Beruflich Dokumente
Kultur Dokumente
Issue A
Slide 1
Causes of failure:
Environment System Mal operation Wrong design Manufacture Material Maintenance
Issue A
Slide 2
1. Internal failure
Causes:
Winding & terminal faults Core faults Onload tap changer faults Overheating faults
Issue A
Slide 3
Issue A
Slide 4
Vector Groups
Group 1 0 Phase displacement Group 2 180 Phase displacement Group 3 30 Lag phase displacement Group 4 30 Lead phase displacement
Yy0 Dd0 Zd0 Yy6 Dd6 Dz6 Yd1 Dy1 Yz1 Yd11 Dy11 Yz11
Issue A
Slide 5
V2
V1
X R Fig.3 If Fig.N
Issue A
Slide 10
>
20%
Basic Protection
Differential Restricted Earthfault Overfluxing Overcurrent & Earthfault
Issue A
Slide 13
Differential Protection
Works on Merz-price current comparison principle Relays with bias characteristic should only be used
Applied
Where protection co-ordination is difficult / not possible using time delayed elements For fast fault clearance For zone of protection
Issue A
Slide 14
Differential Protection
Consideration for applying differential protection Phase correction Filtering of zero sequence currents Ratio correction Magnetizing inrush during energisation Overfluxing
Issue A
Slide 15
R I diff = 0
Issue A
Slide 16
I Diff = 0 : No tripping
R I diff = 0
Issue A
Slide 17
I diff = 0
Issue A
Slide 18
Slide 19
0A
I2
I1
Slide 20
LOAD = 200 A
0.1 A
OLTC SETTING IS AT 10% Differential current = 0.1 A Relay pickup setting = O.2 A, So the Relay restrains
Issue A
Slide 21
2000 A
1A
OLTC SETTING IS AT 10% Relay Pickup Setting is O.2 A So the Relay Operates
Issue A
Slide 22
Role of Bias
3
Operate
80 %
e op Sl
Restrain
lo 20% S pe
Slide 23
Issue A
Slide 24
ZM
ZM
TC satur RCT
Slide 25
Issue A
ZM
ZM
Issue A
Slide 26
ZM
ZM
TC satur
Issue A
Slide 27
ZM
ZM
Issue A
Slide 28
ZM
ZM
TC satur
Issue A
Slide 29
ZM
ZM
Issue A
Slide 30
ZM
ZM
Issue A
TC satur
Slide 31
ZM
ZM=0
False tripping
RCT 2RL M 2RL RCT
CT Saturation
TC satur
Issue A
Slide 32
TC satur
Issue A
Slide 33
Stabilising resistor
TC satur
Issue A
Slide 34
RCT 2RL M
Vset
2RL
RCT
Issue A
Slide 35
ZM = 0
Issue A
Slide 36
RCT
Issue A
Slide 37
RCT
Vset
Issue A
Slide 38
RCT 2RL
M M
RCT 2RL
Vset
Issue A
Slide 39
64
64
64
Slide 40
Issue A
P1
S1
P2
S2
Slide 41
External earth fault - Current circulates between the phase & neutral CTs; no current thro the relay
So, No Operation
Issue A
Slide 42
For an internal earth fault the unbalanced current flows thro the relay
Slide 43
Setting will require calculation of : 1) Setting stability voltage (VS) 2) Value of stabilising resistor required
RS
Issue A
Slide 44
Total impedance = 14 p.u. I1 = 1 = 0.0714 p.u. 14 Base current = 80 x 106 3 x 415 = 111296 Amps IF = 3 x 0.0714 x 111296 = 23840 Amps (primary) = 14.9 Amps (secondary)
Slide 45
4 I2 4 I0
Issue A
= 836 ohms
Issue A
Slide 46
Issue A
Slide 47
Magnetising Inrush
Transient condition - occurs when a transformer is energised Normal operating flux of a transformer is close to saturation level Residual flux can increase the mag-current In the case of three phase transformer, the point-on-wave at switch-on differs for each phase and hence, also the inrush currents
Issue A
Slide 48
Magnetising Inrush
Transformer Magnetising Characteristic
Twice Normal Flux
Normal Flux
Slide 49
Magnetising Inrush
Inrush Current + m - m
Im V
Im
STEADY STATE
2 m
V
Issue A
Slide 50
Magnetising Inrush
Issue A
Slide 51
Magnetising Inrush
Effect of magnetising current
Appears on one side of transformer only - Seen as fault by differential relay - Transient magnetising inrush could cause relay to operate Makes CT transient saturation - Can make mal-operation of Zero sequence relay at primary
Issue A
Slide 52
Magnetising Inrush
IR
P1 P2 S2 P1 S1 P2 S2 P1 S1 P2 S2
IS IT
S1
IR + IS + IT = 3Io = 0
Issue A
Slide 53
Magnetising Inrush
Effect of magnetising current
Issue A
Slide 54
Issue A
Slide 55
Causes
Low frequency High voltage Geomagnetic disturbances
Issue A
Slide 57
m
Ie Effects Transient Overfluxing - Tripping of differential element Prolonged Overfluxing - Damage to transformers
Slide 58
Issue A
Overfluxing - Condition
Differential element should be blocked for transient overfluxing-+
25% OVERVOLTAGE CONDITION
Slide 59
Overfluxing - Protection
V
K f
Trip and alarm outputs for clearing prolonged overfluxing Alarm : Definite time characteristic to initiate corrective action Trip : IT or DT characteristic to clear overfluxing condition
Issue A
Slide 60
BUCCHOLZ PROTECTION
Oil conservator
Bucholz Relay
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Installation
To oil conservator 3 x internal pipe diameter (minimum) 5 x internal pipe diameter (minimum)
76 mm typical Transformer
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay
Petcock Alarm bucket
Trip bucket
Deflector plate
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buccholz Protection Application Accumulation of gaz Oil Leakage Severe winding faults
Issue A
Slide 60
BUCCHOLZ PROTECTION
Accumulation of Gaz Interturn faults Winding faults to earth with low (fault power (fault close to neutral for example) example)
Issue A
Slide 60
BUCCHOLZ PROTECTION
Inter-Turn Fault
Nominal turns ratio : 11,000 / 240 Fault turns ratio Current ratio : 11,000 / 1 :1 / 11,000 Primary
Issue A
Secondary
Slide 60
BUCCHOLZ PROTECTION
Inter-Turn Fault
CT Shorted turn
Nominal turns ratio : 11,000 / 240 Fault turns ratio Current ratio : 11,000 / 1 :1 / 11,000 Primary
Issue A
Secondary
Slide 60
BUCCHOLZ PROTECTION
Interturn Fault Current / Number of Turns Short Circuited
Primary current (multiples of rated current) 100 Fault current (multiples of rated current)
80
60
40
20
10
15
20
25
Issue A
BUCCHOLZ PROTECTION
Interturn Fault Current / Number of Turns Short Circuited
Primary current (multiples of rated current) 100 Fault current (multiples of rated current)
80
60
40
20
Primary phase current very low Not detected by current operated relays
Slide 60
10
15
20
25
Issue A
BUCCHOLZ PROTECTION
Accumulation of Gaz Interturn faults Winding faults to earth with low (fault power (fault close to neutral for example) example)
Issue A
Slide 60
BUCCHOLZ PROTECTION
Earth Fault Current / Number of TurnsofShort Circuited multiples
max fault current Primary current 100
80 Fault current 60
40
20
5
Issue A
10
15
20
25
BUCCHOLZ PROTECTION
Accumulation of Gaz Operating principle
Issue A
Slide 60
BUCCHOLZ PROTECTION
Issue A
Slide 60
BUCCHOLZ PROTECTION
Issue A
Slide 60
BUCCHOLZ PROTECTION
Issue A
Slide 60
BUCCHOLZ PROTECTION
Accumulation of gaz
Color of gaz indicates the type of fault White or Yellow : Insulation burnt Grey : Dissociated oil
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Accumulation of gaz
Issue A
Slide 60
BUCCHOLZ PROTECTION
Effects of Oil Maintenance
After oil maintenance, false tripping may occur because Oil aeration
Bucholz relay tripping inhibited during suitable period
Issue A
Slide 60
BUCCHOLZ PROTECTION
Bucholtz Protection Application Accumulation of gaz Oil Leakage Severe winding faults
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buccholz Protection Application Accumulation of gaz Oil Leakage Severe winding faults
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Severe winding fault
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Severe winding fault
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Severe winding fault
Issue A
Slide 60