Beruflich Dokumente
Kultur Dokumente
305
MECHANICAL
THE MECHANICAL PLAN
The mechanical section, like the plumbing section, may include a site plan at the beginning showing mechanical work to be done outside the building. In addition to this site plan, the mechanical section includes the following: 1. Foundation and/or Basement Plansshow mechanical work to be done in the crawl space, under the slab on grade, or in the basement. 2. Floor Plansone plan per floor shows mechanical work required for each floor. Ductwork is shown on the floor where it is to be installed. For example, ductwork located above the second floor ceiling and serving the second floor is shown on the second floor plan. If ductwork is located above the ceiling of the second floor to serve a space on the third floor, the ductwork is drawn on the second floor and is noted as being installed on the second floor. Piping for the heating and cooling system is drawn and noted in the same manner. 3. Elevations, Sections, and Detailslocated on sheets that follow the floor plan sheets. These large scale drawings show how units, ductwork, and piping are installed. The drawings also show how the units are to be connected with piping, ductwork, water, steam, and so forth. 4. Schedulesmechanical schedule sheets such as those listed below relay information to the mechanical worker: A. B. C. D. Unit or equipment schedules Register, grilles, and diffuser schedules Duct insulation schedule Piping schedule
Sheet M-1 of the Construction Drawings, Mechanical Figure 1, shows mechanical plans for a small bank and trust company, including ductwork, piping installation, and sections and details.
CONTENTS
306
CONTENTS
307
MECHANICAL SPECIFICATIONS
Some small jobs have the specifications printed on a separate sheet and bound with the regular plans. For example, the specifications for the plans at the end of this book are bound in this way. On larger jobs, all specifications are bound in a separate book that accompanies the plans when they are turned over to the contractor.
CONTENTS
308
MECHANICAL Figure 1. Typical mechanical plan and associated drawingssmall bank building.
VIEW PHOTO
CONTENTS
309
CONTENTS
310
Furnace
If the air cycle just described is used for heating, the heat is generated in a furnace. Furnaces for residential heating produce heat by burning fuel oil or natural gas, or from electric heating coils. If the heat comes from burning fuel oil or natural gas, the combustion (burning) takes place inside a combustion chamber. The air to be heated does not enter the combustion chamber but absorbs heat from the outer surface of the chamber. The gases given off by the combustion are vented through a chimney. In an electric furnace, the air to be heated is passed directly over the heating coils. This type of furnace does not require a chimney.
As liquid changes to vapor, it absorbs large amounts of heat. The boiling point of a liquid can be changed by changing the pressure applied to the liquid. This is the same as saying that the temperature of a liquid can be raised by increasing its pressure and lowered by reducing its pressure.
Refrigeration Cycle
If the air from the room is to be cooled, it is passed over a cooling coil. The most common type of residential cooling system is based on the following two principles:
The principal parts of a refrigeration system are the cooling coil (evaporator), compressor (an air pump), the condenser, and the expansion valve, Mechanical Figure 3. Keep in mind that common refrigerants can boil (change to a vapor) at very low temperaturessome as low as 21F below zero. Also remember that a liquid boils at a higher temperature when it is under pressure. The warm air from the ducts is passed over the evaporator. As the cold refrigerant liquid moves through the evaporator coil, it picks up heat from the warm air. As the liquid picks up heat, it changes to a vapor.
CONTENTS
311
The heated refrigerant vapor is then drawn into the compressor where it is put under high pressure. This causes the temperature of the vapor to rise even more. Next, the high-temperature, high-pressure vapor passes to the condenser where the heat is removed. In residential systems this is done by blowing air over the coils of the condenser. As the condenser removes heat, the vapor changes to a liquid. It is still under high pressure, however. From the condenser, the refrigerant flows to the expansion valve. As the liquid refrigerant passes through the valve, the pressure is reduced. This lowers the temperature of the liquid still further, so that it is ready to pick up more heat. The cold, low-pressure liquid then moves to the evaporator. The pressure in the evaporator is low enough to allow the refrigerant to boil again and absorb more heat from the air passing over the coil of the evaporator.
HOT-WATER SYSTEM
Many buildings are heated by hot-water systems. In a hot-water system, the water is heated in an oil or
gas-fired boiler, then circulated through pipes to radiators or convectors in the rooms. The boiler is supplied with water from the fresh waster supply for the house. The water is circulated around the combustion chamber where it absorbs heat. In some systems, one pipe leaves the boiler and runs through the building and back to the boiler. In this type, called a one-pipe system, the heated water leaves the supply, is circulated through the outlet, and is returned to the same pipe. A typical onepipe system uses a specially designed tee to divert water to a radiator or other heating convection outlet. A cone-shaped venturi that is built into the tee by the manufacturer creates resistance to the flow of water. This diverts part of the water flow into the branch outlet, through the radiator, and back into the main flow, Mechanical Figure 4. A two-pipe system uses two pipes running throughout the building. One pipe supplies heated water to all of the outlets. The other is a return pipe, which carries the water back to the boiler for reheating, Mechanical Figure 5. Hot-water systems use a pump, called a circulator, to move the water through the system. The water is kept
WATER MERGES
ONE-PIPE SYSTEM
CONTENTS
312
at a temperature of 150180F in the boiler. When heat is needed, the thermostat starts the circulator.
SUMMARY
Information regarding the scale of the drawing and specific information on the sheet is found on the title of the sheet. It is important for the technician to gain an understanding of the entire mechanical system before concentrating on any of its parts. The types of air conditioning and heating units and their locations are shown on the mechanical plans. If there is no directional arrow on the plans, the top of the plan is considered north. The technician should study the supply and return air ductwork throughout the system. When ductwork sizes are stated, the first number refers to the visible side of the ductwork, and the second number refers to the other dimension. The Air Distribution Schedule describes supply and return outlets for typical units or includes a detailed description in the specification. Written notes and instructions may be placed on the plans.