms about PQ are explained below with their definitions (Bollen, 2001).
Current quality is concerned with deviations of the current from the ideal. The
ideal current is a single-frequency sine wave of constant frequency and magnitude.
An additional requirement is that this sine wave is in phase with the supply voltage.
Thus where voltage quality has to do with what the utility delivers to the consumer,
current quality is concerned with what the consumer takes from the utility. Voltage
2. ELECTRIC POWER QUALITY Ahmet TEKE
8
and current are strongly related and if either voltage or current deviates from the
ideal it is hard for the other to be ideal. Voltage quality is concerned with deviations
of the voltage from the ideal. The ideal voltage is a single-frequency sine wave of
constant frequency and constant magnitude. The term voltage quality can be
interpreted as the quality of the product delivered by the utility to the customers.
Power quality problem is defined as any power problem manifested in voltage,
current or frequency deviations that result in failure or misoperation of customer
equipment.
The power supply system can only control the quality of the voltage, it has no
control over the currents that particular loads might draw. Therefore, the standards in
the power quality area are devoted to maintaining the supply voltage within certain
limits. Any significant deviation in the waveform magnitude, frequency or purity is a
potential power quality problem. Of course, there is always a close relationship
between voltage and current in any practical power system. Although the generators
may provide a near-perfect sine-wave voltage, the current passing through the
impedance of the system can cause a variety of disturbances to the voltage (Dugan et
al., 2003). Power quality is often considered as a combination of voltage and current
quality. In most of the cases, it is considered that the network operator is responsible
for voltage quality at the point of connection while the customers load often
influences the current quality at the point of connection(Bhattacharyya et al., 2007),
(Meral, 2009).

2.2. Classification of Power Quality Problems and Their Impacts

The power quality is seriously disturbed due to the widely use of nonlinear
loads and various faults in power system. Moreover, the controlling equipment and
electronic devices based on computer technology demand higher levels of power
quality. This kind of devices are sensitive to small changes of power quality, a short-
time change on PQ can cause great economical losses. Because of the two reasons
mentioned above, no matter for the power business, equipment manufacturers or for
electric power customers, power quality problems had become an issue of increasing
2. ELECTRIC POWER QUALITY Ahmet TEKE
9
interest. Under the situation of the deregulation of power industry and competitive
market, as the main character of goods, power quality will affect the price of power
directly in near future (Zhao et al., 2004). The most common power quality problems
are given in Table A.1 in Appendix A (Almeida, 2003).
A number of national and local surveys helped to quantify the statistical
aspects of this problem. The most common disturbances and the most commonly
affected equipments are illustrated in Figure 2.1 (Emanuel, 1997). One report shows
that power outages and interruptions cost the U.S. economy between $104 billion
and $164 billion a year due to equipment damage, materials loss, idled labor and lost
production or sales and another $15 billion to $24 billion a year is lost due to power
quality phenomena (Liu et al., 2006).


Figure 2.1. Basic disturbances: (a) Causes at customer side, (b) Causes at utility side
and (c) Affected equipment

Another survey result is given in Figure 2.2. It is concluded that the voltage
sag/swell and harmonics are most common power problems encountered in the
industrial processes (Seng, 2002).


Figure 2.2. Percentage occurrences of PQ disturbances in equipment interruptions
2. ELECTRIC POWER QUALITY Ahmet TEKE
10
This thesis takes into account the most common power quality problems such
as voltage sags/swells and current harmonics as shown in Figure 2.3. Together they
account for high percentage of the power quality disturbances affecting most
commercial and industrial customers (Chen, 2005). The more detailed descriptions of
power quality problems were explained in (Meral, 2009).


Figure 2.3. Most common types of power quality problems

2.2.1. Current Harmonic Distortion

The harmonic voltage and current distortion are strongly linked with each
other because harmonic voltage distortion is mainly due to non-sinusoidal load
currents. Current harmonic distortion requires over-rating of series components like
transformers and cables. As the series resistance increases with frequency, a distorted
current will cause more losses than a sinusoidal current of the same rms value
(Bollen, 2001). Types of equipment that generate current harmonics are single-phase
loads, switched mode power supplies, electronic fluorescent lighting ballasts, small
Uninterruptible Power Supply (UPS) units and variable speed drives (Meral, 2009).
2. ELECTRIC POWER QUALITY Ahmet TEKE
11
The problems caused by current harmonics (Chapman, 2001a) are
overloading of neutrals, overheating of transformers, nuisance tripping of circuit
breakers, over-stressing of power factor correction capacitors and skin effect. The
annual added cost due to harmonics in military electric power installations is $716.3
million for the year 2001 (Liu et al., 2006).

2.2.2. Voltage Sags

Voltage sag is defined as a decrease to between 0.1 and 0.9 per unit (pu) in
rms voltage at the power frequency for durations from 0.5 cycle to 1 min. Voltage
sags are generally related with system faults but can also be caused by energization
of heavy loads or starting of large motors and overloaded wiring. The term sag
describes a short-duration voltage decrease. Although the term has not been formally
defined, it has been increasingly accepted and used by utilities, manufacturers and
end users. IEC definition for this phenomenon is dip. The two terms are considered
interchangeable, with sag being the preferred synonym in the U.S. power quality
community. Terminology used to describe the magnitude of a voltage sag is often
confusing. A 15 percent sag can refer to a sag which results in a voltage of 0.85 or
0.15pu. The preferred terminology would be one that leaves no doubt as to the
resulting voltage level: a sag to 0.85 pu or a sag whose magnitude was 15
percent. When not specified otherwise, a 15 percent sag will be considered an event
during which the rms voltage decreased by 15 percent to 0.85pu. The nominal or
base, voltage level should also be specified (Dugan et al., 2003).
Voltage sag problems in industrial equipment include (Eberhard et al., 2007)
relays opening due to the dip affecting the relays coil voltage, undervoltage sensors
on the AC mains operating unnecessarily, incorrect reports from sensors, such as air
flow sensors or water pressure sensors, circuit breakers or fuses operating, either due
to the increase in current on non-dipped phases or (more often) due to a large
increase in current immediately after the dip or a small section of highly-sensitive
electronics that responds incorrectly to the sag. Typical financial losses per voltage
sag for some types of industries are given in Table 2.1 (Chapman, 2001b).
2. ELECTRIC POWER QUALITY Ahmet TEKE
12
Table 2.1. Financial loss per voltage sag for some types of industries
Industry Typical financial loss per event
Semiconductor production 3.800.000
Financial trading 6.000.000 per hour
Computer centre 750.000
Telecommunications 30.000 per minute
Steel works 350.000
Glass industry 250.000

2.2.3. Voltage Swells

A voltage swell can be defined as an increase to between 1.1 and 1.8 pu in
rms voltage or current at the power frequency for durations from 0.5 cycle to 1 min.
The voltage swells are usually associated with system fault conditions, but they are
not as common as voltage sags. One way that a swell can occur is from the
temporary voltage rise on the unfaulted phases during a single line to ground fault.
(Dugan et al., 2003). Swells can also be caused by switching off a large load or
energizing a large capacitor bank, insulation breakdown, sudden load reduction and
open neutral connection. Voltage swells can negatively affect the performance of
sensitive electronic equipment, cause data errors, produce equipment shutdowns,
may cause equipment damage and reduce equipment life. It causes nuisance tripping
and degradation of electrical contacts. It also causes most of the problems as voltage
sag which explained above (Bangor, 2009).

2.3. Power Quality Standards

Standards are needed to achieve coordination between the characteristics of
the power supply system and the requirements of the end use equipment. This is the
role of power quality standards. The methods have been established for measuring
these phenomena and in some cases defining limits for satisfactory performance of
both the power system and connected equipment. In the international community,
both IEEE and IEC have created a group of standards that addresses these issues
from a variety of perspectives (McGranaghan et al., 2002).
2. ELECTRIC POWER QUALITY Ahmet TEKE
13
2.3.1. Standards Related with Voltage Characteristics

The most common international standards setting limits on voltage quality are
described below.

2.3.1.1. IEEE Standards

Short duration voltage variations include variations in the fundamental
frequency voltage that last less than one minute according to IEEE Standard 1159
and IEC definitions. These variations are best characterized by plots of the rms
voltage versus time but it is often sufficient to describe them by a voltage magnitude
and a duration that the voltage is outside of specified thresholds (McGranaghan,
2005). Voltage variations can be a momentary low voltage (voltage sag), high voltage
(voltage swell) or loss of voltage (interruption). IEEE Standard 1159 specifies
durations for instantaneous, momentary and temporary disturbances.
In IEEE, standards work under way to define indices for characterizing
voltage sag performance is being coordinated by IEEE P1564. The most common
index used is System Average RMS Frequency Index (SARFIx). This index
represents the average number of voltage sags experienced by an end user each year
with a specified characteristic. The SARFI index and other alternatives for describing
voltage sag performance are being formalized in the IEEE Standard 1564 Working
Group (McGranaghan, 2005).

2.3.1.2. IEC Electromagnetic Compatibility Standards

A comprehensive framework of standards on electromagnetic compatibility is
under development within the IEC. Electromagnetic compatibility (EMC) is defined
as: the ability of a device, equipment or system to function satisfactorily in its
electromagnetic environment without introducing intolerable electromagnetic
disturbances to anything in that environment. There are two aspects to EMC: A piece
of equipment should be able to operate normally in its environment and it should not
2. ELECTRIC POWER QUALITY Ahmet TEKE
14
pollute the environment too much. In EMC terms: immunity and emission. There are
standards for both aspects (Bollen, 2001). Immunity standards define the minimum
level of electromagnetic disturbance that a piece of equipment shall be able to
withstand. The basic immunity standard IEC-61000-4-1 gives four classes of
equipment performance: (i) Normal performance within the specification limits, (ii)
Temporary degradation or loss of function which is self-recoverable, (iii) Temporary
degradation or loss of function which requires operator intervention or system reset
and (iv) Degradation or loss of function which is not recoverable due to damage of
equipment, components or software or loss of data.
The maximum amount of electromagnetic disturbance that a piece of
equipment is allowed to produce is defined in emission standards. Within the existing
IEC standards, emission limits exist for current harmonics IEC 61000-3-2 and
61000-3-6 and for voltage fluctuations IEC 61000-3-3, 61000-3-5 and 61000-3-7.
Most power quality phenomena are not due to equipment emission but due to
operational actions or faults in the power system. As the EMC standards only apply
to equipment, there are no "emission limits" for the power system (Bollen, 2001).

2.3.1.3. The European Voltage Characteristics Standard

EN 50160 dealing with requirements concerning the suppliers side
characterizes voltage parameters of electrical energy in public distribution systems.
On the users side, it is the quality of power available to the users equipment that is
important. Correct equipment operation requires the level of electromagnetic
influence on equipment to be maintained below certain limits. Equipment is
influenced by disturbances on the supply and by other equipment in the installation,
as well as itself influencing the supply. These problems are summarized in the EN
61000 series of EMC standards, in which limits of conducted disturbances are
characterized.
European standard 50160 gives the main characteristics of the voltage at the
customer's supply terminals in public low-voltage and medium-voltage networks
under normal operating conditions. Some disturbances are just mentioned below, for
2. ELECTRIC POWER QUALITY Ahmet TEKE
15
others a wide range of typical values are given and for some disturbances actual
voltage characteristics are given (Bollen, 2001). Standard EN 50160 gives limits for
some variations. For each of these variations the value is given which shall not be
exceeded for 95% of the time. The measurement should be performed with a certain
averaging window. The length of this window is 10 minutes for most variations, thus
very short time scales are not considered in the standard.
The following limits for the low-voltage supply are given in the document
(Bollen, 2001):
Voltage magnitude: 95% of the 10-minute averages during one week shall
be within 10% of the nominal voltage of 230 V
Harmonic distortion: For harmonic voltage components up to order 25,
values are given which shall not be exceeded during 95% of the 10-minute averages
obtained in one week. The total harmonic distortion shall not exceed 8% during 95%
of the week.
Standard EN 50160 does not give any voltage characteristics for events. For
completeness a list of events mentioned in EN 50160 is reproduced below (Bollen,
2001), (Meral, 2009):
Voltage magnitude steps: These normally do not exceed 5% of the
nominal voltage, but changes up to 10% can occur a number of times per day.
Voltage sags: Frequency of occurrence is between a few tens and one
thousand events per year. Duration is mostly less than 1 second and voltage drops
rarely below 40%. At some places sags due to load switching occur very frequently.
Voltage swells: They occur under certain circumstances. Over voltages due
to short-circuit faults elsewhere in the system will generally not exceed 1.5 kV rms in
a 230V system.

2.3.2. Standards Related with Current Harmonics

The most common international standards setting limits on harmonics are
described in the following subsections.

2. ELECTRIC POWER QUALITY Ahmet TEKE
16
2.3.2.1. IEEE Standards

The current harmonic limits given in IEEE Std.519-1995 as requirements that
must be guaranteed by the end user is shown in Table 2.2. For the current harmonic
limits, Total Demand Distortion (TDD) calculation is used. TDD shown in (2.1) shall
be less or equal than proper values prescribed in Table 2.2. The term TDD is very
much like Total Harmonic Distortion (THD) as given in (2.2). The only difference is
the dominator. THD calculation compares the momentary measured harmonics with
the momentary measured fundamental component. TDD calculation compares the
momentary (but steady-state) measured harmonics with the maximum demand
current, which is not a momentary number at all. The difference between TDD and
THD is important because it prevents a user from being unfairly penalized for
harmonics during periods of light load (only the harmonic polluting loads are
running). During periods of light load it can appear that harmonic levels have
increased in terms of percent (THD calculation) even though the actual current
harmonics in amperes (TDD calculation) stayed the same (Blooming et al., 2007),
(Meral, 2009).

max
h
2
h
h 2
n
I
RMS harmonic current
TDD
I Max demand load current (15 or 30min)
=
= =


(2.1)

2 2
rms 1
Current
1
X X RMSsumof all harmonic current
THD
X RMS fundamental current

= =

(2.2)

Individual Harmonic Distortion (IHD) at a particular harmonic frequency is
the ratio of the rms of the harmonic under consideration to the rms value of the
fundamental as stated in (2.3).

Harmonic frequency
IHD .100
Fundamental frequency
= (2.3)
2. ELECTRIC POWER QUALITY Ahmet TEKE
17
As the problems caused by harmonics become recognized around the world,
standards setting bodies are creating electrical standards that define legal limits for
the level of current harmonics and voltages (Ingram, 1998). The Institute of
Electrical and Electronic Engineers has drafted a Recommended Practice (IEEE Std.
519, 1995) that provides limits for harmonic distortion. IEEE Std. 519 limits the
current harmonics that can be drawn from the power system.

Table 2.2. IEEE-519 current harmonic distortion limits
Maximum current harmonic distortion in percent of I
LH

Individual harmonic order (Odd harmonics)
I
SC
/I
LH
<11 11h<17 17h<23 23h<35 35h TDD
<20*
20<50
50<100
100<100
0>1000
4.0
7.0
10.0
12.0
15.0
2.0
3.5
4.5
5.5
7.0
1.5
2.5
4.0
5.0
6.0
0.6
1.0
1.5
2.0
2.5
0.3
0.5
0.7
1.0
1.4
5.0
8.0
12.0
15.0
20.0
Even harmonics are limited to 25% of the odd harmonic limits above
Current distortions that results in a DC offset, e.g., half-wave converters,
are not allowed
* All power generation equipment is limited to these values of current
distortions, regardless of actual I
SC
/I
LH
.

These limits are proportional to the short circuit current ratio and each
consumer must limit the current that they draw accordingly as shown in Table 2.2.
The aim of the standard is to ensure that voltage harmonic distortion is kept low by
limiting the current harmonics drawn by end users.

2.3.2.2. The International Electrotechnical Commission

IEC has a standard, IEC 61000-3-2, that defines current harmonic limits for
devices with a current rating less than or equal to 16A (Ingram, 1998). This has been
ratified as a Harmonized European Standard, EN 61000-3-2 and as a British Standard
(BS EN 61000-3-2, 1995). Unlike its predecessor (IEC 555-2, 1982), no distinction
is made between domestic and professional equipment, rack mounted and three-
phase equipment is specifically mentioned in BS EN 61000-3-2.
2. ELECTRIC POWER QUALITY Ahmet TEKE
18
For future, new standards and/or technical reports are currently being drafted
(Routimo, 2008). For example, limits for interharmonics (IEC 61000-3-9) and
emission limits for frequency range 2-9 kHz (IEC 61000-3-10) will apply to
equipment with input current lower than 16 A. In addition, IEC 61000-3-14 will
assess emission limits for the connection of disturbing installations to low voltage
power systems. The limits specified in IEC for low-voltage systems allow a THD of
8% and include limits for individual harmonic components, which decrease with
frequency.

2.3.2.3. Energy Networks Association Engineering Recommendation G5/4

The intention of the Energy Networks Association Recommendation G5/4,
first published in 2001, was to try to ensure that the levels of harmonics in the Public
Electricity Supply do not constitute a problem for other users of that supply. This is a
primary function of EMC Management and Regulation and it forms part of the
Distribution Code which is a statutory requirement placed on the UK Electricity
Supply Industry. In addition, under EU legislation the supply industry has a duty to
meet BS EN 50160, voltage characteristics of electricity supplied by public
distribution systems, which includes magnitudes of harmonic voltage distortion
among other parameters. To facilitate the connection of non-linear equipment, G5/4-
1 specifies current harmonic emission limits with the intention of limiting the overall
voltage distortion to no more than the network planning levels specified in ER G5/4-
1, which in turn are set to achieve compatibility (Ena, 2006).
G5/4-1 identifies consumers by their point of common coupling (PCC) to the
supply and applies limits at that point. G5/4-1 therefore applies to every consumer
connected to the Public Electricity Supply, including domestic, commercial, shop and
office consumers and industrial users.
It forms part of the consumers agreement to connect and it is the
responsibility of the individual consumer to ensure that the appropriate procedures to
agree connection of new loads are followed. It is also very important that the
consumer understands the responsibilities placed on him by the supply utilities to
2. ELECTRIC POWER QUALITY Ahmet TEKE
19
avoid the possibility of having to implement costly remedial measures in the event of
a problem. It is important to understand that G5/4-1 is effectively an Installation
Standard and applies to the total harmonic generating equipment installed by a
consumer. It is not a product or equipment standard and no single items of equipment
can be said to comply.

2.4. Custom Power Devices to Mitigate Power Quality Problems

The mitigation device and point of connection is chosen according to its
economic feasibility and reliability that is required. Innovative solutions employing
power electronics are often applied when rapid response is essential for suppressing
or counteracting the disturbances, while conventional devices are well suited for
steady-state or general regulation (Arora et al., 1998). There are two general
approaches to mitigate the PQ problems. One, named as load conditioning, is to
ensure that the process equipment is less sensitive to disturbances, allowing it to ride
through the disturbances. The other is to install a line conditioning device that
suppresses or counteracts the disturbances (Rudnick et al., 2003). Commercially
available mitigation devices tend to protect against a group of PQ disturbances.
Mitigation devices vary in size and can be installed at all voltage levels of a power
system (high, medium and low voltages).
Custom Power is a concept based on the use of power electronic controllers
in the distribution system to supply value-added, reliable and high quality power to
its customers. CP devices or controllers include APFs and DVRs that have the ability
to perform harmonic mitigation and voltage compensation functions in a distribution
system to improve reliability and/or power quality (Sabin et al., 2003). For simple
load applications, selection of the proper mitigation device is fairly straightforward.
However, in large systems with many loads all aspects of the power system must be
considered carefully. Also, when dealing with large systems it is necessary to know
the different sensitive load requirements. Consideration must also be given to the
potential interaction between mitigation devices, connected loads and the power
system (Arora, 1998).
2. ELECTRIC POWER QUALITY Ahmet TEKE
20
2.4.1. Custom Power Devices

Harmonic current flowing through the impedance of power system results in
harmonic voltage drop at the load bus and along the feeder. Faults on transmission or
distribution system can cause voltage sag at the load bus and along the feeder as
shown in Figure 2.4. Custom power devices are a special category of power
conditioning equipment, used to protect the entire facility from such voltage
disturbances (Ghosh, 2002). Custom power devices have to work within parts of a
cycle, thanks to the advancements in power electronics technology, such that the load
bus will not be affected by the supply disturbance.
CP solutions can be categorized as network reconfiguring type or
compensating type (Ghosh, 2002). The network reconfiguring devices are usually
called switchgear and they include current limiting, circuit breaking and current
transferring devices. Network reconfiguring types are Static Current Limiter, Static
Circuit Breaker and Static Transfer Switch (STS). The compensating devices
compensate a load, correct its power factor, unbalance or improve the quality of
supplied voltage. Compensating types are Active Power Filter (also called as
Distribution Static Compensator), Dynamic Voltage Restorer and Unified Power
Quality Conditioner.

2. ELECTRIC POWER QUALITY Ahmet TEKE
21

Figure 2.4. Single line diagrams of a real system with/without CP devices

The basic circuit diagram of APF is shown in Figure 2.5. APF is shunt
connected device that can eliminate the nonlinear load harmonics and can
compensate load reactive current.


Figure 2.5. Circuit diagram of a shunt APF
2. ELECTRIC POWER QUALITY Ahmet TEKE
22
Dynamic Voltage Restorer is a series compensating device and the basic
diagram of a DVR is shown in Figure 2.6. It is used for protecting a sensitive load
that is connected downstream from sag/swell. It can also regulate the bus voltage at
the load terminal.


Figure 2.6. Circuit diagram of a DVR

UPQC consists of two voltage source inverters. It can simultaneously perform
the tasks of APF and DVR. The basic circuit diagrams of UPQC and OPEN UPQC
are shown in Figure 2.7. UPQC and OPEN UPQC protect the loads against voltage
sag, swell, voltage unbalance, harmonics and poor power factor.
UPQC is a combination of a shunt (Active Power Filter) and a series
compensator (Dynamic Voltage Restorer) connected together via a common DC link
capacitor. OPEN UPQC (a new topology of UPQC) consists of DVR and APF
supplied from separate DC link sources. OPEN UPQC allows local distributors to
supply different grades of power to the final customers.
2. ELECTRIC POWER QUALITY Ahmet TEKE
23

Figure 2.7. Circuit diagram of (a) UPQC and (b) OPEN UPQC

2.4.2. Comparisons of Power Quality Mitigation Devices

Power quality problems can be mitigated using traditional and power
electronics based devices. DVR, STS and UPS are most common types of voltage
sag mitigation devices. DVR is usually designed to mitigate voltage dips with
magnitude lower than 50% (Bongiorno et al., 2003). STS can limit the duration of
interruptions and voltage sags/swells to less than one half-cycle in most cases, by
transferring the load from the affected line to a back-up feeder. This high speed of
response is obtained by using two static switches, constituted each by two
antiparallel thyristors, to perform the transfer of the load. The topologies of DVR and
STS are shown in Figure 2.8.

2. ELECTRIC POWER QUALITY Ahmet TEKE
24

Figure 2.8. The topologies of DVR and STS

DVR is not suitable to compensate for interruptions of the supply voltage and
the range of sags that it can mitigate depends on the size of the energy storage.
However, STS cannot mitigate sags that affect both feeders (Benachaiba et al., 2008).
DVR costs less compared to the UPS systems. UPSs have typically been designed
for the correction of different types of voltage disturbances fall into the category of
voltage sags.
Taking the UPS as an example, this has two major implications
(Ramachandaramurthy et al., 2004). First, the energy that a UPS is required to store
is based upon the long duration of a typical voltage outage or blackout, not relatively
short duration voltage sag as shown in Figure 2.9. Secondly, UPS systems are
typically designed for small loads, such as a computer mainframe or low power
safety critical systems. At high power levels, the cost of a UPS system can be
prohibitive as the UPS would need to be able to withstand not only the load current,
but also the full load voltage.


Figure 2.9. The topology of UPS

2. ELECTRIC POWER QUALITY Ahmet TEKE
25
In terms of minimum apparent power injection or size of the coupling
transformer, the performance of a DVR is found to be superior to a Distribution
Static Synchronous Compensator (DSTATCOM). DVR is also smaller in size and
costs less compared to the DSTATCOM. The amount of apparent power injection
required by a DSTATCOM to correct a given voltage sag is much higher than that of
a DVR. The main reason of that is a DVR corrects the voltage sag only on the
downstream side (Haque, 2001).
Tap changing transformer is another solution where it only takes care of a
limited range of voltage sag. The tap-changing transformer is: slow in response,
exhibits contact erosion, needs routine maintenance of its parts, has an uneconomical
size and requires frequent replacement of transformer oil (Singh et al., 2004).
Compared to the other devices, DVR is clearly considered to be one of the best
economic solutions for its size and capabilities (Benachaiba et al., 2008).
When a Static Synchronous Compensator is employed at the distribution level
or at the load end for power factor improvement, active harmonic filtering, dynamic
load balancing, flicker mitigation and voltage regulation alone it is called as
DSTATCOM. DSTATCOM is a fast-compensating reactive power source thats
applied on the transmission or distribution system to reduce voltage variations such
as sags, surges and flicker, along with instability caused by rapidly varying reactive
power demand. DSTATCOM can also help provide quick recovery for the
transmission system after contingency events such as loss of part of the system or
individual equipment. DSTATCOM is well suited to a major goal of the smart grid:
Integration of renewable energy sources, such as wind, concentrated solar and tidal
power generation. It allows these renewable energy sources to meet utility
interconnection requirements, as well as the power factor, voltage output and low-
voltage ride-through requirements of various worldwide grid codes. When it is used
to do harmonic filtering and reactive power compensation, it is called as Active
Power Filter (Ara et al., 2003), (S&C, 2010).
The use of isolation and harmonic reduction transformers, passive filters and
active solutions are main methods for harmonic mitigation (Chapman, 2001a).
Passive filters are used to provide a low impedance path for current harmonics so
2. ELECTRIC POWER QUALITY Ahmet TEKE
26
that they flow in the filter and not the supply. Passive filters are suited only to
particular harmonics, the isolating transformer being useful only for triple-N
harmonics and passive filters only for their designed harmonic frequency. In some
installations the harmonic content is less predictable. In many IT installations, for
example, the equipment mix and location is constantly changing so that the harmonic
culture is also constantly changing. A convenient solution is the active filter or active
conditioner.
Power Factor Correction (PFC) techniques include both passive and active
solutions for eliminating harmonic distortion and improving power factor. The
passive approach uses inductors, transformers, capacitors and other passive
components to reduce harmonics and phase shift. The passive approach is heavier
and less compact than the active approach, which is finding greater favor due to new
technical developments in circuitry, superior performance and reduced component
costs. Specially corrected transformers are effective only for certain harmonic
frequencies and most passive filters, once installed and tuned, are difficult to upgrade
and may generate harmful system resonance. As for active PFC techniques, they
must be applied to each individual power supply or load in the system, which
complicates architecture and results in high system cost.
Unlike traditional PFC techniques, APF supplies only the harmonic and
reactive power required to cancel the reactive currents generated by nonlinear loads.
In this case, only a small portion of the energy is processed, resulting in greater
overall energy efficiency and increased power processing capability (Brooks, 2004).
APF utilizes harmonic or current injection to achieve PFC. APF determines the
harmonic distortion on the line and injects specific currents to cancel the reactive
loads. This technique has been used for years in high-power, three-phase systems, but
high costs and complicated high-speed circuitry made it impractical for low-level
power systems. However, new techniques that utilize simpler circuitry are making
active power filtering more attractive and advantageous for low power, single-phase
systems. APF is connected in parallel to the front end or AC input of the system and
corrects all loads directly from the AC line. This type of APF provides excellent
harmonic filtering that complies with international harmonic regulations.
2. ELECTRIC POWER QUALITY Ahmet TEKE
27
2.4.3. Cost Range of Custom Power Devices

An overview of events that can be mitigated by the custom power devices
mentioned in this thesis is provided in Table 2.3. Each of these technologies has
found its way into several applications, either as demonstration projects or as cost-
effective and viable solutions to distinct types of PQ problems (Perry et al., 2003).

Table 2.3. Custom power device application matrix

APF STS DVR
Backup Energy
Supply Device
Voltage Sag
2

1

4

Voltage Swell
Momentary Interruption




Capacitor Switching
Transient




Voltage Regulation

Flicker

Harmonics
3


Reactive Power
Compensation


Cost Range (US$)
120 to 175
per kVAR
500 to 1000
per A
150 to 250
per kVA
750 to
1500 per kVA

1
Generally corrects up to 100% of nominal for load-induced sag to 65% to 70% of
nominal. Corrects up to 90% of nominal for load-induced sag to 55% to 60%. This
technology is not a typical solution for power-system fault-induced voltage sags.
2
Generally corrects up to between 90% and 100% for a sag to 20% of nominal.
3
One model corrects to the 25
th
harmonic, one model corrects to the 17
th.

4
One device corrects for voltage sags and momentary interruptions. Others typically
correct for voltage sags down to 50%.




2. ELECTRIC POWER QUALITY Ahmet TEKE
28
2.5. Summary

Some types of the power quality problems are voltage sag/swell, interruption,
voltage fluctuation, voltage unbalance, current harmonic, current unbalance and
current unbalance. Among them, voltage sags/swells and current harmonics are the
most common power quality problems. Some PQ reports indicate that poor PQ can
cause large financial losses to different types of industries. The limits of PQ
problems are generally set by IEEE and IEC standards.
Custom Power is a concept based on the use of power electronic controllers
in the distribution system to supply value-added, reliable and high quality power to
its customers by eliminating PQ problems. CP devices or controllers, include APFs
and DVRs that have the ability to perform harmonic mitigation and voltage
compensation functions in a distribution system to improve reliability and/or power
quality (Sabin et al., 2003). UPQC and OPEN UPQC topologies consist of two
voltage source inverters and it can simultaneously perform the tasks of APF and
DVR with different circuit topologies. UPQC do not allow local distributors to
guarantee different quality demand levels to the final customers, because they
improve power quality for all the supplied end users. The installation investments are
also quite high relative to the power quality level obtained. A solution that has
similar performances and advantages, but also makes cost reduction possible, is
OPEN UPQC.
The next chapter presents the wide literature survey on Active Power Filter,
Dynamic Voltage Restorer and Unified Power Quality Conditioner.

3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
29
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES

The related survey studies are presented under the following heads.

3.1. Literature Review of Active Power Filter

Power electronics based devices/equipments are a major key component of
todays modern power processing, at the transmission as well as the distribution level
because of the numerous advantages offered by them. These devices, equipments,
nonlinear load including saturated transformers, arc furnaces and semiconductor
switches and so on, draw non-sinusoidal currents from the utility. Therefore a typical
power distribution system has to deal with harmonics and reactive power support
(Khadkikar et al., 2009a), (Teke et al., 2010b).
The presence of harmonics and reactive power in the grid is harmful, because
it will cause additional power losses and malfunctions of the grid components (Luo
et al., 2009). Conventionally, passive filters composed of tuned L-C components
have been widely used to suppress harmonics because of their low initial cost and
high efficiency. However, passive filters have many disadvantages, such as large
size, mistuning, instability and resonance with load and utility impedances (Shuai et
al., 2009). Active Power Filters have now become an alternative solution for
controlling current harmonics in supply networks at the low to medium voltage
distribution level or for reactive power and/or voltage control at high voltage
distribution level (Habrouk et al., 2000). APF such as shunt APFs, series APFs,
hybrid APFs, UPQC and other combinations have made it possible to mitigate some
of the major power quality problems (Khadkikar et al., 2009b).
The main circuit of APF is shown in Figure 3.1. APF system can be divided
into two sections as: The control unit and the power circuit. Control unit consists of
reference signal generation, gate signal generation, capacitor voltage balance control
and voltage/current measurement. Power circuit of APF is generally comprised of
energy storage unit, DC/AC converter, harmonic filter and system protection.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
30

Figure 3.1. Basic representation of APF

The findings of the comprehensive literature survey summarize the available
studies related with the control unit and the power circuit of APF.

3.1.1. Power Circuit Topologies of APF

APFs are basically categorized into four types, namely, two-wire (single-
phase) (Fujita, 2009), three-phase three wire (Shuai et al., 2009), three-phase three-
wire with Zig-Zag transformer (Jou et al., 2008) and three-phase four wire
(Vodyakho et al., 2009a) configurations to meet the requirements of the three types
of nonlinear loads on supply systems (Singh et al., 1999). Basic topologies of APF
are shown in Figure 3.2.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
31

Figure 3.2. Various power circuit topologies of APF: (a) Three-phase 3/4 wire based,
(b) Three-phase with uncontrolled rectifier and (c) Cascaded multilevel
inverter based
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
32
APFs are used in low power (<100 kVA), medium power (100 kVA-10 MVA)
and high power (>10 MVA) applications (Habrouk et al., 2000). For low power
applications, APFs can be applied for single-phase and three-phase systems. For
single-phase systems, APFs generally mitigate the current harmonics. For three-
phase systems, APFs generally provide acceptable solution for unbalanced load
currents and mitigate the current harmonics. For medium power applications, the
main aim is to eliminate or reduce the current harmonics. Because of economic
considerations, reactive power compensation using active filters at the high voltage
distribution level is not generally regarded as viable (Habrouk et al., 2000). For high
power applications, the harmonic pollution in high-power ranges is not such a major
problem as in lower-power systems. One of the few applications of active filters in
high power systems is the installation of parallel combination of several active filters
because the control and co-ordination requirements of these filters are complicated.
The power circuit of APF generally consists of DC energy storage unit, DC/AC
converter and passive filter.
DC capacitor serves two main purposes: (1) it maintains a DC voltage with a
small ripple in steady state and (2) it serves as an energy storage element to supply
the real power difference between load and supply during the transient period (Jain et
al., 2003). DC link voltage should be higher than maximum peak of the supply
voltage. DC link voltage can be controlled using proportional-integral-derivative
controller (Rahim et al., 2005), PI controller (Singh et al., 2007) and fuzzy logic
(Brahim et al., 2010). In (Shuai et al., 2009), DC link is fed from separate voltage
supply to stabilize DC-side voltage within a certain range. Switched capacitor APF
that brings new dimension to APF as it reduces components and ratings (particularly
capacitor) while performing at low switching frequency is evaluated in (Radzi et al.,
2009). DC link, instead of a capacitor, is used as a battery pack, which is charged
from a photovoltaic array in (Flores et al., 2009). DC link is fed from renewable
energy sources in (Singh et al., 2011).
The converter types of APF can be either Current Source Inverter (Terciyanli
et al., 2011) or Voltage Source Inverter (VSI) (Singh et al., 1999) bridge structure.
VSI structures with Insulated Gate Bipolar Transistor (IGBTs) or Gate Turn Off
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
33
Thyristor (GTO) have become more dominant, since it is lighter, cheaper and
expandable to multilevel and multi step versions, to enhance the performance with
lower switching frequencies. IGBTs are generally used up to 1 MVA rating, GTO
thyristors are generally used higher than 1 MVA rating (Singh et al., 1999).
Power circuit configuration of APFs can be parallel active filter (Uyyuru et
al., 2009), series active filter (Senturk et al., 2009) and combination of series and
parallel filters (Singh et al., 1999), (Habrouk et al., 2000). The purpose of parallel
active filters is to cancel the load current harmonics fed to the supply. It can also
perform the reactive power compensation and balancing of three-phase currents. The
series active filter produces a PWM voltage waveform which is added/subtracted
to/from the supply voltage to maintain a purely sinusoidal voltage waveform across
the load. However, series active filters are less common industrially than their rivals,
parallel active filters. Combinations of several types of filter can achieve greater
benefits for some applications. The examined combinations are combination of both
parallel and series active filters, combination of series active and parallel passive
filters, combination of parallel active and passive filters (Luo et al., 2010) and active
filter in series with parallel passive filters (Salmeron et al., 2010). Seven-level APF
configuration is also examined in (Massoud et al., 2004), (Xiao et al., 2009).
Multilevel three-leg center-split VSIs are more preferable in medium and large
capacity applications due to lower initial cost and fewer switching devices that need
to be controlled (Dai et al., 2008). The series stacked multilevel converter topology,
which allows standard three-phase inverters to be connected with their DC busses in
series is chosen in (Henning et al., 2008). This converter has both regenerated energy
generation and active power filtering capabilities.
An inductance for output filtering of VSI is used to eliminate the harmonic at
different frequencies. The different combinations of L and C filters to attenuate the
switching ripple currents are examined in (Routimo et al., 2007). A rectifier
employing phase control with extra low inductance characteristic or load which high-
frequency input current, may affect APF and causing it to malfunction or shutdown.
While APF is being applied to this type of load, a reactor (3%~5%) is recommended
to install at the input side of the load to reduce the rising rate of load input current
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
34
(Enersine, 2010). LC passive filter is used in (Shuai et al., 2009) for harmonic
elimination and reactive power compensation. LCL lter is used in (Vodyakho et al.,
2009) that gives advantages in costs and dynamic performance since smaller
inductors can be used compared to L-lter in order to achieve the necessary damping
of the switching harmonics.

3.1.2. Control Techniques of APF

Active power filters are generally designed to compensate current harmonic,
reactive power, voltage harmonic and to balance the supply current and supply
voltage. Control strategy is based on the overall system control, extraction of
reference signal, capacitor voltage balance control and generation of gating signals as
shown in Figure 3.3.


Figure 3.3. Control unit of APF with a specified power circuit topology

The general control techniques to overcome these PQ disturbances are open
loop control system and closed loop control system. The closed loop control systems
can be further subdivided into other techniques as constant capacitor voltage
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
35
technique, constant inductor current technique, optimization techniques and linear
voltage control technique (Habrouk et al., 2000).
Classification according to current/voltage reference estimation techniques
can be made as time domain control and frequency domain control that are processed
by the open loop or closed loop control techniques (Habrouk et al., 2000). Control
strategy in the frequency domain is based on the Fourier analysis of the distorted
voltage or current signals to extract compensating current/voltage reference (Singh et
al., 1999). Frequency domain approaches are suitable for both single and three-phase
systems. The frequency domain algorithms are sine multiplication technique
(Habrouk et al., 2000), conventional Fourier and Fast Fourier Transform (FFT)
algorithms (Fathi et al., 2006) and modified Fourier series techniques (Salam et al.,
2006). Control methods of APFs in the time domain are based on instantaneous
derivation of compensating commands in the form of either voltage or current signals
from distorted and harmonic polluted voltage or current signals (Singh et al., 1999).
Time domain approaches are mainly used for three-phase systems. The time domain
algorithms are Dq method (Fathi et al., 2006), synchronous flux detection algorithm
(Li et al., 2006), fictitious power compensation algorithm (Silva et al., 2008),
constant active power algorithm, constant (unity) power factor algorithm (Flores et
al., 2009), IRPT (p-q) (Mauricio et al., 2009) and neural network (Brahim et al.,
2010). A component that has a frequency between the two frequencies is called an
interharmonic. A method for real-time detection and extraction of interharmonic
components in a power signal with potentially time-varying characteristics is
presented in (Mojiri et al., 2010).
The measurements of load voltage, load current, injected current and
capacitor voltage are required for reactive current extraction (Mauricio et al., 2009).
However, the measurements of load current, injected current and capacitor voltage is
enough for only current harmonic extraction in (Karimi et al., 2003). In (Azevedo et
al., 2008), there is no need to measure the load current or power to calculate the
reference currents.
The switching signals for the solid state devices of APF are generated using
PWM (Massoud et al., 2004), space vector modulation (Zhang et al., 2007), fuzzy
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
36
logic based control techniques (Qu et al., 2007), sliding-mode (Matas et al., 2008),
hysteresis (Vodyakho et al., 2010), multiresonant controller (Pucci et al., 2009) or
deadbeat controller (Fujita, 2009). The capacitor voltage balance control is
performed using PI controller (Jiang, 2001), artificial neural network based adaptive
PI controller (Bhattacharya et al., 2008), space vector modulation (Zhang et al.,
2008) and fuzzy controller (Kumar et al., 2009) methods.
The digital controllers used in APF for real time applications are combination
of DSP and Field Programmable Gate Array (FPGA) (Fujita, 2009), processor board
(Firlit, 2005), FPGA (Shu et al., 2008) and DSP (Kedjar et al., 2009).

3.1.3. Active Power Filter in Service

Applications of shunt active filters are expanding, not only into industry and
electric power utilities but also into office buildings, hospitals, water supply utilities
and rolling stock (Akagi, 1996), (Akagi, 2000), (Bae et al., 2006). The field
applications of APF are:
Shunt APF of 440V 200-kVA and a shunt active filter of 210V 75-kVA,
designed by Toyo Electric-Manufacturing Company, have been installed for
harmonic compensation at water supply facilities in Takatsuki-City, Japan.
300-kVA Shunt APF manufactured by Meidensha Corporation has been
installed to compensate for harmonic currents generated by eight adjustable speed
drives.
1.5-MW inverter and APF system for the injection of regenerated energy
in a Spoornet Traction Substation (one of South-Africas largest railway companies).
21-MVA APF using 4.5-kV 1.5-kA injection-enhanced gate transistors
manufactured by Toshiba-Mitsubishi-Electric Industrial Systems Corporation.
48-MVA APF manufactured by Central Japan Railway Company.
The alternative solution to APF for reactive power compensation can be
capacitor banks and thyristor controlled reactors. The alternative solution to APF for
harmonic mitigation is passive filters. However, APF provides better power quality
than its alternative solutions and it has fast response and fewer transients.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
37
3.2. Literature Review of Dynamic Voltage Restorer

Dynamic Voltage Restorer (also known as Static Series Compensator (Lee et
al., 2004), (Awad et al., 2004), (Awad et al., 2005)) maintains the load voltage at a
desired magnitude and phase by compensating the voltage sag/swell, voltage
unbalance and voltage harmonics presented at the point of common coupling
(Ramachandaramurthy et al., 2004), (Mahesh et al., 2008), (Jowder, 2009), (Teke et
al., 2010a). In order to mitigate voltage disturbances, DVR injects voltages of
suitable magnitude and phase in series with the line as shown in Figure 3.4. During
standby operation, DVR neither absorbs nor delivers real power. However, when
voltage sag/swell occurs in the system, DVR delivers/absorbs real power transiently
to/from DC link. Many loads facilitated in industrial plants such as adjustable speed
drives and process control equipments are able to detect voltage faults as minimal as
a few milliseconds. Due to the sensitivity of the loads, DVR is required to response
in a very high speed (Chan et al., 2006).


Figure 3.4. Basic representation of DVR

The alternative solution to DVR can be UPS, switched autotransformer or D-
STATCOM (Haque, 2001), (Banaei et al., 2006), (Kumar et al., 2007). DVR costs
less compared to the UPS systems. UPSs have typically been designed for the
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
38
correction of different types of voltage disturbances, which may not necessary, fall
into the category of voltage sags. Taking the UPS as an example, this has two major
implications (Ramachandaramurthy et al., 2004). First, the energy that a UPS is
required to store is based upon the long duration of a typical voltage outage or
blackout, not relatively short duration voltage sag. Secondly, UPS systems are
typically designed for small loads, such as a computer mainframe or low power
safety critical systems. DVR is smaller in size and costs less compared to the
DSTATCOM. The amount of apparent power injection required by a DSTATCOM to
compensate a given voltage sag is much higher than that of DVR. The main reason of
that is DVR corrects the voltage sag only on the downstream side (Haque, 2001).
Another solution may be using an autotransformer where it only takes care of a
limited range of voltage sag. The autotransformer has poor controllability, slow
response time for mechanical switching units and needs routine maintenance of its
parts. DVR system consists of power circuit and the control unit. The findings of the
comprehensive literature review summarize the available studies related with the
control unit and the power circuit of DVR and applications of DVR.

3.2.1. Power Circuit Topologies of DVR

DVR can be used for medium voltage (Li et al., 2007b), (Meyer et al., 2008),
(Toodeji et al., 2009) and low voltage applications (Muni et al., 2004). DVR is
generally designed as 3-phase 3-wire (Saleh et al., 2008) but there are also 1-phase
(Kasuni et al., 2006) and 3-phase 4-wire (Wang et al., 2004) studies for DVR.
Available topologies for DVR are transformerless (Li et al., 2002), multilevel (Loh et
al., 2004), four-leg DVR (Naidu et al., 2007), H bridge (Jimichi et al., 2008b) and
interline (Moradlou, et al., 2011). Power circuit of DVR generally consists of DC
link, DC/AC converter, LC filter and injection transformer as shown in Figure 3.5.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
39

Figure 3.5. Various power circuit topologies of DVR
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
40
DC link (energy storage unit) supplies required power for compensation of
load voltage during voltage sag/swell or harmonics. For most DVR applications, the
energy source can be an electrolytic capacitor bank. The selection of the optimum
topology and DVR ratings is related with the distribution of the remaining voltage,
the outage cost and investment cost. The topology of storage systems with auxiliary
supply is applied to increase the performance when the grid of DVR is weak. In this
type, variable DC link voltage (Ho et al., 2008) or constant DC link voltage
(Ramasamy et al., 2007) topologies are applied (Figures 3.5a, 3.5c). In the topology
of storage systems with grid itself, the remaining voltage on supply side (Saleh et al.,
2008) or load side (Jimichi et al., 2008a) is used to supply necessary power to the
system if DVR is connected to the strong grid (Figures 3.5b, 3.5d). Flywheel energy
storage system utilizes a single AC/AC power converter for the grid interface as
opposed to a more conventional AC/DC/AC converter, leading to higher power
density and increased system reliability (Perez et al., 2006), (Zhu et al., 2008), (Wang
et al., 2009). Therefore, a new inter-phase AC-AC topology is presented in (Sree et
al., 2000), (Sasitharan et al., 2009) which needs no storage device. In (Sridhar et al.,
2007), voltage control using a Distributed Generation supported DVR is presented.
When the DC link is fed from the rectifier, the rectifier can be controlled using
hysteresis (Jianfeng et al., 2002) or PI controllers (Sridhar et al., 2007), (Zhu et al.,
2008).
The inverter circuits convert DC power to AC power. The types of inverter
are voltage source (fed) inverter and current source (fed) inverter (Dixon et al.,1997),
(Graovac et al., 2001), (Nielsen et al., 2004). Current source inverter is easy to limit
over current conditions but the value of output voltage varies widely with changes in
load (Figure 3.5d). In the voltage source inverter, the values of output voltage
variations are relatively low due to capacitor but it is difficult to limit current because
of capacitor (Figures 3.5a, 3.5b, 3.5c). Some types of this inverter are: Cyclo
converter based (Sree et al., 2000), 6-bridge (Nguyen et al., 2004), H bridge (Jimichi
et al., 2008b) and Multilevel inverter (Loh et al., 2004), (Sanchez et al., 2009). VSIs
have its drawbacks, such as a rather slow control of converters (LC filter) output
voltage and current protection problems. DC bus voltage oscillations can be observed
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
41
that make the control of series filter output voltage more difficult. Such problems can
be overcome using current-source converters (Graovac et al., 2001).
The filter unit eliminates the dominant harmonics produced by inverter
circuit. Filter unit consists of inductor (L) and capacitor (C). The design procedure
for LC filter is given in (Dahono et al., 1995). The effect of harmonics generated by
the inverter can be minimized using the inverter side (Newman et al., 2005) or line
side filtering (Choi et al., 2000a). Inverter side filtering scheme has the advantage of
being closer to the harmonic source thus high order current harmonics are prevented
to penetrate into the series injection transformer but this scheme has the
disadvantages of causing voltage drop and phase angle shift in the fundamental
component of the inverter output (Figures 3.5a, 3.5b, 3.5d). In line side filtering
scheme, current harmonics penetrate into the series injection transformer but the
voltage drops and phase shift problems do not disturb the system (Figure 3.5c).
DVR is most of time in standby mode and conduction losses will account for
the bulk of converter losses during the operation (Daehler et al., 2000). The voltage
rating of the transformer depends on the grid voltage level and the depth of voltage
sag which will be compensated. The rated current multiplied by the injection voltage
level gives the VA rating of each phase (Wang et al., 2006). Its main tasks are:
connects DVR to the distribution network via the high voltage windings and
transforms and couples the injected compensating voltages generated by the voltage
source converters to the incoming supply voltage (Benachaiba et al., 2008).
In (Loh et al., 2004) and (Sanchez et al., 2009), DVR is implemented using a
multilevel inverter topology allowing the direct connection of DVR to the
distribution network without using a bulky and costly injection transformer. In (Li et
al., 2002), the use of the transformer is eliminated applying the voltage boosting
functions and a dynamic energy replenishing charging circuit.
In standby mode, the injection transformer works like a secondary shorted
current transformer using bypass switches delivering utility power directly to the
load. Alternatively, during standby operation of DVR, two upper IGBTs in each
phase of the inverter remain turned off while the two lower IGBTs remain turned on.
A short circuit across the secondary (inverter side) windings of the series transformer
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
42
through L filter is obtained eliminating the use of bypass switches (Jimichi et al.,
2008b). Differential current protection of the transformer or short circuit current on
the customer load side is only two examples of many protection functions possibility
(Benachaiba et al., 2008). The protection of a DVR against voltage surges and short
circuit conditions to prevent its malfunction or destruction is discussed in (Raithmayr
et al., 1998), (Silva et al., 2004).

3.2.2. Control Techniques of DVR

The main considerations for the control system of a DVR include sag/swell
detection, voltage reference generation for transient/steady state control of the
injected voltage, voltage injection strategies and methods for generating of gating
signals as shown in Figure 3.6. Supply voltage data is generally used to generate
reference voltage signal and sag detection signal in most of DVR studies (Silva et al.,
2005), (Jimichi et al., 2008a), (Cheng et al., 2009).
Use of
2 2
+
d q
V V or V
d
in a vector controller is the simplest type of sag/swell
detection, which will return the state of supply at any instant in time and hence,
detect whether or not sag has occurred (Fitzer et al., 2004), (Cheng et al., 2009). To
separate the positive and negative sequence components, low pass filters are used
after the d-q transformation in the literature. For effective removal, the cut-off
frequency of the low pass filter must be reduced but has the side effect of reducing
the controller response time (Jung et al., 2002). Other methods in use are neural
networks (Santoso et al., 1996), (Chung et al., 2007), tracking the positive sequence
of the supply voltage (Fitzer et al., 2001), kalman filtering (Dash et al., 2004),
applying the Fourier transform (Amaris et al., 2008) and applying the wavelet
transform (Parsons et al., 1999). Further information about conventional sag
detection method is presented in (Mokhtari et al., 2000). In (Jung et al., 2002), a new
control method for DVR system is proposed by detecting the negative and positive
sequence components using differential controllers and digital filters.

3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
43

Figure 3.6. Control unit of a DVR with a specified power circuit topology

There is also single-phase sag detection methods used in DVR. Soft phase
locked loop (Hangzhou et al., 2008), mathematical morphology theory based low-
pass filter (Zhou et al., 2008) and instantaneous value comparison method (Bae et al.,
2007) are the commonly used methods for single-phase sag detection.
Voltage reference generation is achieved using dq (Jung et al., 2002),
(Bongiorno et al., 2003), (Nielsen et al., 2004), (Yin et al., 2005), pqr (Kim et al.,
2004), artificial neural network (Jurado, 2004), sliding mode (Ruilin et al., 2005),
fuzzy logic (Bayindir et al., 2007) and software Phase Locked Loop (PLL)
(Ramasamy, 2007). Most of DVR controllers are using open-loop feed forward
control in order to meet the fast compensation requirement. However, the presence of
the switching harmonic LC filter would introduce voltage oscillations in transients.
These oscillations increase damping response time of the system (Otaduiet al., 2002).
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
44
The saturation of the series injection transformer and the voltage drop across
the inductor in steady-state operation are other factors that affect the performance of
DVR in open-loop control (Choi et al., 2002). The load voltage may not be
compensated to the desired value in open-loop feed forward control. The problems
stated above shows that closed-loop control can reduce the damping oscillations
coursed by the switching harmonic LC filter and the load voltage can track closer to
the reference load voltage under varying load condition. Multi-loop control and
closed-loop state variable control are closed-loop control strategies of DVR
(Vilathgamuwa et al., 2002), (Joos et al., 2004). The performance of these control
strategies are investigated with its dynamic and damping performance. These control
schemes can reduce the damping oscillations, but cannot catch up with the fast
dynamic response. Other control strategy is boundary controller (Chan et al., 2006).
The characteristic of load determines the required control strategy to inject
compensation voltage. DVR should ensure the unchanged load voltage with
minimum energy dissipation for injection. The methods for injection of missing
voltage can be divided into four groups (Chung et al., 2003), (Won et al., 2003),
(Chung et al., 2007), (Ezoji et al., 2009a), (Nielsen et al., 2001): Pre-sag
compensation method (Ramachandaramurthy et al., 2002), in-phase voltage injection
method (Margo et al., 2007), phase advance method (Choi et al., 2000b),
(Vilathgamuwa et al., 2003) and voltage tolerance method with minimum energy
injection (Li et al., 2007a).
In pre-sag compensation, the supply voltage is continuously tracked and the
load voltage is compensated. On the other hand, in in-phase compensation, DVR
voltage is always in phase with the measured supply voltage regardless of the load
current and presag voltage. In phase advance method, decreasing the power angle
between the remaining voltage and the load current minimizes real power consumed
by DVR. In voltage tolerance method with minimum energy injection method, the
phase angle and magnitude of corrected load voltage within the area of load voltage
tolerance are changed. The small voltage drop and phase angle jump on load can be
tolerated by load itself and the size of the energy storage is minimized.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
45
Fuzzy logic control of DVR for voltage injection is reported in (Jurado et al.,
2003), (Bayindir et al., 2007) in the literature using dq synchronous reference frame.
The control of DVR can be implemented using DSP (Fernandes et al., 2009), FPGA
or combination of them with passive circuits.
The generated reference signal is used to produce gate switching signals of
the inverter. The main modulation techniques used in DVR are space vector PWM
modulation (Duane et al., 1999), deadbeat control (Ghosh et al., 2004a), PWM
(Jimichi et al., 2008b) and hysteresis (Ezoji et al., 2009b). The hysteresis control has
the advantages of quick controllability, easy implementation and variable switching
frequency (Ezoji et al., 2009b). PWM has a great impact on its transient performance
and higher operating frequency capability (Jimichi et al., 2008b). PWM method is
widely used for gate signal generation in custom power applications. The deadbeat
controller has very fast transient response (Ghosh et al., 2004a). The space vector
PWM technique can generate output voltages and/or currents with less harmonic
distortion (Duane et al., 1999).

3.2.3. Field Applications of DVR

DVR have been installed in the Semiconductor, Plastic Extrusion, Food
Processing and Paper Mill factories. Some of DVR applications in service are
summarized as follows (Buxton, 1998), (McHattie, 1998).
i) Orian Rug Company: The first DVR to enter service was installed by
Westinghouse at the Orian Rugs Co. Plant in the USA. This is a highly automated
facility with two main processes. The plant is served by a single 12.47-kV feeder
from a 20-MVA substation transformer four miles away. A 2-MVA DVR, with 660 kJ
of energy storage was installed to this plant.
ii) Florida Power Corporation: 2-MVA DVR at Econlockhatchee was installed
as part of Florida Power Corporations new Power Quality Program.
iii) Bonlac Foods, Australia: The Bonlac load is approximately 5.25-MVA and
the facility is served by a 22-kV feeder from Powercors Kyabram substation 11
miles away. A 2-MVA DVR was installed to this plant.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
46
iv) Caledonian Paper: Scottish Power serves Caledonian Paper via a 132-kV
transmission line which is stepped and the total plant load is 47-MVA. 4-MVA DVR,
with 8MJ of energy storage was installed to this plant.
v) PureWave DVR installations have produced exceptional results for both
power suppliers and energy users. Here are but a few examples:
Semiconductor Manufacturer: A pair of 6-MVA PureWave DVRs protects a
microprocessor manufacturing facility in the southwest U.S. Operating at 12.47-kV,
DVRs serve a 35-MVA load.
Plastic Extrusion Manufacturer: A rug manufacturer in the U.S. uses a
PureWave DVR to protect the yarn extrusion process from sags. A 2-MVA DVR
installed on the 12.47-kV system corrected over 40 sags in its first year of full
operation and over 100 sags the second year.
Food Processing Plant: Interruptions at a powdered milk manufacturing plant
in Australia not only resulted in costly cleanups, but also mandated regulatory
inspections. The dairy processor realized savings of over $1 million annually with
the installation of a PureWave DVR on its 22-kV system, protecting a 6-MVA load.
Paper Mill: An 8-MVA machine load required PureWave DVR protection at a
paper mill in Scotland. A 4-MVA DVR placed on the mills 11-kV distribution
system provides sag correction, resulting in increased production by enabling the
machine to run at full speed.

3.3. Literature Review of Unified Power Quality Conditioner

Power quality issues are becoming more and more significant in these days
because of the increasing number of power electronic devices that behave as
nonlinear loads. A wide diversity of solutions to power quality problems is available
for both the distribution network operator and the end user (Singh et al., 1999). The
power processing at supply, load and for reactive and harmonic compensation by
means of power electronic devices is becoming more prevalent due to the vast
advantages offered by them. The shunt APF is usually connected across the loads to
compensate for all current related problems such as the reactive power
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
47
compensation, power factor improvement, current harmonic compensation and load
unbalance compensation, whereas the series active power filter is connected in a
series with a line through series transformer. It acts as controlled voltage supply and
can compensate all voltage related problems, such as voltage harmonics, voltage sag,
voltage swell, flicker, etc (Khadkikar et al., 2008). UPQC is a Custom Power device
and consists of combined series active power filter that compensates voltage
harmonics, voltage unbalance, voltage flicker, voltage sag/swell and shunt active
power filter that compensates current harmonics, current unbalance and reactive
current as shown in Figure 3.7 (Mekri et al., 2008), (Teke et al., 2011).


Figure 3.7. Basic representation of UPQC

UPQC is also known as the universal power quality conditioning system,
universal active power line conditioner and universal active filter (Aredes et al.,
1998), (Jacobina et al., 2007). UPQC system can be divided into two sections: The
control unit and the power circuit. Control unit includes disturbance detection,
reference signal generation, gate signal generation and voltage/current
measurements. Power circuit consists of two voltage source converters, standby and
system protection system, harmonic filters and injection transformers.
The findings of the comprehensive literature survey summarize the available
studies related with control unit and power circuit of UPQC.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
48
3.3.1. Power Circuit Topologies of UPQC

UPQC is a combination of a shunt (Active Power Filter) and a series
compensator (Dynamic Voltage Restorer) connected together via a common DC link
capacitor, which facilitates the sharing of the active power. Each compensator
consists of IGBT inverters, which can be operated in current or voltage controlled
mode. Depending upon the location of the shunt compensator with respect to series
compensator, UPQC model can be named as right shunt-UPQC or left shunt-UPQC.
Typically the active power generated in one unit is consumed in the other unit
maintaining the energy balance overall characteristics of the right shunt-UPQC are
superior to those of the left shunt-UPQC (Ghosh et al., 2002). Basic topologies of
UPQC are shown in Figure 3.8.


Figure 3.8. Various power circuit topologies: (a) Left shunt-UPQC, (b) Right shunt-
UPQC, (c)OPEN UPQC, (d) Interline UPQC and(e) Multilevel UPQC

3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
49
UPQC can be used for medium voltage and low voltage applications. In case
of low power applications, it is not convenient to install a UPQC, since DVR spends
most of its time in standby mode (Mastromauro et al., 2007). UPQC is generally
designed as 3-phase 3-wire (3P3W) systems (Xinming et al., 2009). 3-phase 4-wire
(3P4W) system is also realized from (3P3W) system where the neutral of series
transformer used in series part UPQC is considered as the fourth wire for 3P4W
system (Khadkikar et al., 2009a). There are also single-phase UPQC systems (Nasiri
et al., 2003). Various topologies such as multilevel topology (Tolbert et al., 2000),
single-phase UPQC with two half-bridge converters (Nasiri et al., 2003), H bridge
topology (Ghosh et al., 2004b), (Munoz et al., 2009) and single-phase UPQC with
three legs (Nasiri et al., 2003) are the examined for UPQC applications. A new
topology consists of the DC/DC converter and the supercapacitor is presented in
(Han et al., 2007). The series and parallel units do not have a common DC link in
(Brenna et al., 2009). Advanced renewable generation based distributed power
generation system is developed in (Chakraborty et al., 2009). UPQC is connected
between two independent feeders to regulate the bus voltage of one of the feeders
while regulating the voltage across a sensitive load in the other feeder in (Jindal et
al., 2007). A new configuration, named multiconverter unified power quality
conditioner (MC-UPQC), for simultaneous compensation of voltage and current in
adjacent feeders has been proposed in (Mohammadi et al., 2009). Compared to a
conventional UPQC, MC-UPQC topology is capable of fully protecting critical and
sensitive loads against distortions, sags/swell and interruption in two-feeder systems.
The protection of a UPQC against voltage surges and short circuit conditions
to prevent its malfunction or destruction is discussed in (Chae et al., 2001), (Axente
et al., 2008), (Axente et al., 2010b). The power circuit of UPQC generally consists of
common energy storage unit, DC/AC converter, LC filter and injection transformer.
DC link (energy storage unit) supplies required power for compensation of
load voltage during voltage sag/swell or current harmonics. UPQC generally consists
of two voltage source inverters (series and shunt) using IGBT which operate from a
common DC link storage capacitor (Hosseini et al., 2009). DC link (DC-DC
converter) connected to the battery energy storage system is used in (Davari et al.,
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
50
2009). Voltage interruption can also be eliminated by the use of a UPQC with
distributed generation (George, 2007). Split capacitor topology is used in (Aredes et
al., 1998). Photovoltaic generation as well as the functions of a unified power quality
conditioner is presented in (Cavalcanti et al., 2006).
VSIs are preferred for both shunt and series sides (Hosseini et al., 2009). The
series converters are generally composed of 6 bridge VSI (Leon et al., 2009) and
rarely composed of three single-phase H bridge VSIs (Ghosh et al., 2004b). Shunt
converters are generally composed of 6 bridge VSIs for three-phase (Forghani et al.,
2007). There are also some studies using 6 bridge inverters for series converter
(Xinming et al., 2009) and three single-phase H bridge inverters for shunt converter
(Ghosh et al., 2004b). Current source inverters are preferred for both shunt and series
sides in (Vadirajacharya et al., 2008).
The effect of harmonics generated by the inverter can be minimized using
inverter side and line side filtering (Choi et al., 2000a), (Newman et al., 2005).
Inverter side LC filtering is generally preferred for both series sides (Basu et al.,
2008) and inverter side L filtering is generally preferred for shunt side (Laxmi et al.,
2006). Inverter side C filtering is preferred for shunt side in (Jindal et al., 2007).
UPQC incorporating an LCL filter is presented in (Axente et al., 2007).
Series converter of UPQC is most of time in standby mode and conduction
losses will account for the bulk of converter losses during the operation (Daehler et
al., 2000). In this mode, the series injection transformer works like a secondary
shorted current transformer using bypass switches delivering utility power directly to
the load. UPQC without injection transformer has been designed and reported in (Tey
et al., 2002). A novel configuration of UPQC which can be connected to the
distribution system without series injection transformers is presented in (Han et al.,
2006).

3.3.2. Control Techniques of UPQC Topologies

The control unit is the most important part of UPQC system. Rapid detection
of disturbance signal with high accuracy, fast processing of the reference signal and
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
51
high dynamic response of the controller are the prime requirements for desired
compensation (Rezaeipour et al., 2008). The main considerations for the control
system of a UPQC include (Figure 3.9):
Series inverter control: Sag/swell detection, voltage reference generation,
voltage injection strategies and methods for generating of gating signals.
Shunt inverter control: Current reference generation, methods for
generating of gating signals and capacitor voltage control.


Figure 3.9. Control unit of UPQC with a specified power circuit topology

Monitoring of
2
q
2
d
V V + or V
d
in a vector controller is the simplest type of
sag/swell detection (Fitzer et al., 2004), (Cheng et al., 2009). The sag/swell detection
methods for series inverter side are root mean square method, FFT method (Kisck et
al., 2007), Synchronous frame (dq) detection method (Elnady et al., 2001), Peak
Sequence Analysis method (Srisongkram et al., 2009) and analogical method of
perturbation detection for voltage (Khoor et al., 2005).
To generate reference signals for shunt converter, IRPT is generally preferred
for reference current calculation (Fujita et al., 1998). An extended method based on
IRPT in a rotating reference frame is used to suppress the harmonics and to correct
the power factor. Adaptive detection technique is evaluated in (Karimi et al., 2003)
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
52
that minimizes the affects of noise or parameter variations. Besides, sinusoidal
template vector algorithm (Djeghloud et al., 2008), DC link voltage, neuron based
(Kinhal et al., 2011) and PI controller method (Basu et al., 2008) and fuzzy control
(Singh et al., 1998) are used. Dq transform (Zhu et al., 2003), vector template
generation method (Khadkikar et al., 2006), adaptive detection (Rong et al., 2009),
using peak detector and averaging method (Esfandiari et al., 2004), using band pass
filter and positive sequence calculation (Haque et al., 2002) and finite impulse
response filter (Chen et al., 2000) are used to generate reference signals for series
converter unit. Least squares algorithm (Kamwa et al., 1992), wavelet transform
(Elnady et al., 2001), neural network (Tey et al., 2002), positive sequence component
method (Jaime et al., 2002), linear quadratic regulator (Tey et al., 2004), unit vector
template generation method (Khadkikar et al., 2006), multi variable regulator based
with kalman filters (Kwan et al., 2005), artificial intelligence method (George, 2007),
pole shift control (Jindal et al., 2005) and abc-dq transform method (Lee et al., 2010)
are employed to generate reference signals for both series and shunt converter
simultaneously.
The overall power balance of UPQC is maintained through DC-link capacitor
(Jayanti et al., 2009). DC voltage control can be fulfilled by the traditional DC
voltage feedback or PI control (Basu et al., 2008), composite control (Xinming et al.,
2009). UPQC implemented in (Chen et al., 2004) uses a control circuit without
reference calculation. The control of UPQC can be implemented using DSP (Axente
et al., 2010a), FPGA or combination of them with passive circuits.
The outputs of controller process are the control signals used in generation of
switching signals of the inverter. To generate gating signals for only shunt converter,
hysteresis controller (Basu et al., 2008) and predictive current regulation current
controller (Newman et al., 2002) are employed. Sinusoidal PWM (SPWM) (Basu et
al., 2008) and hysteresis controller (Khadkikar et al., 2004) methods are employed to
generate gating signals for only series converter. Space vector PWM in (Li et al.,
2004), fuzzy hysteresis in (Mekri et al., 2008) and SPWM strategy in (Moreno et al.,
2008) are preferred for both series and shunt side inverter signal generation,
respectively.
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
53
3.3.3. UPQC in Service and Future Trends

Digital controller based UPQC has been developed for a laboratory prototype
in some of the studies (Kolhatkar et al., 2007), (Khadkikar et al., 2008), (Basu et al.,
2008), (Axente et al., 2010a). As a large scale structure, a 250kVA UPQC is
developed at Centre for the Development of Advanced Computing, Trivandrum,
India and is under field trial at the centre (Kumar et al., 2006). Hykon Group
Company installs IGBT based UPQC in the range of 10kVA to 250kVA connected to
a low voltage level (Juha, 2009).
Most of the proposed or practiced control strategies for power quality
conditioners have been reviewed with regard to performance and implementation.
The research reveals that there has been a significant increase in interest of UPQC
and associated control methods. This can be attributed to the availability of suitable
power-switching devices at affordable price as well as new generation of fast
computing devices (microcontroller, DSP, FPGA) at low cost (Rezaeipour et al.,
2008). However, deregulation of electricity market may contribute to rising
penetration level of distributed generation from renewable energy sources (e.g. wind,
solar, biomass, etc.) in the near future. This can lead to an increase in the number of
UPQC studies based on distributed generation (Malabika et al., 2007).

3.4. Summary

Widespread applications of power electronic based devices/equipments in
industry have increased the importance and application of power quality studies.
Decrease in the cost of power electronic devices and improvement in the efficiency
of both power converters and energy storage components have increased the
applicability of new technological solutions such as Custom Power devices. CP
devices including DVR, APF and UPQC are showing tremendous development.
These devices have become very popular in recent years in both low voltage and
medium voltage applications. The comprehensive reviews of articles concerning CP
devices are presented to show the advantages and disadvantages of each possible
3. LITERATURE REVIEWS OF CUSTOM POWER DEVICES Ahmet TEKE
54
configuration and control techniques. The literature survey reveals that new control
algorithms and topologies for CP devices have been developed to minimize the
power losses, increase the system flexibility and efficiency. These reviews will help
the researchers to select the optimum control strategy and power circuit configuration
for their CP applications.
The next chapter discusses the traditional and proposed control strategies for
UPQC and OPEN UPQC in detail.


4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
55
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC

The control systems of UPQC and OPEN UPQC consist of APF and DVR
controllers. APF controller measures the load voltages, capacitor voltage, load
currents and injected currents. The controller algorithm of APF processes the
measured values and generates the required compensation signals. These signals are
then compared in hysteresis controller and the required gate signals are generated.
DVR controller measures the supply voltages to generate the required compensation
and sag/swell detection signals. These signals are then compared in PWM controller
and the required gate signals are generated.

4.1. Control Algorithms for APF

In this thesis, a simple and effective control algorithm is proposed for
reference current generation. The algorithm for reference current generation is based
on the Instantaneous Reactive Power Theory and it presents some interesting features
(Afonso et al., 2000), namely:
It is inherently a three-phase system theory,
It is based in instantaneous values, allowing excellent dynamic response,
Its calculations are relatively simple (it only includes algebraic expressions
that can be implemented using standard processors),
It allows two control strategies: constant instantaneous supply power and
sinusoidal supply current.
The control system of the traditional APF is shown in Figure 4.1. Three-phase
load voltages, DC capacitor voltage, load currents and injected currents are the input
for the control system. The capacitor voltage is controlled using PI controller. The
outputs of the control system are the reference currents (I
a
, I
b
and I
c
). This obtained
error signals are compared with hysteresis controller and required gate signals for
IGBT switches are generated.
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
56
Figure 4.1. The control system of traditional APF

4.1.1. Proposed APF Controller

The fundamentals of IRPT are explained in Appendix B. The most important
disadvantage of IRPT theory is that voltage harmonics in supply voltages (so load
voltages) result in increased THD content. This can cause the incorrect calculation of
reference current. To overcome this problem, only one load voltage measurement is
performed. With the use of the measured value, 90 phase shifted virtual voltage is
generated as shown in Figure 4.2 (Cuma, 2010). The generation of this virtual
voltage depends on the detection of zero crossing of phase-to-phases voltage of A
and B phases. With the zero crossing detection, frequency compensation is made on
virtual voltage. The unbalances between measured load voltages are eliminated using
this control approach.

ab
V V

= (4.1)

a b
V V 90

= (4.2)

A PI controller is used to compensate DC link capacitor voltage if APF is in
compensation state. The instantaneous active power is calculated by using the
transformed values and they are applied to a 100 Hz digital low pass filter.
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
57
The filtered active power value is summed by the output of the voltage
controller to be used in reverse transformation. With a similar way, the reactive
power value is calculated and a reverse transformation is made by using the active
and reactive power values.


Figure 4.2. Proposed APF controller

The basic principle of the compensator will be considered, concerning the
axis instantaneous current on the load side (Akagi et al., 1984). The instantaneous
active and reactive currents are divided into the following two kinds of instantaneous
currents, respectively:

~ ~
2 2 2 2 2 2 2 2
V V
V V
p p q q
V V V V V V V V
i




+ + +
+ + + +
=

(4.3)


where p and

p are the DC and AC components of the instantaneous real power and


q and
%
q are the DC and AC components of the instantaneous imaginary power.

The first term of the right-hand side of (4.3) is the instantaneous value of the
conventional fundamental reactive current. The third term is the instantaneous value
of the conventional fundamental reactive current. The second term is the
instantaneous value of the current harmonics which represents the AC component of
the instantaneous real power. The fourth term is the instantaneous value of the
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
58
current harmonic which represents the AC component of the instantaneous imaginary
power. Accordingly, the sum of the second and fourth terms is the instantaneous
value of the conventional current harmonics. Note that the second and fourth terms
include a conventional negative sequence component. Equation (4.3) leads to the
following essential conclusions (Akagi et al., 1984).
1) The instantaneous reactive power compensator eliminates both the third
and fourth terms. For this reason, the displacement factor is unity not only in steady
states but also in transient states.
2) The current harmonics represented by the fourth term can be eliminated by
the compensator comprising switching devices without energy storage components.
To sum up, from (A.7) in Appendix B, in order to compensate current
harmonics, instantaneous compensating currents (i
c
and i
c
) on and coordinates
are calculated by using
p
and %
q
as given below:

~
1
CP
~
CP
V V I p
I V V
q

(
( (
(
=
( (
(

(

(

(4.4)

4.1.2. Reference Current Generation

The feedback method used to control self-supporting DC bus is very
important. The method consists of controlling the capacitor voltage to a reference
value. To achieve this, a PI control may be chosen for the error between the reference
value and the capacitor voltage value at the end of each period. The result is the
value of the compensator lost power. This value modifies the power term, which
appear in the compensation current expressions. This term is multiplied with a
constant and added as an error to the filtered value of the instantaneous real power
(Herrera et al., 2008). In order to obtain the reference compensation currents the
error signal is calculated using (4.2).

4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
59
err ref f
i i i =

(4.5)

4.1.3. Hysteresis Current Controller

The basic of the hysteresis current control is based on an error signal between
an injection current (I
inj
) and a reference current of APF (I
ref
) which produces proper
control signals. The hysteresis band current controller decides the switching pattern
of APF (Ezoji, 2009a). The conventional hysteresis band current control scheme used
for the control of APF is shown in Figure 4.3. There are bands above and under the
reference current. When the error reaches to the upper limit, the current is forced to
decrease. When the error reaches to the lower limit, the current is forced to increase.


Figure 4.3. Voltage and current waveforms of hysteresis band controller

The switching logic is formulated as follows:
If I
inj
< (I
ref
h
b
) upper switch is OFF and lower switch is ON.
If I
inj
> (I
ref
+ h
b
) upper switch is ON and lower switch is OFF as shown in
Figure 4.3.
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
60
Some significant advantages of hysteresis controllers over other types of
controllers designed with linear or nonlinear control techniques for APF applications
are as follows (Tilli et al., 1998):
Switching behavior of the power inverter can be directly taken into
account at the design level,
Robustness to load parameters variation can be proved,
Almost static response is achieved (the dynamics are obviously bounded
by the DC-link voltage and by the actual switching frequency),
Simple hardware implementation, based on logical devices, is possible
according to Boolean nature of controller input/output variables.

4.2. Control Algorithms for DVR

The control system of DVR performs voltage measurements, sag/swell
detection, reference voltage extraction and gate signal generation. Simple and
effective control algorithms are proposed for both sag detection and reference
voltage generation in this thesis. The algorithms are based on the nonlinear adaptive
filter presented in (Karimi et al., 2002). This filter can be used as a PLL. The filter
has also the abilities of peak detection and signal decomposition. Its performance is
immune to noise and external distortions, accuracy and speed of its response are
controllable and its structural simplicity provides major advantage for its
implementation within embedded controllers.
DVR control includes the reference voltage generation and sag/swell
detection computations as shown in Figure 4.4.

4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
61
Figure 4.4. Structure of series inverter control
4.2.1. Proposed Reference Voltage Generation

The reference voltage computation of series inverter control, which is based
on (4.6-4.23) is shown in Figure 4.5. For series inverter, A(t) corresponds to supply
voltage V
S
and E(t) corresponds to V
PLL_S
.


Figure 4.5. Reference signal generation for the series controller

The required compensation signal V
err_S
is obtained from (V
PLL_S
-V
S
). C(t)
corresponds to V
amp_S
and this signal is used to detect voltage sags/swells. The
measurements of supply voltages are required for control strategy of DVR. The
control signals of DVR controller are derived from the following equations.

4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
62
B(t) can be expressed as a continuous time,

B(t) A(t) - E(t) B(t)E(t)dt =



(4.6)

B(t) and E(t) located at right hand side of (4.6) are assumed as a constant due
the value at the instant t is equal to that of the instance (t-1). Hence, the final
statement of (4.6) is given in (4.7).

B(t) A(t) - E(t 1) B(t -1)E(t -1)dt =

(4.7)

Considering that B(t-1) and E(t-1) are constant, then;

2
B(t) A(t) - B(t 1)E (t 1) dt =

(4.8)

If the constants are assumed as;

2
2
B(t -1)E (t -1) k =
(4.9)

Then, the last statement of B(t) can be written as;

2
B(t) A(t)-k t = (4.10)

(t) can be expressed as;

(t) (B(t)cos (t) ) dt = +

(4.11)

Substituting B(t) and A(t)=Asint into (t), also assuming cos(t) is constant,
then;
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
63

2
( ) cos ( ) (( sin t ) t t A k t dt dt = +

(4.12)

The last statement of (t) is given in (4.13).

2 2
k A
(t) cos (t)( cos t t ) t
2

= +
(4.13)

E(t) can be expressed as;
E(t) sin (t) = (4.14)

Substituting (t) into the E(t), E(t) can be written as;

2 2
k
A
E(t) sin(cos (t)( cos t t ) t)
2

= +
(4.15)

C(t) can be expressed as;

C(t) B(t)E(t) dt =

(4.16)

In (4.16), E(t) is assumed as a constant due the value at the instant t is equal
to that of the instance (t-1). Hence, the last statement of (4.16) is given in the
following.

C(t) B(t) E(t 1)dt =

(4.17)

Considering that E(t-1)=k
3
is a constant, then;

3
C(t) k B(t) dt =

(4.18)

4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
64
Substituting B(t) into the C(t), C(t) can be expressed as;

3 2
C(t) k (Asin t k t) dt =

(4.19)

The last statement of C(t) can be written as follows.

2 3 2 3
k A k k
C(t) cos t t
2

=
(4.20)

D(t) can be expressed as;

D(t) C(t)E(t) =
(4.21)

D(t) C(t)sin (t) = (4.22)

The last statement of D(t) can be written as follows.

3
C(t)
D(t) C(t)sin( t)
k
= +
(4.23)

The difference of A(t) and (4.15) give the required magnitude and phase angle
of series compensating voltage to perform the desired operation. The supply voltage
and its extracted components such as difference of input and synchronized
fundamental component B(t), the amplitude C(t), synchronized fundamental
component D(t) and PLL signal E(t)are shown in Figure 4.6 when a 0.3 pu voltage
sag occurs at 1.5s <t< 2.1s.
E-PLL extracts and directly provides the following pieces of information
from the input (Karimi et al., 2002), (Karimi et al., 2003):
Fundamental sinusoidal component of the input; this signal is synchronous
with the input and is smooth and noise-free,
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
65
Amplitude of the fundamental component of the input,
Phase angle of the fundamental component of the input; this phase can be
adjusted to be its constant phase or total phase.

Figure 4.6. Supply voltage and its extracted components

4.2.2. PWM Gate Signal Generation

The voltage compensation signal V
error
is compared with a fixed frequency
carrier wave to generate the firing pulses as PWM signals as shown in Figure 4.7. In
this way, the voltage in the same phase with supply side generated by DVR voltage
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
66
source inverter is injected to the load side.


Figure 4.7. Generation of PWM gate signals

4.2.3. Proposed Sag/Swell Detection

Proposed sag/swell detection method is compared with the conventional
method using d-q transformation to show the superiority of proposed detection
method. In the conventional method, the phase voltages V
A
, V
B
and V
C
are
transformed to d-q plane as given in (4.24). With the use of (4.25), the sag/swell
depth (S
conv
) is obtained (Teke et al., 2009).


A
d
B
q
C
2 2
V
cos cos( ) cos( )
V
2
3 3
V
3 V 2 2
sin sin( ) sin( )
V
3 3




(
(
( (
(
( (
(
( (
(

(
(


+
=
+
(4.24)


2 2
conv q
d
S 1 V V = +
(4.25)

The block diagram of the d-q transformation based sag/swell detection
method is shown in Figure 4.8a. The most important disadvantage of this method is
that it uses three-phase voltage measurements for the detection. The method is unable
to detect the voltage sag lower than a definite depth. As an instance, a single-phase to
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
67
ground fault resulting in 20% of voltage sag cannot be determined by this method if
the voltage sag detection limit is selected to be 10%. D-q method uses the average of
the three-phase voltage and perceives the single-phase voltage sag as an average
value of 6.67% that is lower than sag detection limit (10%) (Meral, 2009), (Cuma,
2010).
Another restriction of this method is the use of low pass filter tuned at 50 Hz.
This filter reduces the response speed of the detection scheme. To overcome the
disadvantages of the d-q sag detection method, C(t) signal depicted in Figure 4.5 is
used in this thesis. With the proposed fault detection method, the controller is able to
detect balanced and unbalanced voltage sags/swells without an error. C(t) gives the
amplitude of the tracked signal A(t). For example, if the amplitude of the measured
Phase_A supply voltage is 220 V
rms
, C(t) signal is obtained as continuous 1 pu. If the
amplitude falls to the 176 V
rms
, the amplitude of the C(t) signal falls to 0.8 pu. The
voltage sag/swell detection method based on E-PLL method is presented in Figure
4.8b.
By subtracting the C(t) signal from the ideal voltage magnitude (1 pu), the
voltage sag/swell depth (S
prop
) can be detected as given in (4.26). The comparison of
this value with the limit value of 10% (0.1 pu) gives information whether a fault
occurred or not (Meral, 2009), (Cuma, 2010).

4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
68
Figure 4.8. Structures of conventional and proposed sag detection methods

prop
S 1 C(t) =
(4.26)

As an example, a single-phase voltage sag initiates at 1.5s with a duration of
0.5s. The conventional method cannot detect the single-phase sag because the error
signal is not correctly calculated as shown in Figure 4.9. The proposed method can
detect the sag depth with an exact certainty and enables the control system to
generate the required gating signals.

4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
69

Figure 4.9. The depth values of sag with conventional and proposed methods

When the supply voltage is within the nominal operation values, DVR is in
OFF-mode (standby). During standby operation of DVR, two lower IGBTs of each
phase H-bridge inverter remain turned on while the two upper IGBTs remain turned
off, thus forming a short circuit across the secondary (inverter side) windings of the
series transformer through L
F
(Jimichi et al., 2008a). Thus, there is no need to use of
bypass switches. When the supply voltage deviates from its nominal operation value,
DVR comes into ON-mode. In this mode, by using an independent sag detection
method for each phase, each H-bridge inverter is controlled independently. With this
method, minimum energy is injected and switching losses are reduced.


4.3. Summary

The control of UPQC and OPEN UPQC systems consist of APF and DVR
controller. APF controller generates the reference current signal measuring the load
voltage, load current, injected current and capacitor voltage. Proposed APF controller
is derived from IRPT method. The negative effect of traditional IRPT when the
supply voltage is unbalanced and distorted is eliminated using virtual alpha and beta
components. APF controller board protects the overall system by closing the firing
4. CONTROL STRATEGIES OF UPQC AND OPEN UPQC Ahmet TEKE
70
pulses going to IGBT drivers. APF also regulates the DC link voltage. Hysteresis
control technique is used to generate the gate switching pulses of APF. DVR
controller generates the reference voltage and sag detection signals measuring the
supply voltages. DVR controller is based E-PLL and the reference voltage signal and
sag detection signal are extracted simultaneously. DVR controller uses independent
sag detection method for each phase and thus each H-bridge inverter is controlled
independently. Sinusoidal PWM control technique is used to generate the gate
switching pulses of DVR.
The main mathematical and numerical features of the control algorithms are
presented. The improvements on APF and DVR controllers are validated with
simulation cases in PSCAD/EMTDC.
The next chapter presents the design of UPQC and OPEN UPQC power
circuits consisting of both shunt (APF) and series (DVR) compensators in detail.























5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
71
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER

The power circuits of the proposed UPQC topologies namely UPQC and
OPEN UPQC in a three-phase network are shown in Figure 5.1. The shunt unit
(APF) is designed to minimize load current harmonics from 23.5% to <5% at the
supply side. The series unit (DVR) is designed to inject30% of the network power
supplied from a storage system.


Figure 5.1. Power diagram of (a) Proposed UPQC and (b) OPEN UPQC

5.1. Power Circuit Design of Proposed APF

The components of APF power circuit are DC energy storage unit (DC
capacitor), three-phase inverter circuit, smoothing inductor and choke reactor as
shown in Figure 5.2.
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
72
Figure 5.2. Power circuit and control system of APF

The single-phase equivalent circuit of APF is shown in Figure5.3. The load
current drives harmonic polluting current (I
h
), APF injects the required compensation
current (I
inj
) and supply current draws a sinusoidal current (I
s
).


Figure 5.3. The single-phase equivalent circuit of APF


5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
73
5.1.1. Design of DC Link Capacitor

DC capacitor (energy storage unit) supplies required power for harmonic
compensation of load current during operation. The capacitor size need to be selected
to cover the desired di/dt capability required to compensate current harmonics in any
condition (Vodyakho et al., 2009a). In voltage source active filters, DC voltage of the
energy storage capacitor must be greater than the maximum line voltage. For proper
operation of active filter, at any instant the voltage of the DC capacitor voltage
should be 1.5 times of the line maximum voltage (Emadi, 2004).
Design of the DC side capacitor is based on the principle of instantaneous
power flow on the DC and AC side of the converter. The fluctuation due to the load-
change cannot be taken as a method for capacitor design. However, unlike the
voltage ripple caused by the load unbalance that the ripple must be suppressed by
enlarging the capacitor value, the voltage control section will regulate this fluctuation
caused by the load change. The magnitude of the voltage fluctuation depends on the
closed loop response and can be made small by suitable design of the control
parameters. According to the above analysis, the selection of capacitor value C
DC
is
governed by reducing the worst case voltage ripple (at 2) caused by the unbalanced
load and it can be found from (5.1), (Emadi, 2004):

fLrated
DC
DC,p p(max)
I
3wV
C

=

(5.1)

where V
DC,p-p(max)
is the peak to peak voltage ripple, I
fLrated
is the filter current, w is the
angular frequency.

Theoretically, the capacitor voltage and capacitance of the capacitor value can
be also determined using the findings of (Rathle, 2005). The capacitor value is then
selected by considering the commercial capacitor values.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
74
L_ L
DC
a
1.15 V 2
V
m
>

(5.2)

a
afL
c
m
C I
2w V
=

(5.3)

V
DC
= The capacitor voltage
V
L_L
= The peak line to line AC input voltage
m
a
= The modulation index
C= DC capacitor value
I
afL
= The output current of APF
V
c
= The ripple voltage value in % of the capacitor voltage
w= Switching frequency

DC capacitor value is calculated as1900 F using (5.3) when m
a
=1,
V
c
=2.5% of V
DC
, I
afL
=6A and w=62831 rad/s. The capacitor is selected as 2200 F.

5.1.2. Design of Inverter Circuit

The inverter circuit converts DC power to AC power. Three-phase IGBT with
anti-paralleling diodes having turn-off capability are used in the inverter circuits. A
voltage source inverter is energized by a capacitor at the input. The inverter is then
connected in parallel to the distribution line through three smoothing inductors as
shown in Figure 5.2. The proper voltage level for DC capacitor and the power
switching devices with low internal impedance should be selected for the
experimental studies because the active power filter is always on line.
The three-phase PWM voltage source inverter will be used in this thesis.
PWM switched inverters provide better performance to control asymmetries and
especially over currents during unbalanced faults. The current control is achieved by
modulating the output voltage waveform within the inverter. The main advantage of
PWM inverter is including fast switching speed of the power switches. PWM
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
75
technique offers simplicity and good response. Besides, high switching frequencies
can be used to improve on the efficiency of the converter, without incurring
significant switching losses (Lara et al., 2002).

5.1.3. Design of Filter Units

The shunt APF filter system contains the smoothing-coupling inductors and
chokes (line) reactors filters. The smoothing and coupling inductors establish a link
between the filter and system. The active power filter delivers its current to the
system through the inductor. For controllability of APF, this inductor should not be
large (Emadi, 2004).
Peak ripple current is chosen to be the criterion for designing the inductor.
For calculating the ripple current, no-load condition is considered and the effect
inductor resistance is assumed to be negligible. Under this condition, the inverter
reference voltage is equal to the supply voltage. Thus the required smoothing
inductance given by (Chaoui et al., 2008):

DC
sh
s f (p p)max
V
6f I
L

=

(5.4)

where I
f(p-p)max
=% of peak compensation current, V
DC
is the DC side voltage, f
s
is
the switching frequency.

The design of the smoothing and coupling inductor can also be performed
with the constraint that for a given switching frequency the minimum slope of the
inductor current is smaller than the slope of the triangular waveform that defines the
switching frequency. In this way, the intersection between the current error signal and
the triangular waveform will always exist. The slope of the triangular waveform is
defined by (Luis et al., 1995):

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
76
4 f =

(5.5)

where is the amplitude of the triangular waveform, which has to be equal to the
maximum permitted amount of ripple current and f is the frequency of the triangular
waveform (i.e. the inverter switching frequency). The maximum slope of the inductor
current is equal to:

an dc iL
f
V V 2 d
dt L
+
= (5.6)

Since the slope of the inductor current has to be smaller than the slope of the
triangular waveform and the ripple current is known, the value of smoothing-
coupling inductor is calculated using (5.5) and (5.6).

an dc
sh
V V 2
L
4 f
+
= (5.7)

The smoothing inductance is calculated as 10 mH using (5.4) when
V
DC
=375V
DC
, I
f(p-p)max
=0.6A and f=10 kHz. To improve the smoothing inductance
performance considering the filter market, the inductance is selected as 19 mH (multi
output: 15mH+4mH).
The typical diode DC capacitor front-end configuration of loads draws pulsed
currents from the utility lines, which may lead to high harmonic distortion of the line
currents and poor load power factor. To alleviate this problem, drive manufacturers
typically recommend the use of 3-5% choke (line) reactors (Hoevenaars, 1999).

ch L
X (3 5%)Z =
(5.8)


To calculate the actual inductance value, (5.9) should be used.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
77
(5.9)


where L
ch
is inductance in Henrys, X
ch
is inductive reactance or impedance in ohms
and f is the frequency.

The choke reactor is calculated as 5.73 mH using (5.8) and (5.9) when
Z
L
=45 and X
ch
is 4% of Z
L
. To improve the smoothing inductance performance
considering the filter market, the inductance is selected as 6 mH.

5.2. Components of Proposed APF

The experimental setup of DSP based APF is presented in Figure 5.4. The
current harmonics are generated using resistive load supplied from three-phase diode
rectifier. This rectifier is equipped with choke reactors which makes the line current
more sinusoidal. Three-phase three leg IGBT inverter is used as the voltage source
converter. This inverter is fed from a DC link capacitor. The output of the VSI is
connected to the line via smoothing inductors that convert the voltage output of
inverter to current.
A signal conditioning board is designed to measure load voltages, DC link
capacitor voltage, the filter currents and load currents. The current transformers are
used to measure the filter and load currents. The voltage transducers are used to
measure load voltages and DC link capacitor voltage (Cuma, 2010). DSP kit is used
as the controller of APF. DSP is directly connected on the signal conditioning board.
The outputs of the DSP are applied to a protection and firing board. This board is
responsible to protect the overall system by closing the firing pulses going to IGBT
drivers. The board senses the voltage and current levels on the system and makes
analog protection by the use of logic. The firing section is used as a buffer between
the outputs of DSP kit and IGBT drivers.


/(2 )
ch ch
L X f =
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
78

Figure 5.4. Experimental block diagram of APF

5.2.1. Voltage and Current Measurements

CTF-5A current transformers are used to measure the filter and load currents.
Their secondaries are connected to six connectors on the left bottom of the signal
conditioning board. LV25-P voltage transducers are used to measure the load
voltages and capacitor voltage as shown in Figure 5.5.


Figure 5.5. The current transformers and voltage transducers
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
79
5.2.2. Signal Conditioner/Interface Board

Signal conditioning board measures the load voltages, DC link voltage, load
currents and filter currents as shown in Figure 5.6. The details of the circuit diagrams
for signal conditioning board are comprehensively presented in (Cuma, 2010).

Figure 5.6. Picture of signal conditioning board of APF

5.2.3. Firing and Fault Protection Board

Protection and firing board is used to drive the IGBT drivers while making
protection functions at the same time as shown in Figure 5.7. The outputs of signal
conditioning board are limited to 3V
DC
as the ADC inputs of DSP are 3V compatible.
Voltage level greater than 3V
DC
means that the measured signal is out of limits. An
adjustable voltage compare level is used to control APF voltage and currents. Any
voltage above the compare level stops the firing signals going to the drivers. This is
achieved by comparing the compare voltage level with measurement outputs.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
80

Figure 5.7. Picture of firing and fault protection board

TMS320F28335, signal conditioning board, protection and firing board forms
the complete control board as shown in Figure 5.8.


Figure 5.8. APF control board


5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
81
5.2.4. IGBT Driver Circuit

Three Semikron SKHI 22B H4 IGBT drivers are used to drive three
Semikron SKM75GB123D dual IGBT modules. The driver circuit (SKHI 22-2)
amplifies the amplitudes of buffer card at 0-5 V to (-7V)-(15V). IGBT driver card for
one of H-bridge inverters is shown in Figure 5.9.


Figure 5.9. IGBT driver cards for one of H-bridge inverters

5.2.5. Three-Phase Bridge IGBT Inverter with DC Link Capacitor

Three Semikron SKM75GB123D IGBT modules are used to construct the
three wire IGBT inverter as shown in Figure 5.10. DC link capacitors are connected
to the IGBT inverter via busbars. This bank is formed by two series and two parallel
connections of four 450V, 2200F DC capacitors. By this way, DC voltage rating of
the filter is adjusted to 900V
DC
while maintaining 2200 F of capacitor value. Four
1600V
DC
0.22 F snubber capacitors are also added to the inverter to suppress
overshoots.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
82

Figure 5.10. APF inverter with DC link capacitors

5.2.6. Smoothing Inductor and Choke Reactors

The smoothing inductors and choke inductors are shown in Figure 5.11. The
values of smoothing inductances for phases A, B and C are 19.41 mH, 20.04 mH and
19.49 mH, respectively. The values of choke reactors for phases A, B and C are 6.14
mH, 6.07 mH and 6.21 mH, respectively.


5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
83

Figure 5.11. Choke reactors (on the top) and interface reactors (on the bottom)

5.2.7. Three-Phase Bridge Rectifier with a Resistive Load

The single-phase load used for the experiment is shown in Figure 5.12. The
load has two 90/6500 W resistors in series and supplied from SKD62/16 three-
phase rectifier.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
84

Figure 5.12. Harmonic polluting load

5.3. Power Circuit Design of Proposed DVR

The components of DVR power circuit are DC energy storage unit, inverter
circuit, LC harmonic filter and injection transformer as shown in Figure 5.13.

DCInputs
Fuse
3 phase
supply
DC
outputs
Heatsink
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
85

Figure 5.13. DVR system connected with energy storage

The single-phase equivalent circuit of DVR is given in Figure 5.14. The
voltage sag occurs on supply voltage (V
s
), DVR senses the voltage sag and injects the
missing voltage to the system in series (V
inj
) and the load voltage is not affected by
the voltage sag (V
L
).


Figure 5.14. The single-phase equivalent circuit of DVR
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
86
5.3.1. Design of DC Supply

A storage system with auxiliary supply is used in DVR for UPQC and DC
capacitor is used in DVR for OPEN UPQC. The design procedure for DC capacitor
was mentioned in Section 5.1.1. DC supply (energy storage unit) provides required
power for compensation of load voltage during voltage sag/swell. The reactive power
exchanged between DVR and the distribution system is internally generated by DVR
without any AC passive reactive components. Real power exchanged at the AC
terminals of DVR must be provided at DC terminal of DVR (Woodley et al., 1999).
Thus, DC link voltage is almost kept constant with this topology during voltage sag.
DC link voltage level is related with sag level to be compensated and the
turns ratio of injection transformer (Teke, 2005).

DC an sl(pu)
V a 2V V =

(5.10)


where V
an
is the single-phase phase to ground rms voltage, V
sl(pu)
is the sag level to be
compensated and a is the turns ratio.

DC link voltage is calculated as 270V
DC
when V
an
=127V
rms
, V
sl(pu)
=0.3 pu
and a=5 using (5.10).

5.3.2. Design of Inverter Circuit

IGBTs are used in the inverter circuits to convert DC power to AC power. A
voltage source inverter is energized by a constant DC voltage supply of low
impedance at the input. The output voltage is independent of load current. The
inverters are then connected in series to the distribution line through single-phase
injection transformers. IGBT is a unidirectional conducting device and hence in most
of the applications an anti-parallel diode has to be used (Meral, 2009). When IGBTs
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
87
are used as switching components in an inverter or converter, freewheeling diodes are
needed to sustain the current from the inductive load such as a motor or transformer.
PWM switched inverters provide superior performance to control
asymmetries and especially over currents during unbalanced faults. Three single-
phase PWM VSIs are used in this thesis. Use of single-phase H-bridge PWM
inverters in DVR power circuit makes possible the injection of positive, negative and
zero sequence voltages. The voltage control is achieved by modulating the output
voltage waveform within the inverter. The main advantage of PWM inverter is
including fast switching speed of the power switches. PWM technique offers
simplicity and good response. Besides, high switching frequencies can be used to
improve on the efficiency of the converter, without incurring significant switching
losses (Lara et al., 2002).

5.3.3. Design of LC Filter

LC filter suppresses the dominant harmonics produced by inverter circuit.
Inverter side filtering is preferred for harmonic elimination in this thesis. This
scheme has the advantageous of being closer to the harmonic source and low voltage
side thus it prevents the current harmonics to penetrate into the series injection
transformers (Choi et al., 2002).
The design procedure of the LC filter can be divided into four steps by
considering the assumptions of (Dahono et al., 1995), (Teke, 2005).
(i) Based on the DC supply voltage E
d
and nominal load voltage V
o
, the
modulation index k is calculated.


d
o
E
V
k 2 = (5.11)

(ii) The result is used to calculate filter factor K by using (5.12).

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
88

2 / 1
6 5 4 2
1440
4
5
-
5
64
4
15
-
(
(
(
(

+
=
k k k k
K

(5.12)

(iii) Equation (5.13) calculates the optimum value of the filter inductance.


2 / 1
2
2
,
4 1

(
(

|
|

\
|
+

=
oav
d
s
r
av o
d
s o
o
f
V
E
K
f
f
V
E
K
f
V
L (5.13)

I
o
is the load current, f
s
is the switching frequency, f
r
is the fundamental output
frequency and V
o,av
is the total harmonic of the load voltage.

(iv) Equation (5.14) calculates the optimum value of the filter capacitance.


av o s f
d
f
V f L
E
K C
,
2
= (5.14)

L and C values are calculated following the design procedure of (Dahono et
al., 1995) in this thesis. The values of filter design parameters shown in Table 5.1.
The nominal modulation index is calculated using (5.11) and it results in k=1.

d
o
E
V
k 2 =

Table 5.1. The filter design parameters of DVR
V
o
E
d
I
o
f
r
f
s
V
o,av

190 V
rms
270 V
DC
9.09 A
rms
50 Hz 10 kHz 0.1%

The result is then used to calculate the factor K by using (5.12).
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
89
2 / 1
6 5 4 2
1440
4
5
5
64
4
15
(
(
(
(

+
=
k k k k
K 00716 . 0 = K

The optimum values of the inductance and capacitance of the filter can be
calculated by using (5.13) and (5.14).

2 / 1
,
2
2
,
4 1

(
(

|
|

\
|
+

=
av o
d
s
r
av o
d
s o
o
f
V
E
K
f
f
V
E
K
f
V
L
f
L 9.2 mH =

av o s f
d
f
V f L
E
K C
,
2
=
f
C 20 F =

From the view of costs and weight, the capacitor is the much cheaper device
than the inductor. To improve the filter performance considering the filter market, the
capacitor is selected as 18 F and the filter inductor is selected as 10 mH in the
thesis.

5.3.4. Design of Series Injection Transformer

The transformers reduce the voltage requirement of the inverters and provide
isolation between the inverters. This can prevent DC storage capacitor from being
shorted through switches in different inverters (Ghosh, 2002). The electrical
parameters of series injection transformer should be selected correctly to ensure the
maximum reliability and effectiveness. In normal bypass mode, full load currents
pass through these semiconductor switches. The flowing current will increase during
sags because of injected power for compensation so the switches and protection
devices should handle the total current. Injection transformer rated at 1 kVA (5:1 turns
ratio, primary/secondary) are used in this thesis.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
90
5.4. Components of Proposed DVR

The hardware components of DSP controlled three-phase DVR and typical
output waveforms are given in Figure 5.15. DVR prototype system consists of an
eZdsp F2812 DSP board, H-bridge IGBT inverter, LC filter circuit, DC supply,
injection transformer and measurement devices. Three voltage transducer circuits
(LEM LV25-400) are used to measure the supply voltages. Signal conditioning board
is responsible for input and output signal conditioning for DSP controller. The
produced signals have 0-3.3 V
peak
value. These signals are amplified to 0-5 V and
connected to IGBT driver circuit (SKHI 22B). The driver circuit changes the
amplitudes of the (0-5 V) signals to (-7 V
peak
)-(15 V
peak
). The amplified signals are
given to Gate-Emitter of each IGBT (SKM75GB123D) which is now suitable to
trigger an IBGT. Four IGBTs (two legs) are required to obtain an H bridge inverter.
Two IGBT modules are used for each leg and one driver circuit is required for each
leg. The procedure is the same for other two phases.
A constant DC power supply (270V
DC
) is employed as energy storage for
UPQC. DC link capacitor (2200 F) is used as energy storage for OPEN UPQC.
Three single-phase H-bridge PWM inverters consisting of IGBT switches are used in
the voltage source converter circuit. The inverter side filtering is preferred in this
thesis. Voltage sag/swell generator is feeding the load through the series injection
transformers of DVR. Each inverter output is filtered out by an LC filter to eliminate
the higher order harmonics generated by the inverter itself. The filtered output of the
IGBT inverters are connected to the primary side of the injection transformers thus
enabling the injection of the missing voltage to the load.



5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
91

Figure 5.15. Experimental block diagram of DVR

The experimental photographs are taken within the project Modeling and
Implementation of Custom Power Park which is supported by Scientific and
Technological Research Council of Turkey with project number of 106E188.

5.4.1. Disturbance (Sag/Swell) Generator

A disturbance generator is designed and implemented to create voltage sag at
any instant of with amplitudes ranging from 0-220V
l-l
. The designed disturbance
generator system consists of variable voltage sources, thyristors pairs, thyristors
drivers, protection devices and time relays as shown in Figure 5.16. The ratings of
components on disturbance generator are given in Table 5.2. During normal
operating conditions, the load is supplied from Supply-1. This supply is fixed at 220
V
l-l
. When a disturbance is desired, the system is supplied from Supply-2 arranged as
desired voltage level (0-220V
l-l
) and time interval.

5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
92
Table 5.2. The ratings and components of disturbance generator
Component Ratings
Voltage supplies 18.75 kVA, 25 A, 3x380 V input,
3x(0-380) V variable output
Thyristor modules Semikron 1200 V, 40 A
Thyristor drivers Semikron 12 V
Timer relays 220 V, single-phase AC time relays


Figure 5.16. View of disturbance generator system
Supply 1: 220 V
rms
Supply 2: 0-220 V
rms

Sag /swell
generator
Thyristor
pairs
Thyristor
driver
Timer
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
5.4.2. Voltage Transducers

The three-phase set of voltages are measured from the
three LEM LV25-400 transducer cards. The card is adjusted to read
convert it into 1.5 V
peak

Figure 5.17. LEM LV25

5.4.3. Signal Conditioner/Interface Board

The voltage measurement is achieved using transducers
boards. The supply voltages are measured using voltage transducers. The transducers
convert 220 V
rms
value to 1.5 V
used to add 1.5 V
DC

this way, the analog input signals are increased to the 0
inputs, processes them using the internal algorithm and produces square wave output
signals having 0-3.3 V amplitudes.
5 V low and high levels which are required value for the input of IGBT driver.
0.6 V diode voltage drop is used to increase the output voltage level to 3
permissible by the IGBT driver cards.
UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
93
.2. Voltage Transducers
phase set of voltages are measured from the supply
400 transducer cards. The card is adjusted to read
peak
. Transducer card used in the thesis is shown in Figure 5.17
. LEM LV25-400 voltage transducer cards
Signal Conditioner/Interface Board
The voltage measurement is achieved using transducers
voltages are measured using voltage transducers. The transducers
value to 1.5 V
peak
sinusoidal signals. The signal conditioning card is
offset to the transducer outputs and bufferin
this way, the analog input signals are increased to the 0-3V
pk
level
inputs, processes them using the internal algorithm and produces square wave output
3.3 V amplitudes. DSP outputs must be amplified from 0
5 V low and high levels which are required value for the input of IGBT driver.
6 V diode voltage drop is used to increase the output voltage level to 3
permissible by the IGBT driver cards.
UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
supply side by using
400 transducer cards. The card is adjusted to read 220 V
rms
and
is shown in Figure 5.17.

The voltage measurement is achieved using transducers circuit and offset
voltages are measured using voltage transducers. The transducers
The signal conditioning card is
offset to the transducer outputs and buffering DSP outputs. By
level. DSP takes the
inputs, processes them using the internal algorithm and produces square wave output
DSP outputs must be amplified from 0-3.3 V to 0-
5 V low and high levels which are required value for the input of IGBT driver. The
6 V diode voltage drop is used to increase the output voltage level to 3.9 V that is
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
94
The circuit diagram of input section of signal conditioning card is shown in
Figure 5.18. The output of each voltage transducer is connected to the input section
of signal conditioning card as can been seen from the left side in Figure 5.18. Voltage
transducers output a current proportional to voltage applied to its primary.


Figure 5.18. Picture of signal conditioner/interface board

5.4.4. H-Bridge PWM Inverters

The circuit diagram of a single-phase H bridge inverter is given in Figure
5.19. Semikron SKM75GB123D IGBT modules are used to construct the H bridge
inverters. Each IGBT module consists of two IGBTs connected in top bottom
configuration. The inverters are fed from a 270V
DC
supply and give190 V
AC
output at
maximum modulation index. These voltages are filtered and injected to the lines
through injection transformers. The three-phase H-bridge inverters used in the thesis
are shown in Figure 5.19. Each of the IGBT drivers drives two IGBTs on the same
leg of the inverter as shown in Figure 5.19.
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
95

Figure 5.19. Three base VSI with IBGT modules and IGBT driver boards

5.4.5. Passive LC Output Filter

L
f
= 10mH and C
f
= 18F are chosen. The nominal values of inductor and
capacitor are 11A/350 V and 6A/400V, respectively. The designed LC filter is shown
in Figure 5.20.

IGBT module
Heat sink
IGBT driver
Fan
DC link
Gate signals
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
96

Figure 5.20. PassiveLC filters for three-phases of DVR

5.4.6. Injection Transformer

The output of the LC filter is given to the load using a transformer rated at
440:88 V
rms
(turns ratio 5:1). 1 kVA single-phase injection transformers are shown in
Figure 5.21.

Inductor of LC filter
Capacitor of LC filter
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
97

Figure 5.21. Single-phase injection transformers

5.5. Practical Recommendations for Experimental Study

The following recommendations and suggestions can save time and money
during experimental studies.
i. Floating point DSP should be used in the experimental study because it has
the following advantages (Cuma, 2010):
Many algorithms used in control applications see a performance boost
from native floating-point. These algorithms such as square root, division, sine,
cosine, FFT have a floating point nature.
Coding is simplified as one can easily use float data type and use it in
control algorithms.
The scaling and saturation burden seen in fixed point is removed.
The floating point unit of F28335 follows the IEEE 754 format for
single precision floating point math.
Injection transformer
Primary
Secondary
Phase_A
Phase_B
Phase_C
_
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
98
ii. DSP cables should be shielded to reduce their sensitivity to EMI caused
by opening and closing the power switches.
iii. IGBT snubber circuits should be used to prevent the creation of large
over-voltage due to di/dt.
iv. The length of the cable between DC link capacitor and IGBT inverter
should be minimum to reduce the creation of large over-voltage due to di/dt. If
available a laminated busbur should be used.
v. Low noise and high precision operational amplifier should be used in
measurement, signal conditioning and protection boards.
vi. The supplies of measurement signal conditioning and protection boards
should be fed from an isolation transformer.
vii. Shielded twisted pair cable should be used to eliminate inductive and
capacitive coupling.
viii. Accurate and fast measurements of voltage and current are key point for
correct operation and control. Measurement devices (current transformers, current
transducers and voltage transducer) with high accuracy, fast response time and low
power consumption should be used in the experimental studies.
ix. Intelligent power modules that integrate power devices, drivers and
protection circuitry in an ultra compact package provide compact, high precise, low
noise and high performance solution. They satisfy user needs for higher frequency
operation to provide a noiseless inverter.
x. DC power supply of DVR should generate output voltage with low noise,
low ripple, excellent load and line regulation. It should present advanced protection
capabilities.
xi. Circuit protection devices such as circuit breakers, fuses and residual
current protection switch should be properly selected to automatically limit or cut off
the flow of electricity when a ground fault, overload or short circuit occur in the
wiring system. Very fast current limiting fuses should be used to limit both the
magnitude and duration of current flow under short circuit conditions.
xii. Grounding is very important. Improper grounding can be the source of
errors, noise and a lot of trouble.
5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
99
5.6. Summary

This section contains step-by-step design procedures for UPQC and OPEN
UPQC consisting of both shunt (APF) and series (DVR) compensators. The
important criterion for design process is to satisfy the standard limits for PQ. The
power circuit of APF consists of inverter circuit, DC capacitor and passive filters.
The design procedures and rating selections of APF components are mathematically
analyzed. The power circuit of DVR consists of inverter circuit, DC energy storage,
passive filter and injection transformer. The design procedures and rating selections
of DVR components are mathematically analyzed. Practical recommendations and
suggestions for experimental study are presented in order to minimize the time and
financial losses.
The next chapter presents the extensive simulation cases to test the
performance of proposed both proposed UPQC and OPEN UPQC using
PSCAD/EMTDC.
























5. DESIGN OF UNIFIED POWER QUALITY CONDITIONER Ahmet TEKE
100






6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
101
6. SIMULATION STUDY OF UPQC TOPOLOGIES

In this section, the reference current/voltage extraction capabilities of
APF/DVR under unbalanced and distorted supply conditions are presented using
PSCAD/EMTDC program. Several case studies are presented to test the overall
performance of both proposed UPQC and OPEN UPQC. The control algorithms are
the same for both proposed UPQC and OPEN UPQC. UPQC uses common DC link
for APF and DVR. OPEN UPQC uses two separate energy storage devices for APF
and DVR. The data of simulation parameters are summarized in Table 6.1.

Table 6.1. Data of the simulated UPQC system
SYSTEM
Supply voltage Phase_A: 126.26V
rms
, 2.39%THD
Phase_B: 131.96V
rms
, 2.56%THD
Phase_C: 125.49V
rms
, 2.72%THD
System frequency 50 Hz

ACTIVE POWER FILTER
Smoothing inductor Phase_A: 19.41 mH, Phase_B: 20.04 mH,
Phase_C: 19.49 mH
Choke reactor Phase_A: 6.14 mH, Phase_B: 6.07 mH,
Phase_C: 6.21 mH
DC link capacitor and voltage 2200F, 375V
DC

Sampling time 25 s

DYNAMIC VOLTAGE RESTORER
Switching frequency 10 kHz
Inverter filter Capacitance: 18 F, 400 V
Phase_A: 8.42 mH, Phase_B: 8.28 mH,
Phase_C: 8.1 mH
Transformer Primary/Secondary: 440/88V
rms
, 1 kVA
DC supply 270 V
DC

Sampling time 20 s

RESISTIVE LOAD
Three-phase resistive load R=90/6500 W, Two resistors in series



6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
102
6.1. Controller of Proposed APF

The simulation model of APF control system is shown in Figure 6.1. The
control system is consisting of reference current generation, hysteresis current
control and firing pulse generation blocks. The details and operating principles of
proposed APF control system are mentioned in Section 4.2.2.


Figure 6.1. Simulation model of proposed APF control system


Voltage /current
measurements
and Alpha-Beta transform
VrA
IrA
IrB
IrC
Vaph
Iaph
Ibta
B
+
D
+
F
+
B
+
D
+
F
+
*
0. 8165
*
-0 . 4082
*
-0 . 4082
*
0
*
0. 7071
*
-0 . 7071
Pinst
*
Iaph
Vaph
*
Ibta
Vbta
B
+
F
+
*
Iaph
Ibta
B
-
F
+
Vbta
*
Vaph
Qinst
B
-
F
+
Qinstdc
Vcappi
B
+
F
-
q
_ i
n
s
t
p
_
i
n
s
t Calculation of

p
~
p

q
~
q
*
*
B
+
F
-
G
-
Vaph
Pinst
Vbta
Qinst
*
*
B
+
F
+
G
+
Pinst
Qinst
Vbta
Vaph
N
D
N/D
N
D
N/D
a2pb2
a2pb2
Vaph
*
Vaph
B
+
F
+
*
Vbta
Vbta
a 2pb 2
GR
*
Vbta
*
Vaph
*
GR
IcRef
IbRef
IaRef
*
GR
*
GR
B
+
D
+
B
+
D
+
*
0. 8165

D
+
*
0
*
- 0 . 4082
*
0. 7071
*
- 0 . 4082
*
- 0 . 7071
0. 0
0. 0
Calculation of
reference signals
e
-sT
*
1
Vbta
D
+
F
-
err_A
IaRef
err _A
G1
G4
Ifa
D
+
F
-
err _B
IbRef
err_B
G3
G6
Ifb
D
+
F
-
err _C
IcRef
err _ C
G5
G2
Ifc Gate signal
generation
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
103
6.2. Controller of Proposed DVR

PSCAD/EMTDC models of DVR control system for reference signal
generation and sag/swell detection are shown in Figures 6.2a and 6.2b.


Figure 6.2a. PSCAD/EMTDC model of DVR control system: Reference signal
generation

1 2 3 4
1 2 3 4
1 2 3 4
eA
eB
eC
Pa
Pb
Pc
Comparator
Vapu
+
-
* K 2
+
+
+
+
Sin
*
*
yA
Pi
A
Pi
*
100
Sin
1
sT
1
sT
tetaA
Vbpu
+
-
*
+
+
+
+
Sin
*
*
yB
Pi *
-0 . 5
B
Pi
*
100
Sin
1
sT
1
sT
Vcpu
+
-
*
+
+
+
+
Sin
*
*
yC
Pi
*
-0.5
C
Pi
*
100
Sin
1
sT
1
sT
tetaB
tetaC
+
-
xA
yA
eA
+
-
xB
yB
eB
+
-
xC
yC
eC
K 1
K2 K1
K 2 K 1
K3
K3
K 3
K4
K4
K 4
Error calculation
for Phase_A
Error calculation
for Phase_B
Error calculation
for Phase_C
PWM signal
generation
PWM signal
generation
PWM signal
generation
E- PLL: Amplitude and phase angle
extraction for Phase_A
E-PLL: Amplitude and phase angle
extraction for Phase_B
E-PLL: Amplitude and phase angle
extraction for Phase_C
*-
0
.
5
Comparator
Comparator
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
104

Figure 6.2b. PSCAD/EMTDC model of DVR control system: Sag/swell detection

6.3. Simulation Verification of Proposed UPQC

In this section, the reference current/voltage extraction capabilities of
APF/DVR under distorted supply conditions and the minimum energy injection
capability of proposed DVR are presented. Three case studies are presented to test
the overall performance of proposed UPQC. PSCAD/EMTDC diagram of proposed
UPQC system is shown in Figure 6.3.
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
105
C
o
n
tr
o
lle
r
o
f D
V
R
0
.0
0
6
0
7
[H
]
0
.0
0
6
1
4
[H
]
0
.0
0
6
2
1
[H
]
4 5 [o hm]
D D
D D
D D
Ir
A
Ir
B
Ir
C
V
r
B
V
r
C
Vcap
1 3 5
4 6 2
G1 G3 G5
G4 G6 G2
0 . 0 1 9 4 1 [ H ]
I f a
I f b
I f c
0 . 0 2 [ H ]
0 . 0 1 9 4 9 [ H ]
V
a
V
b
V
c
2
2
0
0
[u
F
]
V
r
A
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
V a p
R = 0
V f
f r
R = 0
V f
f r V b p
R = 0
V f
f r V c p
V
d
v
r
A
V
d
v
r
B
V
d
v
r
C
8.2 8 [mH]
8.4 2 [mH]
1
8
[u
F
]
1
8
[u
F
]
8.1 [mH]
# 1 # 2
# 1 # 2
# 1 # 2
g 2 g 4
g 3
1
g 1
4
2 3
g 6 g 8
g 7
1
g 5
4
2 3
g 1 0 g 1 2
g 1 1
1
g 9
4
2 3
C
o
n
tr
o
lle
r
o
f A
P
F
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
V a a
R = 0
V f
f r
R = 0
V f
f r V b a
R = 0
V f
f r V c a
B R K _ A p
B R K _ B p
B R K _ C p
B R K _ A a
B R K _ B a
B R K _ C a
1
8
[u
F
]
D
Y
N
A
M
IC
V
O
L
T
A
G
E

R
E
S
T
O
R
E
R
A
C
T
IV
E
P
O
W
E
R
F
IL
T
E
R
S
U
P
P
L
Y
_
1
S
U
P
P
L
Y
_
2
6
B
R
ID
G
E

R
E
C
T
IF
IE
R
C
H
O
K
E

R
E
A
C
T
O
R
S
M
O
O
T
H
IN
G

IN
D
U
C
T
O
R D
C

C
A
P
A
C
IT
O
R
L
C
F
IL
T
E
R
IN
J
E
C
T
IO
N

T
R
A
N
S
F
O
R
M
E
R
H
B
R
ID
G
E

IN
V
E
R
T
E
R
3
P
H
A
S
E

IN
V
E
R
T
E
R
H
A
R
M
O
N
IC

C
O
M
P
O
N
E
N
T
S

Figure 6.3. PSCAD/EMTDC model of UPQC
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
106
6.3.1. Simulation Results for Standby Operation of DVR

During standby operation of DVR, two lower IGBTs of each phase H-bridge
inverter remain turned on while the two upper IGBTs remain turned off. Each H-
bridge inverter is controlled independently by using an independent sag detection
method for each phase as mentioned in Section 4.2.3. With this method, minimum
energy is injected and switching losses are minimized. The sag detection signals of
each phase of H-bridge inverters are shown in Figure 6.4. In this case, single-phase
25% voltage sag is occurred on phase_A of supply voltage at 0.8 s, so the amplitude
of phase_B and phase_C of supply voltage are at their nominal value. The inverter of
phase_A is in operating mode because the sag detection signal enables the gate signal
generation. But, the inverters of phase_B and phase_C are in stand-by mode.


Figure 6.4. Sag detection signals for H-bridge inverters of supply voltages





6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
107
6.3.2. Simulation Results for Reference Current Extraction

The waveforms of load current, reference current using traditional IRPT
theory and reference current using improved IRPT theory are shown in Figure 6.5
when the supply voltage is unbalanced and harmonic distorted as stated in Table 6.1.


Figure 6.5. The load current and generated reference currents

Traditional IRPT theory fails to generate the required compensation signal
when the load voltage is distorted and unbalanced. This disadvantage can be
eliminated using improved IRPT theory in which the load voltage is filtered using all
pass filter and the alpha-beta components are virtually generated as explained in
Section 4.1.2.

6.3.3. Simulation Results for Voltage Sag Compensation and Current Harmonic
Elimination with Proposed UPQC

In this section, PSCAD/EMTDC simulation results are presented to show the
performance of UPQC for sag mitigation and current harmonic elimination. There
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
108
are four possible types of faults that can occur in a typical power distribution system.
The probabilities of prevalence of the various types of faults are as follows
(Kirawanich et al., 2003):
1- Single line-to-ground faults: 70%
2- Line-to-line faults: 15%
3- Double line-to-ground faults: 10%
4- Three-phase faults: 5%
The case studies are performed taking the findings of (Kirawanich et al.,
2003) into consideration. Three cases are comprehensively analyzed: Case 1) No
voltage sag and current harmonic elimination, Case 2) 25% single-phase voltage sag
and current harmonic elimination, Case 3) 20% double phase voltage sag and current
harmonic elimination.

6.3.3.1. Case Study1: No Voltage Sag, Current Harmonic Elimination

At stand-by operation (no-fault condition), DVR injects no voltage to the
system (DVR is in OFF-mode). The supply voltages and load voltages are in phase
with each other (blue: phase_A, green: phase_B, red: phase_C). The waveform of
load voltage contains more harmonic component than the supply voltage because
current harmonic causes a voltage drop on a series transformer as shown in Figure
6.6 (V
lA
=V
sA
-V
injA
).

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
109

Figure 6.6. The waveforms of supply and load voltages for Case 1

RMS trends of supply and load voltages are shown in Figure 6.7. The trends
are identical to each other.
Figure 6.7. RMS trends of supply and load voltages

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
110
APF is on line and eliminates the load current harmonics as shown in Figure
6.8. At stand-by operation (no-fault condition), average load voltage THD is 2.22%
and supply current THD is 4.09%.


Figure 6.8. Waveforms of supply voltages and supply currents during Case 1

The load voltage is identical to supply voltage as shown in the Figure 6.9.
The voltage waveforms indicate the supply (V
sA
), injected (V
inj
) and load (V
lA
)
voltages of Phase_A, respectively. The current waveforms indicate the supply (I
sA
),
injected (I
injA
) and load (I
lA
) currents of Phase_A, respectively. DC link capacitor
voltage is almost kept constant during voltage sag.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
111

Figure 6.9. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 1

The instantaneous THD contents of supply and filtered currents for Phase_A
are presented in Table 6.2. The amplitudes of low order harmonics (5
th
, 7
th
, 11
th
and
13
th
) are high in load current. APF injects the required compensation current to the
system and the amplitudes of low order harmonics are minimized in the supply
current.

Table 6.2. THD contents of load and supply currents of Phase_A for Case 1
THD content of Phase_A
load current

THD content of Phase_A
supply current

Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.01

1 100 18 0.11
2 0.04 19 0.86

2 0.1 19 0.34
3 1.57 20 0.01

3 1.19 20 0.08
4 0.08 21 0.03

4 0.22 21 0.08
5 22.19 22 0.01

5 3.47 22 0.06
6 0.02 23 0.97

6 0.32 23 0.29
7 8.1 24 0.01

7 1.12 24 0.08
8 0.02 25 0.52

8 0.13 25 0.24
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
112
9 0.52 26 0.01

9 0.12 26 0.11
10 0.02 27 0.07

10 0.19 27 0.17
11 5.46 28 0.01

11 0.73 28 0.11
12 0.02 29 0.47

12 0.19 29 0.22
13 2.62 30 0.01

13 0.55 30 0.06
14 0.01 31 0.41

14 0.07 31 0.07
15 0.05

15 0.01

16 0.01
THD(%)=24.54

16 0.05
THD(%)=4.09
17 1.7

17 0.76

6.3.3.2. Case Study2: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination

DVR comes into ON-mode and injects missing voltage to the system during
the voltage sag. 25% single-phase voltage sag occurs on phase_A of supply voltage
but the phase_A of load voltage is not affected by voltage sag with the help of DVR.
The supply voltages and load voltages are in phase with each other as shown in
Figure 6.10.


Figure 6.10. The waveforms of supply and load voltages for Case 2

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
113
RMS trends of supply and load voltages are shown in Figure 6.11. RMS value
of phase_A load voltage is maintained constant at its nominal value during voltage
sag.


Figure 6.11. RMS trends of supply and load voltages

The waveform results for 25% sag on phase_A of supply voltage for 3s
duration are shown in Figure 6.12. The phase_A load current so its load voltage is
not affected during the voltage sag as shown in Figure 6.12. The waveform of load
voltage is identical with load current waveforms because the load is purely resistive.
The phase_A load current is not affected when the voltage sag occurs on Phase_A.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
114

Figure 6.12. Waveforms of supply voltages and currents during Case 2

DVR injects the missing voltage to the system in series and APF injects the
compensation current to the system in shunt as shown in Figure 6.13.


Figure 6.13. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 2

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
115
THD contents of supply and filtered currents for Phase_A are presented in
Table 6.3. The amplitudes of characteristic harmonics (5
th
, 7
th
, 11
th
and 13
th
) are high
in load current. APF injects the required compensation current to the system and the
amplitudes of characteristic harmonics are minimized in the supply current.

Table 6.3. THD contents of load and supply currents of Phase_A for Case 2
THD content of Phase_A
load current

THD content of Phase_A
supply current

Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.2

1 100 18 0.04
2 1.02 19 0.83

2 1.63 19 0.19
3 1.27 20 0.02

3 2.53 20 0.05
4 2.1 21 0.12

4 1.47 21 0.16
5 22.68 22 0.07

5 2.7 22 0.08
6 0.24 23 1.01

6 0.57 23 0.11
7 7.69 24 0.13

7 1.61 24 0.04
8 0.21 25 0.48

8 0.23 25 0.21
9 0.46 26 0.02

9 0.59 26 0.05
10 0.51 27 0.09

10 0.26 27 0.09
11 5.51 28 0.13

11 1.03 28 0.04
12 0.31 29 0.5

12 0.04 29 0.07
13 2.5 30 0.14

13 0.76 30 0.09
14 0.09 31 0.38

14 0.19 31 0.09
15 0.15

15 0.19

16 0.26
THD(%) 24.94

16 0.1
THD(%) 4.93
17 1.66

17 0.68


At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference, the capacitor voltage and delay originated from
sag detection time. The waveforms of supply voltages and load currents are shown in
Figure 6.14. When the sag occurs, only the related H-bridge inverter of DVR starts to
operate. The voltage sag occurs only on phase_A of supply voltage. The phase_A of
load current (so its voltage) does not affected by voltage sag.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
116

Figure 6.14. Three-phase voltage and current waveforms at starting of single-
phase25% voltage sag for Case 2

At the ending of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. As
shown in the Figure 6.15, DVR comes into standby operation whenever the sag ends.
THD of the load voltages is always kept below the IEEE voltage harmonic limits
(IEEE Std 519, 1995).


6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
117
Figure 6.15. Three-phase voltage and current waveforms at ending of single-phase
25% voltage sag for Case 2
6.3.3.3. Case Study3: 20% Double Phase Voltage Sag, Current Harmonic
Elimination

DVR is in ON-mode and injects the missing voltage to the system during the
voltage sag as shown in Figure 6.16. The supply voltage and load voltage are in
phase with each other. 20% voltage sag occurs on phase_A and phase_B of supply
voltage but the phase_A and phase_B of load voltage are not affected by voltage sag
with the help of DVR.

Figure 6.16. The waveforms of supply and load voltages for Case 3

RMS trends of supply and load voltages are shown in Figure 6.17. RMS
values of phase_A and phase_B load voltages are maintained constant at its nominal
value during voltage sag.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
118

Figure 6.17. RMS trends of supply and load voltages

The waveform results for 20% double phase sag on phase_A and phase_B of
supply voltage for 3 s duration are shown in Figure 6.18. Phase_A and phase_B load
currents so their load voltages are not affected by voltage sag. The load voltage
waveform is identical with load current waveforms because the load is purely
resistive. Phase_A and Phase_B load currents are not affected when a voltage sag
occurs on Phase_A and Phase_B of supply voltage.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
119
Figure 6.18. The waveforms of supply voltages and currents during Case 3

DVR injects the missing voltage to the system in series and APF injects the
filter current to the system in shunt as shown in Figure 6.19. DC link capacitor
voltage is almost kept constant during voltage sag.


6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
120
Figure 6.19. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 3
THD contents of supply and filtered currents for Phase_A are presented in
Table 6.4.

Table 6.4. THD contents of supply and filtered currents of Phase_A for Case 3
THD content of Phase_A
load current
THD content of Phase_A
supply current
Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.2

1 100 18 0.1
2 0.64 19 0.88

2 0.95 19 0.42
3 1.08 20 0.14

3 1.44 20 0.1
4 1.02 21 0.13

4 0.55 21 0.12
5 22.8 22 0.23

5 2.37 22 0.13
6 0.82 23 1.03

6 1.1 23 0.11
7 7.69 24 0.08

7 1.12 24 0.06
8 0.73 25 0.48

8 0.24 25 0.13
9 0.36 26 0.1

9 0.11 26 0.03
10 0.54 27 0.14

10 0.2 27 0.05
11 5.59 28 0.19

11 1.11 28 0.13
12 0.6 29 0.55

12 0.21 29 0.02
13 2.53 30 0.09

13 0.84 30 0.09
14 0.4 31 0.41

14 0.15 31 0.05
15 0.15

15 0.07

16 0.38
THD(%)=24.77

16 0.05
THD(%)=3.75
17 1.74

17 0.6

At the starting of sag, the load voltage is affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. As
shown in Figure 6.20, when the sag occurs, only the related H-bridge inverters of
DVR start to operate. As also shown in the current waveforms, the sag occurs on
phase_ A and phase_B. The phase_ A and phase_B load currents so their voltages are
not affected by sag.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
121

Figure 6.20. Three-phase voltage and current waveforms at starting of double phase
20% voltage sag for Case 3

At the ending of sag, the load voltage is affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. As
shown in the Figure 6.21, DVR comes into standby operation whenever the sag ends.
THD of the load voltages is always kept below the IEEE voltage harmonic limits
(IEEE Std 519, 1995).

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
122

Figure 6.21. Three-phase voltage and current waveforms at ending of double phase
20% voltage sag for Case 3

6.4. Simulation Verification of Proposed OPEN UPQC

In this section, PSCAD/EMTDC simulation results are presented to show the
performance of OPEN UPQC for sag mitigation and current harmonic elimination.
Three cases are comprehensively analyzed: Case 1) No voltage sag and current
harmonic elimination, Case 2) 25% single-phase voltage sag and current harmonic
elimination, Case 3) 20% double phase voltage sag and current harmonic
elimination. PSCAD/EMTDC diagram of proposed OPEN UPQC system is shown in
Figure 6.22.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
123
C
o
n
tr
o
lle
r
o
f D
V
R
0
.0
0
6
0
7
[H
]
0
.0
0
6
1
4
[H
]
0
.0
0
6
2
1
[H
]
4 5 [o h m]
D D
D D
D D
Ir
A
Ir
B
Ir
C
V
r
B
V
r
C
Vc a p
1 3 5
4 6 2
G1 G3 G5
G4 G6 G2
0 . 0 1 9 4 1 [ H ]
I f a
I f b
I f c
0 . 0 2 [ H ]
0 . 0 1 9 4 9 [ H ]
V
a
V
b
V
c
R = 0
2
2
0
0
[u
F
]
V
r
A
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
V a p
R = 0
V f
f r
R = 0
V f
f r V b p
R = 0
V f
f r V c p
V
d
v
r
A
V
d
v
r
B
V
d
v
r
C
8 .2 8 [mH ]
8 .4 2 [mH ]
1
8
[u
F
]
1
8
[u
F
]
8 .1 [mH]
# 1 # 2
# 1 # 2
# 1 # 2
g 2 g 4
g 3
1
g 1
4
2 3
g 6 g 8
g 7
1
g 5
4
2 3
g 1 0 g 1 2
g 1 1
1
g 9
4
2 3
C
o
n
tr
o
lle
r
o
f A
P
F
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
R = 0 R = 0 R = 0
V a a
R = 0
V f
f r
R = 0
V f
f r V b a
R = 0
V f
f r V c a
B R K _ A p
B R K _ B p
B R K _ C p
B R K _ A a
B R K _ B a
B R K _ C a
1
8
[u
F
]
D
Y
N
A
M
IC
V
O
L
T
A
G
E

R
E
S
T
O
R
E
R
A
C
T
IV
E
P
O
W
E
R
F
IL
T
E
R
S
U
P
P
L
Y
_
1
S
U
P
P
L
Y
_
2
6
B
R
ID
G
E

R
E
C
T
IF
IE
R
C
H
O
K
E

R
E
A
C
T
O
R
S
M
O
O
T
H
IN
G

IN
D
U
C
T
O
R D
C

C
A
P
A
C
IT
O
R
D
C
L
IN
K
L
C
F
IL
T
E
R
IN
J
E
C
T
IO
N

T
R
A
N
S
F
O
R
M
E
R
H
B
R
ID
G
E

IN
V
E
R
T
E
R
3
P
H
A
S
E

IN
V
E
R
T
E
R
H
A
R
M
O
N
IC

C
O
M
P
O
N
E
N
T
S

Figure 6.22. PSCAD/EMTDC model of OPEN UPQC
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
124
6.4.1. Case Study4: No Voltage Sag, Current Harmonic Elimination

DVR is in OFF-mode and injects any voltage to the system when no voltage
sags occur on supply voltage. The supply voltages and load voltages are in phase
with each other (blue: phase_A, green: phase_B, red: phase_C) as shown in Figure
6.23 (V
lA
=V
sA
-V
injA
).


Figure 6.23. The waveforms of supply and load voltages for Case 4

RMS trends of supply and load voltages are shown in Figure 6.24. The rms
trends are identical to each other.
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
125
Figure 6.24. RMS trends of supply and load voltages

APF is on line and eliminates the load current harmonics as shown in Figure
6.25. At stand-by operation (no-fault condition), average load voltage THD is 2.75%
and supply current THD is 4.05%.


Figure 6.25. Waveforms of supply voltages and supply currents during Case 4

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
126
The load voltage waveform is identical to supply voltage waveform as shown
in Figure 6.26.


Figure 6.26. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 4

The instantaneous THD contents of supply and filtered currents for Phase_A
are presented in Table 6.5. The amplitudes of low order harmonics (5
th
, 7
th
, 11
th
and
13
th
) are high in load current. APF injects the required compensation current to the
system and the amplitudes of low order harmonics are minimized in the supply
current.

Table 6.5. THD contents of load and supply currents of Phase_A for Case 4
THD content of Phase_A
load current

THD content of Phase_A supply
current
Order (%) Order (%) Order (%) Order (%)
1 100 18 0.01 1 100 18 0.06
2 0.03 19 0.89 2 0.14 19 0.46
3 1.53 20 0.01 3 1.06 20 0.06
4 0.07 21 0.03 4 0.07 21 0.09
5 22.21 22 0.01 5 2.41 22 0.09
6 0.03 23 0.95 6 0.16 23 0.19
7 7.97 24 0.01 7 2.22 24 0.06
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
127
8 0.02 25 0.52 8 0.07 25 0.08
9 0.53 26 0.01 9 0.23 26 0.02
10 0.01 27 0.10 10 0.07 27 0.04
11 5.41 28 0.01 11 1.49 28 0.02
12 0.02 29 0.54 12 0.02 29 0.14
13 2.60 30 0.01 13 1.08 30 0.03
14 0.01 31 0.41 14 0.01 31 0.03
15 0.05

15 0.23
16 0.01
THD (%)24.5
16 0.02
THD (%)4.05
17 1.59 17 0.85

6.4.2. Case Study5: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination

25% single voltage sag occurs on phase_A of supply voltage but the phase_A
of load voltage is not affected by voltage sag with the help of DVR. The supply
voltages and load voltages are in phase with each other as shown in Figure 6.27.


Figure 6.27. The waveforms of supply and load voltages for Case 5

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
128
RMS trends of supply and load voltages are shown in Figure 6.28. RMS
value of phase_A load voltage is maintained constant at its nominal value during
voltage sag.

Figure 6.28. RMS trends of supply and load voltages

The waveform results for 25% sag on phase_ A of supply voltage for 3 s
duration are shown in Figure 6.29. The phase_A load current so its load voltage is
not affected during the voltage sag as shown in Figure 6.29. The load voltage
waveform is identical with load current waveforms because the load is purely
resistive.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
129

Figure 6.29. Waveforms of supply voltages and currents during Case 5

DVR injects the missing voltage to the system in series and APF injects the
compensation current to the system in shunt as given in Figure 6.30.


Figure 6.30. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 5

THD contents of supply and filtered currents for Phase_A are presented in
Table 6.6. The amplitudes of characteristic harmonics (5
th
, 7
th
, 11
th
and 13
th
) are high
in the load current. APF injects the required compensation current to the system and
the amplitudes of characteristic harmonics are minimized in the supply current.
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
130
Table 6.6. THD contents of load and supply currents of Phase_A for Case 5
THD content of Phase_A
load current
THD content of Phase_A
supply current
Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.23

1 100 18 0.06
2 1.18 19 1.04

2 0.92 19 0.45
3 0.84 20 0.22

3 0.47 20 0.06
4 1.86 21 0.38

4 0.62 21 0.02
5 22.82 22 0.1

5 1.94 22 0.13
6 0.46 23 1.02

6 0.1 23 0.12
7 7.52 24 0.14

7 2.48 24 0.03
8 0.93 25 0.57

8 0.4 25 0.08
9 0.58 26 0.15

9 0.34 26 0.08
10 0.6 27 0.39

10 0.51 27 0.01
11 5.6 28 0.05

11 1.7 28 0.08
12 0.28 29 0.56

12 0.12 29 0.19
13 2.63 30 0.09

13 1.23 30 0.08
14 0.44 31 0.57

14 0.2 31 0.01
15 0.42

15 0.13

16 0.36
THD(%)25.09

16 0.1
THD(%)4.14
17 1.67

17 0.68


At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. The
waveforms of supply voltages and load currents are shown in Figure 6.31. When the
sag occurs, only the related H-bridge inverter of DVR starts to operate as shown in
Figure 6.31.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
131

Figure 6.31. Three-phase voltage and current waveforms at starting of single-
phase25% voltage sag for Case 5

At the ending of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. DVR
comes into standby operation whenever the sag ends as shown in Figure 6.32. THD
of the load voltages is always kept below the IEEE voltage harmonic limits (IEEE
Std 519, 1995).

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
132

Figure 6.32. Three-phase voltage and current waveforms at ending of single-phase
25% voltage sag for Case 5

6.4.3. Case Study6: 20% Double Phase Voltage Sag, Current Harmonic
Elimination

DVR comes into ON-mode and injects the missing voltage to the system
during the voltage sag as shown in Figure 6.33. The supply voltage and load voltage
are in phase with each other. 20% voltage sag occurs on phase_A and phase_B of
supply voltages but the phase_A and phase_B of load voltages are not affected by
voltage sag with the help of DVR.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
133
Figure 6.33. The waveforms of supply and load voltages for Case 6

RMS trends of supply and load voltages are shown in Figure 6.34. RMS
values of phase_A and phase_B load voltages are maintained constant at its nominal
value during voltage sag.


Figure 6.34. RMS trends of supply and load voltages

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
134
The waveform results for 20% double phase sag on phase_A and phase_B of
supply voltage for 3 s duration are shown in Figure 6.35. The phase_ A and phase_B
load currents so their load voltages are not affected by voltage sagas shown in Figure
6.35. The load voltage waveform is identical with load current waveforms because
the load is purely resistive. Phase_A and Phase_B load currents are not affected when
voltage sag occurs on Phase_A and Phase_B of supply voltage.

Figure 6.35. Waveforms of supply voltages and currents during Case 6

APF injects the filter current to the system in shunt and DVR injects the
missing voltage to the system in series as shown in Figure 6.36. DC link capacitor
voltage is almost kept constant during voltage sag.

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
135

Figure 6.36. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 6

THD contents of supply and filtered currents for Phase_A are presented in
Table 6.7.

Table 6.7. THD contents of supply and filtered currents of Phase_A for Case 6
THD content of Phase_A
load current
THD content of Phase_A supply
current
Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.15

1 100 18 0.05
2 0.49 19 0.89

2 1.3 19 0.37
3 1.46 20 0.05

3 0.75 20 0.03
4 1.08 21 0.17

4 0.34 21 0.09
5 22.49 22 0.03

5 1.97 22 0.04
6 0.47 23 1.03

6 0.15 23 0.08
7 7.88 24 0.09

7 2.68 24 0.05
8 0.44 25 0.5

8 0.26 25 0.07
9 0.32 26 0.02

9 0.31 26 0.09
10 0.22 27 0.16

10 0.11 27 0.05
11 5.47 28 0.02

11 1.74 28 0.02
12 0.13 29 0.5

12 0.15 29 0.18
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
136
13 2.56 30 0.04

13 1.28 30 0.11
14 0.11 31 0.4

14 0.18 31 0.08
15 0.23

15 0.19

16 0.11
THD(%) 24.77

16 0.01
THD(%) 4.37
17 1.67

17 0.73


At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time as
shown in Figure 6.37. The phase_ A and phase_B load currents so their voltages are
not affected by sag.


Figure 6.37. Three-phase voltage and current waveforms at starting of double phase
20% voltage sag for Case 6

At the ending of sag, the load voltage is affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. DVR
comes into standby operation whenever the sag ends as shown in Figure 6.38. THD
of the load voltages is always kept below the IEEE voltage harmonic limits (IEEE
Std 519, 1995).

6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
137

Figure 6.38. Three-phase voltage and current waveforms at ending of double phase
20% voltage sag for Case 6

6.5. Summary

This chapter demonstrates the power conditioning capabilities of UPQC and
OPEN UPQC in PSCAD/EMTDC. The simulation results are presented to show the
performance of UPQC topologies for sag mitigation and current harmonic
elimination. Three possible types of faults that can occur in a typical power
distribution system are comprehensively analyzed:
Case 1) No voltage sag and current harmonic elimination,
Case 2) 25% single-phase voltage sag and current harmonic elimination,
Case 3) 20% double phase voltage sag and current harmonic elimination.
APF eliminates the load current harmonics and keeps the supply current
almost sinusoidal. DVR quickly senses the voltage sag and inject the missing voltage
to the system keeping the magnitude of the load voltage almost constant. UPQC and
OPEN UPQC perform superior performance to mitigate PQ problems during the
various types of faults.
The performance of OPEN UPQC is better than that of UPQC during start
and end points of voltage sag since OPEN UPQC is fed from two separate DC
6. SIMULATION STUDY OF UPQC TOPOLOGIES Ahmet TEKE
138
energy supplies. In UPQC, the active power required by series inverter is supplied
from DC capacitor during voltage sag. This can cause a voltage drop and fluctuation
of DC capacitor voltage that causes small anomalies during the start and end of
voltage sag.
The next chapter presents the extensive experimental results to show the
performance of proposed DSP based 6 kVA, 220 V
l-l
UPQC and DSP based 6 kVA,
220 V
l-l
OPEN UPQC. The experimental results are compared with the simulation
results.
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
139
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES

In this section, the minimum energy injection capability of proposed DVR
and the reference current/voltage extraction capabilities of proposed APF/DVR under
distorted supply conditions are presented as experimentally. Six case studies are
presented to test the overall performance of proposed UPQC and OPEN UPQC. The
data of experimental setup parameters are summarized in Table 7.1. The
experimental results are taken from the project Modeling and Implementation of
Custom Power Park which is supported by Scientific and Technological Research
Council of Turkey with project number of 106E188.

Table 7.1. Data of the experimental UPQC systems
SYSTEM
Supply voltage
(Phase to neutral)
Phase_ A: 126.26V
rms
, 2.39%THD
Phase_ B: 131.96V
rms
, 2.56%THD
Phase_ C: 125.49V
rms
, 2.72%THD
System frequency 50 Hz

ACTIVE POWER FILTER
Main circuit scheme Voltage source inverter scheme
DSP controller ezDSP TMS320F28335
IGBT inverter Semikron, SKM 75GB123D, 1200V, 50A
IGBT driver Semikron, SKHI 22BH4 R
Smoothing inductor Phase_A: 19.41 mH, Phase_B: 20.04 mH,
Phase_C: 19.49 mH
Choke reactor Phase_A: 6.14 mH, Phase_B: 6.07 mH,
Phase_C: 6.21 mH
Sampling time 25 s
DC link capacitor and voltage 2200F, 375V
DC

Voltage measurement LV25-P transducer, LV25-400, LV25-800, LEM
Current measurement CTF-5A current transformer

DYNAMIC VOLTAGE RESTORER
Main circuit scheme Voltage source inverter scheme
DSP controller ezDSP TMS320F2812
IGBT Inverter Semikron, SKM 75GB123D, 1200 V, 50 A
Switching frequency 10 kHz
IGBT driver Semikron, SKHI 22BH4 R
Inverter filter Capacitor: 18 F, 400 V
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
140
Inductor: Phase_A: 8.42 mH, Phase_B:
8.28mH, Phase_C: 8.1 mH
Transformer Primary/Secondary: 440/88V
rms
, 2 kVA
DC supply 270 V
DC

Voltage measurements LV25-P transducer, LV25-400, LEM
Sampling time 20 s

SAG/SWELL GENERATOR
Variable voltage supplies 18.75 kVA, 25 A, 3x380 V input, 3x(0-435)V
rms

variable output
Thyristor module 1200 V, 40 A Semikron SKKT 42/12E
Thyristor driver Semikron APTT-841M
Timer relay 220 V, single-phase AC time relay, 1 NO and 1
NC contacts, minimum 50 ms range,
3RP 1505-1BP30

3-PHASE BRIDGE RECTIFIER AND LOAD
Three-phase rectifier Semikron SKD62/16, 1600V, 60A
Three-phase resistive load R=45/6500 W, Two 90 resistors in series
Cooling Forced air

WAVEFORM MEASUREMENTS
Power quality analyzer Hioki 3196
Data logger Fluke 1760 PQ recorder
Digital oscilloscope Tektronix TDS 2014B

The control algorithms of APF are implemented with TMS320F28335 DSP
using C and assembly programming languages. The control algorithms of DVR are
implemented with TMS320F2812 DSP using C and assembly programming
languages. The software codes of controllers used in APF and DVR were presented
in (Cuma, 2010).

7.1. Experimental Results for Standby Operation of DVR

Two lower IGBTs of each phase H-bridge inverter remain turned on while the
two upper IGBTs remain turned off during standby operation of DVR. Each H-bridge
inverter is controlled independently by using an independent sag detection method
for each phase as mentioned in Section 4.2.3. With this method, minimum energy is
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
141
injected and switching losses are reduced. The firing signals of Phase_A and
phase_B for H-bridge inverters are demonstrated in Figure 7.1. In this case, sag is
occurred in phase_A of supply voltage, but the amplitude of phase_B of supply
voltage is in its nominal value. Signal_1 and Signal_2 are for the left leg IGBTs of
phase_A and Signals 3 and 4 for the left leg IGBTs of phase_B. The inverter of
phase_A is in operating mode, but the inverter of phase_B is in standby mode.



Figure 7.1. PWM signals for H-bridge inverters of Phase_A and Phase_B

7.2. Experimental Results for Reference Current Extraction

The experimental results of the load current, reference current using
traditional IRPT theory and reference current using improved IRPT theory are
demonstrated in Figure 7.2 when the supply voltage is unbalanced and harmonic
distorted as stated in Table 7.1.

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
142

Figure 7.2. Reference currents using traditional and improved IRPT methods


As demonstrated in Figure 7.2, traditional IRPT theory fails to generate the
required compensation signal and provides unsatisfactorily performance when the
load voltage is distorted and unbalanced. This disadvantage can be eliminated using
improved IRPT theory in which the load voltage is filtered using all pass filter and
the alpha-beta components are virtually generated as explained in Section 4.1.2.


7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
143
7.3. Experimental Results for Voltage Sag Compensation and Current
Harmonic Elimination with Proposed UPQC

In this section, the results of Hioki 3196 power quality analyzer are presented
to show the performance of UPQC for sag mitigation and current harmonic
elimination. Three cases are comprehensively analyzed:
Case 1) No voltage sag and current harmonic elimination,
Case 2) 25% single-phase voltage sag and current harmonic elimination,
Case 3) 20% double phase voltage sag and current harmonic elimination,
The experimental diagram of proposed UPQC system with measurement
points are demonstrated in Figure 7.3.


Figure 7.3. Experimental diagram of UPQC system with measurement points

7.3.1. Case Study1: No Voltage Sag, Current Harmonic Elimination

At stand-by operation (no-fault condition), DVR is in OFF-mode and injects
no voltage to the system. The supply voltage and load voltage are in phase with each
other. RMS trends of supply and load voltages are demonstrated in Figure 7.4.

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
144

Figure 7.4. RMS trends of supply and load voltages

APF is in ON-mode and eliminates the load current harmonics as
demonstrated in Figure 7.5. At stand-by operation, average load voltage THD is
2.22% and supply current THD is 4.3%. Phase_A, phase_B and phase_C are
indicated as red (CH1), green (CH2) and blue (CH3), respectively.


Figure 7.5. Waveforms of supply voltages and supply currents during Case 1

The load voltage is identical to supply voltage as demonstrated in Figure 7.6.
The voltage waveforms of CH1, CH2 and CH3 indicate the supply, injected and load
voltages of Phase_A, respectively. The current waveforms of CH1, CH2 and CH3
indicate the supply, injected and load currents of Phase_A, respectively.
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
145

Figure 7.6. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 1

THD contents of supply and filtered currents for Phase_A are presented in
Table 7.2. The amplitudes of low order harmonics (5
th
, 7
th
, 11
th
and 13
th
) are high in
the load current. APF injects the required compensation current to the system and the
amplitudes of low order harmonics are minimized in the supply current.

Table 7.2. THD contents of load and supply currents of Phase_A for Case 1
THD content of Phase_A
load current

THD content of Phase_A
supply current

Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.07

1 100 18 0.27
2 0.11 19 0.96

2 0.67 19 0.72
3 0.29 20 0.08

3 0.62 20 0.24
4 0.09 21 0.12

4 0.4 21 0.3
5 21.71 22 0.13

5 3.07 22 0.34
6 0.13 23 0.81

6 0.26 23 0.57
7 7.85 24 0.11

7 1.22 24 0.28
8 0.1 25 0.7

8 0.36 25 0.78
9 0.17 26 0.11

9 0.34 26 0.32
10 0.11 27 0.12

10 0.28 27 0.4
11 5.59 28 0.07

11 1.29 28 0.22
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
146
12 0.08 29 0.54

12 0.16 29 0.28
13 2.3 30 0.15

13 0.81 30 0.5
14 0.05 31 0.37

14 0.17 31 0.58
15 0.17

15 0.21

16 0.06
THD(%) 23.98

16 0.16
THD(%) 4.30
17 1.77

17 0.98


7.3.2. Case Study2: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination

When voltage sag on phase_A is detected, DVR starts to inject the missing
voltage to the system and keeps the load voltages at their 0.9-1.1 pu of nominal
voltages. The supply voltage and load voltage are in phase with each other. RMS
trends of supply and load voltages are demonstrated in Figure 7.7.


Figure 7.7. RMS trends of supply and load voltages

The waveform results for 25% sag on phase_A of supply voltage for 3 s
duration are demonstrated in Figure 7.8. The voltage waveforms of CH1 (red), CH2
(green) and CH3 (blue) indicate the phase_A, phase_B and phase_C supply voltages,
respectively. Similarly, the current waveforms of CH1, CH2 and CH3 indicate the
phase_A, phase_B and phase_C supply currents, respectively. The each division is
40V for voltage waveforms and 2.5A for current waveforms. The phase_A load
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
147
current so its load voltage is not affected by voltage sag as demonstrated in Figure
7.8. The load voltage waveform is identical with load current waveforms because the
load is purely resistive. The phase_A load current is not affected when a voltage sag
occurs on Phase_A.


Figure 7.8. Waveforms of supply voltages and currents during Case 2

The voltage waveforms of CH1, CH2 and CH3 indicate the supply voltage,
injected voltage and load voltage of Phase_A in Figure 7.9, respectively. The current
waveforms of CH1, CH2 and CH3 indicate the supply current, injected current and
load current of Phase_A, respectively.

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
148

Figure 7.9. Waveforms of Phase_A supply/injected/load voltages; supply/filter/load
currents during Case 2

THD contents of supply and filtered currents for Phase_A are presented in
Table 7.3. The amplitudes of characteristic harmonics (5
th
, 7
th
, 11
th
and 13
th
) are high
in load current. APF injects the required compensation current to the system and the
amplitudes of characteristic harmonics are minimized in the supply current.

Table 7.3. THD contents of load and supply currents of Phase_A for Case 2
THD content of Phase_A
load current
THD content of Phase_A
supply current
Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.05

1 100 18 0.1
2 0.31 19 0.66

2 0.53 19 0.89
3 1.86 20 0.07

3 1.4 20 0.21
4 0.18 21 0.24

4 0.33 21 0.25
5 22.47 22 0.11

5 3.25 22 0.41
6 0.09 23 1.02

6 0.25 23 0.51
7 7.28 24 0.11

7 1.02 24 0.29
8 0.16 25 0.43

8 0.27 25 0.71
9 1.31 26 0.1

9 0.34 26 0.26
10 0.15 27 0.17

10 0.33 27 0.33
11 5.86 28 0.07

11 0.92 28 0.3
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
149
12 0.06 29 0.64

12 0.15 29 0.52
13 1.78 30 0.09

13 0.85 30 0.33
14 0.06 31 0.22

14 0.19 31 0.69
15 0.52

15 0.29

16 0.07
THD(%) 24.64

16 0.13
THD(%) 4.41
17 2.02

17 0.66


At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. The
waveforms of supply voltages and load currents are demonstrated in Figure 7.10.
When the sag occurs, only the related H-bridge inverter of DVR starts to operate. As
also demonstrated in the current waveforms, the sag occurs only on phase_A and the
phase_A load current so its voltage do not affected by sag.


Figure 7.10. Three-phase voltage and current waveforms at starting of single-phase
25% voltage sag for Case 2

At the ending of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. DVR
comes into standby operation whenever the sag ends as demonstrated in Figure 7.11.
THD of the load voltages is always kept below the IEEE voltage harmonic limits
(IEEE Std 519, 1995).
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
150

Figure 7.11. Three-phase voltage and current waveforms at ending of single-phase
25% voltage sag for Case 2

7.3.3. Case Study3: 20% Double Phase Voltage Sag, Current Harmonic
Elimination

At stand-by operation, DVR is in OFF-mode and injects no voltage to the
system. The supply voltage and load voltage are in phase with each other. RMS
trends of supply and load voltages are demonstrated in Figure 7.12.


Figure 7.12. RMS trends of supply and load voltages

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
151
The waveform results for 20% double phase sag on phase_A and phase_B of
supply voltage for 3 s duration are demonstrated in Figure 7.13. Each division is 40
V for voltage waveforms and 2.5 A for current waveforms. The phase_A load current
so its load voltage is not affected by voltage sag as demonstrated in the Figure 7.13.
The load voltage waveform is identical with load current waveforms because the
load is purely resistive. Phase_A and Phase_B load currents are not affected when a
voltage sag occurs on Phase_A and Phase_B of supply voltage.


Figure 7.13. Waveforms of supply voltages and currents during Case 3

The voltage waveforms of CH1, CH2 and CH3 indicate the supply voltage,
injected voltage and load voltage of Phase_A in Figure 7.14, respectively. The
current waveforms of CH1, CH2 and CH3 indicate the supply current, injected
current and load current of Phase_A, respectively. DVR injects the missing voltage
to the system in series and APF injects the filter current to the system in shunt.
THD contents of supply and filtered currents for Phase_A are presented in
Table 7.4.


7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
152

Figure 7.14. Waveforms of Phase_A supply/injected/load voltages; supply/filter/load
currents during Case 3

Table 7.4. THD contents of supply and filtered currents of Phase_A for Case 3
THD content of Phase_A
load current

THD content of Phase_A
supply current
Order (%) Order (%) Order (%) Order (%)
1 100.00 18 0.11 1 100.00 18 0.20
2 0.38 19 0.66 2 0.44 19 0.93
3 1.86 20 0.04 3 1.23 20 0.14
4 0.32 21 0.16 4 0.36 21 0.39
5 22.39 22 0.04 5 3.20 22 0.07
6 0.17 23 1.05 6 0.12 23 0.39
7 7.27 24 0.10 7 1.15 24 0.19
8 0.15 25 0.44 8 0.42 25 0.61
9 1.19 26 0.13 9 0.46 26 0.28
10 0.18 27 0.17 10 0.21 27 0.38
11 5.80 28 0.12 11 1.09 28 0.37
12 0.13 29 0.60 12 0.15 29 0.39
13 1.82 30 0.11 13 0.85 30 0.38
14 0.09 31 0.19 14 0.35 31 0.46
15 0.53

15 0.21
16 0.10
THD(%)23.55
16 0.18
THD(%)4.38
17 2.00 17 0.83


7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
153
At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time.
When the voltage sag occurs, only the related H-bridge inverters of DVR start to
operate as demonstrated in Figure 7.15. As also demonstrated in the current
waveforms, the sag occurs on phase_A and phase_B. The phase A and phase_B load
currents so their voltages do not affected by sag.


Figure 7.15. Three-phase voltage and current waveforms at starting of double phase
20% voltage sag for Case 3

DVR comes into standby operation whenever the sag ends as demonstrated in
Figure 7.16. For Figures 7.16, THD values of supply voltage and load voltage are
measured as 2.26% and 2.92%, respectively. THD of the load voltages is always kept
below the IEEE voltage harmonic limits (IEEE Std 519, 1995).

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
154

Figure 7.16. Three-phase voltage and current waveforms at ending of double phase
20% voltage sag for Case 3

7.4. Experimental Results for Voltage Sag Compensation and Current
Harmonic Elimination with Proposed OPEN UPQC

The results of Hioki 3196 power quality analyzer and Fluke 1760 PQ recorder
are presented to show the performance of OPEN UPQC for sag mitigation and
current harmonic elimination. Three cases are comprehensively analyzed:
Case 1) No voltage sag and current harmonic elimination,
Case 2) 25% single-phase voltage sag and current harmonic elimination,
Case 3) 20% double phase voltage sag and current harmonic elimination,
The experimental diagram of OPEN UPQC with measurement points are
demonstrated in Figure 7.17.

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
155
Figure 7.17. Experimental diagram of OPEN UPQC with measurement points

7.4.1. Case Study4: No Voltage Sag, Current Harmonic Elimination

At stand-by operation (no-fault condition), DVR is in OFF-mode and injects
no voltage to the system. The supply voltage and load voltage are in phase with each
other. RMS trends of supply and load voltages are demonstrated in Figure 7.18.


Figure 7.18. RMS trends of supply and load voltages

APF is ON-mode and eliminates the load current harmonics as demonstrated
in Figure 7.19. At stand-by operation (no-fault condition), average load voltage THD
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
156
is 2.75% and supply current THD is 4.09%. These values are close to values used in
simulation studies. Phase_A, phase_B and phase_C are indicated as red (CH1), green
(CH2) and blue (CH3), respectively.


Figure 7.19. Waveforms of supply voltages and supply currents during Case 4

The load voltage is identical to supply voltage as demonstrated in the Figure
7.20. The voltage waveforms of CH1, CH2 and CH3 indicate the supply, injected and
load voltages of Phase_A, respectively. The current waveforms of CH1, CH2 and
CH3 indicate the supply, injected and load currents of Phase_A, respectively.

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
157

Figure 7.20. Waveforms of Phase_A supply/injected/load voltages;
supply/injected/load currents during Case 4

THD contents of supply and filtered currents for Phase_A are given in Table
7.5. The amplitudes of low order harmonics (5
th
, 7
th
, 11
th
and 13
th
) are high in load
current. APF injects the required compensation current to the system and the
amplitudes of low order harmonics are minimized in the supply current.

Table 7.5. THD contents of load and supply currents of Phase_A for Case 4
THD content of Phase_A
load current

THD content of Phase_A
supply current

Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.05

1 100 18 0.23
2 0.12 19 1.04

2 0.55 19 0.82
3 1.08 20 0.06

3 0.45 20 0.09
4 0.18 21 0.33

4 0.47 21 0.32
5 22.14 22 0.06

5 2.84 22 0.32
6 0.11 23 0.76

6 0.23 23 0.59
7 7.73 24 0.1

7 1.2 24 0.28
8 0.12 25 0.73

8 0.3 25 0.86
9 0.63 26 0.06

9 0.52 26 0.23
10 0.12 27 0.25

10 0.27 27 0.31
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
158
11 5.48 28 0.14

11 1.26 28 0.45
12 0.07 29 0.51

12 0.22 29 0.23
13 2.24 30 0.1

13 0.92 30 0.26
14 0.07 31 0.39

14 0.09 31 0.48
15 0.47

15 0.15

16 0.08
THD(%) 24.34

16 0.29
THD(%) 4.09
17 1.74

17 0.79


7.4.2. Case Study5: 25% Single-Phase Voltage Sag, Current Harmonic
Elimination

When a voltage sag on phase_A is detected, DVR starts to inject the missing
voltage to the system and keeps the load voltages between 0.9-1.1 pu of nominal
voltages. The supply voltage and load voltage are in phase with each other. RMS
trends of supply and load voltages are demonstrated in Figure 7.21.


Figure 7.21. RMS trends of supply and load voltages

The waveform results for 25% sag on phase_A of supply voltage for 3 s
duration are demonstrated in Figure 7.22. The phase_A load current so its load
voltage is not affected by voltage sag. The load voltage waveform is identical with
load current waveforms because the load is purely resistive. The phase_A load
current is not affected when a voltage sag occurs on Phase_A.
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
159

Figure 7.22. Waveforms of supply voltages and currents during Case 5

The voltage waveforms of CH1, CH2 and CH3 indicate the supply voltage,
injected voltage and load voltage of Phase_A in Figure 7.23, respectively. The
current waveforms of CH1, CH2 and CH3 indicate the supply current, injected
current and load current of Phase_A, respectively. DVR injects the missing voltage
to the system in series and APF injects the compensation current to the system in
shunt.

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
160

Figure 7.23. Waveforms of Phase_A supply/injected/load voltages; supply/filter/load
currents during Case 5

THD contents of supply and filtered currents for Phase_A are presented in
Table 7.6. The amplitudes of characteristic harmonics (5
th
, 7
th
, 11
th
and 13
th
) are high
in load current. APF injects the required compensation current to the system and the
amplitudes of characteristic harmonics are minimized in the supply current.

Table 7.6. THD contents of load and supply currents of Phase_A for Case 5
THD content of Phase_A
load current
THD content of Phase_A
supply current
Order (%) Order (%)

Order (%) Order (%)
1 100 18 0.05

1 100 18 0.17
2 0.18 19 0.67

2 0.4 19 0.91
3 2.37 20 0.06

3 1.05 20 0.3
4 0.12 21 0.4

4 0.27 21 0.34
5 22.98 22 0.07

5 3.25 22 0.32
6 0.11 23 0.94

6 0.21 23 0.47
7 6.8 24 0.06

7 1.11 24 0.27
8 0.21 25 0.45

8 0.25 25 0.73
9 1.85 26 0.05

9 0.49 26 0.19
10 0.08 27 0.31

10 0.24 27 0.34
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
161
11 5.96 28 0.05

11 1.02 28 0.18
12 0.11 29 0.64

12 0.36 29 0.34
13 1.58 30 0.13

13 1.04 30 0.38
14 0.09 31 0.17

14 0.2 31 0.7
15 0.87

15 0.26

16 0.05
THD(%) 24.98

16 0.17
THD(%) 4.28
17 1.96

17 0.78


At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. As
demonstrated in Figure 7.24, when the sag occurs, only the related H-bridge inverter
of DVR starts to operate.


Figure 7.24. Three-phase voltage and current waveforms at starting of single-phase
25% voltage sag for Case 5

At the ending of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time as
demonstrated in Figure 7.25. DVR comes into standby operation whenever the sag
ends. THD of the load voltages is always kept below the IEEE voltage harmonic
limits (IEEE Std 519, 1995).
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
162

Figure 7.25. Three-phase voltage and current waveforms at ending of single-phase
25% voltage sag for Case 5

7.4.3. Case Study6: 20% Double Phase Voltage Sag, Current Harmonic
Elimination

At stand-by operation, DVR is in OFF-mode and injects no voltage to the
system. The supply voltage and load voltage are in phase with each other. RMS
trends of supply and load voltages are demonstrated in Figure 7.26.

Figure 7.26. RMS trends of supply and load voltages
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
163
The waveform results for 20% double phase sag on phase_A and phase_B of
supply voltage for 3 s duration are demonstrated in Figure 7.27. The phase_A load
current so its load voltage does not affected by voltage sag as demonstrated in Figure
7.27. The load voltage waveform is identical with load current waveforms because
the load is purely resistive. Phase_A and Phase_B load currents are not affected when
a voltage sag occurs on Phase_A and Phase_B of supply voltage.


Figure 7.27. Waveforms of supply voltages and currents during Case 6

The voltage waveforms of CH1, CH2 and CH3 indicate the supply voltage,
injected voltage and load voltage of Phase_A in Figure 7.28, respectively. The
current waveforms of CH1, CH2 and CH3 indicate the supply current, injected
current and load current of Phase_A, respectively. DVR injects the missing voltage
to the system in series and APF injects the filter current to the system in shunt.
THD contents of the supply and filtered currents for Phase_A are given in
Table 7.7.


7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
164

Figure 7.28. Waveforms of Phase_A supply/injected/load voltages; supply/filter/load
currents during Case 6

Table 7.7. THD contents of supply and filtered currents of Phase_A for Case 6
THD content of Phase_A
load current
THD content of Phase_A
supply current
Order (%) Order (%)

Order (%) Order (%)
1 100 17 1.92

1 100 17 0.82
2 0.17 18 0.06

2 0.27 18 0.23
3 0.74 19 0.84

3 0.41 19 0.69
4 0.21 20 0.09

4 0.3 20 0.19
5 20.92 21 0.22

5 3.38 21 0.27
6 0.24 22 0.03

6 0.31 22 0.14
7 8.33 23 0.9

7 1.04 23 0.87
8 0.16 24 0.06

8 0.38 24 0.2
9 0.24 25 0.58

9 0.41 25 0.54
10 0.11 26 0.07

10 0.32 26 0.13
11 5.32 27 0.26

11 1.15 27 0.51
12 0.1 28 0.06

12 0.17 28 0.22
13 2.38 29 0.48

13 0.61 29 0.46
14 0.08 30 0.08

14 0.23 30 0.41
15 0.22 31 0.43

15 0.23 31 0.68
16 0.08 THD= 23.32%

16 0.23 THD= 4.2%
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
165
At the starting of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time. The
voltage and current waveforms at starting of double phase 20% voltage sag are
demonstrated in Figure 7.29. When the sag occurs, only the related H-bridge
inverters of DVR start to operate as demonstrated in Figure 7.29. As also
demonstrated in the current waveforms, the sag occurs on phase_A and phase_B. The
phase_A and phase_B load currents so their voltages are not affected by sag.


Figure 7.29. Three-phase voltage and current waveforms at starting of double phase
20% voltage sag for Case 6

At the ending of sag, the load voltage can be affected due to instantaneous
reduction of the voltage reference and delay originated from sag detection time as
demonstrated in Figure 7.30. DVR comes into standby operation whenever the sag
ends. THD values of supply voltage and load voltage are measured as 2.26% and
2.92%, respectively. THD of the load voltages is always kept below the IEEE voltage
harmonic limits (IEEE Std 519, 1995).

7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
166

Figure 7.30. Three-phase voltage and current waveforms at ending of double phase
20% voltage sag for Case 6

7.5. Summary

This chapter demonstrates the experimental results of UPQC and OPEN
UPQC performance. Experimental results illustrate the capabilities of UPQC and
OPEN UPQC for sag mitigation and current harmonic elimination. Several cases are
comprehensively analyzed experimentally for UPQC topologies: Case 1) No voltage
sag and current harmonic elimination, Case 2) 25% single-phase voltage sag and
current harmonic elimination, Case 3) 20% double phase voltage sag and current
harmonic elimination. The experimental results are compatible with IEEE power
quality standards.
APF eliminates the load current harmonics and keeps the supply current
almost sinusoidal with a THD of <5%. Dynamic response is a key consideration in
the controller design of DVR. DVR quickly senses the voltage sag and injects the
missing voltage to the system keeping the magnitude of the load voltage almost 0.9-1
per unit. The experimental results demonstrated in this chapter verify the simulation
results given in Section 6. The power quality improvement capabilities of UPQC and
OPEN UPQC are almost the same during steady state and voltage sag. But, the
7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
167
performance of OPEN UPQC is better than UPQC during the start and end of voltage
sag since OPEN UPQC is supplied from two separate DC energy storage. Besides,
the power circuit of OPEN UPQC is much more flexible than that of UPQC.
The next chapter presents the main points, significant results and future works
of the thesis.






































7. EXPERIMENTAL VERIFICATION OF UPQC TOPOLOGIES Ahmet TEKE
168



8. CONCLUSIONS AND FUTURE WORK Ahmet TEKE
169
8. CONCLUSIONS AND FUTURE WORK


Voltage sags and current harmonics are the most important power quality
problems in commercial and industrial utility's customers. These power quality
problems can cause tripping of sensitive electronic equipments, abnormal operations
of facilities and tremendous economic losses. Custom Power devices have now been
of interest for more than a decade that are able to improve the reliability and the
quality of power delivered to electric power customers. Unified Power Quality
Conditioner consisting of two voltage source inverters with a common DC link is a
Custom Power device and can simultaneously perform the tasks of Active Power
Filter and Dynamic Voltage Restorer. OPEN UPQC consisting of two voltage source
inverters with separate DC links is a relatively new CP device and can
simultaneously perform the tasks of APF and DVR. UPQC and OPEN UPQC
compensate for current harmonics and voltage sag/swell to protect sensitive process
loads as well as improve service reliability. However, UPQC does not provide
different levels of power for their customers since UPQC solves only end user power
quality concerns. OPEN UPQC overcomes these limitations by using two VSIs with
separate DC links. The power circuit of OPEN UPQC is much more flexible than
that of UPQC. Not much work has yet been reported on theoretical, design procedure
and experimental analysis of OPEN UPQC.
The main aim of this thesis is to develop new control algorithms for UPQC
and OPEN UPQC, reduce power consumed by inverters during standby and injection
modes. For this purpose, UPQC and OPEN UPQC are designed, simulated in
PSCAD/EMTDC program and evaluated experimentally with a 6 kVA, 230V
l-l

laboratory prototypes. Extensive literature surveys on APF, DVR and UPQC are
conducted and the lacks of control strategies are identified. The control algorithms
and minimum energy dissipation methods are analyzed and designed in detail using
PSCAD/EMTDC. Then, the available control algorithms of APF and DVR are
improved to meet the stringent power quality standards. The power circuit design
procedures of UPQC topologies are presented in detail. Finally, the designed system
is setup experimentally, suitable interface circuits have been developed and
8. CONCLUSIONS AND FUTURE WORK Ahmet TEKE
170
numerous tests are performed to validate the performance of the proposed UPQC and
OPEN UPQC. When there is no voltage sag in the system (load voltage is within 0.9-
1.1 of its nominal), DVR is in OFF-mode. During this mode, APF eliminates the load
current harmonics and keeps the supply current at the PCC almost sinusoidal.
Dynamic response is very critical for DVR since many industrial loads are very
sensitive to voltage sags. When a voltage sag occurs on the supply voltage, DVR
quickly starts to inject the missing voltage to the system and keeps the load voltage
magnitude nearly at 1 pu. APF continues the current harmonic elimination. The
simulation and experimental results verify the theoretical analysis and designed
system.
A control algorithm for the shunt units of UPQC and OPEN UPQC is
proposed and investigated. TMS320F28335 Digital Signal Processor based 3 kVA
laboratory prototype of voltage source APF is built using three leg three-phase IGBT
based inverter. The nonlinear load generates harmonics with lower order 5
th
, 7
th
, 11
th

and 13
th
harmonics being dominant. APF controller based on Instantaneous Reactive
Power Theory extracts the load current harmonics exactly and the required
compensation current is injected to the system in shunt by keeping the THD level of
supply current below 5%. It is known that voltage unbalance and voltage harmonics
on supply voltage result in very high harmonic distortion and affect the performance
of APF. To overcome these voltage harmonics and unbalance problems, a low pass
filter with a cut off frequency of 50 Hz is used in the voltage measurement of
harmonic filtering and a virtual alpha-beta components are generated in the DSP.
This control approach eliminates the negative effect of traditional IRPT under
distorted and unbalanced supply voltage conditions. The switching signals of APF
are then generated using hysteresis current control. A PI controller is used to
compensate the DC link capacitor voltage when APF is in compensation mode. An
experimental overvoltage protection circuit has been also designed and integrated
into the controller board of APF laboratory prototype. The extensive simulation and
experimental test results show that improved IRPT based APF eliminates the current
harmonics and keeps the supply current almost sinusoidal and below 5% THD.
8. CONCLUSIONS AND FUTURE WORK Ahmet TEKE
171
A new control algorithm for the series units of UPQC and OPEN UPQC is
proposed and investigated. TMS320F2812 Digital Signal Processor based 3-phase 3
kVA laboratory prototype of voltage source DVR is designed and implemented.
Three single-phase H-bridge IGBT based inverters are used for DVR implementation
to control each phase independently. DVR quickly senses the voltage sag on the
supply voltage and injects the missing voltage to system in series thus the load is
prevented from voltage sag. New voltage sag detection and voltage compensation
methods based on enhanced phase locked loop are developed. E-PLL algorithms are
based on the nonlinear adaptive filter. The adaptive filter has the ability of peak
detection, harmonics extraction and signal decomposition. E-PLL structure is very
robust with respect to pollution in the input signal such as noise, harmonic distortion
and disturbances. The power losses are also minimized by controlling the each H-
bridge inverter independently. DVR is designed to compensate voltage sags with
magnitude lower than 30% of nominal voltage. Sinusoidal pulse width modulation
technique is used to generate the switching signals. The performed case studies are
steady state performance test, 25% single-phase voltage sag and20% double phase
voltage sag. The rms voltage trends of supply and load voltages are given. The
results show that the designed DVR quickly responses to the voltage sags and
restores the load voltage to the presag value. The extensive test result shows that the
E-PLL based DVR mitigates the voltage sags and keeps the RMS of load voltage
nearly 0.9-1 per unit. The load voltage THD is less than 5% during fault that has
conformed to the power quality standards recommended by IEEE standard 519-1995.
The constant DC link voltage for APF is also achieved regardless of voltage sags in
supply voltage with the help of proposed DVR. The harmonic elimination
performance of APF is not affected by voltage sag since DVR keeps the magnitude
of load voltage almost constant.
This thesis introduces new control algorithms which not only improves
UPQC and OPEN UPQC systems performance. The experimental design procedure
and practical recommendations for experimental setup are also presented in detail.
These can help the researchers on their custom power based projects. The proposed
UPQC and OPEN UPQC are tested under unbalanced and harmonic polluted supply
8. CONCLUSIONS AND FUTURE WORK Ahmet TEKE
172
voltage. The limitations of UPQC over OPEN UPQC operation in terms of start and
end times of voltage sag are also explained. The simultaneous mitigation of current
harmonics and voltage sags with reduced active power consumption is important
contribution that shows the usefulness of this Ph.D. thesis. The use of a combination
of APF and DVR suggest a cost effective solution to voltage sags and current
harmonics.
In the future, field researches will concentrate on reliability of electric power,
energy conservation, efficient energy use and maximum use of renewable energy
sources. Further research can be carried out in the following areas:
Realization of minimum power dissipation methods for DVR and APF.
Performance comparison of available power quality detection and
reference signal generation methods experimentally.
Implementation of custom power devices using FPGA controller and
performance comparison of the control algorithms using FPGA versus DSP.
Design of a single control algorithm based on E-PLL for APF and DVR
controllers and analysis of the system during dynamic load changes and transients.
Implementation of UPQC (combination of DVR and APF) with different
circuit topologies (e.g. left shunt connected, multilevel voltage source converter
based, three-phase four-wire OPEN UPQC).
Large scale application of UPQC/OPEN UPQC and combination with one
or several distributed generation systems.
The stored energy of DVR can be delivered from different kinds of
renewable energy storage systems such as wind or solar energy.
Harmonic current and reactive power elimination capability of
UPQC/OPEN UPQC using LCL passive filter in its shunt and series units.
UPQC and OPEN UPQC concepts implemented in this thesis can be
extended for the control algorithms of Flexible AC Transmission Systems (FACTS)
and Flexible, Reliable and Intelligent ENergy Delivery System (FRIENDS).





173
REFERENCES

AFONSO J., COUTO C., MARTINS J., 2000. Active filters with control based on
the p-q theory, IEEE Industrial Electronics Society Newsletter, vol. 47, no 3,
pp. 5-10.
AKAGI H., 2000. Active filters and energy storage systems operated under non-
periodic conditions, Power Engineering Society Summer Meeting, IEEE, vol.
2, pp. 965-970.
AKAGI H., KANAZAWA Y., NABAE A., 1984. Instantaneous reactive power
compensators comprising switching devices without energy storage
components, IEEE Transactions on Industry Applications, vol. IA-20, pp.
625-630.
AKAGI H., NABAE A., ATOH S., 1986. Control strategy of active power filters
using multiple voltage-source PWM converters, IEEE Transactions on
Industry Applications, vol. 1A-22, pp. 460-465.
AKAGI H., WATANABE E. H., AREDES M., 2007. Instantaneous power theory and
application to power conditioning, John Wiley&Sons, Hoboken, New Jersey.
AKAGI H., 1996. New trends in active filters for improving power quality,
Power Electronics, Drives and Energy Systems for Industrial Growth,
Proceedings of the 1996 International Conference on, vol.1, pp. 417-425.
ALMEIDA A.D., MOREIRA L., DELGADO J., 2003. Power quality problems and
new solutions, International Conference on Renewable, Energy and Power
Quality, pp. 1-9.
AMARIS H., ALVAREZ C., ALONSO M., FLOREZ D., LOBOS T., JANIK P.,
REZMER J., WACLAWEK Z., 2008. Application of advanced signal
processing methods for accurate detection of voltage dips, Harmonics and
Quality of Power, International Conference, pp. 1-6.
ARA A.L., NIAKI S.A.N., 2003. Comparison of the facts equipment operation in
transmission and distribution systems, International Conference on Electricity
Distribution Barcelona, pp. 1-5.

174
AREDES M., HEUMANN K., WATANABE E.H., 1998. An universal active power
line conditioner, IEEE Transactions on Power Delivery, vol. 13, pp. 545-551.
ARORA A., CHAN K., JAUCH T., KARA A., WIRTH E., 1998. Innovative system
solutions for power quality enhancement, ABB Rev., pp. 4-12.
AWAD H., BLAABJERG F., 2004. Transient performance improvement of static
series compensator by double vector control, IEEE Applied Power
Electronics Conf. and Exposition, vol. 1, pp. 607-613.
AWAD H., NELSEN H., BLAABJERG F., NEWMAN M.J., 2005. Operation of
static series compensator under distorted utility conditions, Power Systems,
IEEE Transactions, vol. 20, pp. 448-457.
AXENTE I., 2008. Unified power quality conditioner: Protection and performance
enhancement, School of Electrical Engineering Systems, Ph.D. Thesis,
Dublin Institute of Technology, Republic of Ireland.
AXENTE I., BASU M., CONLON M.F., GAUGHAN K., 2010b. Protection of
unified power quality conditioner against the load side short circuits, IET
Power Electronics, vol. 3, pp. 542-551.
AXENTE I., BASU M., CONLON M.F., 2007. A control approach for UPQC
connected to weak supply point, Universities Power Engineering Conference,
42nd International, pp. 619-623.
AXENTE I., BASU M., GANESH J.N., CONLON M.F., GAUGHAN K., 2010a. A
12 kVA DSP controlled laboratory prototype UPQC capable of mitigating
unbalance in source voltage and load current, IEEE Transactions on, Power
Electronics, vol. 25, pp. 1471-1479.
AZEVEDO H.J., FERREIRA J.M., MARTINS A.P., CARVALHO A.S., 2008. An
active power filter with direct current control for power quality conditioning,
Electric Power Components and Systems, vol. 36, pp. 587-601.
BAE B.Y., LEE D.K., LEE D.Y., HAN B.M., 2007. Development of high-
performance single-phase line-interactive dynamic voltage restorer,
Universities Power Engineering Conf., pp. 1-6.
BAE, C.H., HAN, M.S., KIM, Y.K., KWON, S.Y., PARK, H.J., 2006. Determining
the capacity and installation positions of regenerative inverters at DC 1500V

175
electric railway substations, The Transactions of the Korean Institute of
Electrical Engineers. B, Society of electrical machinery & energy conversion
systems, vol. 55, pp. 478-484.
BANAEI M.R., HOSSEINI S.H., KHAJEE, M.D., 2006. Mitigation of voltage sag
using adaptive neural network with dynamic voltage restorer, IEEE Power
Electronics and Motion Control Conference, vol. 2, pp. 1-5.
BANGOR, 2009. Common power quality terms, Bangor Hydropower Electric
Company, http://www.bhe.com/residential/quality_terms.cfm.
BASU M., DAS S.P., DUBEY G.K., 2008, Investigation on the performance of
UPQC-Q for voltage sag, IET Gener. Transm. Distrib., vol. 2, pp. 414-423.
BAYINDIR K.., TEKE A., TUMAY M., 2007. A robust control of dynamic voltage
restorer using fuzzy logic, Electrical Machines and Power Electronics,
International Aegean Conf., pp. 55-60.
BENACHAIBA C., DIB S., ABDELKHALEK O., FERDI B., 2008. Voltage quality
improvement using DVR, Electrical Power Quality and Utilization Journal,
vol. 14, pp. 39-46.
BHATTACHARYA A., CHAKRABORTY C., 2008. ANN (Adaline) based
harmonic compensation for shunt active power filter with capacitor voltage
based predictive technique, Industrial and Information Systems, IEEE
3. International Conf., pp. 1-6.
BHATTACHARYYA S., MYRZIK J.M.A., COBBEN J.F.G., KLING W.L.,
DIDDEN M., 2007. Need of voltage quality regulation in the future
electricity infrastructure, Electrical Power Quality and Utilization 9
th

International Conference, pp. 1-6.
BLOOMING T.M., CARNOVALE D.J., 2007. Harmonic convergence, IEEE
Industry Applications Magazine, pp. 21-27.
BOLLEN M.H.J., 2001. Understanding power quality problems, IEEE Press Series
on Power Engineering, New York, 672 pages.
BONGIORNO M., SANNINO A., DUSONCHET L., 2003. Cost-effective power
quality improvement for industrial plants, IEEE Power Tech Conference
Proceedings, vol. 4, pp. 1-6.

176
BRAHIM B., CHELLALI B., RACHID D., BRAHIM F., 2010. Optimization of
shunt active power filter system fuzzy logic controller based on ant colony
algorithm, Journal of Theoretical and Applied Information Technology, vol.
14, pp. 117-125.
BRENNA M., TIRONI R.F., 2009. A new proposal for power quality and custom
power improvement OPEN UPQC, IEEE Transactions on Power Delivery,
vol. 24, pp. 2107-2116.
BROOKS T., 2004. Active power filters provide a cost effective, flexible solution for
system harmonic control, NASA Tech Briefs, http://www.findarticles.com.
BUXTON R., 1998. Protection from voltage dips with the dynamic voltage restorer,
Dynamic Voltage Restorers - Replacing Those Missing Cycles, IEE Half Day
Colloquium, pp. 1-6.
CAVALCANTI M.C., AZEVEDO G.M.S., AMARAL B.A., NEVES F.A.S., 2006.
Unified power quality conditioner in a grid-connected photovoltaic system,
EPQU Journal, vol. 12, pp. 59-69.
CHAE B.S., LEE W.C., LEE T.K., HYUN D.S., 2001. A fault protection scheme for
unified power quality conditioners, Power Electronics and Drive Systems,
Proceedings, 4th IEEE International Conference on vol. 1, pp. 66-71.
CHAKRABORTY S., SIMOES M.G., 2009. Experimental evaluation of active
filtering in a single-phase high-frequency AC microgrid IEEE Transactions
on energy conversion, vol. 24, pp. 673-682.
CHAN P.K.W., LEUNG K.K.S., CHUNG H.S.H., HUI S.Y.R., 2006. Boundary
controller for dynamic voltage restorers to achieve fast dynamic response,
Applied Power Electronics Conference and Exposition, pp. 1-6.
CHAOUI A., GAUBERT J.P., KRIM F., RAMBAULT L., 2008. On the design of
shunt active filter for improving power quality, Industrial Electronics, IEEE
International Symposium on, pp. 31-37.
CHAPMAN D., 2001a. Introduction to power quality, European Copper Institute and
Copper Development Association, Brussels, pp. 1-8.
CHAPMAN D., 2001b. Power quality application guide, The cost of poor power
quality, Copper Development Association, pp. 1-8.

177
CHEN G., CHEN Y., SANCHEZ L.F., SMEDLEY K.M., 2004. Unified power
quality conditioner for distribution system without reference calculations, 4th
Int. Power Electronics and Motion Control Conf., vol. 3, pp. 1201-1206.
CHEN S., 2005, DSP based control of static power quality compensators in industrial
power systems, Ph.D. Electrical and Computer Engineering, Concordia
University, Canada.
CHEN Y., ZHA X., WANG J., LIU H., SUN J., TANG H., 2000. Unified power
quality conditioner (UPQC): The theory, modeling and application, Power
System Technology, International Conference, vol. 3, pp. 1329-1333.
CHENG P.T., CHEN J.M., NI C.L., 2009. Design of a state-feedback controller for
series voltage-sag compensators, Industry Applications, IEEE Transactions,
vol. 45, pp. 260-267.
CHOI S.S., LI B.H., VILATHGAMUWA D.M., 2000a. A comparative study of
inverter- and line-side filtering schemes in the dynamic voltage restorer, IEEE
Power Engineering Society Winter Meeting, vol. 4, pp. 2967-2972.
CHOI S.S., LI B.H., VILATHGAMUWA D.M., 2000b. Dynamic voltage restoration
with minimum energy injection, Power Systems, IEEE Transactions, vol. 15,
pp. 51-57.
CHOI S.S., LI B.H., VILATHGAMUWA D.M., 2002. Design and analysis of the
inverter-side filter used in the dynamic voltage restorer. IEEE Transactions on
Power Delivery, vol. 17, pp. 857-864.
CHUNG I.Y., WON D.J., PARK S.Y., MOON S.I., PARK J.K, 2003. The DC link
energy control method in dynamic voltage restorer system, Electrical Power
and Energy Systems, vol. 25, pp. 525-531.
CHUNG Y.H., KIM H.J., KWON G.H., PARK T.B., KIM S.H, KIM K.S., CHOE
J.W., 2007, Dynamic voltage restorer with neural network controlled voltage
disturbance detector and real-time digital voltage control, IEEE Power
Engineering Society General Meeting, pp. 1-7.
CUMA M.U., 2010. Digital signal processor based implementation of custom power
device controllers, Ph.D. Thesis, ukurova University, Institute of Natural
and Applied Sciences.

178
DAEHLER P., AFFOLTER R., 2000. Requirements and solutions for dynamic
voltage restorer, a case study, IEEE Power Engineering Society Winter
Meeting, vol. 4, pp. 2881-2885.
DAHONO P.A., PURWADI A., QAMARUZZAMAN, 1995. An LC filter design
method for single-phase PWM inverters, Power Electronics and Drive
Systems Proceedings of Conference, vol. 2, pp. 571-576.
DAI N.Y., WONG M.C., FAN N., HAN Y.D., 2008. A FPGA-based generalized
pulse width modulator for three-leg center-split and four-leg voltage source
inverters, Power Electronics, IEEE Transactions on vol. 23, pp. 1472-1484.
DASH P.K., CHILUKURI M.V., 2004. Hybrid S-transform and kalman filtering
approach for detection and measurement of short duration disturbances in
power networks, IEEE Trans. Instrum. Meas., pp. 588-596.
DAVARI M., ALEEMRAN S.M., NAFISI H., SALABEIGI I., GHAREHPETIAN
G.B., 2009. Modeling the combination of UPQC and photovoltaic arrays with
multi-input single-output DC-DC converter, Industrial Technology, IEEE
International Conference, pp. 1-6.
DIXON J.G., VENEGAS G., MORAN L.A., 1997. A series active power filter based
on a sinusoidal current controlled voltage source inverter, IEEE Transaction
on Industrial Electronics, vol. 44, pp. 612-620.
DJEGHLOUD H. , BENALLA H., BENTOUNSI A., 2008. Supply current and load
voltage distortions suppression using the unified power quality conditioner,
Systems, Signals and Devices, IEEE, 5th International Multi-Conf., pp. 1-6.
DUANE J.L., ZWAM A.V., WIJNANDS C., VANDENPUT A., 1999. Reference
frames fit for controlling PWM rectifiers, IEEE Trans. on Ind. Electronics,
vol. 46, pp. 628-630.
DUGAN R.C., MCGRANAGHAN M.F., BEATY H.W., 2003. Electrical power
systems quality, McGraw-Hill, New York, 260 pages.
EBERHARD A., MCEACHERN A., 2007. New developments in power quality
immunity and voltage sag standards, Hands on Applications in North
America, Asia and Europe, Proceedings of the 9th International Conference
on Electric Power Quality and Utilisation, pp. 1-5.

179
ELNADY A., GOAUDA A., SALAMA M.M.A., 2001. Unified power quality
conditioner with a novel control algorithm based on wavelet transform,
Electrical and Computer Engineering, Canadian Conf., vol. 2, pp.1041-1045.
EMADI A., 2004, Energy Efficient Electric Motors, CRC Press, 424 pages.
EMANUEL A.E. MCNEILL J.A., 1997. Electric power quality, Annual review of
energy and the environment, vol. 22, pp. 263-303.
ENA, 2006. Managing harmonics, a guide to ENA engineering recommendation
G5/4-1, Fifth Edition, GAMBICA.
ENERSINE, 2010. Enersine Active Harmonic Filter Users Manual, APF ESD34.
ESFANDIARI A., PARNIANI M., MOKHTARI H., 2004. Mitigation of electric arc
furnace disturbances using the unified power quality conditioner, Industrial
Electronics Society, 30th Annual Conference of IEEE, vol. 2, pp. 1469-1474.
EZOJI H., FAZLALI M., GHATRESAMANI A., NOPOUR M., 2009a. A novel
adaptive hysteresis band voltage controller for dynamic voltage restorer,
European Journal of Scientific Research, vol.37, pp. 240-253.
EZOJI H., SHEIKHOLESLAMI A., TABASI M., SAEEDNIA M.M., 2009b.
Modeling and simulation of dynamic voltage restorer (DVR) based on
hysteresis control, European Jour. of Scientific Research, vol. 27, pp.152-166.
FATHI S.H., PISHVAEI M., GHAREHPETIAN G.B., 2006. A frequency domain
method for instantaneous determination of reference current in shunt active
filter, TENCON, IEEE Region 10 Conference, pp. 1-4.
FERNANDES D.A., NAIDU S.R., COURA C.A.E., 2009. Instantaneous sequence-
component resolution of 3-phase variables and its application to dynamic
voltage restoration, Instrumentation and Measurement, IEEE Transactions,
vol. 58, pp. 2580-2587.
FIRLIT A., 2005. The active power filter operation under the distorted supply
voltage, Inst. of Electr. Drive & Industrial Equipment Control, Power
Electronics and Applications, pp. 10.
FITZER C.Z., RAMACHANDARAMURTHY C., ARULAMPALAM V.K.,
BARNES A., JENKINS M.N., 2001. Software phase-locked loop applied to

180
dynamic voltage restorer (DVR), IEEE Power Engineering Society Winter
Meeting, vol. 3, pp. 1033-1038.
FITZER C., BARNES M., GREEN P., 2004. Voltage sag detection technique for a
dynamic voltage restorer, IEEE Transaction on Industry Applications, vol. 40,
pp. 203-212.
FLORES P., DIXON J., ORTUZAR M., CARMI R., BARRIUSO P., MORAN L.,
2009. Static VAr compensator and active power filter with power injection
capability using 27-level inverters and photovoltaic cells, Industrial
Electronics, IEEE Transactions on, vol. 56, pp. 130-138.
FORGHANI M., AFSHARNIA S., 2007, Online wavelet transform based control
strategy for UPQC control system, Power Delivery, IEEE Transactions on,
vol. 22, pp. 481-491.
FUJITA H., 2009. A single-phase active filter using an H-bridge PWM converter
with a sampling frequency quadruple of the switching frequency, Power
Electronics, IEEE Transactions on, vol. 24, pp. 934-941.
FUJITA H., AKAGI H., 1998. The unified power quality conditioner: the integration
of series and shunt-active filters, Power Electronics, IEEE Transactions on,
vol. 13, pp. 315-322.
GEORGE M., 2007. Artificial intelligence based three-phase unified power quality
conditioner, Journal of Computer Science, vol. 3, no 7, pp. 465-477.
GHOSH A., JINDAL A.K., JOSHI A., 2004a. Design of a capacitor-supported
dynamic voltage restorer (DVR) for unbalanced and distorted loads, Power
Delivery, IEEE Transactions, vol. 19, pp. 405-413.
GHOSH A., JINDAL A.K., JOSHI A., 2004b. Unified power quality conditioner for
voltage regulation of critical load bus, Power Engineering Society General
Meeting, IEEE, vol.1, pp. 471-476
GHOSH A., LEDWICH G., 2002. Power quality enhancement using custom power
devices, Springer, Power Electronics and Power Systems Series, 432 pages.
GRAOVAC D., KATIC V., RUFER A., KNEZEVIC J., 2001. Unified power quality
conditioner based on current source converter topology, European Conf. on
Power Electr. and Applications, pp. 1-9.

181
HABROUK E., DARWISH M. , MEHTA M.K., 2000. Active power filters: A
review, Electric Power Applications, IEE Proceedings, vol. 147, pp.403-413.
HAN B.M., BAE B., 2007, Unified power quality conditioner with super capacitor
for energy storage, European Trans. on Electrical Power, vol. 18, pp. 327-343.
HAN B., BAE B., BAEK S., JANG G., 2006. New configuration of UPQC for
medium-voltage application, IEEE Trans. on Power Delivery, vol. 21, pp.
1438-1444.
HANGZHOU C., 2008. Research on the SPLL based single-phase voltage sag
detection technique, Proceedings of the 7
th
International Conference on
Instrumentation, Measurement, Circuits and Systems, pp. 62-65.
HAQUE M. H., 2001. Compensation of distribution system voltage sag by DVR and
D-STATCOM, Power Tech Proceedings, vol. 1, 5 pages.
HAQUE M.T., ISE T., HOSSEINI S.H., 2002. A novel control strategy for unified
power quality conditioner (UPQC), Power Electronics Specialists
Conference, IEEE 33rd Annual Publication, vol. 1, pp. 94-98.
HENNING P.H., FUCHS H.D., ROUX A.D.L., MOUTON H.A T., 2008. 1.5-MW
seven-cell series-stacked converter as an active power filter and regeneration
converter for a DC traction substation, Power Electronics, IEEE Transactions
on, vol. 23, pp. 2230-2236.
HERRERA R.S., SALMERN P., KIM H., 2008. Instantaneous reactive power
theory applied to active power filter compensation: Different approaches,
assessment and experimental results, IEEE Transactions on Industrial
Electronics, vol. 55, pp. 184-196.
HO C.N., CHUNG H.S.H., AU K.T.K., 2008. Design and implementation of a fast
dynamic control scheme for capacitor supported dynamic voltage restorers,
Power Electronics, IEEE Transactions, vol. 23, pp. 237-251.
HOEVENAARS T., 1999. A new solution for harmonics generated by variable speed
drives, Power quality assurance, Voice of industry, Toronto.
HOSSEINI M., SHAYANFAR H.A., FIRUZABAD M.F., 2009. Modeling of unified
power quality conditioner (UPQC) in distribution systems load flow, Elsevier
Energy Conversion and Management, vol. 50, pp. 1578-1585.

182
IEEE Std 1159, 1995. IEEE recommended practice for monitoring electric power
quality, IEEE Std. 519-1995, IEEE Recommended Practices and
Requirements for Harmonic Control in Electrical Power Systems.
INGRAM. D.M.E., 1998. An evaluation of harmonic isolation techniques for three
phase active filtering, MSc Thesis, University of Canterbury Christchurch,
New Zealand.
JACOBINA C.B., SANTOS W.R.N., OLIVEIRA A.C., SILVA E.R.C., SANTOS
E.C.D., 2007. Single-phase universal active filter without transformer,
Applied Power Electronics Conference, IEEE, pp. 698-703.
JAIME P., SALMERON P., VAZQUEZ J.R., ALCANTARA F., 2002. Series-
parallel configuration of active power filters for VAr and harmonic
compensation, Industrial Electronics Society, IEEE 28th Annual Conference,
vol. 4, pp. 2945-2950.
JAIN K., AGARWAL P.H.O., 2003. Design simulation and experimental
investigations, on a shunt active power filter for harmonics and reactive
power compensation, Electric Power Components and Systems, vol. 33,
pp. 671-692.
JAYANTI N G., 2008. Unified power quality conditioner for grid integration of wind
generators, Ph.D. thesis, Dublin Institute of Technology, Dublin Institute of
Technology, Engineering Doctoral.
JAYANTI N.G., BASU M., CONLON M.F., GAUGHAN K., 2009. Rating
requirements of the unified power quality conditioner to integrate the fixed
speed induction generator-type wind generation to the grid, IET Renewable
Power Generation, vol. 3, pp. 133-143.
JIANFENG Z., PING J., GUOQING T., 2002. Research on VSI-based uninterrupted
dynamic voltage restorer, Transactions of China Electro Technical Society,
vol. 17, pp. 88-92.
JIANG M.C., 2001. Analysis and design of a novel three-phase active power filter,
IEEE Trans. on Aerospace and Electronic Systems, vol. 37, pp. 824-831.

183
JIMICHI T., FUJITA H., AKAGI H., 2008. Design and experimentation of a
dynamic voltage restorer capable of significantly reducing an energy-storage
element, Industry Applications, IEEE Transactions, vol. 44, pp. 817-825.
JIMICHI T., FUJITA H., AKAGI H., 2008. Experimental verification of a dynamic
voltage restorer capable of significantly reducing energy-storage element
requirements, Electrical Engineering in Japan, vol. 165, pp. 73-82.
JINDAL A.K., GHOSH A., JOSHI A., 2005. The protection of sensitive loads from
interharmonic currents using shunt series active filters, Electric Power
Systems Research, pp. 187-196.
JINDAL A.K., GHOSH A., JOSHI A., 2007. Interline unified power quality
conditioner, Power Delivery, IEEE Transactions on, vol. 22, pp. 364-372.
JOOS G., CHEN S., LOPES L., 2004, Closed-loop state variable control of dynamic
voltage restorers with fast compensation characteristics, in record, IEEE IAS,
pp. 2252-2258.
JOU H.L., WU K.D., WU J.C., CHIANG W., 2008. A three phase four wire power
filter comprising a three-phase three-wire active power filter and a zig-zag
transformer, IEEE Transactions on Power Electronics, vol. 23, pp. 252-259.
JOWDER F.A.L., 2009. Design and analysis of dynamic voltage restorer for deep
voltage sag and harmonic compensation, Generation, Transmission &
Distribution, vol. 3, pp. 547-560.
JUHA T., 2009. Series active power filter in power conditioning, Ph.D. Thesis,
Tampere University of Technology, Laboratory of Power Electronics, pp.179.
JUNG H.J., SUH I.Y., KIM B.S., KIM R.Y., CHOI S.Y., SONG J.H., 2002. A study
on DVR control for unbalanced voltage compensation, IEEE Applied Power
Electronics Conference and Exposition, vol. 2, pp. 1068-1073.
JURADO F., 2004, Neural network control for dynamic voltage restorer, IEEE Trans
on Industrial Electronics, vol. 51, pp. 727-729.
JURADO F., VALVERDE M., CARPIO J., 2003. Voltage sag correction by dynamic
voltage restorer on fuzzy logic control, IEEE Canadian Conf. on Electrical
and Computer Engineering, vol. 1, pp. 421-424.

184
KALE M., ZDEMIR E., 2005. Harmonic and reactive power compensation with
shunt active power filter under non-ideal mains voltage, Electric Power
Systems Research, vol. 74, pp. 363-370.
KAMWA I., GRONDIN R., 1992. Fast adaptive schemes for tracking voltage, phasor
and local frequency in power transmission and distribution technique, IEEE
Trans. Power Del., vol. 7, pp. 789-795.
KARIMI H., GHARTEMANI M.K., IRAVANI M.R., BAKHSHAI A.R., 2003. An
adaptive filter for synchronous extraction of harmonics and distortions, Power
Delivery, IEEE Transactions on, vol. 18, pp. 1350-1356.
KARIMI G.M., IRAVANI M.R., 2002. A nonlinear adaptive filter for online signal
analysis in power systems applications, IEEE Transactions on Power
Delivery, vol. 17, pp. 617-622.
KASUNI P., DANIEL S., ARULAMPALAM A., SANATH A., 2006. Automated
control technique for a single-phase dynamic voltage restorer, Information
and Automation, International Conf., pp. 63-68.
KEDJAR B., AL-HADDAD K., 2009, DSP based Implementation of an LQR with
integral action for a three-phase three-wire shunt active power filter, IEEE
Transactions on Industrial Electronics, vol. 56, pp. 2821-2828.
KHADKIKAR V., CHANDRA A. , SINGH B. N., 2009a. Generalised single-phase
p-q theory for active power filtering: simulation and DSP-based experimental
investigation, IET Power Electronics, vol. 2, pp. 67-78.
KHADKIKAR V., AGARWAL P., CHANDRA A., BARRY A.O., NGUYEN T.
D., 2004. A simple new control technique for unified power quality
conditioner (UPQC), 11th International Conference on Harmonics and
Quality of Power, pp. 289-293.
KHADKIKAR V., CHANDRA A., 2008. A new control philosophy for a unified
power quality conditioner (UPQC) to coordinate load-reactive power demand
between shunt and series inverters, IEEE Transactions on Power Delivery,
vol. 23, pp. 2522-2534.

185
KHADKIKAR V., CHANDRA A., 2009b. A novel structure for three-phase four-
wire distribution system utilizing unified power quality conditioner (UPQC),
IEEE Transactions on Industry Applications, vol. 45, pp. 1897-1902.
KHADKIKAR V., CHANDRA A., BARRY A.O., NGUYEN T.D., 2006.
Application of UPQC to protect a sensitive load on a polluted distribution
network, Power Engineering Society General Meeting, IEEE, pp. 1-6.
KHOOR M.S., MACHMOUM M., 2005. Simplified analogical control of a unified
power quality conditioner, Power Electronics Specialists Conference, IEEE
36th, pp. 2565-2570.
KIM H., LEE S.J., SUL S.K., 2004. Reference wave generation in dynamic voltage
restorers by use of PQR power theory, IEEE Applied Power Electr. Conf. and
Exposition, vol. 3, pp. 1452-1457.
KINHAL V.G., AGARWAL P., GUPTA H.O., 2011. Performance investigation of
neural-network based unified power quality conditioner, IEEE Transactions
on Power Delivery, vol. 26, pp. 431-437.
KIRAWANICH P., O'CONNELL, R.M., 2003. Experimental verification of an active
power line conditioner with a fuzzy logic switch controller, IEEE Power
Electronics Specialist Conference, vol. 1, pp. 315-320.
KISCK D.O., NAVRAPESCU V., 2007. Single-phase unified power quality
conditioner with optimum voltage angle injection for minimum VA
requirement, Power Electronics Specialists Conference, IEEE, pp. 574-579.
KOLHATKAR Y.Y., DAS S.P., 2007. Experimental investigation of a single-phase
UPQC with minimum VA loading, Power Delivery, IEEE Trans. on,
vol. 22, pp. 373-380.
KUMAR P., MAHAJAN A., 2009. Soft computing techniques for the control of an
active power filter, IEEE Trans. on Power Delivery, vol. 24, pp. 452-461.
KUMAR R.S., GANESAN P., 2006. 250kVA Unified power quality controller,
TENCON IEEE Region 10 Conference, pp. 1-4.
KUMAR S.V.R., NAGARAJU S.S., 2007. Power quality improvement using
DSTATCOM and DVR, International Journal of Electrical and Power
Engineering, vol. 1, pp. 368-376.

186
KWAN K.H., SO P.L., CHU Y.C., 2005. Unified power quality conditioner for
improving power quality using MVR with kalman filters, Power Engineering
Conference, 7th International, vol. 2, pp. 980-985.
LARA O.A., ACHA E., 2002. Modeling and analysis of custom power systems by
PSCAD/EMTDC. IEEE Transactions on Power Delivery, 17(1): 266-272.
LAXMI A.J., DAS G.T.R., RAO K.U., RAYUDU K.D., 2006. Comparison of PI
and ANN control strategies of unified shunt series compensator, IEEE Power
India Conference, pp. 1-7.
LEE D.M., HABETLER T.G., HARLEY R.G., KEISTER T.L., ROSTRON J.R.,
2007. A voltage sag supporter utilizing a PWM switched autotransformer,
IEEE Transactions on Power Electronics, vol. 22, pp. 626-635.
LEE S. J., KIM H., SUL S. K., BLAABJERG F., 2004. A novel control algorithm for
static series compensators by use of PQR instantaneous power theory, Power
Electronics, IEEE Transactions, vol. 19, pp. 814-827.
LEE W.C., LEE D.M., LEE T.K., 2010. New control scheme for a unified power-
quality compensator-q with minimum active power injection, IEEE
Transactions on Power Delivery, vol. 25, pp. 1068-1076.
LEON A.E., SOLSONA J.A., BUSADA C., CHIACCHIARINI H., VALLA M.I.,
2009. High-performance control of a three-phase voltage-source converter
including feed forward compensation of the estimated load Current, Energy
Conversion and Management, vol. 50, pp. 2000-2008.
LI B.H., CHOI S.S., VILATHGAMUWA D.M., 2002. Transformerless dynamic
voltage restorer, IEE Generation, Transmission and Distribution, Proceedings,
vol. 149, pp. 263-273.
LI D., CHEN Q., JIA Z., ZHANG C., 2006. A high-power active filtering system
with fundamental magnetic flux compensation, IEEE Transactions on Power
Delivery, vol. 21, pp. 823-830.
LI G.J., ZHANG X.P., CHOI S.S., LIE T.T., SUN Y.Z., 2007a. Control strategy for
dynamic voltage restorers to achieve minimum power injection without
introducing sudden phase shift, IET Generation, Transmission & Distribution,
vol. 1, pp. 847-853.

187
LI P.Z., KANG X., CHEN Y., 2004. Control scheme for a universal power quality
manager in a two-phase synchronous rotating frame, Generation,
Transmission and Distribution, IEE Proceedings, vol. 151, pp. 590-596.
LI Y.W., VILATHGAMUWA M., LOH D.P.C., BLAABJERG F., 2007b. A dual-
functional medium voltage level DVR to limit downstream fault currents,
Power Electronics, IEEE Transactions, vol. 22, pp. 1330-1340.
LIU S., SINGER C.H., DOUGAL R.A., 2006. Power anomaly effects and costs in
low-voltage mobile power systems aerospace and electronic systems, IEEE
Transactions on Aerospace and Electronic Systems, vol. 42, pp. 612-624.
LOH P.C., VILATHGAMUWA D.M., TANG S.K., LONG H.L., 2004. Multilevel
dynamic voltage restorer, IEEE Power Electr. Letters, vol. 2, pp. 125-130.
LUIS A.M., DIXON J.W., ROGEL R., WALLACE A., 1995. A three-phase active
power filter operating with fixed switching frequency for reactive power and
current harmonic compensation, IEEE Transactions on Industrial Electronics,
vol. 42, no. 4, pp. 402-408.
LUO A., SHUAI Z., ZHU W., SHEN Z.J., TU C., 2010. Design and application of a
hybrid active power filter with injection circuit, IET Power Electronics, vol.
3, pp. 54-64.
LUO A., SHUAI Z. , ZHU W., 2009. Combined system for harmonic suppression
and reactive power compensation, Industrial Electronics, IEEE Transactions
on, vol. 56, pp. 418-428.
MAHESH S.S., MISHRA M. K., KUMAR B.K., JAYASHANKAR V., 2008. Rating
and design issues of DVR injection transformer, Applied Power Electronics
Conference and Exposition, pp. 449-455.
MALABIKA B., DAS P.S., DUBEY K.G., 2007. Comparative evaluation of two
models of UPQC for suitable interface to enhance power quality, Electric
Power Systems Research, pp. 821-830.
MARGO P., HERI M.P., ASHARI M., HIYAMA T., 2007. Balanced voltage sag
correction using dynamic voltage restorer based fuzzy polar controller,
Proceedings of the Second International Conference on Innovative
Computing, Information and Control, pp. 1-4.

188
MASSOUD A.M. , FINNEY S.J., WILLIAMS B.W., 2004. Seven-level shunt active
power filter, Harmonics and Quality of Power, 11th International Conference
on, pp. 136-141.
MASTROMAURO R.A., LISERRE M., AQUILA A.D., 2007. Single-phase grid
connected photovoltaic systems with power quality conditioner functionality,
Proceedings of EPE, pp. 1-11.
MATAS J., VICUNA L.G., MIRET J., GUERRERO J.M., CASTILLA M., 2008.
Feedback linearization of a single-phase active power filter via sliding mode
control, IEEE Transactions on Power Electronics, vol. 23, pp. 116-125.
MAURICIO A., HIROFUMI A., EDSON H.W., EUMIR V.S., LUCASF.E., 2009.
Comparisons between the p-q and p-q-r theories in three-phase four-wire
systems, IEEE Transactions on Power Electronics, vol. 24, pp. 924-933.
MCGRANAGHAN, M. 2005. Roadmap for power quality standards development.
IEEE Power Engineering Society General Meeting, vol. 3, pp. 2209-2213.
MCGRANAGHAN, M., ROETTGER, B., 2002. Economic evaluation of power
quality, IEEE Power Engineering Review, 22(2), pp. 8-12.
MCHATTIE R., 1998, Dynamic voltage restorer the customers's perspective, IEE
Colloquium on Dynamic Voltage Restorer - Replacing Those Missing Cycles,
pp. 1-5.
MEKRI F., MACHMOUM M.A., MAZARI N.A., IREN B., 2008. A fuzzy
hysteresis voltage and current control of an unified power quality conditioner,
Industrial Electronics, 34th Annual Conference of IEEE, pp. 2684-2689.
MERAL E.M., 2009, Voltage quality enhancement with custom power park, Ph.D.
Thesis, ukurova University, Institute of Natural and Applied Science.
MEYER C., DONCKER R.W.D., LI Y.W., BLAABJERG F., 2008. Optimized
control strategy for a medium voltage DVR - Theoretical investigations and
experimental results, Power Electronics, IEEE Transactions, vol. 23, pp.
2746-2754.
MOHAMMADI H.R., VARJANI A.Y., MOKHTARI H., 2009. Multiconverter
unified power-quality conditioning system: MC-UPQC, Power Delivery,
IEEE Transactions on, vol. 24, pp. 1679-1686.

189
MOJIRI M., KARIMI M.G., BAKHSHAI A., 2010. Processing of harmonics and
interharmonics using an adaptive notch filter, IEEE Transactions on power
delivery, vol. 25, pp. 534-542.
MOKHTARI H., DEWAN S.B., TRAVANI M.R., 2000. Performance evaluation of
thyristor based static transfer switch, IEEE Transactions on Power Delivery,
vol. 15, pp. 960-966.
MORADLOU M., KARSHENAS H.R., 2011. Design strategy for optimum rating
selection of interline DVR, IEEE Transactions on Power Delivery, vol. 26,
pp. 242-249.
MORENO M.V., ALBERTO P., MARCO L., AQUILA A.D., 2008. Unified power
quality conditioner (UPQC) with voltage dips and over-voltages
compensation capability, International Conference on Renewable Energies
and Power Quality, pp. 1-6.
MORRIS B., FARANDA R., TIRONI E., 2009. A new proposal for power quality
and custom power improvement: OPEN UPQC, IEEE Transactions on Power
Delivery, vol. 24, pp. 2107-2116.
MUNI B.P., VENKATESHWARLU S., MAKTHAL H.V., HYDERABAD P.J., 2004.
Review of dynamic voltage restorer for power quality improvement, IEEE
Industrial Electronics Society, vol. 1, pp. 749-754.
MUNOZ J.A., ESPINOZA J.R., RUBILARI.A., MORAN L.A., MELIN P.E., 2008.
A modular approach for integrating harmonic cancellation in a multi-cell
based UPQC, Industrial Electronics, IECON 34th Annual Conference of
IEEE, pp. 3178-3183.
MUNOZ J.A., ESPINOZA J.R., MORAN L.A., BAIER C.R., 2009. Design of a
modular UPQC configuration integrating a components economical analysis,
IEEE Transactions on Power Delivery, vol. 24, pp. 1763-1772.
NAIDU S.R., FEMANDES D.A., 2007. The 4-leg voltage source converter and its
application to dynamic voltage restoration, Industrial Electronics, IEEE
International Symposium, pp. 781-786.

190
NASIRI A., EMADI A., 2003. Different topologies for single-phase unified power
quality conditioners, Industry Applications Conference, 38th IAS Annual
Meeting. Conference Record, vol. 2, pp. 976-981.
NEWMAN M.J., HOLMES D.G., 2002. A universal custom power conditioner with
selective harmonic voltage compensation, IECON 02, Industrial Electronics
Society, IEEE 28th Annual Conference, vol. 2, pp. 1261-1266.
NEWMAN M.J., HOLMES D.G., NIELSEN J.G., BLAABJERG F., 2005. A
dynamic voltage restorer (DVR) with selective harmonic compensation at
medium voltage level, IEEE Transactions on Industry Applications, vol. 41,
pp. 1744-1753.
NGUYEN P.T., SAHA T.K., 2004. Dynamic voltage restorer against balanced and
unbalanced voltage sags: modeling and simulation, Power Engineering
Society General Meeting, IEEE, vol.1, pp. 639-644.
NIELSEN J.G., BLAABJERG F., MOHAN N., 2001. Control strategies for dynamic
voltage restorer compensating voltage sags with phase jump, IEEE Applied
Power Electronics Conference and Exposition, vol. 2, pp. 1267-1273.
NIELSEN J.G., NEWMAN M., NIELSEN H., BLAABJERG F., 2004. Control and
testing of a dynamic voltage restorer (DVR) at medium voltage level, Power
Electronics, IEEE Transactions, vol. 19, pp. 806-813.
OTADUI I.E., VISCARRET U., BACHA S., CABALLERO M., REYERO R., 2002.
Evaluation of different strategies for series voltage sag compensation, IEEE
Power Electronics Specialists Conf., vol. 4, pp. 1797-1802.
PARSONS A.C., GRADY W.M., POWERS E.J., 1999. A wavelet-based procedure
for automatically determining the beginning and end of transmission system
voltage sags, in Proc. IEEE Power Eng. Soc., pp. 1310-1315.
PEREZ J., CARDENAS V., MORAN L., NUNEZ C., 2006. Single-phase AC-AC
converter operating as a dynamic voltage restorer (DVR), IEEE Industrial
Electronics Conference, pp. 1938-1943.
PERRY C., DORR D., 2003, Custom power choices abound, EPRI PEAC Corp.

191
PUCCI M., VITALE M., MIRAOUI A.G., 2009. Current harmonic compensation by
a single-phase shunt active power filter controlled by adaptive neural
filtering, IEEE Transactions on Industrial Electronics, vol. 56, pp. 3128-3143.
QU Y., TAN W., YANG Y., 2007. A fuzzy adaptive detecting approach of harmonic
currents for active power filter, Power Electronics and Drive Systems, 7th
International Conference on, pp. 1695-1699.
RADZI M.A.M., RAHIM N.A., 2009. Neural network and bandless hysteresis
approach to control switched capacitor active power filter for reduction of
harmonics, IEEE Trans. on Industrial Electronics, vol. 56, pp. 1477-1484.
RAHIM N.A., HEW W.P., LIM S.H., 2005. Simple control strategy for fuzzy logic
controlled active power filter, 10th Conference on Artificial Intelligence and
Applications, National University of Kaohsiung, Taiwan.
RAITHMAYR W., DAEHLER P., EICHLER M., LOCHNER G., JOHN E., CHAN
K., 1998. Customer reliability improvement with a DVR or a DUPS, Power
World 98, pp. 1-10.
RAMACHANDARAMURTHY V.K., ARULAMPALAM A., FITZER C., ZHAN C.,
BARNES M., JENKINS N., 2004. Supervisory control of dynamic voltage
restorers, IEE Gener., Transmis. and Distr., vol. 151, pp. 509-516.
RAMACHANDARAMURTHY V.K., FITZER C., ARULAMPALAM A., ZHAN C.,
BARNES M., JENKINS N., 2002. Control of a battery supported dynamic
voltage restorer, IEE Proceedings Generation Transmission and Distribution,
vol. 149, pp. 533-542.
RAMASAMY A., RAMACHANDARAMURTHY V.K., IYER R.K., LIU Z.L.,
2007. Control of dynamic voltage restorer using TMS320F2812, Electrical
Power Quality and Utilisation Conference, pp. 1-6.
RATHLE N.L, 2005. Design procedure for active filters for improving power quality,
Ph.D. Thesis, Department of Electrical and Computer Engineering College of
Engineering and Information Tech., University of South Carolina.
REZAEIPOUR R., KAZEMI A., 2008. Review of novel control strategies for UPQC,
Int. Journal of Electrical and Power Engineering, vol. 2, pp. 241-247.

192
RONG Y., LI C., TANG H., ZHENG X., 2009. Output feedback control of single-
phase UPQC based on a novel model, IEEE Transactions on Power Delivery,
vol. 24, pp. 1586-1597.
ROUTIMO M., 2008. Developing a voltage source shunt active power filter for
improving power quality, Ph.D. Thesis, Tampere University of Technology.
ROUTIMO M., TUUSA H., 2007. LCL type supply filter for active power filter,
comparison of an active and a passive method for resonance damping, Power
Electronics Specialists Conference, IEEE, pp. 2939-2945.
RUDNICK, H., DIXON, J., MORAN, L., 2003. Delivering clean and pure power,
IEEE Power and Energy Magazine, 1(5), pp. 32-40.
RUILIN P., YUEGEN Z., 2005. Sliding mode control strategy of dynamic voltage
restorer, Industrial Electronics and Control Applications, International
Conference on, pp. 1-3.
S&C, 2010, http://www.sandc.com, S&C Electric Company.
SABIN D.D., SANNINO A., 2003. A summary of the draft IEEE P1409 custom
power application guide, IEEE PES Transmission and Distribution
Conference and Exposition, vol. 3, pp. 931-936.
SALAM Z., TAN P.C., JUSOH A., 2006. Harmonics mitigation using active power
filter: A technological review, Harmonics Mitigation Using Active Power
Filter: A Technological Review, Elektrika Journal of Electrical Engineering,
vol. 8, pp. 17-26.
SALEH S.A., MOLONEY C.R., RAHMAN M.A., 2008. Implementation of a
dynamic voltage restorer system based on discrete wavelet transforms, IEEE
Transactions on Power Delivery, vol. 23, pp. 2366-2375.
SALMERON P., LITRAN S.P., 2010. Improvement of the electric power quality
using series active and shunt passive filters, Power Delivery, IEEE
Transactions on, vol. 25, pp. 1058-1067.
SANCHEZ P.R., ACHA E., 2009. Dynamic voltage restorer based on flying
capacitor multilevel converters operated by repetitive control, Power
Delivery, IEEE Transactions, vol. 24, pp. 951-960.

193
SANNINO A., SVENSSON J., LARSSONT., 2003.Power electronic solutions to
power quality problems. Electric Power Systems Research, 66(1): pp. 71-82.
SANTOSO S., POWERS E.J., GRADY W., 1996. Power quality disturbance
identification using wavelet transformers and artificial neutral network,
International Conference on Harmonic and Quality of Power, pp. 615-618.
SASITHARAN S., MISHRA M.K., 2009. Inter phase AC-AC topology for voltage
sag supporter, Power Electronics, IEEE Transactions on: Accepted for future
publication, pp. 1-1.
SENG L.Y., 2002. Probabilistic assessments of voltage-sag occurrence and the
evaluation of the dynamic voltage restorer capability, Ph.D. thesis, University
of Manchester Institute of Science and Tech.
SENTURK O.S., HAVA A.M., 2009. High performance harmonic isolation and load
voltage regulation of the three-phase series active filter utilizing the
waveform reconstruction method, IEEE Transactions on Industry
Applications, vol. 45, pp. 2030-2038.
SHU Z., GUO Y., LIAN J., 2008. Steady-state and dynamic study of active power
filter with efficient FPGA-based control algorithm, Industrial Electronics,
IEEE Transactions on, vol. 55, pp. 1527-1536.
SHUAI Z., LUO A., SHEN Z.J., WENJI Z., XIANYONG X., 2009. Design
considerations for maintaining DC-side voltage of hybrid active power filter
with injection circuit, Power Electronics, IEEE Trans. on, vol. 24, pp. 75-84.
SILVA S.A.O., NOVOCHADLO R., MODESTO R.A., 2008. Single-phase PLL
structure using modified p-q theory for utility connected systems, Power
Electronics Specialists Conference, IEEE, pp. 4706-4711.
SILVA S.M., ELEUTERIO F.A., REIS A.S., FILHO B.J.C., 2004. Protection
schemes for a dynamic voltage restorer, Industry Applications Conference,
39
th
IAS Annual Meeting, vol. 4, pp. 2239-2243.
SILVA S.M., SILVEIRA D.S.E., REIS A.S., FILHO B.J.C., 2005. Analysis of a
dynamic voltage compensator with reduced switch-count and absence of
energy storage system, IEEE Transactions on Industry Applications, vol. 41,
pp. 1255-1262.

194
SINGH B.N., CHANDRA H., AL-HADDAD K., SINGH B., 1998. Fuzzy control
algorithm for universal active filter, Power Quality conference 98, pp. 73-80.
SINGH B.N., SIMINA, M., 2004. Intelligent solid-state voltage restorer for voltage
swell/sag and harmonics Electric Power Applications, IEE Proceedings, vol.
151, pp. 98-106.
SINGH B., AL-HADDAD K., CHANDRA A., 1999. A review of active filters for
power quality improvement, IEEE Transaction on Industrial Electronics,
vol. 46, pp. 960-971.
SINGH G.K., SINGH A.K., MITRA R., 2007. A simple fuzzy logic based robust
active power lter for harmonics minimization under random load variation,
Electric Power Systems Research, vol. 77, pp. 1101-1111.
SINGH M., KHADKIKAR V., CHANDRA A., VARMA R.K., 2011. Grid
interconnection of renewable energy sources at the distribution level with
power-quality improvement features, IEEE Transactions on Power Delivery,
vol. 26, pp. 307-315.
SREE H., MOHAN N., 2000. Voltage sag mitigation using a high frequency link
cyclo converter based DVR, Industrial Electronics Society Conference, IEEE,
vol. 1, pp. 344-349.
SRIDHAR G.R., SINGH R.K., 2007. Distributed generation based dynamic voltage
restorer, Information and Communication Technology in Electrical Sciences
International Conference, pp. 262-266.
SRISONGKRAM W., SUBSINGGHA W., BOONCHIAM P., 2006. Voltage sag
detection method in power distribution systems for power quality issues,
Power System Research Center, pp. 1-3.
TEKE A., 2005. Modeling of dynamic voltage restorer, M. Sc. Thesis, ukurova
University, Institute of Natural and Applied Science.
TEKE A., BAYINDIR K.., TMAY M., 2009. Fast sag/swell detection method for
fuzzy logic based dynamic voltage restorer, IET Generation, Transmission &
Distribution, vol. 4, pp. 1-12.

195
TEKE A., MERAL M.E., SARIBULUT L., TMAY M., 2010a. Dynamic voltage
restorers: A literature review, Faculty of Electrical Engineering Universiti
Teknologi, Malaysia, vol. 12, no. 1, pp. 7-13.
TEKE A., SARIBULUT L., MERAL M.E., TMAY M., 2010b. Active power filter:
Review of converter topologies and control strategies, Gazi University
Journal of Science, vol. 23, no 3, pp. 249-253.
TEKE A., TMAY M., 2011. Unified power quality conditioner: A literature survey,
Journal of Electrical Systems, vol. 7, no 2, pp.122-130.
TERCIYANLI A., ERMIS M., CADIRCI I., 2011, A selective harmonic
amplification method for reduction of kVA rating of current source converters
in shunt active power filters, IEEE Transactions on Power Delivery, vol. 26,
pp. 65-78,
TEY L.H., SO P.L., CHU Y.C., 2002. Neural network-controlled unified power
quality conditioner for system harmonics compensation, Asia Pacific
IEEE/PES Trans. and Distr. Conf. and Exhibition, vol. 2, pp. 1038-1043.
TEY L.H., SO, P.L. CHU, Y.C., 2004. Unified power quality conditioner for
improving power quality using ANN with hysteresis control, Power System
Technology, International Conference, vol. 2, pp. 1441-1446.
TILLI A., TONIELLI A., 1998. Sequential design of hysteresis current controller for
three-phase inverter, IEEE Transactions on Industrial Electronics, vol. 45, pp.
771-781.
TOLBERT L.M., PENG F.Z., HABETLER T.G., 2000. A multilevel converter based
universal power conditioner, IEEE Trans. on Industry Applications, vol. 36,
pp. 596-603.
TOODEJI H., FATHI S.H., 2009. Cost reduction and control system improvement in
electrical arc furnace using DVR, Industrial Electronics and Applications,
IEEE Conference, pp. 211-215.
UYYURU K.R., MISHRA M.K., GHOSH A., 2009. An optimization based
algorithm for shunt active filter under distorted supply voltages, Power
Electronics, IEEE Transactions on, vol. 24, pp. 1223-1232.

196
VADIRAJACHARYA K., AGARWAL P., GUPTA H.O., 2008. Performance
evaluation of CSI based unified power quality conditioner using artificial
neural network, International Journal of Power Electronics, vol. 1, pp. 17-32.
VILATHGAMUWA D.M., PERERA A.A.D.R., CHOI S.S., 2003. Voltage sag
compensation with energy optimized dynamic voltage restorer, Power
Delivery, IEEE Transactions, vol.18, pp. 928-936.
VILATHGAMUWA D.M., PERERA A.A.D.R., CHOI S.S., 2002. Performance
improvement of the dynamic voltage restorer with closed-loop load voltage
and current-mode control, IEEE Transactions on Power Electronics, vol. 17,
pp. 824-834.
VODYAKHO O., KIM T., 2009a. Shunt active filter based on three-level inverter for
three-phase four-wire systems, Power Electronics, IET, vol. 2, pp. 216-226.
VODYAKHO O., MI C.C., 2010. Synchronization of three-phase converters and
virtual microgrid implementation utilizing the power-hardware-in-the-loop
concept, Applied Power Electronics Conference and Exposition, Twenty-Fifth
Annual IEEE, pp. 216-222.
WANG B., VENKATARAMANAN G., 2009. Dynamic voltage restorer utilizing a
matrix converter and flywheel energy storage, Industry Applications, IEEE
Transactions, vol. 45, pp. 222-231.
WANG B., VENKATARAMANAN G., ILLINDALA M., 2006. Operation and
control of a dynamic voltage restorer using transformer coupled H-bridge
converters, Power Electronics, IEEE Transactions, vol. 21, pp. 1053-1061.
WANG K., ZHUO F., LI Y., YANG X., WANG Z., 2004. Three-phase four-wire
dynamic voltage restorer based on a new SVPWM algorithm, IEEE Power
Electronics Specialists Conference, vol. 5, pp. 3877-3882.
WON D.J., AHN S.J., CHUNG I.Y., KIM J.M., MOON S.I., 2003. A new definition
of voltage sag duration considering the voltage tolerance curve, IEEE Power
Tech Conf. Proceedings, vol. 3, pp. 1-5.
WOODLEY N.H., MORGAN L., SUNDARAM A., 1999. Experience with an
Inverter Based Dynamic Voltage Restorer, IEEE Transactions on Power
Delivery, 14(3), pp. 1181-1186.

197
XIAO P., VENAYAGAMOORTHY G.K., CORZINE K.A., 2009. Seven-level shunt
active power filter for high-power drive systems, Power Electronics, IEEE
Transactions on, vol. 24, pp. 6-13.
XINMING H., JINJUN L., HUI Z., 2009. A unified compensator design based on
instantaneous energy equilibrium model for the DC link voltage control of
UPQC, Applied Power Electr. Conf. and Exposition, 24 Annual IEEE,
pp. 1577-1582.
YIN Z., HAN M., ZHOU L., KUNSHAN Y., 2005. Project study of dynamic voltage
restorer, IEEE/PES Transmission and Distribution Conference and
Exhibition, Asia and Pacific, pp. 1-8.
ZHANG H., FINNEY J.S., MASSOUD A., WILLIAMS B.W., 2008. An SVM
algorithm to balance the capacitor voltages of the three-level NPC active
power filter, Power Electronics, IEEE Trans. on, vol. 23, pp. 2694-2702.
ZHANG H., MASSOUD A.M., FINNEY S.J., WILLIAMS B.W., FLETCHER J.E.,
2007. Operation of an active power filter with line voltage SVM under non-
ideal conditions Compatibility in Power Electronics, pp. 1-7.
ZHAO C., ZHAO X., JIA X., 2004. System innovation for solving power quality
problems based on environmental economic, IEEE PES Power Systems
Conference and Exposition, vol. 1, pp. 41-45.
ZHOU H., ZHOU J., QI Z.P., 2008. Fast voltage detection for a single-phase
dynamic voltage restorer (DVR) using morphological low-pass filters , The
Third International Conference on Electric Utility Deregulation and
Restructuring and Power Technologies, pp. 2042-2046.
ZHU J., JIANG X., HUANG L., 2008. A novel dynamic voltage restorer with
flywheel energy storage system, Electrical Machines and Systems,
International Conference, pp. 1995-1999.
ZHU P., LI X., KANG Y., CHEN J., 2003. A novel control scheme in 2-phase unified
power quality conditioner, Industrial Electronics Society, 29th Annual
Conference of the IEEE, vol. 2, pp. 1617-1622.



198


199
BIOGRAPHICAL INFORMATION

Ahmet TEKE was born in Osmaniye, Turkey in 1979. He received his B.S.
and M.Sc. degrees both in Electrical and Electronics Engineering Department from
the ukurova University in 2002 and 2005, respectively. He has been working as a
research assistant in Electrical and Electronics Engineering Department of the
ukurova University since 2005.
He joined the power quality research group in 2007 to pursue a Ph.D. degree
in Electrical and Electronics Engineering. He has worked in several research projects
supported by Scientific and Technological Council of Turkey and Scientific Research
Project Unit of ukurova University. His research areas are custom power, power
converters, energy efficiency and power electronic applications of renewable energy
sources. He is a member of Turkish Chamber of Electrical Engineers and also a
student member of IEEE.















200
APPENDIX A: Most Common Power Quality Problems

Table A.1: Most common PQ problems
1.
Voltage sag
(or dip)

Description: A decrease of the normal voltage level between 10%
and 90% of the nominal rms voltage at the power frequency, for
durations of 0.5 cycle to 1 minute.
Causes: Faults on the transmission or distribution network, faults
in consumers installation, connection of heavy loads and start-up
of large motors.
Consequences: Malfunction of information technology equipment
(namely microprocessor-based control systems such as PCs, PLCs,
ASDs) that may lead to a process stoppage, tripping of contactors
and electromechanical relays, disconnection and loss of efficiency
in electric rotating machines.
2.
Voltage swell

Description: Momentary increase of the voltage, at the power
frequency, outside the normal tolerances, with duration of more
than one cycle and typically less than a few seconds.
Causes: Start/stop of heavy loads, badly dimensioned power
sources, badly regulated transformers (mainly during off-peak
hours).
Consequences: Data loss, flickering of lighting and screens,
stoppage or damage of sensitive equipment, if the voltage values
are too high.
3.
Harmonic
distortion

Description: Voltage or current waveforms assume non-sinusoidal
shape. The waveform corresponds to the sum of different sine-
waves with different magnitude and phase, having frequencies that
are multiples of power-system frequency.
Causes: Classic sources: electric machines working above the
knee of the magnetic saturation, arc furnaces, welding machines,
rectifiers and DC brush motors. Modern sources: all nonlinear
loads, such as ASDs, switched mode power supplies, data
processing equipment, high efficiency lighting.
Consequences: Increased probability in occurrence of resonance,
neutral overload in 3-phase systems, overheating of all cables, loss
of efficiency in electric machines, electromagnetic interference
with communication systems, errors in measures when using
average reading meters, nuisance tripping of thermal protections.
4.
Very short
interruption

Description: Total interruption of electrical supply for duration
from few milliseconds to one or two seconds.
Causes: Mainly due to the opening and automatic reclosure of
protection devices to decommission a faulty section of network.
The main fault causes are insulation failure, lightning and insulator
flashover.
Consequences: Tripping of protection devices, loss of information

201
and malfunction of data processing equipment, stoppage of
sensitive equipment, such as ASDs, PCs, PLCs, if they are not
prepared to deal with this situation.
5.
Long
interruption

Description: Total interruption of electrical supply for duration
greater than 1 to 2 seconds.
Causes: Equipment failure in the power system network, storms
and objects (trees, cars, etc) striking lines or poles, fire, human
error, bad coordination or failure of protection devices.
Consequences: Stoppage of all equipment.
6.
Voltage
spike

Description: Very fast variation of the voltage value for durations
from a several microseconds to few milliseconds. These variations
may reach thousands of volts, even in low voltage.
Causes: Lightning, switching of lines or power factor correction
capacitors, disconnection of heavy loads.
Consequences: Destruction of components (particularly electronic
components) and of insulation materials, data processing errors or
data loss, electromagnetic interference.
7.
Voltage
fluctuation

Description: Oscillation of voltage value, amplitude modulated by
a signal with frequency of 0 to 30 Hz.
Causes: Arc furnaces, frequent start/stop of electric motors (for
instance elevators), oscillating loads.
Consequences: Most consequences are common to undervoltages.
The most perceptible consequence is the flickering of lighting and
screens, giving the impression of unsteadiness of visual
perception.
8.
Noise

Description: Superimposing of high frequency signals on the
waveform of the power-system frequency.
Causes: Electromagnetic interferences provoked by Hertzian
waves such as microwaves, television diffusion and radiation due
to welding machines, arc furnaces and electronic equipment.
Improper grounding may also be a cause.
Consequences: Disturbances on sensitive electronic equipment,
usually not destructive. May cause data loss and data processing
errors.
9.
Voltage
unbalance

Description: A voltage variation in a 3-phase system in which the
three voltage magnitudes or the phase-angle differences between
them are not equal.
Causes: Large single-phase loads (induction furnaces, traction
loads), incorrect distribution of all single-phase loads by the three-
phases of the system (this may be also due to a fault).
Consequences: Unbalanced systems imply the existence of a
negative sequence that is harmful to all three-phase loads. The
most affected loads are three-phase induction machines.




202
APPENDIX B. Fundamentals of Instantaneous Reactive Power Theory

Instantaneous Reactive Power Theory (p-q theory) is based on set of
instantaneous powers defined in the time domain and uses the Park Transform. No
restrictions are imposed on the voltage or current waveforms and it can be applied to
three-phase systems with or without a neutral wire for three-phase generic voltage
and current waveforms. Thus, it is valid not only in the steady state but also in the
transient state. This theory is very efficient and flexible in designing controllers for
power conditioners based on power electronics devices (Akagi et al., 2007).
In three-phase circuits, instantaneous currents and voltages are converted to
instantaneous space vectors. In instantaneous power theory, the instantaneous three-
phase currents and voltages are calculated as given in following equations. These
space vectors are easily converted into the orthogonal coordinates (Kale et al.,
2005), (Akagi et al., 1986).

1 1/ 2 1/ 2
2
3
0 3 / 2 3 / 2
a
b
c
V
V
V
V
V

(
( (
(
=
( (
(


(

(B.1)

1 1/ 2 1/ 2
2
3
0 3 / 2 3 / 2
a
b
c
I
I
I
I
I

(
( (
(
=
( (
(


(

(B.2)

Considering only the three-phase three-wire system, the three-phase currents
can be expressed in terms of harmonic positive, negative and zero sequence currents.
In Equations (B.1) and (B.2), and are orthogonal coordinates. V

and I

are on
axis, V

and I

are on axis. Three-phase conventional instantaneous power is


calculated as follows.


+ = I V I V p
(B.3)


203
In fact, instantaneous real power (p) is equal to following equation:

c c b b a a
I V I V I V p + + = (B.4)

Instantaneous real and imaginary powers are calculated as follows.

V V I
p
I q V V


( (
(
=
( (
(

(

(B.5)


In (B.5), V

and V

are instantaneous real (p) and imaginary (q) powers,


respectively. Since these equations are products of instantaneous currents and
voltages in the same axis, in three-phase circuits, instantaneous real power is p and
its unit is watt. In contrast V

and V

are not instantaneous powers. Since these


are products of instantaneous currents and voltages in two orthogonal axes, q is not
conventional electric unit like watt or VAr. The value q is instantaneous imaginary
power and its unit is imaginer volt ampere (Kale et al., 2005), (Akagi et al., 1984).
These power quantities given above for an electrical system represented in a-b-c
coordinates and have the following physical meaning.
p, the mean value of the instantaneous real power - corresponds to the energy
per time unity which is transferred from the power supply to the load, through a-b-c
coordinates, in a balanced way.
%
p, alternated value of the instantaneous real power - it is the energy per time
unity that is exchanged between the power supply and the load through a-b-c
coordinates.
q , the mean value of the instantaneous imaginary power that is equal to the
conventional reactive power.
%
q , instantaneous imaginary power - corresponds to the power that is
exchanged between the phases of the load. This component does not imply any

204
exchange of energy between the power supply and the load, but is responsible for the
existence of undesirable currents, which circulate between the system phases.
The instantaneous active and reactive power includes AC and DC values and
can be expressed as follows:

~ ~
q q q, p p p

= + = + (B.6)

DC values of the p and q are created from positive-sequence component of
the load current. AC values of the p and q are produced from harmonic components
of the load current (Kale et al., 2005). Equation (B.5) can be written as (B.7):

1
V V I
p
I V V q

( (
(
=
( (
(

(


(B.7)