4 BLAST LOAD Reference: SAES-M-009 - Design Criteria for Blast Resistant Buildings Design of Blast Resistant Buildings in Petrochemical Facilities, ASCE
As per Final Building Risk Assesment Study Report - reference letter LP/TSU-036-2006 dated August 30, 2006.
PSO
1.40 psi
& duration, td =
67.7 ms =
0.0677
sec
7.200 m
PROPOSED SUBSTATION
H=
6.65 m
L=
70.00 m
FGL
TOC
10.72 m
SECTION A - A
PROPOSED SUBSTATION A
B=
PLAN
BLAST FORCE Reference : ASCE Report 97; Design of Blast Resistant Buildings in Petrochemical Plants Building size : Length L = Width B = Height H = 70.00 m 10.72 m 7.20 m = = = 229.60 ft 35.16 ft 23.62 ft
CALCULATION SHEET
DESCRIPTION:
SUBSTATION - UGOSP 7 AND UGOSP 8
NORTH
BI No.
Saudi Arabia
DESIGNED:
ZUHAIR FAYEZ PARTNERSHIP CONSULTANTS
BI-10-00241
DATE:
CHECKED:
APPROVED:
SHEET NO.:
NTP
JAMA
AZJ
1 of 1
APRIL 2007
NTP
\\vboxsrv\conversion_tmp\scratch1155\100405885.xls.ms_office
BLAST LOAD Reference: SAES-M-009 - Design Criteria for Blast Resistant Buildings Design of Blast Resistant Buildings in Petrochemical Facilities, ASCE
As per Final Building Risk Assesment Study Report - reference letter LP/TSU-036-2006 dated August 30, 2006. Peak side-on overpressure, PSO = 1.40 psi & duration, td = 67.7 ms = 0.0677 sec
7.200 m
PROPOSED SUBSTATION
H=
6.65 m
L=
FGL
TOC
10.72 m
SECTION A - A A
B=
PROPOSED SUBSTATION A
PLAN
BLAST FORCE Reference : ASCE Report 97; Design of Blast Resistant Buildings in Petrochemical Plants Building size : Length L = Width B = Height H = 70.00 m 10.72 m 7.20 m = = = 229.60 ft 35.16 ft 23.62 ft
CALCULATION SHEET
DESCRIPTION:
SUBSTATION - UGOSP 7 AND UGOSP 8
NORTH 70.00 m
BI No.
Saudi Arabia
DESIGNED:
ZUHAIR FAYEZ PARTNERSHIP CONSULTANTS
BI-10-00241
DATE:
CHECKED:
APPROVED:
SHEET NO.:
NTP
JAMA
AZJ
1 of 3
APRIL 2007
NTP
\\vboxsrv\conversion_tmp\scratch1155\100405885.xls.ms_office
Blast Loading: Pso = 1.40 psi U and td = 0.068 sec .eq. 3.5 .eq. 3.6 .eq. 3.4
= 1130 ( 1 + 0.058 Pso )^0.5 ft/sec = 1174.98 ft/sec length of pressure wave,Lw = U * td = 79.5 ft qo = 0.022 ( Pso)2 = peak dynamic wind pressure, 0.0431 psi a) Front wall loading :
The front wall is assumed to span vertically from foundation to roof. The design will be for a typical wall segment of one foot width.
reflected overpressure,
Pr = =
clearing distance, S = minimum of H or B/2 = 17.58 ft. Section 3.5.1 reflected overpressure clering time, tc = 3 (S / U) < td .eq. 3.8 = 0.045 < 0.068 drag coefficient, Cd = 1.00 Section 3.3.3 stagnation pressure, Ps = Pso + Cd (qo) = 0.043 psi .eq. 3.7 front wall impulse, Iw = 0.5 ( Pr - Ps ) tc + 0.5Ps*td .eq. 3.9 = 0.066 psi-sec effective duration, b) Side wall loading :
The side wall is the same as the front wall, spanning vertically from foundation to roof. This calculation will be for a wall segment ( L1), 1 foot wide.
te = 2 Iw / Pr
0.045 sec
.eq. 3.10
Drag coefficient, Cd
-0.4
Equivalent load coefficient, Lw / L1 = 35.16 1.00 Reduction factor, Ce = 0.95 however, use Ce = 1.00
Equivalent Peak Overpressure, Pa = Ce PSO + Cd qo .eq 3.11 = 1.383 psi = 9.534 kn/sqm rise time, tr = L1/U = 0.001 sec (negligble) figure 3.8 time of duration, td = 0.068 sec
CALCULATION SHEET
DESCRIPTION:
SUBSTATION - UGOSP 7 AND UGOSP 8
BI No.
Saudi Arabia
DESIGNED:
ZUHAIR FAYEZ PARTNERSHIP CONSULTANTS
BI-10-00241
DATE:
CHECKED:
APPROVED:
SHEET NO.:
NTP
JAMA
AZJ
2 of 3
APRIL 2007
asimksen
\\vboxsrv\conversion_tmp\scratch1155\100405885.xls.ms_office
c) Roof loading :
The roof is a slab spanning between roof beams. For the design of the roof, a section 1 foot wide by span of the slab will be used.
= =
Equivalent load coefficient Lw / S = 35.16 1.00 Reduction factor, Ce however, use Ce = = 0.95 1.00
35.162
. Figure 3.9
= =
figure 3.8
0.098 sec
The rear wall also spanning vertically from foundation to roof. The analysis will be for a wall segment of 1 foot wide.
Drag coefficient, Cd
-0.4
section 3.3.3
Equivalent load coefficient Lw / S = 21.81 1.00 Reduction factor, Ce = 0.95 however, use Ce = 1.00 Equivalent Peak Overpressure, Pb
time of arrival ta
= L/U
tr = S / U = 0.068 sec = tr + td
0.083 sec
CALCULATION SHEET
DESCRIPTION:
SUBSTATION - UGOSP 7 AND UGOSP 8
BI No.
Saudi Arabia
DESIGNED:
ZUHAIR FAYEZ PARTNERSHIP CONSULTANTS
BI-10-00241
DATE:
CHECKED:
APPROVED:
SHEET NO.:
NTP
JAMA
AZJ
3 of 3
APRIL 2007