4-fold Selection Element 42 500 safety-related 2 out of 3 selection The module is TV tested according to DIN V 19250 for RC 1...7, according to IEC 61508 for SIL 4 and EN 954-1 for Cat 4.

42 500
RDY ERR Y1 DF1 Y2 DF2 Y3 DF3 Y4 DF4

Outputs

If at least 2 of 3 inputs z2, d2, z4 (z6, d6, z8 etc.) are set to 1-signal, then the output z22 (d22 etc.) is also on 1-signal. The outputs are decoupled by diodes; they can be connected in parallel for OR functions (wired OR). The switch DZ on the PCB of the module enables the setting of the tolerance time for discrepancies of the signals in 15 steps. If the set time is exceeded, then the output z18 (d18 etc.) is on 1-signal and the LED DF1 (DF2 etc.) is on. The outputs DF are not safety-related; they can be connected via a signal bus to a common annunciation. All functions on the module are monitored by a micro-controller. A malfunction is indicated by ERR, the output d28 is on 1-signal and the relay contact z26-d26 opens. The output z28-b28 is provided for the connection to the communication module, e. g. for data transfer to a process control system. RDY (Ready) indicates the available power supply voltage ( 20 V). Switching time (Y1...Y4) Reset time (Y1...Y4) Switching time (DF1...DF4) Reset time (DF1...DF4) Operating data Space requirement approx. 2 ms approx. 5 ms 3 ms (at DZ = 0)...15 s, in 15 steps approx. 3 ms 24 V DC / 90 mA 3 U high, 4 SU

All rights reserved. The technology is subject to changes without notice: HIMA Paul Hildebrandt GmbH + Co KG, Postfach 1261, 68777 Brhl

1/4

42 500 (0128)
Communication via MODBUS Reading of variables Type BOOL: Function code 1 Type WORD: Function code 3 Events: Function codes 65, 66, 67
Rel. address 0 1 2 3 4 5 6 7...8 9 10 11 12 13 14 15 16 17 18 19 20 21...40 41 42 43 44 45 46 47 48 Data type WORD BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL Value 45 H 0 1 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Value: Meaning Module type 42 500 none Module removed Communication with module not o.k. Module in slot, communication o.k. Operating voltage too low, no RDY Module error, ERR none 1-signal at input z2 1-signal at input d2 1-signal at input z4 1-signal at input z6 1-signal at input d6 1-signal at input z8 1-signal at input z10 1-signal at input d10 1-signal at input z12 1-signal at input z14 1-signal at input d14 1-signal at input z16 none 1-signal at output z22 Y1 1-signal at output z18 DF1 1-signal at output d22 Y2 1-signal at output d18 DF2 1-signal at output z24 Y3 1-signal at output z20 DF3 1-signal at output d24 Y4 1-signal at output d20 DF4 24 25 26 27 28 29 30 31 0 1 2 3 4 5 6 7 8 9 10 11 Rel. event no.

0 always has the contrary meaning H: hexadecimal value absolute address: A = p 256 + rel. address absolute event no.: E = (p - 1) 32 + rel. event no. p = module location no. in the subrack

2/4

42 500 (0128)
Reading of all variables Function code 3, 84 words since address 2000 H, 3000 H or 4000 H
Word 0 (16 bit) Rel. address Data 0 Mod. type Mod. state Word 1 (16 bit) Inputs Inputs Word 2 (16 bit) none none Word 3 (16 bit) 48 . . . . . . 41 none Outputs

8 . . . . . . 1 24 . . . . . . 17 16 . . . . . . 9 40 . . . . . . 33 32 . . . . . . 25

For a faultless data transfer all 84 words must be read. With that all the variables of the modules of one subrack are transferred. For module locations not in use the values 0 are transferred.

3/4

42 500 (0128)
Communication via Profibus-DP Reading of variables Relative addresses type WORD and type BYTE
WORD Bit 0...7 8 9 10 0 11 12 13 14 15 0 1 2 3 4 5 1 6 7 8 9 10 11 12...15 2 0 1 2 3 3 4 5 6 7 8...15 7 6 4...5 0 1 2 3 4 5 6 7 0...7 Value: 3 2 1 BYTE 0 Bit 0...7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4...7 Value 45 H 0 1 1 1 1 1 0 0 1 1 1 1 1 1 1 1 1 1 1 1 0 0 1 1 1 1 1 1 1 1 0 Meaning Module type 42 500 none Module removed Communication with module not o.k. Module in slot, communication o.k. Operating voltage too low, no RDY Module error, ERR none none 1-signal at input z2 1-signal at input d2 1-signal at input z4 1-signal at input z6 1-signal at input d6 1-signal at input z8 1-signal at input z10 1-signal at input d10 1-signal at input z12 1-signal at input z14 1-signal at input d14 1-signal at input z16 none none 1-signal at output z22 Y1 1-signal at output z18 DF1 1-signal at output d22 Y2 1-signal at output d18 DF2 1-signal at output z24 Y3 1-signal at output z20 DF3 1-signal at output d24 Y4 1-signal at output d20 DF4 keine

0 always has the contrary meaning H: hexadecimal value absolute address WORD: W = 4 (p - 1) + rel. address absolute address BYTE: B = 8 (p - 1) + rel. address p = module location no. in the subrack