Sequence of operation

INPUT DEVICES SECTION


P233A-4-AKC P233A-4-AKC P233A-4-AKC

LOGIC
Energy Management Sequences - Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer

OUTPUT DEVICE SECTION


Fan Belt Broken

Supply Fan Differential Pressure switch

Return Fan Differential Pressure switch

Filter Section Differential Pressure switch

Start

TE-702A-3B DH100ACDCI DH100ACDCI

Adjustable Setpoint

T
Supply Air Temperature Sensor Return Air Smoke Detector Signal Supply Air Smoke Detector Signal

Monitoring & Alarming


Supply Fan

Signal From Fire Alarm Panel

HU-226-VCD-3

Supply Fan Status

H/T
Return Air Temperature/Humidity Sensor

- Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence

Stop

Supply Fan Trip

- Differential Pressure Switch in Low alarm while fan is running. - Adjustable Time Channel. (overridable) - If Supply Fan started. - If Smoke detected at either supply or return, and return temperature less than high limit. - Status (COS), Overload and run time totalizer. - Adjustable Time Channel.. - If Fan Belt Broken. - If Supply Fan is stopped and no smoke detected either in supply and return air.

Fan Belt Broken

Return Fan Status

Start

Return Fan Trip

Monitoring & Alarming Stop

Return Fan

- Differential pressure switch in high alarm

Clean Filter

Filter Section

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 1 Logic ( 1 of 3 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 2 SHEET 3 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC
- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.

OUTPUT DEVICE SECTION


Open Close
Supply Air Smoke Damper

P233A-4-AKC

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Return Fan Differential Pressure switch

Filter Section Differential Pressure switch

TE-702A-3B DH100ACDCI DH100ACDCI

Adjustable Setpoint

- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.

Open Close
Return Air Smoke Damper

T
Supply Air Temperature Sensor Return Air Smoke Detector Signal Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

- Through Enthalpy Control Software. - If supply Fan Stopped. - If smoke is detected at either Supply or return. - Through Enthalpy Control Software.

Modulate damper close Fully Closed Modulate damper open


Fresh Air Damper

HU-226-VCD-3

Supply Fan Status

H/T
Return Air Temperature/Humidity Sensor

Supply Fan Trip - Through Enthalpy Control Software. Return Fan Status - If supply Fan Stopped. - If smoke is detected at either Supply or return. - Through Enthalpy Control Software. Return Fan Trip - If smoke is detected at either Supply or return. - Through Enthalpy Control Software. - In case of Return fan stopped. - Through Enthalpy Control block.

Modulate damper close Fully Closed Modulate damper open


Exhaust Air Damper

Fully Opened

Modulate damper close Modulate damper open


Return Air Damper

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 1 Logic ( 2 of 3 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 3 SHEET 4 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit. - If Supply Fan is started while in Heating mode and return temperature Lower than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in Heating mode and return Temperature Highter than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected Higher than a certain limit.

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Return Fan Differential Pressure switch

Filter Section Differential Pressure switch

Modulate Valve Open

TE-702A-3B DH100ACDCI DH100ACDCI

Adjustable Setpoint

T
Supply Air Temperature Sensor Return Air Smoke Detector Signal Supply Air Smoke Detector Signal

Modulate Valve Close Fully Close the Valve

Signal From Fire Alarm Panel

Cooling Coil

HU-226-VCD-3

Supply Fan Status

H/T
Return Air Temperature/Humidity Sensor

Supply Fan Trip

Modulate Valve Open

Return Fan Status

Modulate Valve Close Fully Close the Valve

Return Fan Trip

Heating Coil

Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 1 Logic ( 3 of 3 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 4 SHEET 5 of 20 REV 0

INPUT DEVICES SECTION


P233A-4-AKC P233A-4-AKC

LOGIC
Energy Management Sequences - Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer

OUTPUT DEVICE SECTION


Fan Belt Broken

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

Start

Adjustable Setpoint
DH100ACDCI DH100ACDCI

Monitoring & Alarming


Supply Fan

Return Air Smoke Detector Signal

Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

HU-226-VCD-3

HU-226-VCD-3

Supply Fan Status

H/T
Supply Air Temperature/Humidity Sensor

H/T
Return Air Temperature/Humidity Sensor

- Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence - Differential pressure switch in high alarm - If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return. - If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return. - If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit.

Stop

Clean Filter
Filter Section

Supply Fan Trip

Open Close
Supply Air Smoke Damper

Open Close
Return Air Smoke Damper

Modulate Valve Open

Modulate Valve Close Fully Close the Valve

Cooling Coil

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 2 Logic ( 1 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 5 SHEET 6 of 20 REV 0

INPUT DEVICES SECTION

LOGIC
- If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status - If supply humidity Lower / higher than setpoint, valve Act. Will open / close in function of the deviation between supply humidity and setpoint (PID). - If Supply Fan is started while in cooling mode, and supply humidity highter than Set point, heater will start. The number of stages to be started is function of the deviation between Set point and Supply humidity. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in Cooling mode, and supply humidity lower than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Set point and Supply humidity. - Stop heater completely if supply humidity is lower than a certain value. - Get heater steps status Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

Energy Management Sequences

Start Heater

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

Adjustable Setpoint
DH100ACDCI DH100ACDCI

Stop Heater

Return Air Smoke Detector Signal

Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Electrical Pre-Heater

HU-226-VCD-3

HU-226-VCD-3

Supply Fan Status

Monitoring

H/T
Supply Air Temperature/Humidity Sensor

H/T
Return Air Temperature/Humidity Sensor

Supply Fan Trip

M Start Heater Electrical Humidifier

Stop Heater

Electrical Re-Heater

Monitoring

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 2 Logic ( 2 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 6 SHEET 7 of 20 REV 0

INPUT DEVICES SECTION


P233A-4-AKC P233A-4-AKC

LOGIC
Energy Management Sequences - Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer

OUTPUT DEVICE SECTION


Fan Belt Broken

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

Start

TE-702A-3B DH100ACDCI

Adjustable Setpoint

T
Supply Air Temperature/Humidity Sensor Supply Air Smoke Detector Signal

Monitoring & Alarming


Supply Fan

Signal From Fire Alarm Panel

Supply Fan Status

- Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence - Differential pressure switch in high alarm

Stop

Supply Fan Trip

Clean Filter
Filter Section

- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return. - If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit.

Open Close
Supply Air Smoke Damper

Modulate Valve Open

Modulate Valve Close Fully Close the Valve

Cooling Coil

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 3 Logic
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 7 SHEET 8 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC
- Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Adjustable time channel (Overridable). - If smoke is detected at Supply or by a signal from FAP. - If Differential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence. - Low Flow, Status (COS), overload and Runtime totalizer. - If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID)

OUTPUT DEVICE SECTION


Fan Belt Broken

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

Start

Adjustable Setpoint
DH100ACDCI DH100ACDCI

Return Air Smoke Detector Signal

Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Stop
Supply Fan

TE-702A-3B

TE-702A-3B

Supply Fan Status Monitoring & Alarming

T
Supply Air Temperature Sensor

T
Return Air Temperature Sensor

PR-274-R7VDC

Supply Fan Trip

Speed Control

P
Supply Air Pressure Sensor

- Differential pressure switch in high alarm

Clean Filter

Filter Section

- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.

Open Close
Supply Air Smoke Damper

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 4 Logic ( 1 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 8 SHEET 9 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit. - If Supply Fan is started while in Heating mode and return temperature Lower than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in Heating mode and return Temperature Highter than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected Higher than a certain limit. Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).

Modulate Valve Open

Adjustable Setpoint
DH100ACDCI DH100ACDCI

Modulate Valve Close Fully Close the Valve

Return Air Smoke Detector Signal

Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Cooling Coil

TE-702A-3B

TE-702A-3B

Supply Fan Status

T
Supply Air Temperature Sensor

T
Return Air Temperature Sensor

PR-274-R7VDC

Supply Fan Trip

P
Supply Air Pressure Sensor

Modulate Valve Open

Modulate Valve Close Fully Close the Valve

Heating Coil

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 4 Logic ( 2 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 9 SHEET 10 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

- Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer - Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence

Fan Belt Broken

TE-702A-3B DH100ACDCI

Adjustable Setpoint

Start

T
Supply Air Temperature Sensor Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Monitoring & Alarming


Supply Fan

Supply Fan Status

Stop

Supply Fan Trip

- Differential pressure switch in high alarm

Clean Filter

Filter Section

- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.

Open Close
Supply Air Smoke Damper

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 5 Logic ( 1 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 10 SHEET 11 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit.

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

Modulate Valve Open

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

TE-702A-3B DH100ACDCI

Adjustable Setpoint

Modulate Valve Close Fully Close the Valve

T
Supply Air Temperature Sensor Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Cooling Coil

Supply Fan Status

Supply Fan Trip

- If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status

Start Heater

Stop Heater

Electrical Heater

Monitoring

Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 5 Logic ( 2 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 11 SHEET 12 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC
- Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer - Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence

OUTPUT DEVICE SECTION


Fan Belt Broken

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

Start

Adjustable Setpoint
DH100ACDCI DH100ACDCI

Return Air Smoke Detector Signal

Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Monitoring & Alarming


Supply Fan

TE-702A-3B

TE-702A-3B

Stop

Supply Fan Status

T
Supply Air Temperature Sensor

T
Return Air Temperature Sensor

Supply Fan Trip

- Differential pressure switch in high alarm

Clean Filter

Filter Section

- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.

Open Close
Supply Air Smoke Damper

- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.

Open Close
Return Air Smoke Damper

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 6 Logic ( 1 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 12 SHEET 13 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences

LOGIC

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit. - If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).

Modulate Valve Open

Adjustable Setpoint
DH100ACDCI DH100ACDCI

Modulate Valve Close Fully Close the Valve

Return Air Smoke Detector Signal

Supply Air Smoke Detector Signal

Signal From Fire Alarm Panel

Cooling Coil

TE-702A-3B

TE-702A-3B

Supply Fan Status

T
Supply Air Temperature Sensor

T
Return Air Temperature Sensor

Supply Fan Trip

Start Heater

Stop Heater

Electrical Heater

Monitoring

AdvanSys Trading & Contracting


Building Management System AHU Arrangement 6 Logic ( 2 of 2 )
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 13 SHEET 14 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences
DI 220B / DI 310-01 TE-703B-3A3 P299EVB-1C

LOGIC
- Adjustable time channel ( Overridable ). - If started through Energy Management and Lead/Lag programs. - If stopped through Energy Management and Lead/Lag programs - Monitoring & Alarming of : Chillers run time totalizers. Chillers supply temperatures. pressure and flow. flow totalizer. all other available signals -Provide software interface between Chillers and BEMS. The interface must be a two-way interface and will make available at the BEMS all signals and alarms in the chillers controllers, the interface will also give the BEMS the ability to transfer commands to the chillers controllers -If the decision is taken by Lead/Lag sequence to start a certain chiller it will also start chilled water evaporator pump after making sure the chiller evaporator valve is opened. -If the decision is taken by Lead/Lag sequence to stop a certain chiller it will also stop chilled water evaporator pump. - If pump is started and a delay time T1 is expired without a positive flow indication. - If pump started or stopped and no feedback signals is recieved (status & flow) after a T2 secs delay, and alarm is generated. - COS, trip alarms. - Run-time Totalizer.

OUTPUT DEVICE SECTION

Sta rt
Stop

F
Chiller supply flow

T
Chiller supply temperature TE-703B-3A3

P
Chiller supply pressure TE-703B-3A3

Lead/Lag Sequence

P47FA-9700

T
Primary Pumps P switch Chilled water return header temperature P299EVB-1C

T
Main chilled water supply header temperature TE-703B-3A3

Chiller Interface

Monitoring & Alarming


terfa re In ce

*
Chiller

P299EVB-1C

Adjustable Setpoint

a Softw

Water Chiller

P
Chilled water supply header pressure TE-703B-3A3

P
Chilled water return header pressure P299EVB-1C

T
2-way load return header temperature P299EVB-1C

Primary Pump Trip

T
2-way load Supply header temperature DI 220B / DI 310-01

P
2-way load supply header pressure

P
2-way load return header pressure P299EVB-1C

Star t

P47FA-9700

Primary Pump Status

F
2-way load return flow Secondary Pumps P switch

P
Expansion tank pressure

Secondary Pump VSD Alarm

Stop

Chiller Valves Feedback

Secondary Pump Status

g& r in ito ing n Mo larm A

Chilled Water Primary Pump

Water Treatment Status

Water Treatment Alarm

AdvanSys Trading & Contracting


Building Management System Chilled Water System Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 1 SHEET 2 of 13 REV 0

INPUT DEVICES SECTION


Energy Management Sequences
DI 220B / DI 310-01 TE-703B-3A3 P299EVB-1C

LOGIC
-If the decision is taken by Lead/Lag sequence to start a certain chiller it will also open chilled water evaporator valve. -If the decision is taken by Lead/Lag sequence to stop a certain chiller it will also close chilled water evaporator valve. - If valve is opened and pump started and a delay time T1 is expired without a positive flow indication. - If valve is opened or closed and no feedback signals is received after a T2 seconds delay, an alarm is generated. - Adjustable time channel (Overridable) - according to Energy Management, Lead/Lag programs and load request. - Pump Status & COS. - VFD General Alarm. - Run time totalizer. - If differential pressure measured across the load is lower or equals to a certain pressure (P1), all pump will run at maximum flow output. If the differential pressure starts to increase, the system will modulate the frequency inverter supplied to modulate pump speed and based on the measured differential pressure. If the flow across the load decreases to less than the flow rate of one pump, the system will stop one pump and again start modulating the others until stopping it and vice versa. - Overload current relay will stop the pump in case of reaching maximum operating current. - The frequency inverter frequency range setting must also be set to protect motor from reaching overload so that function will never be lost. - Secondary pump operation will take place if at least one chiller is started, lead/lag sequence will decide which pump will start first. - Get pump status signals (COS), run time tantalizer, overload and lo flow indications and alarms. - Any failed/failed to start pump must be directly disabled and the next pump as per leading/lag sequence must start to replace the failed one.

OUTPUT DEVICE SECTION


Open Valve Close Valve
Chiller Evaporator valve S

F
Chiller supply flow

T
Chiller supply temperature TE-703B-3A3

P
Chiller supply pressure TE-703B-3A3

Lead/Lag Sequence

P47FA-9700

ming Alar

T
Primary Pumps P switch Chilled water return header temperature P299EVB-1C

T
chilled water supply header temperature TE-703B-3A3

Chiller Interface

P299EVB-1C

Adjustable Setpoint
Star t/s

P
Chilled water supply header pressure TE-703B-3A3

P
Chilled water return header pressure P299EVB-1C

T
2-way load return header temperature P299EVB-1C

top

Primary Pump Trip

T
2-way load Supply header temperature DI 220B / DI 310-01

P
2-way load supply header pressure

P
2-way load return header pressure P299EVB-1C

Monitoring & Alarming

P47FA-9700

Primary Pump Status

F
2-way load return flow Secondary Pumps P switch

P
Expansion tank pressure

Secondary Pump VSD Alarm

m Pu

ol ntr Co p

Chilled Water Primary Pump

Chiller Valves Feedback

Secondary Pump Status

Water Treatment Status

Water Treatment Alarm

AdvanSys Trading & Contracting


Building Management System Chilled Water System Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 2 SHEET 3 of 13 REV 0

INPUT DEVICES SECTION


Energy Management Sequences
DI 220B / DI 310-01 TE-703B-3A3 P299EVB-1C

LOGIC
-If the decision is taken by Lead/Lag sequence to start a certain chiller it will also open chilled water evaporator valve. -If the decision is taken by Lead/Lag sequence to stop a certain chiller it will also close chilled water Condenser valve. - If valve is opened and pump started and a delay time T1 is expired without a positive flow indication. - If valve is opened or closed and no feedback signals is received after a T2 seconds delay, an alarm is generated. - If the decision is taken by the Lead/Lag sequence to start a certain chiller it will also start Chiller condenser pump after making sure of the chiller condenser valve is opened. - If the decision is taken by the Lead/Lag sequence to stop a certain Chiller, it will also stop the chiller condenser pump. - If pump is started and a delay time T1 is expired without a positive flow indication - If pump is started or stopped and no feedback signals is recieved (Status&Flow) after a T2 secs delay, and alarm is generated - COS trip alarms - Run-time totalizer - If cooling tower main return header temperature lower than setpoint, valve will open in function of the deviation between main return header temperature and setpoint - If cooling tower main return header temperature higher than setpoint, valve will close in function of the deviation between main return header temperature and setpoint

OUTPUT DEVICE SECTION


Open Valve Close Valve
Chiller Evaporator valve S

F
Chiller supply flow

T
Chiller supply temperature TE-703B-3A3

P
Chiller supply pressure TE-703B-3A3

Lead/Lag Sequence

P47FA-9700

ming Alar

T
Condenser Pumps P switch TE-703B-3A3 Condenser water return header temperature TE-703B-3A3

T
Condenser water supply header temperature TE-703B-3A3

Chiller Interface

Adjustable Setpoint

T
CT return header temperature F63BT-9102

T
CT supply header temperature

T
CT return temperature F63BT-9102

Condenser Pump Trip

Star t

HL
CT High Level

LL
CT Low Level

Stop

Condenser Pump Status

g& itorin Mon ming Alar

CT Valve Status

Condensed Water Pump

CT Fan Trip

Modulate Valve Open


a lv e ate V odul se M C lo

ASPV

CT Pump Status

AdvanSys Trading & Contracting


Building Management System Condensed Water System Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 3 SHEET 4 of 13 REV 0

INPUT DEVICES SECTION


Energy Management Sequences
DI 220B / DI 310-01 TE-703B-3A3 P299EVB-1C

LOGIC
-If the decision is taken by the Lead/Lag sequence to start the corresponding Cooling Tower. -If the decision is taken by the Lead/Lag sequence to to stop the corresponding Cooling tower - If valve is commanded to open and a delay time T1 is expired without a Positive flow Indication. - If valve is opened or closed and no feedback signals is received after a T2 seconds delay, and alarm is generated.

OUTPUT DEVICE SECTION

Ope n Va lv e

F
Chiller supply flow

T
Chiller supply temperature TE-703B-3A3

P
Chiller supply pressure TE-703B-3A3

Lead/Lag Sequence

Close Valve

P47FA-9700

T
Condenser Pumps P switch TE-703B-3A3 Condenser water return header temperature TE-703B-3A3

T
Condenser water supply header temperature TE-703B-3A3

Chiller Interface

ming Alar

Cooling Tower Inlet Valves

Adjustable Setpoint

T
CT return header temperature F63BT-9102

T
CT supply header temperature

T
CT return temperature F63BT-9102

Condenser Pump Trip

- If started through Energy Management and Lead/Lag programs. - Start if CT return temperature starts to increase over setpoint ( SP1 ) - If stopped through Energy Management and Lead/Lag programs. Lead/Lag sequence logic will take the decision to stop the fan totally. - If CT return temperature starts to decrease below setpoint ( SP11 ) - If CT return temperature starts to increase over setpoint ( SP2 ) - If CT return temperature starts to decrease below setpoint ( SP21 ) -Monitoring & Alarming of : Fan status, COS, trip and run-time totalizer, high/low levels, and all other input signals

Start first speed


ed t spe p firs Sto d spee cond r t se ed Sta pe ds on ec ps Sto
g& rin ito ing n Mo larm A
Cooling Tower Fans

HL
CT High Level

LL
CT Low Level

Condenser Pump Status

CT Valve Status

CT Fan Trip

CT Pump Status

AdvanSys Trading & Contracting


Building Management System Condensed Water System Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 4 SHEET 5 of 13 REV 0

INPUT DEVICES SECTION

LOGIC

OUTPUT DEVICE SECTION

P299EVB-1C

P299EVB-1C

828-717

Energy Management Sequences Lead/Lag Sequence Adjustable Setpoint Primary Pump Status Primary Pump Normal Fault Chiller Valve Status Secondary Pump Status Secondary Pump Normal Fault

P
2-way Load supply pressure

P
2-way Load return pressure

- Adjustable time channel (Qverridable). - If started through Energy Management, Lead/ Lag programs and load request. - If the decision is taken by the lead/lag sequence to stop a certain pump. - If differential pressure measured across the load is lower or equals to a certain pressure (P1), pump will run at maximum flow output. If the differential pressure starts to increase, the system will modulate the frequency inverter supplied to modulate pump speed and based on the measured differential pressure. - Overload current relay will stop the pump in case of reaching maximum operating current. - The frequency inverter frequency range setting must also be set to protect motor from reaching overload so that function will never be lost. - Lead/lag sequence will decide which pump will start. - Get pump status signals (COS), run time tantalizer, overload and lo flow indications and alarms. - Any pump fail to start must be directly disabled and the next pump as per leading/lag sequence must start to replace the failed one. - If pump started or stopped and no feedback signals is recieved (status & flow) after a T2 secs delay, and alarm is generated. - COS, trip alarms. - Run-time Totalizer.

Start

F Stop
Chiller supply flow

TE-703B-3A3

TE-703B-3A3

T
2-way load Supply Temperature

T
2-way load return Temperature

Pump Speed Control


Chilled Water variable Speed Secondary Pumps

VFD Status

Monitoring & Alarming

AdvanSys Trading & Contracting


Building Management System Chilled Water System Logic
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 1 SHEET 2 of 20 REV 0

INPUT DEVICES SECTION

LOGIC

OUTPUT DEVICE SECTION

P233A-4-AKC

P233A-4-AKC

Signal From Fire Alarm Panel Supply Fan Status Supply Fan Trip

Supply Fan Differential Pressure switch

Filter Section Differential Pressure switch

Fans will start /stop on adjustable time channels ( Overridable ) -Stop fan in case of fan belt broken. Differential Pressure Switch in Low Alarm while fan is running. Change of state and Overload. -Run time totalizer.

Start / Stop

Fan Belt Broken


Supply Fan

Monitoring & Alarming

- Differential pressure switch in high alarm

Clean Filter
Filter Section

AdvanSys Trading & Contracting


Building Management System Single Speed Supply Fan
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 14 SHEET 15 of 20 REV 0

INPUT DEVICES SECTION

LOGIC

OUTPUT DEVICE SECTION

P233A-4-AKC

Signal From Fire Alarm Panel Exhaust Fan Status Exhaust Fan Trip

Exhaust Fan Differential Pressure switch

Fans will start /stop on adjustable time channels ( Overridable ) -Stop fan in case of fan belt broken. Differential Pressure Switch in Low Alarm while fan is running. Change of state and Overload. -Run time totalizer.

Start / Stop

Fan Belt Broken


Exhaust Fan

Monitoring & Alarming

AdvanSys Trading & Contracting


Building Management System Single Speed Exhaust Fan
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 15 SHEET 16 of 20 REV 0

INPUT DEVICES SECTION


P233A-4-AKC

LOGIC

OUTPUT DEVICE SECTION

Signal From Fire Alarm Panel

Fan Differential Pressure switch

Fans will start /stop on adjustable time channels ( Overridable ) -Stop fan in case of fan belt broken. Differential Pressure Switch in Low Alarm while fan is running. Change of state and Overload. -Run time totalizer.

Start / Stop

Fan Belt Broken


Smoke/Pressurization Fan

Fan Status

Monitoring & Alarming

Fan Trip

ECG
Project,

ENGINEERING CONSULTANTS GROUP S.A. CAIRO-EGYPT MARSA ALAM INTERNATIONAL AIRPORT CONTROL TOWER Subject, Single Speed Smoke/Pressurization Fan SIZE N.T.S Date PROJ. NO 1105/01 11.12.2006 M.G. DWG NO 1 SHEET 1 of 2 REV 0

INPUT DEVICES SECTION

LOGIC
- If Supply Fan is started while in cooling mode and space temperature higher than Setpoint, Valve will open .

OUTPUT DEVICE SECTION

Open the valve

+ On/Off Mode Fan

- If Supply Fan is started while in cooling mode and space temperature Lower than Setpoint, Valve will Close. - If Supply Fan is stopped. - If in Heating mode. - Start upon request from the user, using the room thermostat start/stop switch. - The speed of the fan can be adjusted on user requirement. - Upon request from the user, using the room thermostat start/stop switch.

Close the valve

Cooling Coil

Start

ROOM THERMOSTAT MODULE : - 3 Speed Fan Selector. - Room Temperature Sensor. - Room Temperature Setpoint. - FCU On/Off Switch.

Stop
Supply Fan

AdvanSys Trading & Contracting


Building Management System Mena House Oberoi Hotel Renovation 2-pipe Fan Coil Unit Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 11 SHEET 12 of 13 REV 0

INPUT DEVICES SECTION

LOGIC
- If Supply Fan is started while in cooling mode and space temperature higher than Setpoint, Valve will open .

OUTPUT DEVICE SECTION

Open the valve

+ On/Off Mode Fan

- If Supply Fan is started while in cooling mode and space temperature Lower than Setpoint, Valve will Close. - If Supply Fan is stopped. - If in Heating mode. - Start upon request from the user, using the room thermostat start/stop switch. - The speed of the fan can be adjusted on user requirement. - Upon request from the user, using the room thermostat start/stop switch.

Close the valve

Cooling Coil

Start

ROOM THERMOSTAT MODULE : - 3 Speed Fan Selector. - Room Temperature Sensor. - Room Temperature Setpoint. - FCU On/Off Switch.

Stop
Supply Fan

- If supply fan is started while in heating mode valve will modulate open/close in function of the deviation between setpoint and space temperature.

Modulating Valve Open/Close

Heating Coil

AdvanSys Trading & Contracting


Building Management System 2-pipe Fan Coil Unit Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 12 SHEET 13 of 13 REV 0

INPUT DEVICES SECTION

LOGIC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If supply temperature detected lower than a certain limit. - Start upon request from the user, using the room thermostat start/stop switch. - The speed of the fan can be adjusted on user requirement.

OUTPUT DEVICE SECTION


Modulate Valve Open

Modulate Valve Close Fully Close the Valve

Cooling Coil

Start

ROOM THERMOSTAT MODULE : - 3 Speed Fan Selector. - Room Temperature Sensor. - Room Temperature Setpoint. - FCU On/Off Switch.

- Upon request from the user, using the room thermostat start/stop switch. - If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).

Stop

Smoke/Pressurization Fan

Start Heater

Stop Heater

Electrical Heater

Monitoring

AdvanSys Trading & Contracting


Building Management System Fan Coil Unit Logic
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 19 SHEET 20 of 20 REV 0

INPUT DEVICES SECTION


Energy Management Sequences
TE-703B-3A3 TE-703B-3A3 P299EVB-1C

LOGIC
- If the decision is taken by the lead/lag sequence to start a certain pump.

OUTPUT DEVICE SECTION

Start

T
3-way load return temperature P47FA-9700

T
3-way load supply temperature TE-703B-3A3

P
3-way load supply pressure TE-703B-3A3

Adjustable Setpoint

- If the decision is taken by the lead/lag sequence to stop a certain pump. - If pump is started and a delay time T1 is expired without a positive flow indication. - If pump is started or stopped and no feedback signals is received (Status & Flow) after a T2 secs delay, and alarm is generated - COS trip alarms - Run-time totalizer

Stop

T
Hot water Pumps P switch P299EVB-1C Heat Exchanger supply temperature

T
Heat Exchanger return temperature P299EVB-1C

Hot Water Pump Trip

g& itorin Mon ming Alar

Hot Water Pumps

Hot Water Pump Status - Valve will modulate open/ close in order to achieve the 3-way load supply hot water temperature at a certain level (setpoint ) Modulating Valve Open/Close
M Heat Echanger Temperature Regulating Valve

P
Heat Exchanger supply pressure

P
Heat Exchanger return pressure

Lead/Lag Sequence

AdvanSys Trading & Contracting


Building Management System Hot Water System Logic
SIZE N.T.S Date 11.06.2006 A. M. A. FSCM NO DWG NO 5 SHEET 6 of 13 REV 0

INPUT DEVICES SECTION

LOGIC

OUTPUT DEVICE SECTION

Fans Affected:
-SM.F-1 -SM.F-2 -P.F-1 -P.F-2

Signal from Fire Alarm Panel

-Fans will start /stop upon fire signal from FAP. -Stop fan in case of fan belt broken.

S/S
n roke elt B B Fan

P233A-4-AKC

Supply Fan Differential Pressure Switch

-Differential Pressure Switch in Lo Alarm while fan is running.

Mo

* ing tor ni

ng mi ar l

Toilet Fans

-change of state and Overload. -Run time totalizer.

AdvanSys Buildings Technology


Building Management System
Smoke Exhaust & staircase PressurA. M. A.ation Fans Logic
SA .M . A.E FSCM NO DWG NO 0 N.T.S Date .. A .M .A. SHEET 11 OF 13 REV

INPUT DEVICES SECTION

LOGIC

OUTPUT DEVICE SECTION

Signal From Fire Alarm Panel

All VAV boxes control could be stopped on request from the main BMS software.

DP
VAV BOX Air Velocity Sensor

Supply Fan Status Supply Fan Trip - If space temperature less than setpoint, damper will close in function of the deviation between space temperature and setpoit (PID). - If space temperature higher than setpoint, damper will close in function of the deviation between space temperature and setpoit (PID). Modulate Damper Close

Modulate Damper Open

Supply VAV Box Damper

Room Module: - Room Temperature Sensor - Room Temperature Setpoint

AdvanSys Trading & Contracting


Building Management System Variable Air Volume Box (VAV) Logic
SIZE N.T.S Date 4.09.2006 A. M. A. FSCM NO DWG NO 18 SHEET 19 of 20 REV 0