Sie sind auf Seite 1von 5

Effects of Dynamic Fault Impedance Variation on Accuracy of Fault Location Estimation for Series Compensated Transmission Lines

M. Al-Dabbagh , S. K. Kapuduwage Electrical Energy and Control Systems School of Electrical and Computer Engineering RMIT University City Campus

Abstract: - This paper investigates and compares the effects of dynamic fault impendence variation on the accuracy of estimating location of faults on series compensated transmission lines, using a novel fault location algorithm based on the measurement of instantaneous signals, derived from both ends of high voltage transmission lines. In order to estimate fault location accurately, it is necessary to compute precisely the voltage drops in series compensation units during the fault. However, the methods available for such computations induce considerable errors in fault location estimation algorithms, due to the complexity of the series compensation units. Furthermore, in these methods, fault impedance has been assumed fixed during the fault. In this paper, the fault impedance used in the models has been considered variable and its dynamic inclusion in the fault estimation algorithm has been investigated. The developed algorithm has been tested using the ATP software with 400KV, 300km long transmission line interconnecting two equivalent power systems. The algorithm performed well with fixed fault impedance. However, by representing the fault impedance in its dynamic form, the accuracy of the algorithm has not changed. Such simulation of the fault impedance is more accurate than the assumption of fixed values.

The presented results show that the new algorithm is capable to estimate accurately the location of faults under different conditions, including dynamic fault impedance. The paper will discuss the results obtained and conclusion will be made on the novel scheme for fault location estimation on series compensated high voltage transmission lines.
Key-Words: - Fault location, Fault impedance, Transmission lines, Series compensation, Instantaneous signals, ATP software

1 Introduction
Inclusion of reactive power compensation, using series capacitors in high voltage power transmission networks, particularly where long line sections are involved, is effectively improving power transfer capability, transient stability and damping of power system oscillations. The metal oxide varistors (MOV) are used in parallel with the capacitor to protect the series capacitor against excessive over voltages under fault condition [1]. However, due to the uncertainty of the voltage drop across the series compensator, the design and application of devices such as fault locators and protection schemes in transmission networks seem to be one of the most difficult tasks for manufactures, operators and maintenance engineers [2].

The traditional techniques of estimating location of faults based on direct or indirect measurements of apparent impedance [3] can no longer be used with the series compensated transmission lines. The problem is not in the inclusion of capacitor, but in the operation of the MOV in parallel with the capacitor. In order to estimate fault locations accurately, the voltage drop of series compensation unit required to be computed precisely [4]. Another critical factor to consider, when estimating the location of fault, is the duration of fault data available prior to the clearing of fault. Most of the high voltage transmission line faults are cleared in two to two and half cycles from the inception of a fault. Due to limited fault data measurements, it is difficult to estimate of voltage drop across the capacitor accurately. Fault location algorithm used in this paper

uses instantaneous measured data from both ends of faulted power network to estimate the voltage drop across the capacitor accurately. The basic arrangement of the series compensation using series capacitor (C) is shown in fig. 1.
Icp(t)

MOV
If(t)

Imv(t)

be taken from both ends of the transmission network with absolute time reference. This algorithm was tested using sample data collected form numerous types of faults simulated in ATP program. The results indicate that the average accuracy of fault location estimation is not below 99.9%. The details of the results are given in this authors previous paper [3]. However, in these test cases, it was assumed, fault impedance to be fixed. In this paper investigate the application of this fault location algorithm in the case of time varying fault resistance during the fault.

Breaker

Capacitor Protection

2. Series Compensation Model


Fig. 1 shows the typical configuration of the series compensation device, with its basic protection mechanism. During a fault, when the voltage drop across the capacitor (C) exceeds, MOV is begun to conduct and its vi characteristics could be approximated by a nonlinear equation:
i = p * V VREF

Fig. 1 Typical series compensation arrangement When voltage drop across the capacitor exceeds its protective level, the MOV bypass the heavy fault current protecting the capacitor. If the fault sustains too long, overheating of the MOV is limited by the operation of the breaker, bypassing the current through the MOV. The algorithm used in this paper, conditionally computes the series capacitor voltage drop using measured instantaneous values, before and after the operation of MOV during the fault. MOV begins to operate the when capacitor voltage drop is below the SC protection level. During this period, series compensation voltage drop could be computed using series capacitive reactance. Otherwise, the voltage drop is calculated considering both capacitor and MOV currents. Two-end transmission line, with series compensating device located at the centre of the line has been applied for the testing of this fault location algorithm. First, the algorithm conditionally computes the instantaneous voltage drops across the series compensation unit. Then solving the 3 phase fault equations, expressions for fault location (x) and fault resistance could be obtained. ATP program is used to create and simulate the faults in the two ends transmission networks. The instantaneous fault data of voltages and currents were monitored during the fault simulation and measurements were used to estimate the location of fault. However, at this stage, the line shunt capacitances have not been included in this model, in order to simply the proposed algorithm. Fault data measurements were collected from both ends of the transmission line at a sampling rate of 100 kHz. In this case, measurements of instantaneous values must

(1)

where p and VREF are the reference quantities of the MOV and typically q is in the order of 20 to 30 [5].

The excessive energy absorption by the MOV is limited by the operation of circuit breaker shorting
the compensation device. The expressions for the instantaneous capacitor voltage drop could be obtained with respect to the instantaneous fault current (If (t)) as follows: V cp (t ) = V cp (t T ) +
T I f (t ) + I f (t T ) 2C

(2)

I f (t) = I f (t T ) +

C V cp (t) V cp (t T ) + V cp (t 2T ) + T

g V cp (t ) V cp (t T )

(3)

Where equation (2) and (3) are referred to MOV is not conducting and MOV is conducting stages [5].
4 x 10
5

Co m pa r ision o f S C U in sta n ta n io u s vo lta ge d ro p A cu ta l V s ca lcu la te d


Actu a l vo lta g e d ro p

3 C a lu la te d vo lta g e d ro p 2 SCU Voltage Drop(in Volts)

0 Fa u lt In ce p tio n -1

-2

-3

-4 0

10

20

30

40

50

60

T im e , m s

Fig 2. Instantaneous voltage drop comparison (Actual Vs. Calculated)

In these expressions, Vcp(t) is the current voltage drop and T is the sampling time of fault data measurements. g is the gradient of MOV vi
characteristics, at time t. Figure 2 displays the typical instantaneous capacitor voltage drop computed using above method, for a 3PG fault simulated in ATP program with time period of 60 ms. Also shown the actual voltage drop as determined by ATP program for comparison.

[VD] is the computed instantaneous voltage drop across the series compensation unit.
At any given time (t), the instantaneous voltage drop across the impedance with inductance L and resistance R can be written in discrete form as:
V ( t ) = R . I (t ) + L [I (t ) I (t T ) ] T

(7)

3. System Configuration
Fig. 3 shows a single line diagram of a basic two-end transmission network with a series compensation unit (SCU), which comprises of a capacitor(C) and Metal Oxide Varistor (MOV) located at the center of the line. The network is fed from voltage sources ES and ER connected to each end of the transmission line. It is assumed that a fault occurs at point F1, at a distance x from source S, prior to the SCU.
VR & IR

Where I(t) is the current passing through the impedance at time t. Knowing IS and IR, the instantaneous values of [ZL]{IS] and ,[ZL]{IR] are calculated using equation (13). Solution for distance to fault x can be estimated for each instantaneous value using the following expression:
x (t 0) = V A (t 0 ) V B (t 0 ) + V D (t 0 ) + VZ R (t 0 ) VZ S (t 0 ) + VZ R (t 0 )

(8)

FLoc.
IS ZS VS ES Station S
(Local)

Microwave/Sattelite link

ZL11

F1

F2

IR ZL22 VR ZR

where t0 is the time at which sample values are computed. If the fault position is after the location of series capacitor, equation 8 can be modified to obtain the distance to fault. And also, a simple selection algorithm [5] could be used to determine proper equation to be used to compute x(t0), depends on position of x with respect to series capacitor.

4.2 fault resistance


ER

IF
Distance to fault (x)

MOV

Station R
(Remote)

A general 3-phase fault model is implemented in fault location algorithm to estimate the fault resistance [1]. 3-phase fault conduction matrix can be stated in matrix form:

Fig. 3. Basic two-end transmission network The voltage sources can be expressed as complex phasors which can be denoted in matrix form [3]: ES = [ Esa Esb Esc ]
T

[I F ] [I F ]

[K F ][V F ] Rf = [I S ] + [I R ]
=

(9)

(4)

If the distance to fault F1 from source ES is x, the impendence of the line can be written as: ZL1 = x ZL and ZL2= (1-x)ZL (5)

Where Rf is the aggregated fault resistance and VF is the voltage at the fault. Where the fault matrix KF need to be computed in relation to the type of fault [2]. Applying fault equation to the opposite side of series compensation unit:

[V F ] = [V R ] (1 x )[ZL ][I R ]

(10)

ZL is the total impedance of the line, which can be represented by 3x3 impedance matrix form.

Where VF is the voltage at the fault location. Knowing the distance to fault, then solving above equations 9 and 10 fault resistance can be estimated.

4. Algorithm Development
4.1 fault location
If the voltage and current at the local bus and remote buses are Vs, Is, VR and IR respectively, then the network equation of the faulted system can be written in matrix form: (6) [V s ] x [ZL ][I S ] = [V R ] (1 x ) [ZL ][I R ] [V D ]

5. ATP Modelling
In order to test the accuracy of the newly developed algorithm with having time varying dynamic fault impedance, a two terminal, 3-phase transmission model as shown in Fig. 3, was modeled using the ATP program.

5.1 transmission line and supply systems


The transmission line model used is 300km long and rated at 400KV. The series compensation unit is placed and fixed in the middle of the line. The transmission line is represented by 4 sections of 3 phase distributed parameter branches specifying positive and zero sequence impedance for each branch. Note, that present algorithm, does not take into effects of shunt capacitance of the lines. In order to minimize the effects of shunt capacitance, transmission line has been model in ATP with very low shunt capacitance.

5.5 implementation of the algorithm


The new algorithm was implemented using MATLAB 6.5 software script language [7]. Row data generated from the ATP model was converted to EXCEL worksheet in order to be opened directly from MATLAB. After opening the file from MATLAB, data was further separated to individual arrays, to apply to the new algorithm. The MATLAB algorithm computes the fault location and fault resistance for each sample of voltages and currents exported to MATLAB space from the ATP simulation.

5.2 Series compensation


The series compensation is modeled with a 3 phase capacitors (C) and non-linear resistances (MOV) in parallel for each phase. Type 97 ATP nonlinear resistance is used as the MOV.

6. Case Studies
To illustrate the application of this algorithm with a time varying fault impedance, a SLG fault with dynamic fault resistance of 10 ohms occurs at 75km from the station S. The power transfer from station S to R prior to the fault is 300MW and -200MVAR. The fault is applied when the voltage at station S is at peek.

5.3 fault resistance


For the fault resistance, ATP type 97 Staircase Time Varying Resistance is with initial value of 10 ohms. In time varying fault cases, fault resistance from 10 drops to 8.5, 6.5 and 2.5 ohms during the fault simulation. In this case switching times are selected in line with time steps to avoid solution fluctuations near the switching. [8]

Fig. 4 shows the currents and voltages from the local station pre and post of the fault.
Current, KA
Voltage, KV

4 3 2 0

200 0

5.4 fault simulation


Voltages and currents from both ends are recorded at sampling rate of 100 KHz before and after fault occurrence. Total simulation time is 0.1 sec. and the fault is initiated at 0.035 sec. For comparison of the accuracy of fault location with fixed and dynamic resistances, type 97 Staircase Time Varying Resistance. Same ATP file with minor modifications is used to create different types of faults. The system data used for this model are shown in table 1.

-200
Time, sec.

-2 -3 0

Time, sec.

0.02

0.04

0.06

0.08

0.1

0.02

0.04

0.06

0.08

0.1

Fig 4. (a) 3Ph. currents from station S, (b) 3Ph. voltage at station S Dynamic estimation of fault location and fault resistance, from the inception of fault, using this algorithm is shown in Fig. 5.
Daynamic Calculation of fault location
Distance to fault ( in p.u.)

0.35 0.3 0.25 0.2 0.15 0.1 0.05 0


1 244 487 730 973 1216 1459 1702 1945 2188 2431 2674 2917 3160 3403 3646 3889

SYSTEM S S AND R positive sequence inpedence zero sequence inpedence TRANSM ISSION LINE length voltage degree of compensation location of SCU positive sequence impedence zero sequence impedence shunt Capacitance M OV DATA used in ATP model reference current reference Voltage exponent DATA ACQUISITION sampling frequency kHz 100 kA kV 4.4 330 23 kM 300 kV 400 % 89 kM 150 ohm 8.25+j94.5 ohm 82.5+j308 nf/km ohm ohm 1.31+j15.0 2.33+j26.8

Samples

Fig 5. (a) Dynamic estimation of fault location, (b) Dynamic estimation of fault resistance First calculated value shown in Fig. 5 uses the sample data just after the fault inception, on the simulation time scale. From Fig 5 (a), dynamic estimation of fault location using samples in this test case, are very close to the actual distance to fault simulated in ATP. However, due to fault resistance variation, there is a slight error appears in the fault location calculations.

Table 1. System data used in transmission line model

Estimated fault resistance in Fig 5 (b) clearly shows that initial fault resistance of 10 ohms changes to 8.5, 6.5 and 2.5 ohms in steps as simulated in ATP using type 97 Staircase Time Varying Resistance. At this stage, number of different types of faults simulated in ATP model for testing the accuracy of the algorithm with static and time varying fault resistance. Location of the fault changes from 75km, 150km and 225km for better evaluation of the algorithm. Comparisons of the fault location estimation errors (in percentage) with different types of faults are shown in Fig 6. Overall accuracy of fault location estimation using this algorithm is not below 99.9%
3 Phase to Ground Faults Static 10 ohm
Average distance to Fault Error%
0.12 0.1 0.08 0.06 0.04 0.02 0 75 150 225

References
Rosolowski E., Jzykowski J. Effects of Transmission Load Modelling on Fault Location, Wroclaw, University of Technology, Poland
[1]

Saha M.M., Jzykowski J., Rosolowski E. Kasztenny B. A new accurate fault locating algorithm for series compensated lines, IEEE Transactions on Power Delivery Vol.14, No. 3, July 1999, pp. 789-795
[2]

[3] M. Al-Dabbagh, S. K. Kapuduwage A novel Efficient Fault Location Algorithm for series compensated High Voltage Transmission lines, SCI 2003, July 2003, Vol XIII, pp.20-25 [4] F. Ghassemi J. Goodarzi A.T. Johns Method to improve digital distance relay impedance measurement when used in series compensated lines protected by a metal oxide varistor , IEE Proc., Vol145, No.4, July 1998 [5] S. K. Kapuduwage, M. Al-Dabbagh A New Simplified Fault Location Algorithm for Series Compensated Transmission Lines, AUPEC 2002, Sep. 2002 [6] A.T. Jones, P.J.Moore, R. Whittard New technique for the accurate location of earth faults on transmission systems, IEE Proc., Vol142, No.2, March 1995

Daynam ic 10 - 2.5 ohm


0.12

1 Phase to Ground Faults Static 10 ohm Daynamic 10 - 2.5 ohm


Average distance to Fault Error%
0.1 0.08 0.06 0.04 0.02 0 75 150 225

Distance in kM

Distance in kM

2 Phase to Ground Faults


Average distance to Fault Error%
0.12

2 Phase Faults
Static 10 ohm
0.12 0.1 0.08 0.06 0.04 0.02 0

Static 10 ohm

Daynamic 10 - 2.5 ohm

Daynam ic 10 - 2.5 ohm

Average distance to Fault Error%

0.1

0.08 0.06 0.04 0.02 0 75 150 225

75

150

225

Distance in kM

Distance in kM

Fig. 6 Average fault location errors with different types of faults

[7] MATLAB Version 6.1, Release 12-1 Help Reference Documents [8] Alternative Transients Program Rule book, 1989 edition

7. Conclusions
New algorithm for locating faults in series compensated lines has been tested with time varying fault resistance. This technique uses the instantaneous measurements of currents voltages from both ends of the transmission line with accurate time references to estimate the fault location. Since at this stage, effects of shunt line capacitances are not included in the algorithm, this cannot be used for long transmission lines. The average fault location error using this algorithm in most fault cases does not exceeds 0.1%.

Das könnte Ihnen auch gefallen