Request for Proposals For Appointment of an Agency for Design, Supply, Installation, Configuration, Operations and Maintenance of Physical

and IT Infrastructure for State Data Centre, Andhra Pradesh

Volume-II (Technical and Functional Specifications)

Bid Reference No. APTS/IIP/282/SDC/2009

Andhra Pradesh Technology Services Limited (APTS) 4th Floor, B Block, BRKR Bhavan, Tankbund Road, Hyderabad 500 063 (A.P.)

Volume II Technical and Functional Specifications

TABLE OF CONTENTS

Section I Annexure ................................................................................. 5


1.1
1.1.1 1.1.2 1.1.3

Annexure I Technical Requirements....................................................... 5


SDC Architecture IT .......................................................................................... 5 Bill of Material ...................................................................................................... 8 Technical Specifications - IT Components ........................................................ 12

SDC Architecture Physical Infrastructure ............................................. 49


2.1
2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 2.1.6 2.1.7

Layout of the Data Centre ....................................................................... 49


Electrical Distribution System ............................................................................ 55 Humidity, Ventilation and Air Conditioning Systems .......................................... 55 Rodent Repellant ............................................................................................... 57 False Ceiling ...................................................................................................... 57 UPS Requirements & Features ......................................................................... 57 Diesel Generator Set ......................................................................................... 59 Electrical Work for SDC ..................................................................................... 59

2.2
2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9

Technical Specifications Physical Components .................................... 61


UPS .................................................................................................................... 61 Diesel Generator Set ......................................................................................... 63 Civil & Architectural work ................................................................................... 64 PVC Conduit ...................................................................................................... 68 Wiring ................................................................................................................. 68 Earthing .............................................................................................................. 70 Cable Work ........................................................................................................ 71 Precision Air Conditioning .................................................................................. 71 Split type Comfort Air Conditioning for Auxiliary Areas ..................................... 75

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 2 of 99

Volume II Technical and Functional Specifications

2.2.10 2.2.11 2.2.12 2.2.13 2.2.14 2.2.15 2.2.16 2.2.17 2.2.18 2.2.19 2.2.20 2.2.21

Fire Detection and Control Mechanism ............................................................. 76 Fire Suppression Systems ................................................................................. 79 High Sensitivity Smoke Detection System ......................................................... 80 Access Control System ...................................................................................... 80 CCTV System .................................................................................................... 81 Building Management System (BMS) ................................................................ 88 Water Leak Detection System ........................................................................... 89 Fire Proof Enclosures for Media Storage........................................................... 90 Public Address System ...................................................................................... 90 Common Alarm System ..................................................................................... 90 Physical Security................................................................................................ 90 Electrical Panels ................................................................................................ 91

Section III- Compliance to Specifications ................................................ 98

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 3 of 99

Volume II Technical and Functional Specifications

SECTION I Technical Requirements

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 4 of 99

Volume II Technical and Functional Specifications

1 Section I Annexure
1.1 Annexure I Technical Requirements
The bidders can propose appropriate industry standard products & solutions for the components required for implementation of the Andhra Pradesh State Data Centre Project. It is to be noted that SDA may procure all /part of the Infrastructure requirements/services as specified in the RFP. It is not binding on the SDA to procure all the infrastructure/services from the same organization and at the time of signing the contract. Based on the IT Solution implementation roadmap of the State Government departments, SDA may procure/implement the infrastructure/services as sought under this RFP in phased manner.

1.1.1

SDC Architecture IT

Figure1: A typical SDC architecture is being depicted in the schematic below:

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 5 of 99

Volume II Technical and Functional Specifications

Design Description At SDC, a Gigabit Ethernet link from SWAN (SHQ) will be connected to the L3 switch It should be also noted that, SWAN would also be carrier for CSC information or dataflow between the Citizens / Users (Departments/ Offices) and the SDC. This Router would be the bridge between the Intranet i.e. SWAN users and SDC environment. The router would also have capability to handle the data traffic and multiple SSL/VPN encapsulations for secured data transfer between

SWAN/CSC/Internet and SDC. Intrusion Prevention system should detect malicious traffic and further protect the SDC environment; Intrusion system would also detect (and prevent) any intrusion from Internet/extranet network. Firewalls would provide next layer of protection between the extranets (SWAN/ CSC/ Internet) and DMZ (which has hosted the application server). All the servers would be connected to high capacity LAN Switch, which can process million of packets within seconds, depending on the Users and Application and its contents. The Application servers would be accessing the database from the backend in order to process the user / citizens queries/requests. The Database servers (RDBMS) are further hosted in higher security layer, comprising of components such as Firewall and Intrusion Prevention system. The SDC provides Infrastructure Services such as Firewall Service, Directory Service, Web Service, Database Service, messaging and data storage services etc. which would be shared among all the applications / departments participating in the SDC. Using these services, the SDC ensures centralized delivery of citizen / departmental services. The SDC services would be deployed as components and therefore will have a potential for re-use in launching future services, without disturbing the existing architecture. In this secure infrastructure it has to be ensured that the security devices in the network such as Firewalls, are in high-availability mode, and these devices should be even distributed to optimize performance.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 6 of 99

Volume II Technical and Functional Specifications

The business related services would also have a potential of having multichannel access / integration in future, as the data returned by the components would be in XML /SOAP format. Unicode would be the technology used for dissemination of information in multi-lingual format, though the existing data is stored in font based format. Since, several outside entities will access SDC services, and hence it is important to use international standards such as the Unicode etc.

Another key consideration should be done for hosting the Legacy applications. SG has to migrate / port the applications to n tier architecture, which would be provided using SDC.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 7 of 99

Volume II Technical and Functional Specifications

1.1.2

Bill of Material

Following includes the Bill of Material for the State Data Center for Government of Andhra Pradesh. The specifications of the components listed below are provided in the later sections of the RFP. The bidder shall provide the quotation for unit prices for the following components in the commercial bid. However for overall commercial evaluation, the quantities indicated in the table below shall be considered. At the time actual implementation, based on the requirements, the number of servers may be increased / decreased by the SDA. It is the responsibility of Bidder to provide the recommendations to the SDA as to how many servers would be required to be implemented in the SDC as per the IAs assessment at the time of implementation of the SDC Consolidated Bill of Material for the State Data Centre: S. No Hardware Components 1. 2. 3. 4. 5. 6. 7. 8. 9 10. 11. 12. Application Servers Web Servers Database server (Intel / AMD 64) Enterprise Access Server Management Server Directory Server Enterprise Backup server Staging Server Integration Server Antivirus Server Archival Servers SAN Storage (1) including SAN Switch (2) & SAN 5 2 5 2 1 2 1 1 1 1 2 1 Components Qty

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 8 of 99

Volume II Technical and Functional Specifications

S. No

Components Storage Management Software (1), Backup Software (1)

Qty

13. 14. 15. 16. 17. 18. 19. 20. 21. 22 a. 22 b. 23. 24. 25. 26. 27.

Tape Library NAS Gateway Internet Routers Aggregation Core Switches Edge Switches External Firewall Internal Firewall Intrusion Prevention System (IPS) Host Based Intrusion Prevention System (HIPS) Open Racks for Network Components Server Racks 42 U KVM Switches over IP for Network Racks 15 TFT Monitor, Keyboard and Mouse 8 port KVM for Server Racks Desktop PC for Monitoring & Data Center Management Structured cabling requirements for the Data Center for a total of 59 Racks Other Data Center Civil, Electrical, Physical & Environmental Security Infrastructure Precision Air Conditioning System for the Server Farm Area Phase I of around 1585 sq.ft. as per the specifications BMS Components like CCTV System, Access Control, VESDA, WLDS, RRS, Fire Suppression and Detection

1 1 2 2 2 2 2 2 23 9 20 6 6 12 10 As required

28.

As required

66 TR

29.

30.

As required

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 9 of 99

Volume II Technical and Functional Specifications

S. No

Components System including the BMS software

Qty

31. 32. 33. 34.

Comfort Air Conditioning for the Auxiliary Area as per the specifications for an area of 2532 sq.ft. Generator Set (2 Nos. of each 600 KVA) UPS for the Server Farm Area Phase I for 35 Racks (each of 160 KVA) UPS for BMS, NOC & Staging Area (each 30 KVA)

25 TR

2 4

Software Components 35. 36. 37. 38. 39. 40. 41. Archival Software Microsoft Windows Server 2003, Enterprise Edition R2 64 bit OLP Red Hat Enterprise Linux 5 & 4 AP / SUSE Linux Enterprise Server 9 /Unix. Antivirus Software (Server License) Antivirus Software (Client Licenses)
Oracle 10g R2 Enterprise Edition Processor Licenses Oracle 10g RAC Enterprise Edition Licenses

1 15 8

1 30 4 4

All the servers will be blade servers except the Database servers. For EMS, the DCO will leverage the existing modules available with APSCAN and extend the same to the State Data Centre.

For Server Load Balancer, the DCO will leverage the same available with the SDA for the State Data Centre. APSCAN has already procured and implemented the following management tools from Computer Associates (CA) to manage their existing State Data Centre: The following modules are covered under Enterprise Management : o o o o eTrust Antivirus eTrust Secure Content Manager v1.0 Unicenter Network and Systems Management Unicenter NSM NPO

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 10 of 99

Volume II Technical and Functional Specifications

o o o o o o o o o o o o o o o o o o o o o o

eTrust Access Control for Unicenter Unicenter NSM Database Performance Unicenter Remote Control Unicenter Software Delivery Unicenter Asset Management Unicenter Advanced Network Operations Unicenter Management for Web Servers Unicenter Management Lotus Notes / Domino Option BEB Backup Agent for NT / 2000 Encrypted BEB Open Files for NT / 2000 BEB Backup Agent for SQL BEB Server for NT / 2000 Encrypted eTrust Antivirus LNO Unicenter NSM SPO Unicenter Performance Management Predictive Option CA e Health CA Spectrum CA Secure Content Manager CA Unicenter Single Server Helpdesk CA Insight Database Performance Management CA Audit CA Access Control

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 11 of 99

Volume II Technical and Functional Specifications

1.1.3

Technical Specifications - IT Components

1.1.3.1 Database Server (Intel / AMD 64) Minimum 2x Quad Core Processor Minimum 2.4 or above with 1066 MHz FSB / 2000 MT/s expandable to 4 physical processor with min 2 MB L2 cache per processor OS support: Microsoft Windows Server 2003, Enterprise Edition / Red Hat Enterprise Linux 5 & 4 AP / SUSE Linux Enterprise Server 9 /Unix Memory (RAM): Min. 8 GB scalable to 64 GB DDR 2 RAID controller with RAID 0/1/5 with 256 MB cache HDD: 4 x 146 GB 2.5 10 K RPM HDD or higher Disk bays: Support for min 8 small form factor hot plug SAS / SCSI hard drives in disk drive carriers that slides out from front Atleast 2 x 10/100/1000 Mbps Ethernet ports or more 2 x 4 Gbps Fiber Channel Ports Ports Rear: Two USB ports (Ver 2.0); RJ-45 Ethernet; keyboard and mouse; two RJ-45 Ethernet; / no parallel port Front: One USB (Ver 2.0) Graphics controller: SVGA / PCI bus / ATI ES 1000 / min 16MB SDRAM std/max / 1280x1024 at 16M colors Optical / diskette: 8X / 24X slim-line DVD ROM drive Security: Power-on password / admin password / unattended boot / selectable boot / boot without keyboard Cooling fans: minimum Four fans / multispeed / hot-swap and redundant fan failure signals to management module / fan in each power supply / CPU / memory Power supplies: Hot plug redundant AC power supply Remote Management hardware to monitor server remotely even when server power is off. Management feature to identify failed components even when server is switched off. Rack Mountable It should provide Secure Sockets Layer (SSL) 128 bit encryption and Secure Shell (SSH) Version 2 and support VPN for secure access over internet. Should be able to manage systems through a web-browser

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 12 of 99

Volume II Technical and Functional Specifications

1.1.3.2 Application Server, Web Servers, Enterprise Access Servers, Management Servers, Directory Server, Enterprise Backup Server, Staging Server, Integration Server, Antivirus Server (Blade Servers)

Chassis Specification Single blade chassis should accommodate minimum 6 (QuadProcessor) / 8 (Dual Processor) or higher hot pluggable blades. 6 U to 12 U Rack-mountable Dual network connectivity for each blade server for redundancy should be provided. Backplane should be completely passive device. If it is active, dual backplane should be provided for redundancy Should accommodate Intel, AMD, RISC / EPIC Processor based Blade Servers for future applications Same chassis should support dual CPU and Quad CPU blades Should have the capability for installing industry standard flavors of Windows, Linux / Unix Operating Environments Single console for all blades in the enclosure or KVM Module DVD ROM can be internal or external, which can be shared by all the blades allowing remote installation of S/W and OS Minimum 2 external USB connections functionality Two hot-plug, redundant 1Gbps Ethernet module with minimum 10 ports (cumulative), which enable connectivity to Ethernet via switch. Switch should be (Internal/external) having Layer 3 functionality routing, filtering, traffic queuing etc Two hot-plugs, redundant 4 Gbps Fiber Channel for connectivity to the external Fiber channel Switch and ultimately to the storage device. Power Supplies o Hot Swap redundant power supplies to be provided o Power supplies should have N+N. All Power Supplies modules should be populated in the chassis Hot Swappable and redundant Cooling Unit LED / LCD Alerts/ indication on Hard disk drives, processors, blowers, memory Management o o o Systems Management and deployment tools to aid in Blade Server configuration and OS deployment, Remote management capabilities through internet browser It should provide Secure Sockets Layer (SSL) 128 bit encryption and Secure Shell (SSH) Version 2 and support VPN for secure access over internet.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 13 of 99

Volume II Technical and Functional Specifications

o o

Ability to measure power historically for servers or group of servers for optimum power usage Blade enclosure should have provision to connect to display console / central console for local management like trouble shooting, configuration, system status/health display

Built in KVM switch or Virtual KVM feature over IP. Dedicated management network port should have separate path for management Support heterogeneous environment: AMD, Xeon and RISC/EPIC CPU blades must be in same chassis with scope to run Win2003 Server, Red Hat Linux / 64 Bit UNIX, Suse Linux / 64 Bit UNIX. o o o o o o

Blade Specifications Blade can be half / full height with I/O connectivity to backplane 2 Quad core @ 2.0 GHz or above with 6 MB shared L3 cache, 1066 MHz / 2000 MT/s FSB Min 8 GB FBD DDR2 RAM with min 2 Nos free slots for future expandable capability. Minimum Memory: 8 GB scalable to 64 GB per blade The Blade should have redundant 4 Gbps Fiber Channel HBA 2 X (1000BASE-T) Tx Gigabit LAN ports with TCP / IP offload engine support / dedicated chipset for network I/O on blade server 2 X 146 GB HDD or more hot swappable system disk with mirroring using integrated RAID 0,1 on internal disks. It should be possible to hot swap the drives without shutting down the server. Should support heterogeneous OS platforms VGA / Graphics Port / Controller

o o

1.1.3.3 Storage and Backup Solution SAN Switch 2 Nos. Minimum 16 Active ports (each with minimum port speed 4 GB) within same switch upgradeable to 32 ports with minimum 2 Nos. of additional 10 Gbps FC ports All cable of length of 10 meter each and accessories for connecting Servers /Devices to SAN. Should have capability of ISL trunking of minimum 8 ports. Should support multiple OS. Non disruptive subsystem maintenance.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 14 of 99

Volume II Technical and Functional Specifications

Should have dual Fans and Hot plug power supplies switching and service modules. Should have web based management software for administration and configuration. Non disruptive microcode / firmware upgrades and hot code activation. Switch shall support in built diagnostics, power on self test, command level diagnostics, online and offline diagnostics. Should support hardware ACL based Port security, Port Zoning and LUN Zoning Should support Secure Shell (SSH) encryption to provide additional security for Telnet sessions to the switch. Should support multilevel security on console access prevent unauthorized users from altering the switch configuration Should support Fibre Channel trace route and Fibre Channel Ping for ease of troubleshooting and fault isolation Should support the following diagnostics: o Online Diagnostics o Internal Loopbacks o SPAN o FC Debug o Syslog o Online system health o Power on self test (POST) diagnostics Should support Applications for device management and full fabric management. The management software shall be able to perform following: o Fabric View o Summary View o Physical View o Discovery and Topology Mapping o Network Diagnostics o Monitoring and Alerts

SAN 1 No.
Description Specifications

SAN Controller Cache Host Interface Drive Interface

Dual Active Active Controller 8 GB Total Mirrored Cache for Disk IO Operations scalable to minimum 16 GB across dual controller 4 host ports per controller, Fibre Channel (FC),4 Gbps per port 4 drive portsFibre Channel (FC) Switched or FC Arbitrated Loop (FC-AL) standard per controller,

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 15 of 99

Volume II Technical and Functional Specifications

Description

Specifications

4 Gbps per port RAID Levels supported 0, 1, 5, 6.

Fans and Power supplies SAN support

Dual redundant, hot-swappable Box should be compatible of SAN environment

SAN specifications shall have the following specifications: The storage array shall be configured with at least 8 GB cache scalable to minimum 16 GB mirrored across two storage controllers for disk I/O operations. Storage subsystem shall support 146GB, 300GB 15K RPM disks and 400GB or higher 10K RPM Fibre channel drives & 750GB, 1TB SATA or higher SATA/equivalent drives in the same device array Presently, the storage sub system shall be configured with 300 GB or higher of Performance drives and 750 GB or higher on SATA / equivalent for archiving purpose. The storage system should support Flash drives to maximize performance with minimum foot print and power consumption. The storage system must keep write keep caches persistent during fault conditions to prevent data loss The storage system must provide upgrade path to larger or future array controller and software technology while maintaining the existing investment. All the necessary software to configure and manage the storage space, RAID configuration, logical drives allocation, virtualization, snapshots (including snap clones and snap mirrors) for entire capacity etc. Redundant power supplies, batteries and cooling fans and data path and storage controller. Load balancing must be tools. controlled by system management software

The multi-path software should not only support the supplied storage and operating systems but should also support heterogeneous storage and operating systems from different OEMs. The storage array must have complete cache protection mechanism either by de-staging data to disk or providing complete cache data protection with battery backup for upto 72 hours or more. The storage system should be pre-configured with at least 50 TB of raw Storage Capacity (excluding the storage capacity required for storing the storage array operating system) implemented out of which 20 TB shall be configured using Fiber Channel Hard disks @ 300 GB 15 K RPM drives and

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 16 of 99

Volume II Technical and Functional Specifications

30 TB raw capacity shall be configured using 750 GB or higher SATA / equivalent drives. The Storage should have at least 16 Gbps port bandwidth per controller for the connectivity to servers and at least 16 Gbps port bandwidth (aggregated) for disk connectivity per controller The storage array must have the capability to do array based remote replication using FCIP or IP technology. The storage array should support Synchronous and Asynchronous replication across heterogeneous storage arrays from different OEMs The storage array should support Operating System Platforms & Clustering including: Windows Server 2003 (Enterprise Edition), Sun Solaris, HP-UX, IBM-AIX, Linux. Storage should support non-disruptive online firmware upgrade for both Controllers and disk drives. The storage array should support hardware based data replication at the array controller level across all models of the offered family. The storage should provide automatic rerouting of I/O traffic from the host in case of primary path failure. Should provision for LUN masking, fibre zoning and SAN security. Should support storage virtualization, i.e. automatic logical drive expansion and shrinking based on policy, creation of different RAID types with in disk group etc. Should support hot-swappable physical drive raid array expansion with the addition of extra hard disks The storage system should be scalable from 50 TB to 200 TB of raw capacity using 40% on Fiber Channel drives and 60% on SATA / equivalent drives using the same configuration Should be able to allocate logical spaces to multiple operating systems in the same storage facility. Should be able to support clustered and individual servers at the same time. Should be to take "snapshots" of the stored data to another logical drive for backup purposes. Should be configured with "snapshots and clone" for 50% of the entire capacity of the storage array Vendor should also offer storage performance monitoring and management software. The vendor must provide the functionality of proactive monitoring of Disk drive and Storage system for all possible hard or soft disk failure.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 17 of 99

Volume II Technical and Functional Specifications

Tape Library 1 No. Description Tape drives Interface

Specification 6 x LTO 4 FC drives scalable to minimum 15 Fiber Channel Interface

Should have sufficient speed backup to Tape Library in High Availability for backing up data from the SAN without any user intervention. Should be able to backup 50% of the entire production landscape in 8 hours window. Should support LTO-4 or latest technology based library with at least 6 LTO-4 tape drives (>=6), rack mountable with redundant power supplies. Cartridges should have physical capacity up to 1600 GB per cartridge compressed; 800 GB native. Atleast 50 LTO 4 Media Cartridges with 5 Cleaning Cartridges, Barcode labels shall also be provided

Archival Software The software shall support defined policies that are based on a variety of standard file attributes such as age of file / last access time. The software shall set high and low watermark levels for purging data from high performance storage based upon a percentage of disk space in use. The software shall keep active data on host arrays while inactive or compliance data is automatically moved to disk or tape. The software shall support truncated stub files to point to migrated data, enabling seamless file access regardless of location of the data. Shall enable back-ups at disk speed, while dramatically decreasing recovery times. Shall offer a single logical view of both active and inactive data regardless of where it is physically located. Shall eliminate repeated backups of the same archived data. OS support: Microsoft Windows Server 2003, Enterprise Edition / Red Hat Enterprise Linux 5 & 4 AP / SUSE Linux Enterprise Server 9 / Unix / Solaris / HP Unix / IBM AIX Archival servers shall be offered in cluster, Min 2 Node cluster shall be offered based on Industry Standard Servers with 2 x Dual Core Intel CPU , Min 8 GB of RAM , 2 x DC HBA's ( 4 Gbps ) , 4 x NIC Ports on each node.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 18 of 99

Volume II Technical and Functional Specifications

Backup Software The proposed Backup Solution should be available on various OS platforms such as Windows and UNIX platforms and be capable of supporting SAN based backup / restore from various platforms including UNIX, Linux, and Windows etc. Centralized, web-based administration with a single view of all back up servers within the enterprise. Single console must be able to manage deduplicated and traditional backups. The proposed backup solution should allow creating tape clone facility after the backup process. The proposed Backup Solution has in-built frequency and calendar based scheduling system. The proposed backup solution supports the capability to write multiple data streams to a single tape device or multiple tape devices in parallel from multiple clients to leverage the throughput of the Drives using Multiplexing technology. The proposed backup solution support de-multiplexing of data cartridge to another set of cartridge for selective set of data for faster restores operation to client/servers The proposed backup solution should be capable of taking back up of SAN environment as well as LAN based backup. The proposed backup solution shall be offered with 4 Nos. UNIX based licenses, 15 Nos. Windows based licenses and the rest 6 Nos. LINUX based licenses for both SAN based backup and the LAN based backup The proposed solution also supports advanced Disk staging. The proposed Backup Solution has in-built media management and supports cross platform Device & Media sharing in SAN environment. It provides a centralized scratched pool thus ensuring backups never fail for media. Backup Software is able to rebuild the Backup Database/Catalog from tapes in the event of catalog loss/corruption. Backup software must ensure data recovery on any archived tape. The proposed Backup Software should offer online backup for all the Operating Systems i.e. UNIX, Windows & Linux etc The proposed Backup Solution has online backup solution for different type of Databases such as Oracle, MS SQL, Sybase / DB2 etc. on various OS. The Proposed backup solution shall provide granularity of single file restore. The Proposed backup solution shall be designed in such a fashion so that every client/server in a SAN can share the robotic tape library. Backup Solution shall be able to copy data across firewall.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 19 of 99

Volume II Technical and Functional Specifications

The backup software must also be capable of reorganizing the data onto tapes within the library by migrating data from one set of tapes into another, so that the space available is utilized to the maximum. The software must be capable of setting this utilization threshold for tapes

The backup software should be able to support versioning and should be applicable to individual backed up objects Should have the ability to retroactively update changes to data management policies that will then be applied to the data that is already being backed up or archived

1.1.3.4 NAS Gateway Offered storage solution should be configured with a NAS gateway capable of file serving for all OS platforms including but not limited to IBM AIX, HP-UX, Linux, Microsoft Windows, SUN Solaris, etc. The NAS system should support heterogeneous multi-host connectivity. The system should facilitate connectivity to various flavors of Operating Systems (OS), including but not limited to IBM AIX, HP-UX, Linux, Microsoft Windows, SUN Solaris, etc. Offered NAS shall support multiple protocols like NFS, CIFS, FTP, etc. Offered NAS shall support Active-Active for high availability, load balancing and shall be supplied with two nodes and should be scalable to multiple nodes Internal OS of NAS shall be protected by using hardware based RAID by putting the operating system on the SAN Offered NAS shall support a large file system up to 16TB. Offered NAS shall support minimum of 128 file systems. Should support Automatic Volume Management and should support automatic file system extension for file systems The offered NAS Gateway controller should be configured with 2 numbers of Storage FC per node that can connect to the offered storage array. Four Full duplex 10/100/1000 Mbps Ethernet connections per node. Capacity offered on the NAS should be from the storage array proposed, and should be dynamically expandable in capacity on the storage array itself. Offered NAS cluster solution shall maintain data and cache coherency at all times even in the event of single or multiple node failures. The NAS system should have the capability to support single copy data sharing between multiple servers running, using industry standard protocols like CIFS, NFS etc.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 20 of 99

Volume II Technical and Functional Specifications

The NAS system should support appropriate measures of locking to protect against corruption when a file is shared between multiple servers. Every Node of NAS subsystem shall be supplied with At-least Dual CPU, supporting 4 GB Cache NAS gateway should be appliance based and with Linux / Unix / Real Time Operating System GUI / Web based / CLI Comprehensive NAS Management/ Administration Software All associated cables, connectors, adapters etc should be supplied

1.1.3.5 Internet Router Hardware Architecture (19 Rack mountable) o o Should support IP, MPLS etc. The modules, power supply should have support for hot swappable functionality. o o o Modular Chassis Router performance should be minimum of 400 Kpps Power supply for 230 V AC 50 Hz with Redundant power supply

Interface / Slots o o o Ethernet Port 2 - 10/100/1000 Mbps Should support minimum 6 service slots Shall support variety of interfaces like E3, Ch-E1, E1 G703 Interfaces as per ITU-T Standard. o o Serial V.35 Interfaces 4 ports Console port 1 numbers

Security o o GRE and IP Sec 3DES/AES VPN for configuration of VPN tunnels. Support for IPSEC Site-to-Site and Remote Access VPNs. Should provide a hardware assisted IPSec 3DES encryption performance up to 150Mbps. o o o o NAT, PAT Access control - Multilevel Support ACLs to provide supervision and control. Multiple Privilege Levels for managing & monitoring

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 21 of 99

Volume II Technical and Functional Specifications

o o o

Support for Remote Authentication User Service (RADIUS) and AAA Support for Standard Access Lists to provide supervision and control. Controlled SNMP Access using ACL on router to ensure SNMP access only to identified NMS/EMS

o o

PPP CHAP support. PAP (optional) DoS prevention through TCP Intercept & DDoS protection

Routing Protocols o o o o Static Routes RIPv1, RIPv2, RIPng OSPFv2 and v3. Route redistribution between any of the above protocols

Protocols o o o o o o o PPP, Multi-link PPP Load Balancing Protocol Support for URL Filtering IPv4, IPv6 MPLS L2 & L3 VRRP / HSRP Shall support IPv6 features: DHCPv6, IPv6 QoS, IPv6 Multicast support, Multicast VPN, PIM SSM (Source Specific Multicast), IPv6 PIMv2 Sparse Mode, IPv6 PIMv2 Source-Specific Multicast o MPLS Features: MPLS VPN, MPLS (mVPN (Multicast VPN), Carrier Supporting Carrier (CsC), DiffServ Tunnel Modes, MPLS TE, DiffServAware TE, Inter-AS VPNs

Congestion o o o Random Early Detection Weighted Fair Queuing Priority Queuing

IP Multicasting o IGMPv1&v2, PIM-SM, PIM-DM or MOSPF

Management o Accessibility using Telnet, SSH, Console access.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 22 of 99

Volume II Technical and Functional Specifications

o o

Software upgrades using FTP, TFTP, etc. SNMP Support for v1, v2 , v3

Debug & Diagnostics o o o Display of input and output error status on all interfaces Display of Dynamic ARP table Display of physical layer line status signals like DCD, DSR, DTR, RTS, CTS on all interfaces o Should have support for SLA monitoring for metrics like delay, latency, jitter, packet loss, and MOS o Trace-route, Ping, extended PING

1.1.3.6 Edge Switches Edge switch shall be implemented in the DMZ and shall be connected to the Core LAN switch and the router. Rack Mountable o Mountable in standard 42U rack

Chassis based with minimum 7 payload slots Chassis with Redundant Power supply with support for hot swappable modules

At least one console port for CLI based configuration 300 Gbps backplane capacity 250 Mpps forwarding rate 4 Nos. GBIC Slots 96 ports, 10 / 100 / 1000 Base auto-sensing IEEE 802.3ad support required Link Aggregation Control Protocol (LACP) to aggregate 4x1Gbps i.e. 4Gbps uplink to the Core LAN Switch.

Should support stateful failover and hitless software upgrade Should be loaded with dual management modules. All the relevant hardware should be loaded to achieve the required performance.

Should provide a mechanism to manage the traffic flow of control plane packets to protect the control plane against reconnaissance and Denial of Service (DoS) attacks

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 23 of 99

Volume II Technical and Functional Specifications

Should support IPV6 in hardware. Should support port mirroring i.e. mirror ports from and to any other switch in the network

Should support RIPv2, OSPF, BGP Management o SSH v2,SNMP v1/v2c/v3, IGMP, RMON I, VLANs, GUI, Web based interface o Compatibility with network management with auto discovery & management. o o Manageability on per port basis. Per-port broadcast, multicast, unicast storm control to prevent faulty end stations from degrading overall systems performance.

Security o o o 802.1x support RADIUS support MAC address based port level filtering support

Quality of Service: The switches should support the aggregate QoS model by enabling classification, policing/metering & marking functions on a per-port basis at ingress and queuing/scheduling function at egress o The switches should support QoS classification of incoming packets for QoS flows based on Layer 2, Layer 3, and Layer 4 fields. o The switches should support identification of traffic based on Layer 3 ToS field DSCP values.

Support for rate limiting with granularity of traffic flows. TFTP & NTP support Compliant to Standards such as IEEE 802.1x, 802.1w, 802.1s, 802.3x, 802.1D, 802.1p, 802.1Q, 802.3ad, 802.3u, 802.3ab, 802.3z

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 24 of 99

Volume II Technical and Functional Specifications

1.1.3.7 Aggregation Core Switches Hardware Architecture (19 Rack mountable) o Redundant Supervisor / Switching / Routing engine. All the relevant hardware should be loaded to achieve the required switching & routing performance. Redundancy should be on supervisor on different switching fabric o o o

Internal Redundant Power Supply Power supply 230 Volt 50Hz input Modular Chassis

Interfaces / Slots o o o o Minimum 08 Slots 4 x 48 Ports GE (10/100/1000Mbps) and upgradeable 1 x 24 Ports populated with 4 Nos. of LX SFP and 20 Nos. of SX SFP All service cards must be hot swappable

Performance High back plane speed of 700 Gbps switching fabric

Switch should be loaded with required hardware to provide forwarding rate of 300 Mpps Indicators o Per-port status LEDs: link integrity, disabled, activity, speed, and fullduplex indications o System-status LEDs: system, RPS, and bandwidth-utilization indications L2 Features o o o o IEEE 802.1Q VLAN encapsulation 802.1s 802.1w IGMP snooping v1 and v2

IP Routing Protocols o o o o o Static Routing OSPF v2 and OSPF v3 RIP v1, RIP v2, RIPng HSRP /VRRP IPv6 support

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 25 of 99

Volume II Technical and Functional Specifications

Security o o
o

Standard and extended ACLs on all ports AAA and RADIUS authentication Secure Shell (SSH) Protocol

Manageability & Up gradation o o o o Console port for administration & management Support SNMP v1, v2 Support management using CLI, GUI using Web interface Support FTP/TFTP for upgrading the operating System

Standards o o o o o o o o o o o o o IEEE 802.1s IEEE 802.1w IEEE 802.1x IEEE 802.3ad IEEE 802.3af IEEE 802.3x full duplex on 10BASE-T, 100BASE-TX, and 1000BASET ports IEEE 802.1D Spanning Tree Protocol IEEE 802.1p CoS Prioritization IEEE 802.1Q VLAN IEEE 802.3 10BASE-T specification IEEE 802.3u 100BASE-TX specification IEEE 802.3ab 1000BASE-T specification IEEE 802.3z 1000BASE-X specification

1.1.3.8 External Firewall

Physical attributes o o o Should be mountable on 19 Rack Modular Chassis Internal Redundant power supply

Interfaces o o 4 x GE, upgradeable to 8 x GE Console Port 1 number

Memory o Minimum RAM 1024 MB, Upgradeable to 2048 MB RAM

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 26 of 99

Volume II Technical and Functional Specifications

o o o o

Flash 256 MB Upgradeable to Flash 512 MB Cleartext throughput: minimum 6 Gbps Concurrent connections: up to 2,000,000 Simultaneous VPN tunnels: 2000

Routing Protocols o o o Static Routes RIPv1, RIPv2 OSPF

Protocols o o o o o o o o TCP/IP, PPTP RTP IP Sec, GRE, DES/3DES/AES PPPoE, EAP-TLS, RTP FTP, HTTP, HTTPS SNMP, SMTP DHCP, DNS Support for IPv6

Other support o 802.1Q, NAT, PAT, IP Multicast support, Remote Access VPN, Time based Access control lists, URL Filtering, support VLAN, Layer 2 Firewall, Virtual Firewall, Radius/ TACACS

QoS o QoS features like traffic prioritization, differentiated services,

committed access rate. Should support for QoS features for defining the QoS policies.

Management o o Console, Telnet, SSHv2, Browser based configuration SNMPv1, SNMPv2

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 27 of 99

Volume II Technical and Functional Specifications

1.1.3.9 Internal Firewall

Physical attributes o o o Should be mountable on 19 Rack Modular Chassis Internal Redundant power supply

Interfaces o o 4 x GE, upgradeable to 8 x GE Console Port 1 number

Memory o o o o o Minimum RAM 1024 MB, Upgradeable to 2048 MB RAM Flash 256 MB Upgradeable to Flash 512 MB Cleartext throughput: minimum 4 Gbps Concurrent connections: up to 1,000,000 Simultaneous VPN tunnels: 2000

Routing Protocols o o o Static Routes RIPv1, RIPv2 OSPF

Protocols o o o o o o o o TCP/IP, PPTP RTP IPSec, GRE, DES/3DES/AES PPPoE, EAP-TLS, RTP FTP, HTTP, HTTPS SNMP, SMTP DHCP, DNS Support for IPv6

Other support o 802.1Q, NAT, PAT, IP Multicast support, Remote Access VPN, Time based Access control lists, URL Filtering, support VLAN, Layer 2 Firewall, Virtual Firewall, Radius/ TACACS

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 28 of 99

Volume II Technical and Functional Specifications

QoS o QoS features like traffic prioritization, differentiated services,

committed access rate. Should support for QoS features for defining the QoS policies.

Management o o Console, Telnet, SSHv2, Browser based configuration SNMPv1, SNMPv2

1.1.3.10 Intrusion Prevention System

Features o o Layer 7 Throughput of 2 Gigabit scalable to 3 Gigabit Minimum 4 Numbers of Gigabit segments scalable to 7 numbers of Gigabit segments o Should support fail-open to four Gigabit segments in case of hardware / software or power supply failure o o Should protect against DoS/ DDoS / SYN-flood/ TCP-flood /UDP-flood Must have Zero-day protection against DoS/DDoS and worm attacks based on traffic behavior. Also it should mitigate Zero day http floods and brute force attack & vulnerability scanning attempts based on traffic behavior analysis o Capable of applying the security policies based on VLAN ID, Source/Destination subnets o Flexibility to create new policies or modify existing policies in real time

Action on detection o o o Block attacks in real time, Drop Attack Packets, Packet Logging Reset Connections, Action per Attack Support for detailed intrusion alarms

Stateful Operation o o o o o TCP Reassembly IP Defragment Bi-directional Inspection Forensic Data Collection Access Lists

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 29 of 99

Volume II Technical and Functional Specifications

Signature Detection o o Vendors Signature Database minimum 2000 Should support Automatic signature synchronization from OEM database server

Extensive protocol monitoring: should support monitoring of protocols such as TCP/IP, ICMP, FTP, UDP, SMTP, HTTP, SNMP, DNS, RPC, NetBIOS, Telnet etc

Should also have the ability to monitor MPLS and 802.1Q (trunked) traffic Alerting SNMP, SMTP support o Log File, Syslog support

Operations o o o Should support 24/7 Security Update Service Should support automatic Real Time signature update Should support Provision to add static own attack signatures

Reporting o o System should provide centralized reporting and management. System should provide comprehensive security event reporting

Management o Console, SSH, Telnet, HTTPS, HTTP, SNMP v1, v2

1.1.3.11 Host Based Intrusion Prevention System (HIPS) HIPS should perform log analysis, integrity checking, root kit detection, timebased alerting and active response. It should help to detect attacks, software misuse, policy violations and other forms of inappropriate activities. HIPS should be able to monitor multiple systems, with one system being the HIPS server and the others the HIPS agents that report back to the server. Must have Zero-day protection against DoS / DDoS and worm attacks based on traffic behavior. Also it should mitigate Zero day http floods and brute force attack & vulnerability scanning attempts based on traffic behavior analysis HIPS should be supported on the following platforms: o MS Windows

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 30 of 99

Volume II Technical and Functional Specifications

o o o

Solaris (SPARC) SUSE Linux Server Red Hat Enterprise Linux / HP-UX / AIX

Minimum Features of Host-based intrusion Prevention: o o o o o o o Time to Time Signature updates Monitoring and prevention from Intrusion attack Verifies success or failure of an server Monitors specific system Detects attacks that network-based systems miss Well-suited for encrypted and switched environments Near-real-time detection and response

1.1.3.12 Workstation for Monitoring o o Desktop with Dust Cover CPU: Intel Pentium Core 2 Duo E8600 (3.3 GHz, 6 MB L2 cache) / AMD Phenom-II X4-940 (2.4 GHz, 6 MB L3 Cache) o o Motherboard: Intel (Intel G33 chipset or better )/ AMD equivalent Bus Architecture: Integrated onboard graphics, Two PCI, One PCI Express 1/4, One PCI Express 16 slots, Integrated Audio o o o o o 2 GB DDR2 SDRAM, 1 DIMM slot should be free. HDD: Min 160 GB SATA II 7200 RPM HDD & Pre-failure alert USB or PS/2 104 Keys keyboard USB or PS/2 Two button scroll optical mouse with pad Ports are 1 Serial, 1 Parallel, 4 USB 2.0 (min. 2 at front), VGA, Microphone, Headphone. o o 10/100/1000 Mbps Network card. Pre loaded Windows XP Professional or latest licensed software with latest updates and Restore/ Recovery CD/ Self Mechanism o 17 TFT Monitor with MPR II/TCO 03 certification

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 31 of 99

Volume II Technical and Functional Specifications

1.1.3.13 KVM Keyboard, Video Display Unit and Mouse Unit (KVM) and/or other Control Devices/PCs may be used for the IT Infrastructure Management for which the necessary consoles/devices shall be placed by SDA in the location earmarked. The KVM unit should provide the following functionalities: o o o o o o o o o It should be rack-mountable. It should have a minimum of 8 ports scalable upto 24 ports. It should support local user port for rack access. It should support both USB and PS/2 connections. It should be capable of storing username and profiles. It should support high resolution upto 1600 x 1200 It should be capable to auto scan servers It should work on CAT 6 / CAT 7 cables. Rack Mountable LCD Monitor with In-built Keyboard & Mouse 1 U Rack Mount Display size: 15 inches diagonal Contrast Ratio: 700:1 Display colors: 16 million Resolution: SXGA 1280 x 1024 Brightness: 300 nit Compatible to both PS/2 and USB based inputs

1.1.3.14 IP KVM Switches o o o It should have a minimum of 16 ports scalable & upgradeable. It should support 2 remote users and 1 user at the rack Remote Access appliance should have the following functionalities It should take control of servers at BIOS Level It should facilitate both in-band & out-of band access It should be able to integrate with power strips, so as to be able to reset power of remote device at port level. Remote access of both Servers and serial devices such as routers (through same or different appliances). It should have facility to integrate with secure management device

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 32 of 99

Volume II Technical and Functional Specifications

Gigabit Ethernet ports. Virtual Media Support of multiple media including 'ISO image' files

o o o o o o

Dual (redundant) Power supply Dual Ethernet with Failover PC selection On screen Display menu hot key 19 inch Rack mountable design KVM access over IP Browser based Management available at both remote and local ( Supported Browsers = Internet Explorer for MS-Windows, Firefox for MS-Windows and Linux )

o o o

Support for resolution of 1600*1200 or above Single window access to all equipment. Equipment access logs and event history and send email alerts based on logs details as triggers

o o

Logging should be centralizable in one Syslog server. Absolute Mouse Synchronization.

IP KVM Control Center o The management appliance should provide unified, secure access to KVM, serial and power ports of Data Centre devices via a Web browser. o It should provide policy and security management of users and devices connected to KVM. o o It should be able to assign specific node access to a specific user. It should allow the administrators to access, manage and view all equipment, manage users and access permissions from a single remote device.
o

It should support Virtual Media Deny, View and Control access policies.

Should be able to create unlimited user and minimum 10 concurrent users should be allowed.

It should log user activity (login/logout, connect/disconnect) and configuration changes at both Appliance and managed devices, and status changes of the connected appliances. All of the above can be

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 33 of 99

Volume II Technical and Functional Specifications

forwarded to a network management system or enterprise notification system via SNMP or Syslog. o o o Flexible session time-outs "Strong" user name and password authentication Network Interfaces allows: TCP/IP, HTTP/HTTPS, SSL, DNS, LDAP/LDAPS o o Auto-discovery with device-availability status, and alarms An array of flexible logging and reporting options with audit trails for diagnostics and troubleshooting o o View and manage active user sessions and active ports in real time OS Support: Windows 2000 Server/2003 Server/XP, Windows Vista, RHEL AS 4.0 and Fedora Core 4

1.1.3.15 Cabling CAT 6 / fiber LAN cables should be laid upto the rack level in the Data Centre. Dedicated raceways / cable-trays should be used for laying LAN. Along with LAN cabling, cables for Storage Area Network (SAN) upto the racks in the Data Centre should also be implemented. Cabling for KVM switches on the racks should also be done. Additional cabling requirements on an on-going basis will also need to be catered. All the cable raceways shall be adequately grounded and fully concealed with covers. The cables should be appropriately marked and labeled. There should be enough space between data and power cabling and there should not be any cross wiring of the two, in order to avoid any interference, or corruption of data

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 34 of 99

Volume II Technical and Functional Specifications

State Data Center LAN Cabling

DC Layout
Front

Cold Area
Row 1

Row 2
Front

Cold Area
Front

Row 3

Legend Row 4
Front

2X 2 Floor Box

Cold Area
Front

Open Network Rack 600mmX1000mm Server Rack

Row 5

Rack Placement Details o Total 50 Server Racks and 9 Network Racks will be placed in the Data Center. o Server Rack Size will be 600mm X1000mm o Network Rack - 2 / 4 Post Open Rack with vertical Wire Managers o Each Row will have minimum 1 Network Rack to take care of LAN Cabling requirement for respective Row. o 1st Rack row will have additional Network Rack to Place Core Switch / WAN Equipments. Floor Box Details o Between 2 Server Racks it would have 1 Raised Floor Enclosure. o Raised Floor Enclosures to be placed under False Flooring. o Raised Floor Enclosure should be able to fix under one 2X 2 Floor Tiles. o Raised Floor Enclosure should have provision to fix minimum 4 Nos. of 24 Port Jack Panels

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 35 of 99

Volume II Technical and Functional Specifications

Connectivity

Copper Connectivity Details o Every Server rack will have 24 port Jack Panels and should be fixed under the raised floor Enclosures. o 24 Runs of UTP cables to be laid to Each Server Rack from respective Network rack in the same row. o Servers will be connected by CAT6 RJ 45 RJ 45 Patch cords, directly from floor box Jack Panels. o Network Racks will have Jack Panels and Switches. Interconnect Patching between Switch and Jack Panel to be done by CAT 6 RJ 45 RJ45 Patch cords. Fiber Connectivity Details o Connectivity between core distribution access switches will be on direct lengthy OM3 Fiber duplex patch cords.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 36 of 99

Volume II Technical and Functional Specifications

1.1.3.16 UTP Cable Type o o UTP, Cat 6, ANSI/TIA/EIA 568-B.2-1 The cable jacket shall comply with Article 800 NEC for use as a nonplenum cable. The 4 pair UTP cable shall be UL and c (UL) Listed Type CM. Conductors o 4 pair 23 / 24 AWG Copper with pair separator for uniform characteristic impedance Insulation o o Polyethylene/Polyolefin Thickness 0.22 0.03mm

Operating temperature o -20 to +60 Deg. C Jacket o Flame Retardant PVC Approvals o UL Listed Frequency tested up to o 100 MHz>=250 MHz Delay Skew o 25ns-45ns / 100m Max. Impedance o 100 6 Performance characteristics to be provided along with bid o Attenuation, Pair-to-pair and Powersum NEXT, ELFEXT and PS ELFEXT, Return Loss and Delay skew tested for 100m channel as well as 90m Permanent Link

1.1.3.17 Cable Laying Cabling o o o Structured Cabling as per industry Standards UL * R certified for complete channel for both Fibre and UTP (CAT 5e/ CAT6) cables. 20/ 25 years standard performance warranty should be given on passive components

Documentation & Lay-outs o UTP or OFC Cable route, with detailed diagram and plan for laying of UTP and OFC for approval. o Termination of cabling component, UTP cable and OFC with labels & marking as per approved labeling plan & documentation.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 37 of 99

Volume II Technical and Functional Specifications

Documentation for all POPs (Hard and Soft Copy) to be maintained for entire 5 years of Projects.

Conduits and Channels o PVC pipe or Casing type Should be 1 diameter, with ISI mark. At least 4 cable can laid in one casing Using clamp or gulli channel should be fix on wall and distance between two gulli or clamp not more then 6 inches. o GI pipe Should be 2 inch diameter class B standard At least 2 cable can laid in one pipe only UTP cable laying o Should follow approved plan. OFC laying on wall or under ground o OFC laying on wall or underground in GI pipe, vendor should follow as approved plan. Jack Panel o Should be a 24 port modular / discrete patch panel. o Ports should be individually replaceable and consistent port-to-port performance o Should confirm or exceed TIA/EIA-568-B.2-1 and IEC 60603-7-4 standards requirements for CAT 6 o Metallic high strength and 1U height o Should be UL Listed IO o Should confirm or exceed TIA/EIA-568-B.2-1 and IEC 60603-7-4 standards requirements for CAT 6 o Durability: 750 mating cycles on modular jack and 200 termination cycles on 110 block Multimode OM3 Fiber Patch Chords o Patch Cords 550 metres channel @ 10 Gb/s o The fiber-optic patch cord shall be configurable with standard LC, SC, terminations, and shall be available in either 1.6 mm or 3.0 mm duplex zip cord. o The 1.6 mm cordage shall exceed the requirements for larger diameter cordage and allows at least twice as many fibers to be installed in a cabinet. o The duplex cordage shall be 1.6 mm by 3.5 mm and have two single fiber cords joined together with a web. o The connector shall have a pull-proof design that helps prevent accidental disconnects and helps to assure optimal performance of equipment.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 38 of 99

Volume II Technical and Functional Specifications

All fibers shall be Differential Mode Delay (DMD) tested by using a highresolution test bench that exceeds the FOTP-220 standards and shall be independently certified by UL.

1.1.3.18 Mounting Cords Length o 10, 20, 30 and 40 feet Conductor o 23 / 24 AWG 7 / 32, stranded copper Cable Type o UTP CAT 6 ANSI/TIA/EIA 568-B.2-1 Plug Protection o Anti-snag feature Warranty o 20/ 25-year component warranty Cable Type o Cat 6 Terminals o Phosphor Bronze with gold plating Jacket o PVC o The cable jacket shall comply with Article 800 NEC for use as a nonplenum cable. The 4 pair UTP cable shall be UL and c (UL) Listed Type CM (non-plenum). End point connector o Factory fitted RJ-45 plugs at both ends Insulation o Flame Retardant

1.1.3.19 Server Racks 42U 19 42U racks shall be used in the Data Centre for hosting the department applications of Government of Andhra Pradesh. All the racks should be mounted on the floor with castor wheels with brakes (set of 4 per rack) Floor Standing Server Rack - 42U with Heavy Duty Extruded Aluminium Frame for rigidity. Top cover with FHU provision. Top & Bottom cover with cable entry gland plates. Heavy Duty Top and Bottom frame of MS. Two pairs of 19" mounting angles with 'U' marking. Depth support channels - 3 pairs. with a overall weight carrying Capacity of 500Kgs. The racks should conform to EIA-310 Standard for Cabinets, Racks, Panels and Associated Equipment and accommodate industry standard 19 rack mount equipment.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 39 of 99

Volume II Technical and Functional Specifications

Front and Back doors should be perforated with atleast 63% or higher perforations. All racks should be OEM racks with Adjustable mounting depth, Multioperator component compatibility, Numbered U positions, Powder coat paint finish and Protective grounding provisions. All racks should have mounting hardware 2 Packs, Blanking Panel (1) varying from 4 U to 5 U size Keyboard Tray with BB Slides (Rotary Type) (1 no. per Rack) Stationery Shelf 627mm Network (2 sets per Rack) All racks must be lockable on all sides with unique key for each rack Racks should be compatible with floor-throw as well as top-throw data centre cooling systems. Racks should have Rear Cable Management channels, Roof and base cable access Wire managers o Two vertical and four horizontal Power distribution Unit o Power Distribution Unit - Vertically Mounted, 32AMPs with 25 Power Outputs. (20 Power outs of IEC 320 C13 Sockets & 5 Power outs of 5/13Amp Sockets), Electronically controlled circuits for Surge & Spike protection, LED readout for the total current being drawn from the channel, 32AMPS MCB, 6 KVAC isolated input to Ground & Output to Ground (1 No per Rack) Door o The racks must have steel (solid / grill / mesh) front / rear doors and side panels. Racks should NOT have glass doors / panels. o Both the front and rear doors should be designed with quick release hinges allowing for quick and easy detachment without the use of tools.

Fan trays o Fan 90CFM 230V AC, 4" dia (4 Nos. per Rack) o Fan Housing Unit 4 Fan Position (Top Mounted) (1 no. per Rack) Monitored - Thermostat based - The Fans should switch on based on the Temperature within the rack. The temperature setting should be factory settable. This unit should also include - humidity & temperature sensor Depth o 1000 mm Metal o Aluminium extruded profile

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 40 of 99

Volume II Technical and Functional Specifications

Side panel o Detachable side panels (set of 2 per Rack) Width o 19 equipment mounting, extra width is recommended for managing voluminous cables

1.1.3.20 Network Racks Should be available in 2-Post Configurations Option of 84 or 96 height Should be available with an option of Rail Widths: 3, 6, 12 (2-Post) EIA-310-E Compliant UL Listed, Certification - Information Technology and Communications equipment Load Capacity: 1000 lb (2 and 4-Post Al) EIA Standard Hole Pattern: 12-24 Threads @ 5/8" (127mm), 1/2" (25.4mm) centers Material: Al: 6061-T6 Aluminum Extrusion (3 Rail), Al: 6061-T6 0.125 Thick, (6 and 12 Rail), Steel: 14 Gauge (0.075 Thick), CRS Finish: Durable black epoxy powder-coat Easily assembled, hardware included Cable Management o Ergonomically designed and aesthetically pleasing, Lightweight, but sturdy o o Should have dual hinge latching door & can be opened right or left. Cable fingers spaced at 1RMU increments for exact alignment with EIA standard o o o Rack spacing Cable fingers support up to 48 cables per RMU Should be available in 6, 8, 10 & 12 vertical trough widths both single sided or double sided. o In case of Horizontal cable management the cover should hinges up or down and locks into position with cylindrical finger ends for easy snap on installation o Horizontal cable management troughs should be available in 1, 2 & 3 RMU o Open back on 2U and 3U horizontal troughs for easy pass through of cables
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 41 of 99

Volume II Technical and Functional Specifications

o o

Easy one point removal and installation process for door Handle should be recessed to eliminate snag potential for clothes and arms

Should have C Channel bracket allowing for easy access to the cable trough

Provision for Tool-less installation of Cable Spool

1.1.3.21 Anti Virus Software Should restrict e-mail bound Virus attacks in real time without compromising performance of the system Should be capable of providing multiple layers of defense Should have installation support on gateway / mailing server Should be capable of detecting and cleaning virus infected attachments as well Should support scanning for ZIP, RAR compressed files, and TAR archive files Should support online upgrade, where by most product upgrades and patches can be performed without bringing messaging server off-line. Should use multiple scan engines during the scanning process Should support in-memory scanning so as to minimize Disk IO Should support Multi-threaded scanning Should support scanning of a single mailbox or a one off scan. Should support scanning by file type for attachments Should support scanning of nested compressed files Should be capable of specifying the logic with which scan engines are applied; such as the most recently updated scan engine should scan all emails etc Should support heuristic scanning to allow rule-based detection of unknown viruses Updates to the scan engines should be automated and should not require manual intervention All binaries from the vendor that are downloaded and distributed must be signed and the signature verified during runtime for enhanced security Updates should not cause queuing or rejection of email Updates should be capable of being rolled back in case required Should support content filtering based on sender or domain filtering Should provide content filtering for message body and subject line, blocking messages that contain keywords for inappropriate content

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 42 of 99

Volume II Technical and Functional Specifications

File filtering should be supported by the proposed solution; file filtering should be based on true file type. Common solution for anti-spyware and anti-virus infections; and anti-virus and anti-spyware solution should have a common web based management console. Should support various types of reporting formats such as CSV, HTML and text files Should be capable of being managed by a central management station Should support client lockdown feature for preventing desktop users from changing real-time settings Should support insertion of disclaimers to message bodies Product shall be provided with all the required licenses, software as applicable to meet all the above mentioned specification and hence the proposed solution. The bidder has to account for the following client antivirus software : o for all servers being installed in the SDC o for all other computing devices such as desktops, laptops etc. The bidder would ensure client antivirus subscription valid for the period of project, therefore, no. of client antivirus software/solution, there subscription should work for the project period with out any expiration of services.

1.1.3.22 Directory Services Should be compliant with LDAP v3 Support for integrated LDAP compliant directory services to record information for users and system resources Should provide integrated authentication mechanism across operating system, messaging services Should provide directory services for ease of management and administration / replication Should provide support for Group policies and software restriction policies Should support security features, such as Kerberos, Smart Cards, Public Key Infrastructure (PKI), etc Should provide support for X.500 naming standards Should support Kerberos for logon and authentication Should support that password reset capabilities for a given group or groups of users can be delegated to any nominated user Should support that user account creation/deletion rights within a group or groups can be delegated to any nominated user Should support directory services integrated DNS zones for ease of management and administration/replication.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 43 of 99

Volume II Technical and Functional Specifications

1.1.3.23 Security The Solution implemented for SDC Project has to follow a well-defined security policy. It should provide a framework that ensures the availability, integrity, and confidentiality of information infrastructure. The solution shall accomplish the laid objectives by providing identification, authentication, authorization/access control, administration and audit by incorporating a security architecture which is built upon a foundation of security services, relevant technologies, best practices, guidelines, and standards. The security services used to protect the information infrastructure shall include Identification The process of distinguishing one user from all others Authentication The process of verifying the identity of a user Authorization and Access Control The means of establishing and enforcing user rights and privileges Administration The process of establishing, managing, and maintaining security Audit The process of monitoring the identification, authentication, authorization and access control, and administration to determine if proper security has been established and maintained.

It is important to note that the technologies chosen are in flux, where the services and goals remain constant. It is exigent that as new technologies emerge or existing ones mature that they be re-evaluated in light of the security principles and goals outlined in this document. These security services shall be delivered and that the technologies are implemented in conjunction with a set of best practices guidelines and industry standards. Wherever applicable the following principles must be applied to the security architecture: All passwords must expire after a specified number of days or sooner at users discretion. Reuse of passwords must be separated by a pre-determined number of alternate passwords, not to be less than 10 User IDs not used within a specified period of time must be automatically locked out (length of lock out period to vary between existing and new user IDs) All the systems should run most up-to-date anti-virus software to avoid malicious programs to cause damage to the systems The software solution must ensure that users create strong passwords. The application should allow Role Based Security Access to the application pages and features. The user should belong to a role based on functional role in the system and should have access only to execute the stated operations.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 44 of 99

Volume II Technical and Functional Specifications

The application should be configurable to provide role based security The user profile variables like user id, session id, operational status has to be persisted in each client session and server should be able to track the user at any instance. Each access to the server has to be logged and should be based on digital certificates as and when procured by the user department. The data transfer to and from the server should be secure to hacking and unauthorized access. The application should use a protocol to transfer the data with 128 bit encryption which could only be readable by the application deployed for the SDC Project. The User groups with appropriate roles have to be classified based on the privileges that are sought to be granted and users need to be assigned to the roles as appropriate. The supervisor has to be given appropriate privileges to assign people to roles. Access to all application modules and related functionality will be based on these privileges.

Digital certificates for all servers, data encryption protocols to be supported (SSL). Assessing various touch points with external systems/networks and associated risks and risk mitigation measures should provided in the proposed solution All browser based access for the transactions performed from outside the integrated projects Security boundary must use Secure Socket Layer. All agencies external to the project will need to access the system via security firewall(s) which will have IPSEC enabled network. Information stored in the databases must be protected from unauthorized access. Any access to Database should only be via application authorization. Any administrative access to Database should only be via application authorization which should follow authentication of personnel by a suitable mechanism such as use of single-finger biometric technology. Backup/Restore: Backups should be secured against malicious use by unintended users. o The proposed Security architecture should provide creation and management of digital certificates and PKI including Capability to create and manage a Certification Authority o Issue and revoke certificates/keys and maintain appropriate trust lists o Use of digital certificates for 128-bit encryption and digital signatures o Location and Security Matrix

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 45 of 99

Volume II Technical and Functional Specifications

1.1.3.24 Compliance to ISO27001 Standards of Security The technology solution should comply with ISO27001 standards and the DCO has to get the certificate of the same within three quarters from the date of start of successful operations of the State Data Centre. Subsequently periodic surveillance audits must be carried out. The cost incurred for obtaining and maintaining the certification shall be borne by the DCO. Security certification process shall include Audit of Network, Server and Application Security mechanisms. Assessment of authentication mechanism provided in the application /components / Modules Assessment of data encryption mechanism. Assessment of data access privileges, retention periods and archival mechanisms. Final output of this process would be a comprehensive audit report including all the Network, Server and Application security features incorporated in the project. Manageability Requirements of the project will be tested and certified for the following: o Remote Monitoring of Status and Statistics of all high-level components o Management capability to start/ stop/ restart services & systems. o Auto discovery of all components manageable through SNMP o Auto discovery of all other system components. o Ability to track changes in configurations of the system components to help track Service/ System disruptions. Final output of this process would be a manageability compliance document for the system deployed.

1.1.3.25 Specifications for Data Center Design & Implementation This section details the technical specifications, mandatory compliance of the IA to these specifications in implementation of the State Data Center for Andhra Pradesh. The approximate space for State Data Center is about 4000 Sq.ft. However the vendor shall also provide the cost of data center preparation per Sq.ft in the commercial bid. 1. IT Equipment 2. Civil 3. Electrical 4. CCTV 5. UPS & Battery System 6. Air Conditioning
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 46 of 99

Volume II Technical and Functional Specifications

7. Building Management System Components 8. Fire/Smoke Detection and suppression system 9. DG Sets 1.1.3.26 Commitment from Manufacturers The Agency shall submit letters of commitment issued by the manufacturer(s) confirming minimum Five-year support of the system offered and shall guarantee supply of spares for the equipment service life starting from the date of acceptance.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 47 of 99

Volume II Technical and Functional Specifications

SECTION II Physical Infrastructure

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 48 of 99

Volume II Technical and Functional Specifications

2 SDC Architecture Physical Infrastructure


2.1 Layout of the Data Centre
In the schematic above, entire SDC area is logically divided in Zones based MIT guidelines. Each of these zones are having different objective described further in this section. The respective area of each Zone would actually vary, primarily on the basis of number of applications and Size of the State.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 49 of 99

Volume II Technical and Functional Specifications

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 51 of 99

Volume II Technical and Functional Specifications

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 52 of 99

Volume II Technical and Functional Specifications

a. Zone A The Server Farm area of around 2548 sq.ft. would host servers, Server racks, storage racks and Networking component etc. The DC shall be built to cater an average load of 6 KVA per rack. b. Zone B Comprises of NOC & Helpdesk Area, Reception Area, BMS Control Room, Communication Room, Staging Area, Store Room, Project Manager Room, Meeting Room 1 and Meeting Room 2 etc. c. Zone C Comprises of UPS & Electrical Room, Batteries Room etc. A detailed description of key areas of SDC is given below: Server Farm Area

The server farm area of 2548 sq.ft. within the SDC will host / co-locate State Government Intranet Web Servers, and various Departmental Application Servers including the Database Servers. These servers may be Low end to High-end depending upon the applications hosted on them. These servers may be online or only for repository purpose. The applications which are running on the centralcomputing servers will have load balancing and high availability features. This area will contain all the networking components from routers, switches to passive components. The data communication component area will terminate SWAN connections, LAN Connections and host a network monitoring station for LAN & WAN. All the Data Center LAN connections will be provided through switches placed in this area. This area will host the Security components. The security architecture will provide controlled access to the web and database servers from Internet and other networks. This would be multi-layer architecture with two layers of firewall separating the Internet, web, and database/application and Intranet zones. NOC and Helpdesk Room

This room with an area of approx. 430 sq.ft. will have all the necessary arrangements for the Database, Systems, Application and other Server Administrators. Per shift it is expected to employ one administrator for each of the categories. SDC shift operators taking care of daily operational activities of SDC will use this area. There will be one Data Center In charge per shift sitting in this area along with shift operators (one each for specific activities like backup, daily Data Center administration / operations etc.) Staging and Storage Area

The staging area is around 216 sq.ft. and store room of around 112 sq.ft. will be used for storing all backed up Digital Linear Tapes (DLT). This area will house a 3 x 3 x 6
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 53 of 99

Volume II Technical and Functional Specifications

Feet fireproof cabinet for storing roughly 350 tapes. It is also highly recommended to have an offsite back up location at some suitable place. The offsite backup place should also have a fire and heat proof safe cabinet. UPS and Electrical Room

This area with 608 sq. ft. shall house all the Un-Interrupted Power Supply Units, Main Power Distribution Units (PDU) and Sub Distribution Units to feed the components such as PAC, UPS, lighting, fixtures etc. It is recommended to install transformer based PDUs in the State Data Centre. Batteries Room

This area with 240 sq.ft. shall house all the Batteries accompanying the UPS components. As these components generate good amount of radiation it is advised to house these components in a room separate from main SDC room. BMS Control Room

The Building Management System (BMS) room with 180 sq.ft. shall house all the panels for the BMS components including Closed Circuit Television, Fire Detection & Suppression System, Access Control, Fire Alarm, VESDA, etc. SWAN and Communication Room

This room with 208 sq.ft. shall consists of all the back bone cables and Networking Cables along with the Public Address system. A limited co-location of the SWAN Equipment shall be housed in the SWAN and Communication Room. Project Manager Room

This room with approx. 196 sq.ft. shall be used by the Project Incharge / Project Manager responsible for the overall delivery of the State Data Centre Project. Meeting Room 1

This room with approx. 430 sq.ft. shall be used by the Project Manager to discuss the migration of the applications etc. of the user departments and also for day-to-day operations and maintenance of the State Data Centre Project.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 54 of 99

Volume II Technical and Functional Specifications

Meeting Room 2

This room with approx. 185 sq.ft. shall be used by GOT and SDA for various activities concerning the State Data Centre. Reception Area

The reception area will be approx. 450 sq.ft. shall be used for the external visitors to the State Data Centre. Security Area

The security area will be approx. 396 sq.ft. shall be used by the security personnel for manning the State Data Centre and restricting the physical access to selected personnel.

2.1.1

Electrical Distribution System

A total of 1100 KVA Raw Power would be provided by the SDA along with the separate energy meter for APSDC. The total Raw Power requirement for the Server Farm Area Phase I is 700 KVA. Additional 400 KVA has been catered for certain auxiliary areas like the Server Farm Area Phase II, seating Type A & Seating Type B of the proposed State Data Centre. For Proper and uninterrupted working of Data Centre, supply of clean and uninterrupted power is essential. This can be ensured by having the Data Centre Power distribution system with redundancy at three levels, as follows: Two Incoming HT feeder supply from different substations. Even if one feeder is down, the other one keeps power available. Emergency Diesel-Generator backup on Mains failure of both the feeders.

2.1.2

Humidity, Ventilation and Air Conditioning Systems

The SDC should be precision environment controlled. The temperature inside Server Farm area should be maintained at 20 degree centigrade with a precision of 1 degrees. The Precision Air Conditioning shall be provided for the Server Farm Phase I with around 1585 sq.ft. area with necessary enhancements of cooling capacity in future in terms of additional indoor and outdoor units. The bidder should plan the location of such additional indoor and outdoor units. Bidder should also plan the location of such additional units in the area and lay additional conduits (including associated civil / electrical works) between locations of these additional indoor units and outdoor units, lay additional electrical cable & outlets so as to have other infrastructure ready for deploying additional indoor and outdoor units at a future date.
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 55 of 99

Volume II Technical and Functional Specifications

Air Conditioning should be ensured to the extent of 99.749%. It is suggested to provide air supply typically through false flooring. 2.1.2.1 Air Conditioning Since Zone A is a critical area, a separate air conditioning system (precision air conditioning) should be exclusively installed to maintain the required temperature for Zone A. Zone B & C can have a common air conditioning system for comfort. The general requirements for the two zones are as specified below: Zone A should be provided with precision air conditioning on a 24 x 7 x 365 days operating basis at least meeting with Tier II having n + 1 redundancy architecture requirements and having enough provision to scale it to next level as may be required in a later stage. The units should be able to switch the air conditioner on and off automatically and alternately for effective usage in pre defined sequence. The units should be down-flow fashion, air-cooled conditioning system. Precision Air Conditioning systems specifically designed for stringent environmental Control with automatic monitoring and control of cooling, heating, humidification, dehumidification and air filtration function should be installed. Zone B/C: Zone B/C should be provided with split-type comfort aircooled system ( at least meeting with Tier - II architecture requirements).

2.1.2.2 Natural Convection As the conditioned air is supplied through the grills with volume control dampers on the floor, the cold air-cools the component in a much faster and efficient manner as it does moves up, after extracting heat from the component. This follows the natural convection path of the air. The warm air should be sucked at the top by machine, airconditioned and then supplied back to the room. 2.1.2.3 Air Distribution The air is to be distributed evenly by providing grills with VCDs (Volume Control Dampers) in the floor tiles.

2.1.2.4 Flexibility The system should give the flexibility of discharging air at wherever point required even if the furniture is relocated. Changing the grill/tiles carrying grills, at suitable location does this.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 56 of 99

Volume II Technical and Functional Specifications

2.1.3

Rodent Repellant

The entry of Rodents and other unwanted pests shall be controlled using nonchemical, non-toxic devices. Ultrasonic pest repellents shall be provided in the false flooring and ceiling to repel the pests without killing them. However periodic pest control should be carried out by done by the DCO. Configuration : Master console with necessary transducer

Operating Frequency : Above 20 KHz (Variable) Sound Output Power output Power consumption Power Supply Mounting : 50 dB to 110 dB (at 1 meter) : 800 mW per transducer : 15 W approximately : 230 V AC 50 Hz : Wall / Table Mounting

2.1.4

False Ceiling

The top false ceiling would have 1 6 feet of space from the actual Room ceiling. This false ceiling will house AC ducting (if required) and cables of Electrical lighting, Fire fighting, Rodent Control and CCTV.

2.1.5

UPS Requirements & Features

UPS System design concept is based on redundancy and availability with true online system. To support the dual bus system configuration four units of UPS should be installed. The Zone A area should have four parallel redundant UPS and other areas like NOC, BMS and Staging Area should have a separate UPS system. Dual redundant UPS systems will take care of following needs Servers Access Control / Fire Detection, suppression / surveillance system

The solution should be automatic with power supply from the transformer as the primary source and automatic switchover to DG set as a secondary source for the data centre. Earthing should be provided from the electrical room control panel to the Earthing pits. It is recommended to have 4 x 160 KVA UPS with 20 minutes battery back-up on each UPS for redundant purpose. The first set of 2 x 160 KVA with each UPS having its own battery bank. The second set of 2 x 160 KVA with each UPS having its own battery bank. Both sets of UPS would be connected in Load Bus Synchronization (LBS) configuration. The UPS system shall be provided for the Server Farm Phase I with a capacity to accommodate 35 racks in an area of 1585 sq.ft. and provisioning of
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 57 of 99

Volume II Technical and Functional Specifications

necessary enhancements in the power capacity in future in terms of additional system should be planned. Bidder should also plan the location of the additional unit of the UPS system in the UPS & Electrical Room and lay additional electrical cable & outlets so as to have other infrastructure ready for deploying additional UPS system at a future date. It is also recommended to have 2 x 30 KVA UPS with 15 minutes battery back-up for provisioning of the power to the BMS Room, Staging Area and NOC Area. UPS Modes of Operation The UPS shall operate as an ON LINE reverse transfer system in the following modes: o Normal - The UPS inverter continuously supplies the critical AC load. The rectifier / charger derives power from AC Input source and supplies DC power to the Inverter while simultaneously load charging power reserve battery. o Emergency (Failure of AC Input) Upon failure of AC Input power, the critical AC load will be supplied by the Inverter, which without any switching obtains power from the battery. There shall be no interruption in power to the critical load upon failure or restoration of the AC input source. o Recharge Upon AC power restoration the rectifier / charger shall automatically restart and supply power to the inverter and start charging the batteries.
o

Bypass A static transfer switch should be provided for performing reverse transfer of the load from the inverter to bypass source with no interruption in the power to the critical AC load. A manually operated maintenance bypass switch should be incorporated into UPS cabinet that will connect the load to AC power source bypassing the rectifier charger inverter and static transfer switch. The battery circuit breaker MCCB shall have O/L and U/V protection. The UPS shall have built in isolation transformer in order to isolate neutral of incoming supply from the load. The load has to be provided separate neutral generated by the secondary winding of output isolation transformer.

Paralleling Operations: The output of all the four UPS systems should be directly connected at the load distribution panel through individual circuit breakers (part of the distribution panel). The load at the output should be

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 58 of 99

Volume II Technical and Functional Specifications

shared equally by all the UPS systems. The paralleling control mechanism should be available with individual UPS. There should not be any single point of failure which can lead to collapse of all the UPS systems. Battery Requirements The UPS system batteries shall be of 2 volts, Sealed Valve - Regulated lead acid (VRLA) heavy duty type batteries having design float life of 20 years. Sealed VRLA batteries shall be sized considering end cell voltage of 1.75 volts per cell for 30 minutes backup on full load.

Power Distribution Battery installation shall be outside the SDC area to avoid fire hazard as recommended by NFPA guidelines. Power cabling inside the SDC shall be of copper. The cables and conduits used inside the SDC shall be of FRLS quality. Signal referencing copper Earthing to be used using braided copper wire of 6 Gauge inside the SDC.

2.1.6

Diesel Generator Set

The diesel generator set should be in a redundancy mode and total number of units should not exceed two.

2.1.7

Electrical Work for SDC


Main electrical panel in Data Center Power cabling UPS Distribution Board UPS point wiring Power Cabling for Utility component and Utility Points etc Online UPS Separate Earth Pits for the component

The electrical cabling Work shall include the following:

The distribution of power from the UPS room to the following shall be considered: All proposed component for the production environment Existing servers and other component UPS 4 Nos. each of minimum 160 KVA with static bypass arrangement Both sets of UPS would be connected in Load Bus Synchronization (LBS) configuration

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 59 of 99

Volume II Technical and Functional Specifications

Sub distribution panels for UPS Final Distribution shall be through Power Distributions Units (PDU)/MCB Distribution Boxes. Power in the racks and other components shall be provided with three sockets with power coming from separate UPS in each of these sockets. The bidder is required to maintain two electrical distribution paths (one normal & one alternate) for the cabling inside the server farm area in the proposed State Data Centre

Specifications for Electrical Cabling Fire retardant cables of rated capacity exceeding the power requirement of fully blown configuration of the existing and proposed component to be used. For expansion needs suitable redundant power points to be provided at suitable locations. All materials used shall conform to IS standards as per industry practice. Bunching of Wires Wires carrying current shall be so bunched in the conduit that the outgoing and return wires are drawn into the same conduit. Wires originating from two different phases shall not be run in the same conduit. Drawing of Conductors The drawing Aluminum / Copper conductor wires shall be executed with due regards to the following precautions while drawing insulated wires in to conduits. Care shall be taken to avoid scratches and kinks, which cause breakages. Joints All joints shall be made at main switches, distribution boards, socket outlets, lighting outlets and switch boxes only. No joints shall be made inside conduits and junctions boxes. Conductors shall be continuous from outlet to outlet. Mains & Sub-Mains Mains & sub-mains wires where called for shall be of the rated capacity and approved make. Every main and sub-main shall be drawn into an independent adequate size conduit. Adequate size draw boxes shall be provided at convenient locations to facilitate easy drawing of the mains and sub-mains. An independent earth wire of proper rating shall be provided. The earth wires shall run along the entire length of the mains and sub-mains. Load Balancing Balancing of circuits in three-phase installation shall be planned before the commencement of wiring. Color Code of the Conductors Color code shall be maintained for the entire wiring installation, Red, Yellow, Blue for three phases and OFF circuit black for neutral and green for earth (or bare earth).
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 60 of 99

Volume II Technical and Functional Specifications

Fixing of the Conduits Conduits junction boxes shall be kept in position and proper holdfasts shall be provided. Conduits shall be so arranged as to facilitate easy drawing of the wires through them. Adequate junction boxes of approved shape & size shall be provided. All conduits shall be installed so as to avoid stream and hot water pipes. After conduits, junction boxes, outlet boxes & switch boxes are installed in position their outlets shall be properly plugged so that water, mortar, insects or any other foreign matter does not enter into conduit system. Conduits shall be laid in a neat and organize manner as directed and approved by the Information Technology Department Personnel or person on their behalf. Conductors shall be planned so as not to conflict with any other service pipe lines / ducts.

Protection To minimize condensation or sweating inside the conductors all outlets of conduit system shall be adequately ventilated and approved by the proper competent authority. All screwed and socketed connections shall be adequately made fully water tight by use of proper jointing materials.

Switch-Outlet Boxes and Junction Boxes All boxes shall conform to all prevailing Indian Standards. The cover plates shall be of best quality Hylam sheets or ISI grade Urea Formaldehyde Thermosetting insulating material, which should be mechanically strong and fire retardant. Proper support shall be provided to the outer boxes to fix the cover plates of switches as required. Separate screwed earth terminals shall be provided inside the box for earthling purpose.

Inspection Boxes Rust proof inspection boxes of required size having smooth external and internal Finish shall be provided to permit periodical inspection and to facilitate removal and replacement of wires when required.

2.2 Technical Specifications Physical Components


2.2.1 UPS

Reliability of electric power can affect operations of the State Data Centre. Uninterrupted Power Supplies (UPS) shall be used to support the load of the critical components of the Data Centre for periods of failure of the supplied electric power, while at the same time, filtering out transients. The scope shall include supply, transportation, storage, unpacking, erection, testing, successful commissioning and satisfactory completion of trial operations of the above UPS systems for the State Data Centre.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 61 of 99

Volume II Technical and Functional Specifications

The UPS system should assure the Data center equipment with continuous power at a solution uptime of 99.749% and with redundancy available up to the load end. Input Standard Voltage, 380 /400 / 415 V 3 Phase, 3 or 4 wire, +10 %, -15% Input Frequency, 50 Hz, +5% or -5% Output Steady State Voltage, 380 / 400 / 415 V +1% or -1% Output Frequency, 50 Hz, +0.25Hz to 0.5Hz Output Transient Voltage Stability, < 5% or 5% for a load change from 0% to 100% Overload 125% for 10 minutes and 150% for 60 seconds Efficiency at full rated load, Not less than 92% Total Harmonic Content With Linear Load < 2% for 100 % linear load and with 3:1 Crest factor load < 5% Input Harmonic Filter (for <10% Input current distortion) DC ripple (with & without Battery connected) < 1% Built In power factor correction Automatic shutdown of component for longer power outages Monitoring and logging the status of the power supply Displaying the voltage/current draw of the component Automatic restarting of component following a power outage Displaying the current voltage on the line Providing alarms on some error connections Providing protection against short circuits Operating Temperature range - 0 to 40 Celsius Design compliance with IEC and ISO Software that must be installed and integrated suitable operating system Supplies True Online UPS Power Non-Linear load compatible Capability to handle high Crest Factor load Ventilation- Air cooling with Integral Fans Built in Reliability & High Efficiency Low Audible Noise

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 62 of 99

Volume II Technical and Functional Specifications

Compact Footprint Front Access for easy Maintenance The power factor of the UPS system shall be at 0.9 or better at full load conditions

Input Current Harmonics < 8% The battery circuit breaker MCCB shall have O/L and U/V protection. The UPS shall have built in isolation transformer for re-referencing and to limit neutral- ground voltage to 1.50 volts by directly connecting dedicated earth to neutral of the output isolation transformer of the UPS as stipulated by server manufactures.

2.2.2

Diesel Generator Set

Diesel Engine Diesel Engine, water cooled, Naturally Aspirated, developing 2 x 600 KVA @ 1500 RPM, under NTP conditions of BS: 5514, with Dry Type Air Cleaner, Compact Radiator with Recovery Bottle and Pusher type Fan, Engine with Coolant, Engine mounted panel with wiring harness, Holset Coupling and Industrial Silencer, as per engine manufacturers design standards. Power output guaranteed within 0 to +2 % and can be operated up to 3130 Mt. altitude and no de-rating for ambient temperature or humidity. The DG units should come with sound proofing as per the standards.

Alternator Standard design Alternator, rated at 0.8 PF, 415 Volts, 3 Phase, 4 wires, 50 cycles/sec, 1500 RPM, self-excited and self regulated, with brushless excitation, Self- ventilated, Screen Protected Drip Proof, Insulation Class H, enclosure IP 23. The A.C. Generator shall be Horizontal foot mounted single bearing type and shall be fitted with Automatic Voltage Regulator (AVR) for Voltage regulation of +/- 1% or better. The Alternator generally conforms to BS: 5000/IS: 4722 and suitable to deliver output of the engine capacity having 600 KVA.

Base Frame Sturdy, fabricated, welded construction, channel iron Base Frame for mounting the above Engine and Alternator.

Control Panel Cubicle type, floor mounting Control Panel, with hinged doors, bottom gland plate and accommodating the following: o o o 1-No. ACB or Moulded Case Circuit Breaker 3-No.s Ammeters /1 No. Ammeter with Selector Switch 1 No. Voltmeter with Selector Switch

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 63 of 99

Volume II Technical and Functional Specifications

o o o

1 No. frequency meter 1 Set Pilot Lamps LOAD ON/GENERATOR ON 1 Set Instrument Fuses

Fuel Tank Necessary liters capacity Fuel Tank with mounting brackets to run for 8 hours, complete with level indicator, fuel inlet and outlet, air vent, drain plug, inlet arrangement for direct filling and set of fuel hoses for inlet and return. Diesel storage requirement for minimum 48 hours should be maintained

Battery Dry uncharged maintenance free batteries with leads and terminals. Management - The DG set should be manageable via Building Management System/ NOC with MODBUS Protocol with RS 485 Communication Port so that all software features like Diesel Consumption, Power, and Current etc. can be monitored on the BMS screen.

2.2.3

Civil & Architectural work

The scope for civil work in this RFP is to furnish the data center area in all aspects. The furnishing includes but not limited to the following Cement Concrete Work Cutting and chipping of existing floors Trench works Masonry works Hardware and Metals Glazing Paint work False Flooring False Ceiling Storage Furniture & fixture Partitioning Doors and Locking Painting Fire proofing all surfaces Insulating

The selected bidder should adhere to the following civil and interior specifications: a. Raised Flooring Providing & fixing steel encapsulated raised access floor of FFH upto 450mm finished with antistatic high pressure laminate in size 600 x 600

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 64 of 99

Volume II Technical and Functional Specifications

mm x 35 mm with point load 450 kg and uniform distribution load (UDL) 2200 kg per sq. metre as per following specifications: Panel Type - Fiber reinforced calcium sulphate panels with thickness ranging from 13 mm to 42 mm, Understructure- Edge support rigid grid, Wear resistance (g / cm2) - < 0.08, Bottom profile - Hemispherical shape, Adjustable Pedestal -all steel construction & silver zinc plated / chromatized for protection against corrosion, high precision tube. Exposed surface- Special weather coating on entire surface of the tiles. The same should also be provided with wire manager and tile lifter etc. At least 1' 6 High from existing floor level using antistatic laminated tiles. Supply & Fixing of 1.5 mm Antistatic Laminate skirting matching with floor tiles with 8mm thick MDF Board / Bison Board up to a height of 4". Supplying and fixing vitrified flooring with homogeneous flexible vitrified flooring of approved shade 2.0 mm thick in roll forms and manufacturers specification over the existing floor. Before laying, the existing flooring should be made free from dust and undulations. The finished flooring should be free from air bubbles and thoroughly cleaned without undulations. Providing and laying premium quality Granite white/ cream tiles of size 2'0" x 2'-0", 8.5 mm thick set in cement mortar and pointing with approved tile joint filler compound of approved make of matching shade as per manufacturer's specification as directed. The work shall include the preparation of base surface, cleaning, and acid wash. do - for skirting upto a height of 4" Providing and fixing 9 mm thick floor insulation below the false flooring and joints should be finished properly as per manufacturer's specification.

b. False Ceiling Providing and fixing metal false ceiling with powder coated 0.5mm thick hot dipped galvanised steel tiles 595 x 595 mm with tegular edge (10mm) suitable for 25mm grid supported on suitable powder coated galvanised steel grid as per manufacturer specification. The same shall be inclusive of cut outs for lighting, AC grills, Fire detectors, nozzles and 25mm thick glass wool of 16kg.sq.m density wrapped on both sides with aluminium foil and placed over each tile etc. Providing and fixing 12 mm thick fire line Gypsum false ceiling and lighting troughs 300 mm as per design including 100 mm high cornices as lighting pelmets on G.I. frame work, in G.I. vertical supports at every 450mm c/c
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 65 of 99

Volume II Technical and Functional Specifications

and horizontal runners at every 900mm c/c self taping metal screws to proper line and level. The same shall be inclusive of making holes and required framing for fixing electrical fixtures, A.C. grills etc. Area of electrical fixtures will be paid full fixed to G.I. supports to receive spotlights including cutting hole etc., complete. G.I. metal frame to be of 24 gauge folded strip of 50mm width to be used. GI vertical supports to be anchored to slab by means of anchor fasteners. c. Furniture and Fixture Workstation size of 2' depth made with 1.5mm thick laminate of standard make over 19mm thick commercial board complete with wooden beading including cutting holes & fixing of cable manager etc complete with French polish. The desk top will be 25mm thick & edges shall be factory postformed. The desk shall have the necessary drawers, keyboard trays, cabinets etc. along with sliding / opening as per design, complete with approved quality drawer slides, hinges, locks etc. Providing & making of storage unit with 18 mm thick MDF board along with 1.5 mm approved laminate color out side and 2 coat of enamel paint inside the storage of size 1'6"x1'9"x2'4". The same should be provided with all the required accessories including the handle, lock, sliding channel and necessary hardware, etc. complete with French polish Cabin table of depth 2 made with 1.5mm thick laminate of standard make over 19mm thick commercial board complete with wooden beading including cutting holes & fixing of cable manager etc complete with French polish. Providing, making & fixing 6" high laminated strip using 1.5mm thick laminate over 10mm thick commercial board on all vertical surface in the entire server & ancillary areas including low ht partition, brick wall, partition wall, cladding etc complete with French polish in all respect. Providing, making & fixing an enclosure for gas cylinder of Shutters and Partitions along with wooden support and 18 mm thick MDF board along with 1.5 mm approved laminate color out side and 2 coat of enamel paint inside the shutter. The same should be provided with all the required accessories including the handle, lock, loaded hinges, tower bolt and necessary hardware etc. complete with French polish. Fire proof safe (300 Ltrs. or above) with one hour fire rated. d. Partitions Providing and fixing in position full height partition wall of 125 mm thick fireline gyp-board partition using 12.5 mm thick double fireline gyp-board on both sides with GI steel metal vertical stud frame of size 75 mm fixed in the floor and ceiling channels of 75 mm wide to provide a strong

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 66 of 99

Volume II Technical and Functional Specifications

partition. Glass wool insulation inside shall be provided as required. Fixing is by self tapping screw with vertical studs being at 610 mm intervals. The same should be inclusive of making cutouts for switch board, sockets, grill etc. It shall also include preparing the surface smoothly and all as per manufactures specification etc. finally finishing with one coat of approved brand of fire resistant coating. With glazing including the framework of 4" x 2" powder coated aluminium section complete (in areas like partition between server room & other auxiliary areas). Providing & fixing Fire Rated Wire Glass minimum 6 mm thick for all glazing in the partition wall complete. (External windows not included in this). All doors should be minimum 1200 mm (4 ft) wide. Providing & fixing Fire Rated Wire Glass minimum 6 mm thick for the partition wall between the Server Farm Area I of approx. 1585 sq.ft. and Server Farm Area II of approx. 963 sq.ft. complete with all the required accessories.

e. Painting Providing and applying Fire retardant paint of approved make and shade to give an even shade over a primer coat as per manufacturers recommendations after applying painting putty to level and plumb and finishing with 2 coats of fire retardant paint. Base coating shall be as per manufacturers recommendation for coverage of paint. For all vertical Plain surface. For fireline gyp-board ceiling. Providing and laying POP punning over cement plaster in perfect line and level with thickness of 10 - 12 mm including making good chases, grooves, edge banding, scaffolding pockets etc. Applying approved fire retardant coating on all vertical surfaces, furniture etc. as per manufacturer's specification.

f.

Civil Work Providing and laying 115 mm thick brick work in cement mortar of 1:4 (1 cement : 4 sand) with bricks of approved quality chamber bricks of class designation 50. Providing & making SS signage with text in etched & black painted of Dline make or equivalent to be located as directed (wall mounted) for space nomenclature/ directions. Plastering with cement mortar 1:5 (1 cement : 5 sand) of 12 mm thick in interior face of the walls and concrete columns including hacking the

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 67 of 99

Volume II Technical and Functional Specifications

concrete surface brushing, scaffolding, curing and be smooth trowel finish as per standard specification. Anti-termite treatment of the entire critical area.

surface

shall

2.2.4

PVC Conduit
The conduits for all systems shall be high impact rigid PVC heavy-duty type and shall comply with I.E.E regulations for nonmetallic conduit 1.6 mm thick as per IS 9537/1983. All sections of conduit and relevant boxes shall be properly cleaned and glued using appropriate epoxy resin glue and the proper connecting pieces, like conduit fittings such as Mild Steel and should be so installed that they can remain accessible for existing cable or the installing of the additional cables. No conduit less than 20mm external diameter shall be used. Conduit runs shall be so arranged that the cables connected to separate main circuits shall be enclosed in separate conduits, and that all lead and return wire of each circuit shall be run to the same circuit. All conduits shall be smooth in bore, true in size and all ends where conduits are cut shall be carefully made true and all sharp edges trimmed. All joints between lengths of conduit or between conduit and fittings boxes shall be pushed firmly together and glued properly. Cables shall not be drawn into conduits until the conduit system is erected, firmly fixed and cleaned out. Not more than two right angle bends or the equivalent shall be permitted between draw or junction boxes. Bending radius shall comply with I.E.E regulations for PVC pipes. Conduit concealed in the ceiling slab shall run parallel to walls and beams and conduit concealed in the walls shall run vertical or horizontal. The chase in the wall required in the recessed conduit system shall be neatly made and shall be of angle dimensions to permit the conduit to be fixed in the manner desired. Conduit in chase shall be hold by steel hooks of approved design of 60cm center the chases shall be filled up neatly after erection of conduit and brought to the original finish of the wall with cement concrete mixture 1:3:6 using 6mm thick stone aggregate and course sand.

2.2.5

Wiring
PVC insulated copper conductor cable shall be used for sub circuit runs from the distribution boards to the points and shall be pulled into conduits. They shall be stranded copper conductors with thermoplastic insulation of 650 / 1100 volts grade. Color code for wiring shall be followed.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 68 of 99

Volume II Technical and Functional Specifications

Looping system of wring shall be used, wires shall not be jointed. No reduction of strands is permitted at terminations. No wire smaller than 3.029 sq.mm. shall be used. Wherever wiring is run through trunking or raceways, the wires emerging from individual distributions shall be bunched together with cable straps at required regular intervals. Identification ferrules indication the circuit and D.B. number shall be used for sub main, sub circuit wiring the ferrules shall be provided at both end of each sub main and sub-circuit. Where, single phase circuits are supplied from a three phase and a neutral distribution board, no conduit shall contain wiring fed from more than one phase in any one room in the premises, where all or part of the electrical load consists of lights, fans and/or other single phase current consuming devices, all shall be connected to the same phase of the supply. Circuits fed from distinct sources of supply or from different distribution boards or M.C.B.s shall not be bunched in one conduit. In large areas and other situations where the load is divided between two or three phases, no two single-phase switches connected to difference phase shall be mounted within two meters of each other. All splicing shall be done by means of terminal blocks or connectors and no twisting connection between conductors shall be allowed. Metal clad sockets shall be of dia cast non-corroding zinc alloy and deeply recessed contact tubes. Visible scraping type earth terminal shall be provided. Socket shall have push on protective cap. All power sockets shall be piano type with associates switch of same capacity. Switch and socket shall be enclosed in a M. S. sheet steel enclosure with the operating knob projecting. Entire assembly shall be suitable for wall mounting with Bakelite be connected on the live wire and neutrals of each circuit shall be continuous everywhere having no fuse or switch installed in the line excepting at the main panels and boards. Each power plug shall be connected to each separate and individual circuit unless specified otherwise. The power wiring shall be kept separate and distinct from lighting and fan wiring. Switch and socket for light and power shall be separate units and not combined one. Balancing of circuits in three phases installed shall be arranged before installation is taken up. Unless otherwise specified not more than ten light points shall be grouped on one circuit and the load per circuit shall not exceed 1000 watts The earth continuity insulated copper wire in Green color shall be run inside the conduit to earth the third pin or socket outlets, earth terminal of light fixtures, fan etc. as required. Lights points

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 69 of 99

Volume II Technical and Functional Specifications

shall be either of single control, twin control or multiple points controlled by a single switch / MCB as per scheduled of work. Bare copper wire shall be provided with each circuit from DB as specified in the item of work and terminated in earth bar of DBs and switch boxes with proper lugs as required maximum number of PVC insulated 650 / 1100 grade copper conductor cable which can be drawn in a conduit.

2.2.6

Earthing

All electrical components are to be earthen is to by connecting two earth tapes from the frame of the component ring will be connected via several earth electrodes. The cable arm will be earthen through the cable glands. Earthling shall be in conformity with provision of rules 32, 61, 62, 67 & 68 of Indian Electricity rules 1956 and as per IS- 3843-1986. The entire applicable IT infrastructure in the Data Center shall be earthed. Earthing should be done inside the Data Centre for the entire power system and provisioning should be there to earth UPS systems, Power distribution units, AC units etc. so as to avoid a ground differential. State shall provide the necessary space required to prepare the earthing pits. All metallic objects on the premises that are likely to be energized by electric currents should be effectively grounded. The connection to the earth or the electrode system should have sufficient low resistance in the range of 0 to 25 ohm to ensure prompt operation of respective protective devices in event of a ground fault, to provide the required safety from an electric shock to personnel & protect the equipment from voltage gradients which are likely to damage the equipment. Recommended levels for equipment grounding conductors should have very low impedance level less than 0.25 ohm. The Earth resistance shall be automatically measured on an online basis at a pre-configured interval and corrective action should be initiated based on the observation. The automatic Earthing measurements should be available on the UPS panel itself in the UPS room. There should be enough space between data and power cabling and there should not be any cross wiring of the two, in order to avoid any interference, or corruption of data. The earth connections shall be properly made .A small copper loop to bridge the top cover of the transformer and the tank shall be provided to avoid earth fault current passing through fastened bolts, when there is a lighting surge, high voltage surge or failure of bushings. The DCO would be responsible for providing separate Earthing for

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 70 of 99

Volume II Technical and Functional Specifications

Servers, UPS & Generators as per the standards.

2.2.7

Cable Work
Cable ducts should be of such dimension that the cables laid in it do not touch one another. If found necessary the cable shall be fixed with clamps on the walls of the duct. Cables shall be laid on the walls/on the trays as required using suitable clamping/ fixing arrangement as required. Cables shall be neatly arranged on the trays in such manner that a crisis crossing is avoided and final take off to switch gear is easily facilitated. All cables will be identified close to their termination point by cable number as per circuit schedule. Cable numbers will be punched on 2mm thick aluminum strips and securely fastened to the. In case of control cables all covers shall be identified by their wire numbers by means of PVC ferrules. For trip circuit identification additional red ferrules are to be used only in the switch gear / control panels, cables shall be supported so as to prevent appreciable sagging. In general distance between supports shall not be greater than 600mm for horizontal run and 750mm for vertical run. Each section of the rising mains shall be provided with suitable wall straps so that same the can be mounted on the wall. Whenever the rising mains pass through the floor they shall be provided with a built-in fire proof barrier so that this barrier restricts the spread of fire through the rising mains from one section to the other adjacent section. Neoprene rubber gaskets shall be provided between the covers and channel to satisfy the operating conditions imposed by temperature weathering, durability etc. Necessary earthling arrangement shall be made alongside the rising mains enclosure by Mean of a GI strip of adequate size bolted to each section and shall be earthed at both ends. The rising mains enclosure shall be bolted type. The space between data and power cabling should be as per standards and there should not be any criss-cross wiring of the two, in order to avoid any interference, or corruption of data.

2.2.8

Precision Air Conditioning

The SDC shall be provided with fully redundant Microprocessor based Precision Airconditioning system. Cool air feed to the SDC shall be bottom-charged or downward
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 71 of 99

Volume II Technical and Functional Specifications

flow type using raised floor as supply plenum using perforated aluminum tiles for Air flow distribution. The return air flow shall be through false ceiling to cater to the natural upwardly movement of hot air. Cooling shall be done by the Precision AirConditioning system only. Forced cooling using Fans on False floor etc is not acceptable. A/C should be capable of providing sensible cooling capacities at design ambient temperature & humidity with adequate airflow. The PAC should capable to be integrated with the Building management System for effective monitoring. The Agency will be required to design, supply, transport, store, unpack, erect and test the successful commissioning and satisfactory completion of trial operations of the PAC systems for the Data Centre. This shall also include Connecting the indoor unit with the mains electrical point Connecting indoor and outdoor units mechanically (with 18 G hard Gauge Copper piping). Connecting indoor and outdoor unit electrically. Nitrogen pressure testing, triple vacuum, final gas charging. Connecting the humidifier feed line with the point provided. Connecting the drain line with the point provided. Commissioning and handing over the unit to the customer. Operation and routine maintenance training to up to two persons nominated by the customer while commissioning the units at site

2.2.8.1 Temperature Requirements The environment inside the SDC shall need to be continuously maintained at 20 1o Centigrade. It is advised that the temperature and humidity be controlled at desired levels. The necessary alarms for variation in temperatures shall be monitored on a 24x7 basis and logged for providing reports. 2.2.8.2 Relative Humidity (RH) requirements Ambient RH levels shall need to be maintained at 50% 5 non-condensing. Humidity sensors shall be deployed. The necessary alarms for variation in RH shall be monitored on a 24x7 basis and logged for providing reports. 2.2.8.3 Temperature & Relative Humidity Recorders Temperature & Humidity will be recorded at the inlet of Precision Air Conditioning Indoor Unit i.e. return air condition. In Auxiliary areas, the selected bidder is required to maintain the temperature 20 degree Celsius with a variation of 4 degree Celsius. The humidity is required to be maintained at 85% with a variation of 5%.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 72 of 99

Volume II Technical and Functional Specifications

2.2.8.4 Air quality levels The SDC shall be kept at highest level of cleanliness to eliminate the impact of air quality on the hardware and other critical devices. The SDC shall be deployed with efficient air filters to eliminate and arrest the possibility of airborne particulate matter which may cause air-flow clogging, gumming up of components, causing shortcircuits, blocking the function of moving parts, causing components to overheat etc. Air filters shall be 95% efficiency & provide up-to 5 Micron particulate shall be deployed 2.2.8.5 Additional Points The precision air-conditioners should be capable of maintaining a temperature range of 20 degree with a maximum of 1 degree variation on higher and lower side and relative humidity of 50% with a maximum variation of 5% on higher and lower side. The precision air-conditioners shall have 2 independent refrigeration circuits (each comprising 1 no scroll compressors, refrigeration circuit and condensers) and dual blowers for flexibility of operations and better redundancy. The unit casing shall be in double skin construction on side panels & single skin on the front & back panels for longer life of the unit and low noise level For close control of the SDC environment conditions (Temp. and RH) the controller shall have (PID) proportional integration and differential. The precision unit shall be air cooled refrigerant based system to avoid chilled water in critical space. The internal rack layout design shall follow cold aisle and hot aisle concept as recommended by Ashrae. The refrigerant used shall be environment friendly HFC, R-407-C/ equivalent in view of long term usage of the data center equipments, availability of spares and refrigerant. Fully Deployed Dynamic Smart Cooling with Auto sequencing Provision and Auto Power Management Features Thermal and CFD Analysis diagrams should be provided by the bidder after the award of the contract The fan section shall be designed for an external static pressure of 25 Pa. The fans shall be located downstream of the evaporator coil and be of the electronically commuted backward curved centrifugal type, double width, double inlet and statically and dynamically balanced. Each fan shall be direct driven by a high efficiency DC motor.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 73 of 99

Volume II Technical and Functional Specifications

The evaporator coil shall be A-shape coil / Straight Slant coil (for down flow) incorporating draw-through air design for uniform air distribution. The coil shall be constructed of rifled bore copper tubes and louvered aluminum fins, with the frame and drip tray fabricated from heavy gauge aluminum. Face area of coil shall be selected corresponding to air velocity not exceeding 2.5 m/sec. Dehumidification shall be achieved by either reducing effective coil area by solenoid valve arrangement or using Dew point method of control. Whenever dehumidification is required, the control system shall enable a solenoid valve to limit the exchange surface of the evaporating coil, thereby providing a lower evaporating temperature. The humidifier and heaters shall be a built in feature in each machine individually. Humidification shall be provided by boiling water in a high temperature polypropylene steam generator. The steam shall be distributed evenly into the bypass airstreams of the environment control system to ensure full integration of the water vapor into the supply air without condensation. The humidifier shall have an efficiency of not less the 1.3 kg/kw and be fitted with an auto flush cycle activated on demand from the microprocessor control system. The humidifier shall be fully serviceable with replacement electrodes. Wastewater shall be flushed from the humidifier by the initiation of the water supply solenoid water valve via a U-pipe overflow system. Drain solenoid valves shall not be used. Microprocessor should be able to control the humidification and heating through suitable sensors

Microprocessor Controls: Following features should be displayed on the units o o o o o o o o o o o o o Room temperature and humidity. Supply fan working status Condenser fans working status Electric heaters working status Humidifier working status Manual / Auto unit status Temperature set point Humidity set point Working hours of main component i.e. compressors, fans, heater, humidifier etc. Unit working hours Current date and time Type of alarm (with automatic reset or block) The last 10 intervened alarms

The microprocessor should be able to perform following functions o o o o o Testing of the working of display system Password for unit calibration values modification Automatic re-start of program Cooling capacity control Compressor starting timer

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 74 of 99

Volume II Technical and Functional Specifications

o o o o o o o o

Humidifier capacity limitation Date and time of last 10 intervened alarm Start / Stop status storage Random starting of the unit. Outlet for the connection to remote system Temperature and humidity set point calibration Delay of General Alarm activation Alarm calibration

Following alarms shall be displayed on screen of microprocessor unit: o Air flow loss o Clogged Filters o Compressor low pressure o Compressor high pressure o Smoke - fire o Humidifier Low water level o High / Low room temperature o High/Low room humidity o Spare External Alarms o Water Under floor The control system shall include the following settable features: o o o o o o o Unit identification number Startup Delay, Cold start Delay and Fan Run on timers Sensor Calibration Remote shutdown & general Alarm management Compressor Sequencing Return temperature control Choice of Modulating output types

The unit shall incorporate the following protections: o o o o o Single phasing preventors Reverse phasing Phase imbalancing Phase failure Overload tripping (MPCB) of all components

2.2.9

Split type Comfort Air Conditioning for Auxiliary Areas


Capacity minimum 2 Tonnage each Cooling Capacity minimum 24000 BTU / Hr Compressor Hermetically Sealed Scroll Type Refrigerant R 22 Type Power Supply Three Phase, 380-415 V, 50 Hz Air Flow Rate minimum 19 cu m / min Noise Level - < 50 dB

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 75 of 99

Volume II Technical and Functional Specifications

Operation Remote Control

2.2.10 Fire Detection and Control Mechanism


Fire can have disastrous consequences and affect operations of a Data Center. The early-detection of fire and employing means for automatic suppression of the fire is important for effective functioning of a Data Center. System Description The Fire alarm system shall be an automatic 1 to n (e.g. 24) zone single loop addressable fire detection and alarm system, utilizing conventional detection and alarm sounders. Detection shall be by means of automatic heat and smoke detectors located throughout the Data Center (ceiling, false floor and other appropriate areas where fire can take place) with break glass units on escape routes and exits. Control and indicating component The control panel shall be a microprocessor based single loop addressable unit, designed and manufactured to the requirements of EN54 Part 2 for the control and indicating component and EN54 Part 4 for the internal power supply. All controls of the system shall be via the control panel only. All site-specific data shall be field programmable and stored in an integral EEPROM. The use of EPROMs requiring factory burning and reprogramming is not acceptable. All internal components of the control panel shall be fully monitored. The control panel shall be capable of supporting a multi device, multi zone 2-wire detection loop. Removal of 1 or more detection devices on the loop shall not render the remaining devices on the loop inoperable. The system status shall be made available via panel mounted LEDs and a backlit 8 line x 40-character alphanumeric liquid crystal display. All user primary controls shall be password protected over 4 access levels in accordance with EN54 Part 2. Essential controls, such as Start / Stop sounders and Cancel fault buzzer, etc. will be clearly marked. Cancel fault and display test functions shall be configurable to be accessed from level 1 or level 2. All system controls and programming will be accessed via an alphanumeric keypad. The control panel will incorporate form fill menu driven fields for data entry and retrieval. The control panel shall log a minimum of 700 events comprising of 100 event fire log and 200 event fault, disablement and historic logs, giving time, date, device reference and status of indication.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 76 of 99

Volume II Technical and Functional Specifications

Fire, fault and disablement events shall be logged as they occur. Visual and audible conformation shall be given on an array of LEDs, the Liquid Crystal Display and the internal supervisory buzzer. The control panel shall have an integral automatic power supply and maintenance free sealed battery, providing a standby capacity of a minimum 72 hours and further 30 minutes under full alarm load conditions. The system shall be capable of full re-charge within 24 hours following full system discharge. The performance of the power supply and batteries shall be monitored and alarm rose, should a fault be detected. The system shall protect the batteries from deep discharge. All terminations within the control panel with the exception of the 230V mains connection will be via removable terminal screw fixing points. The control panel will have a programmable maintenance reminder to inform the user that maintenance of the system is required. This function shall provide the user with the option of a monthly, quarterly, annually or bi-annually reminder prompts. The maintenance reminder will be indicated on the control panel. This message shall be resettable by the user and will not require the intervention of specialist support. The control panel will provide programmable free text field as part of the maintenance reminder facility. The system will include a detection verification feature. The user shall have the option to action a time response to a fire condition. This time shall be programmable up to 10 minutes to allow for investigation of the fire condition before activating alarm outputs. The operation of a manual call point shall override any verify command.

Manual Controls Start sounders Silence sounders Reset system Cancel fault buzzer Display test Delay sounder operation Verify fire condition Enter or modify device text label Setup maintenance reminder Assign or modify zones Disable zones, device, sounders, FRE contact, auxiliary contacts Enable zones, device, sounders, FRE contact, auxiliary contacts Action weekly test Disable loop

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 77 of 99

Volume II Technical and Functional Specifications

Cable entries The control panel will include the necessary top entry and rear entry cable entry points via 20mm knockouts. Manual call points (MCP) MCPs shall be addressable and of the steady pressure break glass type manufactured to the requirements of BS 5839: Part 2. A test key shall be provided to allow the routine testing of the unit to meet the requirements of BS 5839 Part 1 1988, without the need for special tools or the need to unfasten the cover plate. The device shall be automatically addressed by the CIE on power up of the loop without the need of the insertion of a pre-programmed EPROM or setting of DIL switches. The device shall incorporate a short circuit isolation device and a red LED indicator. The MCP shall be suitable for surface or flush mounting. When flush mounted the device shall be capable of fixing to an industry standard single gang box.

Smoke detectors Smoke detectors shall be of the optical or ionization type. Devices shall be compatible with the CIE conforming to the requirements of EN54 Part 7 and be LPCB approved. The detectors shall have twin LEDs to indicate the device has operated and shall fit a common addressable base. Heat detectors Heat detectors shall be of the fixed temperature (58 C) or rate of temperature rise type with a fixed temperature operating point. Devices shall be compatible with the CIE conforming to the requirements of EN54 Part 5 and be LPCB approved. The detectors shall have a single LED to indicate the device has operated and shall fit a common addressable base.

Addressable detector bases All bases shall be compatible with the type of detector heads fitted and the control system component used. Each base shall comprise all necessary electronics including a short circuit isolator. The device shall be automatically addressed by the CIE on power up of the loop without the need of the insertion of a pre-programmed EPROM or setting of DIL switches. Detector bases shall fit onto an industry standard conduit box.

Audible Alarms Electronic sounders shall be colored red with adjustable sound outputs and at least 3 sound signals. The sounders should be suitable for operation
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 78 of 99

Volume II Technical and Functional Specifications

with a 24V DC supply providing a sound output of at least 100dBA at 1 meter and 75 dBA min, for a bed head or sounder base type device. The sounder frequency shall be in the range of 500Hz to 1000Hz. Commissioning The fire detection and alarm system will be programmable and configurable via an alpha numeric keypad on the control panel. The labeling of Device and Zone labels should be part of the system. Necessary Software to the control panel

2.2.11 Fire Suppression Systems


The Clean Agent Fire Suppression system cylinder, CCOE, Nagpur approved seamless cylinders, discharge hose, fire detectors and panels and all other accessories required to provide a complete operational system meeting applicable requirements of NFPA 2001 Clean Agent Fire Extinguishing Systems, NFPA 70 National Electric Code, NFPA 72 National Fire Alarm Code or ISO standards must be considered to ensure proper performance as a system with UL/FM approvals and installed in compliance with all applicable requirements of the local codes and standards. The Clean Agent system considered for Total flooding application shall be in compliance with the provisions of Kyoto Protocol. Care should be taken that none of the Greenhouse Gases identified in the Kyoto Protocol is used for fire suppression application. The minimum criterion for the selection of the Clean Agent will be on the following parameters o Zero Ozone Depleting Potential. o Global Warming Potential not exceeding one. o Atmospheric Lifetime not exceeding one week. The clean agent fire suppression system with FK-5-1-12 and Inert Gas based systems are accepted as a replacement of HCFC and HFC as per Kyoto Protocol. The Clean Agent considered for the suppression system must be suitable for manable occupied areas with NOAEL Level (No observable adverse effect level) of 10% as compared to the design concentration to ensure high safety margin for the human who might be present in the hazard area. The minimum design standards shall be as per NFPA 2001, 2004 edition or latest revisions. Care shall be given to ensure proper early warning detection system with minimum sensitivity of 0.03% per foot obscuration as per NFPA 318 & NFPA 72 to ensure that one gets a very early warning to investigate the

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 79 of 99

Volume II Technical and Functional Specifications

incipient fire much before the other detectors activate the fire suppression system automatically. All system components furnished and installed shall be warranted against defects in design, materials and workmanship for the full warranty period which is standard with the manufacturer, but in no case less than five (5) years from the date of system acceptance Additionally, Portable Extinguishers (CO2 or Halon based Extinguishers are not acceptable) shall be placed at strategic stations throughout the Data Centre.

2.2.12 High Sensitivity Smoke Detection System


General The HSSD system shall provide an early warning of fire in its incipient stage, analyze the risk and provide alarm and actions appropriate to the risk. The system shall include, but not be limited to, a Display Control Panel, Detector Assembly and the properly designed sampling pipe network. The system component shall be supplied by the manufacturer or by its authorized distributor. Regulatory Requirements National Electrical Code (NEC) Factory Mutual Local Authority having Jurisdiction

2.2.13 Access Control System


The Access Control System shall be deployed with the objective of allowing entry and exit to and from the premises to authorized personnel only. The system deployed shall be based on Proximity as well as Biometric Technology for the critical areas and Proximity technology for non-critical areas. An access control system consisting of a central PC, intelligent controllers, proximity readers, power supplies, proximity cards and all associated accessories is required to make a fully operational on line access control system. Access control shall be provided for doors. These doors shall be provided with electric locks, and shall operate on fail-safe principle. The lock shall remain unlocked in the event of a fire alarm or in the event of a power failure. The fire alarm supplier shall make potential free contacts available for releasing the locks in a fire condition especially for staircase and main doors. Entry to the restricted area shall be by showing a proximity card near the reader and exit shall be using a push button installed in the secure area. The system shall monitor the status of the doors through magnetic reed contacts. The system should be designed and implemented to provide following functionality: Controlled Entries to defined access points Controlled exits from defined access points Controlled entries and exits for visitors

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 80 of 99

Volume II Technical and Functional Specifications

Configurable system for user defined access policy for each access point Record, report and archive each and every activity (permission granted and / or rejected) for each access point. User defined reporting and log formats Fail safe operation in case of no-power condition and abnormal condition such as fire, theft, intrusion, loss of access control, etc. Day, Date, Time and duration based access rights should be user configurable for each access point and for each user. One user can have different policy / access rights for different access points.

2.2.13.1

Visitor Management System

The security requirements of Data Centre and infrastructure are challenging and growing increasingly. Visitors shall be screened, registered, signed in quickly and allowed to visit only the relevant areas via integration with access control areas via integration with access control devices. These challenges of the visitor management and lobby management activities are seamlessly and efficiently managed by Visitor Management System. The activities shall include: Provision for storage and use of computerized photo of the visitors Each pass has necessary details of the visitor Information and alarms to the security about those visitors, who are in premises after allowable time List of visitors inside the premises, whenever, required Permission for future visitors in advance Daily, Weekly and Monthly report generation of the visitors Extensive query support Duration of stay of each visitors Give details of all visitors visited in the past without delays Data backup facility Data is stored using latest compression techniques

2.2.14 CCTV System


The Critical area of the Data Centre along with the Non Critical area needs to be under constant video surveillance. The primary objective of implementing a CCTV
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 81 of 99

Volume II Technical and Functional Specifications

system is to ensure effective surveillance of the area and also create a record for post event analysis. Monitoring cameras should be installed in proper areas to cover all the critical areas of the data centre. The scope of work involves supply, installation, commissioning, testing and maintenance of the Closed Circuit Television system for State Data Centre. The CCTV system shall provide an on-line display of video images on monitor. The entire setup shall be monitored from the control room on 24/7 basis. Cameras with suitable lenses shall be used to view all the critical areas of the Data Centre, Reception and Corridor. The CCTV system shall be based on the use of fixed dome cameras and integrated pan/tilt/zoom cameras that can be controlled from control room location. The CCTV System shall be a combination of color fixed and PTZ designed for continuous duty. The system and each of its devices shall be designed to meet the site ambient temperature and the site environmental conditions and shall operate satisfactorily under the specified permitted voltage and frequency variation band of the power supply source system. All outdoor cameras shall be IP 66 rated. The CCTV System proposed to fulfill the overall surveillance / observation requirements and enhance the level of security necessary in a software establishment such as ours which shall be complete in all respects and shall comprise of following minimum items. A set of fixed dome cameras and integrated pan / tilt / zoom, (PTZ) cameras with remote control operation of focus and zoom. A professional housing with internal and external cooling fans to protect both the camera and lens from the rigors of all environments and at the same time it should be designed and built for ease of installation and maintenance. A complete CCTV control facility that performs all the functions with provision to increase the total number of inputs for each monitor site. CCTV Cabinets as required complete with all cable termination facilities, cable distribution system for video and power system along with any additional video amplifiers and other video equipment as may be required. End point amplifiers as may be required to achieve satisfactory system operation. Test equipment covering all tools, tackles and testing equipment / kits as required for preventive and first line maintenance including test monitors, camera adjustment and testing facilities. Complete range of accessories as required.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 82 of 99

Volume II Technical and Functional Specifications

All necessary relay boxes connectors, extension cables and adapter boxes as required at each of the ends of the CCTV System as required. All systems and components shall have been thoroughly tested and proven in actual use. All systems and components shall be provided with a one-day turnaround repair express and 24-hour parts replacement. The manufacturer on warranty and non-warranty items shall guarantee the repair and parts expresses. Specifications included in this section are indicative and considered as a minimum; component and software that shall be acquired at the time of implementing the project shall be the latest versions available in the market.

General

The system also should provide clear & accurate indication of an intruder or abnormal movement within and around the Facility. System Capabilities The system shall provide visual images from the cameras located through out the facility. The cameras located shall be fed into the Digital Video Server (DVS) located in the security room. The Digital Video Server shall consist of 2 x 16 channels Digital Multiplexer with built-in recording system into Hard Disk. The Main Security Control Room which shall house the Monitors and the Digital Video Management Server. The CCTV should be equipped with Digital recording facility for later scrutiny, with at least 30 days of recording facility.

Technical Requirements Cameras The cameras will be of 1/3 format CCD pickup device for fixed lens camera and format for PTZ cameras . The cameras are being used for special observation purposes and are being located both indoor and outdoor & mounted on specially designed suitable mounting arrangement for operation under all severe environmental conditions to which these will be subjected especially the outdoor locations. The cameras being used at these locations shall have the following basic minimum requirements. The cameras shall be fixed dome camera and integrated Pan/Tilt/Zoom camera type that can be controlled from its monitor position, such that the cameras can be panned, tilted, zoomed and focused on to any part or entire area which they have been located to bring under observation from keyboard location.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 83 of 99

Volume II Technical and Functional Specifications

The cameras shall be complete with the latest state of the art optical systems, filters, light sensitive pickup systems suitable for capturing images with very low light levels, and necessary interlaced scanners, encoders, decoders, associated amplifiers, synchronization facilities and any interfacing adapters as required, with all systems of that type suitable for a compact, durable, distortion free and clear image processing type camera. The color cameras (Integrated Pan/Tilt/Zoom dome) shall have a minimum resolution of 420 lines and sensitivity of 0.08 lux (colour) and 0.013 lux (monochrome). The outdoor PTZ cameras shall be day/night camera with a minimum of 23 X optical zoom and 12 X digital zoom The Outdoor PTZ camera shall have a minimum of 80 X wide dynamic range, to withstand complex light variations in the environment. The preset accuracy for the camera shall be +/- 0.1degree maximum The Outdoor PTZ camera shall have a preset speed of 360 deg /sec Pan and 200 deg /sec tilt. The camera shall resume after alarm to the previously programmed state of alarm after alarm acknowledgement. The outdoor PTZ camera shall have auto flip feature, whereby which the dome shall rotate at 180 deg at the bottom of the tilt travel. The cameras shall have automatic level control complete with auto iris, and gain control of the amplifier and shall be complete with spot filter as required. The cameras shall have automatic shutter or 100% closing iris to prevent burning-in of image pickup device when the camera is not in use, both the shutter and iris shall fully close upon failure of power supply in order to prevent damage. The cameras shall have standby circuitry for when the camera is not selected on any of the monitors. The beam current of the camera pickup device shall be switched off automatically. The cameras shall have automatic circuitry which relates the black level in the signal to the darkest spot of the picture (black level control), limits the video signal in case of scene high-lights in order to prevent overloading of the monitor (White limiter), and prevents the automatic sensitivity control from reacting to strong highlights (Peak white eliminator).

The cameras shall have the features that shall prevent the occurrence of internal condensation or condensation on the window, necessary heaters/thermostats shall be provided as required. The cameras shall be equipped with Pan & Tilt heads to allow for rotation over a minimum 360 degrees. The cameras shall be provided with a local power distribution junction box, with local isolation switches and fuses to isolate each of the power circuits of

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 84 of 99

Volume II Technical and Functional Specifications

the camera related to main camera power, and other circuits related to Pan & Tilt head, cooling fan, blower etc. The camera housing shall have a rain/sun shield and a weather protection feature with a minimum IP protection of IP66 for outdoor mounted cameras. For indoor cameras, the protection class shall be IP45. The aperture ratio (f-number) of the lenses shall be selected such that, a good picture is obtained at night. Power supply units, as required for the cameras, shall be provided.

Each of the CCTV cameras shall be located, mounted, positioned and install such that: The camera and its supporting structures presence least obstruction of view and least obstruction for satisfactory movement and operation of the camera due to remote and local controls. The cameras shall not be mounted on vibrating structures, where this is not possible than special structures or other facilities/measures for reducing vibrations shall be provided. All the camera movements along with Pan and Tilt, and associated forces on structures are taken in to account during the design and installation of the cameras. The installation presence the least risk of accidental damage. The equipment and its components are accessible for maintenance. The vibration of any object shall be less than that specified for the camera.

Monitors There shall be total of 2 nos. of 21 monitors for each Digital Video Recorder one to view the multiplexed output second to view the switched output. This monitor should be located in the main control room. The monitor shall be positioned such that room lights and windows are minimized. The monitors may also be built in to the control desk as appropriate. Each of the monitors used at the main control room and operator status shall have the following basic minimum requirements. The monitor shall be suitable for use as desktop units. The monitors shall be high-resolution video monitors. The monitor shall have a bandwidth of at least 10 MHz (-3dB) and a horizontal resolution in the center of the picture minimum 420 lines in the case of color monitor. The monitors shall have the facilities to loop the video signal through the other monitor.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 85 of 99

Volume II Technical and Functional Specifications

Each monitor shall have local control knobs and remote control equipment and panel for monitor controls associated with power on/off switch standby on/off switch and for adjustment brightness, contrast, horizontal hold, vertical hold etc. Monitor shall be suitable for use as desktop units or can be rack mounted with suitable racks as appropriate.

Video & Telemetry Cables The video signal shall be transmitted using co-axial cable and control of all zoom lens and Pan-Tilt functions through twisted pair interconnected between receiver and DVR. Cabling for CCTV shall cover: Video link Remote control of cameras in terms of its control of pan tilts zooms & focus. Power supply cables.

The cable shall be shielded or provided with facilities to avoid interference between signals. The transmission losses shall be minimized and where required for satisfactory operation correction amplifiers are cable equalizes shall be provided in the monitors on the CCTV cabinets. Cabinets CCTV cabinets shall be provided near set of monitors. The cable from the cameras shall be terminated in this cabinet from where these signals are distributed to the monitors. All necessary video amplifiers, interfaces etc. that forms the part of the CCTV system shall be installed in the cabinet. Dome Camera The Dome camera unit shall be 1/3 CCD Color Dome camera and shall provide a minimum of 540 TV lines resolution. It shall have built-in 3 -9mm varifocal lens. The camera shall operate on minimum lux level not more than 0.15 lux .The complete unit shall be housed in a integrated dome and base unit, both preferably made from injection moulded plastic. It shall be possible to adjust the camera head inside the dome in both the planes so that it can be wall or ceiling mounted. The camera shall operate on 24 V AC or 12 volts D.C. Digital Video Recorder (DVR)
__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 86 of 99

Volume II Technical and Functional Specifications

The DVR shall provide a high quality recorder capable of storage and play back of images from at a rate of up to 400 FPS(PAL) and shall posses an internal watchdog, duplex operation, Windows NT operating system, watermarking of each frame, 8 alarm inputs, software configurable video motion detection and scheduled event recording. The digital recorder shall comply or exceed the following design and performance specifications: The DVR Digital video recorder shall have 400 images/sec viewing speed as well as 40 images / sec recording speed The recorder shall have a minimum of 2 x 16 video inputs. It shall also have looping inputs for all 2 x 16 inputs The recorder shall run on Windows NT . The recorder shall provide PAL , the following recording resolutions shall be possible 320 x 288 / 640 x 288 / 640 x 576 / 352 x 288 / 704 x 288 / 704 x 576 The DVR shall have 4 high speed USB ports The DVR shall be in a position to display 16 video images simultaneously on the DVR or the remote client from Multiple DVRS on the LAN. The recorder shall support instant playback and shall have programmable favorite channel selection. The recorder shall allow a minimum of 6 X digital zoom on playback The recorder shall support simultaneous playback and record full duplex operation. The recorder shall have the feature of an internal hardware watchdog. The reorder shall have an internal hard disc capacity of minimum 1 TB. The DVR shall be of the same make as that of the cameras to ensure 100% system compatibility. All the components in the DVR including hard disc etc shall be provided for the manufactures factory not locally assembled DVRS shall be provided. 100 % finished goods shall be supplied from the manufacturer The DVR shall have each channel individually programmable. Remote workstation shall be in a position to administer / view live images / search and view playback images The recorder shall have 32 hard-wired alarm inputs, which shall be capable of configuring globally as normally open or normally closed. Each of these inputs shall be assigned to any or all of the cameras to trigger recording at custom record rates. Up to 5 seconds of pre-alarm shall also be available on each camera.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 87 of 99

Volume II Technical and Functional Specifications

The recorder shall provide 24 dry contact outputs, each of which shall be associated with any or all of the camera inputs and/or alarm inputs. The recorder shall provide an extremely flexible scheduling on a week-byweek basis. Each 24-hour period shall be divided into 15-minute blocks enabling different configurations of recording triggers to be available during each 15-minute period. The recorder shall provide onscreen controls for operation of PTZ cameras. All fully functional cameras shall be controlled via a PC comport which shall use an additional converter to communicate via RS 485 / 422

The recorder shall provide an Ethernet port as standard. If required in addition free client software shall supplied which enables remote control and connectivity via TCP/IP. The DVR shall support Gigabit port 10/100/1000 base T The recorder shall be tested to comply with UL regulations/certifications. The recorder shall provide a screen resolution of 1280 x1024 ( XVGA output ) The recorder shall have a built in watchdog that will automatically restart after a power failure and begins to record as per its configured settings. The recorder shall provide the ability to manually back up recorded data to hard disk or DVD / RAID while the unit continues to record. The recorder shall be programmed using a keyboard and mouse via on screen menus. The recording of the recorders are watermarked and encrypted requiring backup software to open and view them. In addition, images backed up in bitmap or JPEG format can be verified for authenticity The recorder shall be suitable for mounting on a standard 19 rack. There shall be a network management Digital Video Recorder (DVR) if more than DVR is required to allow viewing of cameras from multiple DVRs in any combination. The DVR shall support pre-alarm and post alarm recording. The DVR shall support CIF / 2CIF and 4 CIF resolutions while recording.

2.2.15 Building Management System (BMS)


The building management system shall be implemented for effective management, monitoring and Integration of various components like HVAC systems, Access Control systems, fire detection system etc. The BMS shall perform the following general functions including but not limited to: Building Management & Control Data Collection & archival Alarm Event & Management Trending

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 88 of 99

Volume II Technical and Functional Specifications

Reports & MIS Generation Maintenance & Complaint Management

The scope of work shall include designing supplying and installing of Building management (Automation) System. The work shall consist of furnishing all materials, equipment's and appliances necessary to install the said system, complete with Sensors, Direct Digital Controllers, Communication Controllers and Supervisory Software complete with necessary software/hardware support for interfacing with other systems. It shall include laying of cabling duct, conduits and power supply etc., necessary for installation of the system with supply of appropriate type products as indicated in the specification and Bill of Quantities. The controller shall be 32 bit based Microprocessor Controller and shall sit directly on the TCP / IP network. The Controller shall be Web Based, Web Enabled, Real Time Clock, and Web Browser with Communication speed min of 10 Mbps. Agency shall design & provide a full Building automation system on the basis of truly distributed intelligence and shall comprise of the following general functional sub systems. Air Conditioning Management & Control o Precision AC Units o Temperature monitoring and controls at all specified positions/locations Energy Management o LT Panel Energy Monitoring o UPS Monitoring Safety & Security Systems Integration o Fire Alarm System Integration o VESDA (Very Early Smoke Detection Alarm) System Integration o Access Control & Surveillance System Integration o Gas System Integration Integration o DG Set on MODBUS Protocol with RS 485 Communication Port o Energy Meter on MODBUS Protocol with RS 485 Communication Port

2.2.16 Water Leak Detection System


The water leak detector shall be installed to detect any seepage of water into the critical area and alert the Security Control Room for such leakage. It shall consist of water leak detection cable and an alarm module. The cable shall be installed in the ceiling & floor areas around the periphery. Water Leak Detection system should be for the Server and Network room Areas to detect and water flooding below the floor of the DC.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 89 of 99

Volume II Technical and Functional Specifications

Water Leak Detection System should be wire based solution with alarm; the wire needs to lay in DC surrounding the PAC units, which is the probable source of water leakage.

2.2.17 Fire Proof Enclosures for Media Storage


The overall design of the safe should be suitable for safe storage of computer diskettes, tapes, smart cards and similar devices and other magnetic media, paper documents, etc. the safe should have adequate fire protection. Capacity Temperature to Withstand Internal Temperature Locking 300 Litres 1000 C for at least 1 hour 30 C after exposure to high temperature For 1 hour 2 IO-lever high security cylindrical / Electronic lock

2.2.18 Public Address System


The PA system is required for: Making public announcement from the Security Control Room and Facility Managers room. Clear and crisp announcement should reach to the entire Facility area. Microphones should be provided to make announcements / respond to announcement from the designated location within the Facility. To play light music if required.

2.2.19 Common Alarm System


The common alarm panel is required for checking the healthiness of all systems, to be installed at Data center. The panel can be installed in the room of Security Officer at Data center.

The common alarm panel should have provision for accepting potential free signals from all system for relevant status change in that system.

2.2.20 Physical Security


DCO should make provision for the physical security at the proposed State Data Centre.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 90 of 99

Volume II Technical and Functional Specifications

2.2.21 Electrical Panels


The Panels shall be of compartmentalize design so that circuit arc / flash products do not create secondary faults and be fabricated out of high quality CRCA sheet, suitable for indoor installation having dead front operated and floor mounting type. All CRCA sheet steel used in the construction of Panels shall be 2 mm. thick and shall be folded and braced as necessary to provide a rigid support for all components. Joints of any kind in sheet steel shall be seam welded, all welding slag grounded off and welding pits wiped smooth with plumber metal. The Panels shall be totally enclosed, completely dust and vermin proof and degree of protection being not less than IP: 54 to IS: 2147. Gaskets between all adjacent units and beneath all covers shall be provided to render the joints dust proof. All doors and covers shall be fully gasketed with foam rubber and /or rubber strips and shall be lockable. All panels and covers shall be properly fitted and secured with the frame and holds in the panel correctly positioned. Fixing screws shall enter into holes, taped into an adequate thickness of metal or provided with bolts and nuts. Self-threading screws shall not be used in the construction of Panels. A base channel of 75 mm. x 50 mm. x 6 mm. thick shall be provided at the bottom. Panels shall be preferably arranged in multi-tier formation. The size of the Panels shall be designed in such a way that the internal space is sufficient for hot air movement. If necessary, openings shall be provided for natural ventilation, but the said openings shall be screened with fine weld mesh. The entire electrical component shall be derated for 50c. The Panels shall be provided with removable sheet steel plates at top and bottom to drill holes for cable / conduit entry at site. The Panels shall be designed to facilitate easy inspection, maintenance and repair. The Panels shall be sufficiently rigid to support the equipment without distortion under normal and under short circuit condition. They shall be suitably braced for short circuit duty

Circuit Compartments Each MCCB shall be housed in separate compartments and shall be enclosed on all sides. Sheet steel hinged lockable door shall be duty interlocked with the unit in `ON and `OFF position. All instruments and indicating lamp shall be mounted on the compartment door. Sheet steel barriers shall be provided between the tiers in a vertical section.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 91 of 99

Volume II Technical and Functional Specifications

Instrument Compartments Separate adequate compartment shall be provided for accommodating instruments, indicating lamps, control contactors/ relays and control fuses etc. These components shall be accessible for testing and maintenance without any danger of accidental contact with live parts, bus bar and connections Busbars The busbar shall be air insulated and made of high quality, high conductivity, high strength Aluminum. The busbar shall be of 3 phases and neutral system with separate neutral and earth bar. The size of neutral busbar in all main panels or lighting panels and feeders for panel shall be equal to phase busbar. The busbar and interconnection between busbars and various components shall be of high conductivity Aluminum. The busbar shall be of rectangular cross-section designed to withstand full load current for phase busbars and half rated current for neutral busbars in case of MCC panels only and shall be extensible on either side. The busbar size shall be as per the rating of the panel. The busbar shall have uniform cross-section throughout the length. The busbars and interconnections shall be insulated with epoxy-coated busbar. The busbar shall be supported on bus insulators of non flammable type with high creepage and high anti tracking property and non-hydroscopic SMC / DMC insulated supports at sufficiently close intervals to prevent busbars sag and shall effectively withstand electromagnetic stresses in the event of short circuit. The busbar shall be housed in a separate compartment. The busbar shall be isolated with 3-mm. thick bakelite sheet to avoid any accidental contact. The busbar shall be arranged such that minimum clearance between the busbar are maintained as below: o Between phases : 25 mm. minimum o Between phases and neutral : 25 mm. o Between phases and earth : 25 mm. o Between neutral and earth : 20 mm. minimum All busbar connections shall be done by drilling holes in busbars and connecting by chromium plated or tinned plated brass bolts and nuts. Additional cross-section of busbar shall be provided in all Panels to cover up the holes drilled in the busbar. Spring and flat washers shall be used for tightening the bolts.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 92 of 99

Volume II Technical and Functional Specifications

All connections between busbars and circuit breakers / switches and cable terminals shall be through aluminum strips of proper size to carry full rated current. These strips shall be insulated with insulating taps. Panel to panel entry of bus bar shall be effectively sealed by electrical and thermal insulation barriers so that products of flashover do not travel from one panel to another panel creating multiple faults. Busbar calculated on 50 deg. C. ambient temp. and 85 deg. C. for continuous and short time rating. Busbar surrounded air temp. shall be considered 70 deg. C. for busbar calculation All joint shall have non-flammable insulation shrouds for secondary insulation purpose

Electrical Power and Control Wiring Connection Terminal for both incoming and outgoing cable connections shall be suitable for 1100 V grade, aluminum / copper conductor XLPE insulated and PVC sheathed, armored cable and shall be suitable for connections of solder less sockets for the cable size as per the feeder capacity. Power connections for incoming feeders of the main Panels shall be suitable for 1100 V grade aluminium conductor (XLPE) cables. Both control and power wiring shall be brought out in cable alley for ease of external connections, operation and maintenance. Both control and power terminals shall be properly shrouded. 10% spare terminals shall be provided on each terminal block. Sufficient terminals shall be provided on each terminal block, so that not more than one outgoing wire is connected to per terminal. Terminal strips for power and control shall preferably be separated from each other by suitable barriers of enclosures. Wiring inside the modules for power, control, protection and instruments etc. shall be done with use of 660 / 1100 V grade, FRLS insulated copper conductor cables conforming to IS. For current transformer circuits, 2.5 sq.mm. copper conductor wire shall be used. Other control wiring shall be done with 1.5 sq.mm. copper conductor wires. Wires for connections to the door shall be flexible. All conductors shall be crimped with solder less sockets at the ends before connections are made to the terminals. Control power supply to modules through the control transformer Control power wiring shall have control fuses, (HRC fuse type) for circuit protection. All indicating lamps shall be protected by HRC fuses. Particular care shall be taken to ensure that the layout of wiring is neat and orderly. Identification ferrules shall be filled to all the wire termination for ease of identification and to facilitate checking and testing

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 93 of 99

Volume II Technical and Functional Specifications

Terminals The outgoing terminals and neutral link shall be brought out to a cable alley suitably located and accessible from the panel front. The current transformers for instruments metering shall be mounted on the disconnecting type terminal blocks. No direct connection of incoming or outgoing cables to internal components of the distribution board is permitted; only one conductor may be connected in one terminal

Cable Compartments Cable compartments of minimum 300 mm size shall be provided in the Panels for easy termination of all incoming and outgoing cables entering from bottom or top. Labels Engraved PVC labels shall be provided on all incoming and outgoing feeders. Single line circuit diagram showing the arrangements of circuit inside the distribution board shall be pasted on inside of the panel door and covered with transparent laminated plastic sheet. Adequate supports shall be provided in the cable compartments to support cables. All outgoing and incoming feeder terminals shall be brought out to terminals blocks in the cable compartment.

Name Plates A nameplate with the Panels designation in bold letters shall be fixed at top of the central panel. A separate nameplate giving feeder details shall be provided for each feeder module door. Inside the feeder compartments, the electrical components, equipments, accessories like switchgear, control gear, lamps, relays etc. shall suitably be identified by providing stickers. Engraved nameplates shall preferably be of 3 ply, (Red-White-Red or BlackWhite-Black) lamicold sheet. However, black engraved perplex sheet name plates shall also be acceptable. Engraving shall be done with square groove cutters. Nameplate shall be fastened by counter sund screws and not by adhesives

Danger Notice Plates


__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 94 of 99

Volume II Technical and Functional Specifications

The danger notice plate shall be affixed in a permanent manner on operating side of the Panels. The danger notice plate shall indicate danger notice both in Hindi and English and with a sign of skull and bones. The danger notice plates, in general, meet the requirements of local inspecting authorities. Overall dimensions of the danger notice plate shall be 200 mm. wide x 150 mm. high. The danger notice plate shall be made from minimum 1.6 mm. thick mild steel sheet and after due pre-treatment to the plate, the same shall be painted white with vitreous enamel paint on both front and rear surface of the plate. The letters, the figures, the conventional skull and bones etc. shall be positioned on plate as per recommendation of IS : 2551-1982. The said letters, the figures and the sign of skull and bones shall be painted in signal red colour as per IS : 5-1978. The danger plate shall have rounded corners. Location of fixing holes for the plate shall be decided to suit design of the Panels. The danger notice plate, if possible, it should be of ISI certification mark

Moulded Case Circuit Breakers The moulded case circuit breaker (MCCB) shall be air break type and having quick make - quick break with trip free operating mechanism. Housing of the MCCB shall be of heat resistant and flame retardant insulating material. Operating handle of the MCCB shall be in front and clearly indicate ON/OFF/TRIP positions. The electrical contact of the circuit breaker shall be of high conducting nondeteriorating silver alloy contacts. The MCCB shall be provided microprocessor based overload and short circuit protection device. All the releases shall operate on common trip busbar so that in case of operation of any one of the releases in any of the three phases, it will cut off all the three phases and thereby single phasing of the system is avoided. The MCCB shall provide two sets of extra auxiliary contacts with connections for additional controls at future date.

Contactors The contactors shall meet with the requirements of IS : 2959 and BS : 7755.

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 95 of 99

Volume II Technical and Functional Specifications

The contactors shall have minimum making and breaking capacity in accordance with utilization category AC3 and shall be suitable for minimum Class II intermittent duty. If the contactor forms part of a distribution board then a separate enclosure is not required, but the installation of the contactor shall be such that it is not possible to make an accidental contact with live parts

Indicating Lamps Indicating lamps assembly shall be screw type with built in resistor having non-fading colour lens. LED type lamps are required. Wiring for Remote ON, OFF, TRIP indicating lamp is required. Colour shade for the indicating lamps shall be as below : o ON indicating lamp : Red o OFF indicating lamp : Green o TRIP indicating lamp : Amber o PHASE indicating lamp : Red, Yellow, Blue o TRIP circuit healthy lamp : Milky

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 96 of 99

Volume II Technical and Functional Specifications

SECTION III Compliance

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 97 of 99

Volume II Technical and Functional Specifications

3 Section III- Compliance to Specifications


All the hardware specifications mentioned in the RFP are the required minimum, higher or better specifications would be acceptable. Component furnished shall be complete in every respect with all mountings, fittings, fixtures and standard accessories normally provided with such component's and/or needed for erection, completion and safe operation of the component's as required by applicable codes though they may not have been specifically detailed in the technical specification, unless included in the list of exclusions. All similar standard components/parts of similar standard components provided shall be inter-changeable with one another. The methodology of cabling and installation work to be adopted for the State Data Center has to ensure minimum damage to the existing structure of the building. Any damage to the existing flooring/ walls/paint etc. shall be made good by the selected bidder. It is advised that bidder should visit site before submitting the tender to get apprised about the site conditions. The selected bidder shall be responsible for providing all materials, components, and services, specified or otherwise, which are required to fulfill the intent of ensuring operability, maintainability, and reliability of the complete component covered under this specification within his quoted price. This work shall be in compliance with all applicable standards, statutory regulations and safety requirements in force of the date of award of this contract. The selected bidder shall also be responsible for deputing qualified personnel for installation, testing, commissioning and other services under his scope of work as per this specification. All required tools for completing the scope of work as per the specification is also the responsibility of the selected bidder. The selected bidder shall perform the services and carry out its obligations with all due diligence, efficiency and economy in accordance with generally accepted professional techniques and practices and shall observe sound management practices and employ appropriate advance technology and safe methods. The selected bidder shall always act in respect of any matter relating to this contract or to the services as faithful advisers to the SDA. The selected bidder shall furnish complete, well-fabricated and reliably operating and secure systems to SDA. Design and selection of component and software shall be consistent with the requirements of long term trouble free operation with highest degree of reliability and maintainability. All components shall be constructed to operate safely without

__________________________________________________________________________________ RFP for State Data Center, Andhra Pradesh Page 98 of 99

Volume II Technical and Functional Specifications

undue heating, vibration, wear, corrosion, electromagnetic interference or similar problems and all software shall be proven, tested and reliable. All interconnecting cables required to connect the communication component shall be furnished. All cables shall be fully assembled connector preterminated and factory tested as part of overall system checkout. Cables shall be neatly & properly tied up and dressed using appropriate cable hangers and Velcro bands. All the cables, connectors, sockets, panel's etc. shall be labeled for identification purpose. All the cabling should adhere to the TIA-942 Data Center Standard. All component, accessories and cables supplied under this contract shall be in accordance with the latest applicable recommendations, regulations and standards of: CCITT/ITU ANSI IEC 60364 IEEE Standard 1100 IETF TIA 942 ISA 3843 EIA/TIA 568 Standards NFPA 72 and NFPA 318 International Electro-technical Commission (IEC) Cable (Cat 6) and cable accessories (Cat6) UL Listed and verified

For parameters not covered under the above codes, internationally acceptable standards shall be accepted. The selected bidder shall furnish a complete list of all standards and codes under which his component is designed, manufactured and assembled along with the bids. Functionality/accessibility of each component of the system and the system as a whole should be demonstrated to the satisfaction of SDA. Reliable over voltage and over current protection circuits shall be provided in the component power supply units. The component power supply units shall be self protecting and also protect connected component's against interference, noise, voltage dips and surges & impulses that may be present in the mains power supply sources. Component shall be guaranteed for operation over the following AC power range to be made available by SDA: 240 V AC +/-10%, 50 Hz +/- 5% The SDA shall provide suitable AC power at a single power point at one locations and distribution of this power to the various component's shall be responsibility of the selected bidder for which necessary distribution board, cable etc. shall be provided by the selected bidder.