Excel Electricals
C/23 KARELIBAUG IND. CO. OP. ESTATE, NEAR TELEPHONE, OFFICE, KARELIBAUG. VADODARA-390018 . Tele: 2462913. Email: - excel.elect@gmail.com
Study Coordinated by
Contents
1 2 3 4 5 6 7 8 9 10 Purpose Regulatory Background What is Arc Flash Flash Hazard Analysis and Flash Protection Boundary Personal Protective Equipment References Executive Summary Detailed Summary Single Line diagram 11kV-0.433 kV Single Line diagram for coordination study short circuit currents-scenerio 1-Grid 2 2 3 4 5 6 7 8 10 11 12 16 17 21 22 26 27 31 33 37 51 54 55 56 88 89 121 123 124 125
11 Short circuit detailed Report -Scenerio 1 Grid Feeding 12 Single Line diagram for coordination study short circuit currents-scenerio 2-TB 13 Short circuit detailed Report -Scenerio 2 TB Feeding 14 Single Line diagram for coordination study short circuit currents-scenerio 3-Single DG 15 Short circuit detailed Report -Scenerio 3 Single DG Feeding 16 Single Line diagram for coordination study short circuit currents-scenerio 4-parallel DG 17 18 19 20 21 22 23 24 25 26 27 Short circuit detailed Report -Scenerio 4 Parallel DG Feeding Setting Calculations for Transformers Setting Details for 11 kV switch Gear Setting Details for 0.433 kVPCC (Relays ) TCC Curves Table 2-Detailed Summary of Calculations Single Line diagram for ARC FLASH STUDY Labels Sample work permit Estimated Total Energy Graph for various Busbars Arc Flash Boundary Figure
28 PPE details 29 Approach Boundaries to Live parts 30 Illustrated Protective Clothing and Personal Protective Equipments
PURPOSE The purpose of this report is to document and tabulate Incident Energy and the Flash Protection Boundary at various 11 KV and 433 Volt unit substation buses at Clients factory in Kutch, Gujarat in the unlikely event that electrical equipment failures occur when work is being performed in accordance with plant policies and procedures. The results presented in this report are to be used as a guide in the selection of Personal Protective Equipment (PPE) if work must be performed on or near energized electrical equipment. DISCUSSION Regulatory Background U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) are the enforcement agency for workplace incidents involving personnel. If there is an arc flash incident, it will most likely be investigated by OSHA. Currently, OSHA is recommending that companies follow NFPA 70E as a guideline for worker safety. In addition, OSHA has begun to review NFPA 70E guidelines as a part of their routine inspection procedures. NFPA 70E (Standard for Electrical Safety Requirements for Employee Workplaces) and NFPA 70 (National Electrical Code) provide the basis for employers to determine if electrical hazards are present and to determine the proper types of Personal Protective Equipment (PPE) that will protect employees in the unlikely event that electrical equipment failures occur when work is being performed in accordance with plant policies and procedures. NEC Article 110.16 (Flash Protection) states: Switchboards, panel boards, industrial control panels, meter socket enclosures, and motor control centers, that are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly
visible to qualified persons before examination, adjustment, servicing or maintenance of the equipment. Although there is no such regulation is prevailing in India M/s Cargill India Pvt. Ltd were in the interest of safety requested M/s Excel Electricals to do ARC FLASH STUDY for the entire Electrical distribution system and submit the Report for selection of PPE and to indicate the Flash Protection boundary for each Electrical Equipment such as Switch Boards, Panel boards, Control panels etc. This task of analysis and study and submission of Report was entrusted to M/s Interface Electronics Pvt Ltd who is submitting this report.
What is Arc Flash? Arc Flash is the rapid release of energy due to an arcing fault between a phase conductor and another phase conductor, neutral conductor, ground conductor, or grounded surface. During an arcing fault, ionized gases in the air gap between conductive surfaces become current conducting plasma. Arcing faults are generally limited to systems where the bus voltage is in excess of 250 volts, AC. In AC systems, lower voltage levels normally will not sustain an arc as voltage recovery is not quick enough for an arc to restrike after a zero current occurs. An arcing fault is similar to the arc obtained during electric welding. Arcing faults can be the result of a failure, such as: breakdown of insulation, accidental contact, or momentary contact. Hazardous Arc-Flash can occur in any electrical device in which voltage is high enough to sustain an arc. In industrial settings, this includes: Panel boards and switchboards Motor control centers Metal-clad switchgear Transformers Motor starters High voltage switching and grounding equipment Pad-mounted switching equipment Meter bases and meter banks
Any electrical equipment that has sufficient voltage to ionize the air gap in the unlikely event that electrical equipment failure occurs
Flash Hazard Analysis and Flash Protection Boundary Prior to commencing work on electrically energized conductors > 50 volts, NFPA 70E 130.3 requires that a flash hazard analysis be completed in order to protect personnel from the possibility of being injured by an arc flash. The analysis shall determine the Flash Protection Boundary and the personal protective equipment that shall be used within the Flash Protective Boundary. Table 130.7(C)(a) can be used in lieu of an arc flash hazard analysis for various tasks listed in the table. For tasks not listed, or for power systems with greater short-circuit current capacity or longer fault clearing times, a flash hazard analysis shall be required. NFPA 70E 130.3(A) requires employers to establish a flash protection boundary a distance from exposed energized electrical parts at which an employee would sustain no more than a second degree burn if an electric arc flash were to occur. Employees performing work on energized conductors inside the flash protection boundary must be protected with appropriate PPE. At voltage levels below 600 volts, the flash protection boundary is the distance at which incident energy level is equal to 1.2 cal/cm 2. For situations where fault-clearing time is 0.1 seconds or less, the flash protection boundary is the distance at which incident energy level is equal to 1.5 cal/cm 2.
When work is to be performed within the flash protection boundary, the flash hazard analysis determines the incident energy exposure of the worker (cal/cm2). This incident energy exposure level is based on the working distance of the employees face and the chest areas from a potential arc source for the specified task to be performed. Flame resistant clothing and PPE used by the worker must be based upon the incident energy exposure associated with the specific task. Recognizing that incident energy increases as distance from arc flash decreases, additional PPE shall be used for any
parts of the body that are closer than the distance at which the incident energy was determined. NFPA 70E 2004 is a safety standard for worker safety as a part of National Fire Protection Association (NFPA) guidelines. Among other safe workplace practices, it provides awareness on the hazards of arc flash incidents. Steps required to comply with NFPA 70E, Chapter 1 Article 110.8 (B)(1)(b), 130.3, and 130.7 (C)(9)(a) include: A comprehensive safety program. Employee arc flash awareness safety training. Safety procedures and manuals that are updated to comply with the NFPA 70E guidelines. Up to date facility single line diagrams, short circuit studies and protective device coordination studies
Personal Protective Equipment NFPA specifies the requirements for PPE for workers within flash protection boundaries. All parts of the body, which may be exposed to arc flash, need to be covered by appropriate PPE. The entire PPE set may be comprised of fire retardant clothing, helmet, headgear, face shield, safety glasses, gloves, shoes, etc. The amount of PPE required needs to be determined on the basis of calculated incident energy on a worker. The calculations need to be performed by a qualified person, such as an engineer. The protective clothing should limit the incident energy reaching the chest/face of the worker to less than 1.2 cal/cm 2. Fire retardant clothing provides thermal insulation and is also self-extinguishing. Protective clothing is rated in cal/cm2. ASSUMPTIONS & INPUTS 1. Short circuit values were calculated through the use of a computerized plant electrical system model using field collected data and drawings. 2. The Calculations and results are based on the input information furnished by Excel Electricals..
3. Short circuit MVA of 250 for one sec is assumed at the point of supply for calculation purpose, as the correct fault level is not available from the local Electricity authorities. 4. Minimum personnel distance from the arc fault was determined using standard industry practice. References 1. NFPA 70 - National Electrical Code - 2005 Edition 2. NFPA 70E - Standard for Electrical Safety in the Workplace - 2004 Edition
EXECUTIVE SUMMARY Calculations were prepared utilizing EDSA Paladin Design Base 4, a commercially available, computer aided engineering tool for the analysis of industrial, utility, and commercial electrical power systems. Arc flash hazard analysis was developed within the short circuit module of EDSA Paladin Design base 2. A copy of the one line diagram developed within EDSA is included as an attachment.
A table giving the details BUS NAME, ARC GAP, BOLTED FAULT,
ESTIMATED ARC FAULT, ESTMATED ARC FLASH BOUNDARY, INCIDENT OF ENERGY, WORKING DISTANCE and REQUIRED CLOTHING CLASS is
included
in the report Illustrations of different PPE are given in the Report. Warning Labels as Generated for various Buses based on the Energy incident calculations is given in the report. Graph giving the Incident of Energy with reference to Distance is given for all the Busses for reference.
DETAILED SUMMARY Incident energy and arc flash boundary calculations were prepared utilizing EDSA-Paladin Design Base 2. The analysis yields results as required by NFPA-70E, namely, specification of the arc flash boundary (AFB) and the incident arc energy at a probable working distance. We have evaluated the calculations for two different fault levels namely 5000 MVA sec and 1500 mva sec at the Incoming side of the Plant. Complete results are listed in Table 1. and Table 2 respectively. The graphs and the warning Labels are prepared based on Table I only. An explanation of the data presented in Table 1 is as follows: Arc Fault Bus Name: This is the name of the buses where an arc flash is postulated. Arc Fault Bus Voltage: The nominal voltage of the bus where an arc flash is postulated. Arc Gap (mm): This is the gap between the phase conductors. The gap is specified according to voltage. Bolted Fault (kA): This is the calculated current for a 3-phase bolted fault at the faulted bus. Estimated Arc Fault (kA): This is the estimated current when arc resistance is included in calculation. When calculating incident energy, bolted fault current at the faulted bus is used. Arc Time (sec): Total duration of arc fault as explained in assumptions and inputs. Estimated Arc Flash Boundary: The flash protection boundary distance in cm for the arc gap, bolted fault current, and arc time as explained above.
Working Distance: Approximate working distance in cm corresponding to the trip device. The trip time associated with the trip device is used in the calculation. The rating of personal protective equipment (PPE) worn by workers should be based on this value.
Incident Energy (cal/cm): This is the incident energy from arc flash
Required Clothing Class: This is the hazard/risk category as per NFPA 70E. Appropriate PPE, as listed in Table 5, is recommended according to this classification.
TG PGVCL
GEN
CAB_TG
50 51
R_P1_HT
Transformer 11
50 51
R_P2_HT
50 51
GEN
DG1_ACB
GEN
DG2_ACB
GEN
DG3_ACB
GEN
DG4_ACB
GEN
DG5_ACB
CAB_TR1
CAB_TR2
CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51
50 51
R_P1
50 51
R_P2
50 51
R_P15
50 51
R_P16
50 51
R_P17
50 51
R_P18
50 51
R_P19
BD_TR1 TR1_IC_1F
OG_PCC AUX_3F
OG_REF1_4F
OG_DMP_6F
BD_TR2 TR2_IC_2F
DG1_IC_15F
DG2_IC_16F
DG3_IC_17F
DG4_IC_18F
OG_EO_12F3
OG BOI1_10F
OG_SL_14F2
OGBOI2_11F
OG_DCT2_8F
OG_CCT2_9F
OG_FR_12F1
OG_HG_12F2
OGCCT1_13F1
OG_ETP_13F2
OG_ROT_13F3
OG_CHP_14F3
FIRE PUMP_14F1
RP_14
50 51
R_P3
50 51
R_P4
50 51
R_P6
50 51
R_P10
50 51
R_P11
50 51
R_P13
50 51
R_P12
CAB_PACK2
CAB_PACK3
CAB_PACK1
CAB_PCCAUX
CAB_BOILER2
WAREHOUSE1
CAB_WH1 WH1_IC
WAREHOUSE2
CAB_WH2 WH2_IC
CAB_DCT
CAB_CAP
CAB_WSS
CAB_REF1
CAB_DMP
CAB_EO
CAB_BOILER1
CAB_SL
CAB_DCT2
CAB_CCT2
CAB_FR
CAB_HG
CAB_CCT1
CAB_ETP
CAB_AOP
CAB_ROT
CAB_COT
CAB_CHP
290
CAB:CAP1
PACK2_IC
PACK1_IC
PACK3_IC
DCT_IC
CAP_IC
IWS_IC FWS_IC
295
BOILER1_IC
SL_IC
BOILER2_IC
DCT2_IC
CCT2_IC
IFR_IC FFR_IC
IHY_IC FHY_IC
ICCT1_IC FCCT1_IC
IETP_IC3 FETP_IC
IAOP_IC1 FAOP_IC1
IROT_IC2 FROT_IC2
ICOT_IC4 FCOT_IC4
Packing MCC 2
Packing MCC 1
Packing MCC 3 DCT 3 CAPACITOR PNL Work Shop CAP1 PCC AUX IPDB_OG IVPDB_OG DM PLANT FPDB_OG FVPDB_OG ENGG OFF
BOILER1
IBF1_OG
STREET LIGHT
BOILER 2
IBF2_OG
FBF1_OG
FBF2_OG
Coal H Plant
CAB_BF1
CAB:BF2
IBF1_IC
IBF2_IC
FBF1_IC
FBF2_IC
Bag Filter1
Bag Filter2
REV. DATE
ECO#
DWN APP
DESCRIPTION
DRAWN B Y/DATE :
DW G N o.:
10
RE V.
EN G. APP./ DATE:
SCAL E:
GEN
CAB_TG
50 51
R_P1_HT
Transformer 11
50 51
R_P2_HT
50 51
GEN
DG1_ACB
GEN
DG2_ACB
GEN
DG3_ACB
GEN
DG4_ACB
GEN
DG5_ACB
CAB_TR1
CAB_TR2
CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 29374.74A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51
50 51
R_P1
50 51
R_P2
50 51
R_P15
50 51
R_P16
50 51
R_P17
50 51
R_P18
50 51
R_P19
BD_TR1 TR1_IC_1F
OG_PCC AUX_3F
OG_REF1_4F
OG_DMP_6F
BD_TR2 TR2_IC_2F
DG1_IC_15F
DG2_IC_16F
DG3_IC_17F
DG4_IC_18F
OG_EO_12F3
OG BOI1_10F
OG_SL_14F2
OGBOI2_11F
OG_DCT2_8F
OG_CCT2_9F
OG_FR_12F1
OG_HG_12F2
OGCCT1_13F1
OG_ETP_13F2
OG_ROT_13F3
OG_CHP_14F3
FIRE PUMP_14F1
RP_14
50 51
R_P3
50 51
R_P4
50 51
R_P6
50 51
R_P10
50 51
R_P11
50 51
R_P13
50 51
R_P12
CAB_PACK2
CAB_PACK3
CAB_PACK1
CAB_PCCAUX
CAB_BOILER2
CAB_WH1 WH1_IC
CAB_WH2 WH2_IC
CAB_DCT
CAB_CAP
CAB_WSS
CAB_REF1
CAB_DMP
CAB_EO
CAB_BOILER1
CAB_SL
CAB_DCT2
CAB_CCT2
CAB_FR
CAB_HG
CAB_CCT1
CAB_ETP
CAB_AOP
CAB_ROT
CAB_COT
CAB_CHP
290
CAB:CAP1
PACK2_IC
PACK1_IC
PACK3_IC
DCT_IC
CAP_IC
IWS_IC FWS_IC
295
IDMP_IC FDMP_IC
EO_IC
BOILER1_IC
SL_IC
BOILER2_IC
DCT2_IC
CCT2_IC
IFR_IC FFR_IC
IHY_IC FHY_IC
ICCT1_IC FCCT1_IC
IETP_IC3 FETP_IC
IAOP_IC1 FAOP_IC1
IROT_IC2 FROT_IC2
ICOT_IC4 FCOT_IC4
CAPACITOR PNL Sym : 7555.11A Work Shop Sym : 14317.94A CAP1 Sym : 16742.59A
CCT2 Sym : 8972.44A FRACTIONATION Sym : 13097.17A HYDROGENERATION Sym : 13175.97A CCT1 Sym : 12146.36A ETP Sym : 5530.48A AOP Sym : 5956.55A ROT Sym : 4388.88A CRUDE OIL TANK Sym : 5155.98A Coal H Plant Sym : 18051.05A FIRE PUMP PANEL Sym : 18463.48A
IVPDB_OG
IBF1_IC
IBF2_IC
FBF1_IC
FBF2_IC
SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO1- GRID: SOURCE MAINS FEED
REV. DATE
ECO#
DWN APP
DESCRIPTION
DRAWN B Y/DATE :
DW G N o.:
11
RE V.
EN G. APP./ DATE:
SCAL E:
Short Circuit Detailed Report MAINS SOURCE FAULT 250MVASEC SCENERIO 1 GRID FEEDING
3P Fault - IEC60909 Method
Bus Name Pre Fault Voltage 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 13122 29375 29328 22210 22112 22112 22052 19122 18463 18051 16743 16057 15791 15630 14318 13721 13715 13176 13097 12732 12146 11752 11688 11436 9812 8972 8173 7582 7582 7555 5957 5530 5156 4389 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 34416 13122 13122 64185 29375 29375 63495 29328 29328 39332 22210 22210 38933 22112 22112 38933 22112 22112 40835 22052 22052 31956 19122 19122 33686 18463 18463 30712 18051 18051 28488 16743 16743 28400 16057 16057 25237 15791 15791 26022 15630 15630 22942 14318 14318 24096 13721 13721 23422 13715 13715 20766 13176 13176 20621 13097 13097 21356 12732 12732 18902 12146 12146 17993 11752 11752 17884 11688 11688 17458 11436 11436 14887 9812 9812 13410 8972 8972 12158 8173 8173 11236 7582 7582 11236 7582 7582 11193 7555 7555 8772 5957 5957 8122 5530 5530 7318 5156 5156 6223 4389 4389
PGVCL Main panel_TB Main panel BB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT
12
PGVCL Main panel_TB Main panel BB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT
13
PGVCL Main panel_TB Main panel BB PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 DCT2 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ROT ETP
14
PGVCL Main panel_TB Main panel BB PCC AUX ENGG OFF BOILER 2 BOILER1 Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT
15
GEN
CAB_TG
50 51
R_P1_HT
VCB_IC1
Transformer 11
50 51
R_P2_HT
50 51
GEN
DG1_ACB
GEN
DG2_ACB
GEN
DG3_ACB
GEN
DG4_ACB
GEN
DG5_ACB
CAB_TR1
CAB_TR2
CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 3088.91A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51
50 51
R_P1
50 51
R_P2
50 51
R_P15
50 51
R_P16
50 51
R_P17
50 51
R_P18
50 51
R_P19
BD_TR1 TR1_IC_1F
OG_PCC AUX_3F
OG_REF1_4F
OG_DMP_6F
BD_TR2 TR2_IC_2F
DG1_IC_15F
DG2_IC_16F
DG3_IC_17F
DG4_IC_18F
OG_EO_12F3
OG BOI1_10F
OG_SL_14F2
OGBOI2_11F
OG_DCT2_8F
OG_CCT2_9F
OG_FR_12F1
OG_HG_12F2
OGCCT1_13F1
OG_ETP_13F2
OG_ROT_13F3
OG_CHP_14F3
FIRE PUMP_14F1
RP_14
50 51
R_P3
50 51
R_P4
50 51
R_P6
50 51
R_P10
50 51
R_P11
50 51
R_P13
50 51
R_P12
CAB_PACK2
CAB_PACK3
CAB_PACK1
CAB_PCCAUX
CAB_BOILER2
CAB_WH1 WH1_IC
CAB_WH2 WH2_IC
CAB_DCT
CAB_CAP
CAB_WSS
CAB_REF1
CAB_DMP
CAB_EO
CAB_BOILER1
CAB_SL
CAB_DCT2
CAB_CCT2
CAB_FR
CAB_HG
CAB_CCT1
CAB_ETP
CAB_AOP
CAB_ROT
CAB_COT
CAB_CHP
290
CAB:CAP1
PACK2_IC
PACK1_IC
PACK3_IC
DCT_IC
CAP_IC
IWS_IC FWS_IC
295
IDMP_IC FDMP_IC
EO_IC
BOILER1_IC
SL_IC
BOILER2_IC
DCT2_IC
CCT2_IC
IFR_IC FFR_IC
IHY_IC FHY_IC
ICCT1_IC FCCT1_IC
IETP_IC3 FETP_IC
IAOP_IC1 FAOP_IC1
IROT_IC2 FROT_IC2
ICOT_IC4 FCOT_IC4
CAPACITOR PNL Sym : 2512.18A Work Shop Sym : 2842.23A CAP1 Sym : 2898.21A
CCT2 Sym : 2621A FRACTIONATION Sym : 2805.03A HYDROGENERATION Sym : 2807.69A CCT1 Sym : 2770.62A ETP Sym : 2283.21A AOP Sym : 2339.61A ROT Sym : 2230.73A CRUDE OIL TANK Sym : 2360.75A Coal H Plant Sym : 2932.56A FIRE PUMP PANEL Sym : 2928.15A
IVPDB_OG
IBF1_IC
IBF2_IC
FBF1_IC
FBF2_IC
SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO2- TURBO SET: SOURCE TURBOSET FEED
REV. DATE
ECO#
DWN APP
DESCRIPTION
DRAWN B Y/DATE :
DW G N o.:
16
RE V.
EN G. APP./ DATE:
SCAL E:
TG TG_PNL Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT
11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
17
TG TG_PNL Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT
11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
18
TG TG_PNL Main panel BB Main panel_TB PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 DCT2 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ROT ETP
11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
19
TG TG_PNL Main panel_TB Main panel BB PCC AUX ENGG OFF BOILER 2 BOILER1 Refinary 1 FIRE PUMP PANEL CAP1 Coal H Plant DCT2 Bag Filter1 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT
11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
20
TG PGVCL
GEN
CAB_TG
50 51
R_P1_HT
Transformer 11
50 51
R_P2_HT
50 51
R_P3_HT
DG2
DG3
DG4
DG5
GEN
DG1_ACB
GEN
DG2_ACB
GEN
DG3_ACB
GEN
DG4_ACB
GEN
DG5_ACB
CAB_TR1
CAB_TR2
CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 724.14A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51
50 51
R_P1
50 51
R_P2
50 51
R_P15
50 51
R_P16
50 51
R_P17
50 51
R_P18
50 51
R_P19
BD_TR1 TR1_IC_1F
OG_PCC AUX_3F
OG_REF1_4F
OG_DMP_6F
BD_TR2 TR2_IC_2F
DG1_IC_15F
DG2_IC_16F
DG3_IC_17F
DG4_IC_18F
OG_EO_12F3
OG BOI1_10F
OG_SL_14F2
OGBOI2_11F
OG_DCT2_8F
OG_CCT2_9F
OG_FR_12F1
OG_HG_12F2
OGCCT1_13F1
OG_ETP_13F2
OG_ROT_13F3
OG_CHP_14F3
FIRE PUMP_14F1
RP_14
50 51
R_P3
50 51
R_P4
50 51
R_P6
50 51
R_P10
50 51
R_P11
50 51
R_P13
50 51
R_P12
CAB_PACK2
CAB_PACK3
CAB_PACK1
CAB_PCCAUX
CAB_BOILER2
CAB_WH1 WH1_IC
CAB_WH2 WH2_IC
CAB_DCT
CAB_CAP
CAB_WSS
CAB_REF1
CAB_DMP
CAB_EO
CAB_BOILER1
CAB_SL
CAB_DCT2
CAB_CCT2
CAB_FR
CAB_HG
CAB_CCT1
CAB_ETP
CAB_AOP
CAB_ROT
CAB_COT
CAB_CHP
290
CAB:CAP1
PACK2_IC
PACK1_IC
PACK3_IC
DCT_IC
CAP_IC
IWS_IC FWS_IC
295
IDMP_IC FDMP_IC
EO_IC
BOILER1_IC
SL_IC
BOILER2_IC
DCT2_IC
CCT2_IC
IFR_IC FFR_IC
IHY_IC FHY_IC
ICCT1_IC FCCT1_IC
IETP_IC3 FETP_IC
IAOP_IC1 FAOP_IC1
IROT_IC2 FROT_IC2
ICOT_IC4 FCOT_IC4
CAPACITOR PNL Sym : 690.58A Work Shop Sym : 710.35A CAP1 Sym : 713.45A PCC AUX Sym : 719.24A IPDB_OG FPDB_OG
IBF1_OG FBF1_OG
CCT2 Sym : 697.43A FRACTIONATION Sym : 708.2A HYDROGENERATION Sym : 708.35A CCT1 Sym : 706.19A ETP Sym : 674.62A AOP Sym : 678.66A ROT Sym : 678.81A CRUDE OIL TANK Sym : 686.47A Coal H Plant Sym : 715.47A FIRE PUMP PANEL Sym : 715.09A
IVPDB_OG
IBF1_IC
IBF2_IC
FBF1_IC
FBF2_IC
SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO3- DG SINGLE: SOURCE SINGLE DG FEED
REV. DATE
ECO#
DWN APP
DESCRIPTION
DRAWN B Y/DATE :
DW G N o.:
21
RE V.
EN G. APP./ DATE:
SCAL E:
DG1 Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 Coal H Plant FIRE PUMP PANEL CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop HYDROGENERATION Bag Filter2 FRACTIONATION VPDB PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT
433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
22
Bus Name DG1 Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 Coal H Plant FIRE PUMP PANEL CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop HYDROGENERATION Bag Filter2 FRACTIONATION VPDB PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT
Pre-Flt( V ) Ik" 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
23
DG1 Main panel BB Main panel_TB PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 STREET LIGHT DCT2 Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK ROT AOP ETP
433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
24
Bus Name DG1 Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ETP ROT
Pre-Flt( V ) Ik" 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433
25
TG PGVCL
GEN
CAB_TG
50 51
R_P1_HT
Transformer 11
50 51
R_P2_HT
50 51
R_P3_HT
GEN
DG1_ACB
GEN
DG2_ACB
GEN
DG3_ACB
GEN
DG4_ACB
GEN
DG5_ACB
CAB_TR1
CAB_TR2
CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 2896.67A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51
50 51
R_P1
50 51
R_P2
50 51
R_P15
50 51
R_P16
50 51
R_P17
50 51
R_P18
50 51
R_P19
BD_TR1 TR1_IC_1F
OG_PCC AUX_3F
OG_REF1_4F
OG_DMP_6F
BD_TR2 TR2_IC_2F
DG1_IC_15F
DG2_IC_16F
DG3_IC_17F
DG4_IC_18F
OG_EO_12F3
OG BOI1_10F
OG_SL_14F2
OGBOI2_11F
OG_DCT2_8F
OG_CCT2_9F
OG_FR_12F1
OG_HG_12F2
OGCCT1_13F1
OG_ETP_13F2
OG_ROT_13F3
OG_CHP_14F3
FIRE PUMP_14F1
RP_14
50 51
R_P3
50 51
R_P4
50 51
R_P6
50 51
R_P10
50 51
R_P11
50 51
R_P13
50 51
R_P12
CAB_PACK2
CAB_PACK3
CAB_PACK1
CAB_PCCAUX
CAB_BOILER2
CAB_WH1 WH1_IC
CAB_WH2 WH2_IC
CAB_DCT
CAB_CAP
CAB_WSS
CAB_REF1
CAB_DMP
CAB_EO
CAB_BOILER1
CAB_SL
CAB_DCT2
CAB_CCT2
CAB_FR
CAB_HG
CAB_CCT1
CAB_ETP
CAB_AOP
CAB_ROT
CAB_COT
CAB_CHP
290
CAB:CAP1
PACK2_IC
PACK1_IC
PACK3_IC
DCT_IC
CAP_IC
IWS_IC FWS_IC
295
IDMP_IC FDMP_IC
EO_IC
BOILER1_IC
SL_IC
BOILER2_IC
DCT2_IC
CCT2_IC
IFR_IC FFR_IC
IHY_IC FHY_IC
ICCT1_IC FCCT1_IC
IETP_IC3 FETP_IC
IAOP_IC1 FAOP_IC1
IROT_IC2 FROT_IC2
ICOT_IC4 FCOT_IC4
CAPACITOR PNL Sym : 2390.3A Work Shop Sym : 2681.37A CAP1 Sym : 2730.02A
IBF1_OG FBF1_OG
CCT2 Sym : 2486.95A FRACTIONATION Sym : 2648.73A HYDROGENERATION Sym : 2651.07A CCT1 Sym : 2618.52A ETP Sym : 2184.73A AOP Sym : 2235.51A ROT Sym : 2144.66A CRUDE OIL TANK Sym : 2261.3A Coal H Plant Sym : 2760.31A FIRE PUMP PANEL Sym : 2755.89A
IVPDB_OG
IBF1_IC
IBF2_IC
FBF1_IC
FBF2_IC
SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO4- DG PARALLEL: SOURCE PARALLEL DG FEED
REV. DATE
ECO#
DWN APP
DESCRIPTION
DRAWN B Y/DATE :
DW G N o.:
26
RE V.
EN G. APP./ DATE:
SCAL E:
Main panel BB Main panel_TB DG4 DG2 DG1 DG3 DG5 ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT
27
Main panel BB Main panel_TB DG4 DG2 DG1 DG3 DG5 ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT
28
Main panel BB Main panel_TB DG4 DG5 DG2 DG1 DG3 PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 DCT2 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ROT ETP
29
Main panel BB Main panel_TB DG4 DG5 DG2 DG1 DG3 PCC AUX ENGG OFF BOILER 2 BOILER1 Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 Bag Filter1 STREET LIGHT Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT
30
11kV
CTHV:100/5
1.25 MVA
In:2500A
0.433kV
Transformer capacity Primary Voltage Secondary Voltage Transformer HV side CT details CTHV Turns Ratio Transformer LV ACB rating Turns Ratio Percentage Impedance of Transformer Fault Current at 11 kV Bus as per report Fault current at 0.433 kV Bus as per report Transformer HV side Primary Current Transformer LV side current as per name plate Transformer HV side Primary current with 10 % Over load Transformer HV side CT Secondary Full Load Current Transformer HV side CT Secondary current with 10 % Over load IDMT setting at 11 kV side
Setting proposed Ip
PT Vp Vs CTR1
Ipfl
Isfl
1250 11 0.433 100/5 20 2500 2500 5.00% 13122 29328 65.68 1666.00 72.25 3.28 3.61 4.25 85.00
kVA kV kV
A A Amps Amps
Isfl
Transformer LV side Primary current with 10 % Over load Transformer LV side CT Secondary current with 10 % Over load IDMT setting at0.433kV side
Setting proposed Ip Curve
Amps
0.73
Fault current at0.433kV Bus as per report,for MINIMUM SOURCE Fault HV side current due to fault at 0.433 kV bus HV side CT Secondary current due to fault at0.433kV bus HV side CT current due to fault at Transformer HV side Setting proposed on HV side relay I>> Setting proposed on LV side relay I>>
29328.00 1154.46
57.72 656.10
45.00 900.00 6
11kV
CTHV:125/1
0.433kV
31
11kV
CTHV:125/1
0.433kV
Transformer capacity Primary Voltage Secondary Voltage Transformer HV side CT details CTHV Turns Ratio Transformer LV side CT details CTLV Turns Ratio Transformer LV side ACB rating Percentage Impedance of Transformer Fault Current at 11 kV Bus as per report Fault current at 0.433 kV Bus Transformer HV side current as per name plate Transformer LV side current as per name plate Transformer HV side Primary current with 10 % Over load Transformer HV side CT Secondary Full Load Current Transformer HV side CT Secondary current with 10 % Over load IDMT setting at 11 kV side
Setting proposed Ip
PT Vp Vs CTR1 CTR1 Z
Ipfl
Isfl
2000 11 0.433 125/1 125 3000/5 600 4000 6.78% 1535 20272 105.00 2666.80 115.50 0.84 0.92 115.47/125 0.92
0.95
kVA kV kV
A A
Amps
Transformer Full Load LV side Primary Current Transformer LV side Primary current with 10 % Over load Transformer LV side CT Secondary Full Load Current Transformer LV side CT Secondary current with 10 % Over load IDMT setting at 0.433kV side at 100 % load IDMT setting at 0.433kV side at 110 % load
Setting proposed Ip Curve
Isfl
2666.82 2933.51
4.44 4.89
Amps Amps
Fault current at0.433kV Bus as per report,for MINIMUM SOURCE Fault HV side current due to fault at 0.433 kV bus HV side CT Secondary current due to fault at0.433kV bus HV side CT current due to fault at Transformer HV side Setting proposed on HV side relay I>> Setting proposed on LV side relay I>>
20272.00 797.98
6.38 12.28
8.00 3
32
RELAY POINTS:VCB_IC Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
100A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
33
Setting Enabled
Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
Setting
250A
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
34
RELAY POINTS:RP2_HT Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
125A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
35
RELAY POINTS:RP3_HT Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
125A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
36
RELAY POINTS:RP1 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
3000 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
37
RELAY POINTS:RP1 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
3000 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
38
RELAY POINTS:RP15 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
39
RELAY POINTS:RP16 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
40
RELAY POINTS:RP17 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
41
RELAY POINTS:RP18 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
42
RELAY POINTS:RP19 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
43
RELAY POINTS:RP3 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
44
RELAY POINTS:RP4 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
1600 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
45
RELAY POINTS:RP6 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
46
RELAY POINTS:RP10 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
1000 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
47
RELAY POINTS:RP11 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
1000 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
48
RELAY POINTS:RP12 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
49
RELAY POINTS:RP13 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled
Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A
Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve
Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve
Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse
50
1000
10000
Time in Seconds
10
.01
.1
INRUSH
.5
10
1000
0 - Path:PGVCL-11kV Panel-Transformer3-MP_IC_26F
C:\Users\ramesh.cuppu\Documents\PALADIN_PROJECTS\EXELELE240212.PDC
51
1000
10000
.01
.1 .5
Time in Seconds
10
10
1000
C:\Users\ramesh.cuppu\Documents\PALADIN_PROJECTS\EXELELE050312.PDC
52
1000
10000
BOILER1_IC
R_P10
R_P1_1F 100
R_P2_HT
R_P1_HT
Time in Seconds
10
.01
.1
INRUSH
.5
10
1000
C:\Users\ramesh.cuppu\Documents\PALADIN_PROJECTS\EXELELE050312.PDC
53
Bus Name
Bus kV
AOP Bag Filter1 Bag Filter2 BOILER 2 BOILER1 CAPACITOR PNL CCT1 CCT2 Coal H Plant CRUDE OIL TANK DCT 3 DCT2 DM PLANT ENGG OFF ETP FIRE PUMP PANEL FRACTIONATION HYDROGENERATION Main panel BB Main panel_TB Packing MCC 1 Packing MCC 2 Packing MCC 3 PCC AUX PDB Refinary 1 ROT STREET LIGHT TG_PNL WAREHOUSE1 WAREHOUSE2 Work Shop
0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 11.000 0.433 0.433 0.433
0.033 0.030 0.030 0.030 0.030 15.178 2.709 0.030 0.015 3.483 0.030 0.030 0.346 0.022 2.774 0.015 0.015 2.094 0.030 2.389 0.015 0.015 0.015 0.013 0.010 0.030 5.816 0.023 0.030 0.015 0.030 0.015
Trip 3P Fault 3P Arc Flash Working Delay Duratio Boundary Distance Time n (sec) (cm) (cm) (sec)
0.033 0.030 0.030 0.030 0.030 15.178 2.709 0.030 0.015 3.483 0.030 0.030 0.346 0.022 2.774 0.015 0.015 2.094 0.030 2.389 0.015 0.015 0.015 0.013 0.010 0.030 5.816 0.023 0.030 0.015 0.030 0.015 18.9 35.3 32.6 43.1 43.1 1384.7 571.6 25.2 24.1 405.5 21.2 35.9 124.2 35.5 362.6 24.4 19.8 504.0 51.9 900.9 18.2 18.5 18.5 21.6 14.8 39.9 521.9 29.4 1.5 14.3 20.3 20.9 61.000000 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 91.000579 61.000642 61.000642 61.000642
Clothing Required
4.5 - 14.0 oz/yd^2 untreated cotton FR shirt and pants, plus flash suit hood Cotton underclothing plus FR shirt and pants Cotton underclothing plus FR shirt, pants, overalls or equivalent Cotton underclothing plus FR shirt, pants, plus double layer switching coat and pants or equiv. Level exceeds 40 cal/cm^2 - Never work on or near energized system
54
GEN
TG_PNL Vs: 11000 V PPE: 0 AHE: 0.02 cal/cm^2(100%) AFB: 1.51 cm AFD: 0.03 sec WD: 91 cm LAB: 304.8 cm RAB: 66.04 cm PAB: 17.78 cm Isc: 0.7 kA Iarc: 0.71 kA Config.: Box OG_TR1 CAB_TG
TG Vs: 11000 V
50 51
R_P1_HT
VCB_IC1
OG_TR2
Transformer 11
MP_IC_26F
Main panel_TB Vs: 433 V PPE: Extreme Danger AHE: 97.08 cal/cm^2(85%) AFB: 900.86 cm AFD: 2.39 sec WD: 45.5 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 30.71 kA Iarc: 12.33 kA Config.: Switchgear
50 51
R_P2_HT
50 51
R_P3_HT
GEN
DG1_ACB
GEN
DG2_ACB
GEN
DG3_ACB
GEN
DG4_ACB
GEN
DG5_ACB
CAB_TR1
CAB_TR2
CAB_MP1
Transformer 1
Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5 Main panel BB Vs: 433 V PPE: 0 AHE: 0.94 cal/cm^2(100%) AFB: 51.92 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 30.66 kA Iarc: 14.48 kA Config.: Switchgear OG_CCT2_9F OG_FR_12F1 OG_HG_12F2 OGCCT1_13F1 OG_ETP_13F2 OG_CHP_14F3 FIRE PUMP_14F1
50 51
R_P1
50 51
R_P2
COS11
COS21
COS31
COS41
COS51
COS61
COS71
50 51
R_P15
50 51
R_P16
50 51
R_P17
50 51
R_P18
50 51
R_P19
BD_TR1
BD_TR2
COS12
COS22
COS32
COS42
COS52
COS62
COS72
COS82
TR1_IC_1F
TR2_IC_2F
DG1_IC_15F
DG2_IC_16F
DG3_IC_17F
DG4_IC_18F
DG5_IC_18F
OG_PCC AUX_3F
OG_REF1_4F
OG_DMP_6F
OG_EO_12F3
OG BOI1_10F
OG_SL_14F2
OGBOI2_11F
OG_DCT2_8F
OG_ROT_13F3
RP_14
50 51
R_P3
50 51
R_P4
50 51
R_P6
50 51
R_P10
50 51
R_P11
50 51
R_P13
50 51
R_P12
CAB_PACK2
CAB_PACK3
CAB_PACK1
CAB_PCCAUX
CAB_BOILER2
WAREHOUSE1 Vs: 433 V PPE: 0 AHE: 0.14 cal/cm^2(100%) AFB: 14.25 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 7.65 kA Iarc: 4.72 kA Config.: Switchgear WAREHOUSE2 Vs: 433 V PPE: 0 AHE: 0.24 cal/cm^2(85%) AFB: 20.25 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 7.65 kA Iarc: 4.02 kA Config.: Switchgear
CAB_WH1 WH1_IC
CAB_WH2 WH2_IC
CAB_DCT
CAB_CAP
CAB_WSS
CAB_REF1
CAB_DMP
CAB_EO
CAB_BOILER1
CAB_SL
CAB_DCT2
CAB_CCT2
CAB_FR
CAB_HG
CAB_CCT1
CAB_ETP
CAB_AOP
CAB_ROT
CAB_COT
CAB_CHP
290
CAB:CAP1
PACK2_IC
PACK1_IC
PACK3_IC
DCT_IC
CAP_IC
IWS_IC FWS_IC
295
REF1_IC PCC_AUX_IC Refinary 1 Vs: 433 V PPE: 0 AHE: 0.64 cal/cm^2(100%) AFB: 39.87 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 19.63 kA Iarc: 10.11 kA Config.: Switchgear
IDMP_IC FDMP_IC
EO_IC
BOILER1_IC
SL_IC
BOILER2_IC
DCT2_IC
CCT2_IC
IFR_IC FFR_IC
IHY_IC FHY_IC
ICCT1_IC FCCT1_IC
IETP_IC3 FETP_IC
IAOP_IC1 FAOP_IC1
IROT_IC2 FROT_IC2
ICOT_IC4 FCOT_IC4
Packing MCC 2 Packing MCC 3 Vs: 433 V Vs: 433 V PPE: 0 PPE: 0 AHE: 0.21 cal/cm^2(100%) AHE: 0.21 cal/cm^2(100%) AFB: 18.48 cm AFB: 18.54 cm AFD: 0.02 sec AFD: 0.02 sec WD: 61 cm WD: 61 cm LAB: 304.8 cm LAB: 304.8 cm RAB: 30.48 cm RAB: 30.48 cm PAB: 2.54 cm PAB: 2.54 cm Isc: 11.86 kA Isc: 11.92 kA Iarc: 6.73 kA Iarc: 6.76 kA Config.: Switchgear Packing MCC 1 Config.: Switchgear Vs: 433 V PPE: 0 AHE: 0.2 cal/cm^2(100%) AFB: 18.24 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 11.6 kA Iarc: 6.61 kA Config.: Switchgear
CAPACITOR PNL Vs: 433 V PPE: Extreme Danger AHE: 118.74 cal/cm^2(85%) CAP1 AFB: 1384.68 cm Vs: 433 V AFD: 15.18 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 7.62 kA Work Shop Iarc: 4 kA DCT 3 Vs: 433 V Config.: Switchgear Vs: 433 V PPE: 0 PPE: 0 AHE: 0.25 cal/cm^2(100%) AHE: 0.25 cal/cm^2(85%) AFB: 20.89 cm AFB: 21.18 cm AFD: 0.02 sec AFD: 0.03 sec WD: 61 cm WD: 61 cm LAB: 304.8 cm LAB: 304.8 cm RAB: 30.48 cm RAB: 30.48 cm PAB: 2.54 cm PAB: 2.54 cm Isc: 14.59 kA Isc: 8.25 kA Iarc: 7.96 kA Iarc: 4.27 kA Config.: Switchgear Config.: Switchgear PCC AUX Vs: 433 V PPE: 0 AHE: 0.26 cal/cm^2(85%) AFB: 21.6 cm AFD: 0.01 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.77 kA Iarc: 9.68 kA Config.: Switchgear
IPDB_OG
FPDB_OG
ENGG OFF Vs: 433 V PPE: 0 AHE: 0.54 cal/cm^2(100%) AFB: 35.46 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.92 kA Iarc: 11.45 kA Config.: Switchgear
IBF1_OG
FBF1_OG
STREET LIGHT Vs: 433 V PPE: 0 AHE: 0.41 cal/cm^2(100%) AFB: 29.44 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 16.12 kA Iarc: 8.62 kA Config.: Switchgear
IBF2_OG
FBF2_OG
DCT2 Vs: 433 V PPE: 0 AHE: 0.55 cal/cm^2(100%) AFB: 35.88 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 16.43 kA Iarc: 8.75 kA Config.: Switchgear
IPDB_IC
FPDB_IC
DM PLANT Vs: 433 V PPE: 1 AHE: 3.4 cal/cm^2(85%) AFB: 124.22 cm AFD: 0.35 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 9.93 kA Iarc: 4.96 kA Config.: Switchgear BOILER1 Vs: 433 V PPE: 0 AHE: 0.72 cal/cm^2(100%) AFB: 43.15 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.82 kA Iarc: 11.41 kA Config.: Switchgear
IBF1_IC
IBF2_IC
FBF1_IC
FBF2_IC
PDB Vs: 433 V PPE: 0 AHE: 0.15 cal/cm^2(100%) AFB: 14.79 cm AFD: 0.01 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 12.96 kA Iarc: 7.23 kA Config.: Switchgear
Bag Filter1 Vs: 433 V PPE: 0 AHE: 0.53 cal/cm^2(100%) AFB: 35.28 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 15.97 kA Iarc: 8.56 kA Config.: Switchgear
Bag Filter2 Vs: 433 V PPE: 0 AHE: 0.47 cal/cm^2(100%) AFB: 32.61 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 13.98 kA Iarc: 7.69 kA Config.: Switchgear
FRACTIONATION Vs: 433 V PPE: 0 AHE: 0.23 cal/cm^2(100%) AFB: 19.8 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 13.32 kA CCT2 Iarc: 7.39 kA Vs: 433 V Config.: Switchgear PPE: 0 HYDROGENERATION AHE: 0.33 cal/cm^2(100%) Vs: 433 V AFB: 25.24 cm PPE: 4 AFD: 0.03 sec AHE: 26.8 cal/cm^2(85%) WD: 61 cm AFB: 504.01 cm LAB: 304.8 cm AFD: 2.09 sec RAB: 30.48 cm WD: 61 cm PAB: 2.54 cm LAB: 304.8 cm Isc: 9.07 kA RAB: 30.48 cm BOILER 2 Iarc: 5.42 kA PAB: 2.54 cm Vs: 433 V Config.: Switchgear Isc: 13.4 kA PPE: 0 Iarc: 6.31 kA AHE: 0.72 cal/cm^2(100%) Config.: Switchgear AFB: 43.15 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.82 kA Iarc: 11.41 kA Config.: Switchgear
CCT1 Vs: 433 V PPE: 4 AHE: 32.26 cal/cm^2(85%) AFB: 571.63 cm AFD: 2.71 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 12.33 kA Iarc: 5.91 kA Config.: Switchgear ETP Vs: 433 V PPE: 3 AHE: 16.5 cal/cm^2(85%) AFB: 362.58 cm AFD: 2.77 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 5.56 kA Iarc: 3.11 kA Config.: Switchgear
AOP Vs: 433 V PPE: 0 AHE: 0.21 cal/cm^2(85%) AFB: 18.92 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 6 kA Iarc: 3.4 kA Config.: Switchgear
CRUDE OIL TANK Vs: 433 V PPE: 3 AHE: 19.45 cal/cm^2(85%) AFB: 405.48 cm AFD: 3.48 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 5.18 kA Iarc: 2.93 kA Config.: Switchgear
ROT Vs: 433 V PPE: 4 AHE: 28.2 cal/cm^2(85%) AFB: 521.86 cm AFD: 5.82 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 4.4 kA Iarc: 2.57 kA Config.: Switchgear
Coal H Plant Vs: 433 V PPE: 0 AHE: 0.3 cal/cm^2(100%) AFB: 24.05 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 18.51 kA Iarc: 9.64 kA Config.: Switchgear
FIRE PUMP PANEL Vs: 433 V PPE: 0 AHE: 0.31 cal/cm^2(100%) AFB: 24.4 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 18.96 kA Iarc: 9.83 kA Config.: Switchgear
CAB_BF1
CAB:BF2
cab:PDB
REV. DATE
ECO#
DWN APP
DESCRIPTION
DRAWN B Y/DATE :
DW G N o.:
55
RE V.
EN G. APP./ DATE:
SCAL E:
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
6.0
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.9 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: AOP
Project: EXELELE050312
56
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
16.0
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 35.3 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Bag Filter1
Project: EXELELE050312
57
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
14.0
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 32.6 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Bag Filter2
Project: EXELELE050312
58
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
22.8
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 43.1 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: BOILER 2
Project: EXELELE050312
59
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
22.8
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 43.1 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: BOILER1
Project: EXELELE050312
60
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
7.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 1384.7 cm)
Danger 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CAPACITOR PNL
Project: EXELELE050312
61
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
12.3
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 571.6 cm)
4 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CCT1
Project: EXELELE050312
62
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
9.1
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 25.2 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CCT2
Project: EXELELE050312
63
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
18.5
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 24.1 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Coal H Plant
Project: EXELELE050312
64
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
5.2
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 405.5 cm)
3 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CRUDE OIL TANK
Project: EXELELE050312
65
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
8.2
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 21.2 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: DCT 3
Project: EXELELE050312
66
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
16.4
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 35.9 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: DCT2
Project: EXELELE050312
67
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
9.9
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 124.2 cm)
1 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: DM PLANT
Project: EXELELE050312
68
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
22.9
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 35.5 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: ENGG OFF
Project: EXELELE050312
69
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
5.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 362.6 cm)
3 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: ETP
Project: EXELELE050312
70
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
19.0
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 24.4 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: FIRE PUMP PANEL
Project: EXELELE050312
71
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
13.3
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 19.8 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: FRACTIONATION
Project: EXELELE050312
72
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
13.4
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 504.0 cm)
4 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: HYDROGENERATION
Project: EXELELE050312
73
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
30.7
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 51.9 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Main panel BB
Project: EXELELE050312
74
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
30.7
PPE Based on 46 cm Working Distance (Arc Flash boundary, PPE required within 900.9 cm)
Danger 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Main panel_TB
Project: EXELELE050312
75
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
11.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.2 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Packing MCC 1
Project: EXELELE050312
76
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
11.9
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.5 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Packing MCC 2
Project: EXELELE050312
77
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
11.9
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.5 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Packing MCC 3
Project: EXELELE050312
78
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
22.8
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 21.6 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: PCC AUX
Project: EXELELE050312
79
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
13.0
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 14.8 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: PDB
Project: EXELELE050312
80
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
19.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 39.9 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Refinary 1
Project: EXELELE050312
81
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
4.4
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 521.9 cm)
4 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: ROT
Project: EXELELE050312
82
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
16.1
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 29.4 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: STREET LIGHT
Project: EXELELE050312
83
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
11000.0
0.7
PPE Based on 91 cm Working Distance (Arc Flash boundary, PPE required within 1.5 cm)
0 2
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: TG_PNL
Project: EXELELE050312
84
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
7.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 14.3 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: WAREHOUSE1
Project: EXELELE050312
85
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
7.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 20.3 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: WAREHOUSE2
Project: EXELELE050312
86
!
Volts
WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required
433.0
14.6
PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 20.9 cm)
0 00
Not Allowed X
Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Work Shop
Project: EXELELE050312
87
_________________________________________________
Requester / Title
______________________________________
Date
PART II: TO BE COMPLETED BY THE ELECTRICALLY QUALIFIED PERSONS DOING THE WORK: Check When Complete ____ (1) Detailed job description procedure to be used in performing the above detailed work:
___________________________________________________________________________________________________________ ___________________________________________________________________________________________________________ ____ (2) Description of the Safe Work Practices to be employed: ___________________________________________________________________________________________________________ ___________________________________________________________________________________________________________
18.9 cm
0.2 cal/cm^2
Limited Approach 304.8 cm Restricted Approach 30.5 cm Required PPE 0 Shock Hazard 0.433000 kV Cotton underclothing plus FR shirt, pants, overalls or equivalent
61.000000 cm 2.5 cm 00
(3) Means employed to restrict the access of unqualified persons from the work area:
____ ___________________________________________________________________________________________________________ ____ (4) Evidence of completion of a Job Briefing including discussion of any job-related hazards: ___________________________________________________________________________________________________________
(5) Do you agree the above described work can be done safely? Electrically Qualified Person(s)
_________________________________________________
Yes
______________________________________
Date
_________________________________________________
______________________________________
Date
PART III: APPROVAL(S) TO PERFROM THE WORK WHILE ELECTRICALLY ENERGIZED Maintenance / Engineering Manager Safety Manager
_________________________________________________ _________________________________________________ _________________________________________________ ______________________________________
Manufacturing Manager
______________________________________
General Manager
______________________________________
88
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
89
10.0
Energy (Cal/cm^2)
1.00
0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0
Date: 03/05/12
90
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
91
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
92
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
93
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
94
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
95
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
96
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
97
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
98
10.0
Energy (Cal/cm^2)
1.00
0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0
Date: 03/05/12
99
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
100
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
101
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
102
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
103
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
104
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
105
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
106
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
107
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
108
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
109
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
110
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
111
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
112
10.0
Energy (Cal/cm^2)
1.00
0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0
Date: 03/05/12
113
10.0
Energy (Cal/cm^2)
1.00
0.100 0 20 40 60 80 100
Date: 03/05/12
114
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
115
10.0
Energy (Cal/cm^2)
1.00
0.100 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0
Date: 03/05/12
116
10.0
Energy (Cal/cm^2)
1.00
0.100 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00
Date: 03/05/12
117
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
118
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
119
10.0
Energy (Cal/cm^2)
1.00
Date: 03/05/12
120
121
122
123
124
125
126
127
128
129
130
131