Sequence of operation
LOGIC
Energy Management Sequences - Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer
Start
Adjustable Setpoint
T
Supply Air Temperature Sensor Return Air Smoke Detector Signal Supply Air Smoke Detector Signal
HU-226-VCD-3
H/T
Return Air Temperature/Humidity Sensor
- Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence
Stop
- Differential Pressure Switch in Low alarm while fan is running. - Adjustable Time Channel. (overridable) - If Supply Fan started. - If Smoke detected at either supply or return, and return temperature less than high limit. - Status (COS), Overload and run time totalizer. - Adjustable Time Channel.. - If Fan Belt Broken. - If Supply Fan is stopped and no smoke detected either in supply and return air.
Start
Return Fan
Clean Filter
Filter Section
LOGIC
- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return.
P233A-4-AKC
P233A-4-AKC
P233A-4-AKC
Adjustable Setpoint
Open Close
Return Air Smoke Damper
T
Supply Air Temperature Sensor Return Air Smoke Detector Signal Supply Air Smoke Detector Signal
- Through Enthalpy Control Software. - If supply Fan Stopped. - If smoke is detected at either Supply or return. - Through Enthalpy Control Software.
HU-226-VCD-3
H/T
Return Air Temperature/Humidity Sensor
Supply Fan Trip - Through Enthalpy Control Software. Return Fan Status - If supply Fan Stopped. - If smoke is detected at either Supply or return. - Through Enthalpy Control Software. Return Fan Trip - If smoke is detected at either Supply or return. - Through Enthalpy Control Software. - In case of Return fan stopped. - Through Enthalpy Control block.
Fully Opened
LOGIC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit. - If Supply Fan is started while in Heating mode and return temperature Lower than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in Heating mode and return Temperature Highter than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected Higher than a certain limit.
P233A-4-AKC
P233A-4-AKC
P233A-4-AKC
Adjustable Setpoint
T
Supply Air Temperature Sensor Return Air Smoke Detector Signal Supply Air Smoke Detector Signal
Cooling Coil
HU-226-VCD-3
H/T
Return Air Temperature/Humidity Sensor
Heating Coil
Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).
LOGIC
Energy Management Sequences - Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer
Start
Adjustable Setpoint
DH100ACDCI DH100ACDCI
HU-226-VCD-3
HU-226-VCD-3
H/T
Supply Air Temperature/Humidity Sensor
H/T
Return Air Temperature/Humidity Sensor
- Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence - Differential pressure switch in high alarm - If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return. - If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return. - If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit.
Stop
Clean Filter
Filter Section
Open Close
Supply Air Smoke Damper
Open Close
Return Air Smoke Damper
Cooling Coil
LOGIC
- If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status - If supply humidity Lower / higher than setpoint, valve Act. Will open / close in function of the deviation between supply humidity and setpoint (PID). - If Supply Fan is started while in cooling mode, and supply humidity highter than Set point, heater will start. The number of stages to be started is function of the deviation between Set point and Supply humidity. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in Cooling mode, and supply humidity lower than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Set point and Supply humidity. - Stop heater completely if supply humidity is lower than a certain value. - Get heater steps status Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).
P233A-4-AKC
P233A-4-AKC
Start Heater
Adjustable Setpoint
DH100ACDCI DH100ACDCI
Stop Heater
Electrical Pre-Heater
HU-226-VCD-3
HU-226-VCD-3
Monitoring
H/T
Supply Air Temperature/Humidity Sensor
H/T
Return Air Temperature/Humidity Sensor
Stop Heater
Electrical Re-Heater
Monitoring
LOGIC
Energy Management Sequences - Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer
Start
TE-702A-3B DH100ACDCI
Adjustable Setpoint
T
Supply Air Temperature/Humidity Sensor Supply Air Smoke Detector Signal
- Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence - Differential pressure switch in high alarm
Stop
Clean Filter
Filter Section
- If no smoke is detected at Supply or return. - If smoke is detected at either Supply or return. - If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit.
Open Close
Supply Air Smoke Damper
Cooling Coil
LOGIC
- Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Adjustable time channel (Overridable). - If smoke is detected at Supply or by a signal from FAP. - If Differential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence. - Low Flow, Status (COS), overload and Runtime totalizer. - If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID)
P233A-4-AKC
P233A-4-AKC
Start
Adjustable Setpoint
DH100ACDCI DH100ACDCI
Stop
Supply Fan
TE-702A-3B
TE-702A-3B
T
Supply Air Temperature Sensor
T
Return Air Temperature Sensor
PR-274-R7VDC
Speed Control
P
Supply Air Pressure Sensor
Clean Filter
Filter Section
Open Close
Supply Air Smoke Damper
LOGIC
P233A-4-AKC
P233A-4-AKC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit. - If Supply Fan is started while in Heating mode and return temperature Lower than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in Heating mode and return Temperature Highter than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected Higher than a certain limit. Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).
Adjustable Setpoint
DH100ACDCI DH100ACDCI
Cooling Coil
TE-702A-3B
TE-702A-3B
T
Supply Air Temperature Sensor
T
Return Air Temperature Sensor
PR-274-R7VDC
P
Supply Air Pressure Sensor
Heating Coil
LOGIC
P233A-4-AKC
P233A-4-AKC
- Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer - Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence
TE-702A-3B DH100ACDCI
Adjustable Setpoint
Start
T
Supply Air Temperature Sensor Supply Air Smoke Detector Signal
Stop
Clean Filter
Filter Section
Open Close
Supply Air Smoke Damper
LOGIC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit.
P233A-4-AKC
P233A-4-AKC
TE-702A-3B DH100ACDCI
Adjustable Setpoint
T
Supply Air Temperature Sensor Supply Air Smoke Detector Signal
Cooling Coil
- If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status
Start Heater
Stop Heater
Electrical Heater
Monitoring
Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).
LOGIC
- Differential Pressure Switch in Low alarm while fan is running. - Adjustable time channel (overridable) - If stopped by energy management sequences. and maximum stop time configured expires. - If decided by energy management sequences. - Low Flow, Status (COS), overload and Runtime totalizer - Adjustable time channel (Overridable) - If smoke is detected at Supply or by a signal from FAP - If Diffrential Pressure Switch in Low alarm while fan is running - If decided by Energy Management sequence
P233A-4-AKC
P233A-4-AKC
Start
Adjustable Setpoint
DH100ACDCI DH100ACDCI
TE-702A-3B
TE-702A-3B
Stop
T
Supply Air Temperature Sensor
T
Return Air Temperature Sensor
Clean Filter
Filter Section
Open Close
Supply Air Smoke Damper
Open Close
Return Air Smoke Damper
LOGIC
P233A-4-AKC
P233A-4-AKC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If smoke detected at either supply or return or as indicated by FAP signal. - If fan belt broken. - If supply temperature detected lower than a certain limit. - If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).
Adjustable Setpoint
DH100ACDCI DH100ACDCI
Cooling Coil
TE-702A-3B
TE-702A-3B
T
Supply Air Temperature Sensor
T
Return Air Temperature Sensor
Start Heater
Stop Heater
Electrical Heater
Monitoring
LOGIC
- Adjustable time channel ( Overridable ). - If started through Energy Management and Lead/Lag programs. - If stopped through Energy Management and Lead/Lag programs - Monitoring & Alarming of : Chillers run time totalizers. Chillers supply temperatures. pressure and flow. flow totalizer. all other available signals -Provide software interface between Chillers and BEMS. The interface must be a two-way interface and will make available at the BEMS all signals and alarms in the chillers controllers, the interface will also give the BEMS the ability to transfer commands to the chillers controllers -If the decision is taken by Lead/Lag sequence to start a certain chiller it will also start chilled water evaporator pump after making sure the chiller evaporator valve is opened. -If the decision is taken by Lead/Lag sequence to stop a certain chiller it will also stop chilled water evaporator pump. - If pump is started and a delay time T1 is expired without a positive flow indication. - If pump started or stopped and no feedback signals is recieved (status & flow) after a T2 secs delay, and alarm is generated. - COS, trip alarms. - Run-time Totalizer.
Sta rt
Stop
F
Chiller supply flow
T
Chiller supply temperature TE-703B-3A3
P
Chiller supply pressure TE-703B-3A3
Lead/Lag Sequence
P47FA-9700
T
Primary Pumps P switch Chilled water return header temperature P299EVB-1C
T
Main chilled water supply header temperature TE-703B-3A3
Chiller Interface
*
Chiller
P299EVB-1C
Adjustable Setpoint
a Softw
Water Chiller
P
Chilled water supply header pressure TE-703B-3A3
P
Chilled water return header pressure P299EVB-1C
T
2-way load return header temperature P299EVB-1C
T
2-way load Supply header temperature DI 220B / DI 310-01
P
2-way load supply header pressure
P
2-way load return header pressure P299EVB-1C
Star t
P47FA-9700
F
2-way load return flow Secondary Pumps P switch
P
Expansion tank pressure
Stop
LOGIC
-If the decision is taken by Lead/Lag sequence to start a certain chiller it will also open chilled water evaporator valve. -If the decision is taken by Lead/Lag sequence to stop a certain chiller it will also close chilled water evaporator valve. - If valve is opened and pump started and a delay time T1 is expired without a positive flow indication. - If valve is opened or closed and no feedback signals is received after a T2 seconds delay, an alarm is generated. - Adjustable time channel (Overridable) - according to Energy Management, Lead/Lag programs and load request. - Pump Status & COS. - VFD General Alarm. - Run time totalizer. - If differential pressure measured across the load is lower or equals to a certain pressure (P1), all pump will run at maximum flow output. If the differential pressure starts to increase, the system will modulate the frequency inverter supplied to modulate pump speed and based on the measured differential pressure. If the flow across the load decreases to less than the flow rate of one pump, the system will stop one pump and again start modulating the others until stopping it and vice versa. - Overload current relay will stop the pump in case of reaching maximum operating current. - The frequency inverter frequency range setting must also be set to protect motor from reaching overload so that function will never be lost. - Secondary pump operation will take place if at least one chiller is started, lead/lag sequence will decide which pump will start first. - Get pump status signals (COS), run time tantalizer, overload and lo flow indications and alarms. - Any failed/failed to start pump must be directly disabled and the next pump as per leading/lag sequence must start to replace the failed one.
F
Chiller supply flow
T
Chiller supply temperature TE-703B-3A3
P
Chiller supply pressure TE-703B-3A3
Lead/Lag Sequence
P47FA-9700
ming Alar
T
Primary Pumps P switch Chilled water return header temperature P299EVB-1C
T
chilled water supply header temperature TE-703B-3A3
Chiller Interface
P299EVB-1C
Adjustable Setpoint
Star t/s
P
Chilled water supply header pressure TE-703B-3A3
P
Chilled water return header pressure P299EVB-1C
T
2-way load return header temperature P299EVB-1C
top
T
2-way load Supply header temperature DI 220B / DI 310-01
P
2-way load supply header pressure
P
2-way load return header pressure P299EVB-1C
P47FA-9700
F
2-way load return flow Secondary Pumps P switch
P
Expansion tank pressure
m Pu
ol ntr Co p
LOGIC
-If the decision is taken by Lead/Lag sequence to start a certain chiller it will also open chilled water evaporator valve. -If the decision is taken by Lead/Lag sequence to stop a certain chiller it will also close chilled water Condenser valve. - If valve is opened and pump started and a delay time T1 is expired without a positive flow indication. - If valve is opened or closed and no feedback signals is received after a T2 seconds delay, an alarm is generated. - If the decision is taken by the Lead/Lag sequence to start a certain chiller it will also start Chiller condenser pump after making sure of the chiller condenser valve is opened. - If the decision is taken by the Lead/Lag sequence to stop a certain Chiller, it will also stop the chiller condenser pump. - If pump is started and a delay time T1 is expired without a positive flow indication - If pump is started or stopped and no feedback signals is recieved (Status&Flow) after a T2 secs delay, and alarm is generated - COS trip alarms - Run-time totalizer - If cooling tower main return header temperature lower than setpoint, valve will open in function of the deviation between main return header temperature and setpoint - If cooling tower main return header temperature higher than setpoint, valve will close in function of the deviation between main return header temperature and setpoint
F
Chiller supply flow
T
Chiller supply temperature TE-703B-3A3
P
Chiller supply pressure TE-703B-3A3
Lead/Lag Sequence
P47FA-9700
ming Alar
T
Condenser Pumps P switch TE-703B-3A3 Condenser water return header temperature TE-703B-3A3
T
Condenser water supply header temperature TE-703B-3A3
Chiller Interface
Adjustable Setpoint
T
CT return header temperature F63BT-9102
T
CT supply header temperature
T
CT return temperature F63BT-9102
Star t
HL
CT High Level
LL
CT Low Level
Stop
CT Valve Status
CT Fan Trip
ASPV
CT Pump Status
LOGIC
-If the decision is taken by the Lead/Lag sequence to start the corresponding Cooling Tower. -If the decision is taken by the Lead/Lag sequence to to stop the corresponding Cooling tower - If valve is commanded to open and a delay time T1 is expired without a Positive flow Indication. - If valve is opened or closed and no feedback signals is received after a T2 seconds delay, and alarm is generated.
Ope n Va lv e
F
Chiller supply flow
T
Chiller supply temperature TE-703B-3A3
P
Chiller supply pressure TE-703B-3A3
Lead/Lag Sequence
Close Valve
P47FA-9700
T
Condenser Pumps P switch TE-703B-3A3 Condenser water return header temperature TE-703B-3A3
T
Condenser water supply header temperature TE-703B-3A3
Chiller Interface
ming Alar
Adjustable Setpoint
T
CT return header temperature F63BT-9102
T
CT supply header temperature
T
CT return temperature F63BT-9102
- If started through Energy Management and Lead/Lag programs. - Start if CT return temperature starts to increase over setpoint ( SP1 ) - If stopped through Energy Management and Lead/Lag programs. Lead/Lag sequence logic will take the decision to stop the fan totally. - If CT return temperature starts to decrease below setpoint ( SP11 ) - If CT return temperature starts to increase over setpoint ( SP2 ) - If CT return temperature starts to decrease below setpoint ( SP21 ) -Monitoring & Alarming of : Fan status, COS, trip and run-time totalizer, high/low levels, and all other input signals
HL
CT High Level
LL
CT Low Level
CT Valve Status
CT Fan Trip
CT Pump Status
LOGIC
P299EVB-1C
P299EVB-1C
828-717
Energy Management Sequences Lead/Lag Sequence Adjustable Setpoint Primary Pump Status Primary Pump Normal Fault Chiller Valve Status Secondary Pump Status Secondary Pump Normal Fault
P
2-way Load supply pressure
P
2-way Load return pressure
- Adjustable time channel (Qverridable). - If started through Energy Management, Lead/ Lag programs and load request. - If the decision is taken by the lead/lag sequence to stop a certain pump. - If differential pressure measured across the load is lower or equals to a certain pressure (P1), pump will run at maximum flow output. If the differential pressure starts to increase, the system will modulate the frequency inverter supplied to modulate pump speed and based on the measured differential pressure. - Overload current relay will stop the pump in case of reaching maximum operating current. - The frequency inverter frequency range setting must also be set to protect motor from reaching overload so that function will never be lost. - Lead/lag sequence will decide which pump will start. - Get pump status signals (COS), run time tantalizer, overload and lo flow indications and alarms. - Any pump fail to start must be directly disabled and the next pump as per leading/lag sequence must start to replace the failed one. - If pump started or stopped and no feedback signals is recieved (status & flow) after a T2 secs delay, and alarm is generated. - COS, trip alarms. - Run-time Totalizer.
Start
F Stop
Chiller supply flow
TE-703B-3A3
TE-703B-3A3
T
2-way load Supply Temperature
T
2-way load return Temperature
VFD Status
LOGIC
P233A-4-AKC
P233A-4-AKC
Signal From Fire Alarm Panel Supply Fan Status Supply Fan Trip
Fans will start /stop on adjustable time channels ( Overridable ) -Stop fan in case of fan belt broken. Differential Pressure Switch in Low Alarm while fan is running. Change of state and Overload. -Run time totalizer.
Start / Stop
Clean Filter
Filter Section
LOGIC
P233A-4-AKC
Signal From Fire Alarm Panel Exhaust Fan Status Exhaust Fan Trip
Fans will start /stop on adjustable time channels ( Overridable ) -Stop fan in case of fan belt broken. Differential Pressure Switch in Low Alarm while fan is running. Change of state and Overload. -Run time totalizer.
Start / Stop
LOGIC
Fans will start /stop on adjustable time channels ( Overridable ) -Stop fan in case of fan belt broken. Differential Pressure Switch in Low Alarm while fan is running. Change of state and Overload. -Run time totalizer.
Start / Stop
Fan Status
Fan Trip
ECG
Project,
ENGINEERING CONSULTANTS GROUP S.A. CAIRO-EGYPT MARSA ALAM INTERNATIONAL AIRPORT CONTROL TOWER Subject, Single Speed Smoke/Pressurization Fan SIZE N.T.S Date PROJ. NO 1105/01 11.12.2006 M.G. DWG NO 1 SHEET 1 of 2 REV 0
LOGIC
- If Supply Fan is started while in cooling mode and space temperature higher than Setpoint, Valve will open .
- If Supply Fan is started while in cooling mode and space temperature Lower than Setpoint, Valve will Close. - If Supply Fan is stopped. - If in Heating mode. - Start upon request from the user, using the room thermostat start/stop switch. - The speed of the fan can be adjusted on user requirement. - Upon request from the user, using the room thermostat start/stop switch.
Cooling Coil
Start
ROOM THERMOSTAT MODULE : - 3 Speed Fan Selector. - Room Temperature Sensor. - Room Temperature Setpoint. - FCU On/Off Switch.
Stop
Supply Fan
LOGIC
- If Supply Fan is started while in cooling mode and space temperature higher than Setpoint, Valve will open .
- If Supply Fan is started while in cooling mode and space temperature Lower than Setpoint, Valve will Close. - If Supply Fan is stopped. - If in Heating mode. - Start upon request from the user, using the room thermostat start/stop switch. - The speed of the fan can be adjusted on user requirement. - Upon request from the user, using the room thermostat start/stop switch.
Cooling Coil
Start
ROOM THERMOSTAT MODULE : - 3 Speed Fan Selector. - Room Temperature Sensor. - Room Temperature Setpoint. - FCU On/Off Switch.
Stop
Supply Fan
- If supply fan is started while in heating mode valve will modulate open/close in function of the deviation between setpoint and space temperature.
Heating Coil
LOGIC
- If Supply Fan is started while in cooling mode and return temperature higher than setpoint, valve will open in function of the deviation between setpoint and return temperature. (PID) - If Supply Fan is started while in cooling mode and return Temperature lower than setpoint, valve will close in function of the deviation between setpoint and supply temperature (PID) - If Supply Fan is Stopped. - If supply temperature detected lower than a certain limit. - Start upon request from the user, using the room thermostat start/stop switch. - The speed of the fan can be adjusted on user requirement.
Cooling Coil
Start
ROOM THERMOSTAT MODULE : - 3 Speed Fan Selector. - Room Temperature Sensor. - Room Temperature Setpoint. - FCU On/Off Switch.
- Upon request from the user, using the room thermostat start/stop switch. - If Supply Fan is started while in heating mode, and supply temperature lower than Setpoint, heater will start. The number of stages to be started is function of the deviation between Setpoint and Supply temperature. - If Supply Fan is stopped. - If no flow detected. - If Supply fan started while in heating mode, and supply temperature higher than Set point, heater will stop. The number of stages to be stopped is function of the deviation between Setpoint and Supply temperature. - Stop heater completely if supply temperature is detected higher than a certain value. (Overheat Protection) - Get heater steps status Transfer between heating mode in winter time and cooling mode in summer time will have to take place automatically. The DDC will decide whether to follow cooling/heating modes based on outside air temperature . If outside air temperature is less than a certain limit TL heating mode will take place. If outside air temperature is higher than a certain limit TH cooling mode will take place. A range of x degrees between TH and TL will be left to optimize energy usage ( dead band zone ).
Stop
Smoke/Pressurization Fan
Start Heater
Stop Heater
Electrical Heater
Monitoring
LOGIC
- If the decision is taken by the lead/lag sequence to start a certain pump.
Start
T
3-way load return temperature P47FA-9700
T
3-way load supply temperature TE-703B-3A3
P
3-way load supply pressure TE-703B-3A3
Adjustable Setpoint
- If the decision is taken by the lead/lag sequence to stop a certain pump. - If pump is started and a delay time T1 is expired without a positive flow indication. - If pump is started or stopped and no feedback signals is received (Status & Flow) after a T2 secs delay, and alarm is generated - COS trip alarms - Run-time totalizer
Stop
T
Hot water Pumps P switch P299EVB-1C Heat Exchanger supply temperature
T
Heat Exchanger return temperature P299EVB-1C
Hot Water Pump Status - Valve will modulate open/ close in order to achieve the 3-way load supply hot water temperature at a certain level (setpoint ) Modulating Valve Open/Close
M Heat Echanger Temperature Regulating Valve
P
Heat Exchanger supply pressure
P
Heat Exchanger return pressure
Lead/Lag Sequence
LOGIC
Fans Affected:
-SM.F-1 -SM.F-2 -P.F-1 -P.F-2
-Fans will start /stop upon fire signal from FAP. -Stop fan in case of fan belt broken.
S/S
n roke elt B B Fan
P233A-4-AKC
Mo
* ing tor ni
ng mi ar l
Toilet Fans
LOGIC
All VAV boxes control could be stopped on request from the main BMS software.
DP
VAV BOX Air Velocity Sensor
Supply Fan Status Supply Fan Trip - If space temperature less than setpoint, damper will close in function of the deviation between space temperature and setpoit (PID). - If space temperature higher than setpoint, damper will close in function of the deviation between space temperature and setpoit (PID). Modulate Damper Close