Arc-Flash Hazard Analysis

Arc Flash Hazard Analysis Calculation of Incident Energy

Flash Protection Boundary

&

Cargill India Pvt. Ltd


Survey No. 415, Bhimasar Padana Road, PO. Bhimasar, Ta Anjar Dist. - Kutch, Gujarat

Excel Electricals
C/23 KARELIBAUG IND. CO. OP. ESTATE, NEAR TELEPHONE, OFFICE, KARELIBAUG. VADODARA-390018 . Tele: 2462913. Email: - excel.elect@gmail.com

Study Coordinated by

Study Conducted and Compiled by

5, Nana Street Nagar, Chennai, 600017, Mobile No::9884370326 Email:ife@vsnl.com

Contents
1 2 3 4 5 6 7 8 9 10 Purpose Regulatory Background What is Arc Flash Flash Hazard Analysis and Flash Protection Boundary Personal Protective Equipment References Executive Summary Detailed Summary Single Line diagram 11kV-0.433 kV Single Line diagram for coordination study short circuit currents-scenerio 1-Grid 2 2 3 4 5 6 7 8 10 11 12 16 17 21 22 26 27 31 33 37 51 54 55 56 88 89 121 123 124 125

11 Short circuit detailed Report -Scenerio 1 Grid Feeding 12 Single Line diagram for coordination study short circuit currents-scenerio 2-TB 13 Short circuit detailed Report -Scenerio 2 TB Feeding 14 Single Line diagram for coordination study short circuit currents-scenerio 3-Single DG 15 Short circuit detailed Report -Scenerio 3 Single DG Feeding 16 Single Line diagram for coordination study short circuit currents-scenerio 4-parallel DG 17 18 19 20 21 22 23 24 25 26 27 Short circuit detailed Report -Scenerio 4 Parallel DG Feeding Setting Calculations for Transformers Setting Details for 11 kV switch Gear Setting Details for 0.433 kVPCC (Relays ) TCC Curves Table 2-Detailed Summary of Calculations Single Line diagram for ARC FLASH STUDY Labels Sample work permit Estimated Total Energy Graph for various Busbars Arc Flash Boundary Figure

28 PPE details 29 Approach Boundaries to Live parts 30 Illustrated Protective Clothing and Personal Protective Equipments

PURPOSE The purpose of this report is to document and tabulate Incident Energy and the Flash Protection Boundary at various 11 KV and 433 Volt unit substation buses at Clients factory in Kutch, Gujarat in the unlikely event that electrical equipment failures occur when work is being performed in accordance with plant policies and procedures. The results presented in this report are to be used as a guide in the selection of Personal Protective Equipment (PPE) if work must be performed on or near energized electrical equipment. DISCUSSION Regulatory Background U.S. Department of Labor, Occupational Safety and Health Administration (OSHA) are the enforcement agency for workplace incidents involving personnel. If there is an arc flash incident, it will most likely be investigated by OSHA. Currently, OSHA is recommending that companies follow NFPA 70E as a guideline for worker safety. In addition, OSHA has begun to review NFPA 70E guidelines as a part of their routine inspection procedures. NFPA 70E (Standard for Electrical Safety Requirements for Employee Workplaces) and NFPA 70 (National Electrical Code) provide the basis for employers to determine if electrical hazards are present and to determine the proper types of Personal Protective Equipment (PPE) that will protect employees in the unlikely event that electrical equipment failures occur when work is being performed in accordance with plant policies and procedures. NEC Article 110.16 (Flash Protection) states: Switchboards, panel boards, industrial control panels, meter socket enclosures, and motor control centers, that are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly

visible to qualified persons before examination, adjustment, servicing or maintenance of the equipment. Although there is no such regulation is prevailing in India M/s Cargill India Pvt. Ltd were in the interest of safety requested M/s Excel Electricals to do ARC FLASH STUDY for the entire Electrical distribution system and submit the Report for selection of PPE and to indicate the Flash Protection boundary for each Electrical Equipment such as Switch Boards, Panel boards, Control panels etc. This task of analysis and study and submission of Report was entrusted to M/s Interface Electronics Pvt Ltd who is submitting this report.

What is Arc Flash? Arc Flash is the rapid release of energy due to an arcing fault between a phase conductor and another phase conductor, neutral conductor, ground conductor, or grounded surface. During an arcing fault, ionized gases in the air gap between conductive surfaces become current conducting plasma. Arcing faults are generally limited to systems where the bus voltage is in excess of 250 volts, AC. In AC systems, lower voltage levels normally will not sustain an arc as voltage recovery is not quick enough for an arc to restrike after a zero current occurs. An arcing fault is similar to the arc obtained during electric welding. Arcing faults can be the result of a failure, such as: breakdown of insulation, accidental contact, or momentary contact. Hazardous Arc-Flash can occur in any electrical device in which voltage is high enough to sustain an arc. In industrial settings, this includes: Panel boards and switchboards Motor control centers Metal-clad switchgear Transformers Motor starters High voltage switching and grounding equipment Pad-mounted switching equipment Meter bases and meter banks

Any electrical equipment that has sufficient voltage to ionize the air gap in the unlikely event that electrical equipment failure occurs

Flash Hazard Analysis and Flash Protection Boundary Prior to commencing work on electrically energized conductors > 50 volts, NFPA 70E 130.3 requires that a flash hazard analysis be completed in order to protect personnel from the possibility of being injured by an arc flash. The analysis shall determine the Flash Protection Boundary and the personal protective equipment that shall be used within the Flash Protective Boundary. Table 130.7(C)(a) can be used in lieu of an arc flash hazard analysis for various tasks listed in the table. For tasks not listed, or for power systems with greater short-circuit current capacity or longer fault clearing times, a flash hazard analysis shall be required. NFPA 70E 130.3(A) requires employers to establish a flash protection boundary a distance from exposed energized electrical parts at which an employee would sustain no more than a second degree burn if an electric arc flash were to occur. Employees performing work on energized conductors inside the flash protection boundary must be protected with appropriate PPE. At voltage levels below 600 volts, the flash protection boundary is the distance at which incident energy level is equal to 1.2 cal/cm 2. For situations where fault-clearing time is 0.1 seconds or less, the flash protection boundary is the distance at which incident energy level is equal to 1.5 cal/cm 2.

When work is to be performed within the flash protection boundary, the flash hazard analysis determines the incident energy exposure of the worker (cal/cm2). This incident energy exposure level is based on the working distance of the employees face and the chest areas from a potential arc source for the specified task to be performed. Flame resistant clothing and PPE used by the worker must be based upon the incident energy exposure associated with the specific task. Recognizing that incident energy increases as distance from arc flash decreases, additional PPE shall be used for any

parts of the body that are closer than the distance at which the incident energy was determined. NFPA 70E 2004 is a safety standard for worker safety as a part of National Fire Protection Association (NFPA) guidelines. Among other safe workplace practices, it provides awareness on the hazards of arc flash incidents. Steps required to comply with NFPA 70E, Chapter 1 Article 110.8 (B)(1)(b), 130.3, and 130.7 (C)(9)(a) include: A comprehensive safety program. Employee arc flash awareness safety training. Safety procedures and manuals that are updated to comply with the NFPA 70E guidelines. Up to date facility single line diagrams, short circuit studies and protective device coordination studies

Arc flash assessment and analysis

Personal Protective Equipment NFPA specifies the requirements for PPE for workers within flash protection boundaries. All parts of the body, which may be exposed to arc flash, need to be covered by appropriate PPE. The entire PPE set may be comprised of fire retardant clothing, helmet, headgear, face shield, safety glasses, gloves, shoes, etc. The amount of PPE required needs to be determined on the basis of calculated incident energy on a worker. The calculations need to be performed by a qualified person, such as an engineer. The protective clothing should limit the incident energy reaching the chest/face of the worker to less than 1.2 cal/cm 2. Fire retardant clothing provides thermal insulation and is also self-extinguishing. Protective clothing is rated in cal/cm2. ASSUMPTIONS & INPUTS 1. Short circuit values were calculated through the use of a computerized plant electrical system model using field collected data and drawings. 2. The Calculations and results are based on the input information furnished by Excel Electricals..

3. Short circuit MVA of 250 for one sec is assumed at the point of supply for calculation purpose, as the correct fault level is not available from the local Electricity authorities. 4. Minimum personnel distance from the arc fault was determined using standard industry practice. References 1. NFPA 70 - National Electrical Code - 2005 Edition 2. NFPA 70E - Standard for Electrical Safety in the Workplace - 2004 Edition

EXECUTIVE SUMMARY Calculations were prepared utilizing EDSA Paladin Design Base 4, a commercially available, computer aided engineering tool for the analysis of industrial, utility, and commercial electrical power systems. Arc flash hazard analysis was developed within the short circuit module of EDSA Paladin Design base 2. A copy of the one line diagram developed within EDSA is included as an attachment.

A table giving the details BUS NAME, ARC GAP, BOLTED FAULT,
ESTIMATED ARC FAULT, ESTMATED ARC FLASH BOUNDARY, INCIDENT OF ENERGY, WORKING DISTANCE and REQUIRED CLOTHING CLASS is

included

in the report Illustrations of different PPE are given in the Report. Warning Labels as Generated for various Buses based on the Energy incident calculations is given in the report. Graph giving the Incident of Energy with reference to Distance is given for all the Busses for reference.

DETAILED SUMMARY Incident energy and arc flash boundary calculations were prepared utilizing EDSA-Paladin Design Base 2. The analysis yields results as required by NFPA-70E, namely, specification of the arc flash boundary (AFB) and the incident arc energy at a probable working distance. We have evaluated the calculations for two different fault levels namely 5000 MVA sec and 1500 mva sec at the Incoming side of the Plant. Complete results are listed in Table 1. and Table 2 respectively. The graphs and the warning Labels are prepared based on Table I only. An explanation of the data presented in Table 1 is as follows: Arc Fault Bus Name: This is the name of the buses where an arc flash is postulated. Arc Fault Bus Voltage: The nominal voltage of the bus where an arc flash is postulated. Arc Gap (mm): This is the gap between the phase conductors. The gap is specified according to voltage. Bolted Fault (kA): This is the calculated current for a 3-phase bolted fault at the faulted bus. Estimated Arc Fault (kA): This is the estimated current when arc resistance is included in calculation. When calculating incident energy, bolted fault current at the faulted bus is used. Arc Time (sec): Total duration of arc fault as explained in assumptions and inputs. Estimated Arc Flash Boundary: The flash protection boundary distance in cm for the arc gap, bolted fault current, and arc time as explained above.

Working Distance: Approximate working distance in cm corresponding to the trip device. The trip time associated with the trip device is used in the calculation. The rating of personal protective equipment (PPE) worn by workers should be based on this value.

Incident Energy (cal/cm): This is the incident energy from arc flash

Required Clothing Class: This is the hazard/risk category as per NFPA 70E. Appropriate PPE, as listed in Table 5, is recommended according to this classification.

TG PGVCL

GEN
CAB_TG

50 51

R_P1_HT

CAB_IC1 VCB_IC OG_TR1 CAB_TR

VCB_IC1 TG_PNL OG_TR2

Transformer 11

50 51

R_P2_HT

50 51

R_P3_HT DG1 DG2 DG3 DG4 DG5

GEN
DG1_ACB

GEN
DG2_ACB

GEN
DG3_ACB

GEN
DG4_ACB

GEN
DG5_ACB

CAB_TR1

CAB_TR2

CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51

Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5

50 51

R_P1

50 51

R_P2

50 51

R_P15

50 51

R_P16

50 51

R_P17

50 51

R_P18

50 51

R_P19

BD_TR1 TR1_IC_1F

OG_PCC AUX_3F

OG_REF1_4F

OG_DMP_6F

BD_TR2 TR2_IC_2F

DG1_IC_15F

DG2_IC_16F

DG3_IC_17F

DG4_IC_18F

DG5_IC_18F Main panel BB

OG_EO_12F3

OG BOI1_10F

OG_SL_14F2

OGBOI2_11F

OG_DCT2_8F

OG_CCT2_9F

OG_FR_12F1

OG_HG_12F2

OGCCT1_13F1

OG_ETP_13F2

OG_ROT_13F3

OG_CHP_14F3

FIRE PUMP_14F1

RP_14

50 51

R_P3

50 51

R_P4

50 51

R_P6

50 51

R_P10

50 51

R_P11

50 51

R_P13

50 51

R_P12

CAB_PACK2

CAB_PACK3

CAB_PACK1

CAB_PCCAUX

CAB_BOILER2

WAREHOUSE1

CAB_WH1 WH1_IC

WAREHOUSE2

CAB_WH2 WH2_IC

CAB_DCT

CAB_CAP

CAB_WSS

CAB_REF1

CAB_DMP

CAB_EO

CAB_BOILER1

CAB_SL

CAB_DCT2

CAB_CCT2

CAB_FR

CAB_HG

CAB_CCT1

CAB_ETP

CAB_AOP

CAB_ROT

CAB_COT

CAB_CHP

290

CAB:CAP1

PACK2_IC

PACK1_IC

PACK3_IC

DCT_IC

CAP_IC

IWS_IC FWS_IC

295

REF1_IC PCC_AUX_IC Refinary 1

298 EO_IC DMP_IC

BOILER1_IC

SL_IC

BOILER2_IC

DCT2_IC

CCT2_IC

IFR_IC FFR_IC

IHY_IC FHY_IC

ICCT1_IC FCCT1_IC

IETP_IC3 FETP_IC

IAOP_IC1 FAOP_IC1

IROT_IC2 FROT_IC2

ICOT_IC4 FCOT_IC4

ICHP_IC5 FCHP_IC5 FPP_IC1

Packing MCC 2

Packing MCC 1

Packing MCC 3 DCT 3 CAPACITOR PNL Work Shop CAP1 PCC AUX IPDB_OG IVPDB_OG DM PLANT FPDB_OG FVPDB_OG ENGG OFF

BOILER1

IBF1_OG

STREET LIGHT

BOILER 2

IBF2_OG

DCT2 CCT2 CCT1 FRACTIONATION HYDROGENERATION ETP AOP ROT

FBF1_OG

FBF2_OG

CRUDE OIL TANK

Coal H Plant

FIRE PUMP PANEL

CAB_BF1

CAB:BF2

cab:PDB IPDB_IC FPDB_IC PDB VPDB

CAB:VPDB IVPDB_IC FVPDB_IC

IBF1_IC

IBF2_IC

SINGLE LINE DIAGRAM FOR COORDINATION STUDY

FBF1_IC

FBF2_IC

Bag Filter1

Bag Filter2

REV. DATE

ECO#

DWN APP

DESCRIPTION

THIS DR AWING IS PROP RIETA RY INF OR MATION

Yo ur C o mp an y N am e Ad dress Ad dress Ph on e an d w eb site

Electrical One-Line Diagram

DRAWN B Y/DATE :

DW G N o.:

10

RE V.

EN G. APP./ DATE:

MFG. APP ./DATE :

PAR T N o.: DWG SI ZE :

SCAL E:

TG PGVCL Sym : 13121.6A

GEN
CAB_TG

50 51

R_P1_HT

CAB_IC1 VCB_IC OG_TR1 CAB_TR

VCB_IC1 TG_PNL OG_TR2

Transformer 11

50 51

R_P2_HT

50 51

R_P3_HT DG1 DG2 DG3 DG4 DG5

GEN
DG1_ACB

GEN
DG2_ACB

GEN
DG3_ACB

GEN
DG4_ACB

GEN
DG5_ACB

CAB_TR1

CAB_TR2

CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 29374.74A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51

Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5

50 51

R_P1

50 51

R_P2

50 51

R_P15

50 51

R_P16

50 51

R_P17

50 51

R_P18

50 51

R_P19

BD_TR1 TR1_IC_1F

OG_PCC AUX_3F

OG_REF1_4F

OG_DMP_6F

BD_TR2 TR2_IC_2F

DG1_IC_15F

DG2_IC_16F

DG3_IC_17F

DG4_IC_18F

DG5_IC_18F Main panel BB Sym : 29328.02A

OG_EO_12F3

OG BOI1_10F

OG_SL_14F2

OGBOI2_11F

OG_DCT2_8F

OG_CCT2_9F

OG_FR_12F1

OG_HG_12F2

OGCCT1_13F1

OG_ETP_13F2

OG_ROT_13F3

OG_CHP_14F3

FIRE PUMP_14F1

RP_14

50 51

R_P3

50 51

R_P4

50 51

R_P6

50 51

R_P10

50 51

R_P11

50 51

R_P13

50 51

R_P12

CAB_PACK2

CAB_PACK3

CAB_PACK1

CAB_PCCAUX

CAB_BOILER2

WAREHOUSE1 Sym : 7582.43A

CAB_WH1 WH1_IC

WAREHOUSE2 Sym : 7582.43A

CAB_WH2 WH2_IC

CAB_DCT

CAB_CAP

CAB_WSS

CAB_REF1

CAB_DMP

CAB_EO

CAB_BOILER1

CAB_SL

CAB_DCT2

CAB_CCT2

CAB_FR

CAB_HG

CAB_CCT1

CAB_ETP

CAB_AOP

CAB_ROT

CAB_COT

CAB_CHP

290

CAB:CAP1

PACK2_IC

PACK1_IC

PACK3_IC

DCT_IC

CAP_IC

IWS_IC FWS_IC

295

REF1_IC PCC_AUX_IC Refinary 1 Sym : 19121.72A

IDMP_IC FDMP_IC

EO_IC

BOILER1_IC

SL_IC

BOILER2_IC

DCT2_IC

CCT2_IC

IFR_IC FFR_IC

IHY_IC FHY_IC

ICCT1_IC FCCT1_IC

IETP_IC3 FETP_IC

IAOP_IC1 FAOP_IC1

IROT_IC2 FROT_IC2

ICOT_IC4 FCOT_IC4

ICHP_IC5 FCHP_IC5 FPP_IC1

Packing MCC 2 Sym : 11687.82A

Packing MCC 1 Sym : 11436.26A

Packing MCC 3 Sym : 11751.87A

DCT 3 Sym : 8172.6A

CAPACITOR PNL Sym : 7555.11A Work Shop Sym : 14317.94A CAP1 Sym : 16742.59A

ENGG OFF Sym : 22210.04A DM PLANT Sym : 9812.44A

PCC AUX Sym : 22051.6A IPDB_OG FPDB_OG

BOILER1 Sym : 22112.5A IBF1_OG FBF1_OG

STREET LIGHT Sym : 15790.84A

BOILER 2 Sym : 22112.5A IBF2_OG FBF2_OG

DCT2 Sym : 16057.3A

CCT2 Sym : 8972.44A FRACTIONATION Sym : 13097.17A HYDROGENERATION Sym : 13175.97A CCT1 Sym : 12146.36A ETP Sym : 5530.48A AOP Sym : 5956.55A ROT Sym : 4388.88A CRUDE OIL TANK Sym : 5155.98A Coal H Plant Sym : 18051.05A FIRE PUMP PANEL Sym : 18463.48A

IVPDB_OG

FVPDB_OG CAB_BF1 CAB:BF2

PDB Sym : 12732.08A

cab:PDB IPDB_IC FPDB_IC

VPDB Sym : 13721.34A

CAB:VPDB IVPDB_IC FVPDB_IC

IBF1_IC

IBF2_IC

FBF1_IC

FBF2_IC

SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO1- GRID: SOURCE MAINS FEED

Bag Filter1 Sym : 15629.52A

Bag Filter2 Sym : 13714.95A

REV. DATE

ECO#

DWN APP

DESCRIPTION

THIS DR AWING IS PROP RIETA RY INF OR MATION

Yo ur C o mp an y N am e Ad dress Ad dress Ph on e an d w eb site

Electrical One-Line Diagram

DRAWN B Y/DATE :

DW G N o.:

11

RE V.

EN G. APP./ DATE:

MFG. APP ./DATE :

PAR T N o.: DWG SI ZE :

SCAL E:

Short Circuit Detailed Report MAINS SOURCE FAULT 250MVASEC SCENERIO 1 GRID FEEDING
3P Fault - IEC60909 Method
Bus Name Pre Fault Voltage 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 13122 29375 29328 22210 22112 22112 22052 19122 18463 18051 16743 16057 15791 15630 14318 13721 13715 13176 13097 12732 12146 11752 11688 11436 9812 8972 8173 7582 7582 7555 5957 5530 5156 4389 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 34416 13122 13122 64185 29375 29375 63495 29328 29328 39332 22210 22210 38933 22112 22112 38933 22112 22112 40835 22052 22052 31956 19122 19122 33686 18463 18463 30712 18051 18051 28488 16743 16743 28400 16057 16057 25237 15791 15791 26022 15630 15630 22942 14318 14318 24096 13721 13721 23422 13715 13715 20766 13176 13176 20621 13097 13097 21356 12732 12732 18902 12146 12146 17993 11752 11752 17884 11688 11688 17458 11436 11436 14887 9812 9812 13410 8972 8972 12158 8173 8173 11236 7582 7582 11236 7582 7582 11193 7555 7555 8772 5957 5957 8122 5530 5530 7318 5156 5156 6223 4389 4389

PGVCL Main panel_TB Main panel BB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT

12

LL Fault - IEC60909 Method


Bus Name Pre Fault Voltage 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 13122 25740 25698 19396 19310 19310 19260 16675 16103 15737 14589 13990 13751 13612 12462 11944 11938 11462 11393 11078 10562 10217 10161 9941 8525 7792 7095 6582 6582 6558 5168 4797 4470 3804 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 34416 13122 13122 56135 25740 25740 55526 25698 25698 34266 19396 19396 33917 19310 19310 33917 19310 19310 35584 19260 19260 27809 16675 16675 29322 16103 16103 26722 15737 15737 24778 14589 14589 24701 13990 13990 21940 13751 13751 22625 13612 13612 19938 12462 12462 20944 11944 11944 20356 11938 11938 18041 11462 11462 17915 11393 11393 18555 11078 11078 16417 10562 10562 15625 10217 10217 15531 10161 10161 15160 9941 9941 12922 8525 8525 11638 7792 7792 10549 7095 7095 9747 6582 6582 9747 6582 6582 9711 6558 6558 7607 5168 5168 7043 4797 4797 6344 4470 4470 5393 3804 3804

PGVCL Main panel_TB Main panel BB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT

13

LG Fault - IEC60909 Method


Bus Name Pre Fault Voltage 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 13122 30153 30100 19046 18003 17936 17936 15619 14347 13741 13514 11639 11071 10969 9958 9911 9580 9542 8913 8845 8044 7584 7534 7341 6227 5537 4983 4584 4584 4566 4064 3546 3457 3272 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 34416 13122 13122 64926 30153 30153 64219 30100 30100 34266 19046 19046 31138 18003 18003 30888 17936 17936 30888 17936 17936 26534 15619 15619 23755 14347 14347 23060 13741 13741 23188 13514 13514 19240 11639 11639 18550 11071 11071 17622 10969 10969 16032 9958 9958 16722 9911 9911 15876 9580 9580 15787 9542 9542 14197 8913 8913 14079 8845 8845 12708 8044 8044 11854 7584 7584 11772 7534 7534 11452 7341 7341 9678 6227 6227 8521 5537 5537 7646 4983 4983 7016 4584 4584 7016 4584 4584 6987 4566 4566 5925 4064 4064 5404 3546 3546 5024 3457 3457 4978 3272 3272

PGVCL Main panel_TB Main panel BB PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 DCT2 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ROT ETP

14

LLG Fault - IEC60909 Method


Bus Name Pre Fault Voltage 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 13603 30043 29995 21329 21068 20959 20959 17679 17520 16784 16278 15034 14446 14405 13089 12845 12704 12057 11985 11804 11127 10791 10733 10505 9020 8272 7540 7001 7001 6976 5507 5283 5117 4510 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 35679 13603 13603 65157 30043 30043 64456 29995 29995 39076 21329 21329 37009 21068 21068 36622 20959 20959 36622 20959 20959 29448 17679 17679 31428 17520 17520 28427 16784 16784 27672 16278 16278 26229 15034 15034 23096 14446 14446 23922 14405 14405 20981 13089 13089 22313 12845 12845 21525 12704 12704 19031 12057 12057 18901 11985 11985 19716 11804 11804 17357 11127 11127 16576 10791 10791 16478 10733 10733 16092 10505 10505 13738 9020 9020 12418 8272 8272 11268 7540 7540 10423 7001 7001 10423 7001 7001 10384 6976 6976 8148 5507 5507 7527 5283 5283 7550 5117 5117 6416 4510 4510

PGVCL Main panel_TB Main panel BB PCC AUX ENGG OFF BOILER 2 BOILER1 Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT

15

TG Sym : 131.14A PGVCL

GEN
CAB_TG

50 51

R_P1_HT

CAB_IC1 VCB_IC OG_TR1 CAB_TR

VCB_IC1

TG_PNL Sym : 131.13A OG_TR2

Transformer 11

50 51

R_P2_HT

50 51

R_P3_HT DG1 DG2 DG3 DG4 DG5

GEN
DG1_ACB

GEN
DG2_ACB

GEN
DG3_ACB

GEN
DG4_ACB

GEN
DG5_ACB

CAB_TR1

CAB_TR2

CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 3088.91A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51

Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5

50 51

R_P1

50 51

R_P2

50 51

R_P15

50 51

R_P16

50 51

R_P17

50 51

R_P18

50 51

R_P19

BD_TR1 TR1_IC_1F

OG_PCC AUX_3F

OG_REF1_4F

OG_DMP_6F

BD_TR2 TR2_IC_2F

DG1_IC_15F

DG2_IC_16F

DG3_IC_17F

DG4_IC_18F

DG5_IC_18F Main panel BB Sym : 3089.03A

OG_EO_12F3

OG BOI1_10F

OG_SL_14F2

OGBOI2_11F

OG_DCT2_8F

OG_CCT2_9F

OG_FR_12F1

OG_HG_12F2

OGCCT1_13F1

OG_ETP_13F2

OG_ROT_13F3

OG_CHP_14F3

FIRE PUMP_14F1

RP_14

50 51

R_P3

50 51

R_P4

50 51

R_P6

50 51

R_P10

50 51

R_P11

50 51

R_P13

50 51

R_P12

CAB_PACK2

CAB_PACK3

CAB_PACK1

CAB_PCCAUX

CAB_BOILER2

WAREHOUSE1 Sym : 2514.54A

CAB_WH1 WH1_IC

WAREHOUSE2 Sym : 2514.54A

CAB_WH2 WH2_IC

CAB_DCT

CAB_CAP

CAB_WSS

CAB_REF1

CAB_DMP

CAB_EO

CAB_BOILER1

CAB_SL

CAB_DCT2

CAB_CCT2

CAB_FR

CAB_HG

CAB_CCT1

CAB_ETP

CAB_AOP

CAB_ROT

CAB_COT

CAB_CHP

290

CAB:CAP1

PACK2_IC

PACK1_IC

PACK3_IC

DCT_IC

CAP_IC

IWS_IC FWS_IC

295

REF1_IC PCC_AUX_IC Refinary 1 Sym : 2962.4A

IDMP_IC FDMP_IC

EO_IC

BOILER1_IC

SL_IC

BOILER2_IC

DCT2_IC

CCT2_IC

IFR_IC FFR_IC

IHY_IC FHY_IC

ICCT1_IC FCCT1_IC

IETP_IC3 FETP_IC

IAOP_IC1 FAOP_IC1

IROT_IC2 FROT_IC2

ICOT_IC4 FCOT_IC4

ICHP_IC5 FCHP_IC5 FPP_IC1

Packing MCC 2 Sym : 2760.3A

Packing MCC 1 Sym : 2749.7A

Packing MCC 3 Sym : 2762.94A

DCT 3 Sym : 2562.44A

CAPACITOR PNL Sym : 2512.18A Work Shop Sym : 2842.23A CAP1 Sym : 2898.21A

ENGG OFF Sym : 3009.86A DM PLANT Sym : 2662.94A

PCC AUX Sym : 3000.15A IPDB_OG FPDB_OG

BOILER1 Sym : 3009.21A IBF1_OG FBF1_OG

STREET LIGHT Sym : 2892.35A

BOILER 2 Sym : 3009.21A IBF2_OG FBF2_OG

DCT2 Sym : 2868.97A

CCT2 Sym : 2621A FRACTIONATION Sym : 2805.03A HYDROGENERATION Sym : 2807.69A CCT1 Sym : 2770.62A ETP Sym : 2283.21A AOP Sym : 2339.61A ROT Sym : 2230.73A CRUDE OIL TANK Sym : 2360.75A Coal H Plant Sym : 2932.56A FIRE PUMP PANEL Sym : 2928.15A

IVPDB_OG

FVPDB_OG CAB_BF1 CAB:BF2

PDB Sym : 2761.95A

cab:PDB IPDB_IC FPDB_IC

VPDB Sym : 2789.97A

CAB:VPDB IVPDB_IC FVPDB_IC

IBF1_IC

IBF2_IC

FBF1_IC

FBF2_IC

SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO2- TURBO SET: SOURCE TURBOSET FEED

Bag Filter1 Sym : 2871.76A

Bag Filter2 Sym : 2797.07A

REV. DATE

ECO#

DWN APP

DESCRIPTION

THIS DR AWING IS PROP RIETA RY INF OR MATION

Yo ur C o mp an y N am e Ad dress Ad dress Ph on e an d w eb site

Electrical One-Line Diagram

DRAWN B Y/DATE :

DW G N o.:

16

RE V.

EN G. APP./ DATE:

MFG. APP ./DATE :

PAR T N o.: DWG SI ZE :

SCAL E:

3P Fault - IEC60909 Method


Bus Name

Short Circuit Detailed Report SCENERIO 2 TURBO GENERATOR FEEDING


Pre Fault Voltage Initial Symmetrical SCCurrent 1536 1535 20272 20258 16858 16814 16814 16687 15144 14576 14432 13588 13086 13078 12887 12022 11527 11498 11277 11222 10850 10544 10252 10205 10019 8792 8143 7471 6983 6983 6960 5602 5228 4971 4262 Peak Short 0.5 Cycle Circuit Current Symmetrical SC Current 4121 4117 48488 48103 33100 32817 32817 34145 27715 29005 26777 25071 22504 25002 23138 20515 21061 21606 18873 18753 19374 17316 16451 16359 16001 13878 12582 11428 10609 10609 10571 8408 7810 7087 6060 1536 1535 20272 20258 16858 16814 16814 16687 15144 14576 14432 13588 13086 13078 12887 12022 11527 11498 11277 11222 10850 10544 10252 10205 10019 8792 8143 7471 6983 6983 6960 5602 5228 4971 4262 Std Symmetrical SC Current 131 131 3089 3089 3010 3009 3009 3000 2962 2928 2933 2898 2892 2869 2872 2842 2797 2790 2808 2805 2762 2771 2763 2760 2750 2663 2621 2562 2515 2515 2512 2340 2283 2361 2231

TG TG_PNL Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT

11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

17

LL Fault - IEC60909 Method


Bus Name Pre Fault Voltage Initial Symmetrical SCCurrent 1330 1330 17556 17544 14599 14561 14561 14451 13115 12623 12498 11768 11333 11326 11160 10412 9983 9958 9766 9718 9396 9131 8879 8838 8677 7614 7052 6470 6047 6047 6027 4852 4527 4305 3691 Peak Short 0.5 Cycle Circuit Current Symmetrical SC Current 3569 3565 41992 41658 28665 28421 28421 29570 24002 25119 23189 21712 19489 21653 20038 17766 18240 18711 16344 16240 16778 14996 14247 14168 13857 12019 10896 9897 9187 9187 9155 7282 6763 6138 5249 1330 1330 17556 17544 14599 14561 14561 14451 13115 12623 12498 11768 11333 11326 11160 10412 9983 9958 9766 9718 9396 9131 8879 8838 8677 7614 7052 6470 6047 6047 6027 4852 4527 4305 3691 Std Symmetrical SC Current 208 208 4627 4627 4421 4419 4419 4398 4299 4220 4227 4144 4122 4077 4079 4003 3907 3893 3920 3913 3825 3831 3808 3802 3777 3582 3483 3356 3254 3254 3249 2906 2799 2864 2617

TG TG_PNL Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT

11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

18

LG Fault - IEC60909 Method


Bus Name Pre Fault Voltage Initial Symmetrical SCCurrent 1536 1535 25471 25446 17262 16458 16408 16408 14469 13403 12858 12637 11015 10495 10438 9492 9443 9153 9119 8567 8504 7766 7326 7280 7100 6066 5414 4876 4494 4494 4477 4014 3497 3421 3231 Peak Short 0.5 Cycle Circuit Current Symmetrical SC Current 4121 4115 59523 58940 32941 30040 29807 29807 25731 23106 22450 22573 18811 18152 17258 15646 16398 15583 15498 13959 13845 12516 11639 11560 11251 9565 8433 7555 6939 6939 6911 5881 5368 4993 4947 1536 1535 25471 25446 17262 16458 16408 16408 14469 13403 12858 12637 11015 10495 10438 9492 9443 9153 9119 8567 8504 7766 7326 7280 7100 6066 5414 4876 4494 4494 4477 4014 3497 3421 3231 Std Symmetrical SC Current 333 333 7628 7627 6737 6639 6634 6634 6315 6134 6009 5944 5600 5455 5483 5220 5159 5088 5079 4946 4927 4686 4543 4526 4460 4043 3761 3503 3308 3308 3299 3113 2744 2758 2581

TG TG_PNL Main panel BB Main panel_TB PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 DCT2 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ROT ETP

11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

19

LLG Fault - IEC60909 Method


Bus Name Pre Fault Voltage Initial Symmetrical SCCurrent 1536 1535 25125 25108 18054 17724 17670 17670 15162 14824 14691 14476 12938 12662 12535 11449 11327 11213 10601 10590 10529 9788 9406 9357 9165 7966 7392 6799 6366 6366 6346 5125 5043 4790 4342 Peak Short 0.5 Cycle Circuit Current Symmetrical SC Current 4121 4116 58243 58718 35532 33588 33305 33305 27105 28312 26515 26217 23937 22324 21291 19330 20723 20034 18605 17589 17465 15994 15056 14965 14609 12571 11441 10427 9702 9702 9668 7723 7230 7185 6204 1536 1535 25125 25108 18054 17724 17670 17670 15162 14824 14691 14476 12938 12662 12535 11449 11327 11213 10601 10590 10529 9788 9406 9357 9165 7966 7392 6799 6366 6366 6346 5125 5043 4790 4342 Std Symmetrical SC Current 188 188 4713 4705 4435 4428 4425 4425 4244 4274 4173 4182 4105 4014 4010 3892 3903 3892 3790 3794 3786 3693 3647 3641 3614 3424 3351 3253 3173 3173 3169 2877 3057 2784 2832

TG TG_PNL Main panel_TB Main panel BB PCC AUX ENGG OFF BOILER 2 BOILER1 Refinary 1 FIRE PUMP PANEL CAP1 Coal H Plant DCT2 Bag Filter1 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT

11000 11000 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

20

TG PGVCL

GEN
CAB_TG

50 51

R_P1_HT

CAB_IC1 VCB_IC OG_TR1 CAB_TR

VCB_IC1 TG_PNL OG_TR2

Transformer 11

50 51

R_P2_HT

50 51

R_P3_HT

DG1 Sym : 725.34A

DG2

DG3

DG4

DG5

GEN
DG1_ACB

GEN
DG2_ACB

GEN
DG3_ACB

GEN
DG4_ACB

GEN
DG5_ACB

CAB_TR1

CAB_TR2

CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 724.14A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51

Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5

50 51

R_P1

50 51

R_P2

50 51

R_P15

50 51

R_P16

50 51

R_P17

50 51

R_P18

50 51

R_P19

BD_TR1 TR1_IC_1F

OG_PCC AUX_3F

OG_REF1_4F

OG_DMP_6F

BD_TR2 TR2_IC_2F

DG1_IC_15F

DG2_IC_16F

DG3_IC_17F

DG4_IC_18F

DG5_IC_18F Main panel BB Sym : 724.14A

OG_EO_12F3

OG BOI1_10F

OG_SL_14F2

OGBOI2_11F

OG_DCT2_8F

OG_CCT2_9F

OG_FR_12F1

OG_HG_12F2

OGCCT1_13F1

OG_ETP_13F2

OG_ROT_13F3

OG_CHP_14F3

FIRE PUMP_14F1

RP_14

50 51

R_P3

50 51

R_P4

50 51

R_P6

50 51

R_P10

50 51

R_P11

50 51

R_P13

50 51

R_P12

CAB_PACK2

CAB_PACK3

CAB_PACK1

CAB_PCCAUX

CAB_BOILER2

WAREHOUSE1 Sym : 690.73A

CAB_WH1 WH1_IC

WAREHOUSE2 Sym : 690.73A

CAB_WH2 WH2_IC

CAB_DCT

CAB_CAP

CAB_WSS

CAB_REF1

CAB_DMP

CAB_EO

CAB_BOILER1

CAB_SL

CAB_DCT2

CAB_CCT2

CAB_FR

CAB_HG

CAB_CCT1

CAB_ETP

CAB_AOP

CAB_ROT

CAB_COT

CAB_CHP

290

CAB:CAP1

PACK2_IC

PACK1_IC

PACK3_IC

DCT_IC

CAP_IC

IWS_IC FWS_IC

295

REF1_IC PCC_AUX_IC Refinary 1 Sym : 717.23A

IDMP_IC FDMP_IC

EO_IC

BOILER1_IC

SL_IC

BOILER2_IC

DCT2_IC

CCT2_IC

IFR_IC FFR_IC

IHY_IC FHY_IC

ICCT1_IC FCCT1_IC

IETP_IC3 FETP_IC

IAOP_IC1 FAOP_IC1

IROT_IC2 FROT_IC2

ICOT_IC4 FCOT_IC4

ICHP_IC5 FCHP_IC5 FPP_IC1

Packing MCC 2 Sym : 705.77A

Packing MCC 1 Sym : 705.15A

Packing MCC 3 Sym : 705.93A

DCT 3 Sym : 693.78A

CAPACITOR PNL Sym : 690.58A Work Shop Sym : 710.35A CAP1 Sym : 713.45A PCC AUX Sym : 719.24A IPDB_OG FPDB_OG

ENGG OFF Sym : 719.83A DM PLANT Sym : 699.78A

BOILER1 Sym : 719.81A

IBF1_OG FBF1_OG

STREET LIGHT Sym : 713.32A

BOILER 2 Sym : 719.81A IBF2_OG FBF2_OG

DCT2 Sym : 711.6A

CCT2 Sym : 697.43A FRACTIONATION Sym : 708.2A HYDROGENERATION Sym : 708.35A CCT1 Sym : 706.19A ETP Sym : 674.62A AOP Sym : 678.66A ROT Sym : 678.81A CRUDE OIL TANK Sym : 686.47A Coal H Plant Sym : 715.47A FIRE PUMP PANEL Sym : 715.09A

IVPDB_OG

FVPDB_OG CAB_BF1 CAB:BF2

PDB Sym : 705.15A

cab:PDB IPDB_IC FPDB_IC

VPDB Sym : 706.75A

CAB:VPDB IVPDB_IC FVPDB_IC

IBF1_IC

IBF2_IC

FBF1_IC

FBF2_IC

SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO3- DG SINGLE: SOURCE SINGLE DG FEED

Bag Filter1 Sym : 711.94A

Bag Filter2 Sym : 707.28A

REV. DATE

ECO#

DWN APP

DESCRIPTION

THIS DR AWING IS PROP RIETA RY INF OR MATION

Yo ur C o mp an y N am e Ad dress Ad dress Ph on e an d w eb site

Electrical One-Line Diagram

DRAWN B Y/DATE :

DW G N o.:

21

RE V.

EN G. APP./ DATE:

MFG. APP ./DATE :

PAR T N o.: DWG SI ZE :

SCAL E:

3P Fault - IEC60909 Method


Bus Name

Short Circuit Detailed Report SCENERIO 3 SINGLE DG FEEDING


Pre Fault Voltage Initial Symmetrical SCCurrent 8141 7992 7991 7463 7458 7458 7410 7156 6986 6978 6789 6725 6639 6633 6447 6253 6246 6238 6220 6061 6050 5989 5975 5918 5497 5280 5015 4810 4810 4800 4147 3974 3951 3542 Peak Short Circuit Current 21845 20832 20762 17428 17352 17352 17697 15837 15524 16222 14938 14003 14904 14238 13209 12510 13422 12457 13634 12722 11807 11396 11352 11177 10095 9386 8724 8236 8236 8213 6840 5942 6436 5211 0.5 Cycle Symmetrical SC Current 8141 7992 7991 7463 7458 7458 7410 7156 6986 6978 6789 6725 6639 6633 6447 6253 6246 6238 6220 6061 6050 5989 5975 5918 5497 5280 5015 4810 4810 4800 4147 3974 3951 3542 Std Symmetrical SC Current 725 724 724 720 720 720 719 717 715 715 713 713 712 712 710 708 707 708 707 705 706 706 706 705 700 697 694 691 691 691 679 686 675 679

DG1 Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 Coal H Plant FIRE PUMP PANEL CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop HYDROGENERATION Bag Filter2 FRACTIONATION VPDB PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT

433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

22

LL Fault - IEC60909 Method


Bus Name Pre Fault Voltage Initial Symmetrical SCCurrent ip 7051 6921 6920 6464 6459 6459 6418 6198 6050 6043 5880 5824 5749 5744 5584 5415 5410 5403 5387 5249 5240 5187 5174 5126 4761 4573 4343 4165 4165 4157 3592 3442 3422 3067 18919 18041 17981 15093 15027 15027 15326 13716 13444 14049 12936 12127 12907 12330 11439 10834 11624 10788 11807 11017 10225 9869 9831 9680 8743 8128 7555 7132 7132 7112 5923 5146 5574 4513 Peak Short Circuit Current 0.5 Cycle Symmetrical SC Current 0.5C Sym 7051 6921 6920 6464 6459 6459 6418 6198 6050 6043 5880 5824 5749 5744 5584 5415 5410 5403 5387 5249 5240 5187 5174 5126 4761 4573 4343 4165 4165 4157 3592 3442 3422 3067 Std Symmetrical SC Current Std Sym 1153 1149 1149 1137 1136 1136 1135 1129 1124 1123 1118 1118 1113 1114 1109 1103 1101 1103 1099 1095 1097 1096 1096 1094 1079 1072 1062 1053 1053 1053 1020 1036 1008 1012

Bus Name DG1 Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 Coal H Plant FIRE PUMP PANEL CAP1 STREET LIGHT DCT2 Bag Filter1 Work Shop HYDROGENERATION Bag Filter2 FRACTIONATION VPDB PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT

Pre-Flt( V ) Ik" 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

23

LG Fault - IEC60909 Method


Bus Name Pre Fault Voltage Initial Symmetrical SCCurrent 8141 7851 7850 6910 6806 6801 6801 6465 6274 6144 6076 5717 5593 5565 5320 5257 5183 5174 5035 5015 4765 4616 4599 4531 4100 3809 3545 3345 3345 3336 3144 2781 2769 2603 Peak Short Circuit Current 21845 20131 20066 15871 15180 15121 15121 14005 13197 12979 13016 11678 11062 11420 10377 10701 10349 10311 9606 9552 8899 8445 8403 8238 7295 6614 6061 5657 5657 5638 4924 4285 4566 4257 0.5 Cycle Symmetrical SC Current 8141 7851 7850 6910 6806 6801 6801 6465 6274 6144 6076 5717 5593 5565 5320 5257 5183 5174 5035 5015 4765 4616 4599 4531 4100 3809 3545 3345 3345 3336 3144 2781 2769 2603 Std Symmetrical SC Current 1844 1829 1829 1775 1769 1769 1769 1746 1734 1724 1718 1691 1683 1677 1659 1649 1643 1642 1633 1631 1607 1592 1591 1583 1532 1495 1457 1426 1426 1425 1414 1348 1320 1284

DG1 Main panel BB Main panel_TB PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 STREET LIGHT DCT2 Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK ROT AOP ETP

433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

24

LLG Fault - IEC60909 Method


Bus Name Pre Fault Voltage Initial Symmetrical SCCurrent ip 8141 8000 7998 7370 7363 7363 7351 6997 6904 6836 6710 6522 6484 6451 6198 6086 6081 5972 5955 5890 5741 5645 5630 5567 5130 4879 4604 4393 4393 4383 3909 3740 3566 3505 21845 20687 20619 16891 16817 16817 17264 15192 15565 14902 14662 14191 13268 13601 12492 12997 12745 11769 11715 12137 11054 10620 10576 10401 9341 8622 7976 7500 7500 7478 5913 6167 5814 5213 Peak Short Circuit Current 0.5 Cycle Symmetrical SC Current 0.5C Sym 8141 8000 7998 7370 7363 7363 7351 6997 6904 6836 6710 6522 6484 6451 6198 6086 6081 5972 5955 5890 5741 5645 5630 5567 5130 4879 4604 4393 4393 4383 3909 3740 3566 3505 Std Symmetrical SC Current Std Sym 1041 1048 1048 1054 1054 1054 1049 1052 1063 1048 1025 1060 1045 1040 1038 1042 1043 1033 1033 1028 1027 1025 1024 1023 1008 999 988 979 979 979 1011 946 939 1000

Bus Name DG1 Main panel BB Main panel_TB ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ETP ROT

Pre-Flt( V ) Ik" 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433

25

TG PGVCL

GEN
CAB_TG

50 51

R_P1_HT

CAB_IC1 VCB_IC OG_TR1 CAB_TR

VCB_IC1 TG_PNL OG_TR2

Transformer 11

50 51

R_P2_HT

50 51

R_P3_HT

DG1 Sym : 2887.2A

DG2 Sym : 2887.69A

DG3 Sym : 2886.72A

DG4 Sym : 2888.66A

DG5 Sym : 695.19A

GEN
DG1_ACB

GEN
DG2_ACB

GEN
DG3_ACB

GEN
DG4_ACB

GEN
DG5_ACB

CAB_TR1

CAB_TR2

CAB_MP1 MP_IC_26F Transformer 1 Main panel_TB Sym : 2896.67A COS11 COS21 COS31 COS41 COS51 COS61 COS71 COS81 TIE BREAKER_21F COS12 COS22 COS32 COS42 COS52 COS62 COS72 COS82 CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R
50 51

Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5

50 51

R_P1

50 51

R_P2

50 51

R_P15

50 51

R_P16

50 51

R_P17

50 51

R_P18

50 51

R_P19

BD_TR1 TR1_IC_1F

OG_PCC AUX_3F

OG_REF1_4F

OG_DMP_6F

BD_TR2 TR2_IC_2F

DG1_IC_15F

DG2_IC_16F

DG3_IC_17F

DG4_IC_18F

DG5_IC_18F Main panel BB Sym : 2896.76A

OG_EO_12F3

OG BOI1_10F

OG_SL_14F2

OGBOI2_11F

OG_DCT2_8F

OG_CCT2_9F

OG_FR_12F1

OG_HG_12F2

OGCCT1_13F1

OG_ETP_13F2

OG_ROT_13F3

OG_CHP_14F3

FIRE PUMP_14F1

RP_14

50 51

R_P3

50 51

R_P4

50 51

R_P6

50 51

R_P10

50 51

R_P11

50 51

R_P13

50 51

R_P12

CAB_PACK2

CAB_PACK3

CAB_PACK1

CAB_PCCAUX

CAB_BOILER2

WAREHOUSE1 Sym : 2392.4A

CAB_WH1 WH1_IC

WAREHOUSE2 Sym : 2392.4A

CAB_WH2 WH2_IC

CAB_DCT

CAB_CAP

CAB_WSS

CAB_REF1

CAB_DMP

CAB_EO

CAB_BOILER1

CAB_SL

CAB_DCT2

CAB_CCT2

CAB_FR

CAB_HG

CAB_CCT1

CAB_ETP

CAB_AOP

CAB_ROT

CAB_COT

CAB_CHP

290

CAB:CAP1

PACK2_IC

PACK1_IC

PACK3_IC

DCT_IC

CAP_IC

IWS_IC FWS_IC

295

REF1_IC PCC_AUX_IC Refinary 1 Sym : 2786.76A

IDMP_IC FDMP_IC

EO_IC

BOILER1_IC

SL_IC

BOILER2_IC

DCT2_IC

CCT2_IC

IFR_IC FFR_IC

IHY_IC FHY_IC

ICCT1_IC FCCT1_IC

IETP_IC3 FETP_IC

IAOP_IC1 FAOP_IC1

IROT_IC2 FROT_IC2

ICOT_IC4 FCOT_IC4

ICHP_IC5 FCHP_IC5 FPP_IC1

Packing MCC 2 Sym : 2609.86A

Packing MCC 1 Sym : 2600.55A

Packing MCC 3 Sym : 2612.19A

DCT 3 Sym : 2435A

CAPACITOR PNL Sym : 2390.3A Work Shop Sym : 2681.37A CAP1 Sym : 2730.02A

ENGG OFF Sym : 2828.04A DM PLANT Sym : 2523.67A

BOILER1 Sym : 2827.5A

PCC AUX Sym : 2819.24A IPDB_OG FPDB_OG

IBF1_OG FBF1_OG

STREET LIGHT Sym : 2725.6A

BOILER 2 Sym : 2827.5A IBF2_OG FBF2_OG

DCT2 Sym : 2703.83A

CCT2 Sym : 2486.95A FRACTIONATION Sym : 2648.73A HYDROGENERATION Sym : 2651.07A CCT1 Sym : 2618.52A ETP Sym : 2184.73A AOP Sym : 2235.51A ROT Sym : 2144.66A CRUDE OIL TANK Sym : 2261.3A Coal H Plant Sym : 2760.31A FIRE PUMP PANEL Sym : 2755.89A

IVPDB_OG

FVPDB_OG CAB_BF1 CAB:BF2

PDB Sym : 2609.55A

cab:PDB IPDB_IC FPDB_IC

VPDB Sym : 2633.92A

CAB:VPDB IVPDB_IC FVPDB_IC

IBF1_IC

IBF2_IC

FBF1_IC

FBF2_IC

SINGLE LINE DIAGRAM FOR COORDINATION STUDY SHORT CIRCUIT CURRENTS-SCENARIO4- DG PARALLEL: SOURCE PARALLEL DG FEED

Bag Filter1 Sym : 2706.89A

Bag Filter2 Sym : 2640.5A

REV. DATE

ECO#

DWN APP

DESCRIPTION

THIS DR AWING IS PROP RIETA RY INF OR MATION

Yo ur C o mp an y N am e Ad dress Ad dress Ph on e an d w eb site

Electrical One-Line Diagram

DRAWN B Y/DATE :

DW G N o.:

26

RE V.

EN G. APP./ DATE:

MFG. APP ./DATE :

PAR T N o.: DWG SI ZE :

SCAL E:

3P Fault - IEC60909 Method


Bus Name

Short Circuit Detailed Report SCENERIO 4 PARALLEL DG FEEDING


Pre Fault Voltage 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 31990 31973 30991 30878 30821 30765 30755 24307 24209 24209 23982 20807 19840 19509 17992 17142 17007 16750 15243 14542 14518 14032 13944 13462 12885 12408 12337 12059 10309 9395 8498 7863 7863 7834 6145 5693 5306 4498 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 83443 31990 2897 82338 31973 2897 77248 30991 2889 76749 30878 2888 76502 30821 2887 76257 30765 2887 76252 30760 2887 46424 24307 2828 45869 24209 2828 45869 24209 2828 48514 23982 2819 36478 20807 2787 38753 19840 2756 34869 19509 2760 32030 17992 2730 31921 17142 2704 27964 17007 2726 28943 16750 2707 24959 15243 2681 25764 14542 2641 26584 14518 2634 22574 14032 2651 22403 13944 2649 23284 13462 2610 20387 12885 2619 19204 12408 2612 19080 12337 2610 18596 12059 2601 15791 10309 2524 14138 9395 2487 12698 8498 2435 11696 7863 2392 11696 7863 2392 11650 7834 2390 9077 6145 2236 8384 5693 2185 7532 5306 2261 6377 4498 2145

Main panel BB Main panel_TB DG4 DG2 DG1 DG3 DG5 ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT

27

LL Fault - IEC60909 Method


Bus Name Pre Fault Voltage 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 27704 27689 26839 26741 26692 26643 26633 21050 20966 20966 20769 18019 17182 16895 15582 14846 14729 14506 13201 12594 12573 12152 12076 11658 11159 10745 10684 10443 8927 8137 7359 6809 6809 6784 5321 4930 4595 3895 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 72264 27704 4597 71307 27689 4597 66899 26839 4573 66467 26741 4571 66253 26692 4569 66041 26643 4568 66031 26633 4568 40204 21050 4398 39724 20966 4396 39724 20966 4396 42015 20769 4374 31591 18019 4279 33561 17182 4200 30198 16895 4208 27739 15582 4126 27645 14846 4059 24218 14729 4107 25065 14506 4062 21615 13201 3990 22313 12594 3892 23022 12573 3878 19550 12152 3908 19401 12076 3902 20165 11658 3812 17655 11159 3821 16631 10745 3800 16524 10684 3793 16104 10443 3769 13675 8927 3576 12244 8137 3480 10997 7359 3354 10129 6809 3253 10129 6809 3253 10089 6784 3248 7861 5321 2907 7260 4930 2801 6523 4595 2871 5523 3895 2625

Main panel BB Main panel_TB DG4 DG2 DG1 DG3 DG5 ENGG OFF BOILER 2 BOILER1 PCC AUX Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 STREET LIGHT Bag Filter1 Work Shop Bag Filter2 VPDB HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP ETP CRUDE OIL TANK ROT

28

LGFault - IEC60909 Method


Bus Name Pre Fault Voltage 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 31449 31430 29656 29556 29455 29356 29258 19956 18901 18836 18836 16326 14982 14305 14031 12058 11439 11367 10254 10200 9863 9823 9181 9109 8266 7767 7715 7513 6365 5649 5066 4654 4654 4636 4134 3593 3508 3312 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 80740 31449 7318 79700 31430 7317 71713 29656 7220 71703 29646 7220 70923 29455 7208 70536 29356 7202 70154 29258 7197 38631 19956 6506 34703 18901 6417 34392 18836 6413 34392 18836 6413 29077 16326 6118 25769 14982 5951 24955 14305 5833 25108 14031 5770 20539 12058 5451 19756 11439 5313 18702 11367 5343 16824 10254 5095 17696 10200 5032 16751 9863 4967 16652 9823 4958 14889 9181 4836 14759 9109 4818 13259 8266 4590 12279 7767 4454 12191 7715 4438 11848 7513 4375 9994 6365 3975 8764 5649 3704 7820 5066 3455 7162 4654 3266 7162 4654 3266 7132 4636 3257 6041 4134 3083 5501 3593 2717 5108 3508 2736 5059 3312 2558

Main panel BB Main panel_TB DG4 DG5 DG2 DG1 DG3 PCC AUX ENGG OFF BOILER 2 BOILER1 CAP1 Refinary 1 Coal H Plant FIRE PUMP PANEL Bag Filter1 DCT2 STREET LIGHT Work Shop VPDB Bag Filter2 PDB HYDROGENERATION FRACTIONATION CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL CRUDE OIL TANK AOP ROT ETP

29

LLGFault - IEC60909 Method


Bus Name Pre Fault Voltage 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 433 Initial Symmetrical SCCurrent 32020 31998 30906 30900 30778 30714 30649 23057 22954 22841 22841 19177 18801 18084 17287 16032 15397 15341 13774 13570 13451 12694 12617 12451 11683 11294 11231 10984 9402 8603 7796 7223 7223 7197 5656 5423 5246 4613 Peak Short 0.5 Cycle Std Circuit Symmetrical Symmetrical Current SC Current SC Current 82885 32020 4189 81792 31998 4189 75986 30906 4203 75980 30900 4203 75413 30778 4204 75131 30714 4205 74852 30649 4205 45955 23057 4092 43334 22954 4108 42808 22841 4102 42808 22841 4102 33459 19177 3981 35911 18801 4048 32119 18084 3932 30780 17287 3795 29341 16032 3917 26509 15397 3795 25228 15341 3806 22563 13774 3712 24518 13570 3724 23599 13451 3719 20455 12694 3664 20305 12617 3661 21425 12451 3603 18533 11683 3610 17548 11294 3618 17438 11231 3613 17006 10984 3596 14465 9402 3438 13009 8603 3377 11709 7796 3275 10799 7223 3191 10799 7223 3191 10758 7197 3187 8399 5656 2886 7730 5423 3063 7765 5246 2792 6563 4613 2836

Main panel BB Main panel_TB DG4 DG5 DG2 DG1 DG3 PCC AUX ENGG OFF BOILER 2 BOILER1 Refinary 1 FIRE PUMP PANEL Coal H Plant CAP1 DCT2 Bag Filter1 STREET LIGHT Work Shop VPDB Bag Filter2 HYDROGENERATION FRACTIONATION PDB CCT1 Packing MCC 3 Packing MCC 2 Packing MCC 1 DM PLANT CCT2 DCT 3 WAREHOUSE1 WAREHOUSE2 CAPACITOR PNL AOP CRUDE OIL TANK ETP ROT

30

Setting Calculation for Power Transformers 1250 kVA

11kV

CTHV:100/5

1.25 MVA

In:2500A

0.433kV

Transformer capacity Primary Voltage Secondary Voltage Transformer HV side CT details CTHV Turns Ratio Transformer LV ACB rating Turns Ratio Percentage Impedance of Transformer Fault Current at 11 kV Bus as per report Fault current at 0.433 kV Bus as per report Transformer HV side Primary Current Transformer LV side current as per name plate Transformer HV side Primary current with 10 % Over load Transformer HV side CT Secondary Full Load Current Transformer HV side CT Secondary current with 10 % Over load IDMT setting at 11 kV side
Setting proposed Ip

PT Vp Vs CTR1

Ipfl

Isfl

1250 11 0.433 100/5 20 2500 2500 5.00% 13122 29328 65.68 1666.00 72.25 3.28 3.61 4.25 85.00

kVA kV kV

A A Amps Amps

Transformer Full Load LV side Primary Current

Isfl

Amps % 4.25 A 1250 X 1000 )/ (1.732 Amps 1666.76 Amps 1833.44


0.73

Transformer LV side Primary current with 10 % Over load Transformer LV side CT Secondary current with 10 % Over load IDMT setting at0.433kV side
Setting proposed Ip Curve

Amps

0.73

0.7 Extreme Inverse

Fault current at0.433kV Bus as per report,for MINIMUM SOURCE Fault HV side current due to fault at 0.433 kV bus HV side CT Secondary current due to fault at0.433kV bus HV side CT current due to fault at Transformer HV side Setting proposed on HV side relay I>> Setting proposed on LV side relay I>>

29328.00 1154.46
57.72 656.10

45.00 900.00 6

Amps Amps Amps Amps Amps % xIn

11kV

CTHV:125/1

CTLV:3000/5 2.0 MVA

0.433kV

31

Setting Calculation for 2.0 MVA Transformers

11kV

CTHV:125/1

CTLV:3000/5 2.0 MVA

0.433kV

Transformer capacity Primary Voltage Secondary Voltage Transformer HV side CT details CTHV Turns Ratio Transformer LV side CT details CTLV Turns Ratio Transformer LV side ACB rating Percentage Impedance of Transformer Fault Current at 11 kV Bus as per report Fault current at 0.433 kV Bus Transformer HV side current as per name plate Transformer LV side current as per name plate Transformer HV side Primary current with 10 % Over load Transformer HV side CT Secondary Full Load Current Transformer HV side CT Secondary current with 10 % Over load IDMT setting at 11 kV side
Setting proposed Ip

PT Vp Vs CTR1 CTR1 Z

Ipfl

Isfl

2000 11 0.433 125/1 125 3000/5 600 4000 6.78% 1535 20272 105.00 2666.80 115.50 0.84 0.92 115.47/125 0.92
0.95

kVA kV kV

A A

Amps

Transformer Full Load LV side Primary Current Transformer LV side Primary current with 10 % Over load Transformer LV side CT Secondary Full Load Current Transformer LV side CT Secondary current with 10 % Over load IDMT setting at 0.433kV side at 100 % load IDMT setting at 0.433kV side at 110 % load
Setting proposed Ip Curve

Isfl

2666.82 2933.51
4.44 4.89

Amps Amps

2666/3000 0.89 0.98


1 Extreme Inverse

xIn Amps Amps Amps Amps Amps Amps

Fault current at0.433kV Bus as per report,for MINIMUM SOURCE Fault HV side current due to fault at 0.433 kV bus HV side CT Secondary current due to fault at0.433kV bus HV side CT current due to fault at Transformer HV side Setting proposed on HV side relay I>> Setting proposed on LV side relay I>>

20272.00 797.98
6.38 12.28

8.00 3

32

Setting Details for 11kV Switch Gear


1.1 INCOMER 1 FROM MAINS
Relay type: ABB MAKE NI 41

RELAY POINTS:VCB_IC Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
100A

5A Setting ON 9 0.55 0.85 1 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.55 0.1 1 IEC Normal Inverse

33

Setting Details for 11kV Switch Gear 3 PANEL BOARD


2.1 INCOMING FROM TURBO ALTERNATOR RELAY POINTS:RP1_HT Relay type:AREVA P343 SCOPE OF FUNCTION Address Setting Title Fault Records Function 50/51 Function 50N/51N Other functions are disabled Power System Data 1 Title Setting CTs Main Protection CT CT rated primary CT rated secondary Phase over current Protection: 50/51 Setting name Units FCT 50/51 50-2 Pickup I>> 50-2 Delay T I>> 51 pickup Ip 51 time dial Tp IEC Curve

Setting Range Enabled/Disabled

Setting Enabled

Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting
250A

1A Setting ON 5 0.7 0.7 0.55 IEC EXTREM E Inverse

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 0.7 0.7 0.1 0.7 IEC Normal Inverse

34

2.2 OUTGOING 1 TO TRANSFORMER 1


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP2_HT Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
125A

1A Setting ON 8 0.55 0.95 1 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.55 0.1 0.7 IEC Normal Inverse

35

Setting Details for 11kV Switch Gear 3 PANEL BOARD


2.3 OUTGOING 2 TO TRANSFORMER 2
Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP3_HT Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
125A

1A Setting ON 8 0.55 0.95 1 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.55 0.1 0.7 IEC Normal Inverse

36

Setting Details for 0.433kV RELAYS IN PCC


3.1 INCOMING FROM TRANSFORMER 1
Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP1 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
3000 A

5A Setting ON 4 0.4 1 0.7 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.7 IEC Normal Inverse

37

3.2 INCOMING FROM TRANSFORMER 2


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP1 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
3000 A

5A Setting ON 4 0.4 1 0.7 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.7 IEC Normal Inverse

38

3.3 INCOMING FROM DG1


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP15 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 8 0.4 0.85 0.6 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.6 IEC Normal Inverse

39

3.4 INCOMING FROM DG2


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP16 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 8 0.4 0.85 0.6 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.6 IEC Normal Inverse

40

3.5 INCOMING FROM DG3


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP17 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 8 0.4 0.85 0.6 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.6 IEC Normal Inverse

41

3.6 INCOMING FROM DG4


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP18 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 8 0.4 0.85 0.6 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.6 IEC Normal Inverse

42

3.7 INCOMING FROM DG5


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP19 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 8 0.4 0.85 0.6 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.4 0.1 0.6 IEC Normal Inverse

43

3.8 OUTGOING TO AUXILIARY PCC


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP3 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 7 0.25 0.5 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

44

3.9 OUTGOING TO REFINARY


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP4 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
1600 A

5A Setting ON 3 0.25 0.9 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

45

3.10 OUTGOING TO DM PLANT


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP6 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 7 0.25 0.5 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

46

3.11 OUTGOING TO BOILER 1


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP10 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
1000 A

5A Setting ON 5 0.25 1 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

47

3.12 OUTGOING TO BOILER 2


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP11 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
1000 A

5A Setting ON 5 0.25 1 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

48

3.13 OUTGOING TO CCT2


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP12 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 7 0.25 1 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

49

3.14 OUTGOING TO DCT2


Relay type:SEGC IRI1-3I-E0-1-1-HD

RELAY POINTS:RP13 Setting Title Fault Records Function 50/51 Function 50N/51N Setting Range Enabled/Disabled Setting Enabled

SCOPE OF FUNCTION Address

Other functions are disabled Power System Data 1 CTs Title Setting Main Protection CT CT rated primary CT rated secondary Units I>> T I>> Ip Tp Range 10..50000 A 1A/5A Range ON/OFF 0.1..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse Setting
800 A

5A Setting ON 7 0.25 1 1.5 IEC EXTREM E Inverse

Phase over current Protection: 50/51 Setting name FCT 50/51 50-2 Pickup 50-2 Delay 51 pickup 51 time dial IEC Curve

Ground over current Protection: 50N/51 N Setting name Units FCT 50N / 51 N 50N-2 Pickup I>> 50N-2 Delay T I>> 51N pickup Ip 51N time dial Tp IEC Curve

Range ON/OFF 0.05..35.00 A 0.00..60.00 s 0.25..20.00 0.05..1.0 s, oo Normal Inverse ,Very Inverse ,Extremely Inverse ,Long Inverse

Setting ON 1 0.25 0.1 0.5 IEC Normal Inverse

50

1000

10000

MP_IC_26F 100 PGVCL

Time in Seconds

10

Transformer 3 1250.0 KVA Transformer

.01

.1

INRUSH

.5

10

100 Current in Amperes X 10 Time-Current Characteristic Curves

1000

10000 03-05-2012 10:56:51

11000 Volt Phase

0 - Path:PGVCL-11kV Panel-Transformer3-MP_IC_26F

C:\Users\ramesh.cuppu\Documents\PALADIN_PROJECTS\EXELELE240212.PDC

51

1000

10000

REF_IC 100 R_P4 R_P1_1F R_P2_HT R_P1_HT

.01

.1 .5

Time in Seconds

10

10

100 Current in Amperes X 10 Time-Current Characteristic Curves

1000

10000 03-05-2012 17:53:17

433 Volt Phase 6 - REFINARY

C:\Users\ramesh.cuppu\Documents\PALADIN_PROJECTS\EXELELE050312.PDC

52

1000

10000

BOILER1_IC

R_P10

R_P1_1F 100

R_P2_HT

R_P1_HT

Transformer 1 2000.0 KVA Transformer

Time in Seconds

10

.01

.1

INRUSH

.5

10

100 Current in Amperes X 10 Time-Current Characteristic Curves

1000

10000 03-05-2012 18:06:57

433 Volt Phase 7 - BOILER 1

C:\Users\ramesh.cuppu\Documents\PALADIN_PROJECTS\EXELELE050312.PDC

53

SUMMARY REPORT OF ARCFLASH STUDY

Bus Name

Bus kV

3P Bolted Fault (kA)


6.00 15.97 13.98 22.82 22.82 7.62 12.33 9.07 18.51 5.18 8.25 16.43 9.93 22.92 5.56 18.96 13.32 13.40 30.66 30.71 11.60 11.86 11.92 22.77 12.96 19.63 4.40 16.12 0.70 7.65 7.65 14.59

Branch Current (kAmp)


6.00 15.97 13.98 22.82 22.82 7.62 12.33 9.07 18.51 5.18 8.25 16.43 9.93 22.92 5.56 18.96 13.32 13.40 30.66 30.71 11.60 11.86 11.92 22.77 12.96 19.63 4.40 16.12 17.70 7.65 7.65 14.59

3P Arcing Current (kA)


3.400 8.555 7.685 11.411 11.411 4.004 5.905 5.420 9.638 2.932 4.269 8.754 4.957 11.454 3.107 9.828 7.392 6.314 14.483 12.328 6.610 6.730 6.760 9.683 7.229 10.106 2.573 8.622 0.708 4.725 4.016 7.955

AOP Bag Filter1 Bag Filter2 BOILER 2 BOILER1 CAPACITOR PNL CCT1 CCT2 Coal H Plant CRUDE OIL TANK DCT 3 DCT2 DM PLANT ENGG OFF ETP FIRE PUMP PANEL FRACTIONATION HYDROGENERATION Main panel BB Main panel_TB Packing MCC 1 Packing MCC 2 Packing MCC 3 PCC AUX PDB Refinary 1 ROT STREET LIGHT TG_PNL WAREHOUSE1 WAREHOUSE2 Work Shop

0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 0.433 11.000 0.433 0.433 0.433

0.033 0.030 0.030 0.030 0.030 15.178 2.709 0.030 0.015 3.483 0.030 0.030 0.346 0.022 2.774 0.015 0.015 2.094 0.030 2.389 0.015 0.015 0.015 0.013 0.010 0.030 5.816 0.023 0.030 0.015 0.030 0.015

Trip 3P Fault 3P Arc Flash Working Delay Duratio Boundary Distance Time n (sec) (cm) (cm) (sec)
0.033 0.030 0.030 0.030 0.030 15.178 2.709 0.030 0.015 3.483 0.030 0.030 0.346 0.022 2.774 0.015 0.015 2.094 0.030 2.389 0.015 0.015 0.015 0.013 0.010 0.030 5.816 0.023 0.030 0.015 0.030 0.015 18.9 35.3 32.6 43.1 43.1 1384.7 571.6 25.2 24.1 405.5 21.2 35.9 124.2 35.5 362.6 24.4 19.8 504.0 51.9 900.9 18.2 18.5 18.5 21.6 14.8 39.9 521.9 29.4 1.5 14.3 20.3 20.9 61.000000 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 61.000642 91.000579 61.000642 61.000642 61.000642

3P Energy Required IEEE (cal/cm^2) 1584 PPE Class


0.21 0.53 0.47 0.72 0.72 118.74 32.26 0.33 0.30 19.45 0.25 0.55 3.40 0.54 16.50 0.31 0.23 26.80 0.94 97.08 0.20 0.21 0.21 0.26 0.15 0.64 28.20 0.41 0.02 0.14 0.24 0.25 0 0 0 0 0 Extreme Danger 4 0 0 3 0 0 1 0 3 0 0 4 0 Extreme Danger 0 0 0 0 0 0 4 0 0 0 0 0

Clothing Required
4.5 - 14.0 oz/yd^2 untreated cotton FR shirt and pants, plus flash suit hood Cotton underclothing plus FR shirt and pants Cotton underclothing plus FR shirt, pants, overalls or equivalent Cotton underclothing plus FR shirt, pants, plus double layer switching coat and pants or equiv. Level exceeds 40 cal/cm^2 - Never work on or near energized system

54

PGVCL Vs: 11000 V

GEN
TG_PNL Vs: 11000 V PPE: 0 AHE: 0.02 cal/cm^2(100%) AFB: 1.51 cm AFD: 0.03 sec WD: 91 cm LAB: 304.8 cm RAB: 66.04 cm PAB: 17.78 cm Isc: 0.7 kA Iarc: 0.71 kA Config.: Box OG_TR1 CAB_TG

TG Vs: 11000 V

50 51

R_P1_HT

CAB_IC1 VCB_IC CAB_TR

VCB_IC1

OG_TR2

Transformer 11

MP_IC_26F

Main panel_TB Vs: 433 V PPE: Extreme Danger AHE: 97.08 cal/cm^2(85%) AFB: 900.86 cm AFD: 2.39 sec WD: 45.5 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 30.71 kA Iarc: 12.33 kA Config.: Switchgear

50 51

R_P2_HT

50 51

R_P3_HT

DG1 Vs: 433 V

DG2 Vs: 433 V

DG3 Vs: 433 V

DG4 Vs: 433 V

DG5 Vs: 415 V

GEN
DG1_ACB

GEN
DG2_ACB

GEN
DG3_ACB

GEN
DG4_ACB

GEN
DG5_ACB

CAB_TR1

CAB_TR2

CAB_MP1

Transformer 1

Transformer 2 CAB_DG1 CAB_DG2 CAB_DG3 CAB_DG4 CAB_DG5 Main panel BB Vs: 433 V PPE: 0 AHE: 0.94 cal/cm^2(100%) AFB: 51.92 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 30.66 kA Iarc: 14.48 kA Config.: Switchgear OG_CCT2_9F OG_FR_12F1 OG_HG_12F2 OGCCT1_13F1 OG_ETP_13F2 OG_CHP_14F3 FIRE PUMP_14F1

50 51

R_P1

50 51

R_P2

COS11

COS21

COS31

COS41

COS51

COS61

COS71

COS81 TIE BREAKER_21F

50 51

R_P15

50 51

R_P16

50 51

R_P17

50 51

R_P18

50 51

R_P19

BD_TR1

BD_TR2

COS12

COS22

COS32

COS42

COS52

COS62

COS72

COS82

TR1_IC_1F

TR2_IC_2F

DG1_IC_15F

DG2_IC_16F

DG3_IC_17F

DG4_IC_18F

DG5_IC_18F

CAP OG 5F OG_WH1_24F OG_WH2_25F OG_PACK2_23F OG_PACK1_22F OG_PACK3_25R OG_DCT_23R OG_CAP_24R CAB_WS_22R


50 51

OG_PCC AUX_3F

OG_REF1_4F

OG_DMP_6F

OG_EO_12F3

OG BOI1_10F

OG_SL_14F2

OGBOI2_11F

OG_DCT2_8F

OG_ROT_13F3

RP_14

50 51

R_P3

50 51

R_P4

50 51

R_P6

50 51

R_P10

50 51

R_P11

50 51

R_P13

50 51

R_P12

CAB_PACK2

CAB_PACK3

CAB_PACK1

CAB_PCCAUX

CAB_BOILER2

WAREHOUSE1 Vs: 433 V PPE: 0 AHE: 0.14 cal/cm^2(100%) AFB: 14.25 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 7.65 kA Iarc: 4.72 kA Config.: Switchgear WAREHOUSE2 Vs: 433 V PPE: 0 AHE: 0.24 cal/cm^2(85%) AFB: 20.25 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 7.65 kA Iarc: 4.02 kA Config.: Switchgear

CAB_WH1 WH1_IC

CAB_WH2 WH2_IC

CAB_DCT

CAB_CAP

CAB_WSS

CAB_REF1

CAB_DMP

CAB_EO

CAB_BOILER1

CAB_SL

CAB_DCT2

CAB_CCT2

CAB_FR

CAB_HG

CAB_CCT1

CAB_ETP

CAB_AOP

CAB_ROT

CAB_COT

CAB_CHP

290

CAB:CAP1

PACK2_IC

PACK1_IC

PACK3_IC

DCT_IC

CAP_IC

IWS_IC FWS_IC

295

REF1_IC PCC_AUX_IC Refinary 1 Vs: 433 V PPE: 0 AHE: 0.64 cal/cm^2(100%) AFB: 39.87 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 19.63 kA Iarc: 10.11 kA Config.: Switchgear

IDMP_IC FDMP_IC

EO_IC

BOILER1_IC

SL_IC

BOILER2_IC

DCT2_IC

CCT2_IC

IFR_IC FFR_IC

323 Vs: 433 V

IHY_IC FHY_IC

ICCT1_IC FCCT1_IC

IETP_IC3 FETP_IC

325 Vs: 433 V

IAOP_IC1 FAOP_IC1

IROT_IC2 FROT_IC2

ICOT_IC4 FCOT_IC4

ICHP_IC5 FCHP_IC5 FPP_IC1

Packing MCC 2 Packing MCC 3 Vs: 433 V Vs: 433 V PPE: 0 PPE: 0 AHE: 0.21 cal/cm^2(100%) AHE: 0.21 cal/cm^2(100%) AFB: 18.48 cm AFB: 18.54 cm AFD: 0.02 sec AFD: 0.02 sec WD: 61 cm WD: 61 cm LAB: 304.8 cm LAB: 304.8 cm RAB: 30.48 cm RAB: 30.48 cm PAB: 2.54 cm PAB: 2.54 cm Isc: 11.86 kA Isc: 11.92 kA Iarc: 6.73 kA Iarc: 6.76 kA Config.: Switchgear Packing MCC 1 Config.: Switchgear Vs: 433 V PPE: 0 AHE: 0.2 cal/cm^2(100%) AFB: 18.24 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 11.6 kA Iarc: 6.61 kA Config.: Switchgear

CAPACITOR PNL Vs: 433 V PPE: Extreme Danger AHE: 118.74 cal/cm^2(85%) CAP1 AFB: 1384.68 cm Vs: 433 V AFD: 15.18 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 7.62 kA Work Shop Iarc: 4 kA DCT 3 Vs: 433 V Config.: Switchgear Vs: 433 V PPE: 0 PPE: 0 AHE: 0.25 cal/cm^2(100%) AHE: 0.25 cal/cm^2(85%) AFB: 20.89 cm AFB: 21.18 cm AFD: 0.02 sec AFD: 0.03 sec WD: 61 cm WD: 61 cm LAB: 304.8 cm LAB: 304.8 cm RAB: 30.48 cm RAB: 30.48 cm PAB: 2.54 cm PAB: 2.54 cm Isc: 14.59 kA Isc: 8.25 kA Iarc: 7.96 kA Iarc: 4.27 kA Config.: Switchgear Config.: Switchgear PCC AUX Vs: 433 V PPE: 0 AHE: 0.26 cal/cm^2(85%) AFB: 21.6 cm AFD: 0.01 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.77 kA Iarc: 9.68 kA Config.: Switchgear

IPDB_OG

FPDB_OG

ENGG OFF Vs: 433 V PPE: 0 AHE: 0.54 cal/cm^2(100%) AFB: 35.46 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.92 kA Iarc: 11.45 kA Config.: Switchgear

IBF1_OG

FBF1_OG

STREET LIGHT Vs: 433 V PPE: 0 AHE: 0.41 cal/cm^2(100%) AFB: 29.44 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 16.12 kA Iarc: 8.62 kA Config.: Switchgear

IBF2_OG

FBF2_OG

DCT2 Vs: 433 V PPE: 0 AHE: 0.55 cal/cm^2(100%) AFB: 35.88 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 16.43 kA Iarc: 8.75 kA Config.: Switchgear

IPDB_IC

FPDB_IC

DM PLANT Vs: 433 V PPE: 1 AHE: 3.4 cal/cm^2(85%) AFB: 124.22 cm AFD: 0.35 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 9.93 kA Iarc: 4.96 kA Config.: Switchgear BOILER1 Vs: 433 V PPE: 0 AHE: 0.72 cal/cm^2(100%) AFB: 43.15 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.82 kA Iarc: 11.41 kA Config.: Switchgear

IBF1_IC

IBF2_IC

FBF1_IC

FBF2_IC

PDB Vs: 433 V PPE: 0 AHE: 0.15 cal/cm^2(100%) AFB: 14.79 cm AFD: 0.01 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 12.96 kA Iarc: 7.23 kA Config.: Switchgear

Bag Filter1 Vs: 433 V PPE: 0 AHE: 0.53 cal/cm^2(100%) AFB: 35.28 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 15.97 kA Iarc: 8.56 kA Config.: Switchgear

Bag Filter2 Vs: 433 V PPE: 0 AHE: 0.47 cal/cm^2(100%) AFB: 32.61 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 13.98 kA Iarc: 7.69 kA Config.: Switchgear

FRACTIONATION Vs: 433 V PPE: 0 AHE: 0.23 cal/cm^2(100%) AFB: 19.8 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 13.32 kA CCT2 Iarc: 7.39 kA Vs: 433 V Config.: Switchgear PPE: 0 HYDROGENERATION AHE: 0.33 cal/cm^2(100%) Vs: 433 V AFB: 25.24 cm PPE: 4 AFD: 0.03 sec AHE: 26.8 cal/cm^2(85%) WD: 61 cm AFB: 504.01 cm LAB: 304.8 cm AFD: 2.09 sec RAB: 30.48 cm WD: 61 cm PAB: 2.54 cm LAB: 304.8 cm Isc: 9.07 kA RAB: 30.48 cm BOILER 2 Iarc: 5.42 kA PAB: 2.54 cm Vs: 433 V Config.: Switchgear Isc: 13.4 kA PPE: 0 Iarc: 6.31 kA AHE: 0.72 cal/cm^2(100%) Config.: Switchgear AFB: 43.15 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 22.82 kA Iarc: 11.41 kA Config.: Switchgear

CCT1 Vs: 433 V PPE: 4 AHE: 32.26 cal/cm^2(85%) AFB: 571.63 cm AFD: 2.71 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 12.33 kA Iarc: 5.91 kA Config.: Switchgear ETP Vs: 433 V PPE: 3 AHE: 16.5 cal/cm^2(85%) AFB: 362.58 cm AFD: 2.77 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 5.56 kA Iarc: 3.11 kA Config.: Switchgear

AOP Vs: 433 V PPE: 0 AHE: 0.21 cal/cm^2(85%) AFB: 18.92 cm AFD: 0.03 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 6 kA Iarc: 3.4 kA Config.: Switchgear

CRUDE OIL TANK Vs: 433 V PPE: 3 AHE: 19.45 cal/cm^2(85%) AFB: 405.48 cm AFD: 3.48 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 5.18 kA Iarc: 2.93 kA Config.: Switchgear

ROT Vs: 433 V PPE: 4 AHE: 28.2 cal/cm^2(85%) AFB: 521.86 cm AFD: 5.82 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 4.4 kA Iarc: 2.57 kA Config.: Switchgear

Coal H Plant Vs: 433 V PPE: 0 AHE: 0.3 cal/cm^2(100%) AFB: 24.05 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 18.51 kA Iarc: 9.64 kA Config.: Switchgear

FIRE PUMP PANEL Vs: 433 V PPE: 0 AHE: 0.31 cal/cm^2(100%) AFB: 24.4 cm AFD: 0.02 sec WD: 61 cm LAB: 304.8 cm RAB: 30.48 cm PAB: 2.54 cm Isc: 18.96 kA Iarc: 9.83 kA Config.: Switchgear

CAB_BF1

CAB:BF2

cab:PDB

SINGLE LINE DIAGRAM FOR ARC FLASH STUDY-

REV. DATE

ECO#

DWN APP

DESCRIPTION

THIS DR AWING IS PROP RIETA RY INF OR MATION

Yo ur C o mp an y N am e Ad dress Ad dress Ph on e an d w eb site

Electrical One-Line Diagram

DRAWN B Y/DATE :

DW G N o.:

55

RE V.

EN G. APP./ DATE:

MFG. APP ./DATE :

PAR T N o.: DWG SI ZE :

SCAL E:

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

6.0

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.9 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: AOP

Project: EXELELE050312

56

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

16.0

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 35.3 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Bag Filter1

Project: EXELELE050312

57

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

14.0

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 32.6 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Bag Filter2

Project: EXELELE050312

58

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

22.8

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 43.1 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: BOILER 2

Project: EXELELE050312

59

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

22.8

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 43.1 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: BOILER1

Project: EXELELE050312

60

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

7.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 1384.7 cm)

Clothing Level Glove Class Insulated Tools


Required

Danger 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CAPACITOR PNL

Project: EXELELE050312

61

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

12.3

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 571.6 cm)

Clothing Level Glove Class Insulated Tools


Required

4 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CCT1

Project: EXELELE050312

62

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

9.1

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 25.2 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CCT2

Project: EXELELE050312

63

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

18.5

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 24.1 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Coal H Plant

Project: EXELELE050312

64

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

5.2

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 405.5 cm)

Clothing Level Glove Class Insulated Tools


Required

3 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: CRUDE OIL TANK

Project: EXELELE050312

65

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

8.2

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 21.2 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: DCT 3

Project: EXELELE050312

66

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

16.4

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 35.9 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: DCT2

Project: EXELELE050312

67

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

9.9

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 124.2 cm)

Clothing Level Glove Class Insulated Tools


Required

1 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: DM PLANT

Project: EXELELE050312

68

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

22.9

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 35.5 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: ENGG OFF

Project: EXELELE050312

69

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

5.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 362.6 cm)

Clothing Level Glove Class Insulated Tools


Required

3 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: ETP

Project: EXELELE050312

70

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

19.0

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 24.4 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: FIRE PUMP PANEL

Project: EXELELE050312

71

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

13.3

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 19.8 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: FRACTIONATION

Project: EXELELE050312

72

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

13.4

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 504.0 cm)

Clothing Level Glove Class Insulated Tools


Required

4 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: HYDROGENERATION

Project: EXELELE050312

73

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

30.7

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 51.9 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Main panel BB

Project: EXELELE050312

74

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

30.7

PPE Based on 46 cm Working Distance (Arc Flash boundary, PPE required within 900.9 cm)

Clothing Level Glove Class Insulated Tools


Required

Danger 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Main panel_TB

Project: EXELELE050312

75

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

11.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.2 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Packing MCC 1

Project: EXELELE050312

76

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

11.9

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.5 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Packing MCC 2

Project: EXELELE050312

77

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

11.9

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 18.5 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Packing MCC 3

Project: EXELELE050312

78

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

22.8

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 21.6 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: PCC AUX

Project: EXELELE050312

79

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

13.0

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 14.8 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: PDB

Project: EXELELE050312

80

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

19.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 39.9 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Refinary 1

Project: EXELELE050312

81

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

4.4

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 521.9 cm)

Clothing Level Glove Class Insulated Tools


Required

4 00

Suit Hood Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: ROT

Project: EXELELE050312

82

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

16.1

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 29.4 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: STREET LIGHT

Project: EXELELE050312

83

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 66.0, Prohibited = 17.8

11000.0

Max Short Circuit kA

0.7

PPE Based on 91 cm Working Distance (Arc Flash boundary, PPE required within 1.5 cm)

Clothing Level Glove Class Insulated Tools


Required

0 2

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: TG_PNL

Project: EXELELE050312

84

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

7.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 14.3 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: WAREHOUSE1

Project: EXELELE050312

85

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

7.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 20.3 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: WAREHOUSE2

Project: EXELELE050312

86

!
Volts

WARNING
Bus Electrical Shock and Arc Flash Hazard
Appropriate PPE Required

Shock Distances (cm) - Limited = 304.8, Restricted = 30.5, Prohibited = 2.5

433.0

Max Short Circuit kA

14.6

PPE Based on 61 cm Working Distance (Arc Flash boundary, PPE required within 20.9 cm)

Clothing Level Glove Class Insulated Tools


Required

0 00

Face Shield Eye Protection Non-melting FR Hair/Beard Nets

Not Allowed X

Arc Flash boundary at energy < 1.2 cal/cm^2 Equipment Name: Work Shop

Project: EXELELE050312

87

ENERGIZED ELECTRICAL WORK PERMIT


Job/Work Order Number: PART 1: TO BE COMPLETED BY THE REQUESTER
(1) Description of circuit / equipment / job location / bus name:
AOP

(2) Description of work to be done:


(3) Reasons why the circuit / equipment cannot be de-energized or the work deferred until the next scheduled outage:

_________________________________________________

Requester / Title

______________________________________

Date

PART II: TO BE COMPLETED BY THE ELECTRICALLY QUALIFIED PERSONS DOING THE WORK: Check When Complete ____ (1) Detailed job description procedure to be used in performing the above detailed work:

___________________________________________________________________________________________________________ ___________________________________________________________________________________________________________ ____ (2) Description of the Safe Work Practices to be employed: ___________________________________________________________________________________________________________ ___________________________________________________________________________________________________________

Arc Flash Boundary

18.9 cm

Arc Flash Hazard

0.2 cal/cm^2

Working Distance Prohibited Approach Glove Class

Limited Approach 304.8 cm Restricted Approach 30.5 cm Required PPE 0 Shock Hazard 0.433000 kV Cotton underclothing plus FR shirt, pants, overalls or equivalent

61.000000 cm 2.5 cm 00

(3) Means employed to restrict the access of unqualified persons from the work area:

____ ___________________________________________________________________________________________________________ ____ (4) Evidence of completion of a Job Briefing including discussion of any job-related hazards: ___________________________________________________________________________________________________________

(5) Do you agree the above described work can be done safely? Electrically Qualified Person(s)
_________________________________________________

Yes

No (if no, return to requestor)

______________________________________

Date

Electrically Qualified Person(s)

_________________________________________________

______________________________________

Date

PART III: APPROVAL(S) TO PERFROM THE WORK WHILE ELECTRICALLY ENERGIZED Maintenance / Engineering Manager Safety Manager
_________________________________________________ _________________________________________________ _________________________________________________ ______________________________________

Manufacturing Manager

______________________________________

Electrically Knowledgeable Person Date

General Manager

______________________________________

88

Estimated Total Energy 3-Phase


100

Bus:CCT1,433.0V, Bolted Short-circuit = 12333.476563A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 200 400 600 800 1000

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

89

Estimated Total Energy 3-Phase


100

Bus:AOP,433.0V, Bolted Short-circuit = 5995.899414A, 25 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

90

Estimated Total Energy 3-Phase


Bus:Bag Filter1,433.0V, Bolted Short-circuit = 15965.124023A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 20.0 40.0 60.0 80.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

91

Estimated Total Energy 3-Phase


Bus:Bag Filter2,433.0V, Bolted Short-circuit = 13977.703125A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 20.0 40.0 60.0 80.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

92

Estimated Total Energy 3-Phase


Bus:BOILER 2,433.0V, Bolted Short-circuit = 22816.070313A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 20 40 60 80 100 120

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

93

Estimated Total Energy 3-Phase


Bus:BOILER1,433.0V, Bolted Short-circuit = 22816.070313A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 20 40 60 80 100 120

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

94

Estimated Total Energy 3-Phase


Bus:CAPACITOR PNL,433.0V, Bolted Short-circuit = 7619.831055A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

95

Estimated Total Energy 3-Phase


100

Bus:CCT2,433.0V, Bolted Short-circuit = 9066.217773A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

96

Estimated Total Energy 3-Phase


Bus:Coal H Plant,433.0V, Bolted Short-circuit = 18507.517578A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0 60.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

97

Estimated Total Energy 3-Phase


Bus:CRUDE OIL TANK,433.0V, Bolted Short-circuit = 5177.104492A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 100 200 300 400 500 600 700 800

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

98

Estimated Total Energy 3-Phase


100

Bus:DCT 3,433.0V, Bolted Short-circuit = 8249.337891A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

99

Estimated Total Energy 3-Phase


100

Bus:DCT2,433.0V, Bolted Short-circuit = 16426.253906A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 20.0 40.0 60.0 80.0 100.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

100

Estimated Total Energy 3-Phase


Bus:DM PLANT,433.0V, Bolted Short-circuit = 9928.815430A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 50 100 150

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

101

Estimated Total Energy 3-Phase


Bus:ENGG OFF,433.0V, Bolted Short-circuit = 22922.187500A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 20.0 40.0 60.0 80.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

102

Estimated Total Energy 3-Phase


100

Bus:ETP,433.0V, Bolted Short-circuit = 5564.045898A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 100 200 300 400 500 600 700

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

103

Estimated Total Energy 3-Phase


Bus:FIRE PUMP PANEL,433.0V, Bolted Short-circuit = 18960.271484A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0 60.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

104

Estimated Total Energy 3-Phase


Bus:FRACTIONATION,433.0V, Bolted Short-circuit = 13318.649414A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

105

Estimated Total Energy 3-Phase


Bus:HYDROGENERATION,433.0V, Bolted Short-circuit = 13400.445313A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 200 400 600 800 1000

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

106

Estimated Total Energy 3-Phase


Bus:Main panel BB,433.0V, Bolted Short-circuit = 30661.220703A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 20 40 60 80 100 120 140

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

107

Estimated Total Energy 3-Phase


Bus:Main panel_TB,433.0V, Bolted Short-circuit = 30714.003906A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 500 1000 1500 2000

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

108

Estimated Total Energy 3-Phase


Bus:Packing MCC 1,433.0V, Bolted Short-circuit = 11596.562500A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

109

Estimated Total Energy 3-Phase


Bus:Packing MCC 2,433.0V, Bolted Short-circuit = 11856.061523A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

110

Estimated Total Energy 3-Phase


Bus:Packing MCC 3,433.0V, Bolted Short-circuit = 11922.164063A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

111

Estimated Total Energy 3-Phase


Bus:PCC AUX,433.0V, Bolted Short-circuit = 22768.208984A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

112

Estimated Total Energy 3-Phase


100

Bus:PDB,433.0V, Bolted Short-circuit = 12955.328125A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

113

Estimated Total Energy 3-Phase


Bus:Refinary 1,433.0V, Bolted Short-circuit = 19627.724609A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 20 40 60 80 100

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

114

Estimated Total Energy 3-Phase


100

Bus:ROT,433.0V, Bolted Short-circuit = 4403.567871A, 32 mm arc


Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0 200 400 600 800 1000

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

115

Estimated Total Energy 3-Phase


Bus:STREET LIGHT,433.0V, Bolted Short-circuit = 16119.906250A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

116

Estimated Total Energy 3-Phase


Bus:TG_PNL,11000.0V, Bolted Short-circuit = 696.923096A, 153 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

117

Estimated Total Energy 3-Phase


Bus:WAREHOUSE1,433.0V, Bolted Short-circuit = 7647.652344A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

118

Estimated Total Energy 3-Phase


Bus:WAREHOUSE2,433.0V, Bolted Short-circuit = 7647.652344A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

119

Estimated Total Energy 3-Phase


Bus:Work Shop,433.0V, Bolted Short-circuit = 14588.853516A, 32 mm arc
100 Working Distance PPE 4 Min Distance >1.2 cal/ cm^2 <1.2 cal/ cm^2

10.0

Energy (Cal/cm^2)

1.00

0.100 0.0 10.0 20.0 30.0 40.0 50.0

Distance from Arc Gap (cm)


0 20 40 60 80 100

Job File: EXELELE050312

Date: 03/05/12

120

121

122

123

124

125

126

127

128

129

130

131

132