The ever increasing demand for energy is causing an ever increasing number of short-circuit currents across low voltage electrical networks. This places high demands on the protective switch-gear with regard to safety, reliability and switching capacity. The Heavy Duty Circuit Breaker S500 satisfies these requirements by virtue of its special technical features. It is provided with thermal and/or electromagnetic trip functions to protect circuits, motors, equipment and systems from the results of overload and short-circuit currents.
Major features
High rated breaking capacities, up to 30/50 kA High rated operating voltage 400/690 VAC, 750 VDC Energy and current limiting interruption Extremely short breaking time Optimum selectivity Reliable switching and contact position indication Numerous versions for special applications Compact dimensions, DIN cap size Wide range of accessories, including undervoltage and shunt trip, auxiliary and signal contacts
Railway
Commercial building
Offshore
40040
Ships
Process industry
Rail, tram
10139/B
- Description ............................................................................................... 2 - Application ............................................................................................... 4 - Technical Data .......................................................................................... 8 - Selectivity ............................................................................................... 13 - Back-up protection ................................................................................. 16 - Circuit protection .................................................................................... 17 S500-B, S500-C, S500-D - Motor protection S500-K .................................................................................................... 18 S503-KM ................................................................................................. 20 S503X-AG0084 ........................................................................................ 22 - DC circuit protection ............................................................................... 24 S500UC-B, S500UC-K - Customer-fitted RCD protection with overload protection ....................... 26 DDA - RCD protection with overload protection ................................................ 27 F500-C, F500-D - Short delay and selective RCD protection with overload protection ......... 28 F500K0.03, F500S0.3 - RCD protection with motor protection ..................................................... 30 F500K - Accessories ............................................................................................ 32 Accessories: Factory-fitted ........................................................................ 34 Accessories: Customer-fitted ..................................................................... 35 - Dimensions/installation instructions ...................................................... 38
1
10139/B
Connection All units are supplied with open terminals. The terminals have captive plus/minus screws. The terminals can be fitted with various, fully-proven wiring systems for power supply input. IP40 terminal covers to insulate the connection terminals are available as accessories.
Nameplate Data for all important information at a glance on the front of the device. Type designation: S500 Rated voltage: 400/690 VAC, 750V DC Rated insulation voltage: 690 VAC Rated breaking capacity Icu per IEC 60947-2: 50 kA Sealing and locking devices A prepared retainer permits simple attachment of a lockout device or seal in the ON or OFF position.
Data plate (side mounted) The Heavy Duty Circuit Breakers have been subjected to many short-circuit, insulation, heating and endurance tests at independent test centres and at the ABB Schweiz AG, CMC Low Voltage Products internal test laboratory and have been approved by the authorities mentioned.
Z100028.eps
Release knob (Not for adjustable types) The breaker can be tripped locally by turning the grey release knob on the line and switched neutral poles. The knob must be reset before the breaker can be closed again. Position indicator The breaker has a reliable switching position and contact indicator in accordance with IEC 60947-2: Position "ON"; " " = red Contacts closed Position "OFF"; "0" = green Contacts open Contacts open after manual operation or trip by overload, short-circuit, residual current, shunt trip or undervoltage trip.
2
10139/B
10 A 15 14 12
Z100029.eps
Rated current setting The rated current is adjustable between 70 % and 100 % of the max. rated value.
RCD reset lever This lever moves down following a residual current trip. It being reclosed, it must be reset to the up position.
Test button for RCD protection Test button T can be used to simulate a residual current for checking the function of the RCD protection. This check should be performed upon commissioning and regularly thereafter.
RCD connection diagram and data plate Display of RCD-specific data. RC-signal contact T10 See the Chapter on Accessories: Factory-fitted.
Z100030.eps
3
10139/B
40037
Trip characteristic
10 000
10 000
1000
1000
100
100
Trip time in s
Trip time in s
10
10
0,1
0,1
0,01
Z100031eps
0,01
Z100032eps
0,002 1 2 3 5 10 20 30
0,002 1 2 3 5 10 20 30
1.13...1.45 xIn
1.13...1.45 xIn
3...5 xIn
5...10 xIn
30 C
30 C
4
10139/B
40101
40038
10 000
10 000
1000
1000
100
100
Trip time in s
Trip time in s
10
10
0,1
0,1
0.1 0.21 A 0.2 0.42 A 0.38 45 A
0,01
Z100033.eps
0,01
40040
0,002 1 2 3 5 10 20 30
0,002 1 2 3 5 10 20 30
Z100036eps
1.13...1.45 xIn
1.05...1.2 xIn
10...20 xIn
30 C
40702
5
10139/B
Trip characteristic
10 000
40042
10 000
1000
1000
100
100
Trip time in s
10
10
0,1
0,1
0.1 0.21 A 0.2 0.42 A 0.38 45 A
0,01
Z100034eps
0,01
40041
0,002 1 2 3 5 10 20 30
0,002 1 2 3 5 10 20 30
UC-B
UC-K
1.13...1.45 xIn
1.05...1.2 xIn
0.21 A: 8...10 xIn (DC) 0.42 A: 10...12 xIn (DC) 0.38 A: 12...14 xIn (DC) 40 C
30 C
6
10139/B
Z100035eps
40459
10 000
10 000
40459
10 000
1000
1000
1000
100
100
100
Trip time in s
Trip time in s
Trip time in s
10
10
10
0,1
0,1
0,1
0.1 0.21 A 0.2 0.42 A 0.38 45 A
0,01
Z100037.eps
0,01
Z100038.eps
0,01
40460
0,002 1 2 3 5 10 20 30
0,002 1 2 3 5 10 20 30
0,002 1 2 3 5 10 20 30
1.13...1.45 xIn
1.13...1.45 xIn
1.05...1.2 xIn
5...10 xIn
10...20 xIn
30 C
30 C
10139/B
Z100039.eps
6...63 A -
0.1...45 A -
Max. rated operating voltage Ue: Rated insulation voltage Ui: Rated impulse withstand voltage Uimp (1, 2/50 s): Impulse current withstand (8/20 s): Rated breaking capacity according to EN 60898: 230/400 VAC: Rated breaking capacity according to IEC60947-2: single pole/multiple pole 230/400 VAC: 250/440 VAC: 3 x 500 VAC: 400/690 VAC: Rated breaking capacity according to UL1077 and CSA: single pole/multiple pole 240/415 VAC: 277/480 VAC: 346/600 VAC: 250 VDC L/R 15 ms (1-pole) 500 VDC L/R 15 ms (2-pole) 750 VDC L/R 15 ms (3-pole) 750 VDC L/R 15 ms (4-pole) Rated frequency:
400/690 VAC
400/690 VAC
Icu 50 kA 30 kA 15 kA 6 kA 25 A Icc6) 30 kA 14 kA 6 kA -
5)
0.13 A : 100 kA Icu = Ics 2.8 11 A: 1045 A: Ics Icu Ics Icu 50 kA 30 kA 30 kA 25 kA 30 kA 22 kA 25 kA 22 kA 20 kA 15 kA 15 kA 11 kA 6 kA 3 kA 6 kA 3 kA 25 A Icc 30 kA 14 kA 6 kA 25 A...45 A Icc 18 kA 14 kA 6 kA -
Permissible ambient temperature: Climatic resistance: Current limitation at IK 30 kA: Total short-circuit breaking time: Mechanical endurance: Protection class: Isolator capability according to ICE 60947-3: Mounting position: Line connection: Wire size range: Screw tightening torque: Approvals:
max. 2.5 ms at IK 30 kA 20,000 switching cycles IP20 yes any Top/bottom 1...25 mm2
max. 2.5 ms at IK 30 kA 20,000 switching cycles IP20 yes any Top/bottom 1...25 mm2 2.5 Nm
2.5 Nm electrosuisse (SEV), VE, cUR, UR Lloyd's Register of Shipping RINA Registro Italiano Navale, DNV Det Norske Veritas, CCC, GOST EN 60898, IEC 60947-2, UL1077, CE-compliant
4) I 5) I 6) I
VE, cUR, UR, Lloyd's Register of Shipping, DNV Det Norske Veritas, CCC, GOST UL 1077, IEC 60947-2 CE compliant
Standards, regulations:
1) N: 3) I
2) NA:
for separating neutral conductor, see page 34 for switched neutral conductor, see page 34 cn: rated short-circuit breaking capacity
cs:
rated service short-circuit breaking capacity rated critical short-circuit breaking capacity cc: short-circuit current
cu:
8
10139/B
1.6...75 A -
1.6...63 A -
F500-C, -D: 10...63 A F500-K: 0.28...45 A 0.01/0.03/0.3 A Short delay version: 0.03 A G Selective version: 0.3 A S 230 VAC, 400 VAC, 500 VAC, 690 VAC 690 VAC see page 16
415 VAC
690 VAC
per pole 250 VDC/three poles in series max. 750 VDC + 20 % 1000 VDC 6 kV -
690 VAC 6 kV -
690 VAC 6 kV -
as S500-C, D or K
Icu 25 kA
Ics 12.5 kA
Icu 50 kA 30 kA 15 kA 6 kA
Ics 25 kA 22 kA 11 kA 3 kA
as S500-C, D or K
UL1077+CSA 30 kA 30 kA 30 kA 30 kA -
25 C + 55 C DIN 50016 max. 3 ms at IK 25 kA 20,000 switching cycles IP20 yes any Top/bottom 1...25 mm2
max. 2.5 ms at IK 30 kA 20,000 switching cycles IP20 yes any Top/bottom 1...25 mm2
max. 2.5 ms at IK 30 kA 10,000 switching cycles IP20 yes any Top/bottom 1...25 mm2 2.5 Nm -
2.5 Nm GOST
2.5 Nm -
9
10139/B
ms ms ms ms
C C mm2 mm mm g g
61009 61009 60947-2 Annex B 60947-2 Annex B AC A 63 63 2P, 3P, 4P 2P, 3P, 4P 230/ 400 230/ 400 690 690 440 440 195 195 dependent on rated breaking capacity of the MCB dependent on rated breaking capacity of the MCB 50 50 5 5 5060 5060 0.030.3 0.030.3 0.51 ln 0.51 ln 0.111.4 ln 0.111.4 ln < 220 < 220 < 80 < 80 < 40 < 40 < 40 < 40 10 ,000 10 ,000 20 ,000 20 ,000 IP4X IP4X (without terminal area) (without terminal area) IP2X IP2X 25+ 55 25+ 55 25+ 70 25+ 70 25 25 on DIN rails EN 50022 (35 mm) 44 44 79 79 250 250 325/ 390 325/ 390
50 5 5060 0.030.5 1 0.51 ln 0.111.4 ln 130500 60200 50150 40150 10 ,000 20 ,000 IP4X (without terminal area) IP2X 25+ 55 25+ 70 25 44 79 250 325/ 390
10
10139/B
General use:
Undervoltage trip UA
Rated voltages Un: Operating range: - dropout - pickup Power consumption (holding power): Wire size range: Screw tightening torque: Approvals: Standards, regulations: 3570 % Un 80 % Un max. 3.5 VA, 3.5 W 125 mm2 2.5 Nm electrosuisse (SEV), cUR, UR, CCC IEC 60947, UL1077, CE compliant For terminal designation, see page 34 24, 110, 230, 400 V AC 24, 110, 230, 400 V DC
Shunt trip AL
Rated voltages Un: Operating range: Power consumption: (transient pickup power; coil interrupted on trip) Wire size range: Screw tightening torque: Approvals: Standards, regulations: 24, 110, 230, 400 V AC/DC 50110 % Un max. 130 VA, 120 W
125 mm2 2.5 Nm electrosuisse (SEV), cUR, UR, CCC IEC 60947, UL1077, CE compliant For terminal designation, see page 34
control of electromagnetic load (higher than 72 VA) control of resistive and semiconductor loads in input circuits resistive 3-phase load
11
10139/B
Ri ( ) 0.0200 0.0100 0.0071 0.0050 0.0035 0.0030 0.0019 0.0017 0.0017 F500-D Ri ( ) 0.0042 0.0026 0.0022
Ri ( ) 0.018 0.018 0.009 0.009 0.009 0.0045 0.0018 0.0015 0.0014 0.0014 S500X-AG0084 Ri ( ) 0.95 0.50 0.195 0.090 0.045 0.012 0.0055 0.0017 0.0017
Adjustable version
Rated current In (A) 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 S500-K Ri ( ) 78 48 23.5 12.3 6.6 3.5 2.0 1.05 0.68 0.35 0.175 0.095 0.055 0.035 0.023 0.012 0.008 0.0055 0.0035 0.0025 0.0017 Power loss Pvmax (W) 1.76 2.12 2.12 2.17 2.22 2.24 2.42 2.36 3.00 3.15 3.09 3.20 3.52 4.24 5.18 4.80 5.41 5.63 4.79 4.20 3.44 S500UC-K Ri ( ) 84 51 25.5 12.8 7.0 3.6 2.04 1.08 0.68 0.35 0.175 0.095 0.055 0.035 0.023 0.012 0.008 0.005 0.0035 0.0025 0.0017 Power loss Pvmax (W) 1.89 2.25 2.30 2.26 2.35 2.30 2.47 2.43 3.00 3.15 3.09 3.20 3.52 4.24 5.18 4.80 5.41 5.12 4.79 4.20 3.44 Rated current In (A) 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45 F500-K Ri ( ) 12.4 6.7 3.6 2.1 1.1 0.73 0.3507 0.1757 0.0957 0.0557 0.0357 0.0237 0.0127 0.0087 0.0062 0.0042 0.0032 0.0024 Power loss Pv (W) 2.19 2.25 2.30 2.54 2.48 3.22 3.16 3.10 3.22 3.56 4.32 5.33 5.08 5.88 6.35 5.75 5.38 4.86
Weights
1-pole, with/without separating neutral conductor N/ switched neutral NA 2-pole, with/without separating neutral conductor N/ switched neutral NA
Type S501... S501N... S501NA... S502... S502N... S502NA... F502 S503... S503N... S503NA... F503 S504 F504 S500-H S500-S F504+T10 S500+UA S500+AL = = = = = = = 250 g 320 g 460 g 500 g 570 g 710 g 820 g
4-pole Auxiliary contact H Signal contact S RCD + RCD-trip signal contact T10 Undervoltage trip UA Shunt trip AL
= 1650 g
12
10139/B
Circuit breakers (MCCB's) upstream S500 Heavy Duty Circuit Breakers downstream
MCCB's The S500 Heavy Duty Circuit Breaker has a very good selectivity behaviour with respect to the upstream circuit breaker owing to its low let-through energy and rapid breaking. The following table shows the max. short-circuit currents at which the S500 Heavy Duty Circuit Breaker functions selectively with the upstream SACE circuit breaker.
S500
Upstream Version Trip Rated current (A) Electromagnetic trip (A) Downstream S500-B, S500-C, S500-D Icu [kA] 50 50 50 50 50 50 50 50 50 50 50 50 50 30 30 30 30 30 30 30 Rated current (A) 6 10 13 16 20 25 32 40 50 63 5.8 5.3..8 7.3..11 10..15 14..20 18..26 23..32 29..37 34..41 38..45
16
20
25
32
Tmax T1 B, C, N TM 160 40 50 63
80
100
125
160
Max. short-circuit (kA) 5.5 5.5 5.5 4.5 5.5 4.5 4.5 5.5 4.5 4.5 4.5 5.5 4.5 4.5 4.5 4.5 10.5 8 7.5 7.5 7.5 6 15 10 10 10 10 10 7.5 20 20 15 15 15 15 10 10 25 25 25 25 25 20 20 20 15 T T T T T T T T T T T T T T T T T T T T
S500-K
36 5.5
36 5.5
T 5.5 4.5
T T T 10 10 10 10 7.5
T T T 15 15 15 15 10 10
T T T T T T 20 20 20 15
Upstream Version Trip Rated current (A) Electromagnetic trip (A) Downstream S500-B, S500-C, S500-D Icu [kA] 50 50 50 50 50 50 50 50 50 50 50 50 50 30 30 30 30 30 30 30 Rated current (A) 6 10 13 16 20 25 32 40 50 63 5.8 5.3..8 7.3..11 10..15 14..20 18..26 23..32 29..37 34..41 38..45
12.5
16
20
25
32
40
50
Max. short-circuit (kA) 4.5 5.5 5.5 4.5 4.5 5.5 4.5 5.5 4.5 4.5 4.5 4.5 5.5 4.5 4.5 4.5 5.5 4.5 4.5 4.5 4.5 4.5 4.5 10.5 8 7.5 7.5 7.5 6 15 10 10 10 10 10 7.5 5 5 20 20 15 15 15 15 10 10 7.5 5 36 36 36 15 15 15 15 10 10 7.5 25 25 25 25 25 20 20 20 15 36 36 36 36 36 36 36 36 36 36 50 50 50 T T T T T T T 50 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 36 50 50 50 T T T T T T T
S500-K
36 4.5
36 5.5
36 5.5 4.5
36 36 36 10 10 10 10 7.5 5 5
36 36 36 T T T 20 20 20 15
50 50 50 T
50 50 50 T T T T
50 50 50 T T T T T T T
13
10139/B
Upstream Version Trip Rated current (A) Electromagnetic trip (A) downstream S500-B, S500-C, S500-D Icu [kA] 50 50 50 50 50 50 50 50 50 50 50 50 50 30 30 30 30 30 30 30 Rated current (A) 6 10 13 16 20 25 32 40 50 63 5.8 5.3..8 7.3..11 10..15 14..20 18..26 23..32 29..37 34..41 38..45
63
80
200
250
Max. short-circuit (kA) 10.5 8 7.5 7.5 7.5 6 15 10 10 10 10 10 7.5 20 20 15 15 15 15 10 10 7.5 5 36 36 36 15 15 15 15 10 10 7.5 25 25 25 25 25 20 20 20 15 6 36 36 36 T T T 20 20 20 15 36 36 36 36 36 36 36 36 36 36 T T T T T T T T T T 36 36 36 36 36 36 36 36 36 36 T T T T T T T T T T 36 36 36 36 36 36 36 36 36 36 T T T T T T T T T T
S500-K
36 36 36 10 10 10 10 7.5
S500-K
9 50 50 6 20 50 1.3 13 23 1.1 6 10 0.82 1.05 1.2 0.6 1 1.1 0.9 1.05 0.7 1 0.96 0.7 -
14
10139/B
S500
Should a short-circuit occur, selective break action will be performed by the MCB up to the selectivity current values listed in the following table.
MCBS
upstream Rated current (A) downstream B6 / C6 B10 / C10 B13 / C13 B16 / C16 B20 / C20 B25 / C25 B32 / C32 B40 / C40 B50 / C50 Rated current (A) 6 10 13 16 20 25 32 40 50
S500-C, D C40
D40
C50
D50
C63
D63
Max. short-circuit current (kA) 0.6 0.55 0.55 0.55 0.5 0.45 1.2 1.1 1.1 1.1 1 0.9 0.9 0.8 0.7 0.7 0.7 0.6 0.55 0.55 1.4 1.3 1.3 1.3 1.2 1.1 1.1 0.95 0.85 0.85 0.85 0.8 0.75 0.7 0.7 0.7 1.8 1.7 1.7 1.7 1.55 1.4 1.4 1.4 1.4
15
10139/B
Heavy Duty Circuit Breakers S500 Back-up protection 230 V/400 VAC
S500 Heavy Duty Circuit Breakers without back-up protection
If the short circuit current in the 3 x 230/400 V network at the point of installation does not exceed 50/30 kA, then the S500 Heavy Duty Circuit Breaker may be installed with or without an upstream circuit breaker or backup fuse of any size. This condition is met if the power available to supply the transformer is not greater than 2,000/1,250 kVA or if in the case of a larger transformer the cable between the transformer and the S500 Heavy Duty Circuit Breaker has a minimum length as listed in the table below.
Transformer capacity (3 x 400 VAC) (m) 1,600 kVA 2,000 kVA 33 28 25 22 19 15 11 8 6 4 2.3 1.5 1 0.6 0.4 2,500 kVA 40 35 31 27 23 18 13 9.5 7 4.5 2.9 1.8 1.2 0.8 0.5 2,500 kVA 72 62 53 44 36 27 20 14 10 6.5 4.1 2.5 1.7 1 0.6
S500 Heavy Duty Circuit Breaker upstream Miniature circuit breaker (MCBs) downstream
Due to its high breaking capacity, the short-circuit current seldom exceeds the capacity of the S500 circuit breaker, and thus it can be used in the majority of cases either with no upstream protection, with an upstream circuit breaker or with an upstream backup fuse of any size. Where in doubt, the short-circuit current, which could possibly occur at the location of the S500 circuit breaker, needs to be determined. If the short-circuit current at the point of installation of the circuit breaker is greater than its breaking capacity, the rated currents of the upstream S500 circuit breaker must not exceed the values in the table (back-up protection for circuit breaker)
S500
MCBs
upstream Rated current (A) downstream B6 / C6 B10 / C10 B13 / C13 B16 / C16 B20 / C20 B25 / C25 B32 / C32 B40 / C40 B50 / C50 Rated current (A) 6 10 13 16 20 25 32 40 50
S500-C, D C40
D40
C50
D50
C63
D63
16
10139/B
Heavy Duty Circuit Breakers S500 Circuit protection S500-B, S500-C, S500-D
General
S500 Heavy Duty Circuit Breakers are current and energy limiting devices with high breaking capacities. They are suitable for domestic installations with no or only very small inrush currents and for commercial and industrial applications with high inrush currents (fluorescent lights, transformers and capacitor banks). The high rated breaking capacity of 50 kA at 400 VAC and rapid breaking time 2 ms ensure an excellent selectivity behaviour with respect to upstream overcurrent devices.
Major features
High rated breaking capacity of 50 kA at 230/400 VAC according to IEC 60947-2 Outstanding current and energy limiting Clear contact position indication for all poles Back-up protection for downstream circuit breakers (MCBs) Wide range of accessories such as undervoltage and shunt trip devices, auxiliary and signal contacts
Order data
Circuit protection Characteristic
Rated current (A) 6 10 13 16 20 25 32 40 50 63
B
Type 1-pole S501-B6 S501-B10 S501-B13 S501-B16 S501-B20 S501-B25 S501-B32 S501-B40 S501-B50 S501-B63 Module Type (25 mm) 2-pole 1 1 1 1 1 1 1 1 1 1 S502-B6 S502-B10 S502-B13 S502-B16 S502-B20 S502-B25 S502-B32 S502-B40 S502-B50 S502-B63 Module Type (25 mm) 3-pole 2 2 2 2 2 2 2 2 2 2 S503-B6 S503-B10 S503-B13 S503-B16 S503-B20 S503-B25 S503-B32 S503-B40 S503-B50 S503-B63 Module Type (25 mm) 4-pole 3 3 3 3 3 3 3 3 3 3 S504-B6 S504-B10 S504-B13 S504-B16 S504-B20 S504-B25 S504-B32 S504-B40 S504-B50 S504-B63 Module (25 mm) 4 4 4 4 4 4 4 4 4 4
40037
Characteristic
6 10 13 16 20 25 32 40 50 63
40101
C
S501-C6 S501-C10 S501-C13 S501-C16 S501-C20 S501-C25 S501-C32 S501-C40 S501-C50 S501-C63 1 1 1 1 1 1 1 1 1 1 S502-C6 S502-C10 S502-C13 S502-C16 S502-C20 S502-C25 S502-C32 S502-C40 S502-C50 S502-C63 2 2 2 2 2 2 2 2 2 2 S503-C6 S503-C10 S503-C13 S503-C16 S503-C20 S503-C25 S503-C32 S503-C40 S503-C50 S503-C63 3 3 3 3 3 3 3 3 3 3 S504-C6 S504-C10 S504-C13 S504-C16 S504-C20 S504-C25 S504-C32 S504-C40 S504-C50 S504-C63 4 4 4 4 4 4 4 4 4 4
Characteristic
10 13 16 20 25 32 40 50 63
40038
D
S501-D10 S501-D13 S501-D16 S501-D20 S501-D25 S501-D32 S501-D40 S501-D50 S501-D63 1 1 1 1 1 1 1 1 1 S502-D10 S502-D13 S502-D16 S502-D20 S502-D25 S502-D32 S502-D40 S502-D50 S502-D63 2 2 2 2 2 2 2 2 2 S503-D10 S503-D13 S503-D16 S503-D20 S503-D25 S503-D32 S503-D40 S503-D50 S503-D63 3 3 3 3 3 3 3 3 3 S504-D10 S504-D13 S504-D16 S504-D20 S504-D25 S504-D32 S504-D40 S504-D50 S504-D63 4 4 4 4 4 4 4 4 4
Module
17
10139/B
Major features
High rated operating voltage up to 400/690 VAC All poles disconnected in event of a fault Ready for reclosing immediately after a fault No need for thermal trip on contactor Space saving and economical Optimum coordination with A-contactors Wide range of accessories, including undervoltage and shunt trips, auxiliary and signal contacts
+
Contactor
S503-K
Contactor contact
Z100055.eps
Motor
Operational switching The S500-K Heavy Duty Circuit Breaker may be used up to a current rating of 11 A for direct operational switching of motors. Starting conditions The motor starting time should not be longer than 2.5 seconds to avoid nuisance tripping, which occurs when a motor is started repeatedly in quick succession.
Order data
Motor protection Characteristic
Range of adjustment (A) 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45
K
Type 1-pole S501-K-0.15 S501-K0.21 S501-K0.3 S501-K0.42 S501-K0.58 S501-K0.8 S501-K1.1 S501-K1.5 S501-K2.1 S501-K3 S501-K4.2 S501-K5.8 S501-K8 S501-K11 S501-K15 S501-K20 S501-K26 S501-K32 S501-K37 S501-K41 S501-K45 Module (25 mm) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Type 2-pole S502-K-0.15 S502-K0.21 S502-K0.3 S502-K0.42 S502-K0.58 S502-K0.8 S502-K1.1 S502-K1.5 S502-K2.1 S502-K3 S502-K4.2 S502-K5.8 S502-K8 S502-K11 S502-K15 S502-K20 S502-K26 S502-K32 S502-K37 S502-K41 S502-K45 Module (25 mm) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Type 3-pole S503-K0.15 S503-K0.21 S503-K0.3 S503-K0.42 S503-K0.58 S503-K0.8 S503-K1.1 S503-K1.5 S503-K2.1 S503-K3 S503-K4.2 S503-K5.8 S503-K8 S503-K11 S503-K15 S503-K20 S503-K26 S503-K32 S503-K37 S503-K41 S503-K45 Module (25 mm) 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
40040
Module
18
10139/B
I max. (A) 0.58 0.8 1.1 1.5 2.1 2.1 3 4.2 5.8 5.8 8 11 15 20 26 32 37 45
19
10139/B
Heavy Duty Circuit Breakers S500 Motor protection with separate overload protection: S503-KM
General
The S503-KM Heavy Duty Circuit Breaker provides short-circuit protection for motors, power supplies, provides a combination of contactor and thermal overload relay functions, and protects system installation and non-fused motor control centres (MCC). The S5503-KM possesses only an electromagnetic tripping function. The conductor cross-sections can be dimensioned to suit the max. rated current of the downstream thermal overload relay. In combination with a separate overload protection, the S503-KM provides protection against difficult external starting. Since the thermal overload relay trips on overload and the circuit breaker on short-circuit, the cause of the trip is apparent. The high rated breaking capacity of 50 kA at 400 VAC based on coordination according to IEC 60947-4-1 as well as the short tripping time of < 2 ms ensure excellent protection and an optimum economical solution.
Major features
High rated operating voltage up to 400 VAC Special electromagnetic trip For motors up to a capacity of 30 kW Clear contact position indication for all poles Optimum coordination with A-contactors Space saving and economical Designed for the standard ABB rotary drive (tilting motion to rotary motion) Wide range of accessories
+
Contactor + Overload protection (Thermal overload relay)
S503-KM
Contactor contact
Motor
Operational switching The S503-KM circuit breaker may be used up to a current rating of 9 A for direct, operational switching of motors.
Order data
Motor protection Characteristic
Rated current (A) 1.6 2.5 4 6 9 20 32 52 63 Module
KM
Magnetic (A) ( 10 %) 16 25 45 55 100 200 400 580 800 Rated breaking trip capacity (kA) 25 25 25 25 25 25 25 25 25 type 3-pole S503-KM1.6 S503-KM2.5 S503-KM4 S503-KM6 S503-KM9 S503-KM20 S503-KM32 S503-KM52 S503-KM63 Module (25 mm) 3 3 3 3 3 3 3 3 3
40052
20
10139/B
Z100056.eps
Heavy Duty Circuit Breakers S500 Motor protection with separate overload protection: S503-KM
Coordination table for S503-KM motor starter according to IEC 60947-4-1, type 2, for 415 VAC, 50 kA with A-contactor and thermal overload relay
Combination starter The data in the table below are applicable if the protective device and the starter are fitted in the same compartment or enclosure, or when supplied in separate parts and assembled by the installation technician. S503-KM Contactor contact Overcurrent relay Cable a
M
Motor Rated output Pe (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 1.65 2.2 3 4 5.5 7.5 11 11 15 18.5 22 Heavy Duty Circuit Breaker Type Range of adjustment In (A) S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM1.6 S503-KM2.5 S503-KM2.5 S503-KM4.0 S503-KM6.0 S503-KM6.0 S503-KM6.0 S503-KM9.0 S503-KM20 S503-KM20 S503-KM20 S503-KM32 S503-KM32 S503-KM32 S503-KM52 S503-KM63 1.6 1.6 1.6 1.6 2.5 2.5 4.0 6.0 6.0 6.0 9.0 20.0 20.0 20.0 32.0 32.0 32.0 52.0 63.0 Contactor Magnetic Type trip ( 10 %) Im (A) 16 16 16 16 25 25 45 55 55 55 100 200 200 200 400 400 400 580 800 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A12-30-10 A12-30-10 16-30-10 A16-30-10 A16-30-10 A26-30-10 A26-30-10 A26-30-10 A26-30-10 A26-30-10 A30-30-10 A40-30-10 A50-30-00 Thermal overload relay Type Range of adjustment In (A) TA 25 DU 0.63 TA 25 DU 1.00 TA 25 DU 1.00 TA 25 DU 1.40 TA 25 DU 1.80 TA 25 DU 2.40 TA 25 DU 3.10 TA 25 DU 4.00 TA 25 DU 5.00 TA 25 DU 6.50 TA 25 DU 8.50 TA 25 DU 11.0 TA 25 DU 14.0 TA 25 DU 19.0 TA 25 DU 25.0 TA 25 DU 25.0 TA 25 DU 32.0 TA 75 DU 42.0 TA 75 DU 52.0 0.400.63 0.631.00 0.631.00 1.001.40 1.301.80 1.702.40 2.203.10 2.804.00 3.505.00 4.506.50 6.008.50 7.5011.0 10.014.0 13.019.0 16.025.0 18.025.0 24.032.0 29.042.0 36.052.0 Cable Crosssection (mm2) 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 4 6 6 10
Starter group
Rated current ln (A) 0.44 0.72 0.83 1.12 1.45 1.9 2.59 3.45 4.4 4.8 6.48 8.6 11.1 14.8 21.5 21.5 28.5 35 41
I max. (A) 0.63 1.0 1 1.4 1.8 2.4 3.1 4 5 6.5 8.5 11 14 19 25 25 62 42 52
Maximum cable lengths for protection against indirect contact (earth leakage current) to IEC 364-4-41
Association An association is present when the short-circuit device (S503-KM) and the starter are fitted separately and connected by cable (see illustration). In this case, the rated breaking capacity of the shortcircuit protection device must correspond at least with the short-circuit current occurring at the point of installation. For cable b, the maximum permissible cable lengths according to the table below must be taken into account. S503-KM Cable b Contactor contact Overcurrent relay
M Cable a
Maximum permissible cable lengths and cross-sections 2.50 mm2 4.00 mm2 6.00 mm2 1.50 mm2 L (m) L (m) L (m) L (m) 1,120 700 400 325 180 90 1,850 1,200 660 540 300 150 75 1,050 870 480 240 120 1,300 720 360 180 120 90
Z100062.eps
Heavy Duty Circuit Breaker Type Rated current ln (A) S503-KM1.6 S503-KM2.5 S503-KM4 S503-KM6 S503-KM9 S503-KM20 S503-KM32 S503-KM52 S503-KM63 1.6 2.5 4 6 9 20 32 52 63
If the line is longer than the specified length and a short-circuit to earth occurs, the magnetic trip no longer trips. On request Coordination tables S500 with A-contactors, No. 10107/B
21
10139/B
Z100061.eps
Heavy Duty Circuit Breakers S500 Motor protection with separate overload protection: S503X-AG0084
General
The S503X-AG0084 was developed as an alternative to the S503-KM. This high rated breaking capacity of 50 kA at 400 VAC simplifies application in installations with high short-circuit currents, for example, in substation distribution systems, the paper industry, etc. Additional overload protection is necessary for all applications. This can be a thermal overload relay or an electronic overload protection. Since the thermal overload relay trips on overload and the circuit breaker on short-circuit, the cause of the trip is apparent. The short-circuit is indicated via a signal contact in the S503X-AG0084. A motor overload is detected by the overload protection. The contactor provides operational switching of the motor.
Major features
High rated operating voltage up to 690 VAC High rated breaking capacity of 65 kA at 400 VAC according to coordination type 2, page 23, per IEC 60947-4-1, with thermal overload relay High rated breaking capacity of 50 kA to 400 VAC per IEC 60947-4-1, with electronic overload protection, electronic INSUM Optimum coordination with A-contactors Compact and economical design Clear contact position indication for all poles Designed for the standard ABB rotary drive (tilting motion to rotary motion) Wide range of accessories
S503X-AG0084
Motor
Operational switching The S503X-AG0084 circuit breaker may be used up to a current rating of 9 A for a direct, operational switching of motors.
Order data*
Motor protection Characteristic
Rated current (A) 1.6 2.5 4 6 9 20 32 52 63 Module
AG0084
Magnetic trip (A) ( 10 %) 22 34 55 83 124 275 440 715 866 Rated breaking capacity (kA) 50 50 50 50 50 50 50 50 50 type 3-pole S503X-AG0084 1.6 S503X-AG0084 2.5 S503X-AG0084 4 S503X-AG0084 6 S503X-AG0084 9 S503X-AG0084 20 S503X-AG0084 32 S503X-AG0084 52 S503X-AG0084 63 Module (25 mm) 3 3 3 3 3 3 3 3 3
40054
22
10139/B
Heavy Duty Circuit Breakers S500 Motor protection with separate overload protection: S503X-AG0084
Coordination table motor starter S503X-AG0084 according to IEC 60947-4-1, type 2, for 415 VAC, 65 kA with A-contactor and thermal overload relay
Combination starter The data in the table below are applicable if the protective device and the starter are fitted in the same compartment or enclosure, or when supplied in separate parts and assembled by the installation technician. S503X-AG0084 Contactor contact Overcurrent relay Cable a
M
Motor Rated output Pe (kW) 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 1.85 2.2 3 4 5.5 7.5 11 11 15 18.5 22 Rated current ln (A) 0.44 0.72 0.83 1.12 1.45 1.9 2.59 3.45 4.4 4.8 6.48 8.6 11.1 14.8 21.5 21.5 28.5 35 41 Heavy duty circuit breaker Type Contactor Range of Magnetic Type adjustment trip In (A) ( 10 %) Im (A) 1.6 1.6 1.6 1.6 2.5 2.5 4.0 6.0 6.0 6.0 9.0 20.0 20.0 20.0 32.0 32.0 32.0 52.0 63.0 22 22 22 22 34 34 55 83 83 83 124 275 275 275 440 440 440 715 866 A9-30-10 A9-30-10 A9-30-10 A9-30-10 A3 30 -10 A9-30-10 A9-30-10 A9-30-10 A12-30-10 A12-30-10 A12-30-10 A16-30-10 A16-30-10 A26-30-10 A20-30-10 A26-30-10 A30-30-10 A40-30-10 A50-30-00 Thermal overload relay Safety clearance (mm) 20 20 20 20 20 20 20 20 20 20 20 35 35 35 85 35 35 35 35 Type Cable Range of Crossadjustment section In (A) (mm2) 0.400.63 0.631.00 0.631.00 1.001.40 1.301.80 1.702.40 2.203.10 2.804.00 3.505.00 4.506.50 6.008.50 7.5011.0 10.014.0 13.019.0 18.025.0 18.025.0 24.032.0 29.042.0 36.052.0 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 4 6 6 10
Starter group
I max. (A) 0.63 1.0 1 1.4 1.8 2.4 3.1 4 5 6.5 8.5 11 14 19 25 25 32 42 52
S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084
TA 25 DU 0.63 TA 25 DU 1.00 TA 25 DU 1.00 TA 25 DU 1.40 TA 25 DU 1.80 TA 25 DU 2.40 TA 25 DU 3.10 TA 25 DU 4.00 TA 25 DU 5.00 TA 25 DU 6.50 TA 25 DU 8.50 TA 25 DU 11.0 TA 25 DU 14.0 TA 25 DU 19.0 TA 25 DU 25.0 TA 25 DU 25.0 TA 25 DU 32.0 TA 75 DU 42.0 TA 75 DU 52.0
Maximum cable lengths for protection against indirect contact (earth leakage current) to IEC 364-4-41
Association An association is present when the short-circuit device (S503X-AG0084) and the starter are fitted separately and connected by cable (see illustration). In this case, the rated breaking capacity of the shortcircuit protection device must correspond at least with the short-circuit current occurring at the point of installation. For cable b, the maximum permissible cable lengths according to the table below must be taken into account. S503X-AG0084 Cable b Contactor contact Overcurrent relay
M Cable a
Maximum permissible cable lengths and cross-sections 1.50 mm2 2.50 mm2 4.00 mm2 6.00 mm2 L (m) L (m) L (m) L (m) 815 525 325 215 145 65 1,360 880 540 360 240 110 70 870 575 385 175 110 865 580 260 160 100 80
Z100062.eps
Heavy Duty Circuit Breaker Type Rated current ln (A) S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 S503X-AG0084 1.6 2.5 4 6 9 20 32 52 63 1.6 2.5 4 6 9 20 32 52 63
If the line is longer than the specified length and a short-circuit to earth occurs, the magnetic trip no longer trips. On request Coordination tables S500 with A-contactors, No. 10107/B
23
10139/B
Z100061.eps
Major features
High rated operating voltage up to 750 VDC High rated breaking capacity 30 kA (250 VDC, 500 VDC, 750 VDC) Independent polarity connection Fixed and adjustable versions Compact dimensions, DIN cap size Clear contact position indication for all poles Wide range of accessories
Order data
DC circuit protection Characteristic
Rated Current (A) 6 10 13 16 20 25 32 40 50 63
B
Type 1-pole S501UC-B6 S501UC-B10 S501UC-B13 S501UC-B16 S501UC-B20 S501UC-B25 S501UC-B32 S501UC-B40 S501UC-B50 S501UC-B63 Module (25 mm) 1 1 1 1 1 1 1 1 1 1 Type 2-pole S502UC-B6 S502UC-B10 S502UC-B13 S502UC-B16 S502UC-B20 S502UC-B25 S502UC-B32 S502UC-B40 S502UC-B50 S502UC-B63 Module (25 mm) 2 2 2 2 2 2 2 2 2 2 Type 3-pole S503UC-B6 S503UC-B10 S503UC-B13 S503UC-B16 S503UC-B20 S503UC-B25 S503UC-B32 S503UC-B40 S503UC-B50 S503UC-B63 Module (25 mm) 3 3 3 3 3 3 3 3 3 3 Type 4-pole S504UC-B6 S504UC-B10 S504UC-B13 S504UC-B16 S504UC-B20 S504UC-B25 S504UC-B32 S504UC-B40 S504UC-B50 S504UC-B63 Module (25 mm) 4 4 4 4 4 4 4 4 4 4
40042
Characteristic
Range of adjustment (A) 0.1 0.14 0.2 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 14 18 23 29 34 38 0.15 0.21 0.3 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 20 26 32 37 41 45
K
Type 1-pole S501UC-K0.15 S501UC-K0.21 S501UC-K0.3 S501UC-K0.42 S501UC-K0.58 S501UC-K0.8 S501UC-K1.1 S501UC-K1.5 S501UC-K2.1 S501UC-K3 S501UC-K4.2 S501UC-K5.8 S501UC-K8 S501UC-K11 S501UC-K15 S501UC-K20 S501UC-K26 S501UC-K32 S501UC-K37 S501UC-K41 S501UC-K45 Module (25mm) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Type 2-pole S502UC-K0.15 S502UC-K0.21 S502UC-K0.3 S502UC-K0.42 S502UC-K0.58 S502UC-K0.8 S502UC-K1.1 S502UC-K1.5 S502UC-K2.1 S502UC-K3 S502UC-K4.2 S502UC-K5.8 S502UC-K8 S502UC-K11 S502UC-K15 S502UC-K20 S502UC-K26 S502UC-K32 S502UC-K37 S502UC-K41 S502UC-K45 Module (25mm) 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Type 3-pole S503UC-K0.15 S503UC-K0.21 S503UC-K0.3 S503UC-K0.42 S503UC-K0.58 S503UC-K0.8 S503UC-K1.1 S503UC-K1.5 S503UC-K2.1 S503UC-K3 S503UC-K4.2 S503UC-K5.8 S503UC-K8 S503UC-K11 S503UC-K15 S503UC-K20 S503UC-K26 S503UC-K32 S503UC-K37 S503UC-K41 S503UC-K45 Module (25 mm) 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Type 4-pole S504UC-K0.15 S504UC-K0.21 S504UC-K0.3 S504UC-K0.42 S504UC-K0.58 S504UC-K0.8 S504UC-K1.1 S504UC-K1.5 S504UC-K2.1 S504UC-K3 S504UC-K4.2 S504UC-K5.8 S504UC-K8 S504UC-K11 S504UC-K15 S504UC-K20 S504UC-K26 S504UC-K32 S504UC-K37 S504UC-K41 S504UC-K45 Module (25mm) 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
40041
Module
Connection diagrams
Earthed network
1 Pol 250 V DC 1 2
2 Pole 500 V DC 1 2 3 4
3 Pole
IT 750 V DC
1 2
3 4
5 6
Load
Load
Load
Unearthed network
2 Pole 500 V DC 1 2 3 4 1 2
4 Pole 750 V DC 3 4 5 6 7 8
Z100040.eps
Load
Load
25
10139/B
Heavy Duty Circuit Breakers S500 Customer-fitted RCD protection with overload protection: DDA
General
The DDA500 residual current protection family is a residual current circuit breaker that can be fitted by the customer and mounted on the S500 Heavy Duty Circuit Breaker. The DDA500 can be employed for sinusoidal AC residual currents as well as for impulse residual currents in DC circuits. Depending on the requirements, the DDA500 system can be classified into 2 categories. DDA560 and DDA 570 The DDA 560 is suitable for applications with sinusoidal AC residual currents (type AC) The DDA 570 is suitable for applications with impulse residual currents in DC circuits (type A) DDA590 The DDA 590 is suitable for applications with impulse residual currents in DC circuits (type A) and operates selectively with respect to downstream, sensitive residual current circuit breakers
40983
Major features
40984
The DDA500 can be fitted by the customer to the S500 Heavy Duty Circuit Breakers Large range of residual currents at 30 mA, 300 mA, 500 mA, 1,000 mA (The S500-B6, S500-C6, S500-D6 and the S500-K series are excluded)
Order data
RCD protection with overload protection Sensitivity DDA560
Rated trip current I n
40985
AC
Rated current (A) 63 63 Type 2-pole 5060 Hz) EY8302 EY8310 Type 3-pole 5060 Hz) EY8328 EY8336 Type 4-pole 5060 Hz) EY8344 EY8351
30 mA 300 mA
Sensitivity DDA570
30 mA 300 mA
A
63 63 EY8369 EY8377 EY8385 EY8393 EY8401 EY8419
Sensitivity DDA590
300 mA 500 mA 1000 mA
A (selective)
63 63 63 EY8427 EY8435 EY8443
26
10139/B
Heavy Duty Circuit Breakers S500 RCD protection with circuit protection F500-C, F500-D
General
The Heavy Duty Circuit Breaker type F500 is suitable as a miniature circuit breaker in all types of applications. Furthermore the F500 is equipped with a residual current trip. The residual current trip is effective with sinusoidal AC and pulsating DC residual currents (type A, according to EN 61009-1). The F500 Heavy Duty Circuit Breaker ensures powerful protection in high power networks against: direct contact with an energised conductor dangerous residual currents from excessive shock hazard voltages by physical contact (protection from indirect contact with an operating circuit) electrical burns from partial earth contact overload and short circuit
Major features
High rated operating voltage up to 400/690 VAC High rated breaking capacity of 50 kA at 230/400 VAC Clear contact position indication for all poles Back-up protection of downstream miniature circuit breakers (MCBs) Wide range of accessories
2-pole
Order data
RCD protection with circuit protection Characteristic
Rated trip current I n
40459
C
Type 2-pole (L+NA, 230 VAC, PE 4560 Hz) (25 mm) F502-C10/0.01 F502-C13/0.01 F502-C16/0.01 F502-C20/0.01 F502-C25/0.01 F502-C10/0.03 F502-C13/0.03 F502-C16/0.03 F502-C20/0.03 F502-C25/0.03 F502-C40/0.03 F502-C50/0.03 F502-C63/0.03 F502-C10/0.3 F502-C13/0.3 F502-C16/0.3 F502-C20/0.3 F502-C25/0.3 F502-C40/0.3 F502-C50/0.3 F502-C63/0.3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 Type 3-pole (3L, 400 VAC, 4560 Hz) F503-C10/0.01 F503-C13/0.01 F503-C16/0.01 PE (25 mm) 4 4 4 Type 4-pole (3L+NA, 230/400 VAC, PE 4560 Hz) (25 mm) F504-C10/0.01 F504-C13/0.01 F504-C16/0.01 5 5 5
10 mA
3-pole
30 mA
F503-C10/0.03 F503-C13/0.03 F503-C16/0.03 F503-C20/0.03 F503-C25/0.03 F503-C40/0.03 F503-C50/0.03 F503-C63/0.03 F503-C10/0.3 F503-C13/0.3 F503-C16/0.3 F503-C20/0.3 F503-C25/0.3 F503-C40/0.3 F503-C50/0.3 F503-C63/0.3
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
F504-C10/0.03 F504-C13/0.03 F504-C16/0.03 F504-C20/0.03 F504-C25/0.03 F504-C40/0.03 F504-C50/0.03 F504-C63/0.03 F504-C10/0.3 F504-C13/0.3 F504-C16/0.3 F504-C20/0.3 F504-C25/0.3 F504-C40/0.3 F504-C50/0.3 F504-C63/0.3
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
300 mA
40704
Characteristic
4-pole 30 mA 25 40 63 25 40 63
D
F502-D25/0.03 F502-D40/0.03 F502-D63/0.03 F502-D25/0.3 F502-D40/0.3 F502-D63/0.3 3 3 3 3 3 3 F503-D25/0.03 F503-D40/0.03 F503-D63/0.03 F503-D25/0.3 F503-D40/0.3 F503-D63/0.3 4 4 4 4 4 4 F504-D25/0.03 F504-D40/0.03 F504-D63/0.03 F504-D25/0.3 F504-D40/0.3 F504-D63/0.3 5 5 5 5 5 5
300 mA
40461
On request Rated operating voltages: Rated residual current IDn: Rated frequencies:
Module
110 VAC, 500 VAC, (10 mA, 30 mA types) 110 VAC, 500 VAC, 690 VAC (300 mA types) 500 mA, 1,000 mA (only type AC for 1,000 mA) 16 2/3 Hz, 400 Hz
27
10139/B
Heavy Duty Circuit Breakers S500 Short-delay RCD protection with circuit protection: F500K0.03 G Selective residual current protection with circuit protection: F500S0.3 S
General
The F500K0.03 G short-delay residual current circuit breaker differs from the F500S0.3 S selective residual current protection by its significantly shorter delay times. The F500K0.03 G should therefore be used to avoid undesired tripping, while the F500S0.3 S ensures selectivity with respect to downstream, more sensitive RCD circuit breakers.
40459
Long line capacitance Large number of fluorescent lamps (particularly when using electronic ballast units) Electronic equipment and components (PC terminals, PLCs, voltage converters etc.) Transient network overvoltages
Major features
High rated operating voltage up to 400/690 VAC High rated breaking capacity of 50 kA at 230/400 VAC RCD pulsating DC sensitivity (type A, according to EN 61009-1) RCD short-delay G and selective S types
300 mA s
Technical Data
EN 61009 Impulse current withstand Standard according to regulation: - with I n - with 5 I n Total breaking time (mean value) - with I n - with 5 IDn Time delay for 5 I n F500 (Standard) 250 A, 8/20 s 300 ms 40 ms 40 ms 25 ms F500K0.03 G 3 kA, 8/20 s 10300 ms 10 40 ms 240 ms 35 ms 10 ms F500S0.3 S 5 kA, 8/20 s 130500 ms 50150 ms 300 ms 115 ms 90 ms
28
10139/B
Z20106.eps
30 mA 10 mA
Heavy Duty Circuit Breakers S500 Short-delay RCD protection with circuit protection: F500K0.03 G Selective residual current protection with overload protection: F500S0.3 S
Order data
2-pole
C
Type G 2-pole (L+NA, 230 VAC, 4560 Hz) F502K-C16/0.03 F502K-C25/0.03 F502K-C40/0.03 F502K-C63/0.03 Module (25 mm) 3 3 3 3 Type G 3-pole (3L, 400 VAC, 4560 Hz) F503K-C16/0.03 F503K-C25/0.03 F503K-C40/0.03 F503K-C63/0.03 Module (25 mm) 4 4 4 4 Type G 4-pole (3L+NA, 230/400 VAC, 4560 Hz) F504K-C16/0.03 F504K-C25/0.03 F504K-C40/0.03 F504K-C63/0.03 Module (25 mm) 5 5 5 5
Rated current
(A) 16 25 40 63
30 mA
Characteristic
30 mA 16 25 40 63
D
F502K-D16/0.03 F502K-D25/0.03 F502K-D40/0.03 F502K-D63/0.03 3 3 3 3 F503K-D16/0.03 F503K-D25/0.03 F503K-D40/0.03 F503K-D63/0.03 4 4 4 4 F504K-D16/0.03 F504K-D25/0.03 F504K-D40/0.03 F504K-D63/0.03 5 5 5 5
3-pole
Order data
Selective residual current circuit breaker with overload protection
Rated tripping current I
n
40704
Rated current
(A)
Characteristic
4-pole 300 mA 16 25 40 63
C
F502S-C16/0.3 F502S-C25/0.3 F502S-C40/0.3 F502S-C63/0.3 3 3 3 3 F503S-C16/0.3 F503S-C25/0.3 F503S-C40/0.3 F503S-C63/0.3 4 4 4 4 F504S-C16/0.3 F504S-C25/0.3 F504S-C40/0.3 F504S-C63/0.3 5 5 5 5
Characteristic
300 mA
40461
D
F502S-D16/0.3 F502S-D25/0.3 F502S-D40/0.3 F502S-D63/0.3 3 3 3 3 F503S-D16/0.3 F503S-D25/0.3 F503S-D40/0.3 F503S-D63/0.3 4 4 4 4 F504S-D16/0.3 F504S-D25/0.3 F504S-D40/0.3 F504S-D63/0.3 5 5 5 5
16 25 40 63
110 VAC, 500 VAC, (30 mA types) 110 VAC, 500 VAC, 690 VAC (300 mA types) 1000 mA S
29
10139/B
Heavy Duty Circuit Breakers S500 RCD protection with motor protection F500-K
General
The F500-K circuit breaker is an overcurrent breaker with motor protection characteristic. The residual current Trip is effective with sinusoidal AC and pulsating DC residual currents (type A, according to EN 61009-1). The F500 Heavy Duty Circuit Breaker ensures powerful protection in high power networks against: dangerous residual currents from excessive shock hazard voltages by physical contact overheating of electrical operating equipment (motors) by overcurrent overload and short circuit
Major features
High rated operating voltage up to 690 VAC All poles disconnected in event of a fault No need for thermal trip on contactor The cable cross-sections from F500-K to the motor can be dimensioned for the rated current set on the S500-K Short-delay RCD protection switch 30 mA G types for special applications, such as frequency converter, soft-start, etc.
40460
Contactor contact
Z100058.eps
Motor
Motor
Operational switching The F500-K Heavy Duty Circuit Breaker may be used up to a current rating of 11 A for direct, operational switching of motors. Starting conditions The motor starting time should not be longer than 2.5 seconds to avoid nuisance tripping, which occurs when a motor is started repeatedly in quick succession.
30
10139/B
Heavy Duty Circuit Breakers S500 RCD protection with motor protection F500-K
Order data
3-pole
K
Range of adjustment (A) 0.28 0.38 0.53 0.73 1 1.4 2 2.8 3.8 5.3 7.3 10 0.42 0.58 0.8 1.1 1.5 2.1 3 4.2 5.8 8 11 15 Type 3-pole (3L, 400 VAC, 4560 Hz) F503-K0.42/0.01 F503-K0.58/0.01 F503-K0.8/0.01 F503-K1.1/0.01 F503-K1.5/0.01 F503-K2.1/0.01 F503-K3/0.01 F503-K4.2/0.01 F503-K5.8/0.01 F503-K8/0.01 F503-K11/0.01 F503-K15/0.01 Module (25 mm) 4 4 4 4 4 4 4 4 4 4 4 4 Type 4-pole (3L+NA, 230/400 VAC, 4560 Hz) F504-K0.42/0.01 F504-K0.58/0.01 F504-K0.8/0.01 F504-K1.1/0.01 F504-K1.5/0.01 F504-K2.1/0.01 F504-K3/0.01 F504-K4.2/0.01 F504-K5.8/0.01 F504-K8/0.01 F504-K11/0.01 F504-K15/0.01 Module (25 mm) 5 5 5 5 5 5 5 5 5 5 5 5
10 mA
4-pole
30 mA
F503-K1.1/0.03 F503-K1.5/0.03 F503-K2.1/0.03 F503-K3/0.03 F503-K4.2/0.03 F503-K5.8/0.03 F503-K8/0.03 F503-K11/0.03 F503-K15/0.03 F503-K20/0.03 F503-K26/0.03 F503-K32/0.03 F503-K37/0.03 F503-K41/0.03 F503-K45/0.03
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
F504-K1.1/0.03 F504-K1.5/0.03 F504-K2.1/0.03 F504-K3/0.03 F504-K4.2/0.03 F504-K5.8/0.03 F504-K8/0.03 F504-K11/0.03 F504-K15/0.03 F504-K20/0.03 F504-K26/0.03 F504-K32/0.03 F504-K37/0.03 F504-K41/0.03 F504-K45/0.03
5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
40705
300 mA
4.2 5.8 8 11 15 20 26 32 37 41 45
F503-K4.2/0.3 F503-K5.8/0.3 F503-K8/0.3 F503-K11/0.3 F503-K15/0.3 F503-K20/0.3 F503-K26/0.3 F503-K32/0.3 F503-K37/0.3 F503-K41/0.3 F503-K45/0.3
4 4 4 4 4 4 4 4 4 4 4
F504-K4.2/0.3 F504-K5.8/0.3 F504-K8/0.3 F504-K11/0.3 F504-K15/0.3 F504-K20/0.3 F504-K26/0.3 F504-K32/0.3 F504-K37/0.3 F504-K41/0.3 F504-K45/0.3
5 5 5 5 5 5 5 5 5 5 5
110 VAC, 500 VAC (10 mA, 30 mA types) 110 VAC, 500 VAC, 690 VAC (300 mA types) 16 2/3 Hz, 400 Hz (10 mA, 30 mA, 300 mA types, non G types)
31
10139/B
S500
S500-Z1
UA / AL
S500 basic element S500Grundelement Anbau werkseitig Factory-fitted Anbau durch Kunde Customer-fitted
32
10139/B
Z100083.eps
S500-ME...
S500-356
N I O
O OFF
S500-H2...
S500-H8...
S500-HP2...
33
10139/B
Z100083.eps
S500-K2 -K3
Type Switched neutral NA located to the right of pole Separating neutral N located to the right of the pole
Packing unit
NA
0.5
+UA 24 VAC +UA 110 VAC +UA 230 VAC +UA 400 VAC +UA 24 VDC +UA 110 VDC +UA 230 VDC +UA 400 VDC
1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1
40573
The S500 Heavy Duty Circuit Breaker can only be closed when the undervoltage trip is energised. If the control voltage decreases or fails, the S500 circuit breaker trips immediately. The undervoltage trip can be specially used as an EMERGENCY STOP switch in conjunction with a suitable EMERGENCY STOP button. On request: Other AC or DC coil voltages
Type Shunt trip AL located to the left of pole UC = Universal Current, AC/DC supply
Packing unit
+AA 24 VUC +AA 110 VUC +AA 230 VUC +AA 400 VUC
1 1 1 1
1 1 1 1
The shunt trip serves for remote tripping of the S500 circuit breaker by means of an electrical pulse (no continuous command). On request: Other coil voltages
40574
Type T10 RCD tripping signal contact T10 located to the right of pole - 1 normally closed contact T10
Packing unit
40654
The T10 has a tripping signal contact, which opens on residual current trip. It is used to indicate residual current trip operations. By pressing the test button "T", the breaker (main contact) trips, and the contact state can be checked on the RCD signal contact T10. The RCD signal contact does not indicate that it has tripped when manually operated (ON/OFF). Through the use of auxiliary and signal contacts, which the customer can fit on the left side of the equipment, the following trip events can be displayed: The auxiliary contact always switches simultaneously with the main contacts; the signal contact closes or opens only in the event of a thermal trip (overload), electromagnetic trip (short circuit) or undervoltage, shunt or residual current trip. The T10 RCD signal contact gives the user better ability to distinguish between fault sources. Applications with residual current signal contact T10 Specific indication of residual current tripping in: Hospitals Industrial facilities Laboratories Telecommunication Facilities with high requirements for power availability
Terminal designation
D1
Undervoltage trip UA
U<
C1
Shunt trip AL RCD signal contact T10
15
Z100059.eps
D2
C2
16
Module
34
10139/B
Type Auxiliary contact HK located to the left of pole - 1 NO and 1 NC contact - 2 NO contacts
Packing unit
S500-H11 S500-H20
0.5 0.5
1 1
The auxiliary contacts always switch simultaneously with the main contacts
40620
Signal contact SK located to the left of pole with orange indicator/acknowledgement button and grey test button - 1 NO and 1 NC contact - 2 NO contacts The signal contacts close or open only for thermal trip electromagnetic trip undervoltage (UA) and shunt (AL) trip residual current trip NO contacts: close on trip NC contacts: open on trip
S500-H11 S500-H20
0.5 0.5
1 1
40618
Auxiliary and signal contacts are fitted to a closed circuit breaker. When using auxiliary and signal contacts, the auxiliary contacts must first be snapped directly
The following can be fitted to each circuit breaker: 1 auxiliary contact or 1 signal contact or 2 auxiliary contacts or 1 auxiliary and 1 signal contact
Terminal designation
13 21 13 21
Auxiliary contact HK
S500-H11
Signal contact SK
S500-S11
14 13
22 23
14 13
22 23
S500-H20
40656
S500-S20
14 24
14
24
Type Locking device S500 circuit breakers are lockable in open or closed position
Packing unit
S500-SA
Set of 10
Application To secure from being switched OFF inadvertently or from being switched ON and thus creating a hazard. For padlock shackle diameter max. 4 mm One locking device must be fitted per pole for 1 lock, i.e. for a 3-pole unit 3 locking devices must be used.
40655
Module
35
10139/B
Z100060.eps
Type Rotary drive for 5 mm spindles - for 1- to 3-pole circuit breaker, Module 3 - for 4- to 6-pole circuit breaker, Module 4 (3-pole circuit breaker plus NA, UA or AA = 4-pole breaker, rotary actuator fitted over centre pole)
40607
Packing unit
S500-RD3 S500-RD3
1 1
Rotary handle Protection class IP65 lockable in OFF position, door interlock in ON position, door opening possible in ON position - front plate and switch handle black - front plate yellow and switch handle red
40622
S500-H2B2 S500-H2Y2
1 1
lockable in OFF position, door interlock in ON position - front plate and switch handle black - front plate yellow and switch handle red
S500-H2B1 S500-H2Y1
1 1
40621
S500-HP2B S500-HP2Y
1 1
40619
40613
S500-S51 S500-S51
1 1
Pistol grip lockable in OFF position door interlock in ON position door opening possible in ON position - black handle - lower part of swich handle yellow and switch handle red
40611
S500-H8B S500-H8Y
1 1
S500-S51
Module
36
10139/B
Type S500-AK20 Busbar terminal1) for connecting conductors to interconnected poles Max. connection cross-section: round 50 mm2, square 36 mm2 or flat copper 6 x 20 mm Max. connection cross-section: round 16 mm2, square 20 mm2 or flat copper 5 x 20 mm - for 4 to 6-pole circuit breaker S500-L3 S500-L1
Packing unit
S500-AK50 S500-AK50
Set of 10 Set of 10
40578
Busbar terminal1) with insulating cover for connecting conductors to adjacent poles Max. connection cross-section: round 50 mm2, 8 mm square 36 mm2 or flat copper 6 x 20 mm - L1 - L2 - L3 -N - NA
1)
40603
40604
Post-assembly exchange of individual units from system possible without disconnecting busbars.
Busbar with insulating cover and end caps for connecting conductors to adjacent poles Rated breaking capacity: analogue S500 Max. rated operating voltage Ue: 400/690 VAC Conductor cross section: 35 mm2 Centre supply: 250 A Side supply: 125 A - 8 x 2-pole circuit breaker, length 390 mm S500-BB28 - 8 x 3-pole circuit breaker, length 590 mm S500-BB28 - 13 x 3-pole circuit breaker, length 965 mm (maximum) S500-BB313 - 4 x 4-pole circuit breaker, length 390 mm S500-BB44 with separate neutral conductor rail can also be used with 3-pole breakers with auxiliary contact HK and/or signal contact SK instead of a neutral conductor rail, always leave 1 module open In this case use supply terminal S500-K2 4 4 4 4
S500-EK
40644
S500-K1
40645
On request
40657
- 1-pole busbar barrier strip - other lengths/partitions End cap Attach to ends of busbar for protection after cutting to length
S500-K2
S500-EK
10 pack
40646
Terminal, insulated for rear connection of main contacts connection cross-section max. 25 mm2, Cu cable or strand
S500-K1
Set of 10
Line terminal suitable for 2 and 3-pole busbars, insulated connection cross-section max. 635 mm2, Cu cable or strand suitable for 4-pole busbar, insulated connection cross-section max. 2590 mm2, Cu cable or strand
40229
S500-K2 S500-K3
1 1
S500-A1
S500-F1
40600
Flush-mounting frame of grey plastic for fitting in front panel or door Fitting widths: minimum 24 mm, maximum 184 mm any intermediate values possible by cutting to length - insertion width 38 mm - insertion width 88 mm - insertion width 184 mm
1 1 1
S500-F2
S500-A1
Set of 10
40575
40659
S500-F1 S500-F1
Set of 10 Set of 10
37
10139/B
S500UC
75 50 6 62 92 80
35
45 75 91
35
Z100042.eps
45 91
UA/AL
1P
2P
3P
NA
UA/AL
1P
2P
3P
DDA 2-pole
3-4-pole
45 97.5
Z100088.eps
45 97.5
44
79
35
UA/AA
150
45
45.5
Z100089.eps
Types
38
10139/B
Z100052.eps
Z100065.eps
100 83.5
25.5
min. 65 80
Busbar terminal
S500-AK50 S500-AK20
External drive
25.5
Z100045.eps
min. 65 80
Rotary handle
65
I ON
48 36 3.2
40 M22x1
41.5
24.5
O OFF
36 48
Z100044.eps
22.5
Z100046.eps
25.5
10 34
80
40.7
Pistol grip
Z100048.eps
Z100047.eps
39
10139/B
Z100049.eps
Safety spacing in mm Dimension Spacing from earthed components, insulating covers or wiring ducting 25 7 25 For 10 mm busbar spacing.
A B C
1)
38.4
21.5
23.9
590
19.7
40
10139/B
Z100084.eps
Z100053.eps
ABB Switzerland Ltd. CMC Low Voltage Products Fulachstrasse 150 CH-8201 Schaffhausen Phone +41 (0)58 586 41 11 Telefax +41 (0)58 586 42 22 www.abb.com
10139/B