Beruflich Dokumente
Kultur Dokumente
he application of the electromagnetic core imperfection detector (EL CID) technique invented by Sutton [19801] in the late 1970s is now familiar to many manufacturers and users of large rotating electrical machines. Over the years a number of initially puzzling phenomena have been observed in the results, particularly with respect to large diameter salient-pole machines, which are common in hydroelectric schemes. There have also been some interesting features encountered in results from turbogenerators. While all the phenomena observed have now been defined and analysed by Ridley [20042], the purpose of this paper is to bring these matters into deeper focus so that EL CID may be used to greatest advantage. Some aspects may be already fully identified, but are included for completeness. It is assumed that the basis of the technique is familiar, that is, in essence the stator under investigation for soundness of its interlaminar insulation has a circumferential flux induced in it and any damage to the insulation allows a circulating fault current to flow (see Fig. 1). The magnetic fields from both the circumferential flux and fault current are detected by a Chattock potentiometer (also known as a Rogowski Coil), and by phase separation the magnitude of the fault defect may be determined.
Appendix 2.1 of Ridley 20042]. The required value of volts per turn (Vt) is given approximately by [12.5 machine line voltage in kV] / [Stator winding series turns per phase], assuming that the combined spread and chording factor [K] is 0.926. Vt is inversely proportional to K.
Initially the relevant vector diagram, relating the electromagnetic fields of the main flux and that produced by fault current () in the laminations, was conceived
87
as a simple orthogonal relationship, comprising PHASE [P] and QUAD [Q] vectors respectively, placed at 90 to each other. The PHASE value was proportional to the excitation current [Ie]. QUAD was proportional to the fault current (). It was always understood that contains an in-phase component, but this was considered negligible, compared with the quadrature component, since the fault path through the fault, stator laminations and corebuild (or key) bars is predominantly resistive. Test results indicated, particularly at joints between the sections in large diameter hydro generators, that the phase relationship was more complex. The relationship, for zero fault current, was identified by a characteristic line, cutting the PHASE axis at a value other than zero. This is basically the magnetic potential difference [mpd] which would be the constant PHASE value [Pe] if the permeability around the core was constant, and there was no fault current. Pe is calculated as [Magnetising Ampere-turns / Number of Teeth (or Slots)] = AT / S. Thus, the equation of the characteristic line is given by P = Pe + RQ, where R is the slope of the line. Ridley designated this as the zero line, applicable for no fault current (). The PHASE value at zero QUAD value is modified because of the effect of core joints and the presence or otherwise of the machine rotor during the EL CID test [see Section 7.6 of Ridley 20042]. To develop a comprehensive vector diagram, another factor had to be recognized and introduced (see below).
88
Fig. 6. EL CID vector diagram taking account of circulating current with PHASE reference set to the excitation current.
Fig. 5. EL CID vector diagram taking account of circulating current with PHASE reference set to the leakage flux.
siderations). Moreover, it is possible that there may be some net fault current also reflected in the excitation current. In any case, the basic reference vector is the excitation current [Ie], which includes an orthogonal component of current required to establish the iron loss. The vector diagram in Fig. 6 is drawn on the assumption that the PHASE reference is established where there is neither local stator winding circulating current nor fault current. As before, the variation of circulating current moves the operating point in its vectorial direction, which is again the zero line. The variation in the QUAD reading for a particular slot once again indicates the maximum value, which may merit closer examination.
5.2 PHASE reference from a current transformer round the excitation cable
A superficial consideration of stator winding circulating current indicates that there is no net value to be provided by the excitation current, since the currents sum to zero. However, they are induced only when the excitation is asymmetric, deliberately by the user or inevitably because of core construction. In this case, the coupling between excitation winding and generator windings is not symmetric and a portion of the circulating current must be contributed by the excitation winding (as would be expected on simple energy conHydropower & Dams Issue Four, 2005
analysis also showed an unexpected result. The form of the flux density distribution induced in the iron can be seen in Fig. 9. The surprising feature is that directly beneath the cable, the flux density is zero, whatever the spacing of the conductor from the iron. This explains the deep valley in the value of EL CID results in the neighbourhood of the cable. An understanding of this phenomenon helps to locate the position of the excitation cable, if it has not been recorded [see Fig. 20 in Ridley 20042].
Fig. 8. EL CID results exhibiting trace axis slope and significant deviation at one end of the core.
90
tence of air currents, core size, and the duration of the test. With regard to the last item, different personnel have quite different standards. It is recommended that a study is undertaken to identify the effect of these ambient conditions on HFRT results, so that correlation with EL CID results can be improved, thus enhancing the reliability with which the latter may be used. Nevertheless, the EL CID technique has been extensively applied and found to be a useful tool for monitoring core condition both for normal service and when under repair.
10. Conclusion
Although a number of phenomena in the EL CID results have been observed, they are now well understood, which allows their effect to be taken into account. The understanding gained permits use of EL CID in the same relatively simple manner as first proposed, and the results are consequently acceptable as a pointer to the core condition.
Eur. Ing. G.K. Ridley was a designer of large electrical rotating machines, mainly hydro generators, for nearly 40 years with BTH, Rugby, UK, and its successors, concluding his career as Design Manager. He has been a registered engineer with FEANI since 1990. He became a Chartered Engineer in 1960, subsequently achieving the status of FIEE (1970) and FIMechE (1992). He is also a Senior Member of the IEEE. He has been an active member of CIGRE since 1992, having undertaken worldwide surveys of bearing design and practice for large vertical hydro generators, and also the comparison of EL CID and High Flux Ring Tests (HFRT) results. He was invited to present a preferred subject paper on the latter topic at the biennial meeting of the CIGRE Session in Paris in 2002. Mr Ridley has had 37 papers published and in 2000 he authored a book entitled EL CID - Application and Analysis, the second edition of which was published in 2004. Since nominal retirement in 1994, he has served as an independent consultant on hydro generators, with a special interest in EL CID result analysis. 11 Hoskyn Close, Hillmorton, Rugby, Warwickshire CV21 4LA, UK. Eur. Ing. David Bertenshaw graduated with a B.Sc. (Eng) degree in Electrical Engineering from Imperial College, London University, in 1971. He was elected as MIEE in 1980, as FIEE in 1998, and is a Chartered Eur. Ing. He has spent many years in the development of lighting and control systems, and communications systems, as R&D and Engineering Director. He joined ADWEL International, UK, in 1998 and he now directs the engineering and commercial management of the companys stator core test systems. He has authored and presented 20 conference papers, is the inventor on six international patents and a member of national standards committees relating to EMC. ADWEL International, Park House, Greenhill Crescent, Watford, Herts WD18 8PH, UK.
G.K. Ridley
D. Bertenshaw
References
1. Sutton, J., EL CID: an easier way to test stator cores, Electrical Review, Vol. 207, No. 1, 1980. 2. Ridley, G. K., EL CID application and analysis, Ed: 2, ADWEL International Ltd; 2004. 3. Bertenshaw, D. R and Sutton, J, Application of the EL CID Test with Circulating Currents in Stator Windings, Inductica 2004, Berlin, Germany; June 2004. 4. Ridley, G. K., Hydro-generator EL CID results referred to High Flux Ring Test results, Proceedings, Session 2002 of CIGRE, Paper 11-201; August 2002. 5. Bertenshaw, D. R et al, Computational modelling of stator core faults in large hydro-generators and turbo-generators, Hydro 2004, Porto, Portugal; October 2004.
91