Beruflich Dokumente
Kultur Dokumente
Backup Protection
A B
1 2 3 Fault X 4
Local backup is the additional (or secondary, redundant) protection provided for the primary zone to assure breaker trip if the primary relaying fails. Remote backup is the overlapping of the primary zone provided by remote (adjacent busses) protection that will operate, after a suitable coordinating time, if the primary zone breaker does not trip. Relays at 1 protecting line AB are also remote backup to relays at 3 protecting line BC. Breaker failure is initiated when the primary and/or local backup relays have operated and the local breaker fails to trip.
2
Remote Backup
A B
1 2 3 Fault X 4
Fault on line BC - Failure of breaker 3 to operate Relays at 1,5 and 8 are backup to to relays at 3 Backup relays may not see fault due to infeed Coordination time may be undesirably slow Sequential remote tripping If one remote can see the fault and clear there will be a redistribution of fault currents reducing the effect of infeed The second remote relay will trip eliminating infeed The last remote relay will trip
4
Breaker Failure
EHV and UHV Applications Greater fault currents produce more stress on power circuit breakers Stability demands for faster backup clearing Critical Clearing Time
Thus, Local Breaker Failure Breaker failure does not preclude remote backup
4 3
Fault on line BC and relays at 1, 2 and 5 operate Breakers 1 and 5 trip - breaker 2 fails to operate Breaker failure at 2 trips breaker 3 and removes any infeed seen by relays at 4 Relays at 4 will operate as remote backup to clear fault Transfer tripping of breaker 4 by breaker failure at 2 is also possible Breaker Failure Protection
+ dc
Relay Scheme
+ dc 62X 50 62Y
#1
#2
52a
94
62Y 62 BF - dc
62BF 86 BF 86BF
Multiple
86BF
Contacts
- dc
50 - Phase and ground instantaneous overcurrent relays 52a - Breaker auxiliary contact, open when breaker is open 52T - Breaker trip coil 62X,Y - Breaker failure auxiliary (BFI) 62BF - Breaker failure timer 86BF - Breaker failure lockout relay 94 - Breaker trip relay (used for single trip coil applications)
7
86BF
50 - Phase and ground instantaneous overcurrent relays 52a - Breaker auxiliary contact, open when breaker is open 62X,Y - Breaker failure auxiliary (BFI) 62BF - Breaker failure timer 86BF - Breaker failure lockout relay 86T - Transformer differential lockout
8
Typical Logic
62X,Y 50BF-1 62X,Y 50BF-2 62X,Y 50BF-3 62 BF 86 BF
N 50 BF
62X,Y 50BF-N
Breaker-and-a-half Bus
Line 1 Bus L 1 2
Line 2
4 3 50 3 Bus R
Breaker Failure 1 2 3
86 Relay Operations
Trip 2 and all Bus L breakers. Transfer trip Line 1 Trip 1 and 3. Transfer trip lines 1 & 2. Trip 2 and all Bus R breakers, such as 4. Transfer trip line 2
50 1
50 2 Line 2 Relays
Line 1 Relays
10
Ring Bus
Relays Line 1 Relays 4 50 4 50 3 3 86T Transformer Differential 1 50 1 2 Relays Line 3 50 2 Line 2
Breaker Failure 1 2 3 4 86 Relay Operations
Trip 2 and 4 Transfer trip lines 1 & 2 Trip 1 and 3 Transfer trip lines 2 & 3 Trip 2, 4, and 5 Transfer trip line 3 Trip 1, 3, and 5 Transfer trip line 1
11
* 62X 62Y
50 52a Options 86T 52a T 0 62BF 86BF
62X,Y - Breaker failure auxiliary (BFI) Include both line relays 62X, Y for common breaker Breaker-and-a-half bus - center breaker Ring bus
12
Relay Operate
50 Reset
Normal Clearing Local Backup BF Total Clearing Remote Backup BF Total Clearing
13
Breaker Failure
50BF Overcurrent Reset is affected by: Breaker arcing contacts and shunting resistors Fault current level prior to interruption CT saturation 50BF setting Breaker-and-a-half and ring bus applications Solid state relays have faster reset than electromechanical relays Reset is generally assured to be within one cycle using microprocessor relays -this is dependent on sampling and computation rate
14
62X 62Y
50BF - Phase and ground torque controlled instantaneous overcurrent relays Relay cannot operate until after 62BF time Fast pickup, 0.25 to 1.0 cycle depending on setting and fault current Allows more sensitive setting Control timer resets breaker failure operation
15
Relay Operate
Margin 86 50 BF Pickup Local Backup Clearing TFR TRIP Remote Backup Clearing
Normal Clearing Local Backup BF Total Clearing Remote Backup BF Total Clearing
16
A maximum allowable time that a fault may persist before jeopardizing the integrity of the power system System location Loading Fault type Breaker failure clearing time including remote backup clearing must be less than critical clearing time
17
IPO Breakers
Independent Pole Operated Breakers Single pole tripping and reclosing Three pole tripping
On breaker failure
the opening of two phases on a three-phase fault will likely clear the fault or change the fault characteristic to single-phase-to-ground. Increase the maximum critical clearing time.
18
Pole Discrepancy
Based on auxiliary 52a and/or 52b contact positions Based on breaker current level
19
Pole Discrepancy
Auxiliary contact arrangement for three pole gang operated breaker position indication
20
Pole Discrepancy
Auxiliary contact arrangement for IPO breaker position indication Using 52a - parallel 52a = 0 (All poles open) 52a = 1 (Any pole closed) Using 52b - series 52b = 1 (All poles open) 52b = 0 (Any pole closed)
CIRCUIT BREAKER
A B C
A B C
A 52b
B 52b
21
Pole Discrepancy
Auxiliary contact arrangement for IPO breaker position indication Using 52a - series 52a = 0 (Any pole open) 52a = 1 (All poles closed) Using 52b - parallel 52b = 1 (Any pole open) 52b = 0 (All poles closed)
CIRCUIT BREAKER
A B C
A B C
A 52a
B 52a
22
Pole Discrepancy
CIRCUIT BREAKER
A B C
Auxiliary contact arrangement at IPO breaker Breaker position Pole discrepancy indication
A B C
52a 52a 52a Breaker position with 52a (any pole closed) Pole Discrepancy From Breaker
A B C
23
Pole Discrepancy
Auxiliary contact arrangement at IPO breaker Breaker position with 52a and 52b Pole discrepancy logic in IED
24
Pole Discrepancy
CIRCUIT BREAKER
A B C
Auxiliary contact arrangement at IPO breaker Breaker position with 52a/pole Pole discrepancy logic in IED Particularly suitable for SPT
AND AND
A B C
Pole Discrepency
IED Logic
25
Pole Discrepancy
Auxiliary contact arrangement at IPO breaker Breaker position with 52a and 52b per pole Pole discrepancy logic in IED Particularly suitable for SPT
26
Pole Discrepancy
27
Questions?
28