Beruflich Dokumente
Kultur Dokumente
http://www.exide4u.com/exide/JSP/masters/apnpro/inva_tubular.htm
May 1, 2012
Home
Contact us
Sitemap
GENERAL
Corporate Overview Manufacturing Accreditations Financials Social Responsibility News & Views Battery Recycling
INDUSTRIAL
You are here: Home > Industrial > Application & Products > Stand By > Inverter
Technology Application & Products Battery Sizing Post An Enquiry Battery Servicing Locate a Dealer Contact Us FAQs
EXIDE4U
Inverter
Inva Tubular
Back to Product
Features Ironclad Tubular Technology Electrolyte level indicator High Acid volume per ampere hour Deep cycle design Advantages Very long life User friendly Acid volume per ampere hour is 30% more than that of ordinary tubular batteries. It acts as a coolant and also ensures very low maintenance Suited for use in areas of frequent power cuts (800 to 1000 cycles of deep discharge as against 300/400 cycles of other batteries) Application The next generation Tubular battery designed specially for withstand long and frequent powercuts. It is the ultimate Inverter battery. Technical Specification Can withstand overcharge better Occupies less floor space, totally new look Less pollution, environment friendly Resistance to abuse Tower type design Common Side Venting Conforms to IS 13369-1992
Model
Capacity
Dimension (+/-3mm)
Initial Charge of Constant Current (A) Start (upto 2.36 vpc) Finish (upto 2.75 vpc)
Length
Width
Height*
Dry
Filied
Min.
Max.
1 of 2
5/1/2012 7:06 PM
http://www.exide4u.com/exide/JSP/masters/apnpro/inva_tubular.htm
IT 400 110 Ah IT 500 150 Ah IT 550 165 Ah IT 650 200 Ah 500 187 430 45.00 72.00 21.60 720 19.2 9.6 40 160 640 500 187 430 35.80 60.80 20.00 610 16 8 34 135 540 500 187 430 33.80 60.05 23.80 540 14.4 7.2 30 120 480 506 220 257 29.10 43.35 11.40 450 12 6 25 100 400
Hours
10
IT400
100
83
72
50
120
100
86
60
135
112
97
68
IT650
160
133
115
88
Initial Charging Information 1. 2. 3. 4. Filling in Specific Gravity Rest Period Minimum Ah input 1.220 +/ - 0.005 at 27 C 10-12 hrs 450 Ah for IT400, 540 Ah for IT500, 610 Ah for IT550 and 720 Ah for IT 650
In order to reduce the charging time, the following routine may be adopted. For IT400, the initial charging current may be 12A upto 2.36vpc followed By 6A upto 2.75 vpc. For IT500, the initial charging current may be 14.4A upto 2.36vpc followed By 7.2A upto 2.75 vpc. For IT550, the initial charging current may be 16A upto 2.36vpc followed By 8A upto 2.75 vpc. For IT 650 , the initial charging current may be 19.2A Up to 2.36vpc followed by 9.6A upto 2.75vpc. However in both cases, minimum Ah to be given. Under the circumstances, Battery temperature should not exceed 50C. In case the temperature exceeds 50C Adequate rest to be given till the electrolyte temp. comes to ambient temp. and charging to be continued.
5.
Conditions of fully charged 3 consecutive hourly readings of specific gravity and voltage become constant. Top of charge voltage will e around 16.2V 16.5V. All cells should gas freely. Minimum Ah has been given.
6.
1.250 +/ - 0.005 at 27
Normal Recharging Instruction Recharging through Inverter at constant potential mode of 14.4V with limited current as specified. After battery potential matches 14.4V, the battery should continue in trickle charge made at constant potential of 13.8V. Statutory Notice All batteries contain lead, which is harmful for humans and environment. As per statutory requirements, the used battery must be returned to the authorized dealer, manufacturer or at the designated collection centres. Back to Product