Beruflich Dokumente
Kultur Dokumente
Topic
Page
Additional Resources
Product Overview
Design Considerations
11
31
Cable Considerations
48
Motor Considerations
49
52
Drive Options
87
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Title
Publication
750-IN001
750-PM001
20HIM-UM001
750-UM002
Safe Speed Monitor Option Module for PowerFlex 750-Series AC Drives Reference Manual
750-RM001
750COM-UM
PFLEX-AT001
DRIVES-IN001
DRIVES-TD001
Safety Guidelines for the Application, Installation and Maintenance of Solid State Control
SGI-1.1
Product Overview
The PowerFlex 750-Series is a robust family of AC drives that provide ease of
use, flexibility, and performance for a variety of industrial applications. The
PowerFlex 753 provides general purpose control for applications ranging up to
350 Hp and 250 kW. The PowerFlex 755 provides maximum flexibility and
performance ranging up to 2000 Hp and 1500 kW.
Maximize your productivity by taking advantage of the following key features
offered in the PowerFlex 750-Series:
DeviceLogix Embedded control technology that supports the
manipulation of discrete outputs and drive control functions, while
using discrete inputs and drive status information onboard the drive.
Predictive Diagnostics Allows the drive to keep track of information
that affects the life of its cooling fans and relay outputs. The drive can also be programmed to monitor the run time
hours for machine or motor bearings.
Option Cards Each drive has a slot-based architecture. Supported hardware control options are common for both
products, to help reduce your inventory and spare parts requirements.
Safe Torque-Off and Safe Speed Monitor provides a choice for safety levels depending on your application
requirements.
Communications The PowerFlex 755 comes with a built-in Ethernet port. Ethernet can easily be added to the
PowerFlex 753 with a communication module.
I/O option cards are available for additional analog and discrete I/O. The PowerFlex 753 comes with built-in I/O
that can also be easily expanded with option cards.
Packaging Factory and field installable enclosure options are available to meet most environmental requirements:
Open Type and Flange Mount options to support Cabinet Mount requirements, Extra Protection Wall Mount for
harsh environments, and supporting debris hoods and conduit plate kits.
Standard Power Structure a common power structure is shared to provide the same physical footprint and power
range.
Frame 17
IP00/IP20, NEMA/UL Type Open Drive
Frames 810
IP20, NEMA/UL Type 1 Drive
(2500 MCC Style Cabinet)
Frames 810
IP20, NEMA/UL Type 1 Drive with Options
(2500 MCC Style Cabinet)
includes:
DC link choke
Internal brake transistor standard on Frames 15
and optional on Frames 67
includes:
DC link choke
AC line fuses
Roll-out design
includes:
DC link choke
AC line fuses
Roll-out design
Option bay for control/protection devices
Roll-out Cart
Required for Frame 8 and larger drives
Adjustable Curb Height: 0182 mm (07.2 in.)
Adjustment for Curb Offset/Reach: 0114 mm (04.5 in.)
810
11
12
13
14
15
16
17
18
20G
248
f1f4
- LD - P3 - P11
Cabinet Options (21G)
Drive
Voltage Rating
Code
Type
Code
Voltage
20F
PowerFlex 753
400V AC/540V DC
20G
PowerFlex 755
480V AC/650V DC
21G
600V AC/725V DC
b
Future Use
f1
f2
ND Rating
ND Rating
400V, 50 Hz Input
480V, 60 Hz Input
Input Type
Frame
Enclosure Code
Description
Frames
15,
810
DC Input w/Precharge
510
2P1
2.1
0.75
2P1
2.1
68
3P5
3.5
1.5
3P4
3.4
5P0
5.0
2.2
5P0
5.0
8P7
8.7
8P0
8.0
011
11.5
5.5
011
11
7.5
015
15.4
7.5
014
14
10
022
22
11
022
22
15
Enclosure
030
30
15
027
27
20
034
34
25
040
40
30
052
52
40
065
65
50
077
77
60
096
96
75
125
125
100
156
156
125
186
186
150
248
248
200
302
302
250
361
361
300
415
415
350
Code
Amps
kW
B, J,
L, T
Code
Amps
Hp
K, P,
R
W, Y
B, J,
L, T
Code
Description
Frames
037
37
18.5
043
43
22
25
060
60
30
27
072
72
37
27
085
85
45
104
104
55
140
140
75
170
170
90
205
205
110
260
260
132
302
302
160
367
367
200
456
456
250
460
460
250
430
430
350
540
540
315
485
485
400
567
567
315
545
545
450
650
650
355
617
617
500
750
750
400
710
710
600
770
770
400
740
740
650
910
910
500
800
800
700
1K0
1040
560
960
960
800
1K1
1090
630
1K0
1045
900
1K2
1175
710
1K2
1135
1000
1K4
1465
800
1K3
1365
1100
1K5
1480
850
1K4
1420
1250
1K6
1590
900
1K5
1525
1350
2K1
2150
1250
2K0
2070
1750
810
810
810
810
810
810
810
810
Frame
Enclosure Code
Code
3
4
5
5
5
6
6
10
10
K, P,
R
W, Y
5
5
5
6
6
10
10
f3
f4
ND Rating
ND Rating
600V, 60 Hz Input
Code
Amps
Hp
B, J,
L, T
Code
Filtering
Frame
Yes
Jumper Removed
Enclosure Code
Enclosure Code
Yes
Jumper Installed
Code
Amps
kW
B, J,
L, T
K, P,
N
R
W, Y
K, P,
N
R
W, Y
480V drives must select code "A." Jumpers are included for field
reconfiguration as desired.
1P7
1.7
12
12
7.5
2P7
2.7
15
15
11
3P9
3.9
20
20
15
6P1
6.1
23
23
18.5
7.5
30
30
22
Code
11
11
10
34
34
30
No
Yes
37
No
No
17
17
15
46
46
22
22
20
50
50
45
27
27
25
61
61
55
32
32
30
82
82
75
41
41
40
98
98
90
52
52
50
119
119
110
63
63
60
142
142
132
77
77
75
171
171
160
99
99
100
212
212
200
125
125
125
263
263
250
Internal Resistor
Internal Transistor
Frames 12 only.
Code
Option
LD
Light Duty
ND
Normal Duty
Heavy Duty
Type
Frames
System Overload
Duty Cycle
810
265
265
250
HD
330
330
315
P3
370
370
355
300
415
415
400
P5
295
300
460
460
450
P14
355
350
500
500
500
395
395
400
590
590
560
435
435
450
650
650
630
460
460
500
710
710
710
510
510
500
765
765
750
595
595
600
795
795
800
630
630
700
760
760
800
825
825
900
144
144
150
192
192
200
242
242
250
289
289
295
355
900
900
950
980
980
1000
1K1
1110
1100
1K4
1430
1400
960
960
900
1K0
1040
1000
1K4
1400
1400
10
810
10
10
Power
Disconnect or
Wiring Only Bay
10
Option
P11
Input Contactor
P12
Output Contactor
L1
3% Input Reactor
L2
3% Output Reactor
L3
5% Input Reactor
L4
5% Output Reactor
P20
P22
P24
P30
Type
Contactors
Frames
8
810
Reactors
8
810
810
C-Tick
c-UL-us
Listed to UL508C and CAN/CSA-C22.2 No. 14-05 (does not apply to 21G drives with enclosure code P or W).
CE
EPRI/SEMI F47
TV
TV Rheinland - Certification applies to 20-750-S and 20-750-S1 Safety Options when installed in drive.
Standards applied:
EN 61800-3:2004
EN 61800-5-2:2007
EN 61800-5-1:2007
EN 61508 PARTS 1-7:2000
EN ISO 13849-1:2008
EN 62061:2005
EN ISO 13849-2:2003
EN 60204-1:2006
Environmental Specifications
Category
Specification
Altitude:
Based on Load:
Based on Voltage:
Overvoltage Category
II (2)
III (3)
II (2)
III (3)
(1)
050 C (32122 F)
050 C (32122 F)
040 C (32104 F)
040 C (32104 F)
040 C (32104 F)
040 C (32104 F)
050 C (32122 F)
050 C (32122 F)
040 C (32104 F)
040 C (32104 F)
-4070 C (-40158 F)
Atmosphere:
Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or
dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a
corrosive atmosphere.
UV Radiation
The HIM and IP54, NEMA/UL Type 12 drive plastics are not UV rated.
Relative Humidity:
595% non-condensing
Shock - Operating
Frame 16:
Frame 7:
Frame 810:
Frame 12:
Frame 34:
Frame 5:
Frame 610:
Category
Specification
Vibration - Operating
Frame 12:
Frame 35:
Frame 67:
Frame 810:
Frame 15:
Frame 610:
Frame 15:
Frame 610:
20.0 mm (0.8 in.) peak to peak, 25.186 Hz; 1.1 g peak from 5.18620 Hz
Meets ISTA 2B packaging standards
Frequency (Hz)
PSD (g2/Hz)
1
0.00005
4
0.01
16
0.01
40
0.001
80
0.001
200
0.00001
Meets International Safe Transit Association (ISTA) test procedure 2B
Required Airflow:
Frame
12
3
4
5
6
Frame
7
8
9
10
Sound:
Frame
12
3
4
5
6
Sound Level
63 dB
64 dB
72 dB
77 dB
73 dB
Frame
7
8
9
10
Sound Level
74 dB
79 dB
79 dB
83 dB
Technical Specifications
Category
Specification
Protection
Electrical
Motor Voltage
380/400
480V
600V
690V
576V AC
576V AC
825V AC
825V AC
250V AC
300V AC
400V AC
400V AC
815V DC
815V DC
1167V DC
1167V DC
200V DC
400V DC
200V DC
400V DC
400V DC
400V DC
540V DC
648V DC
810V DC
932V DC
Line transients:
Power Ride-Thru:
Frequency Tolerance:
4763 Hz
Input Phases:
Three-phase input provides full rating for all drives. Single-phase operation on Frames 17 provides up to
50% of rated current at 25 C (77 F) surrounding temperature. Single-phase operation is not recommended
for Frames 8 and larger.
DC Link Impedance:
5%
Efficiency:
Determined by AIC rating of installed fuse/circuit breaker. See page 46 for 21G drives
5A
Battery:
User installed CR1220 lithium coin cell battery provides power to the real time clock (optional, not supplied).
Preserves the clock setting in the event power to the drive is lost or cycled. Approximate life is 4.5 years with
dive unpowered, or lifetime if drive is powered.
Category
Specification
Control
Method:
Sine coded PWM with programmable carrier frequency. Ratings apply to all drives.
Carrier Frequency:
Default Settings:
Drive Frame 14:
Drive Frame 510:
Settings:
Drive Frame 16:
Drive Frame 7:
Drive Frame 810:
Frequency Accuracy
Digital Input:
Analog Input:
4 kHz
2 kHz
2, 4, 8, 12 kHz
2, 4, 8 kHz
2, 4 kHz
Frequency Control:
Speed regulation - with Slip Compensation (V/Hz & Sensorless Vector modes)
0.5% of base speed across 40:1 speed range, 40:1 operating range
Speed Control:
Without feedback (Flux Vector mode), 0.1% of base speed across 100:1 speed range, 120:1 operating range,
50 rad/sec bandwidth
With feedback (Flux Vector mode), 0.001% of base speed across 100:1 speed range, 1000:1 operating range,
190 rad/sec bandwidth
Torque Regulation:
Stop Modes:
Multiple programmable stop modes including - Ramp, Coast, DC-Brake, Ramp-to-Hold, Fast Braking, and
Current Limit Stop.
Accel/Decel:
Two independently programmable accel and decel times. Each time may be programmed from 0 to 3600
seconds in 0.1 second increments (0 to motor nameplate speed).
S Curve Time
Intermittent Overload:
Light Duty (Frames 810 Only)
Normal Duty
Heavy Duty
10
Proactive Current Limit programmable from 20 to 160% of rated output current. Independently
programmable proportional and integral gain.
Class 10 protection with speed sensitive response. Complies with N.E.C. Article 430. U.L. File E59272, vol. 12.
Design Considerations
Drive Rating
Nominal Line
Voltage
Nominal Motor
Voltage
Drive Operating
Range
380480
380
380
380528
342528
400
400
400528
480
460
460528
600
575
575759
600690
690
660
517759
660759
Drive Full Power Range = Nominal Motor Voltage to Drive Rated Voltage + 10%.
Rated current is available across the entire Drive Full Power Range
EXAMPLE
IMPORTANT
Lowest Nominal Motor Voltage - 10% to Drive Rated Voltage + 10%. Drive
Output is linearly derated when Actual Line Voltage is less than the
Nominal Motor Voltage
5 Hp
No Drive
Output
3.7 Hp
No Drive
Output
342V
480V
460V
528V
For maximum protection of the drive and its internal components, Rockwell Automation prefers the use of fast acting
semiconductor fuses to other methods of circuit protection. This reduces risk of drive damage from power quality events, and
improves machine and process utilization, thus maximizing productivity.
11
Normal Duty
Drive Catalog
Number (1) (2)
kW
Cont. Output
Amps
20xC2P1
0.75
2.1
20xC3P5
1.5
3.5
External
Watts (3)
Internal
Watts (3)
16 (16)
26 (33)
External
Watts (3)
Drive Catalog
Number (1) (2)
Hp
Cont. Output
Amps
55 (56)
71 (72)
20xD2P1
1.0
2.1
17 (21)
60 (61)
77 (82)
57 (60)
83 (93)
20xD3P4
2.0
3.4
27 (39)
61 (64)
88 (103)
400 Volt
Internal
Watts (3)
Total
Watts (3)
480 Volt
20xC5P0
2.2
39 (44)
58 (62)
97 (106)
20xD5P0
3.0
41 (54)
63 (67)
104 (121)
20xC8P7
4.0
8.7
75 (79)
64 (80)
139 (159)
20xD8P0
5.0
71 (91)
68 (82)
139 (173)
20xC011
5.5
11.5
108 (107)
70 (85)
178 (192)
20xD011
7.5
11
108 (118)
74 (88)
182 (206)
20xC015
7.5
15.4
161 (166)
80 (80)
241 (246)
20xD014
10
14
149 (152)
81 (81)
230 (233)
20xC022
11
22
225
86
311
20xD022
15
22
237
91
328
20xC030
15
30
300
103
403
20xD027
20
27
273
101
374
20xC037
18.5
37
362
115
477
20xD034
25
34
368
115
483
20xC043
22
43
505
126
631
20xD040
30
40
503
126
629
20xC060
30
60
487
130
617
20xD052
40
52
422
125
547
20xC072
37
72
615
147
762
20xD065
50
65
559
144
703
20xC085
45
85
705
162
867
20xD077
60
77
646
158
804
20xC104
55
104
928
201
1129
20xD096
75
96
855
189
1044
20xC140
75
140
1239
319
1558
20xD125
100
125
1109
299
1408
20xC170
90
170
1381
300
1681
20xD156
125
156
1299
294
1593
20xC205
110
205
1893
381
2274
20xD186
150
186
1718
358
2076
20xC260
132
260
2449
502
2951
20xD248
200
248
2384
492
2876
20xC302
160
302
2566
461
3027
20xD302
250
302
2704
491
3195
20xC367
200
367
3322
586
3908
20xD361
300
361
3409
606
4015
20xC456
250
456
3922
743
4665
20xD415
350
415
3604
683
4287
2xGC460
250
460
4779
1090
5869
2xGD430
350
430
4385
971
5356
2xGC540
315
540
5316
1216
6532
2xGD485
400
485
5091
1126
6217
2xGC567
315
567
5652
1298
6950
2xGD545
450
545
5649
1253
6902
2xGC650
355
650
7011
1577
8588
2xGD617
500
617
6942
1489
8431
2xGC750
400
750
7577
1726
9303
2xGD710
600
710
7631
1659
9290
2xGC770
400
770
8086
1848
9934
2xGD740
650
740
8133
1776
9909
2xGC910
500
910
9155
2251
11406
2xGD800
700
800
8710
2216
10926
2xGC1K0
560
1040
9732
2357
12089
2xGD960
800
960
9696
2391
12087
2xGC1K1
630
1090
10745
2548
13293
2xGD1K0
900
1045
10784
2589
13373
2xGC1K2
710
1175
13778
2978
16756
2xGD1K2
1000
1135
13378
2899
16277
2xGC1K4
800
1465
13959
3013
16973
2xGD1K3
1100
1365
14055
3025
17080
2xGC1K5
850
1480
15441
3308
18749
2xGD1K4
1250
1420
15573
3314
18887
2xGC1K6
900
1590
15569
3717
19286
2xGD1K5
1350
1525
15619
3779
19398
2xGC2K1
1250
2150
22320
4790
27110
2xGD2K0
1750
2070
22495
4802
27297
12
Normal Duty
External
Watts
Internal
Watts
Total Watts
Drive Catalog
Number (1) (2)
Hp
Cont. Output
Amps
210
53
263
20xE1P7
1.7
279
28
15
43
60
339
20xE2P7
2.7
48
17
65
71
437
20xE3P9
3.9
62
19
81
77
485
20xE6P1
6.1
98
24
122
94
627
20xE009
7.5
147
31
178
597
104
701
20xE011
10
11
183
37
220
809
139
948
20xE017
15
17
297
58
355
471
Drive Catalog
Number (1) (2)
kW
Cont. Output
Amps
20xF012
7.5
12
20xF015
11
15
20xF020
15
20
366
20xF023
18.5
23
408
20xF030
22
30
533
20xF034
30
34
20xF046
37
46
690 Volt
External
Watts
Internal
Watts
Total
Watts
600 Volt
20xF050
45
50
873
152
1025
20xE022
20
22
391
80
20xF061
55
61
918
143
1061
20xE027
25
27
486
90
576
20xF082
75
82
1257
199
1456
20xE032
30
32
592
113
705
20xF098
90
98
1566
252
1818
20xE041
40
41
731
140
871
20xF119
110
119
1971
328
2299
20xE052
50
52
971
191
1162
20xF142
132
142
2379
418
2797
20xE063
60
63
936
147
1083
20xF171
160
171
3209
434
3643
20xE077
75
77
1157
184
1341
20xF212
200
212
4050
568
4618
20xE099
100
99
1561
253
1814
20xF263
250
263
5104
756
5860
20xE125
125
125
2058
349
2407
20xE144
150
144
2408
426
2834
20xE192
200
192
3537
492
4029
20xE242
250
242
4593
670
5263
20xE289
300
289
5602
857
6459
2xGF265
250
265
4314
996
5310
2xGE295
300
295
4592
1030
5622
2xGF330
315
330
5160
1127
6287
2xGE355
350
355
5191
1131
6321
2xGF370
355
370
5803
1233
7036
2xGE395
400
395
5812
1240
7052
2xGF415
400
415
5865
1211
7076
2xGE435
450
435
5590
1163
6753
2xGF460
450
460
6638
1337
7975
2xGE460
500
460
6407
1301
7708
2xGF500
500
500
7117
1417
8534
2xGE510
500
510
6946
1396
8342
2xGF590
560
590
8941
2077
11019
2xGE595
600
595
8903
2053
10956
2xGF650
630
650
9865
2220
12085
2xGE630
700
630
9942
2225
12167
2xGF710
710
710
11136
2425
13561
2xGE760
800
760
11093
2424
13517
2xGF765
750
765
11139
2368
13507
2xGE825
900
825
11046
2342
13389
2xGF795
800
795
12663
2611
15275
2xGE900
950
900
12225
2539
14764
2xGF960
900
860
13608
2767
16375
2xGE980
1000
980
13211
2709
15920
2xGF1K0
1000
1040
16147
3545
19692
2xGE1K1
1100
1110
16169
3552
19720
2xGF1K4
1400
1400
19716
4034
23750
2xGE1K4
1400
1430
19256
3966
23222
13
Normal Duty
Hp
Cont. Output
Amps
219
626
21GD430
350
430
177
652
540
256
735
21GD485
400
485
204
652
567
280
792
21GD545
450
545
239
725
355
650
359
1123
21GD617
500
617
295
983
21GC750
400
750
404
1549
21GD710
600
710
355
1410
21GC770
400
770
441
1692
21GD740
650
740
388
1542
Drive Catalog
Number (1)
kW
Cont. Output
Amps
21GC460
250
460
21GC540
315
21GC567
315
21GC650
400V
480V
690V
600V
21GF265
250
265
266
1090
21GE295
300
295
233
838
21GF330
315
330
304
1067
21GE355
350
355
289
902
21GF370
355
370
343
1288
21GE395
400
395
328
759
21GF415
400
415
379
1547
21GE435
450
435
354
1208
21GF460
450
460
240
1195
21GE460
500
460
379
1327
21GF500
500
500
251
1315
21GE510
500
510
246
775
14
Derating Guidelines
Ambient Temperature/Load and Altitude/Load - 400V AC
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Catalog
Number
Heavy Duty
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
8.7
5.0
4.0
2.2
Ambient Temperature/Load
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
20xC8P7
(Frame 1)
Normal Duty
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
5.5
11.5
4.0
8.7
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC011
(Frame 1)
50
30
20
60
50
40
10
30
20
40
7.5
15.4
5.5
11.5
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC015
(Frame 1)
50
30
20
60
50
40
10
30
20
40
7.5
15.4
5.5
11.5
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC015
(Frame 2)
50
30
20
60
50
40
10
30
20
40
11
22
7.5
15.4
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC022
50
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
15
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Normal Duty
Heavy Duty
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
20xC030
30
22
15
11
Ambient Temperature/Load
Altitude/Load
2 kHz
2 kHz
4 kHz
8 kHz
12 kHz
60
8 kHz
12 kHz
100
90
50
80
40
70
Load (%)
Max Ambient ( C)
4 kHz
30
20
60
50
40
10
30
20
40
20xC037
18.5
37
15
30
50
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
30
20
60
50
40
10
30
20
40
22
43
18.5
37
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC043
50
30
20
60
50
40
10
30
20
40
30
60
22
43
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC060
50
30
20
60
50
40
10
30
20
40
37
72
30
60
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC072
50
30
20
60
50
40
10
30
20
40
16
50
60
70
% Load
80
90
100
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Heavy Duty
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
20xC085
85
72
37
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
45
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
55
104
45
85
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC104
50
30
20
60
50
40
10
30
20
40
75
140
55
104
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC140
50
30
20
60
50
40
10
30
20
40
90
170
75
140
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC170
50
30
20
60
50
40
10
30
20
40
110
205
90
170
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC205
50
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
17
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Heavy Duty
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
20xC260
260
205
110
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
132
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
160
302
132
260
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC302
50
30
20
60
50
40
10
30
20
40
200
367
160
302
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC367
50
30
20
60
50
40
10
30
20
40
250
456
200
367
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xC456
50
30
20
60
50
40
10
30
20
40
2xGC460
315
540
250
460
200
385
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
18
50
60
70
% Load
80
90
100
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Normal Duty
Heavy Duty
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
2xGC540
315
585
540
456
315
250
Ambient Temperature/Load
Altitude/Load
2 kHz
2 kHz
4 kHz
8 kHz
12 kHz
60
8 kHz
12 kHz
100
90
50
80
40
70
Load (%)
Max Ambient ( C)
4 kHz
30
20
60
50
40
10
30
20
40
2xGC567
355
612
315
567
250
472
50
60
70
% Load
80
90
100
60
100
90
50
80
40
70
Load (%)
Max Ambient ( C)
30
20
60
50
40
10
30
20
40
2xGC650
400
750
355
650
315
540
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
2xGC750
450
796
400
750
315
585
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
2xGC770
450
832
400
770
355
642
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
2xGC910
560
1040
500
910
400
750
see 2xGC460
see 2xGC460
2xGC1K0
630
1090
560
1040
500
880
see 2xGC540
see 2xGC540
2xGC1K1
710
1175
630
1090
500
910
see 2xGC567
see 2xGC567
19
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Normal Duty
Heavy Duty
Ambient Temperature/Load
Altitude/Load
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
2xGC1K2
800
1465
710
1175
560
1040
see 2xGC650
see 2xGC650
2xGC1K4
850
1480
800
1465
630
1090
see 2xGC750
see 2xGC750
2xGC1K5
900
1600
850
1480
710
1175
see 2xGC770
see 2xGC770
2xGC1K6
1000 1715
900
1590
710
1325
see 2xGC567
see 2xGC567
2xGC2K1
1400 2330
1250 2150
1000 1800
see 2xGC770
see 2xGC770
2 kHz
2 kHz
4 kHz
8 kHz
12 kHz
4 kHz
8 kHz
12 kHz
Catalog
Number
Heavy Duty
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
Ambient Temperature/Load
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
20xD8P0
(Frame 1)
Normal Duty
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
7.5
11
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD011
(Frame 1)
50
30
20
60
50
40
10
30
20
40
10
14
7.5
11
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD014
(Frame 1)
50
30
20
60
50
40
10
30
20
40
20
50
60
70
% Load
80
90
100
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Catalog
Number
Heavy Duty
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
14
11
10
7.5
Ambient Temperature/Load
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
20xD014
(Frame 2)
Normal Duty
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
15
22
10
14
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD022
50
30
20
60
50
40
10
30
20
40
20
27
15
22
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD027
50
30
20
60
50
40
10
30
20
40
25
34
20
27
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD034
50
30
20
60
50
40
10
30
20
40
30
40
25
34
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD040
50
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
21
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Heavy Duty
Catalog
Number
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
20xD052
52
40
30
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
40
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
50
65
40
52
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD065
50
30
20
60
50
40
10
30
20
40
60
77
50
65
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD077
50
30
20
60
50
40
10
30
20
40
75
96
60
77
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD096
50
30
20
60
50
40
10
30
20
40
100
125
75
96
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD125
50
30
20
60
50
40
10
30
20
40
22
50
60
70
% Load
80
90
100
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Heavy Duty
Catalog
Number
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
20xD156
156
125
100
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
125
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
150
186
125
156
60
70
% Load
80
90
100
60
100
50
90
500
80
40
70
Load (%)
Max Ambient ( C)
20xD186
50
30
20
60
50
40
10
30
20
40
20xD248
200
248
150
186
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
250
302
200
248
60
70
% Load
80
90
100
60
100
50
90
1000
1500
2000
2500 3000
Altitude (m)
3500
4000
4500
4800
80
40
70
Load (%)
Max Ambient ( C)
20xD302
50
30
20
60
50
40
10
30
20
40
300
361
250
302
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xD361
50
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
23
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Heavy Duty
Catalog
Number
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
20xD415
415
361
300
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
350
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
2xGD430 400
485
350
430
300
370
50
60
70
% Load
80
90
100
60
100
90
50
80
40
70
Load (%)
Max Ambient ( C)
30
20
60
50
40
10
30
20
40
2xGD485 450
545
400
485
350
414
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
2xGD545 500
590
450
545
350
454
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
2xGD617 600
710
500
617
400
485
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
24
50
60
70
% Load
80
90
100
Derating for IP20 NEMA/UL Type Open (Frames 15), IP00 NEMA/UL Type Open (Frames 67) and
IP20 NEMA/UL Type 1 (Frames 810)
Hp
2xGD710 650
Normal Duty
Heavy Duty
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
765
710
545
600
450
Ambient Temperature/Load
Altitude/Load
2 kHz
2 kHz
4 kHz
8 kHz
12 kHz
60
8 kHz
12 kHz
100
90
50
80
40
70
Load (%)
Max Ambient ( C)
4 kHz
30
20
60
50
40
10
30
20
40
2xGD740 700
800
650
740
500
617
50
60
70
% Load
80
90
100
60
100
90
50
80
40
70
Load (%)
Max Ambient ( C)
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
2xGD800 800
960
700
800
600
710
see 2xGD430
see 2xGD430
2xGD960 900
1045
800
960
700
795
see 2xGD485
see 2xGD485
900
1045
750
800
see 2xGD545
see 2xGD545
1000 1135
800
960
see 2xGD617
see 2xGD617
1100 1365
900
1045
see 2xGD710
see 2xGD710
1250 1420
1000 1135
see 2xGD740
see 2xGD740
1350 1525
1100 1270
see 2xGD545
see 2xGD545
1750 2070
1650 1730
see 2xGD740
see 2xGD740
25
Heavy Duty
Catalog
Number
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
20xE022
22
17
15
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
20
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
25
27
20
22
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xE027
50
30
20
60
50
40
10
30
20
40
30
32
20
27
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
Max Ambient ( C)
20xE032
50
30
20
60
50
40
10
30
20
40
355
300
295
250
272
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
350
Max Ambient ( C)
2xGE295
50
30
20
60
50
40
10
30
20
40
395
350
355
300
295
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
400
Max Ambient ( C)
2xGE355
50
30
20
60
50
40
10
30
20
40
26
50
60
70
% Load
80
90
100
Heavy Duty
Catalog
Number
Hp
Cont.
Amps Hp
Cont.
Amps Hp
Cont.
Amps
2xGE395
450
435
395
329
350
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
400
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
460
450
435
350
355
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
500
Max Ambient ( C)
2xGE435
50
30
20
60
50
40
10
30
20
40
2xGE460
500
510
500
460
400
395
50
60
70
% Load
80
90
100
60
100
90
80
40
70
Load (%)
Max Ambient ( C)
50
30
20
60
50
40
10
30
20
40
545
500
510
450
425
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
550
Max Ambient ( C)
2xGE510
50
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
2xGE595
700
595
600
595
500
510
see 2xGE295
see 2xGE295
2xGE630
800
760
700
630
600
595
see 2xGE355
see 2xGE355
2xGE760
900
835
800
760
700
630
see 2xGE395
see 2xGE395
2xGE825
950
900
900
825
750
700
see 2xGE435
see 2xGE435
2xGE900
1000 980
950
900
800
760
see 2xGE460
see 2xGE460
2xGE980
1100 1045
1000 980
900
815
see 2xGE510
see 2xGE510
2xGE1K1
1200 1220
1100 1110
1000 920
see 2xGE395
see 2xGE395
2xGE1K4
1500 1530
1400 1430
1250 1190
see 2xGE510
see 2xGE510
27
Heavy Duty
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
2xGF265
315
330
265
215
200
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
250
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
370
315
330
250
265
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
355
Max Ambient ( C)
2xGF330
50
30
20
60
50
40
10
30
20
40
410
355
370
300
308
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
400
Max Ambient ( C)
2xGF370
50
30
20
60
50
40
10
30
20
40
460
400
415
355
370
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
450
Max Ambient ( C)
2xGF415
50
30
20
60
50
40
10
30
20
40
500
450
460
375
375
60
70
% Load
80
90
100
60
100
50
90
80
40
70
Load (%)
500
Max Ambient ( C)
2xGF460
50
30
20
60
50
40
10
30
20
40
28
50
60
70
% Load
80
90
100
Heavy Duty
Catalog
Number
kW
Cont.
Amps kW
Cont.
Amps kW
Cont.
Amps
2xGF500
530
530
500
413
400
Altitude/Load
2 kHz
2 kHz
Max Ambient ( C)
500
Ambient Temperature/Load
4 kHz
8 kHz
12 kHz
4 kHz
60
100
50
90
8 kHz
12 kHz
80
40
70
Load (%)
Light Duty
30
20
60
50
40
10
30
20
40
50
60
70
% Load
80
90
100
2xGF590
630
650
560
590
450
460
see 2xGF265
see 2xGF265
2xGF650
710
710
630
650
500
500
see 2xGF330
see 2xGF330
2xGF710
800
790
710
710
560
590
see 2xGF370
see 2xGF370
2xGF765
850
860
750
765
630
650
see 2xGF415
see 2xGF415
2xGF795
900
960
800
795
710
750
see 2xGF460
see 2xGF460
2xGF960
1000 1020
900
960
800
795
see 2xGF500
see 2xGF500
2xGF1K0
1100 1150
1000 1040
900
865
see 2xGF370
see 2xGF370
2xGF1K4
1500 1485
1400 1400
1120 1160
see 2xGF500
see 2xGF500
29
480V
Frame
ND kW
Catalog Code
Minimum Resistance
Maximum DB Current
ND Hp
Catalog Code
Minimum Resistance
Maximum DB Current
0.75
C2P1
79.0
10
1.0
D2P1
79.0
10
1.5
C3P5
79.0
10
2.0
D3P4
79.0
10
2.2
C5P0
79.0
10
3.0
D5P0
79.0
10
4.0
C8P7
52.7
15
5.0
D8P0
52.7
15
5.5
C011
31.6
25
7.5
D011
31.6
25
7.5
C015
31.6
25
10
D014
31.6
25
0.75
C2P1
31.6
25
1.0
D2P1
31.6
25
1.5
C3P5
31.6
25
2.0
D3P4
31.6
25
2.2
C5P0
31.6
25
3.0
D5P0
31.6
25
4.0
C8P7
31.6
25
5.0
D8P0
31.6
25
5.5
C011
31.6
25
7.5
D011
31.6
25
7.5
C015
31.6
25
10
D014
31.6
25
11
C022
22.6
34.9
15
D022
22.6
34.9
15
C030
31.6
25
20
D027
31.6
25
18.5
C037
31.6
25
25
D034
31.6
25
22
C043
16.6
47.6
30
D040
16.6
47.6
30
C060
15.8
50
40
D052
15.8
50
37
C072
15.8
50
50
D065
15.8
50
37 (1)
C072
7.9
100
50 (1)
D065
7.9
100
45
C085
7.9
100
60
D077
7.9
100
55
C104
7.9
100
75
D096
7.9
100
55 (1)
C104
3.3
239.4
75 (1)
D096
3.3
239.4
75
C140
3.3
239.4
100
D125
3.3
239.4
90
C170
3.3
239.4
125
D156
3.3
239.4
110
C205
3.3
239.4
150
D186
3.3
239.4
132
C260
3.3
239.4
200
D248
3.3
239.4
132 (1)
C260
2.4
329
200 (1)
D248
2.4
329
160
C302
2.4
329
250
D302
2.4
329
200
C367
2.4
329
300
D361
2.4
329
250
C456
1.65
478.8
350
D415
1.65
478.8
30
Enclosure
Catalog Code
25
67
Enclosure Type
Installation Type
UL Certification Required
IP20
NEMA/UL Open Type
IP20
NEMA/UL Open Type
Flange
IP20
NEMA/UL Open Type
Flange
IP54
NEMA/UL Type 12
IP00
NEMA/UL Open Type
UL Certification
Not Required
All devices listed on pages
32 through 44 are
acceptable.
810
IP54
NEMA/UL Type 12
B, L, P, W
IP20
NEMA/UL Type 1
J, K, Y
IP54
NEMA/UL Type 12
Fusing
If fuses are chosen as the desired protection method, refer to the recommended types listed below. If available amp ratings
do not match the tables provided, the closest fuse rating that exceeds the drive rating should be chosen.
IEC BS88 (British Standard) Parts 1 & 2 (1), EN60269-1, Parts 1 & 2, type gG or equivalent should be used.
UL UL Class T, J or L should be used.
Circuit Breakers
The non-fuse listings in the following tables include both circuit breakers (inverse time or instantaneous trip). If one of
these is chosen as the desired protection method, the following requirements apply.
IEC and UL Both types of devices are acceptable for IEC and UL installations.
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.
31
32
0.75 kW
1.5 kW
2.2 kW
4.0 kW
5.5 kW
5.5 kW
7.5 kW
11 kW
30 kW
37 kW
45 kW
55 kW
75 kW
90 kW
110 kW
132 kW
160 kW
200 kW
250 kW
20xC367 403.7
20xC456 501.6
456
20xC302 332.2
20xC260 286.0
20xC205 225.5
20xC170 187.0
20xC140 154.0
20xC104 114.4
20xC085 93.5
20xC072 79.2
20xC060 66.0
20xC043 47.3
20xC037 40.7
20xC030 33.0
20xC022 24.2
20xC015 16.9
20xC011 17.2
20xC8P7 13.0
20xC5P0 7.5
20xC3P5 5.2
20xC2P1 3.1
20xC015 16.9
20xC011 12.7
20xC8P7 9.6
20xC5P0 5.5
20xC3P5 3.9
20xC2P1 2.3
367
302
260
205
170
140
104
85
72
60
43
37
30
22
15.4
11.5
8.7
3.5
2.1
15.4
11.5
8.7
3.5
2.1
684.0
550.5
453.0
390.0
307.5
255.0
210.0
156.0
127.5
108.0
90.0
64.5
55.5
45.0
33.0
23.1
20.7
15.6
9.0
6.3
3.7
23.1
17.3
13.1
7.5
5.3
3.2
20xC456 550.5
20xC367 453.0
20xC302 390.0
20xC260 307.5
20xC205 255.0
20xC170 210.0
20xC140 156.0
20xC104 127.5
20xC085 108.0
20xC072 90.0
20xC060 66.0
20xC043 55.5
20xC037 45.0
20xC030 33.0
20xC022 24.2
20xC011 17.2
20xC8P7 13.0
20xC5P0 7.5
20xC3P5 5.2
20xC2P1 3.1
20xC022 17.3
20xC011 13.1
20xC8P7 9.6
20xC5P0 5.5
20xC3P5 3.9
20xC2P1 2.3
(x = F or G) 1 min
3 sec
1 min
684.0
550.5
468.0
390.0
307.5
255.0
210.0
156.0
129.6
108.0
90.0
66.6
55.5
45.0
33.0
20.7
15.6
9.0
6.3
3.7
23.1
17.3
13.1
7.5
5.3
3.2
3 sec
Output
Overload
Amps
Catalog
Number
Output
Overload
Amps
309.5
249.1
205.0
176.5
139.1
115.4
95.0
71.3
57.7
48.9
39.8
28.5
24.5
19.9
14.6
10.1
7.4
5.4
3.1
1.9
1.2
10.1
7.4
5.4
3.1
1.9
1.2
kVA
446.7
359.5
295.9
254.7
200.8
166.5
137.2
102.9
83.3
70.5
57.4
41.2
35.4
28.7
21.1
14.6
10.7
7.8
4.5
2.8
1.7
14.6
10.7
7.8
4.5
2.8
1.7
600
475
400
325
275
225
175
130
110
90
75
55
45
40
30
20
15
10
20
15
10
1000
800
675
575
450
375
300
225
175
150
125
90
80
60
45
30
25
17.5
10
25
20
15
600
475
400
325
275
225
175
130
110
90
75
55
45
40
30
20
15
10
20
15
10
1800
1000
900
750
600
600
550
400
325
275
225
150
125
120
80
60
45
30
20
12
25
20
15
Amps
Non-Time
Delay Fuse
Dual Element
Continuous AC Time Delay
Input
Fuse
Input
Drive Sized For Normal Duty Drive Sized For Heavy Duty Quantities
Cont. Catalog
Output Number
Amps (x = F or G)
22 kW
4.0 kW
2.2 kW
18.5 kW
1.5 kW
15 kW
0.75 kW
Applied
Rating (1)
7.5 kW
Frame (2)
1300
1100
900
700
600
500
400
300
250
200
180
120
110
100
80
60
45
30
20
15
15
60
45
30
20
15
15
600
600
600
400
400
250
250
150
150
100
100
60
50
50
30
20
15
15
20
15
15
M-F8E-C45
M-F8E-C32
M-C2E-B63 M-D8E-B63
M-C2E-B40 M-D8E-B40
M-C2E-B25 M-D8E-B25
Circuit Motor
Breaker Circuit
Max Size Protector 140M Motor Starter with Adjustable
(5)
(6)
Current Range (7) (8)
DC Input
Protection (9)
281.9
226.9
186.7
160.7
126.7
105.1
86.5
64.9
52.5
44.5
36.2
26.0
22.3
18.1
13.3
9.2
6.8
5.0
2.9
2.0
1.1
9.2
6.8
5.0
2.9
2.0
1.1
522.0
420.2
345.7
297.7
234.7
194.6
160.3
120.2
97.3
82.4
67.1
48.1
41.4
33.6
24.6
17.0
12.6
9.3
5.3
3.7
2.1
17.0
12.6
9.3
5.3
3.7
2.1
Bussman 170M6613
Bussman 170M6612
Bussman 170M6608
HSJ400
HSJ350
HSJ350
HSJ250
HSJ175
HSJ150
HSJ125
HSJ100
HSJ90
HSJ70
HSJ50
HSJ40
HSJ25
HSJ20
HSJ15
JKS-10
JKS-8
JKS-6
HSJ25
HSJ20
HSJ15
JKS-10
JKS-8
JKS-6
Continuous DC
Input
Non-Time Delay
kW
Amps Fuse
Input
Quantities
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a C022 drive can be used in Normal Duty mode on a 11 kW motor, or in Heavy Duty mode on a 7.5 kW motor. A C015 drive can be used in Heavy Duty mode on a 5.5 kW motor with
the same ratings as a C011. The drive can be programmed for either mode. Wiring and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with
respect to Heavy Duty mode. See parameter 306 [Duty Rating].
(2) Enclosure codes F, N, and R only. See Frame/Rating Cross-Reference in PowerFlex 750-Series AC Drives Technical Data, publication 750-TD001, for frame sizes of other enclosure types.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
(7) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(8) Manual Self-Protected (Type E) Combination Motor Controller. 480Y/277V and 600Y/347V AC Input.
(9) See Fuse Certification and Test Data in PowerFlex AC Drives in Common Bus Configurations Application Guidelines, publication DRIVES-AT002, for fuse self-certification and test data for Bussmann 170M and JKS fuses recommended for the DC bus fusing.
33
34
400 kW
450 kW
400 kW
500 kW
560 kW
630 kW
Light
Normal
Heavy
1090
1090
Heavy
1040
1090
Light
Normal
Normal
910
1040
Heavy
910
1040
Heavy
Heavy
880
750
Light
Light
832
832
Normal
770
Light
Normal
750
796
Light
Heavy
750
20GC650
Normal
650
642
20GC1K4
20GC1K1
20GC1K0
20GC1K2
20GC1K0
20GC910
20GC910
20GC1K1
20GC1K0
20GC910
20GC770
20GC770
20GC750
20GC770
20GC750
20GC650
20GC770
20GC567
20GC750
20GC567
20GC540
20GC650
20GC540
20GC460
20GC567
20GC540
20GC460
20GC460
Catalog
Number
Light
Heavy
585
612
Light
Normal
585
540
567
Normal
Heavy
540
Light
Heavy
472
540
Normal
Heavy
460
Heavy
Duty
456
385
Cont.
Output
Amps
continued on page 35
355 kW
315 kW
250 kW
315 kW
200 kW
Applied
Rating (1)
Frame
1635
1199
1199
1560
1144
1144
1001
1365
1320
1125
915
915
876
847
825
825
963
715
673
878
624
644
810
594
594
708
684
506
578
1 min
2198
1638
1872
1584
1365
1638
1584
1365
1155
1125
1155
975
1125
851
975
821
851
821
693
693
3 sec
1073
1073
1073
1024
1024
1024
896
896
867
739
819
819
784
758
739
739
634
640
604
577
560
578
533
533
534
466
450
455
380
Amps
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
Amps
1300
1300
1400 (3)
1400 (3)
1400 (3)
1400
(3)
1350
1350
1350
1300
1400 (3)
1400
1100
(3)
1100
1400 (3)
1100
1400 (3)
1400
900
1400 (3)
(3)
1100
1100
1000
1000
1000
1000
800
850
800
750
750
750
700
700
700
600
600
600
500
675
675
675
650
650
650
550
550
550
450
550
550
500
500
500
500
400
425
400
375
375
375
350
350
2400
2400
2400
2300
2300
2300
2000
2000
2000
1700
1800
1800
1700
1700
1600
1600
1400
1400
1300
1300
1200
1300
1200
1200
1200
1000
1000
1000
850
1/Phase 2/Phase
Min (4) Min (4) Max (5)
Dual Element
Time Delay Fuse
1350
1350
1350
1300
1300
1300
1100
1100
1100
900
1100
1100
1000
1000
1000
1000
800
850
800
750
750
750
700
700
700
600
600
600
500
675
675
675
650
650
650
550
550
550
450
550
550
500
500
500
500
400
425
400
375
375
375
350
350
3200
3200
3200
3100
3100
3100
2700
2700
2600
2200
2400
2400
2300
2300
2200
2200
1900
1900
1800
1700
1700
1700
1600
1600
1600
1400
1300
1300
1100
1/Phase 2/Phase
Min (4) Min (4) Max (5)
3200
3200
3200
3100
3100
3100
2700
2700
2600
2200
2400
2400
2300
2300
2200
2200
1900
1900
1800
1700
1700
1700
1600
1600
1600
1400
1300
1300
1100
Circuit
Breaker Max
Size (6)
Amps
DC Bay to Bay
AC Input Integral Integral
Semiconductor
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2) Fuse Size (170M)
400 Volt AC and 540 Volt DC Input Protection Devices - Frames 810
1350
1350
1350
1300
1300
1300
1100
1100
1100
900
1200
1200
1000
1000
1000
1000
800
800
800
800
700
800
700
700
700
600
600
600
500
Motor Circuit
Protector (7)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
540V DC Input
Amps
DC Input Integral
Semiconductor
Fuse Size (170M) (8)
Heavy
1175
10
1250 kW
Normal
Heavy
1800
2150
Light
1715
Normal
20GC2K1
20GC2K1
20GC1K6
20GC1K6
20GC1K5
20GC1K5
20GC1K4
20GC1K4
20GC1K2
20GC1K6
20GC1K5
20GC1K2
20GC1K1
Catalog
Number
2365
2700
1887
1749
1760
1628
1628
1612
1612
1988
1763
1293
1293
1 min
3240
3240
2058
2385
2220
2198
2385
2220
1872
3 sec
2117
1773
1689
1566
1576
1457
1457
1443
1443
1305
1157
1157
1157
Amps
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
Amps
1400 (3)
1400
2650
2200
(3)
2100
1400 (3)
1950
1400 (3)
1400
1950
(3)
1800
1400 (3)
1400 (3)
1800
1800
1800
(3)
1650
1450
1400 (3)
1400
1400
(3)
1400 (3)
1400
1450
1400 (3)
(3)
1450
1400 (3)
Amps
1325
1100
1050
975
975
900
900
900
900
825
725
725
725
4800
4000
3800
3500
3500
3300
3300
3200
3200
2900
2600
2600
2600
1/Phase 2/Phase
Min (4) Min (4) Max (5)
Dual Element
Time Delay Fuse
2650
2200
2100
1950
1950
1800
1800
1800
1800
1650
1450
1450
1450
1325
1100
1050
975
975
900
900
900
900
825
725
725
725
6400
5300
5100
4700
4700
4400
4400
4300
4300
3900
3500
3500
3500
1/Phase 2/Phase
Min (4) Min (4) Max (5)
6400
5300
5100
4700
4700
4400
4400
4300
4300
3900
3500
3500
3500
Circuit
Breaker Max
Size (6)
2650
2200
2100
1950
1950
1800
1800
1800
1800
1650
1450
1450
1450
Motor Circuit
Protector (7)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
540V DC Input
Amps
DC Input Integral
Semiconductor
Fuse Size (170M) (8)
1400 kW 10 2330
Light
20GC2K1 2563
2796
2294
1100
2850
1425
5200
2850
1425
6900
6900
2850
1600 (3)
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a C460 drive can be used in Normal Duty mode on a 250 kW motor, in Heavy Duty mode on a 200 kW motor or in Light Duty mode on a 315 kW motor. The drive can be programmed
for each mode. Wiring and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with respect to Heavy Duty mode. See parameter 306 [Duty Rating].
Refer to Specifications for an explanation of Duty Ratings.
(2) These AC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection. AC input protection devices for branch circuit protection based on US NEC are listed in the table. Each drive bay has one fuse per phase.
(3) Each drive bay has one fuse per DC line.
(4) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(5) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(7) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
(8) These DC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection.
10
1000 kW
1590
10
Light
Normal
1600
1480
900 kW
Light
1480
Normal
1465
850 kW
Light
1465
Heavy
Normal
1175
1325
Light
Duty
1175
10
Cont.
Output
Amps
800 kW
710 kW
Applied
Rating (1)
Frame
DC Bay to Bay
AC Input Integral Integral
Semiconductor
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2) Fuse Size (170M)
35
36
200 Hp
250 Hp
300 Hp
350 Hp
20xD361
20xD415
415
20xD302
20xD248
20xD186
20xD156
20xD125
20xD096
20xD077
20xD065
20xD052
20xD040
20xD034
20xD027
20xD022
20xD014
20xD011
20xD8P0
20xD5P0
20xD3P4
20xD2P1
20xD014
20xD011
20xD8P0
20xD5P0
20xD3P4
20xD2P1
361
302
248
186
156
125
96
77
65
52
40
34
27
22
14
11
3.4
2.1
14
11
3.4
2.1
456.5
397.1
332.2
272.8
204.6
171.6
137.5
105.6
84.7
71.5
57.2
44.0
37.4
29.7
24.2
15.4
16.5
12.0
7.5
5.1
3.1
15.4
12.1
8.8
5.5
3.7
2.3
20xD077 97.5
20xD065 78.0
20xD052 60.0
20xD040 51.0
20xD034 40.5
20xD027 33.0
20xD022 24.2
20xD011 16.5
20xD8P0 12.0
20xD5P0 7.5
20xD3P4 5.1
20xD2P1 3.1
20xD022 16.5
20xD011 12.1
20xD8P0 8.8
20xD5P0 5.5
20xD3P4 3.7
39.7
30.5
25.9
20.6
16.6
10.4
7.9
5.7
3.2
2.2
1.3
10.4
7.9
5.7
3.2
2.2
1.3
117.0 49.6
97.5
78.0
61.2
51.0
40.5
33.0
19.8
14.4
9.0
6.1
3.7
21.0
16.5
12.0
7.5
5.1
3.2
117.4
90.1
72.3
59.6
47.7
36.7
31.2
24.8
19.9
12.5
9.5
6.9
3.9
2.6
1.6
12.5
9.5
6.9
3.9
2.6
1.6
622.5
323.9 389.6
525
475
400
325
250
200
175
125
100
90
65
50
45
35
30
20
12
10
20
15
10
900
800
675
550
400
350
275
200
170
125
110
90
75
60
50
30
20
17.5
10
25
20
15
525
475
400
325
250
200
175
125
100
90
65
50
45
35
30
20
12
10
20
15
10
1200
1000
900
700
600
600
500
375
300
250
200
150
125
100
80
55
40
30
20
12
25
20
15
Amps
97.5
78.0
60.0
51.0
40.5
33.0
21.0
19.8
14.4
9.0
6.1
3.7
21.0
16.5
12.0
7.5
5.1
3.2
Dual Element
Continuous AC Time Delay
Non-Time
Input
Fuse
Delay Fuse
Input
Quantities
Output
Overload
Amps
20xD2P1 2.3
(x = F or G)
1 min
3 sec
Catalog
Number
Output
Overload
Amps
Cont. Catalog
Output Number
Amps (x = F or G)
150 Hp
50 Hp
40 Hp
30 Hp
125 Hp
25 Hp
100 Hp
20 Hp
15 Hp
10 Hp
75 Hp
7.5 Hp
60 Hp
2.0 Hp
5.0 Hp
1.0 Hp
3.0 Hp
7.5 Hp
10 Hp
2.0 Hp
1.0 Hp
5.0 Hp
Applied
Rating (1)
3.0 Hp
Frame (2)
1200
1000
900
700
550
450
375
275
225
175
150
120
100
100
80
50
40
30
20
15
15
50
40
30
20
15
15
600
600
600
400
250
250
250
125
100
100
70
50
50
50
30
20
15
15
20
15
15
M-C2E-C25 M-D8E-C25
M-C2E-C16 M-D8E-C16
M-C2E-C16 M-D8E-C16
M-C2E-C10 M-D8E-C10
M-C2E-B63 M-D8E-B63
M-C2E-B40 M-D8E-B40
M-C2E-B25 M-D8E-B25
CMN-9000
CMN-9000
M-F8E-C45 CMN-9000
M-F8E-C45 CMN-6300
M-F8E-C32 CMN-4000
M-F8E-C25 CMN-4000
M-F8E-C16 CMN-4000
M-F8E-C16 CMN-2500
M-F8E-C10
Circuit Motor
Breaker Circuit
Protector 140M Motor Starter with Adjustable Current
Max
Range (7) (8)
Size (5) (6)
DC Input
Protection (9)
295.0
256.6
214.7
176.3
132.2
110.9
88.9
68.3
54.7
45.1
36.1
27.8
23.6
18.8
15.1
9.5
7.2
5.2
2.9
1.9
1.2
9.5
7.2
5.2
2.9
1.9
1.2
455.3
396.1
331.3
272.1
204.1
171.2
137.1
105.3
84.5
69.7
55.7
42.9
36.4
28.9
23.3
14.7
11.1
8.1
4.5
3.0
1.9
14.7
11.1
8.1
4.5
3.0
1.9
Bussman 170M6612
Bussman 170M6612
Bussman 170M6608
HSJ400
HSJ400
HSJ300
HSJ200
HSJ175
HSJ150
HSJ100
HSJ90
HSJ80
HSJ60
HSJ50
HSJ40
HSJ30
HSJ20
HSJ15
JKS-10
JKS-6
JKS-6
HSJ30
HSJ20
HSJ15
JKS-10
JKS-6
JKS-6
Continuous DC
Input
Non-Time Delay
kW
Amps Fuse
Input
Quantities
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a D022 drive can be used in Normal Duty mode on a 15 Hp motor, or in Heavy Duty mode on a 10 Hp motor. A D014 drive can be used in Heavy Duty mode on a 7.5 Hp motor with
the same ratings as a D011. The drive can be programmed for either mode. Wiring and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with
respect to Heavy Duty mode. See parameter 306 [Duty Rating].
(2) Enclosure codes F, N, and R only. See Frame/Rating Cross-Reference in PowerFlex 750-Series AC Drives Technical Data, publication 750-TD001, for frame sizes of other enclosure types.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
(7) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(8) Manual Self-Protected (Type E) Combination Motor Controller. 480Y/277V and 600Y/347V AC Input.
(9) See Fuse Certification and Test Data in PowerFlex AC Drives in Common Bus Configurations Application Guidelines, publication DRIVES-AT002, for fuse self-certification and test data for Bussmann 170M and JKS fuses recommended for the DC bus fusing.
37
38
Heavy
454
Normal
Heavy
1045
1045
Heavy
960
Light
Normal
960
1045
Light
960
Heavy
Normal
800
800
Heavy
Heavy
795
710
Light
Normal
800
Light
740
Normal
710
765
Light
Heavy
617
710
Normal
617
Heavy
545
Light
Normal
590
Light
545
Heavy
485
545
Normal
485
Light
Heavy
485
Normal
414
Heavy
Duty
430
370
Cont.
Output
Amps
continued on page 39
900 Hp
700 Hp
600 Hp
700 Hp
800 Hp
650 Hp
750 Hp
600 Hp
400 Hp
350 Hp
500 Hp
300 Hp
Applied
Rating (1)
450 Hp
Frame
20GD1K3
20GD1K0
20GD960
20GD1K2
20GD960
20GD800
20GD1K0
20GD800
20GD960
20GD800
20GD740
20GD740
20GD710
20GD710
20GD617
20GD740
20GD617
20GD545
20GD710
20GD545
20GD485
20GD617
20GD485
20GD430
20GD545
20GD485
20GD430
20GD430
Catalog
Number
1568
1150
1150
1440
1056
1056
1200
880
1193
1065
880
814
842
781
781
926
679
649
818
600
600
728
534
534
681
621
473
555
1 min
2048
1568
1728
1440
1568
1278
1440
1278
1110
1065
1110
926
1065
818
926
745
818
745
666
666
3 sec
986
986
986
906
906
906
755
755
750
670
755
698
722
670
670
582
582
557
514
514
514
458
458
458
428
391
406
349
Amps
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
Amps
950
950
1150
1150
1400 (3)
1400 (3)
1400 (3)
1400 (3)
1400
1250
1250
1400 (3)
(3)
1250
1400 (3)
1150
950
1400 (3)
1400
850
1400 (3)
(3)
1000
900
1000
850
850
750
750
700
650
650
650
600
600
600
550
500
550
450
625
625
625
575
575
575
475
475
475
425
500
450
500
425
425
375
325
325
2200
2200
2200
2000
2000
2000
1700
1700
1700
1500
1800
1600
1700
1500
1500
1300
1300
1300
1200
1200
1200
1000
1000
1000
1000
900
900
800
1/Phase 2/Phase
Min (4)
Max (5)
Min (4)
Dual Element
Time Delay Fuse
1250
1250
1250
1150
1150
1150
950
950
950
850
1000
900
1000
850
850
750
750
700
650
650
650
600
600
600
550
500
550
450
1/Phase
Min (4)
625
625
625
575
575
575
475
475
475
425
500
450
500
425
425
375
325
325
3000
3000
3000
2700
2700
2700
2300
2300
2300
2000
1800
2200
2200
2100
2100
2400
1800
1700
1600
1600
1600
1400
1400
1400
1300
1200
1200
1100
2/Phase
Max (5)
Min (4)
3000
3000
3000
2700
2700
2700
2300
2300
2300
2000
2400
2200
2200
2100
2100
1800
1800
1700
1600
1600
1600
1400
1400
1400
1300
1200
1200
1100
Circuit
Breaker Max
Size (6)
Amps
DC Bay to Bay
AC Input Integral Integral
Semiconductor
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2) Fuse Size (170M)
480 Volt AC and 650 Volt DC Input Protection Devices - Frames 810
1250
1250
1250
1150
1150
1150
950
950
950
850
1000
900
1000
900
900
800
800
700
650
650
650
600
600
600
550
500
550
450
Motor Circuit
Protector (7)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
Amps
DC Input Integral
Semiconductor Fuse
Size (170M) (8)
1350 Hp
Normal
10 1730
10 2070
1650 Hp
1750 Hp
Normal
Heavy
Light
20GD2K0
20GD2K0
20GD1K5
20GD1K5
20GD1K4
20GD1K4
20GD1K3
20GD1K5
20GD1K3
20GD1K2
20GD1K4
20GD1K2
20GD1K0
Catalog
Number
2277
2595
1821
1678
1694
1562
1562
1905
1502
1502
1703
1249
1249
1 min
3114
3114
1986
2288
2130
2288
2048
2130
1728
3 sec
1953
1633
1562
1439
1453
1340
1340
1199
1288
1288
1071
1071
1071
Amps
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
Amps
1400 (3)
1400
2450
2050
(3)
1950
1400 (3)
1800
1400 (3)
1400
1800
1400 (3)
(3)
1700
1400 (3)
1500
1600
1700
(3)
1600
1350
1400 (3)
1400
1400
(3)
1400 (3)
1400
1350
1400 (3)
(3)
1350
1400 (3)
Amps
1225
1025
975
900
900
850
850
750
800
800
675
675
675
4400
3700
3500
3200
3300
3000
3000
2700
2900
2900
2400
2400
2400
1/Phase 2/Phase
Min (4)
Min (4)
Max (5)
Dual Element
Time Delay Fuse
2450
2050
1950
1800
1800
1700
1700
1500
1600
1600
1350
1350
1350
1/Phase
Min (4)
1225
1025
975
900
900
850
850
750
800
800
675
675
675
5900
4900
4700
4300
4400
4000
4000
3600
3900
3900
3200
3200
3200
2/Phase
Min (4)
Max (5)
5900
4900
4700
4300
4400
4000
4000
3600
3900
3900
3200
3200
3200
Circuit
Breaker Max
Size (6)
2450
2050
1950
1800
1800
1700
1700
1500
1600
1600
1350
1350
1350
Motor Circuit
Protector (7)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
1600 (3)
Amps
DC Input Integral
Semiconductor Fuse
Size (170M) (8)
2000 Hp 10 2240
Light
20GD2K0 2464
2688
2114
1100
2650
1325
4800
2650
1325
6300
6300
2650
1600 (3)
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a D430 drive can be used in Normal Duty mode on a 350 Hp motor, in Heavy Duty mode on a 300 Hp motor or in Light Duty mode on a 400 Hp motor. The drive can be programmed
for each mode. Wiring and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with respect to Heavy Duty mode. See parameter 306 [Duty Rating].
Refer to Specifications for an explanation of Duty Ratings.
(2) These AC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection. AC input protection devices for branch circuit protection based on US NEC are listed in the table. Each drive bay has one fuse per phase.
(3) Each drive bay has one fuse per DC line.
(4) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(5) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(7) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
(8) These DC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection.
10 1655
1500 Hp
Normal
Light
1420
1540
Light
1420
10 1525
1250 Hp
Heavy
Heavy
1135
10 1270
Normal
1135
Normal
1100 Hp
Light
1135
Duty
1365
1000 Hp
Cont.
Output
Amps
Light
Applied
Rating (1)
1365
Frame
DC Bay to Bay
AC Input Integral Integral
Semiconductor
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2) Fuse Size (170M)
39
40
32
32
30 Hp
125
125 Hp
192
242
20xE242
20xE192
20xE144
20xE125
20xE099
20xE077
20xE063
20xE052
20xE041
20xE032
20xE027
20xE022
20xE017
20xE011
20xE009
20xE6P1
20xE3P9
20xE2P7
20xE1P7
20xE1P7
266
211
158
138
109
85
69
57
45
35
30
24
18.7
12.1
9.9
6.7
4.3
3.0
1.9
1.4
1 min
(x = F or G)
363
288
216
188
149
116
95
78
62
48
41
33
25.5
16.5
13.5
9.2
5.9
4.1
2.6
2.6
20xE289
20xE242
20xE192
20xE144
20xE125
20xE099
20xE077
20xE063
20xE052
20xE041
20xE032
20xE027
20xE022
20xE017
20xE011
20xE009
20xE6P1
20xE3P9
20xE2P7
20xE1P7
(x = F or G)
Catalog
Number
363
288
216
188
149
116
95
78
62
48
41
33
26
16.5
13.5
9.2
5.9
4.1
2.6
1.4
1 min
653
518
389
338
267
208
170
140
111
86
73
59
46
29.7
24.3
16.5
10.5
7.3
4.6
2.6
600V AC
3 sec
Catalog
Number
229
181
136
136
118
118
94
73
60
49
49
39
30
30
26
21
16.1
10.4
8.5
5.8
3.7
2.6
1.6
0.9
Amps
Continuous AC
Input
290
230
175
175
150
150
120
95
75
65
65
50
40
40
35
30
20
13
11
Min
(2)
515
410
305
305
265
265
210
165
135
110
110
85
70
70
55
45
35
25
20
12
Max
(3)
Dual Element
Time Delay Fuse
290
230
175
175
150
150
120
95
75
65
65
50
40
40
35
30
20
13
11
690
545
410
410
355
355
285
220
180
150
150
120
95
95
80
65
50
35
30
20
15
10
690
550
410
410
360
360
290
220
180
150
150
120
100
100
80
70
50
40
30
20
20
10
10
10
290
230
175
175
150
150
120
95
75
65
65
50
40
40
35
30
25
15
15
10
Motor Circuit
Protector (5)
300 Hp
7 289
20xE289
318
434
273
345
615
345
820
820
345
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a E063 drive can be used in Normal Duty mode on a 60 Hp motor, in Heavy Duty mode on a 50 Hp motor. The drive can be programmed for each mode. Wiring
and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with respect to Heavy Duty mode. See parameter 306 [Duty
Rating]. Refer to Specifications for an explanation of Duty Ratings.
(2) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(3) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
144
200 Hp
144
99
250 Hp
150 Hp
125
100 Hp
77
75 Hp
63
52
60 Hp
50 Hp
41
52
40 Hp
27
22
17
11
7.5 Hp
6.1
25 Hp
5 Hp
3.9
3 Hp
2.7
20 Hp
2 Hp
1.7
1 Hp
0.9
0.5 Hp
Cont. Output
Amps
15 Hp
Applied
Rating (1)
10 Hp
Frame
550 Hp
500 Hp
600 Hp
700 Hp
750 Hp
800 Hp
Normal
510
Light
Heavy
Normal
Light
760
760
760
Heavy
595
700
Normal
630
Normal
Heavy
595
630
Heavy
Heavy
595
510
Light
Normal
460
545
Light
510
Heavy
Light
425
460
Normal
435
Heavy
Light
395
435
Normal
Heavy
355
395
Heavy
329
Light
Normal
355
395
Light
Normal
355
Heavy
295
Heavy
Duty
295
272
Cont.
Output
Amps
continued on page 42
500 Hp
350 Hp
300 Hp
450 Hp
250 Hp
Applied
Rating (1)
400 Hp
Frame
20GE630
20GE760
20GE900
20GE825
20GE595
20GE630
20GE760
20GE595
20GE630
20GE595
20GE510
20GE510
20GE460
20GE460
20GE435
20GE510
20GE435
20GE395
20GE460
20GE395
20GE355
20GE435
20GE395
20GE355
20GE295
20GE295
20GE355
20GE295
Catalog
Number
836
836
1140
1050
693
693
945
655
893
765
600
561
506
561
506
638
479
479
593
435
435
533
494
391
391
325
443
408
1 min
1140
1368
1260
1071
1149
918
1071
918
765
711
765
639
711
593
639
593
533
490
533
490
3 sec
717
717
717
661
651
595
595
562
562
481
514
481
429
481
429
401
396
411
373
373
373
335
310
335
335
302
278
257
Amps
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
Amps
Amps
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
900
900
900
850
800
750
750
700
700
600
650
650
550
650
550
550
500
550
500
500
500
450
400
450
450
400
350
350
1/Phase
Min (3)
450
450
450
425
400
375
375
350
350
300
325
325
275
325
275
275
250
275
250
250
250
225
200
225
225
200
175
175
2/Phase
Min (3)
1600
1600
1600
1500
1500
1300
1300
1300
1300
1100
1200
1100
1000
1100
1000
1000
900
1000
900
900
900
800
700
800
800
700
700
600
Max (4)
900
900
900
850
800
750
750
700
700
600
650
650
550
650
550
550
500
550
500
500
500
450
400
450
450
400
350
350
1/Phase
Min (3)
450
450
450
425
400
375
375
350
350
300
325
325
275
325
275
275
250
275
250
250
250
225
200
225
225
200
175
175
2/Phase
Min (3)
2200
2200
2200
2000
2000
1800
1800
1700
1700
1400
1600
1500
1300
1500
1300
1300
1200
1300
1200
1200
1200
1100
1000
1100
1100
1000
900
800
Max (4)
2200
2200
2200
2000
2000
1800
1800
1700
1700
1400
1600
1500
1300
1500
1300
1300
1200
1300
1200
1200
1200
1100
1000
1100
1100
1000
900
800
900
900
900
850
800
750
750
700
700
600
650
650
550
650
550
550
500
550
500
500
500
450
400
450
450
400
350
350
DC Bay to Bay AC Input Protection Devices Recommended for Branch Circuit Protection
Integral
(Does not apply to 21G Drives with Options)
Semiconductor
Fuse Size
Dual Element Time Delay Fuse Non-Time Delay Fuse
(170M6648)
AC Input Integral
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2)
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
725V DC Input
Amps
DC Input Integral
Semiconductor
Fuse Size
(170M6253) (7)
41
42
Light
Normal
900
980
1045
10 1190
10 1430
1250 Hp
1400 Hp
Normal
Heavy
Light
Normal
Light
20GE1K4
20GE1K4
20GE1K1
20GE1K1
20GE980
20GE1K1
20GE900
20GE980
20GE825
20GE900
20GE760
20GE825
20GE980
Catalog
Number
1573
1785
1342
1221
1150
1380
1078
1078
990
990
919
908
1223
1 min
2145
2145
1464
1665
1665
1470
1368
1260
1470
3 sec
1350
1123
1151
1048
986
868
925
925
849
849
788
779
769
Amps
900
900
900
900
900
900
900
900
900
900
900
900
900
Amps
Amps
1/Phase
Min (3)
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1700
1400
1450
1300
1250
1100
1150
1150
1050
1050
1000
950
950
AC Input Integral
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2)
850
700
725
650
625
550
575
575
525
525
500
475
475
2/Phase
Min (3)
3000
2500
2600
2400
2200
2000
2100
2100
1900
1900
1800
1800
1700
Max (4)
1700
1400
1450
1300
1250
1100
1150
1150
1050
1050
1000
950
950
1/Phase
Min (3)
850
700
725
650
625
550
575
575
525
525
500
475
475
2/Phase
Min (3)
4100
3400
3500
3100
3000
2600
2800
2800
2500
2500
2400
2300
2300
Max (4)
4100
3400
3500
3100
3000
2600
2800
2800
2500
2500
2400
2300
2300
4100
3400
3500
3100
1250
1100
1150
1150
1050
1050
1000
950
950
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
725V DC Input
Amps
DC Input Integral
Semiconductor
Fuse Size
(170M6253) (7)
1500 Hp 10 1530
Light
20GE1K4 1683
1836
1444
900
1000
1800
900
3200
1800
900
4300
4300
4300
1000
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a E420 drive can be used in Normal Duty mode on a 450 Hp motor, in Heavy Duty mode on a 350 Hp motor or in Light Duty mode on a 500 Hp motor. The drive can be programmed
for each mode. Wiring and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with respect to Heavy Duty mode. See parameter 306 [Duty Rating].
Refer to Specifications for an explanation of Duty Ratings.
(2) These AC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection. AC input protection devices for branch circuit protection based on US NEC are listed in the table. Each drive bay has one fuse per phase.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
(7) These DC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection.
10 1220
1200 Hp
10 1110
Heavy
1000 Hp
Normal
Normal
Light
825
835
900
Heavy
815
Duty
10 920
950 Hp
1100 Hp
900 Hp
Cont.
Output
Amps
Light
Applied
Rating (1)
980
Frame
DC Bay to Bay AC Input Protection Devices Recommended for Branch Circuit Protection
Integral
(Does not apply to 21G Drives with Options)
Semiconductor
Fuse Size
Dual Element Time Delay Fuse Non-Time Delay Fuse
(170M6648)
110 kW
132 kW
212
171
119
98
82
61
50
20xF212
20xF171
20xF142
20xF119
20xF098
20xF082
20xF061
20xF050
20xF046
20xF034
20xF030
20xF023
20xF020
20xF015
20xF012
20xF012
233
188
156
131
108
90
67
55
51
37
33
25
22
16.5
12.7
12.8
1 min
(x = F or G)
318
257
213
179
147
123
92
75
69
51
45
35
30
22.5
17.3
23.0
20xF263
20xF212
20xF171
20xF142
20xF119
20xF098
20xF082
20xF061
20xF050
20xF046
20xF034
20xF030
20xF023
20xF020
20xF015
(x = F or G)
Catalog
Number
318
257
213
179
147
123
92
75
69
51
45
35
30
23
17.3
1 min
572
462
383
321
265
221
165
135
124
92
81
62
54
41
31.1
690V AC
3 sec
Catalog
Number
209
169
140
140
117
97
81
60
49
45
34
30
23
20
15
11.3
8.4
Amps
Continuous AC
Input
265
215
175
175
150
125
105
80
65
60
45
40
30
25
18
14
10
Min
(2)
470
380
315
315
265
215
180
135
110
100
75
65
52
44
34
26
18
Max
(3)
Dual Element
Time Delay Fuse
265
215
175
175
150
125
105
80
65
60
45
40
30
25
18
14
10
630
510
420
420
355
290
245
185
150
140
105
90
70
60
45
35
25
630
510
420
420
360
290
250
190
150
140
110
90
70
60
50
40
30
265
215
175
175
150
125
105
80
65
60
45
40
30
25
19
15
11
Motor Circuit
Protector (5)
250 kW
7 263
20xF263
289
395
259
325
585
325
780
780
325
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a F061 drive can be used in Normal Duty mode on a55 kW motor, in Heavy Duty mode on a 45 kW motor. The drive can be programmed for each mode. Wiring
and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with respect to Heavy Duty mode. See parameter 306 [Duty
Rating]. Refer to Specifications for an explanation of Duty Ratings.
(2) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(3) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
90 kW
200 kW
142
75 kW
55 kW
160 kW
142
45 kW
34
46
30 kW
30
23
20
15
12
8.5
Cont. Output
Amps
37 kW
22 kW
11 kW
7.5 kW
5.5 kW
18.5 kW
Applied
Rating (1)
15 kW
Frame
43
44
Applied
Rating (1)
200 kW
250 kW
300 kW
315 kW
355 kW
375 kW
400 kW
450 kW
500 kW
530 kW
450 kW
500 kW
560 kW
630 kW
710 kW
750 kW
Heavy
370
Normal
Light
710
765
Normal
710
Light
650
Heavy
Normal
650
750
Heavy
Normal
650
Heavy
590
Heavy
Heavy
590
500
460
Light
Normal
530
500
Normal
Light
500
460
Heavy
413
Light
Normal
415
460
Light
410
Heavy
Normal
375
Light
370
Normal
370
Light
330
Heavy
330
308
Normal
Heavy
265
Heavy
Duty
265
215
Cont.
Output
Amps
continued on page 45
Frame
20GF765
20GF650
20GF710
20GF795
20GF590
20GF650
20GF765
20GF590
20GF710
20GF650
20GF590
20GF500
20GF500
20GF460
20GF460
20GF415
20GF500
20GF415
20GF370
20GF460
20GF415
20GF370
20GF330
20GF330
20GF265
20GF370
20GF330
20GF265
20GF265
Catalog
Number
842
781
781
1125
715
715
975
649
885
750
690
583
550
550
506
506
620
457
451
563
555
407
407
363
363
462
398
292
323
1 min
1170
1065
1350
975
1170
885
1065
975
885
750
675
750
639
675
639
555
473
555
473
375
375
3 sec
721
706
706
706
612
612
612
556
556
471
433
499
471
471
424
424
389
377
386
353
334
349
349
297
297
290
235
235
188
Amps
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
Amps
Amps
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
900
900
900
900
750
750
750
700
700
600
550
650
600
600
550
550
500
500
500
450
450
450
450
400
400
400
300
300
250
1/Phase
Min (3)
450
450
450
450
375
375
375
350
350
300
275
325
300
300
275
275
250
250
250
225
225
225
225
200
200
200
150
150
125
2/Phase
Min (3)
1600
1600
1600
1600
1400
1400
1400
1300
1300
1100
1000
1200
1100
1100
1000
1000
900
900
900
800
800
800
800
700
700
700
600
600
500
Max (4)
900
900
900
900
750
750
750
700
700
600
550
650
600
600
550
550
500
500
500
450
450
450
450
400
400
400
300
300
250
1/Phase
Min (3)
450
450
450
450
375
375
375
350
350
300
275
325
300
300
275
275
250
250
250
225
225
225
225
200
200
200
150
150
125
2/Phase
Min (3)
2200
2100
2100
2100
1800
1800
1800
1700
1700
1400
1300
1500
1500
1500
1300
1300
1200
1200
1200
1100
1100
1100
1100
900
900
900
800
800
600
Max (4)
2200
2100
2100
2100
1800
1800
1800
1700
1700
1400
1300
1500
1500
1500
1300
1300
1200
1200
1200
1100
1100
1100
1100
900
900
900
800
800
600
900
900
900
900
750
750
750
700
700
600
550
650
600
600
550
550
500
500
500
450
450
450
450
400
400
400
300
300
250
DC Bay to Bay AC Input Protection Devices Recommended for Branch Circuit Protection
Integral
(Does not apply to 21G Drives with Options)
Semiconductor
Fuse Size
Dual Element Time Delay Fuse Non-Time Delay Fuse
(170M6648)
AC Input Integral
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2)
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
932V DC Input
Amps
DC Input Integral
Semiconductor
Fuse Size
(170M6253) (7)
800 kW
850 kW
900 kW
790
Light
960
1020
10 1160
10 1400
1120 kW
1400 kW
Normal
Heavy
Light
Normal
Light
20GF1K4
20GF1K4
20GF1K0
20GF1K0
20GF795
20GF1K0
20GF795
20GF960
20GF765
20GF710
20GF795
20GF960
Catalog
Number
1540
1740
1265
1144
1122
1298
1056
1056
946
869
875
1193
1 min
2100
2100
1380
1560
1560
1440
1350
1440
3 sec
1319
1093
1083
980
961
815
904
904
810
744
749
749
Amps
900
900
900
900
900
900
900
900
900
900
900
900
Amps
Amps
1/Phase
Min (3)
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1650
1350
1350
1250
1200
1000
1150
1150
1000
950
950
950
AC Input Integral
Output
Continuous Semiconductor
Overload Amps AC Input
Fuse Size (170M) (2)
825
675
675
625
600
500
575
575
500
475
475
475
2/Phase
Min (3)
3000
2500
2400
2200
2200
1800
2000
2000
1800
1700
1700
1700
Max (4)
1650
1350
1350
1250
1200
1000
1150
1150
1000
950
950
950
1/Phase
Min (3)
825
675
675
625
600
500
575
575
500
475
475
475
2/Phase
Min (3)
4000
3300
3200
2900
2900
2400
2700
2700
2400
2200
2200
2200
Max (4)
4000
3300
3200
2900
2900
2400
2700
2700
2400
2200
2200
2200
1650
1350
1350
1250
1200
1000
1150
1150
1000
950
950
950
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
932V DC Input
Amps
DC Input Integral
Semiconductor
Fuse Size
(170M6253) (7)
1500 kW 10 1485
Light
20GF1K4 1634
1782
1399
900
1000
1750
875
3100
1750
875
4200
4200
1750
1000
(1) Applied Rating refers to the motor that will be connected to the drive. For example, a F400 drive can be used in Normal Duty mode on a 400 kW motor, in Heavy Duty mode on a 355 kW motor or in Light Duty mode on a 450 kW motor. The drive can be programmed
for each mode. Wiring and fuses can be sized based on the programmed mode. For any given drive catalog number, Normal Duty mode provides higher continuous current but smaller overload current with respect to Heavy Duty mode. See parameter 306 [Duty Rating].
Refer to Specifications for an explanation of Duty Ratings.
(2) These AC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection. AC input protection devices for branch circuit protection based on US NEC are listed in the table. Each drive bay has one fuse per phase.
(3) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(6) Recommended Motor circuit protector - Instantaneous trip circuit breaker. The trip setting should be set to the input current of the drive and should be sized for the continuous current of the system.
(7) These DC line fuses (with blown fuse indicators) are included in the drive to provide drive short circuit protection.
10 1150
1100 kW
10 1040
Heavy
Normal
960
Light
Normal
Light
795
860
Heavy
Duty
795
Cont.
Output
Amps
10 865
Applied
Rating (1)
1000 kW
Frame
DC Bay to Bay AC Input Protection Devices Recommended for Branch Circuit Protection
Integral
(Does not apply to 21G Drives with Options)
Semiconductor
Fuse Size
Dual Element Time Delay Fuse Non-Time Delay Fuse
(170M6648)
45
Duty
Cycle
kW
21GC460
LD
315
100
30
65 or
100 w/700800 A Class L fuse
ND
250
100
30 or
65 w/600 A Class J fuse
65
HD
200
100
65
LD
315
100
5 or
100 w/500600 A Class J fuse
18 w/600800 A Class L fuse
18 w/500 A CB
30
ND
315
100
30
65 or
100 w/700800 A Class L fuse
HD
250
100
30 or
65 w/600 A Class J fuse
65
LD
355
100
30
65 or
100 w/800 A Class L fuse
ND
315
100
30
65 or
100 w/750800 A Class L fuse
HD
250
100
30 or
65 w/600 A Class J fuse
65
LD
400
100
42
65 or
100 w/10001200 A Class L fuse
ND
355
100
42
65 or
100 w/8501200 A Class L fuse
HD
315
100
30
65 or
100 w/700800 A Class L fuse
LD
450
100
42
65 or
100 w/10001200 A Class L fuse
ND
400
100
42
65 or
100 w/10001200 A Class L fuse
HD
315
100
30
65 or
100 w/700800 A Class L fuse
LD
450
100
42
65 or
100 w/10001200 A Class L fuse
ND
400
100
42
65 or
100 w/10001200 A Class L fuse
HD
355
100
42
65 or
100 w/700800 A Class L fuse
21GC540
21GC567
21GC650
21GC750
21GC770
65 or
100 w/750800 A Class L fuse
(1) These circuit breakers are considered Branch Circuit Protection for the unit.
(2) No additional protection is provided with the P5 Molded Case Switch option. Branch circuit protection is required based on NEC guidelines.
46
5 or
30 w/7001200 A Class L fuse
30 w/7001200 A CB
5 or
65 w/600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
5 or
100 w/500600 A Class J fuse
18 w/600800 A Class L fuse
18 w/500 A CB
5 or
30 w/7501300 A Class L fuse
30 w/8001200 A CB
5 or
30 w/7001200 A Class L fuse
30 w/7001200 A CB
5 or
65 w/600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
5 or
30 w/8001300 A Class L fuse
30 w/8001200 A CB
5 or
30 w/7501200 A Class L fuse
30 w/8001200 A CB
5 or
65 w/600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
5 or
42 w/10001600 A Class L fuse
42 w/10001200 A CB
5 or
42 w/8501400 A Class L fuse
42w/9001200 A CB
5 or
30 w/7001200 A Class L fuse
30 w/7001200 A CB
5 or
42 w/10001700 A Class L fuse
42 w/10001200 A CB
5 or
42 w/10001600 A Class L fuse
42 w/10001200 A CB
5 or
30 w/7501300 A Class L fuse
30 w/8001200 A CB
5 or
42 w/11001800 A Class L fuse
42 w/11001200 A CB
5 or
42 w/10001700 A Class L fuse
42 w/10001200 A CB
5 or
42 w/8001400 A Class L fuse
42 w/8001200 A CB
Drive Catalog
Number
Duty
Cycle
Hp
21GD430
LD
400
100
30 or
65 w/600 A Class J fuse
65
ND
350
100
65
HD
300
100
LD
450
100
30 or
65 w/550600 A Class J fuse
5 or
100 w/450600 A Class J fuse
18 w/600800 A Class L fuse
18 w/500 A CB
30
ND
400
100
30 or
65 w/600 A Class J fuse
65
HD
350
100
65
LD
500
100
5 or
100 w/500600 A Class J fuse
18 w/600900 A Class L fuse
30
ND
450
100
30
65 or
100 w/650800 A Class L fuse
HD
350
100
30 or
65 w/550600 A Class J fuse
65
LD
600
100
42
65 or
100 w/8501200 A Class L fuse
ND
500
100
30
65 or
100 w/750800 A Class L fuse
HD
400
100
30 or
65 w/600 A Class J fuse
65
LD
650
100
42
65 or
100 w/10001200 A Class L fuse
ND
600
100
42
65 or
100 w/8501200 A Class L fuse
HD
450
100
30
65 or
100 w/650800 A Class L fuse
LD
700
100
42
65 or
100 w/10001200 A Class L fuse
ND
650
100
42
65 or
100 w/9001200 A Class L fuse
HD
500
100
30
65 or
100 w/750800 A Class L fuse
21GD485
21GD545
21GD617
21GD710
21GD740
65
65 or
100 w/800 A Class L fuse
65 or
100 w/800 A Class L fuse
5 or
65 w/600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
30 or
65 w/550600 A Class J fuse
5 or
100 w/500600 A Class J fuse
18 w/600800 A Class L fuse
18 w/500 A CB
5 or
30 w/6501200 A Class L fuse
30 w/7001200 A CB
5 or
65 w/600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
5 or
100 w/500600 A Class J fuse
18 w/600900 A Class L fuse
5 or
30 w/7001300 A Class L fuse
30 w/7001200 A CB
5 or
30 w/6501200 A Class L fuse
30 w/7001200 A CB
5 or
65 w/550600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
5 or
42 w/8501500 A Class L fuse
42 w/9001200 A CB
5 or
30 w/7501300 A Class L fuse
30 w/8001200 A CB
5 or
65 w/600 A Class J fuse
30 w/6001000 A Class L fuse
30 w/6001200 A CB
5 or
42 w/10001700 A Class L fuse
42 w/10002000 A CB
5 or
42 w/8501500 A Class L fuse
42 w/9001200 A CB
5 or
30 w/6501200 A Class L fuse
30 w/7001200 A CB
5 or
42 w/10001700 A Class L fuse
42 w/10002000 A CB
5 or
42 w/9001600 A Class L fuse
42 w/9002000 A CB
5 or
30 w/7501300 A Class L fuse
30 w/8001200 A CB
(1) These circuit breakers are considered Branch Circuit Protection for the unit.
(2) No additional protection is provided with the P5 Molded Case Switch option. Branch circuit protection is required based on NEC guidelines.
47
Cable Considerations
Power Cable Types Acceptable for 200600 Volt Installations
A variety of cable types are acceptable for drive installations. For an in depth discussion of cable types, including a table of
maximum motor cable lengths, refer to the Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC
Drives, publication DRIVES-IN001.
Description
600V
75 C (167 F)
Wiring Considerations
Type
Wire Type(s)
Description
Power
Standard
600V,
75 C (167 F)
Signal
Remote Pot
300V,
7590 C (167194 F)
Encoder/
Pulse I/O
<30 m (100 ft)
Combined
Encoder/
Pulse I/O
30 to 152 m
(100 to 500 ft)
Signal
Power
Combined
Signal
(1) (2)
Digital I/O
Safety Inputs
Homing Inputs
(1) (3) (4)
Encoder/
Pulse I/O
152 to 259 m
(500 to 850 ft.)
Power
Combined
Un-shielded
Multi-conductor
shielded cable
Shielded
300V,
60 C (140 F)
(1)
(2)
(3)
(4)
Control and signal wires should be separated from power wires by at least 0.3 meters (1 foot).
The use of shielded wire for AC input power may not be necessary but is always recommended.
If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary, but is always recommended.
I/O terminals labeled () or Common are not referenced to earth ground and are designed to greatly reduce common mode interference. Grounding these terminals can cause signal noise. For
CE installations, 115V I/O must use shielded cable or have a cable length less than 30 m (98 ft).
48
600 or 800 mm Deep Drive Bay w/ 600 or 800 mm Deep Drive Bay
600 mm Wide Wiring Only Bay
w/600 mm Cabinet Options Bay
Cable Option
3
(2)
(1) Other configurations with shielded cable are possible, however the use of conduit hubs is recommended.
(2) This wiring configuration is possible when there are no ouput options in the option bay and the motor connections are wired from the drive bay.
Motor Considerations
Due to the operational characteristics of AC variable frequency drives, motors with inverter grade insulation systems
designed to meet or exceed NEMA MG1 Part 31.40.4.2 standards for resistance to spikes of 1600 volts are recommended.
Guidelines must be followed when using non-inverter grade motors to avoid premature motor failures. Refer to Wiring and
Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001 for
recommendations.
Model Number
Motor NP Volts
(line-line V rms)
Motor NP
Amps
(A rms)
Motor NP
Hertz
(Hz)
Motor NP RPM
(oper. rpm)
Motor NP
Power
(kW)
Motor
Poles
Current peak
(A rms)
System Cont.
Stall Torque
(Nm)
Motor Max
RPM
MPL-B4530K
460
7.8
200.7
3010
2.6
19.1
8.25
4000
MPL-B4560F
460
8.3
144.7
2170
3.2
25.5
14.1
3000
MPL-B520K
460
8.1
208
3120
3.5
23.3
10.7
4000
MPL-B540K
460
14.5
177.3
2660
5.4
42.4
19.4
4000
MPL-B560F
460
14.5
130.7
1960
5.5
42.4
26.8
3000
MPL-B580F
460
18.4
132.7
1990
7.1
66.5
34
3000
MPL-B580J
460
22.6
148
2220
7.9
66.5
34
3800
MPL-B640F
460
22.7
106
1590
6.11
46
36.7
3000
49
Model Number
Motor NP Volts
(line-line V rms)
Motor NP
Amps
(A rms)
Motor NP
Hertz
(Hz)
Motor NP RPM
(oper. rpm)
Motor NP
Power
(kW)
Motor
Poles
Current peak
(A rms)
System Cont.
Stall Torque
(Nm)
Motor Max
RPM
MPL-B660F
460
27.2
81.3
1220
6.15
67.9
48
3000
MPL-B680D
460
24
94
1410
9.3
66.5
62.8
2000
MPL-B680F
460
33.9
79.3
1190
7.5
67.9
60
3000
MPL-B860D
460
33.6
96
1440
12.5
67.5
83.1
2000
MPL-B880C
460
33.6
72.7
1090
12.6
69
110
1500
MPL-B880D
460
40.3
86.7
1300
15
113.2
110
2000
MPL-B960B
460
29.7
62
930
12.7
63.6
130
1200
MPL-B960C
460
38.9
76
1140
14.8
88.4
124.3
1500
MPL-B960D
460
50.2
76.7
1150
15
102.5
124.3
2000
MPL-B980B
460
31.8
59.3
890
15.02
70.7
162.7
1000
MPL-B980C
460
48.2
67.3
1010
16.8
99
158.2
1500
MPL-B980D
460
63.6
74.7
1120
18.6
141.4
158.2
2000
MPM-B1151F
480
1.5
266.7
4000
0.75
2.18
5000
MPM-B1151T
480
3.1
333.3
5000
0.9
14.5
2.18
7000
MPM-B1152C
480
2.3
166.7
2500
1.2
8.8
2.18
3000
MPM-B1152F
480
2.9
266.7
4000
1.4
15.5
4.74
5200
MPM-B1152T
480
5.2
266.7
4000
1.4
26.8
4.74
7000
MPM-B1153E
480
2.7
200
3000
1.4
15.3
6.55
3500
MPM-B1153F
480
3.2
266.7
4000
1.45
22.6
6.55
5500
MPM-B1153T
480
5.5
266.7
4000
1.45
39.2
6.55
7000
MPM-B1302F
480
3.4
266.7
4000
1.65
15.6
5.99
4500
MPM-B1302M
480
4.9
266.7
4000
1.65
22.6
5.99
6000
MPM-B1302T
480
6.6
266.7
4000
1.65
30.7
5.99
7000
MPM-B1304C
480
3.4
183.3
2750
15.8
10.2
2750
MPM-B1304E
480
4.1
166.7
2500
2.2
24.2
10.2
4000
MPM-B1304M
480
7.3
233.3
3500
2.2
42.9
10.2
6000
MPM-B1651C
480
4.7
200
3000
2.5
20.6
10.7
3500
MPM-B1651F
480
8.2
200
3000
2.5
36
10.7
5000
MPM-B1651M
480
10.9
200
3000
2.5
40.2
10.7
5000
MPM-B1652C
480
166.7
2500
3.8
23.8
16
2500
MPM-B1652E
480
233.3
3500
4.3
42.8
19.4
3500
MPM-B1652F
480
11
233.3
3500
4.3
59.5
19.4
4500
MPM-B1653C
480
10.5
133.3
2000
4.6
41.9
26.8
2500
MPM-B1653E
480
10.2
200
3000
5.1
51.6
26.8
3500
MPM-B1653F
480
13.2
200
3000
5.1
66.7
26.8
4000
MPM-B2152C
480
12.3
133.3
2000
5.6
39.2
36.7
2500
MPM-B2152F
480
18.7
166.7
2500
5.9
69.3
33
4500
MPM-B2152M
480
21
166.7
2500
5.9
54
30
5000
MPM-B2153B
480
12.7
116.7
1750
6.8
42.4
48
2000
50
Model Number
Motor NP Volts
(line-line V rms)
Motor NP
Amps
(A rms)
Motor NP
Hertz
(Hz)
Motor NP RPM
(oper. rpm)
Motor NP
Power
(kW)
Motor
Poles
Current peak
(A rms)
System Cont.
Stall Torque
(Nm)
Motor Max
RPM
MPM-B2153E
480
19.3
133.3
2000
7.2
69.7
48
3000
MPM-B2153F
480
22.1
133.3
2000
7.2
69.6
45
3800
MPM-B2154B
480
13.9
116.7
1750
6.9
69.3
62.8
2000
MPM-B2154e
480
18.3
133.3
2000
7.5
69.5
56
3000
MPM-B2154F
480
19.8
133.3
2000
7.5
59.3
56
3300
(1)
460
9.5
88.7
2660
2.9
28.5
10.4
5000
1326AB-B520F
(1)
460
8.8
70.3
2110
2.9
26.4
13.1
3500
1326AB-B530E
(1)
460
9.5
74.3
2230
4.2
28.5
18
3000
1326AB-B720E
(1)
460
17.5
70
2100
6.8
52.5
30.9
3500
1326AB-B720F (1)
460
27.5
117
3510
11.7
66.5
31.8
5000
(1)
460
22.8
78.3
2350
9.6
66.5
39
3350
1326AB-B740C (1)
460
20.9
52.3
1570
8.7
62.7
53
2200
1326AB-B740E (1)
460
32
79.7
2390
12.7
66.5
50.8
3400
MPG-B050-031 (2)
460
16.3
92
920
1.2
12
32.5
12.4
2510
MPG-B110-031 (2)
460
12.9
112
1120
12
31.1
17
2420
MPG-B110-091 (2)
460
10.6
184
1840
1.6
12
20.5
8.3
3500
1326AS-B630F (2)
460
7.8
142.7
2140
2.4
18.5
10.7
4500
1326AS-B660E (2)
460
11.8
100.7
1510
3.4
29.8
21.5
3000
1326AS-B690E (2)
460
19
87.3
1310
41.3
36.4
3000
1326AS-B840E (2)
460
21.2
79.3
1190
4.7
39.5
37.6
3000
1326AS-B860C (2)
460
17.6
77.3
1160
44.4
49.3
2000
1326AB-B515G
1326AB-B730E
(1) 1326AB-series motors are being replaced by MPM-series motors. They will be available for a limited time. Do not specify for new projects.
(2) 1326AS and MPG-series motors are no longer available. Do not specify for new projects.
For motor power and feedback cable information, refer to the Kinetix Motion Control Selection Guide
(publication GMC-SG001).
51
Light Duty
kW Output
Normal Duty
kW Output
Heavy Duty
kW Output
Catalog
Number
Light Duty
Hp Output
400 Volt
20xC2P1
20xC3P5
20xC5P0
20xC8P7
20xC011
20xC015
20xC022
20xC030
20xC037
20xC043
20xC060
20xC072
20xC085
20xC104
20xC140
20xC170
20xC205
20xC260
20xC302
20xC367
20xC456
2xGC460
2xGC540
2xGC567
2xGC650
2xGC750
2xGC770
2xGC910
2xGC1K0
2xGC1K1
2xGC1K2
2xGC1K4
2xGC1K5
2xGC1K6
2xGC2K1
52
315
315
355
400
450
450
560
630
710
800
850
900
1000
1400
0.75
1.5
2.2
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
250
315
315
355
400
400
500
560
630
710
800
850
900
1250
Normal Duty
Hp Output
Heavy Duty
Hp Output
480 Volt
0.75
1.5
2.2
4
5.5
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
200
250
250
315
355
355
400
500
500
560
630
710
710
1000
20xD2P1
20xD3P4
20xD5P0
20xD8P0
20xD011
20xD014
20xD022
20xD027
20xD034
20xD040
20xD052
20xD065
20xD077
20xD096
20xD125
20xD156
20xD186
20xD248
20xD302
20xD361
20xD415
20xD430
20xD485
20xD545
20xD617
20xD710
20xD740
20xD800
20xD960
20xD1K0
20xD1K2
20xD1K3
20xD1K4
20xD1K5
20xD2K0
400
450
500
600
650
700
800
900
1000
1100
1250
1350
1500
2000
1
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
350
350
400
450
500
600
650
700
800
900
1000
1100
1250
1350
1750
1
2
3
5
7.5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
300
300
350
400
450
500
600
600
700
750
800
900
1000
1100
1650
4
5
5
6
N/A
7
7
10
10
600/690V AC
Light Duty Normal Duty
Catalog Number kW Output kW Output
690 Volt
20xF012
7.5
20xF015
11
20xF020
15
20xF023
18.5
20xF030
22
20xF034
30
20xF046
37
20xF050
45
20xF061
55
20xF082
75
20xF098
90
20xF119
110
20xF142
132
20xF171
160
20xF212
200
20xF263
250
2xGF265
315
250
2xGF330
355
315
2xGF370
400
355
2xGF415
450
400
2xGF460
500
450
2xGF500
530
500
2xGF590
630
560
2xGF650
710
630
2xGF710
800
710
2xGF765
850
750
2xGF795
900
800
2xGF960
1000
900
2xGF1K0
1100
1000
2xGF1K4
1500
1400
Normal
Heavy Duty
Light Duty Duty
kW Output Catalog Number Hp Output Hp Output
600 Volt
5.5
20xE1P7
1
7.5
20xE2P7
2
11
20xE3P9
3
15
20xE6P1
5
18.5
20xE009
7.5
22
20xE011
10
30
20xE017
15
37
20xE022
20
45
20xE027
25
55
20xE032
30
75
20xE041
40
90
20xE052
50
110
20xE063
60
132
20xE077
75
160
20xE099
100
200
20xE125
125
20xE144
150
20xE192
200
20xE242
250
20xE289
300
200
20xE295
350
300
250
20xE355
400
350
300
20xE395
450
400
355
20xE435
500
450
375
20xE460
500
500
400
20xE510
550
500
450
20xE595
700
600
500
20xE630
800
700
560
20xE760
900
800
630
20xE825
950
900
710
20xE900
1000
950
800
20xE980
1100
1000
900
20xE1K1
1200
1100
1120
20xE1K4
1500
1400
6
7
10
10
53
Enclosure Options
IMPORTANT
IP00, IP20, and NEMA/UL Open Type PowerFlex 750-Series drives must be mounted in a clean, dry location. Contaminants such as
oils, corrosive vapors and abrasive debris must be kept out of the enclosure. These enclosures are intended for indoor use primarily
to provide a degree of protection against contact with enclosed equipment. These enclosures offer no protection against airborne
contaminants. Refer to the following tables for an explanation of enclosure options and the environmental specifications found on
page 7.
Description
No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.
Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation is to be expected, when the drive is out of
operation.
Conductive pollution or dry non-conductive pollution occurs, which becomes conductive due to condensation, which is to be expected.
The pollution generates persistent conductivity caused, for example by conductive dust or rain or snow.
Frames
Enclosure Type
(Cat. No.
Position 6)
Installed Accessory
Kit
Enclosure Type
Pollution
Degree
Enclosure Type
Pollution
Degree
None
1, 2
1, 2
NEMA Type 1
1, 2
1, 2
None
1, 2
1, 2
NEMA Type 1
1, 2
1, 2
Flange
1, 2
1, 2
None
1, 2
1, 2, 3, 4
None
1, 2, 3, 4
1, 2, 3, 4
None
1, 2
1, 2
NEMA Type 1
1, 2
1, 2
1, 2
1, 2, 3, 4
None
1, 2, 3, 4
1, 2, 3, 4
B, L, P, W
None
1, 2
1, 2
J, K, Y
None
1, 2, 3, 4
1, 2, 3, 4
25
67
810
54
Frames 17
Top View
860.0 mm
(33.9 in.) Min.
Roll-out Cart
Approximate Weights
Drive
Standard
(20F, 20G)
Frame
Size
AC Input
1
and Common 2
DC Input
3
4
5
6
7
Standard
(20G)
AC Input
Common DC
Input
with Options AC Input
(21G)
8
9
10
8
9
10
8
9
10
Drive Rating
kW
0.757.5
0.7511
1522
3037
4555
75
90132
160200
250
Hp
110
115
2030
4050
6070
100
125200
250300
350
250400
500850
9001250
250400
500850
9001250
250400
500850
9001250
350650
7001250
13501750
350650
7001250
13501750
350650
7001250
13501750
8 (17)
12 (26)
14 (30)
20 (45)
37 (82)
38 (84)
69 (152)
96 (212)
B, L
623 (1374)
1246 (2748)
1869 (4122)
566 (1248)
1132 (2497)
1698 (3745)
1145 (2525)
1730 (3815)
2315 (5106)
8 (17)
12 (26)
14 (30)
20 (45)
37 (82)
39 (85)
79 (174)
106 (234)
J
644 (1419)
1287 (2838)
1931 (4257)
586 (1293)
1173 (2587)
1760 (3880)
1166 (2570)
1771 (3905)
2377 (5241)
8 (17)
12 (26)
14 (30)
20 (45)
89 (197)
91 (200)
135 (297)
162 (357)
P, W
1145 (2525)
2290 (5051)
3435 (7576)
1088 (2400)
2176 (4799)
3264 (7199)
1675 (3694)
2820 (6219)
3965 (8745)
R
6 (13)
K, Y
1166 (2570)
2332 (5141)
3498 (7711)
1109 (2445)
2218 (4889)
3327 (7334)
1696 (3739)
2862 (6309)
4028 (8880)
AC Input - kg (lb
64 (140)
222 (490)
286 (630)
55
Frame
Approximate Dimensions
Type
1 IP20,
NEMA/UL Type Open
2 (Frame 2 Shown)
6.4
(0.25)
A
D
14.3
(0.56)
B
F
Weight
D
E
F
kg (lb)
110.0 400.5 211.0 68.0 82.0 390.4 6.0
(4.33) (15.77) (8.31) (2.68) (3.23) (15.37) (12.75)
Frame A
1
2
Flange Mount
206.2
(8.12)
212.0
(8.35)
481.8
(18.97)
188.3 (7.41)
169.2 (6.66)
14x: 3.50
(0.138)
94.2 (3.71)
19.2 (0.76)
63.7
(2.51)
460.6
(18.13)
399.60 +1.80/-0.00
(15.7 +0.1/-0.0)
395.3
(15.56)
285.3
(11.23)
175.3
(6.90)
65.3 (2.57)
30.2 (1.19)
56
128.00 +1.80/-0.00
(5.0 +0.1/-0.0)
30.5
(1.20)
Frame
Type
IP54,
NEMA/UL Type 12
215.3
(8.48)
100.0
(3.94)
6.4 (0.25)
222.2
(8.75)
14.3 (0.56)
528.2
(20.80)
543.2
(21.39)
88.1 (3.47)
85.7 (3.37)
65.1 (2.56)
44.5 (1.75)
42.1 (1.66)
2x: 22.0
(0.87)
3x: 29.0
(1.14)
179.4
(7.06)
146.4
(5.76)
109.4
(4.31)
IP20,
NEMA/UL Open Type
190.0
(7.48)
158.0
(6.22)
6.4 (0.25)
212.0
(8.35)
14.3 (0.56)
435.0
(17.13)
454.0
(17.87)
57
Frame
Type
Flange Mount
212.0
(8.35)
515.0
(20.28)
240.5 (9.47)
208.3 (8.20)
16x: 3.50
(0.138)
120.3 (4.74)
32.3 (1.27)
495.5
(19.51)
457.8
(18.02)
352.8
(13.89)
434.00 +1.80/-0.00
(17.087 +0.070/-0.000)
247.8
(9.76)
142.8
(5.62)
4x: 5.00R
(0.197R)
37.8
(1.48)
30.75
(1.211)
179.00 +1.80/-0.00
(7.047 +0.070/-0.000)
30.75
(1.211)
84.6
(3.33)
58
Frame
Type
IP54,
NEMA/UL Type 12
268.0
(10.55) 185.5
(7.30)
158.0
(6.22)
6.4 (0.25)
220.1
(8.67)
14.3 (0.56)
533.0
(20.98)
551.0
(21.69)
135.8 (5.35)
123.3 (4.85)
92.8 (3.65)
62.3 (2.45)
49.8 (1.96)
3x: 22.2
(0.87)
2x: 43.7
(1.72)
183.5
(7.22)
136.5
(5.37)
IP20,
NEMA/UL Open Type
194.0
(7.64)
222.0
(8.74)
6.4 (0.25)
212.0
(8.35)
14.3 (0.56)
455.0
(17.91)
474.0
(18.66)
202.0
(7.95)
59
Frame
Type
Flange Mount
211.9
(8.34)
535.0
(21.06)
272.50 (10.728)
224.25 (8.829)
136.25 (5.364)
16x: 3.50
(0.138)
48.25 (1.900)
515.50
(20.295)
454.00 +1.80/-0.00
(17.874 +0.070/-0.000)
477.75
(18.809)
367.75
(14.478)
257.75
(10.148)
147.75
(5.817)
37.75
(1.486)
30.75
(1.211)
4x: 5.00R
(0.197R)
211.00 +1.80/-0.00
(8.307 +0.070/-0.000)
30.75
(1.211)
84.5
(3.33)
60
Frame
Type
IP54,
NEMA/UL Type 12
300.0
(11.81)
194.0
(7.64)
217.5
(8.56)
6.4 (0.25)
220.1
(8.67)
14.3 (0.56)
553.0
(21.77)
571.0
(22.48)
165.8 (6.53)
140.8 (5.54)
108.8 (4.28)
76.8 (3.02)
51.8 (2.04)
3x: 22.2
(0.87)
2x: 43.7
(1.72)
182.0
(7.17)
136.5
(5.37)
IP20,
NEMA/UL Open Type
238.0
(9.37)
270.0
(10.63)
6.4 (0.25)
212.0
(8.35)
14.3 (0.56)
531.0
(20.91)
550.0
(21.65)
61
Frame
Type
Flange Mount
211.9
(8.34)
611.0
(24.06)
320.50 (12.618)
280.25 (11.033)
200.25 (7.884)
22x: 3.50
(0.138)
120.25 (4.734)
40.25 (1.585)
591.50
(23.287)
550.75
(21.683)
465.75
(18.337)
531.0 +1.8/-0.0
(20.91 +0.07/-0.00)
380.75
(14.990)
295.75
(11.644)
210.75
(8.297)
125.75
(4.951)
40.75
(1.604)
30.75
(1.211)
4x: 5.00R
(0.197R)
259.0 +1.8/-0.0
(10.20 +0.07/-0.00)
30.25
(1.191)
84.5
(3.33)
62
Frame
Type
IP54,
NEMA/UL Type 12
348.0
(13.70)
238.0
(9.37)
265.5
(10.45)
6.4 (0.25)
220.1
(8.67)
14.3 (0.56)
629.0
(24.76)
647.0
(25.47)
6.4
(0.25)
212.8 (8.38)
172.8 (6.80)
132.8 (5.23)
92.8 (3.65)
52.8 (2.08)
3x: 22.2
(0.87)
2x: 50.0
(1.97)
181.9
(7.16)
141.9
(5.59)
63
Frame
Type
IP00,
NEMA/UL Open Type
346.4
(13.64)
308.0
(12.13)
208.4
(8.20)
665.5
(26.20)
644.0
(25.35)
6.4 (0.25)
6.5 (0.26)
14.5 (0.57)
283.0
254.0 (11.14)
(10.00)
14.5
(0.57)
609.0
(23.98)
623.0
(24.53)
64
Frame
Type
Flange Mount
208.4
(8.20)
665.5
(26.20)
284.0 (11.18)
258.0 (10.16)
225.5 (8.88)
193.0 (7.60)
91.0 (3.58)
58.5 (2.30)
26.0 (1.02)
24x: 6.4
(0.25)
624.0
(24.57)
600.0
(23.62)
562.0
(22.13)
138.0
(5.43)
462.0
(18.19)
362.0
(14.25)
561.0 +2.0/-1.5
(22.09 +0.08/-0.06)
262.0
(10.31)
162.0
(6. 38)
62.0 (2.44)
24.0 (0.94)
8.0
(0.30)
268.0 +2.0/-1.5
(10.60 +0.08/-0.06)
31.5
(1.24)
65
Frame
Type
IP54,
NEMA/UL Type 12
558.8
(22.00)
609.4
(23.99)
464.7
(18.30)
1298.3
(51.11)
1238.3
(48.75)
10.5 (0.41)
22.0 (0.87)
66
Frame
Type
IP00,
NEMA/UL Open Type
430.0
(16.93)
207.9
(8.19)
349.6
(13.76)
881.5
(34.70)
875.0
(34.45)
380.0
330.0 (14.96)
(12.99)
8.5 (0.33)
8.5 (0.33)
16.0 (0.63)
25.0
(0.98)
825.0
(32.48)
838.0
(32.99)
67
Frame
Type
Flange Mount
208.4
(8.20)
875.0
(34.45)
403.00 (15.87)
352.63 (13.88)
251.88 (9.92)
151.13 (5.95)
50.38 (1.98)
32x: 7.0
(0.28)
812.0
(31.97)
784.0
(30.87)
744.8
(29.32)
666.4
(26.24)
588.0
(23.15)
768.0
(30.24)
509.6
(20.06)
431.2
(16.98)
352.8
(13.89)
274.4
(10.80)
196.0
(7.72)
117.6
(4.63)
39.2 (1.54)
28.0 (1.10)
8.0 (0.31)
387.0
(15.24)
8.0
(0.31)
138.0
(5.43)
68
Frame
Type
NEMA/UL Type 1
1271.0
(50.04)
1221.0
(48.07)
881.8
(34.72)
825.0
(32.48)
8.5 (0.33)
16.0 (0.63)
339.2
(13.35)
20.5 (0.81)
389.2
(15.32)
389.0
(15.31)
430.0
(16.93)
561.0
(22.08)
69
Frame
Type
609.6
(24.00)
558.8
(22.00)
464.8
(18.30)
1614.0
(63.54)
1543.1
(60.75)
10.5 (0.41)
22.0 (0.87)
70
Frame
Type
440
(17.3)
68
(2.7)
76
(3.0)
127
(5.0)
600
(23.6)
240
(9.4)
600
(23.6)
2453
(96.6)
2300
(90.6)
76
(3.0)
1183
(46.6)
127
(5.0)
18.0
(0.71)
542
(21.3)
141
(5.6)
No. Description
500
(19.7)
531
(20.9)
300
(11.8)
69
(2.7)
43
(1.7)
71
Frame
Type
440
(17.3)
270
(10.6)
102
(4.0)
800
(31.5)
152
(6.0)
600
(23.6)
240
(9.4)
2453
(96.6)
2300
(90.6)
1862
(73.3)
76
(3.0)
1374
(54.1)
No. Description
127
(5.0)
292
(11.5)
742
(29.2)
440
(17.3)
531
(20.9)
72
18.0
(0.71)
300
(11.8)
43
69 (1.7)
(2.7)
Frame
Type
440
(17.3)
440
(17.3)
180
(7.1)
68
(2.7)
76
(3.0)
600
(23.6)
127
(5.0)
240
(9.4)
1200
(47.2)
2453
(96.6)
2300
(90.6)
1808
(71.2)
76
(3.0)
127
(5.0)
18.0
(0.71)
440
205 (17.3)
(8.1)
141
(5.6)
No. Description
542
(21.3)
500
(19.7)
1131
(44.5)
900
(35.4)
531
669 (20.9)
(26.3)
300
(11.8)
69
(2.7)
43
(1.7)
73
Frame
Type
440
(17.3)
440
(17.3)
270
(10.6)
270
(10.6)
102
(4.0)
152
(6.0)
240
(9.4)
1200
(47.2)
800
(31.5)
2453
(96.6)
2300
(90.6)
1808
(71.2)
76
(3.0)
127
(5.0)
18.0
(0.71)
440
200 (17.3)
(7.9)
No. Description
742
(29.2)
292
(11.5)
440
(17.3)
1131
(44.5)
74
900
(35.4)
669
(26.3)
531
(20.9)
300
(11.8)
69
(2.7)
43
(1.7)
Frame
Type
102
(4.0)
898
(35.4)
152 (6.0)
240
(9.4)
600 (23.6)
800
(31.5)
2477
(97.5)
2300
(90.6)
1862
(73.3)
547
(21.5)
680
(26.8)
76
(3.0)
1374
(54.1)
127
(5.0)
18.0
(0.71)
440
292 (17.3)
(11.5)
300 (11.8)
531 (20.9)
742
(29.2)
No. Description
43
69 (1.7)
(2.7)
75
Frame
Type
440
(17.3)
440
(17.3)
68
(2.7)
127
(5.0)
1200
(47.2)
76
(3.0)
127
(5.0)
240
(9.4)
600
(23.6)
2453
(96.6)
2300
(90.6)
76
(3.0)
127
(5.0)
141
(5.6)
18.0
(0.71)
No. Description
500
(19.7)
1131
(44.5)
76
76
(3.0)
542
(21.3)
500
(19.7)
669
900 (26.3)
(35.4)
300
531 (11.8)
(20.9)
43
69 (1.7)
(2.7)
Frame
Type
440
(17.3)
440
(17.3)
270
(10.6)
102
(4.0)
152
(6.0)
1200
(47.2)
152
(6.0)
800
(31.5)
240
(9.4)
2453
(96.6)
2300
(90.6)
1862
(73.3)
76
(3.0)
127
(5.0)
292
(11.5)
76
(3.0)
No. Description
440
(17.3)
440
(17.3)
1131
(44.5)
18.0
(0.71)
900
(35.4)
531
669 (20.9)
(26.3)
742
(29.2)
300
(11.8)
43
69 (1.7)
(2.7)
77
Frame
Type
270
(10.6)
440
(17.3)
440
(17.3)
440
(17.3)
102
(4.0)
270
(10.6)
152
(6.0)
800
(31.5)
152
(6.0)
240
(9.4)
1800
(70.9)
2453
(96.6)
2300
(90.6)
1808
(71.2)
76
(3.0)
76
(3.0)
18.0
(0.71)
440
(17.3)
127
(5.0)
200
(7.9)
742
(29.2)
292
(11.5)
440
(17.3)
1731
(68.1)
78
440
(17.3)
1500
(59.1)
1131
1269 (44.5)
(50.0)
900
(35.4)
531
669 (20.9)
(26.3)
300
(11.8)
43
69 (1.7)
(2.7)
No. Description
Frame
Type
102
(4.0)
152 (6.0)
898
(35.4)
152 (6.0)
240
(9.4)
1200 (47.2)
800
(31.5)
2477
(97.5)
2300
(90.6)
1862
(73.3)
547
(21.5)
680
(26.8)
76 (3.0)
76 (3.0)
18.0
(0.71)
127
(5.0)
292
(11.5)
440
(17.3)
440
(17.3)
742
(29.2)
No. Description
300 (11.8)
531 (20.9)
669 (26.3)
900 (35.4)
43
69 (1.7)
(2.7)
1131 (44.5)
79
Frame
10
Type
440
(17.3)
440
(17.3)
440
(17.3)
127
(5.0)
68
(2.7)
76
(3.0)
127
(5.0)
1800
(70.9)
127
(5.0)
240
(9.4)
600
(23.6)
2453
(96.6)
2300
(90.6)
76
(3.0)
127
(5.0)
141
(5.6)
500
(19.7)
1731
(68.1)
80
76
(3.0)
500
(19.7)
1500
(59.1)
76
(3.0)
1131
1269 (44.5)
(50.0)
500
(19.7)
669
900 (26.3)
(35.4)
300
531 (11.8)
(20.9)
18.0
(0.71)
542
(21.3)
43
69 (1.7)
(2.7)
No. Description
Frame
10
Type
440
(17.3)
440
(17.3)
440
(17.3)
152
(6.0)
1800
(70.9)
270
(10.6)
152
(6.0)
152
(6.0)
102
(4.0)
240
(9.4)
800
(31.5)
2453
(96.6)
2300
(90.6)
1862
(73.3)
76
(3.0)
127
(5.0)
292
(11.5)
76
(3.0)
76
(3.0)
440
(17.3)
440
(17.3)
440
(17.3)
1731
(68.1)
1500
(59.1)
1131
1269 (44.5)
(50.1)
669
900 (26.3)
(35.4)
300
531 (11.8)
(20.9)
18.0
(0.71)
742
(29.2)
43
69 (1.7)
(2.7)
No. Description
81
Frame
10
Type
102
(4.0)
152 (6.0)
1800 (70.9)
152 (6.0)
898
(35.4)
152 (6.0)
240
(9.4)
800
(31.5)
2477
(97.5)
2300
(90.6)
1862
(73.3)
547
(21.5)
680
(26.8)
76 (3.0)
76 (3.0)
76 (3.0)
18.0
(0.71)
127
(5.0)
292
(11.5)
440
(17.3)
440
(17.3)
440
(17.3)
300 (11.8)
531 (20.9)
669 (26.3)
900 (35.4)
1131 (44.5)
1269 (50.1)
1500 (59.1)
1731 (68.1)
82
742
(29.2)
43
69 (1.7)
(2.7)
No. Description
Frame
Type
777.9
(30.63)
1978.8
(77.91)
1728.6
(68.05)
1600.6
(63.02)
1619.8
(63.77)
2111.8
(83.14)
1472.6
(57.98)
2065.6
(81.32)
2145.0
(84.45)
1228.3
(48.36)
2035.2
(80.13)
1100.0
(43.31)
953.1
(37.52)
788.0
(31.02)
623.0
(24.53)
466.0
(18.35)
236.0
(9.29)
119.2
(4.69)
0.0
420.5
(16.56)
Outside of
Cabinet Post
54.4 (2.14)
Max. Backset
93.9 (3.70)
0.0
17.0
(0.67)
403.9 (15.90)
83
Frame
Type
15
Frame
215.4 (8.48)
458.8 (18.06)
222.2 (8.75)
497.1 (19.57)
117.7 (4.63)
38.0 (1.50)
223.1 (8.78)
530.1 (20.87)
154.7 (6.09)
38.0 (1.50)
222.7 (8.77)
564.4 (22.22)
154.7 (6.09)
40.0 (1.57)
222.7 (8.77)
665.4 (26.20)
155.0 (6.10)
55.0 (2.17)
308.0
(12.13)
346.7
(13.65)
945.1
(37.21)
84
Frame
Type
15
Frame 1
130.0 (5.12)
125.0 (4.92)
89.7 (3.53)
87.0 (3.43)
67.5 (2.66)
48.0 (1.89)
45.3 (1.78)
95.0 (3.74)
65.0 (2.56)
60.0 (2.36)
5x: 22.0
(0.87)
2x: 43.7
(1.72)
2x: 29.0
(1.14)
168.7
(6.64)
156.7
(6.17)
118.7
(4.67)
171.6
(6.76)137.6
(5.42) 94.6
(3.72)
Frame 2
Frame 3
201.0 (7.91)
180.0 (7.09)
135.0 (5.31)
158.8 (6.25)
144.8 (5.70)
110.8 (4.36)
76.8 (3.02)
62.8 (2.47)
5x: 22.2
(0.87)
2x: 43.7
(1.72)
187.0
(7.36)
168.7
(6.64)
5x: 22.2
(0.87)
90.0 (3.54)
69.0 (2.72)
2x: 50.0
(1.97)
187.0
(7.36)
173.0
(6.81)
118.7
(4.67)
5x: 22.2
(0.87)
123.0
(4.84)
Frame 4
Frame 5
85
Frame
Type
15
B
C
D
F
Enclosures are shown without venting. Supplied enclosures will have proper venting.
Frame
110.0 (4.33)
478.8 (18.85)
400.5 (15.77)
78.3 (3.08)
37.4 (1.47)
73.4 (2.89)
134.5 (5.30)
485.9 (19.13)
424.2 (16.70)
61.7 (2.43)
43.5 (1.71)
79.5 (3.13)
190.0 (7.48)
514.0 (20.24)
454.0 (17.87)
60.0 (2.36)
74.0 (2.91)
116.0 (4.57)
222.0 (8.74)
533.7 (21.01)
474.0 (18.66)
59.7 (2.35)
84.0 (3.31)
138.0 (5.43)
270.0 (10.63)
609.7 (24.00)
550.0 (21.65)
59.7 (2.35)
77.8 (3.06)
191.8 (7.55)
Important: EMC Kits (20-750-EMC-Fx) do not change the mounting dimensions. Refer to the PowerFlex 750-Series EMC
86
Drive Options
Human Interface Modules
Blank Plate
20-HIM-A6
20-HIM-C6S
Description
Cat. No.
20-HIM-A0
Enhanced, LCD, Full Numeric, Handheld/Local (Drive Mount, Frames 15) (1)
Enhanced, LCD, Full Numeric, IP66 NEMA Type 4X/12 (for indoor use only)
(2)(3)
20-HIM-A6
20-HIM-C6S
20-HIM-C6S (1)
050 C (32122 F)
-4085 C (-40185 F)
595% non-condensing
Important: The module must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the
module is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
The HIM is not UV rated.
2.5 G at 52000 Hz
5 G at 52000 Hz
30 G peak acceleration, 11 (1) ms pulse width
50 G peak acceleration, 11 (1) ms pulse width
UL508C
CAN / CSA C22.2 No. 14
EN61800-3
EN61800-3
(1) NOTE: This is a product of category C2 according to IEC 61800-3. In a domestic environment this product may cause radio interference in which case supplementary mitigation measures may be required.
87
Cat. No.
20-HIM-B1
(2)
20-HIM-H10
1202-C03
1202-C10
1202-C30
1202-C90
1202-H03
1202-H10
1202-H30
1202-H90
DPI Cable Kit with Connectors, Tools and 100 m (328 ft.) Cable
1202-CBL-KIT-100M
1202-TB-KIT-SET
1203-S03
88
Cat. No.
20-750-BNETIP
20-750-CNETC
20-COMM-C (3)
20-COMM-C-MX3 (3)
20-750-DNET
20-COMM-D (3)
20-COMM-D-MX3 (3)
20-750-ENETR
20-COMM-E (3)
20-COMM-E-MX3 (3)
20-COMM-H (3)
20-COMM-K (3)
20-COMM-L (3)
20-COMM-M (3)
20-750-PBUS
20-750-PNET
20-750-PNET2P
20-COMM-P (3)(4)
20-COMM-Q (3)
20-COMM-R (3)(5)
20-COMM-R-MX3 (3)(5)
20-COMM-S (3)
20-COMM-S-MX3 (3)
20-XCOMM-AC-PS1
20-XCOMM-DC-BASE
20-XCOMM-IO-OPT1
1769-SM1
1203-SNM
Smart Self-powered Serial Converter (RS232) includes 1203-SFC and 1202-C10 Cables
1203-SSS
Universal Serial Bus (USB) Converter includes 2 m USB, 20-HIM-H10 & 22-HIM-H10 Cables
1203-USB
1786-TPR
20-750-20COMM-F1 (6)
20-750-20COMM (6)
(1) Only compatible with the following; 20-COMM-E EtherNet/IP, 20-COMM-C ControlNet (coax), 20-COMM-Q ControlNet (fiber),
20-COMM-D DeviceNet (Series B or later), 20-COMM-M Modbus/TCP.
(2) For use only with DPI External Communications Kits 20-XCOMM-DC-BASE.
(3) Requires a Communication Carrier Card (20-750-20COMM or 20-750-COMM-F1). Refer to page 90 for compatibility details.
(4) Not supported in Frame 1.
(5) This item has Silver Series status. For information, refer to http://www.ab.com/silver.
(6) Refer to the description for applicable frames.
89
Adapter
20-COMM-B
(2)
20-COMM-D
20-COMM-H
v2.009 (3)
20-COMM-K
v1.001 (4)
20-COMM-L
v1.007 (4)
(2)
20-COMM-Q
v3.001 (4)
(5)
v4.001 (4)
Not Compatible
v2.001 (4)
Not Compatible
v2.001 (4)
v3.001 (4)
(5)
v3.001 (4)
(2)
Not Compatible
20-COMM-S
(1)
(2)
(3)
(4)
(5)
(6)
(5)
Not Compatible
v4.001 (4)
20-COMM-E
20-COMM-R (1)
Not Compatible
v3.001 (4)
20-COMM-C
20-COMM-M
This item has Silver Series status. For information, refer to http://www.ab.com/silver.
Controller must be capable of reading/writing 32-bit floating point (REAL) values.
Supports all three modes of operation (RTU, P1, N2).
Requires this adapter firmware version or higher.
Requires firmware version v1.05 or higher of the drive Add On Profiles for RSLogix 5000 version v16 or higher.
Chinese, Japanese, and Korean languages are supported at the time of publication.
-1050 C (14122 F)
-4085 C (-40185 F)
Relative Humidity:
5 to 95% non-condensing
Atmosphere:
Important: The module must not be installed in an area where the ambient atmosphere contains volatile or corrosive
gas, vapors or dust. If the module is not going to be installed for a period of time, it must be stored in an area where it will
not be exposed to a corrosive atmosphere.
90
20-COMM-C
20-750-DNET
20-COMM-D
20-COMM-E
20-COMM-H
Network
Protocol:
Data Rate:
ControlNet
5 Mbps (fixed)
ControlNet
5 Mbps
DeviceNet
125, 250, and 500 kbps
DeviceNet
125, 250, and 500 kbps
Drive
Protocol:
Data Rates:
DPI
500 Kbps
DPI
125 or 500 Kbps
DPI
500 Kbps
DPI
125 or 500 Kbps
DPI
125 or 500 Kbps
DPI
125 or 500 Kbps
Consumption
Drive (DPI):
Network:
250 mA at 14V DC
None
275 mA at 5V DC
None
50 mA at 14V DC
60 mA at 24V DC
150 mA at 5 VDC
60 mA at 24 VDC
370 mA at 5 VDC
N/A
150 mA at 5 VDC
N/A
Dimensions:
HxLxW
Weight:
62 g (2.1 oz.)
85 g (3 oz)
62 g (2.1 oz.)
85 g (3 oz)
85 g (3 oz)
85 g (3 oz)
Compliance
UL:
c-UL:
CE:
C-Tick:
UL508C
CAN/CSA C22.2 No. 14-05
EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50178 and EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50178 and EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50178 and EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50178 and EN61800-3
EN61800-3
20-COMM-K
20-COMM-L
20-COMM-M
20-750-PBUS
20-COMM-Q
Network
Protocol:
Data Rate:
CANopen
10 Kbps1 Mbps
LonWorks
78 Kbps
Modbus/TCP
10/100 Mbps, Half/Full Duplex
Profibus
9600 bps12 Mbps (autobauds)
ControlNet
5 Mbps
Drive
Protocol:
Data Rates:
DPI
125 or 500 Kbps
DPI
125 or 500 Kbps
DPI
125 or 500 Kbps
DPI
500 Kbps
DPI
125 or 500 Kbps
Consumption
Drive (DPI):
Network:
500 mA at 5V DC
None
200 mA on DPI
N/A
350 mA at 5V DC
N/A
250 mA at 14V DC
None
275 mA at 5V DC
N/A
Dimensions:
HxLxW
Weight:
85 g (3 oz)
85 g (3 oz)
85 g (3 oz)
57 g (2 oz)
85 g (3 oz)
Compliance
UL:
c-UL:
CE:
C-Tick:
UL508C
CAN/CSA C22.2 No. 14
EN61000-6-4 & EN61000-6-2
UL508C
UL508C
CAN/CSA C22.2 No. 14
EN50178 & EN61800-3
EN61800-3
UL508C
CAN/ CSA C22.2 No.14-M91
IEC50178 and IEC61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50178 & EN61800-3
EN61800-3
20-COMM-R (1)
20-COMM-S
1203-SSS
1203-USB
1769-SM1
Network
Protocol:
Data Rate:
Remote I/O
57.6, 115.2 or 230.4 kbps
DF1
120038400 bps
DF1
960038400 bps
Drive
Protocol:
Data Rates:
DPI
125 or 500 Kbps
DPI
125 or 500 Kbps
DPI or SCANport
125 or 500 Kbps (DPI only)
DPI or SCANport
125 or 500 Kbps (DPI only)
Consumption
Drive (DPI):
Network:
250 mA at 5V DC
N/A
150 mA at 5V DC
N/A
130 mA at 12V DC
N/A
130 mA at 12V DC
170 mA at +5V DC (DSI)
Module:280 mA at 5V DC
Channel: 60 mA at 12V DC
Dimensions:
HxLxW
Weight:
85 g (3 oz)
60 g (2 oz)
71 g (2.5 oz)
71 g (2.5 oz)
71 g (2.5 oz)
UL508C
CAN/CSA C22.2 No. 14
EN50178 and EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50178 and EN61800-3
EN61800-3
UL508C
CAN/CSA C22.2 No. 14
EN50081-2 and EN61000-6-2
AS/NZS 2064, 1997, Group 1, Class A
Compliance
UL:
UL508C
UL508C
c-UL:
CAN/CSA C22.2 No. 14
CAN/CSA C22.2 No. 14
CE:
EN50178 and EN61800-3
EN50178 and EN61800-3
C-Tick:
EN61800-3
EN61800-3
(1) This item has Silver Series status. For information, refer to http://www.ab.com/silver.
91
20-XCOMM-IO-OPT1
20-XCOMM-AC-PS1
6 (single common)
27V DC
100240V AC
90264V AC
AC Input Frequency:
4763 Hz
8 mA (each input)
1027V DC (3 mA minimum)
05V DC (2 mA maximum)
-30V DC
Number of Outputs:
27V DC/125V AC
2A
Network
Protocol:
Data Rate:
Drive
Protocol:
Data Rates:
DPI
125/500 Kbps
Number of Inputs:
Output Voltage:
24V DC
Output Current:
830 mA
Consumption
Module:
Network:
Dimensions (H x W x D):
108* x 108 x 75 mm
(4.25 x 4.25 x 2.95 in.)
with I/O terminal block attached
Weight:
Certifications
UL
UL508C
c-UL
CAN/CSA C22.2 No. 14
CE
C-Tick
(1) Since the Comms Kit is powered by a nominal 24 VDC, the current consumption listed in this table differs from the value shown on the label of the communication adapter, which is based on the adapter
being powered by 5 VDC from the drive.
(2) The I/O board is NOT designed for fast I/O response times. Do NOT use with input devices that will transition (OFF-ON-OFF) faster than the response time. Potential input devices include auxiliary contact
inputs from relays or overloads, pushbuttons, etc.
(3) The I/O board is NOT designed for fast I/O response times. Do NOT use with output devices that need to transition (OFF-ON-OFF) faster than the response time. Potential output devices include pilot lights
or a contact closure reset to another hardware device.
92
Feedback Options
Description
Cat. No.
Incremental Encoder
20-750-ENC-1 (2)
20-750-DENC-1 (2)
20-750-UFB-1
Cat. No.
24V DC I/O with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs
20-750-2262C-2R
115V AC I/O with 2 Analog In, 2 Analog Out, 6 Digital In and 2 Relay Outputs
20-750-2262D-2R
24V DC I/O with 2 Analog In, 2 Analog Out, 6 Digital In, 3 Digital Out, 1 Relay & 2 Transistor
Outputs
20-750-2263C-1R2T
(1) I/O option kits are not allowed in CIP motion mode.
Safety Options
Two safety options are available for the PowerFlex 750-Series:
Safe Torque-Off
Safe Speed Monitor
Safe Torque-Off is ideal for safety related applications requiring removal of rotational power to the motor without shutting
down the drive. Safe Torque-Off functionality offers the benefit of quick start-up after a demand on the safety system and
helps reduce wear from repetitive start-up and provides safety ratings up to and including SIL CL3, PLe, and Category 3.
In applications where the speed needs to be controlled and monitored, the Safe-Speed Monitor option combines Safe
Torque-Off capability with integrated safety relay functionality and the Safe-Speed Control technology in one hardware
option to provide safety ratings up to and including SIL CL3, PLe, and Category 4.
With the Safe Speed Monitor option you can safely monitor and control the speed of your application which allows
operators to perform process or maintenance work without stopping the machine.
Note that the drive can accomodate only one option.
Description
Cat. No.
Safe Torque-Off
20-750-S
20-750-S1
(1) Requires the Dual Incremental Encoder or Universal Feedback Option. Also requires the 20-750-EMCSSM1-F8 EMC Option Kit
with Frame 89 drives.
93
Safe-Torque -Off
Safety Category:
Cat. 3 and PL(e) per EN ISO 13849-1; SIL CL3 per IEC 61508 and EN 62061
Power Consumption:
4.4 W
36 W
15V
5V
5V
2.5 mA @ 5V DC
2 mA
20 ms
User-configurable
Inputs (S34):
Strip Length:
10 mm (0.39 in.)
6 mm (0.25 in.)
Certification (2)
c-UL-us
CE
C-Tick
TV Certified for Functional Safety: up to SIL CL3, according to EN 61800-5-2, TV Certified for Functional Safety: up to SIL CL3, according to EN 61800-5-2,
EN 61508, and EN 62061; up to Performance Level PL(e) and Category 4,
EN 61508, and EN 62061; up to Performance Level PL(e) and Category 3,
according to EN ISO 13849-1; when used as described.
according to EN ISO 13849-1; when used as described.
(1) Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(2) When product is marked.
(3) Safety outputs need additional fuse for reverse voltage protection of the control circuit. Install a 6 A slow-blow or 10 A fast-acting fuse.
TV
94
Frame(s)
(1)
Cat. No.
20-750-APS
17
20-750-DCBB1-F6
20-750-DCBB1-F7
Allows connection of the drive DC bus terminals to the bus rails at the back of the cabinet.
810
20-750-BUS1-F8
20-750-EMC1-F1
20-750-EMC1-F2
20-750-EMC1-F3
20-750-EMC1-F4
20-750-EMC1-F5
EMC Core
20-750-EMC2-F1
20-750-EMC2-F2
20-750-EMC2-F3
EMC Cores
45
20-750-EMC2-F45
810
20-750-EMCCM1-F8
810
20-750-CBPEMCCM1-F8
810
20-750-EMCCM1-F9
EMC Cores Required when using the Safe Speed Monitor option 20-750-S1.
810
20-750-EMCSSM1-F8
10
20-750-EMCDK1-F10
Converts Open Type drive to external heatsink (flange) with NEMA/UL Type 1 integrity
backside. (2)
20-750-FLNG1-F2
20-750-FLNG1-F3
20-750-FLNG1-F4
20-750-FLNG1-F5
Converts Open Type drive to external heatsink (flange) with NEMA/UL Type 4X/12 integrity
backside.
20-750-FLNG4-F6
20-750-FLNG4-F7
810
20-750-LBRKT1
20-750-NEMA1-F1
20-750-NEMA1-F2
20-750-NEMA1-F3
20-750-NEMA1-F4
20-750-NEMA1-F5
20-750-NEMA1-F6
20-750-NEMA1-F7
20-750-ACTE1-F6
20-750-PTG1-F6
20-750-PTG1-F7
Mounting hardware with 25 m (75 ft) fiber optic and 24V control cables for mounting the
control POD in a cabinet that is separate from the drive.
810
20-750-RPD1-F8
Provides a means to move the power core and allow access to the power terminals.
810
20-750-CART1-F8
(1) Frame 8 and up drives can be powered from an external 24V DC source, a 20-750-APS is not required.
(2) This kit is for use with IP20, NEMA/UL Type 0 drives and will not provide an air-tight or water-tight seal. Where sealing is required (e.g. contaminated, dirty or wet environments), a drive with
an F enclosure option must be used.
(3) Required for Frame 8 and up drives to perform power wiring.
95
Frame 9
Frame 10
Description
Required?
Cat. No.
Qty.
Cat. No.
Qty.
Cat. No.
Qty.
Recommended
20-750-BUS2-F8
20-750-BUS2-F9
20-750-BUS2-F10
Recommended
20-750-BUS3-F8
20-750-BUS3-F9
20-750-BUS3-F10
Recommended
20-750-BUS4-F8
20-750-BUS4-F9
20-750-BUS4-F10
Recommended
20-750-BUS5-F8
20-750-BUS5-F9
20-750-BUS5-F10
Required
20-750-POD1-F8
20-750-POD1-F8
20-750-POD1-F8
Required
20-750-PH1-F8
(4)
20-750-PH2-F9
20-750-PH3-F10
Required
20-750-FCBL1-F8
Required
20-750-FCBL1-F10
20-750-FCBL1-F10
Optional
20-750-RPD1-F8
20-750-RPD1-F9
20-750-RPD1-F10
Recommended
20-750-MNT2-F8
20-750-MNT2-F9
20-750-MNT2-F10
Recommended
20-750-MNT3-F8
20-750-MNT3-F9
20-750-MNT3-F10
Recommended
20-750-DUCT2-F8
20-750-DUCT2-F8
20-750-DUCT2-F8
Recommended
20-750-DUCT4-F8
20-750-DUCT4-F8
20-750-DUCT4-F8
Roll-Out Cart
Recommended
20-750-CART1-F8
20-750-CART1-F8
20-750-CART1-F8
Recommended
1489-A2D130
1489-A2D130
1489-A2D130
Recommended
1489-AAL0A
1489-AAL0A
1489-AAL0A
Optional
20-750-EMCBUS1-F8
20-750-EMCBUS1-F9
20-750-EMCBUS1-F10
Optional
20-750-EMCCM1-F8
20-750-EMCCM1-F8
20-750-EMCCM1-F8
(1)
(2)
(3)
(4)
96
Frame
1
2
Cat. No.
20-750-DB1-D1
20-750-DB1-D2
Terminators
Description (1)
for use with 3.7 kW (5 Hp) & below drives
for use with 1.5 kW (2 Hp) & up drives
Cat. No.
1204-TFA1
1204-TFB2
Cat. No.
1204-RWC-17-A
ND kW
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
149
187
ND Hp
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
250
Cat. No.
1321-RWR8-DP
1321-RWR12-DP
1321-RWR18-DP
1321-RWR25-DP
1321-RWR35-DP
1321-RWR35-DP
1321-RWR45-DP
1321-RWR55-DP
1321-RWR80-DP
1321-RWR80-DP
1321-RWR100-DP
1321-RWR130-DP
1321-RWR160-DP
1321-RWR200-DP
1321-RWR250-DP
1321-RWR320-DP
97
Isolation Transformers
IP32, NEMA/UL Type 3R Standalone, 46% Nominal Impedance
H2
2
5
X2
X2
H2
X0
H1
X1
H3
X0
H1
X1
X3
X3
H3
Diagram 1
Diagram 2
Motor Rating
Motor Rating
kW
Hp
Wiring
Diagram
0.75
1321-3TW005-BB
110
150
1321-3TH175-BB
522
700
1321-3TH770-BB
1.5
1321-3TW005-BB
149
200
1321-3TH220-BB
560
750
1321-3TH770-BB
2.2
1321-3TW005-BB
187
250
1321-3TH275-BB
597
800
1321-3TH880-BB
22
30
1321-3TW040-BB
224
300
1321-3TH330-BB
671
900
900 kVA
30
40
1321-3TW051-BB
261
350
1321-3TH440-BB
746
1000
1000 kVA
37
50
1321-3TH063-BB
298
400
1321-3TH440-BB
821
1100
1200 kVA
45
60
1321-3TH075-BB
336
450
1321-3TH550-BB
933
1250
1200 kVA
55
75
1321-3TH093-BB
373
500
1321-3TH550-BB
1007
1350
1300 kVA
75
100
1321-3TH118-BB
448
600
1321-3TH660-BB
1119
1500
1500 kVA
90
125
1321-3TH145-BB
485
650
1492
2000
2000 kVA
Cat. No.
kW
Hp
Wiring
Diagram
Cat. No.
kW
Hp
Wiring
Diagram
Cat. No.
A 1321 Isolation
Transformer
solution is not
available.
Approximate drive
kVA is shown at left.
Motor Rating
Motor Rating
kW
Hp
Wiring
Diagram
0.75
1321-3TW005-CC
90
125
1321-3TH145-CC
410
550
1321-3TH660-CC
1.5
1321-3TW005-CC
110
150
1321-3TH175-CC
448
600
1321-3TH770-CC
2.2
1321-3TW005-CC
149
200
1321-3TH220-CC
522
700
1321-3TH770-CC
22
30
1321-3TW040-CC
187
250
1321-3TH275-CC
597
800
1321-3TH880-CC
30
40
1321-3TW051-CC
224
300
1321-3TH330-CC
671
900
950 kVA
37
50
1321-3TH063-CC
261
350
1321-3TH440-CC
709
950
1000 kVA
45
60
1321-3TH075-CC
298
400
1321-3TH550-CC
746
1000
1100 kVA
55
75
1321-3TH093-CC
336
450
1321-3TH550-CC
895
1200
1200 kVA
75
100
1321-3TH118-CC
373
500
1321-3TH660-CC
1119
1500
1500 kVA
98
Cat. No.
kW
Hp
Wiring
Diagram
Cat. No.
kW
Hp
Wiring
Diagram
Cat. No.
A 1321 Isolation
Transformer
solution is not
available.
Approximate drive
kVA is shown at left.
kW
0.75
1.1
1.5
Hp
1
1.5
2
2.2
5.5
7.5
7.5
10
11
15
15
20
18.5
25
22
30
30
40
37
50
45
60
55
75
75
100
90
125
110
150
132
160
200
250
315
200
250
300
350
400
450
Duty
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
99
kW
355
Hp
500
400
450
600
650
500
560
630
710
800
850
900
1000
1400
700
750
800
900
1000
1100
1250
1350
1500
2000
Duty
Light/Normal/Heavy
Light
Normal/Heavy
Light/Heavy
Normal
Light/Normal/Heavy
Light
Light
Normal
Light/Normal/Heavy
Heavy
Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal
Light/Normal
Light/Normal
Light/Normal
Light
Light
Light
Light
Light
Light
100
kW
0.75
1.1
1.5
Hp
1
1.5
2
2.2
5.5
7.5
7.5
10
11
15
15
20
18.5
25
22
30
30
40
37
50
45
60
55
75
75
100
90
125
110
150
132
160
200
250
315
355
200
250
300
350
400
450
Duty
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
101
kW
Hp
500
400
450
600
650
500
560
630
710
800
850
900
1000
1400
700
750
800
900
1000
1100
1250
1350
1500
2000
Duty
Light
Normal/Heavy
Light/Heavy
Normal
Light/Normal/Heavy
Light
Light
Normal
Light/Normal/Heavy
Heavy
Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal
Light/Normal
Light/Normal
Light/Normal
Light
Light
Light
Light
Light
Light
102
kW
Hp
0.5
1
5.5
7.5
3
5
7.5
10
11
15
15
20
18.5
22
30
37
45
55
25
30
40
50
60
75
75
100
90
110
125
150
132
200
160
Duty
Heavy
Normal
Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Heavy
Normal/Heavy
Normal
Heavy
Normal
Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
1321-3R160-B
1321-3R200-B
1321-3R160-C
1321-3R200-B
1321-3RA160-B
1321-3RA200-B
1321-3RA160-C
1321-3RA200-B
1321-3R160-B
1321-3R200-B
1321-3R160-C
1321-3R200-B
1321-3RA160-B
1321-3RA200-B
1321-3RA160-C
1321-3RA200-B
Normal
Heavy
1321-3R160-C
1321-3R200-C
1321-3RA160-C
1321-3RAB200-C
1321-3R160-C
1321-3R200-C
1321-3RA160-C
1321-3RAB200-C
103
kW
200
Hp
250
300
Duty
Normal/Heavy
Normal/Heavy
Normal
Heavy
250
350
300
315
355
375
400
450
450
500
500
530
560
630
710
750
800
850
400
450
500
500
550
600
700
750
800
900
950
1000
1100
Heavy
Light/Normal/Heavy
Normal
Normal/Heavy
Light/Normal/Heavy
Heavy
Light/Normal/Heavy
Light/Normal
Light/Normal
Light/Normal/Heavy
Heavy
Light/Normal/Heavy
Light/Normal
Heavy
Light/Normal
Heavy
Light
Heavy
Light
Normal/Heavy
Light/Normal/Heavy
Normal/Heavy
Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Normal
Light/Normal
Light/Normal/Heavy
Light/Normal
Light
Light
900
1000
1100
1500
1200
1500
Light/Normal
Light
Light/Normal
Light
Light/Normal
Light
1321-3RA250-B
1321-3RAB400-B
1321-3RAB250-C
1321-3RAB320-B
1321-3RAB400-B
1321-3RAB400-B
1321-3RA500-B
1321-3RAB400-B
1321-3RA600-B
1321-3RA500-B
1321-3RA500-B
1321-3RA500-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA750-B
1321-3RA750-B
1321-3RA750-B
1321-3RA750-B
1321-3RA850-B
1321-3RA850-B
1321-3RA850-B
1321-3RA850-B
1321-3RA1000-B
1321-3RA1000-B
1321-3RA1000-B
1321-3RA1000-B
1321-3R250-B
1321-3RB400-B
1321-3RB250-C
1321-3RB320-B
1321-3RB400-B
1321-3RB400-B
1321-3R500-B
1321-3RB400-B
1321-3R600-B
1321-3R500-B
1321-3R500-B
1321-3R500-B
1321-3R600-B
1321-3R600-B
1321-3R600-B
1321-3R600-B
1321-3R600-B
1321-3R600-B
1321-3R600-B
1321-3R600-B
1321-3R750-B
1321-3R750-B
1321-3R750-B
1321-3R750-B
1321-3R850-B
1321-3R850-B
1321-3R850-B
1321-3R850-B
1321-3R1000-B
1321-3R1000-B
1321-3R1000-B
1321-3R1000-B
1321-3RA250-B
1321-3RAB400-B
1321-3RAB250-C
1321-3RAB320-B
1321-3RAB400-B
1321-3RAB400-B
1321-3RA500-B
1321-3RAB400-B
1321-3RA600-B
1321-3RA500-B
1321-3RA500-B
1321-3RA500-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA600-B
1321-3RA750-B
1321-3RA750-B
1321-3RA750-B
1321-3RA750-B
1321-3RA850-B
1321-3RA850-B
1321-3RA850-B
1321-3RA850-B
1321-3RA1000-B
1321-3RA1000-B
1321-3RA1000-B
1321-3RA1000-B
1321-3RA600-B (1)
1321-3RA600-B (1)
1321-3RA600-B (1)
1321-3RA600-B (2)
1321-3RA600-B (2)
1321-3RA600-B (2)
1321-3RA600-B (2)
1321-3R600-B (1)
1321-3R600-B (1)
1321-3R600-B (1)
1321-3R600-B (2)
1321-3R600-B (2)
1321-3R600-B (2)
1321-3R600-B (2)
1321-3RA600-B (1)
1321-3RA600-B (1)
1321-3RA600-B (1)
1321-3RA600-B (2)
1321-3RA600-B (2)
1321-3RA600-B (2)
1321-3RA600-B (2)
104
kW
Hp
0.5
1
5.5
7.5
11
15
18.5
22
2
3
5
7.5
10
15
20
25
30
30
37
45
55
75
40
50
60
75
90
110
132
160
100
125
150
200
200
250
250
300
350
400
Duty
Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Normal
Heavy
Normal/Heavy
Normal
Heavy
Heavy
Normal/Heavy
Normal/Heavy
Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
105
kW
300
315
355
375
400
450
500
500
530
560
630
710
750
800
850
900
1000
1100
1500
Hp
450
500
550
600
700
750
800
900
950
1000
1100
1200
1500
Duty
Heavy
Light/Normal/Heavy
Light/Normal
Light/Normal/Heavy
Light/Normal/Heavy
Light
Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal
Heavy
Light
Normal/Heavy
Light/Normal/Heavy
Normal/Heavy
Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Light/Normal/Heavy
Normal
Light/Normal
Light/Normal/Heavy
Light/Normal
Light
Light
Light/Normal
Light
Light/Normal
Light
Light/Normal
Light
106
Notes:
107
Important Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this publication are included solely for illustrative purposes. Because of the many variables
and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
www.rockwel lautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Copyright 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.