Page 1
AB DE-ION
Circuit Breakers
April 1998
Breaker Description
Curve No.
Page
Types EB, EHB; MARK 75 Type HFB; 15-40 Amperes, 1 Pole ................
Types EB, EHB; MARK 75 Type HFB; 50-70 Amperes, 1 Pole ................
Types EB, EHB; MARK 75 Type HFB; 90-100 Amperes, 1 Pole ..............
Types EB, EHB, FB; MARK 75 Type HFB; 15-40 Amperes, 2, 3 Poles ...
Types EB, EHB, FB; MARK 75 Type HFB; 50-70 Amperes, 2, 3 Poles ...
Types EB, EHB; 90-100 Amperes, 2, 3 Poles ............................................
Type FB; MARK 75 Type HFB; 90-150 Amperes, 2, 3 Poles ...................
Type FB Magnetic Only with Current Limiter; 3-150 Amperes, 3 Poles
LFB Current Limiter for Type FB, 3 Pole, Thermal Magnetic Breakers .
Types JB, KB; MARK 75 Type HKB; 70-250 Amperes, 2, 3 Poles ..........
Types JA, KA; MARK 75 Type HKA; 70-225 Amperes, 2, 3 Poles ..........
Types CA, CAH, HCA; 125-225 Amperes, 2, 3 Poles ...............................
Type DA, 250-400 Amperes, 2, 3 Poles ....................................................
Types LBB, LB; MARK 75 Type HLB; 70-400 Amperes, 2, 3 Poles .........
Types LAB, LA; MARK 75 Type HLA; 125-400 Amperes, 2, 3 Poles ......
Type LA, MARK 75 Type HLA; 250-600 Amperes, 2, 3 Poles .................
Type MA, MARK 75 Type HMA; 125-600 Amperes, 2, 3 Poles ..............
Type MA, MARK 75 Type HMA; 700-800 Amperes, 2, 3 Poles ..............
Type NB, MARK 75 Type HNB; 800-1200 Amperes, 2, 3 Poles ..............
Type PB, 600-1600 Amperes, 2, 3 Poles ...................................................
Type PB, 1800-3000 Amperes, 2, 3 Poles .................................................
Types LC, LCG; MARK 75 Types HLC, HLCG; 75-150 Amperes,
2-3 Poles ....................................................................................................
Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 75-150 Amperes,
2-3 Poles ....................................................................................................
Types LC, LCG; MARK 75 Types HLC, HLCG; 150-300 Amperes,
2-3 Poles ....................................................................................................
Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 150-300 Amperes,
2-3 Poles ....................................................................................................
Types LC, LCG; MARK 75 Types HLC, HLCG; 200-400 Amperes,
2-3 Poles ....................................................................................................
Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 200-400 Amperes,
2-3 Poles ....................................................................................................
Types LC, LCG; MARK 75 Types HLC, HLCG; 300-600 Amperes,
2-3 Poles ....................................................................................................
Types LCA, LCGA; MARK 75 Types HLCA, HLCGA; 300-600 Amperes,
2-3 Poles ....................................................................................................
Types LCG, LCGA, HLCG, HLCGA Ground Fault Pick-up Curves ..........
Type LCLG 250 Ground Fault Pick-up Curves .........................................
Type LCLG 400 Ground Fault Pick-up Curves .........................................
Type LCG 150 Ground Fault Pick-up Curves ...........................................
Type LCG 300 Ground Fault Pick-up Curves ...........................................
Type LCG 400 Ground Fault Pick-up Curves ...........................................
Type LCG 600 Ground Fault Pick-up Curves ...........................................
Types MCA, MCGA; MARK 75 Types HMCA, HMCGA;
400-800 Amperes, 2-3 Poles ...................................................................
Types MC, MCG; MARK 75 Types HMC, HMCG; 400-800 Amperes,
2-3 Poles ....................................................................................................
Types MCG, MCGA, HMCG, HMCGA; NCG, NCGA, HNCG,
HNCGA Ground Fault Pick-up Curves ...................................................
Type MCG 800 Ground Fault Pick-up Curves ..........................................
Types NCA, NCGA; MARK 75 Types HNCA, HNCGA;
800-1200 Amperes, 2-3 Poles .................................................................
Types NC, NCG; MARK 75 Types HNC, HNCG; 800-1200 Amperes,
2-3 Poles ....................................................................................................
Type NCG 1200 Ground Fault Pick-up Curves .........................................
SC-3506-77
SC-3507-77
SC-3508-77
SC-3509-77
SC-3510-77
SC-3511-77
SC-3511-77
SC-3513-77
SC-3512-77A
SC-4009-77
SC-3514-77
SC-3504-77A
SC-3505-77
SC-3516-77
SC-3515-77
SC-3517-77
SC-3521-77
SC-3522-77
SC-3524-77
SC-3527-77
SC-3528-77
3
4
5
6
7
8
8
9
10
11
12
12.1
13
14
15
16
17
18
19
20
21
SC-3600-81A
22
SC-3612-81A
23
SC-3601-81A
24
SC-3613-81A
25
SC-3611-81A
26
SC-3623-81
27
SC-3602-81A
28
SC-3614-81A
SC-3603-81
SC-4122-87
SC-4123-87
SC-4124-87
SC-4125-87
SC-4126-87
SC-4127-87
29
30
31
32
33
34
35
36
SC-3616-81A
37
SC-3604-81A
38
SC-3606-81
SC-4128-87
39
40
SC-3617-81A
41
SC-3605-81A
SC-4129-87
42
43
Application Data
29-168
Page 2
Curve No.
Page
SC-3607-81A
44
SC-3619-81A
45
SC-3608-81A
46
SC-3620-81A
SC-3609-81A
SC-3621-81A
47
48
49
SC-3610-81
50
SC-3505-76
SC-3637-76
51
52
Individual oversize copies of curves listed above printed on onion-skin paper are available
in limited quantity from:
Cutler-Hammer
Customer Support Center
Five Parkway Center
Pittsburgh, PA 15220
When ordering onion-skin curves, use number at bottom of page where curve appears,
i.e., SC-3506-77. Requests for full sets of curves will not be honored.
October 1997
Application Data
29-168
Page 3
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
2,000
1,000
500
5,000
Maximum Volts
Breaker
Type
Ac Volts,
60 Hz
Dc Volts
EB
EHB
HFB
120
277
277
125
125
125
Breaker Ratings
Continuous
Amperes
Instantaneous
Trip, Amperes
15-40
See Curve
300
120 Volts
277 Volts
1,000
500
Dc Amps
.....
14,000
65,000
25,000
5,000
10,000
10,000
10,000
200
100
50
50
30
30
20
20
Minimum
Maximum
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
TIME IN SECONDS
300
125 Volts
1 MINUTE
1 MINUTE
100
10,000
.....
.....
.....
3,000
2,000
200
EB
EHB
HFB (15-30 Amps)
HFB (40 Amps)
1 HOUR
1 HOUR
2 HOURS
2 HOURS
10,000
.05
.03
.03
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 4
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
2,000
5,000
Maximum Volts
Breaker
Type
Ac Volts,
60 Hz
Dc Volts
EB
EHB, HFB
120
277
125
125
3,000
2,000
1,000
1,000
500
Breaker Ratings
Continuous
Amperes
Instantaneous
Trip, Amperes
50-70
See Curve
300
EB
EHB
HFB
200
500
Dc Amps
300
120 Volts
277 Volts
125 Volts
10,000
.....
.....
.....
14,000
25,000
5,000
10,000
10,000
100
200
100
50
30
1 MINUTE
1 MINUTE
1 HOUR
1 HOUR
2 HOURS
2 HOURS
10,000
30
Maximum
20
20
Minimum
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
.05
.03
.02
.01
.03
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
TIME IN SECONDS
10
October 1997
Application Data
29-168
Page 5
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
3,000
2,000
5,000
Maximum Volts
Breaker
Type
Ac Volts,
60 Hz
Dc Volts
EB
EHB, HFB
120
277
125
125
1,000
500
Breaker Ratings
Continuous
Amperes
Instantaneous
Trip, Amperes
90-100
See Curve
300
EB
EHB
HFB
200
100
500
Dc Amps
300
120 Volts
277 Volts
125 Volts
10,000
.....
.....
.....
14,000
25,000
5,000
10,000
10,000
200
100
50
50
30
1 MINUTE
1 MINUTE
3,000
2,000
1,000
30
Minimum
Maximum
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
TIME IN SECONDS
1 HOUR
1 HOUR
2 HOURS
2 HOURS
10,000
.05
.03
.03
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 6
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
Types EB, EHB, FB, HFB Breakers, Two and Three Poles
Westinghouse Electric Corporation
3,000
1,000
500
Maximum Volts
Breaker
Type
Ac Volts,
60 Hz
Dc Volts
EB
EHB
FB
HFB
240
480
600
600
125/250
250
250
250
Breaker Ratings
Continuous
Amperes
Instantaneous
Trip, Amperes
15-40
See Curve
300
Dc Amps
.....
14,000
14,000
25,000
.....
.....
14,000
18,000
1,000
500
300
5,000 (125/250)
10,000
10,000
20,000
200
100
50
50
30
1 MINUTE
1 MINUTE
100
10,000
18,000
18,000
65,000
3,000
2,000
250 Volts
200
EB
EHB
FB
HFB
5,000
1 HOUR
1 HOUR
2,000
30
20
20
10
10
Minimum
Maximum
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
.05
.03
.03
.02
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
October 1997
Application Data
29-168
Page 7
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
Types EB, EHB, FB, HFB Breakers, Two and Three Poles
Westinghouse Electric Corporation
3,000
1,000
Ac Volts,
60 Hz
Dc Volts
EB
EHB
FB, HFB
240
480
600
125/250
250
250
Breaker Ratings
Continuous
Amperes
Instantaneous
Trip, Amperes
500
50-70
See Curve
300
Dc Amps
EB
EHB
FB
HFB
5,000 (125/250)
10,000
10,000
20,000
200
10,000
18,000
18,000
65,000
.....
14,000
14,000
25,000
.....
.....
14,000
18,000
3,000
2,000
1,000
500
300
250 Volts
100
200
100
50
50
30
1 MINUTE
1 MINUTE
Maximum Volts
Breaker
Type
5,000
1 HOUR
1 HOUR
2,000
30
Minimum
Maximum
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
.05
.03
.02
.01
.03
.02
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 8
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
Types EB, EHB, FB, HFB Breakers, Two and Three Poles
Westinghouse Electric Corporation
3,000
1,000
Maximum
500
Minimum
300
200
3,000
2,000
Maximum Volts
Breaker
Type
Ac Volts,
60 Hz
Dc Volts
EB
EHB
FB, HFB
240
480
600
125/250
250
250
Breaker Ratings
Breaker
Type
Continuous
Amperes
Instantaneous
Trip, Amperes
EB, EHB
FB, HFB
90-100
90-150
See Curve
See Curve
250 Volts
EB
EHB
FB
HFB
5,000 (125/250)
10,000
10,000
20,000
.....
14,000
14,000
25,000
.....
.....
14,000
18,000
500
300
1,000
Dc Amps
200
100
50
30
30
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
1 MINUTE
.05
.03
.02
.01
.03
.02
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
70
80
90
100
.005
60
.005
50
1 MINUTE
100
5,000
1 HOUR
1 HOUR
2,000
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
October 1997
Application Data
29-168
Page 9
500
400
300
200
60
70
80
90
100
50
40
30
20
7
8
9
10
.6
.7
.8
.9
1
.5
R.M.S. AMPERES
10,000
10,000
2 HOURS
2 HOURS
5,000
5,000
1 HOUR
1 HOUR
(7-22) FB3022MRL
(15-45) FB3045MRL
3,000
3,000
(35-110) FB3110MRL
(32-80) 2610D53G30
2,000
2,000
1,000
1,000
(150-480) 1268C14G04
(160-480) FB3480MRL
500
500
(100-270) 2610D53G31
(450-1550) FB31550MRL
300
300
(575-1800) FB31800MRL
200
200
50
30
20
FB Breaker
Rating
(Amps)
Use Limiter
Catalog
Number
3
5
10
25
30
50
70
100
150
LFB3003MR
LFB3005MR
LFB3010MR
LFB3025MR
LFB3030MR
LFB3050MR
LFB3070MR
LFB3100MR
LFB3150MR
100
50
30
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
Maximum Breaker
Interrupting Time
.01
TIME IN SECONDS
.01
LFB3003MR
LFB3005MR
LFB3010MR
LFB3025MR
LFB3030MR
LFB3050MR
LFB3070MR
LFB3100MR
LFB3150MR
.005
.003
.002
.005
.003
.002
.001
CURRENT IN AMPERES
October 1997
5000
4000
3000
2000
600
700
800
900
1000
500
300
400
200
150
60
70
80
90
100
30
35
40
45
50
25
15
20
6
7
8
9
10
.7
.8
.9
1
.6
.5
.001
6000
7000
8000
9000
10,000
TIME IN SECONDS
1 MINUTE
1 MINUTE
100
Application Data
29-168
Page 10
500
400
300
200
60
70
80
90
100
50
40
30
20
7
8
9
10
.6
.7
.8
.9
1
.5
CURRENT IN AMPERES
10,000
10,000
2 HOURS
2 HOURS
5,000
3,000
3,000
2,000
2,000
1,000
1,000
1 HOUR
1 HOUR
5,000
500
500
300
200
Breaker Rating
Use Limiter
Up to 70
Amps
80-150 Amps
LFB3070R
300
200
LFB3150R
100
50
50
30
30
20
20
10
10
1 MINUTE
1 MINUTE
100
LFB3070R
2
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
TIME IN SECONDS
.02
.01
CURRENT IN AMPERES
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
150
60
70
80
90
100
30
35
40
45
50
20
25
15
.001
6
7
8
9
10
.001
5
.002
.002
.003
.003
.7
.8
.9
1
.005
.6
.005
.5
TIME IN SECONDS
LFB3150R
October 1997
Application Data
29-168
Page 11
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
3,000
500
300
70-250
250 Volts
JB, KB
HKB
10,000
20,000
22,000
25,000
14,000
18,000
1,000
Dc Amps
200
Breaker Ratings
Continuous Amperes
25,000
65,000
3,000
2,000
1,000
500
300
200
100
100
Minimum
Maximum
50
50
30
30
20
20
10
10
Adjustable
Magnetic
Trip
High (10%)
TIME IN SECONDS
Low (25%)
1
1 MINUTE
1 MINUTE
5,000
1 HOUR
1 HOUR
2,000
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 12
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
500
300
Dc Amps
JA, KA
HLB
10,000
20,000
22,000
35,000
22,000
25,000
250 Volts
200
Breaker Ratings
Continuous Amperes
70-225
25,000
65,000
1,000
500
300
200
100
100
Maximum
Minimum
50
50
30
30
20
20
10
10
1 MINUTE
1 MINUTE
3,000
2,000
1,000
5,000
1 HOUR
1 HOUR
2,000
Low (25%)
Adjustable
Magnetic
Trip
High (10%)
TIME IN SECONDS
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
October 1997
AB DE-IONT
Circuit Breakers
Cutler-Hammer
Application Data
Effective: April 1998
Page 12.1
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
10,000
2 HOURS
5,000
3,000
Maximum Ac Volts
CA, CAH, HCA Breakers: 240 at 60 Hz
3,000
2,000
Breaker Rating
Continuous
Amperes
2,000
Instantaneous Trip,
Amperes
125-225
See Curve
1 HOUR
1 HOUR
2 HOURS
1,000
1,000
300
Maximum Single-Pole
Trip Times at 25C
200
200
100
100
50
50
30
30
Minimum
Maximum
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
TIME IN SECONDS
300
1 MINUTE
1 MINUTE
10,000
22,000
42,000
CA
CAH
HCA
500
.05
.03
.02
.01
.01
AD 29-168
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
.001
400
.001
300
.002
200
.003
.002
70
80
90
100
.003
60
.005
50
.005
Application Data
29-168
Page 13
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
3,000
2,000
2,000
500
300
5,000
Breaker Ratings
Continuous
Amperes
Instantaneous
Trip, Amperes
250-400
1000%
Dc Amps
240 Volts
250 Volts
22,000
10,000
1,000
500
300
200
200
100
100
30
1 MINUTE
50
50
1 HOUR
1 HOUR
1,000
1 MINUTE
2 HOURS
2 HOURS
10,000
30
Maximum
Minimum
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
TIME IN SECONDS
TIME IN SECONDS
.05
.03
.03
.02
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 14
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
500
300
70-400
Dc Amps
LB, LBB
HLB
20,000
20,000
30,000
35,000
250 Volts
1,000
500
300
200
100
100
Maximum
Minimum
50
50
30
30
20
20
10
10
Adjustable
Magnetic
Trip
High (10%)
TIME IN SECONDS
Low (25%)
1
1 MINUTE
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
1 MINUTE
22,000
25,000
200
Breaker Ratings
Continuous Amperes
42,000
65,000
3,000
2,000
1,000
5,000
1 HOUR
1 HOUR
2,000
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
October 1997
Application Data
29-168
Page 15
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
3,000
Breaker Ratings
Continuous Amperes
70-400
500
22,000
25,000
500
300
200
100
100
Maximum
Minimum
50
50
30
30
20
20
10
10
Adjustable
Magnetic
Trip
High (10%)
TIME IN SECONDS
Low (25%)
1
1 MINUTE
1 MINUTE
1,000
20,000
20,000
200
30,000
35,000
3,000
2,000
1,000
5,000
1 HOUR
1 HOUR
2,000
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 16
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
3,000
2,000
2,000
Breaker Ratings
Continuous Amperes
1,000
250-600
LA-600
HLA-600
20,000
20,000
42,000
65,000
30,000
35,000
22,000
25,000
500
300
200
100
100
Maximum
Minimum
50
50
30
30
20
20
10
10
1 MINUTE
1 MINUTE
1,000
250 Volts
300
200
5,000
1 HOUR
1 HOUR
500
Low (25%)
Adjustable
Magnetic
Trip
High (10%)
TIME IN SECONDS
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.02
.02
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
October 1997
Application Data
29-168
Page 17
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
3,000
3,000
2,000
2,000
Breaker Ratings
Continuous Amperes
1,000
125-600
Dc Amps
MA
HMA
20,000
20,000
42,000
65,000
30,000
35,000
22,000
25,000
500
300
200
100
100
Maximum
Minimum
50
50
30
30
20
20
10
10
1 MINUTE
1 MINUTE
1,000
250 Volts
300
200
5,000
1 HOUR
1 HOUR
500
Low (25%)
Adjustable
Magnetic
Trip
High (10%)
TIME IN SECONDS
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 18
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
70
80
90
100
60
50
10,000
1 HOUR
Maximum
5,000
3,000
3,000
2,000
2,000
Minimum
Breaker Ratings
Continuous Amperes
700-800
3000-6000
1 HOUR
5,000
1,000
1,000
500
600 Volts
MA
HMA
22,000
25,000
42,000
65,000
30,000
35,000
300
500
300
200
200
100
100
50
50
30
30
20
20
10
1 MINUTE
1 MINUTE
2 HOURS
2 HOURS
10,000
10
Adjustable
Magnetic
Trip
Low (25%)
High (10%)
700 Amps
TIME IN SECONDS
.5
.5
800 Amps
.3
.3
.2
.2
.1
.1
.05
.05
.03
.02
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
TIME IN SECONDS
October 1997
Application Data
29-168
Page 19
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
1 HOUR
Maximum
3,000
3,000
2,000
2,000
Minimum
Breaker Ratings
Continuous Amperes
700-1200
1,000
500
600 Volts
NB
HNB
22,000
25,000
42,000
65,000
30,000
35,000
300
1,000
500
300
200
200
100
100
50
50
30
30
20
20
10
10
Low Setting
RMS Amps (25%)
High Setting
RMS Amps (10%)
1000 Amps
1000 Amps
1200 Amps
1200 Amps
1 MINUTE
1 MINUTE
5,000
1 HOUR
5,000
TIME IN SECONDS
TIME IN SECONDS
2 HOURS
2 HOURS
10,000
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.02
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 20
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
1 HOUR
Maximum
5,000
3,000
3,000
2,000
2,000
Minimum
Breaker Ratings
Continuous Amperes
600-1600
1,000
1500-5000
2000-6000
2500-7000
3000-8000
500
300
(600-1000 Amps)
(1200 Amps)
(1400 Amps)
(1600 Amps)
600 Volts
PB
100,000
125,000
100,000
1,000
500
200
1 HOUR
5,000
300
200
100
100
50
50
30
30
20
20
Adjustable
Magnetic Trip
Low (25%)
10
10
1000 Amps
1 MINUTE
1 MINUTE
2 HOURS
2 HOURS
10,000
1200 Amps
800, 1400, 1600 Amps
3
600 Amps
High (10%)
800 Amps
TIME IN SECONDS
600 Amps
.5
.5
.3
.3
.2
.2
.1
.05
.05
.03
.02
.01
.01
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
.001
600
700
800
900
1000
.001
500
.002
400
.003
.002
300
.003
200
.005
60
70
80
90
100
.005
50
TIME IN SECONDS
October 1997
Application Data
29-168
Page 21
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
10,000
1 HOUR
Maximum
5,000
3,000
3,000
2,000
2,000
Minimum
Breaker Ratings
Continuous Amperes
1800-3000
1,000
500
600 Volts
PB
100,000
125,000
100,000
300
1,000
500
300
200
200
100
100
30
30
20
20
Adjustable
Magnetic Trip
Low (25%)
10
1800 Amps
1 MINUTE
50
50
10
1 HOUR
5,000
1 MINUTE
2 HOURS
2 HOURS
10,000
2000 Amps
2500 Amps
3
3000 Amps
High (10%)
1800 Amps
TIME IN SECONDS
TIME IN SECONDS
2500 Amps
.5
.5
.3
.3
.2
.2
.1
.05
.05
.03
.02
.02
.01
.01
October 1997
60,000
70,000
80,000
90,000
100,000
50,000
40,000
30,000
20,000
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
.001
500
.001
400
.002
300
.003
.002
200
.003
60
70
80
90
100
.005
50
.005
Application Data
29-168
Page 22
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
75-150
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
1 MINUTE
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
75 - 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
75 Amp Rating Plug
150 Amp Rating Plug
8X
.5
9X
.5
.3
.3
Short Delay
Pickup Settings
.2
10X
Maximum Total
Clearing Time
0.20 Seconds
.2
.1
.05
.03
.02
150 A
.03
Fixed
Override
.02
Fixed
(2)
Fixed
Overide
Override
.01
125 A
.01
Fixed
Override
TIME IN SECONDS
100 A
.1
.05
.005
90 A
.005
.003
.003
.002
AMPERES X 100
60
50
40
30
20
80
10
60
50
40
30
20
10
60.0
50.0
40.0
30.0
20.0
10.0
8.0
5.0
6.0
4.0
3.0
2.0
1.0
0.8
.001
0.6
75 A
.002
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 23
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
75-150
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
1 MINUTE
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
75 - 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
75 Amp Rating Plug
150 Amp Rating Plug
8X
TIME IN SECONDS
.5
9X
.5
Maximum Total
Clearing Time
0.34 Seconds
with Short Delay
Time Adjust Set
to Maximum
.2
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.13 Seconds
with Short Delay
Time Adjust Set
to Minimum
.05
.1
.05
.03
.02
150 A
.03
Fixed
Override
.02
Fixed
(2)
Fixed
Overide
Override
.01
125 A
.01
Fixed
Override
TIME IN SECONDS
100 A
.1
.2
10X
.3
.005
90 A
.005
.003
.003
.002
October 1997
AMPERES X 100
60
50
40
30
20
80
10
60
50
40
30
20
10
60.0
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
75 A
.002
.001
Application Data
29-168
Page 24
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
150-300
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
1 MINUTE
Minimum Total
Clearing Time
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
50
30
3X
20
4X
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
150 Amp Rating Plug
300 Amp Rating Plug
8X
.5
9X
.5
.3
.3
Maximum Total
Clearing Time
0.20 Seconds
Short Delay
Pickup Settings
.2
10X
.2
.1
.05
.03
.02
Fixed
Override
.01
175 A
275 A
.01
.005
.02
Fixed
Override
200 A
Fixed
Override
300 A
.03
TIME IN SECONDS
225 A
.1
.05
.005
.003
250 A
.003
.002
AMPERES X 100
100
60
80
50
40
30
20
80
15
60
50
40
30
20
10
60.0
50.0
40.0
30.0
20.0
10.0
8.0
5.0
6.0
4.0
3.0
2.0
1.0
0.8
.001
0.6
150 A
.002
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 25
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
150-300
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
1 MINUTE
Minimum Total
Clearing Time
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
50
30
3X
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
150 Amp Rating Plug
300 Amp Rating Plug
8X
TIME IN SECONDS
.5
9X
.5
Maximum Total
Clearing Time
0.34 Seconds
with Short Delay
Time Adjust Set
to Maximum
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.13 Seconds
with Short Delay
Time Adjust Set
to Minimum
.05
.1
.05
.03
.02
Fixed
Override
.005
.003
250 A
.003
.01
175 A
275 A
.01
.005
.02
Fixed
Override
200 A
Fixed
Override
300 A
.03
.002
October 1997
AMPERES X 100
80
100
60
50
40
30
20
80
15
60
50
40
30
20
10
60.0
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
150 A
.002
TIME IN SECONDS
225 A
.1
.2
10X
.3
.2
.001
Application Data
29-168
Page 26
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
200-400
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
1 MINUTE
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
200 Amp Rating Plug
400 Amp Rating Plug
8X
.5
9X
.5
.3
.3
Maximum Total
Clearing Time
0.20 Seconds
Short Delay
Pickup Settings
.2
10X
.2
.1
.05
.03
.02
.02
(2)
Fixed
Fixed
Overide
Override
225 A
Fixed
Override
400 A
.03
Fixed
Override
.01
200 A
350 A
.01
TIME IN SECONDS
300 A
.1
.05
.005
.005
.003
AMPERES X 100
150
100
60
80
50
30
40
20
15
80
100
60
50
40
30
20
10
60.0
50.0
.002
40.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.6
.001
30.0
250 A
.003
.002
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 27
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
200-400
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
30
20
3X
50
4X
1 MINUTE
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
200 Amp Rating Plug
400 Amp Rating Plug
8X
TIME IN SECONDS
.5
9X
.5
Maximum Total
Clearing Time
0.34 Seconds
with Short Delay
Time Adjust Set
to Maximum
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.13 Seconds
with Short Delay
Time Adjust Set
to Minimum
.05
.1
.05
.03
.02
.02
Fixed
Override
Fixed
Override
225 A
Fixed
Override
400 A
.03
.01
350 A
.01
TIME IN SECONDS
300 A
.1
.2
10X
.3
.2
200 A
.005
.005
.003
October 1997
AMPERES X 100
150
80
100
60
50
40
30
20
80
100
15
60
50
40
30
20
10
60.0
50.0
.002
40.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.6
0.5
.001
30.0
250 A
.003
.002
.001
Application Data
29-168
Page 28
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
300-600
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
75 - 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
1 MINUTE
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
300 Amp Rating Plug
600 Amp Rating Plug
8X
.5
9X
.5
.3
.3
Short Delay
Pickup Settings
.2
10X
Maximum Total
Clearing Time
0.20 Seconds
.2
.1
.05
.03
.02
600 A
.03
Fixed
Override
Fixed
Override
500 A
.01
.02
Fixed
Override
TIME IN SECONDS
450 A
.1
.05
.01
.005
400 A
.005
.003
.003
.002
.002
AMPERES X 100
200
100
60
80
50
30
40
20
80
100
60
50
40
30
20
60.0
50.0
40.0
30.0
300 A
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.6
.001
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 29
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
300-600
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
75 - 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
1 MINUTE
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
300 Amp Rating Plug
600 Amp Rating Plug
8X
TIME IN SECONDS
.5
9X
.5
Maximum Total
Clearing Time
0.34 Seconds
with Short Delay
Time Adjust Set
to Maximum
Maximum Total
Clearing Time
0.13 Seconds
with Short Delay
Time Adjust Set
to Minimum
.2
.1
.05
.05
.03
.02
600 A
.03
Fixed
Override
Fixed
Override
500 A
.01
.02
Fixed
Override
TIME IN SECONDS
450 A
.1
.3
Short Delay
Pickup Settings
10X
.3
.2
.01
.005
400 A
.005
.003
.003
.002
October 1997
AMPERES X 100
200
100
60
80
50
30
40
20
200
80
100
60
50
40
30
20
60.0
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
300 A
.002
.001
Application Data
29-168
Page 30
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
40
30
20
7
8
9
10
10,000
10,000
2 HOURS
2 HOURS
1 HOUR
3,000
3,000
2,000
2,000
1,000
1,000
500
300
300
200
200
100
100
50
50
30
30
20
20
Minimum Pick-Up*
(20%)
Maximum Pick-Up
( +0
-20%)
10
1 MINUTE
10
TIME IN SECONDS
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
.005
.005
.003
.003
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
60
70
80
90
100
50
40
30
.001
20
.001
6
7
8
9
10
.002
.002
200
1 MINUTE
500
TIME IN SECONDS
1 HOUR
5,000
5,000
October 1997
Application Data
29-168
Page 31
1 HOUR
2,000
900
700
800
500
600
400
300
200
100
80
90
60
70
50
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
Minimum Pickup
(20%)
200
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
1 MINUTE
300
Maximum Pickup
( +0
20%)
200
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
October 1997
2,000
900
1,000
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
0.001
AMPERES
Application Data
29-168
Page 32
1 HOUR
2,000
900
700
800
500
600
400
300
200
90
100
70
80
50
60
40
30
20
5,000
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
1,000
900
800
700
600
500
500
400
400
300
200
Maximum Pickup
(+0
20%)
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
10
9
8
7
6
TIME IN SECONDS
40
30
1 MINUTE
Maximum Time
(20%)
1.0
.9
.8
.7
.6
1.0
.9
.8
.7
.6
.5
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
2,000
900
800
700
600
500
400
1,000
AMPERES
300
200
90
100
80
70
50
60
40
30
20
0.001
10
1 MINUTE
300
Minimum Pickup
(20%)
200
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
2 HOURS
2 HOURS
10
AMPERES
1,000
October 1997
Application Data
29-168
Page 33
1 HOUR
2,000
900
700
800
500
600
400
300
200
100
80
90
60
70
50
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
300
200
200
Maximum Pickup
( +0 %)
20
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
1 MINUTE
Minimum Pickup
(20%)
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
October 1997
2,000
900
1,000
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
0.001
AMPERES
Application Data
29-168
Page 34
1 HOUR
2,000
800
900
600
700
500
400
300
200
90
100
70
80
50
60
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
Minimum Pickup
(20%)
300
Maximum Pickup
( +0 %)
20
200
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
2,000
900
800
700
600
500
400
1,000
AMPERES
300
200
90
100
80
70
50
60
40
30
20
0.001
10
1 MINUTE
200
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
October 1997
Application Data
29-168
Page 35
1 HOUR
2,000
900
700
800
500
600
400
300
200
100
80
90
60
70
50
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
300
200
200
Maximum Pickup
( +0 %)
20
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
1 MINUTE
Minimum Pickup
(20%)
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
October 1997
2,000
900
1,000
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
0.001
AMPERES
Application Data
29-168
Page 36
1 HOUR
2,000
900
700
800
500
600
400
300
200
90
100
70
80
50
60
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
Maximum Pickup
( +0 %)
20
200
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
2,000
900
800
700
600
500
400
1,000
AMPERES
300
200
90
100
80
70
50
60
40
30
20
0.001
10
1 MINUTE
300
Minimum Pickup
(20%)
200
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
October 1997
Application Data
29-168
Page 37
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
400-800
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
80 - 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
1 MINUTE
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
400 Amp Rating Plug
800 Amp Rating Plug
8X
9X
TIME IN SECONDS
.5
.5
Maximum Total
Clearing Time
0.42 Seconds
with Short Delay
Time Adjust Set
to Maximum
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.14 Seconds
with Short Delay
Time Adjust Set
to Minimum
.1
.05
.05
.03
.02
800 A
.03
Fixed
Override
Fixed
Override
700 A
.01
.02
Fixed
Override
TIME IN SECONDS
600 A
.1
.2
10X
.3
.2
.01
.005
500 A
.005
.003
.003
.002
October 1997
AMPERES X 100
200
100
60
80
50
30
40
20
200
80
100
60
50
40
30
20
60.0
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
400 A
.002
.001
Application Data
29-168
Page 38
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
400-800
2,000
1,000
500
300
Maximum Total
Clearing Time
200
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
80 - 100%
Fixed 100%
Minimum Total
Clearing Time
50
30
3X
1 MINUTE
4X
20
5X
10
6X
7X
8X
Expanded view in short circuit area with short time adjustment set at minimum
400 Amp Rating Plug
800 Amp Rating Plug
9X
.5
.5
.3
.3
Short Delay
Pickup Settings
.2
10X
Maximum Total
Clearing Time
0.222 Seconds
.2
.1
.05
.03
.02
800 A
.03
Fixed
Override
Fixed
Override
700 A
.01
.02
Fixed
Override
TIME IN SECONDS
600 A
.1
.05
.01
.005
500 A
.005
.003
.003
.002
.002
AMPERES X 100
200
100
60
80
50
30
40
20
200
80
100
60
50
40
30
20
60.0
50.0
40.0
30.0
400 A
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.6
.001
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 39
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
40
30
20
7
8
9
10
10,000
10,000
2 HOURS
2 HOURS
1 HOUR
3,000
3,000
2,000
2,000
1,000
1,000
500
300
300
200
200
100
100
50
50
30
30
20
20
Minimum Pick-Up
(20%)
1 MINUTE
1 MINUTE
500
Maximum Pick-Up
( +0
-20 %)
10
10
TIME IN SECONDS
TIME IN SECONDS
1 HOUR
5,000
5,000
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
October 1997
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
.001
50
.001
40
.002
30
.003
.002
20
.003
6
7
8
9
10
.005
.005
Application Data
29-168
Page 40
1 HOUR
2,000
900
700
800
500
600
400
300
200
100
80
90
60
70
50
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
300
200
200
100
90
80
70
60
50
Maximum Pickup
( +0 %)
20
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
2,000
900
800
700
600
500
400
1,000
AMPERES
300
200
100
90
80
70
60
50
40
30
20
0.001
10
1 MINUTE
Minimum Pickup
(20%)
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
October 1997
Application Data
29-168
Page 41
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
800-1200
2,000
1,000
500
Maximum Total
Clearing Time
300
200
Minimum Total
Clearing Time
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
75 - 100%
50
2X
1 MINUTE
30
3X
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
800 Amp Rating Plug
1200 Amp Rating Plug
8X
TIME IN SECONDS
.5
.5
Maximum Total
Clearing Time
0.42 Seconds
with Short Delay
Time Adjust Set
to Maximum
.2
.2
Maximum Total
Clearing Time
0.14 Seconds
with Short Delay
Time Adjust Set
to Minimum
.1
.3
Short Delay
Pickup Settings
.1
1000 A
.3
.05
.03
.02
1200 A
.03
.01
Fixed
Override
.01
.005
900 A
.005
.02
Fixed
Override
1100 A
Fixed
Override
TIME IN SECONDS
.05
.003
800 A
.003
October 1997
AMPERES X 100
200
100
60
80
50
30
40
20
200
80
100
60
50
40
30
20
60.0
50.0
40.0
30.0
.002
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
.002
.001
Application Data
29-168
Page 42
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
800-1200
2,000
1,000
500
300
Maximum Total
Clearing Time
200
Minimum Total
Clearing Time
100
600 Volts
22,000
25,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
75 - 100%
50
2X
1 MINUTE
30
3X
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
800 Amp Rating Plug
1200 Amp Rating Plug
8X
.5
.5
.3
.2
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.222 Seconds
.2
.1
1000 A
.1
.05
.03
.02
1200 A
.03
.01
Fixed
Override
.01
.005
900 A
.005
.02
Fixed
Override
1100 A
Fixed
Override
TIME IN SECONDS
.05
.003
800 A
.003
AMPERES X 100
200
100
60
80
50
30
40
20
200
80
100
60
50
40
30
20
60.0
50.0
40.0
30.0
.002
20.0
10.0
8.0
5.0
6.0
4.0
3.0
2.0
1.0
0.8
.001
0.6
.002
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 43
1 HOUR
2,000
900
700
800
500
600
400
300
200
100
80
90
60
70
50
40
30
20
4,000
4,000
3,000
3,000
2,000
2,000
1,000
900
800
700
600
500
1,000
900
800
700
600
500
400
400
300
Minimum Pickup
(20%)
300
Maximum Pickup
+0
(
%)
20
200
100
90
80
70
60
50
100
90
80
70
60
50
40
30
20
20
10
9
8
7
6
5
10
9
8
7
6
5
TIME IN SECONDS
40
30
1 MINUTE
1 MINUTE
200
TIME IN SECONDS
10,000
9,000
8,000
7,000
6,000
5,000
1 HOUR
10,000
9,000
8,000
7,000
6,000
5,000
2 HOURS
2 HOURS
10
AMPERES
1,000
Maximum Time
(20%)
1.0
.9
.8
.7
.6
.5
1.0
.9
.8
.7
.6
.5
.4
.4
.3
.3
.2
.2
Minimum Time
(20%)
0.1
0.09
0.08
0.07
0.06
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.04
0.03
0.03
0.02
0.02
0.01
0.009
0.008
0.007
0.006
0.005
0.01
0.009
0.008
0.007
0.006
0.005
0.004
0.004
0.003
0.003
0.002
0.002
0.001
October 1997
2,000
900
1,000
800
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
0.001
AMPERES
Application Data
29-168
Page 44
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
2,000
Continuous Amperes
1000-2000
1,000
500
300
Maximum Total
Clearing Time
200
Minimum Total
Clearing Time
600 Volts
100,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
100
50
2X
1 MINUTE
20
4X
3X
30
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
1000 Amp Rating Plug
2000 Amp Rating Plug
8X
.5
.5
Short Delay
Pickup Settings
.3
.3
Maximum Total
Clearing Time
0.222 Seconds
.2
.2
.1
.05
.03
.02
Fixed
Override
.02
Fixed
Override
1200A
Fixed
Override
2000A
.03
.005
.01
.005
1000A
1800A
.01
.003
1400A
.003
600
500
400
300
200
80
AMPERES X 100
100
600
60
500
400
300
200
80
100
60
60.0
50.0
40.0
.002
30.0
20.0
10.0
8.0
5.0
6.0
4.0
3.0
2.0
1.0
0.8
.001
0.6
.002
TIME IN SECONDS
1600A
.1
.05
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 45
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
2,000
Continuous Amperes
1000-2000
1,000
500
300
Maximum Total
Clearing Time
200
Minimum Total
Clearing Time
600 Volts
100,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
100
50
2X
1 MINUTE
20
4X
3X
30
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
1000 Amp Rating Plug
2000 Amp Rating Plug
8X
TIME IN SECONDS
.5
.5
Maximum Total
Clearing Time
0.42 Seconds
with Short Delay
Time Adjust Set
to Maximum
.1
.3
.2
Maximum Total
Clearing Time
0.14 Seconds
with Short Delay
Time Adjust Set
to Minimum
.1
.05
.05
.03
.02
Fixed
Override
.02
Fixed
Override
1200A
Fixed
Override
2000A
.03
.005
.01
.005
1000A
1800A
.01
.003
1400A
.003
October 1997
600
500
400
300
200
80
AMPERES X 100
100
600
60
500
400
300
200
80
100
60
60.0
50.0
40.0
.002
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
.002
TIME IN SECONDS
1600A
.3
.2
Short Delay
Pickup Settings
.001
Application Data
29-168
Page 46
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
2,000
Continuous Amperes
1400-2500
1,000
500
300
Maximum Total
Clearing Time
200
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
2X
50
30
3X
4X
20
600 Volts
100,000
Minimum Total
Clearing Time
100
1 MINUTE
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
1400 Amp Rating Plug
2500 Amp Rating Plug
8X
.5
.5
.3
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.222 Seconds
.2
.2
.1
.05
.03
.02
Fixed
Override
.02
Fixed
Override
2000A
Fixed
Override
2500A
.03
.01
.01
1600A
.005
TIME IN SECONDS
1800A
.1
.05
.005
.003
1400A
.003
600
500
400
300
200
80
AMPERES X 100
100
600
60
500
400
300
200
80
100
60
60.0
50.0
40.0
.002
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
.001
0.6
.002
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 47
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
2,000
Continuous Amperes
1400-2500
1,000
500
Maximum Total
Clearing Time
300
200
Minimum Total
Clearing Time
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
2X
50
30
3X
4X
20
600 Volts
100,000
100
1 MINUTE
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
1400 Amp Rating Plug
2500 Amp Rating Plug
8X
TIME IN SECONDS
.5
.5
Maximum Total
Clearing Time
.3 0.42 Seconds
with Short Delay
Time Adjust Set
.2 to Maximum
.3
.2
Maximum Total
Clearing Time
0.14 Seconds
with Short Delay
Time Adjust Set
to Minimum
.1
.05
.05
.03
.02
Fixed
Override
.02
Fixed
Override
2000A
Fixed
Override
2500A
.03
.01
.01
1600A
.005
TIME IN SECONDS
1800A
.1
Short Delay
Pickup Settings
.005
.003
1400A
.003
October 1997
600
500
400
300
200
80
AMPERES X 100
100
600
60
500
400
300
200
80
100
60
60.0
50.0
40.0
.002
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
.002
.001
Application Data
29-168
Page 48
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
1600-3000
2,000
1,000
500
300
Maximum Total
Clearing Time
200
600 Volts
100,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
100
50
2X
1 MINUTE
3X
30
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
1600 Amp Rating Plug
3000 Amp Rating Plug
8X
.5
.5
.3
.3
Short Delay
Pickup Settings
Maximum Total
Clearing Time
0.222 Seconds
.2
.2
.1
.05
.03
.02
3000A
.03
Fixed
Override
.02
Fixed
Override
2500A
Fixed
Override
.01
TIME IN SECONDS
2000A
.1
.05
.01
1800A
.005
.005
.003
1600A
.003
600
500
400
300
200
80
AMPERES X 100
100
600
60
500
400
300
200
80
100
60
60.0
50.0
40.0
.002
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
.001
0.6
.002
0.5
TIME IN SECONDS
.001
October 1997
Application Data
29-168
Page 49
50.0
40.0
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
0.6
10,000
2 HOURS
1 HOUR
5,000
Breaker Ratings
Maximum Ac Volts 600, 50/60 Hz
Continuous Amperes
1600-3000
2,000
1,000
500
300
Maximum Total
Clearing Time
200
600 Volts
100,000
Range of Adjustment
Fixed 100%
50 - 100%
Fixed 100%
70 - 100%
Fixed 100%
Fixed 100%
Fixed 100%
Minimum Total
Clearing Time
100
50
2X
1 MINUTE
3X
30
4X
20
5X
10
6X
7X
Expanded view in short circuit area with short time adjustment set at minimum
1600 Amp Rating Plug
3000 Amp Rating Plug
8X
TIME IN SECONDS
.5
.5
Maximum Total
Clearing Time
0.42 Seconds
with Short Delay
Time Adjust Set
to Maximum
.1
.3
Short Delay
Pickup Settings
.2
Maximum Total
Clearing Time
0.14 Seconds
with Short Delay
Time Adjust Set
to Minimum
.1
.05
.05
.03
.02
3000A
.03
Fixed
Override
.02
Fixed
Override
2500A
Fixed
Override
.01
TIME IN SECONDS
2000A
.3
.2
.01
1800A
.005
.005
.003
1600A
.003
October 1997
600
500
400
300
200
80
AMPERES X 100
100
600
60
500
400
300
200
80
100
60
60.0
50.0
40.0
.002
30.0
20.0
10.0
8.0
6.0
5.0
4.0
3.0
2.0
1.0
0.8
0.5
.001
0.6
.002
.001
Application Data
29-168
Page 50
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
40
30
20
6
7
8
9
10
10,000
10,000
2 HOURS
2 HOURS
1 HOUR
3,000
3,000
2,000
2,000
1,000
1,000
500
300
300
200
200
100
100
50
50
30
PCG/PCCG2000
PCG/PCCG2500
PCG/PCCG3000
PCG/PCCG2000
PCG/PCCG2500
PCG/PCCG3000
30
20
1 MINUTE
1 MINUTE
500
20
10
10
Minimum Pick-Up
Each Rating
(20%)
Maximum Pick-Up ( +0 %)
-20
2
TIME IN SECONDS
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
.01
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
.001
50
.001
40
.002
30
.003
.002
20
.003
7
8
9
10
.005
.005
TIME IN SECONDS
1 HOUR
5,000
5,000
October 1997
Application Data
29-168
Page 51
500
400
300
200
60
70
80
90
100
50
40
30
20
7
8
9
10
.6
.7
.8
.9
1
.5
CURRENT IN AMPERES
10,000
10,000
2 HOURS
2 HOURS
5,000
5,000
1 HOUR
1 HOUR
MCP0322R
MCP0358R
3,000
3,000
MCP03150R
2,000
2,000
MCP13300R
MCP23480R
MCP331000R
1,000
1,000
MCP431550R
MCP431800R
300
300
200
200
100
100
50
50
30
30
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
MCP
Catalog Number
( 7- 22A) MCP0322R
( 18- 58A) MCP0358R
( 50- 150A) MCP03150R
(100- 300A) MCP13300R
(160- 480A) MCP23480R
(275-1000A) MCP331000R
(450-1550A) MCP431550R
(575-1800A) MCP431800R
.01
.005
.003
.002
Use Limiter
Catalog No.
EL3003R
EL3007R
EL3015R
EL3030R
EL3050R
EL3100R
EL3150R
EL3150R
TIME IN SECONDS
.01
Maximum MCP
Interrupting Time
EL3030R
EL3050R
.005
EL3100R
EL3150R
.003
.002
.001
CURRENT IN AMPERES
October 1997
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
40
30
20
6
7
8
9
10
.7
.8
.9
1
.6
.5
.001
6000
7000
8000
9000
10,000
TIME IN SECONDS
500
1 MINUTE
1 MINUTE
500
Application Data
29-168
Page 52
500
400
300
200
60
70
80
90
100
50
40
30
20
7
8
9
10
.6
.7
.8
.9
1
.5
CURRENT IN AMPERES
10,000
10,000
2 HOURS
2 HOURS
5,000
1 HOUR
1 HOUR
5,000
MCP532500 and
MCP532500C
(1250-2500)
3,000
3,000
2,000
2,000
MCP534000 and
MCP534000C
(2000-4000)
500
500
300
300
200
200
100
100
50
50
30
30
20
20
10
10
.5
.5
.3
.3
.2
.2
.1
.1
.05
.05
.03
.03
.02
.02
.01
TIME IN SECONDS
.01
Maximum MCP
Interrupting Time
CURRENT IN AMPERES
6000
7000
8000
9000
10,000
5000
4000
3000
2000
600
700
800
900
1000
500
400
300
200
60
70
80
90
100
50
40
30
20
6
7
8
9
10
.001
5
.001
4
.002
.003
.002
.003
.7
.8
.9
1
.005
.6
.005
.5
TIME IN SECONDS
1,000
1 MINUTE
1 MINUTE
1,000
October 1997