Sie sind auf Seite 1von 12

Solar Powered BTS System

APPLICATIONS
Cellular/GSM Repeaters Microwave Radio Repeaters Telephone Exchanges Fiber Optic Repeaters Earth Stations TV Translators Relay Stations

Advantages
Integrated system with highly efficient PV module, long service life of 25 years. Simple to install and less maintenance required. Easy transportation with light weight. Reduce fossil fuel dependency,environmental friendly. Reliable and clock round telecommunications services even in remote area. Seamless integration into existing power systems. PV can easily be combined with diesel generator sets for a hybrid system.

Quality and Warranty


Rigorous quality control system meeting the highest international standards: ISO9001:2008 and ISO 14001:2004 25 years power output warranty for module

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

BTS System Sizing


SOLAR BTS SYSTEM SIZING
DC Power System Voltage BTS Power Requirement Running Hour Autonomy Day AC Power PV Technology Type No. of Panel PV Panels PV System Size No. of Series No. of Parallel PV Area Type Controller Optimum Working Current Remote monitoring Type Voltage Capacity Battery No. of Series No. of Parallel Quantity of battery Total Capacity PV mounting system Cable & accessary Inverter 2V 200 Ah 24 1 24 48V200Ah 2V 600 Ah 24 1 24 48V600Ah 8 pcs 1440 W 2 4 15 m2 48V30A 20 A 20 pcs 3600 W 2 10 40 m2 48V100A 50 A 100 W 300 W -48V DC 24 hrs/day 3 days 500 W -48V DC 24 hrs/day 3 days Optional Crystalline Silicon STP180S-24/Ad 32 pcs 5760 W 2 16 60 m2 48V150A 80 A Optional Lead Acid battery or Gel battery 2V 1000 Ah 24 1 24 48V1000Ah 2V 800 Ah 24 2 48 48V1600Ah 2V 1000 Ah 24 2 48 48V2000Ah 2V 1500 Ah 24 2 48 48V3000Ah 50 pcs 9000 W 2 25 90 m2 48V200A 125 A 64 pcs 11520 W 2 32 120 m2 48V250A 160 A 76 pcs 13680 W 2 38 140 m2 48V300A 190 A 800 W -48V DC 24 hrs/day 3 days 1000 W -48V DC 24 hrs/day 3 days 1200 W -48V DC 24 hrs/day 3 days

-48V DC
24 hrs/day 3 days

Customized according to project requirement and installation method Customized according to project requirement and installation method Optional according to BTS AC power requirement

Note: Usually, BTS is -48V DC system , if there is any AC load, inverter could be used accordingly. BTS system should be customized by detail project requirement. Battery backup designed for 3 days. Minimum Monthly Averaged Insolation considered as 4.5KWh/day.

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Repeater

Battery

Charge Controller

Inverter

AC Loads

PV Module

PV Module
Series
Optimum Operating Voltage (Vmp) Optimum Operating Current (Imp) Open-Circuit Voltage (Voc) Short-Circuit Current (Isc) Maximum Pwer at STC (Pmax) Operating Temperature Maximum System Voltage Maximum Series Fuse Rating Power Tolerance Total Weight Size (mm)

STP180S-24/Ad
36.0 V 5.00 A 44.8 V 5.29A 180 W -40 C to +85 C 1000 V DC 15 A 0/+5 W 17.2 kgs (37.9 lbs.) 1580 x 808 x 35

STP280-24/Vd
35.2 V 7.95 A 44.8 V 8.33 A 280 W -40 C to +85 C 1000 V DC 20 A 0/+5 W 27 kgs (59.5 lbs.) 1956 x 992 x 50

Product Photo

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Controller
Rated Voltage (V) Rated Current (A) Max. Solar Module power(KWp) Max. Number of Strings Max. Current of String(A) Battery Low Voltage Disconnect (LVD) (Adjustable) Battery Low Voltage Reconnect (LVR) (Adjustable) Battery Charge Disconnect (Adjustable) Load-over-voltage Protection Point (Adjustable) Load-over-voltage Recovery Point (Adjustable) Power Consumption (mA) Solar Array and Battery(V) Battery and load(V) 30 1.44 1 30 60 2.4 2 100 4.8 4 25 43.2 49.2 57.6 70 60 <100 0.3 0.1 0 ~ 5(Adjustable) -20 ~ +50 5000 IP20 400482177(4U) 455482266 (6U) 6006001200 DC48 150 7.2 6 200 9.6 6 34 300 14.4 10 30

Voltage Drop

Temperature compensation coefficient(mv/C) Environment Temperature(C) Altitude(m) Protection Level Dimensions (D W H) (mm)

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Inverter
Input Voltage (V) Input Current (A) Input Volage range (V) Capacity (KVA) Output Power (KW) Output Voltage Frequency Output Current (A) Output Voltage Accuracy (V) Output Frequency Accuracy (Hz) AC Input Waveform Distortion (linear load) Dynamic Response (load 0 ~ 100%) Power Factor Overload Peak factor Nverter Efficiency (80% resistive load) Environment Temperature(C) Altitude(m) Protection Level Dimensions (D W H) (mm) Dimensions (D W H) (mm) 205365425 482177440 84% -20 ~ +50 5000 IP20 400 750 470 2.2 AC220V3% 500.05 5% 5% 0.8 120%,10 sec 3:1 86% 90% 0.5 0.4 25 21~32 1 0.8 AC220V , 50Hz 9.0 13.6 22.7 2 1.6 DC 24 50 24 48 42~64 3 2.4 5 4 DC 48 73 116

DC Input

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Project Reference

Base transmit station in China PV system capacity is 1.02KW Telecom equipment and PV system are all outdoor installed DC load 100W

Equipment list
SN
1 2 3 4 5 6 7

Name
PV Module Controller Bracket Battery Junction Box Wires Others

Model
STP-170S-24/Ac 48V 20A AT-2*3-Ac 200Ah 2V STB-3/4-P/Z BVR4mm2

Quan.
6 1 1 24 9 20 1

Unit
pcs set set pcs pcs m set

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Project Reference

Base-central station in Laos PV system capacity is 13.2KW DC load 400W, AC load 800W

Equipment list
SN
1 2 3 4 5 6 7 8 9

Name
PV Module Controller Inverter Bracket Battery Junction Box Distribution Box Wires Others

Model
STP-165S-24/Ac 48V 200A 220V 1000W AT-4*10-Ac 2500Ah 2V STB-4/1-P/Z STB-2/8-J BVR4mm2 BVE10mm2

Quan.
80 1 1 2 24 2 1 500 200 1

Unit
pcs set set set pcs pcs pcs m m set

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Project Reference

Microwave station in Mongolia PV system capacity is 10.4KW DC load 700W

Equipment list
SN
1 2 3 4 5 6 7 8

Name
PV Module Controller Bracket Battery Junction Box Distribution Box Wires Others

Model
STP-165S-24/Ac 48V 100A AT-4*10-Ac 1200Ah 2V STB-4/1-P/Z STB-1/4-J BVR4mm2 BVE10mm2

Quan.
40 1 1 24 1 1 300 100 1

Unit
pcs set set pcs pcs pcs m m set

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Case Study
Base transmit station in China PV system capacity is 1.02KW Module: STP170S-24/Ac Quantity: 6pcs Controller: 48V/30A

Base transmit station in Niger PV system capacity is 9.9KW Module: STP165S-24/Ac Quantity: 44pcs Controller: 48V/150A

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Case Study
Base-central station in Laos PV system capacity is 13.2KW Module: STP165S-24/Ac Quantity: 80pcs Controller: 48V/300A

Base-central station in Sudan PV system capacity is 6.48KW Module: STP180S-24/Ac Quantity: 36pcs Controller: 48V/150A

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Case Study
Microwave station in Mongolia PV system capacity is 6.6KW Module: STP165S-24/Ac Quantity: 40 pcs Controller: 48V/150A

Base transmit station in Burkina Faso PV system capacity is 6.27KW Module: STP170S-24/Ac Quantity: 20 pcs Controller: 48V/100A

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Case Study
Microwave station in Ethiopia PV system capacity is 9.9KW Module: STP165S-24/Ac Quantity: 60 pcs Controller: 48V/200A

Microwave station in Congo PV system capacity is 4.16KW Module: STP160S-24/Ac Quantity: 26 pcs Controller: 48V/100A

Copyright 2010 Suntech Power

www.suntech-power.com

EN-CSS-DX-NO1.01-Rev 2010

Das könnte Ihnen auch gefallen