Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.

6 kV, ANSI, Air-Insulated, Extendable


Medium-Voltage Switchgear Catalog HA 41.31 2008

Answers for energy.

Contents
Application, Requirements Typical uses, features Technical Data Electrical data, pressure values, temperature Switchgear installation Shipping data Product Range Product range overview, equipment features Panels Design Panel design Components Two/three-position switch-disconnector Two/three-position switch Busbars, HV CL (current-limiting) fuse assembly Operating mechanisms Indicating and measuring equipment Transformers Cable connection Dimensions (in mm/inch) Panels Floor openings, fixing points Standards Standards, specifications, guidelines Notes 42 Invalid: Catalog HA 41.31 2007 40 and 41 30 to 38 39 20 21 22 and 23 24 25 26 and 27 28 and 29 19 8 and 9 10 to 18 5 6 7 Page 2 to 4
R-HA41-086 eps

Application

SIMOSEC ANSI switchgear

2008 Siemens Power Transmission & Distribution, Inc. SIEMENS is a registered trademark of Siemens AG.

2 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Application
Typical uses
R-HA41-109 eps

R-HA41-085 eps

R-HA41-110 eps

R-HA41-111 eps

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 3

R-HA41-112 eps

Application, Requirements
Features
SIMOSEC ANSI switchgear is a factory-assembled, typetested, three-phase, metalenclosed, indoor switchgear according to ANSI/IEEE C37.20.3 * for single busbars. Typical uses SIMOSEC ANSI switchgear is used for power distribution in distribution systems with feeder currents up to 1200 A. Modular space-saving design allows use in
Substations, customer trans-

Technical features
Air-insulated indoor

Reliability
Type (design) tested with

Mechanical switch position

switchgear
Gas-insulated, maintenance-

third-party witness
Standardized and manu-

indications integrated in mimic diagram


Switchgear interlocking

free switching functions for the two/three-position switch


Three-pole primary enclosure Phases arranged one behind

factured using numerically controlled machines


Quality management system

system with logical mechanical interlocks Life-cycle cost-efficiency Extremely low life-cycle costs and extremely high availability throughout the entire product service life cycle as a result of:
Two/three-position switch

according to ISO 9001


More than 500,000 switchgear

the other
No cross-insulation between

phases
Busbar system at the top or

panels in operation worldwide for many years


No cross-insulation between

fer substations, distribution substations and switching substations of power supply and public utilities
Public buildings, such as

bottom, as required by application


Air-insulated busbar and cable

phases Personal safety


All switching operations can

with gas-insulated quenching principle


Minimum space requirement Easy switchgear extension

connection system
Two/three-position switch,

high-rise buildings, railway stations, hospitals


Industrial plants

metal-enclosed, with airinsulated primary terminals and gas-insulated switching functions


Hermetically-sealed (welded)

be performed with closed panel front


Metal-enclosed switchgear HV CL fuses and cable termi-

Electrical features
Rated voltages up to 27.6 kV Rated short-circuit current

Typical examples
Office parks Airports Underground railway stations Sewage treatment plants Schools Shopping centers Petroleum industry Chemical industry Industrial plants Textile, paper and

stainless-steel switchgear vessel, For switching devices With welded-in bushings (for electrical connections and mechanical components) With insulating gas SF6
Metal-enclosed design Pressure relief

nations are only accessible when the outgoing feeders are grounded
Logical mechanical inter-

(fused) up to 63 kA at 15 kV and below, and 20 kA at 27.6 kV


Rated short-time withstand

locking
Capacitive voltage detection

system for verification of safe isolation from supply


Grounding of outgoing feeders

current up to 20 kA, 2 second or 25 kA, 2 seconds


Rated normal current of

by means of make-proof grounding switches Security of operation


Components, e.g., operating

To the rear and upwards Separately for each compartment


Air-insulated cable connection

feeders Up to 600 A (feeders) Up to 1200 A (panel without switch)


Rated normal current of

busbar up to 1200 A

food industry Modular design


Individual panels, for free

system for conventional cable lugs


Three-phase current trans-

mechanisms, three-position switches proven for years


Metal-enclosed panels plus

former, factory-assembled on the feeder bushings


Integrated low-voltage niche

combination and extension

(standard) for installation of low-voltage devices E.g. terminals, pushbuttons MCBs


Option: Space heaters for

metal compartmentalization between busbar and switching device and between switching device and cable connection compartment
Three-position switch metal-

severe ambient conditions, e.g. condensation

enclosed with gas-insulated switching functions Welded sealed-for-life switchgear vessel No cross-insulation between phases With welded-in bushings for cable connection, busbar and operating mechanism
Switch operating mechanisms

outside switchgear vessel


Maintenance-free operating

mechanism parts

* Standards see page 40


4 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Technical Data
Electrical data of panels, pressure values, temperature
Complete switchgear
Rated insulation level Rated voltage Ur kV Rated short-duration (one minute) power-frequency kV withstand voltage Ud, rms Rated lightning impulse withstand voltage Up, peak kV Hz On request A Standard A for switchgear with all feeders fused (panel type FS) kA (sym) kA (asym) kA (peak) for switchgear with tk = 2 s rated duration up to kA up to kA PSI (kPa) at 20 C/68 F (absolute) for panels without secondary equipment C/F 4.76 19 60 50/60 600 1200 63 101 164 20 25 52 65 21.8 (150) 18.9 (130) 15 36 95 27.6 60 125

Rated frequency fr Rated continuous current Ir 1) of busbar Rated short-circuit current

Rated short-time withstand current Ik 6) Rated peak withstand current Ip 6) Rated filling pressure pre 2) Minimum operating pressure pme 2) Ambient temperature T

63 101 164 20 52

25 65

20 32 52 20 52

-30 to +40 / -22 to +104

Cable switch panel type CS, cable connection panel type CC, cable grounding panel type CG
Rated voltage Ur Rated continuous current Ir 1) Rated fault closing current Ima 6) for panel type CS, CG only for panel type CC only for panel type CS kV A A kA (asym) kA (peak) 4.76 600 600, 1200 32 40 52 65 15 27.6

32 52

40 65

32 52

Fuse panel types FS, FU


Rated voltage Ur Rated continuous current Ir 1) 4) Rated peak withstand current Ip 5) Rated fault closing current Ima 5) Reference dimension e 3) Maximum fuse rating for feeder only for panel type FS for HV CL (current limiting) fuses for panel FS-1 for panel FS-2 for panel FS-3 kV A up to kA kA (asym) kA (peak) mm/inch A A A 4.76 200, 600 164 101 164 537/21.1 450E two 350E three 200E 15 164 101 164 200E two 200E three 200E 27.6 52 32 52 65E two 65E three 65E

Busbar grounding panel type BG


Rated voltage Ur Rated fault closing current Ima 6) kV kA (asym) kA (peak) 4.76 32 52 40 65 15 32 52 40 65 27.6 32 52

Busbar voltage metering switch panel types MS2, MS3


Rated voltage Ur Rated peak withstand current Ip 5) Rated fault closing current Ima 5) kV up to kA kA (asym) kA (peak) 4.76 52 32 52 65 40 65 15 52 32 52 65 40 65 27.6 52 32 52

Metering panel types MT3, MC3, bus riser panel BR


Rated voltage Ur Rated continuous current Ir 1) kV A 4.76 600, 1200 15 27.6

1) The rated continuous currents apply to ambient temperatures of 40 C/104 F. 2) Pressure values for SF6-insulated vessels. 3) The fuse assembly is designed for a reference dimension e = 537 mm/21.1 inch. With reference dimension e = 442 mm/17.4 inch, an extension tube (95 mm/3.7 inch long) is required. 4) Depending on the HV CL fuse links. 5) Fused 6) Without fuses

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 5

Technical Data
Switchgear installation
Room planning Room planning (dimensions in mm/inch) Switchgear installation Wall-standing or free-standing arrangement Single row Double row (for face-to-face arrangement)
2550/100.5 *

Switchgear room

1 2
2600/102.4 2550/100.5 *

Switchgear room

2250/88.5

Door dimensions The door dimensions depend on the Number of panels in a transport unit Height of the panel Switchgear fastening
For floor openings and

2250/88.5

See opposite dimension drawings

1080/42.5 1230/48.4 >950/37.5***

1080/42.5

2600/102.4
1230/48.4 >950/37.5***

Room dimensions

5 6

600/23.5 **

210 8.3

850/33.5

90/3.5

10

210 8.3

850/33.5

90/3.5

fixing points of the switchgear, see page 39


Foundations:

Cable basement

Cable basement

Wall-standing arrangement (side view)

Free-standing arrangement (side view)

Steel structure Steel-reinforced concrete Panel dimensions

600/23.5 **

50/2 150/6

11 12

150/6

15

Weight The weight of a panel depends on the extent to which it is equipped (e.g. with motor operating mechanism, voltage transformer). For details, please refer to page 7.

10/0.4

50/2

See pages 30 to 38

HA41-2510a eps

Plan view

1 Relief opening 2 Direction of pressure relief 3 Pressure relief of switchgear 4 Room height 5 Individual panel depth 6 Control aisle 7 Option: Floor cover 8 Cable

* Switchgear height 2250 mm /


88.5" or 2550 mm / 100.5"

** Depending on bending radius of


cable

*** 950/37.5 distance shown is the


space required by the equipment. The actual space must also reflect requirements of applicable codes (e.g. NEC) or standards and regulations.

6 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

HA41-2511a eps

10/0.4

50/2

13 14

Plan view

9 Foundation 10 Height of cable basement corresponding to cable bending radius 11 Wall distance 12 Side wall distance 13 Panel width 14 End wall 15 Depth of pressure relief duct

Technical Data
Shipping data
Transport units for shipping (plan view)
T2 T1

Transport of individual panels


Panel type Cable switch panel Fuse switch panel CS1 CS2 FS1 FS2 FS3 FU1 FU2 FU3 CC1 CC2 CG1 CG2 MT3 MC3 MS2 MS3 BR1 BR2 BG1 Weight kg/lb 180/397 205/452 205/452 230/507 250/551 160/353 185/408 210/463 145/320 170/375 180/397 205/452 420/926 420/926 350/772 420/926 145/320 170/375 180/397 Width B1 mm / inch 375 / 14.8 500 / 19.7 375 / 14.8 500 / 19.7 750 / 29.5 375 / 14.8 500 / 19.7 750 / 29.5 375 / 14.8 500 / 19.7 375 / 14.8 500 / 19.7 750 / 29.5 750 / 29.5 500 / 19.7 750 / 29.5 375 / 14.8 500 / 19.7 375 / 14.8 Height H1 mm / inch 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 2250 / 88.6 Depth T1 mm / inch 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4 1230 / 48.4

1 3

HA41-2512 eps

B1

B2

Fuse panel

With individual panel Cable connection panel


T2 T1

Cable grounding panel

1
Metering panel Metering cable panel Metering switch panel Bus riser panel

3 2
B1

4 2
B3 B2 B1

Busbar grounding panel

Transport of combinations of different individual panels


Transport unit Overall width B3 Weight * Width B2 Height H2 ** Depth T2 Volume B2 x H2 x T2 m3 / yd3 3.8 / 5.0 7.6 / 10.0

HA41-2513 eps

B1

mm / inch Transport unit With combinations of different individual panels Transport unit w 750 / 29.5 w 1750 / 58.9

kg/lb 70/155 120/265

mm / inch 1100 / 43.3 2200 / 86.6

mm / inch 2450 / 96.5 2450 / 96.5

mm / inch 1400 / 56.1 1400 / 56.1

Top case necessary for cable top entry, delivered in accessory bag 1 T1 = Depth of individual panel 2 Individual panel dimension B1 x T1 3 Transport unit, dimension B2 x T2 4 B3 = Overall width of combination of different individual panels 5 B2 = Width of the transport unit

Packing, transport (examples)


Packing Panels mounted on wooden floor and covered with protection sheeting Version For container For supply Overseas Transport Ship + truck

* Additional packing weight in kg/lb (without weight of panels) ** Transport unit for air freight, height H2 2610 mm /102.8 inch
and width B2 1700 mm /66.9 inch

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 7

Product Range
Product range overview
Panel designation Panel type Panel width

Standard panels
R-HA41-087 eps

Column No. Cable switch panel Cable switch panel type CS CS1 CS2 Fuse switch panel FS1 FS2
R-HA41-088 eps

375 mm / 14.8" 500 mm / 19.7" 375 mm / 14.8" 500 mm / 19.7" 750 mm / 29.5" 375 mm / 14.8" 500 mm / 19.7" 750 mm / 29.5" 375 mm / 14.8" 500 mm / 19.7" 375 mm / 14.8" 500 mm / 19.7" 750 mm / 29.5" 750 mm / 29.5" 500 mm / 19.7" 750 mm / 29.5" 375 mm / 14.8" 500 mm / 19.7" 375 mm / 14.8"

FS3 Fuse panel FU1 FU2 FU3 Cable connection panel CC1 CC2 Cable grounding panel (= cable connection panel with grounding switch) Metering panel Metering cable panel Fuse switch panel type FS Metering switch panel CG1 CG2 MT3 MC3 MS2 MS3

R-HA41-089 eps

Bus riser panel

BR1 BR2

Busbar grounding panel

BG1

Cable connection panel type CC

8 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Product Range
Equipment features
se fu n y he tio t la ca D) if re di le DE sm ay vice e in ni sib el UN s d ha de rvic RO po e a ec se e n ly -G tim by or-s ) pe w y m lea on EN N g by ing y-f do ow s o h is re PE -OP er g in en ri d c nt ad -O D in ) pp N) en w in op doo wit tri l re d- shu ripp n ED OSE ED OPE w is s S a io re al e ND Ded oor ct by cal t nic tric to LO (CL N) th ctor r e s C d OU SE sp nfra e d le if ne ha elec r ( ctor OPE tri ith rate in i GR CLO ec to ec w th sib e on D- m e ( Nm ote el th th ec nne if i i E bl n os sm op isc DE nis ni sm r w er w ding t p e d ca OP nism on isco UN em n t t o D- ha ix ism nism r r ve ov ha cha ni h sc -d n f ta n t ta di ch RO ec co c a fo low OSE ec a an e os dis ou ing ing act to hh (G m m ech ech ech O) b L it nt ent -gr ts s s nt m tc tc rm mi e g g i i e w N (C e e ch se lo g le clo i ck sw n s wit ratin ratin y m y m y m (1 hu th fu itch in e sw artm artm d c and cab ra g g g h n h s io at t p p ith e ith er itc pe ope ner ner ng king king ed itc tio osit ing ix ith b ver sw per mo w yp w f si ki w w l y en e e om om l o al g g g t d- edd- al s al s iliar or o l re le c le c rloc rloc rloc stal il to il w r co po ee-p und ua tin tin tin el a t re r re nu n n on ea Hea Hea Pan ux Mo Loc Cab Cab Inte Inte Inte is in C-ra C-ra Floo to Sig hr Gro Ma Ma Sto Sto w ig H A S S T T

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

7 )

7 )

CS1 CS2 FS1 FS2 FS3 FU1 FU2 FU3 CC1 CC2 CG1 CG2 MT3 MC3 MS2 MS3 BR1 BR2 BG1

Basic equipment

Additional (optional) equipment Not available

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 9

Product Range
Cable switch panel
Cable switch panel as feeder panel
HA41-2515 eps
HA41-2514 eps

Cable switch panel as transfer panel


HA41-22516 eps

*
Three-position switch-disconnector

*
either... or
Three-position switch-disconnector

either... or

either... or

Capacitve voltage detection system

Surge arrester

either... or

Cable (not included in the scope of supply) Type CS Type CS Type CS 2nd cable (not included in the scope of supply)
HA41-2608.eps

either... or

Cable-type current transformer

either... or

either... or

either... or

HA41-2517 eps

HA41-2518 eps

Type CS

Type CS

HA41-2519 eps

Type CS

* Switch-disconnector
as: two-position switch-disconnector three-position switch-disconnector

Note: For detailed design, please contact your local Siemens partner.

10 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Product Range
Fuse switch panel
Fuse switch panel as feeder panel
HA41-2520 eps

Fuse switch panel as transfer panel


HA41-2521 eps HA41-2522 eps

*
Three-position switch-disconnector

*
either... or

either... or

either... or

Three-position switch-disconnector

either... or

either... or

either... or

Capacitve voltage detection system

Surge arrester
DS

DS

DS

either... or

Discharge switch

Type FS

Type FS

Type FS

HV CL fuse

2nd HV CL fuse
either... or

2nd and 3rd HV CL fuse

DS

DS

DS

either... or

either... or

either... or

Cable (not included in the scope of supply)

either... or

either... or

either... or

2nd cable (not included in the scope of supply)

HA41-2524 eps

HA41-2523 eps

HA41-2525 eps

2nd and 3rd cable (not included in the scope of supply)


HA41-2608.eps

Type FS

Type FS

Type FS

Cable-type current transformer

* Switch-disconnector
as: two-position switch-disconnector three-position switch-disconnector

Note: For detailed design, please contact your local Siemens partner.

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 11

Product Range
Fuse panel
Fuse panel as feeder panel
HA41-2526 eps HA41-2527 eps

Fuse panel as transfer panel


HA41-2528 eps

Capacitve voltage detection system

Surge arrester
either... or

either... or

either... or

Grounding stud

either...

HV CL fuse

... or

2 HV CL fuse

nd

2 and 3 HV CL fuse Type FU Type FU Type FU

nd

rd

Cable (not included in the scope of supply)


either...

... or

2 cable (not included in the scope of supply)

nd

2nd and 3rd cable (not included in the scope of supply)


either... or either... or either... or
HA41-2608.eps

Cable-type current transformer


HA41-2530 eps HA41-2531 eps

Type FU

HA41-2529 eps

Type FU

Type FU

Note: For detailed design, please contact your local Siemens partner.

12 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Product Range
Cable connection panel
Cable connection panel as feeder panel
HA41-2532 eps

Capacitve voltage detection system

Surge arrester

Grounding stud

Cable (not included in the scope of supply)

either... or

2nd cable (not included in the scope of supply)


HA41-2608.eps

Type CC

Cable-type current transformer

either... or

Type CC

Note: For detailed design, please contact your local Siemens partner.

HA41-2535 eps

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 13

Product Range
Cable grounding panel, busbar grounding panel
Cable grounding panel (= cable connection panel with grounding switch)
HA41-2537 eps

Cable grounding panel/busbar grounding panel (with grounding switch)


HA41-2538 eps

Capacitve voltage detection system

HA41-2536 eps

Surge arrester

Grounding switch

Cable (not included in the scope of supply)

either... or
2 cable (not included in the scope of supply) Type CG Type CG Type CG
HA41-2608.eps
nd

Cable-type current transformer

either... or

HA41-2540 eps

Type CG

HA41-2539 eps

Type CG

Note: For detailed design, please contact your local Siemens partner.

14 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

HA41-2541 eps

Type CG

Product Range
Metering panel
Metering panel
Capacitve voltage detection system
HA41-2542 eps HA41-2543 eps

Grounding stud

either...

either...

... or

... or

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

Type MT3

Type MT3

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

HA41-2544 eps

either...

HA41-2545 eps

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

either...

... or

... or

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)
HA41-2608.eps

Type MT3

Type MT3

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

Note: For detailed design, please contact your local Siemens partner.

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 15

Product Range
Metering panel with cable
Metering panel with cable
Capacitve voltage detection system
HA41-2546 eps

either... or

either... or

HA41-2547 eps

Grounding stud

either... or

either... or

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

Type MC
HA41-2548 eps

Type MC
either... or either... or
HA41-2549 eps

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

Surge arrester

2 cable (not included in the scope of supply)

nd

either... or

either... or

Type MC
HA41-2550 eps

Type MC
HA41-2551 eps

either... or

either... or

either... or

either... or

Type MC

Type MC

Note: For detailed design, please contact your local Siemens partner.

16 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

HA41-2608.eps

either... or

either... or

Cable (not included in the scope of supply)

Product Range
Metering panel with cable (continued), metering switch panel
Metering panel with cable
either... or either... or

*
Three-position switch-disconnector
HA41-2553 eps

HA41-2552 eps

*
Three-position switch-disconnector

either... or

either... or

Capacitve voltage detection system

Grounding stud
either... or either... or

Type MC

Type MC

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)

Metering switch panel

HA41-2554 eps

Block-type current-transformer 4MA and voltage transformer 4MR (both cast-resin insulated)
HA41-2555 eps HA41-2556 eps

Surge arrester

HV CL fuse ***

Option **

Option **

Option **

Voltage transformer 4MR (cast-resin insulated)

either... or VT CPT

either... or VT CPT

either... or VT CPT

Control power transformer (CPT) make ITI

Type MS

Type MS

Type MS Cable (not included in the scope of supply)


HA41-2608.eps

2nd cable (not included in the scope of supply)

* Switch-disconnector as:
two-position switch-disconnector three-position switch-disconnector

** Only in combination with VT or CPT *** Fuses: Potential transformer fuses type CAV
Note: For detailed design, please contact your local Siemens partner.

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 17

Product Range
Bus riser panel, busbar grounding panel
Bus riser panel
HA41-2557 eps HA41-2558 eps

Capacitve voltage detection system

Grounding stud
HA41-2608.eps

Grounding switch

Type BR

Type BR

Busbar grounding panel


HA41-2559 eps HA41-2560 eps HA41-2561 eps

Type BG

Type BG

Type BG

HA41-2562 eps

HA41-2563 eps

HA41-2564 eps

Type BG

Type BG

Type BG

Note: For detailed design, please contact your local Siemens partner.

18 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Design
Panel design (examples)
Cable switch panel type CS
HA41-2565a eps

Fuse switch panel type FS


23 24 25 26 27 12 28 29 30 31 32 20
HA41-2566a eps

2 3 4 5 6 4

7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 2 3 4 5 6 4

7 8 9 10 11 12 13 14 15 16 17 18 19 36 34

23 24 25 26 27 12 28 29 30

32 36 34

21 22 21 33
Type CS1 Section

35 20 21 33

22 21

Type FS2 Legend

Section

1 Indicator Fuse intact/fuse blown

18 Feeder designation label 19 Pressure relief duct 20 Cable termination (not incl. in scope of supply) 21 Cable bracket with clamps 22 Cable connection compartment 23 Busbar 24 Insulating cap on busbar (for > 15 kV) 25 Bushing-type insulator for busbar 26 Metal compartmentalization of busbar compartment 27 Spring-operated mechanism for three-position switch 28 Three-position switch 29 Grounding busbar 30 Bushing-type insulator for feeder 31 Cable connection 32 Cable compartment: As cover or door (latched or screwed-on) 33 Grounding connection 34 Grounding switch to discharge capacitance of connected transformers 35 Post insulator 36 HV CL (current limiting) fuse 37 4MA7 block-type current transformer 38 Fuse holder for VT fuse 39 4MR voltage transformer

Metering panel type MT


HA41-2567a eps

2 Switch position indicator 3 View port for switch blade position

23 24

4 Sockets for capacitive voltage detection system 5 Information label for view port 6 Mimic diagram

35 35 6 4 16 17 18 19 37 38 29 32 37 38

7 Warning label 8 Gas-insulated vessel for switching device 9 Manual operation for the mechanism of the load-breakdisconnecting function 10 Ready-for-service indicator for switching device 11 Manual operation for the mechanism of the grounding function 12 Interlocking lever of cable compartment cover (option) 13 Option: Locking device for three-position switch

39 39 33
Type MT3 Section

14 Pressure relief device for switching device 15 Metal compartmentalization of cable connection compartment 16 Rating and type plate 17 Option: Local-remote switch and momentary-contact rotary control switch CLOSED-OPEN for the motor operating mechanism

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 19

Components
Two/three-position switch-disconnector
Characteristics
Switch positions: CLOSED-OPEN or CLOSED-OPEN-GROUNDED Designed as a multi-chamber
R-HA35-047 eps

Three-position switch-disconnector

Fixed contact

Arcing chamber Moving contact, complete Switch shaft Compression vane (with nozzle)

switch incorporating the following functions Switch-disconnector and Make-proof grounding switch
Operation via gas-tight

welded bushing at the front of the switchgear vessel


Switching functions as

general purpose switchdisconnector according to ANSI/IEEE C37.20.3 * Mode of operation The switch shaft with the moving contacts rotates inside the chamber containing the fixed contacts. Compression vanes, which rotate in conjunction with the switch shaft, divide the arcing chamber into two subchambers each of which changes in conjunction with the rotation. During the switching movement, the compression vanes generate a pressure difference between the subchambers. The SF6 gas flows through a nozzle, causes a directional blow-out of the breaking arc and quenches it rapidly. Interlocking is not necessary as the CLOSED and GROUNDED functions cannot be implemented simultaneously.

Exploded view

Switching functions

Control board with switch position indicators for detachable lever mechanism

R-HA41-091 eps

R-HA41-090 eps

R-HA41-092 eps

HA41-2568 eps

Switch positions: Three-position switch-disconnector CLOSED OPEN GROUNDED

2 3
Switch positions of three-position switch-disconnector

CLOSED

OPEN

GROUNDED Switch positions of two-position switch-disconnector

Legend 1 Moving contact 2 Fixed contact for GROUNDED 3 Fixed contact for CLOSED CLOSED OPEN

* Standards see page 40


20 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Components
Two/three-position switch as two/three-position switch-disconnector
Common features
Metal-enclosed Located in a

Two/three-position switch-disconnector 600 A


Up to 600 A With gas-insulated,
1

gas-insulated switchgear vessel


Switch positions:

maintenance-free quenching principle Operating mechanism


Spring-operated mechanism
2 5 3
R-HA41-093 eps

CLOSED-OPEN or CLOSED-OPENGROUNDED
No cross insulation

with detachable lever


Manual operation with the

between phases
Two/three-position

aid of a detachable lever


Options:

switch with air-insulated primary connections for busbar and feeder


Operation via a

gas-tight welded-in metal bellows in the front of the switchgear vessel View port The visual inspection of the actual position of the two/three-position switch is possible via a view port. (Fig. shown on the right)

Mechanical ready-forservice indication Auxiliary switch Motor operating mechanism for switch-disconnector Locking device
Spring-operated/stored-

4 6
Three-position switch-disconnector 600 A (side removed for photo)
1 Bushing-type insulator for busbar 2 Switchgear vessel for gas insulation 3 Three-position switch-disconnector 4 Bushing-type insulator for feeder 5 Spring-operated mechanism with detachable lever 6 View port

energy mechanism for transformer panel type FS Interlocks


Opening of panel cover or

cable compartment cover only in GROUNDED position Operating cycles


Capable of 100 operating

cycles at rated continuous current 600 A 1000 operating cycles


HA41-2569a eps

Switch positions of three-position switch:

Mechanical endurance of

7
CLOSED

OPEN

GROUNDED Detachable lever mechanism with three-position switch-disconnector 7 Operating lever, inserted

Switching functions of the three-position switch-disconnector 600 A


Switching and disconnecting under load General-purpose switching function Make-proof grounding function

View port
1 2 3
Legend for view port 1 Moving contact 2 Fixed contact for CLOSED 3 Fixed contact for GROUNDED
HA41-2570b eps

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 21

Components
Busbars, HV CL (current-limiting) fuse assembly
Busbars
Metal-enclosed busbar

HV CL fuse assembly
For fuse panel type FS For busbar voltage meter-

Busbars
1 Busbar

compartment
Three-pole design,

ing panel type MS


HV CL fuse links

bolted from panel to panel


Easy switchgear

2 Bushing-type insulator for busbar

extension
Made of copper:

Round-edge copper for up to 1200 A Option: Shrink-on sleeve

acc. to ANSI/IEEE C37.41/C37.46 * As short-circuit protection before transformers With selectivity (depending on correct selection) to upstream and downstream connected equipment
Requirements fulfilled as

2
R-HA41-094 eps

Busbar compartment extending over 2 panels, example (side view)

HV alternating current switch fuse combination


Selection of HV CL

HV HRC fuse assembly


Displays

fuses for transformers


Fuse replacement possi-

Fuse intact

ble only when feeder is grounded


Option: Shunt release on
Fuse blown

operating mechanism of two/three-position switchdisconnector


Option: Tripped indica-

tion of two/three-position switch-disconnector in transformer feeder (transformer switch) for remote electrical indication with one normally-open contact (1NO) HV CL fuse tripped Following the tripping of an HV CL fuse link, the mechanism for charging the spring must be set to the OPEN position Subsequently, grounding can be implemented by means of the two/threeposition switch-disconnector and e.g., the fuse can be replaced. Replacement of HV CL fuse links
Isolating and grounding

R-HA41-095 eps

Control board of a fuse panel

3 HV CL fuse 4 Lower fuse holder 5 Grounding stud 6 Cable termination (not included in the scope of supply)

of the transformer feeder


Subsequent manual

replacement of the HV CL fuse links

HV CL fuses in fuse panel type FS (side view, 2 sets of fuses shown)

* Standards see page 40


22 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

R-HA41-096 eps

Components
Allocation of HV CL fuses and transformers
The table opposite shows the recommended fuse links (electrical data valid for ambient temperatures of up to 40 oC/ 104 F) for the fuse protection of transformers Recommendation The two/three-position switchdisconnector in the transformer feeder (transformer switch) is combined with Bussmann fuse links. Dimensions according to DIN standards (especially manufactured for Siemens) Standards HV CL fuse links according to ANSI/IEEE C37.41/C37.46 *
Bussmann fuses Rated voltage kV 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 15.5 15.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 17.5 25.8 25.8 25.8 25.8 25.8 25.8 25.8 25.8 Length Diameter Rated current I1 A 10 15 20 25 30 40 50 65 80 100 125 150 175 200 250 300 350 400 450 175 200 10 15 20 25 30 40 50 65 80 100 125 150 10 15 20 25 30 40 50 65 Power loss W 8 11 11 15 17 27 36 44 53 69 94 103 121 126 139 147 161 167 183 177 238 22 30 32 41 47 79 95 130 126 169 203 221 27 41 44 50 67 87 103 140 Panel type ** FS1/FU1 FS2/FU2 FS3/FU3 Permissible continuous current A A A 10 15 20 25 30 40 50 65 80 100 120 150 164 183 220 241 269 302 325 167 165 10 15 20 25 30 40 50 59 73 85 112 123 10 15 20 25 30 40 50 65 18 27 36 45 54 72 90 117 144 180 220 270 292 327 390 429 478 536 575 310 305 18 27 36 45 54 72 90 104 131 155 207 238 18 27 36 45 54 72 90 117 24 36 48 60 72 96 120 156 192 240 300 360 416 466 555 598 600 600 600 420 430 24 36 48 60 72 69 120 149 186 225 292 336 24 36 48 60 72 96 120 156 Code/reference No. for SIMOSEC ANSI 55GDMSJ10ES 55GDMSJ15ES 55GDMSJ20ES 55GDMSJ25ES 55GDMSJ30ES 55GDMSJ40ES 55GDMSJ50ES 55GDMSJ65ES 55GDMSJ80ES 55GDMSJ100ES 55GDMSJ125ES 55GDMSJ150ES 55GDMSJ175ES 55GDMSJ200ES 55GDMSJ250ES 55GDMSJ300ES 55GDMSJ350ES 55GDMSJ400ES 55GDMSJ450ES 175GXQSJ175ES 175GXQSJ200ES 175GDMSJ10ES 175GDMSJ15ES 175GDMSJ20ES 175GDMSJ25ES 175GDMSJ30ES 175GFMSJ40ES 175GFMSJ50ES 175GFMSJ65ES 175GXMSJ80ES 175GXMSJ100ES 175GXQSJ125ES 175GXQSJ150ES 258GDQSJ10ES 258GDQSJ15ES 252GDQSJ20ES 252GDQSJ25ES 252GDQSJ30ES 252GDQSJ40ES 252GDQSJ50ES 252GDQSJ65ES

mm / inch 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4

mm / inch 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 76 / 3.0 76 / 3.0 76 / 3.0 76 / 3.0 76 / 3.0 76 / 3.0 76 / 3.0 76 / 3.0

537 / 21.14 88 / 3.5 537 / 21.14 88 / 3.5 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 442 / 17.4 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 51 / 2.0 76 / 3.0 76 / 3.0 76 / 3.0 76 / 3.0 88 / 3.5

537 / 21.14 88 / 3.5 537 / 21.14 88 / 3.5 537 / 21.14 51 / 2.0 537 / 21.14 51 / 2.0 537 / 21.14 51 / 2.0 537 / 21.14 51 / 2.0 537 / 21.14 51 / 2.0 537 / 21.14 88 / 3.5 537 / 21.14 88 / 3.5 537 / 21.14 88 / 3.5

* Standards see page 40 ** FS1/FU1: Single fuse


FS2/FU2: Two fuses in parallel FS3/FU3: Three fuses in parallel

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 23

Components
Operating mechanisms for two/three-position switches
Manual operating mechanism
Standard:

Shunt release (option) Spring-operated/storedenergy mechanisms can be equipped with a shunt release. Remote electrical tripping of the two/threeposition switch-disconnector is possible via the magnetic coil of the shunt release, e.g., transformer overtemperature tripping. To avoid thermal overloading of the shunt release in the event of a continuous signal that may be applied, the shunt release is switched off via an auxiliary switch which is mechanically coupled with the three-position switchdisconnector. Auxiliary switch (option) Each operating mechanism of the two/three-position switch-disconnector can be optionally equipped with an auxiliary switch for the switch position indication: Function switch-disconnector or disconnector: CLOSED and OPEN: 2NO + 2NC Function grounding switch at the two/threeposition switch: CLOSED and OPEN: 2NO + 2NC
1 2 3 4 5

Operating mechanisms
R-HA41-097 eps R-HA41-098 eps

As detachable lever mechanism


Spring-operated mecha-

nism For cable-switch panel type CS For all two/three-position switches (except in panel type FS)
Spring-operated /stored-

energy mechanism For fuse panel type FS as well as for busbar voltage metering switch panel type MS The two/three-position switch is operated via a rocker with metal bellows which is gas-tight and welded at the switchgear vessel. Motor operating mechanism (option) The manual operating mechanisms can be equipped with motor operating mechanisms for the two/three-position switch-disconnector. Operating voltages for motor operating mechanisms: 24, 48, 60, 125 V DC 50/60 Hz 120 and 240 V AC Electrical operation:
Standard: Remote opera-

Detachable lever mechanism as spring-operated/ stored-energy mechanism

Detachable lever mechanism as spring-operated mechanism


R-HA41-099 eps

1 Ready-for-service indicator 2 Auxiliary switch 3 Switch position indicator for the three-position switch-disconnector 4 Locking device (standard for motor operating mechanism) 5 Operating mechanism for the three-position switch-disconnector coupled with the motor operating mechanism 6 Low-voltage niche 7 Terminal strip located in the low-voltage niche 8 M.c.b. (option) in the low-voltage niche 9 Local-remote switch (option) 10 Actuation for the motor operating mechanism of the three-position switch-disconnector

6 7 8

tion (applied to terminal)


Option: Local operation

by momentary-contact rotary control switch


9 10

Operating mechanism parts in panel types FS (transformer feeders)

Technical data of the auxiliary switch


Breaking capacity AC operation at 50 Hz to 60 Hz Operating Normal voltage current V A up to 240 10 DC operation Operating Normal current voltage resistive inductive: T=20 ms V A A 24 10 10 48 10 9 60 9 7 110 5 4 125 5 4 240 2.5 2 Rated switching capacity Rated insulation voltage 250 V AC/DC Insulation group C to VDE 0110 Continuous current 10 A Making capacity 50 A

Abbreviations: NO = normally-open contact NC = normally-closed contact

24 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Components
Indicating and measuring equipment
Ready-for-service indicator (option for three-position switch)
Self-monitoring; easy to

Voltage detection systems For voltage detection according to IEC 61 243-5 / VDE 0682-415 Plug-in voltage detection systems
1

Indicating and measuring equipment (examples)


R-HA41-100 eps

read
Independent of tempera-

ture and pressure variations Standard: HR system Independent of site altitude Features of the Only responds to changes HR system in gas density
Option: Alarm switch Voltage indicator

1NO contact Mode of operation For the ready-for-service indicator, a gas-tight measuring box is installed on the inside of the switchgear vessel. A coupling magnet, which is fitted to the bottom end of the measuring box, transmits its position to an outside armature through the stainless steel switchgear vessel. This armature moves the ready-for-service indicator of the switchgear. While changes in the gas density during the loss of gas, which are decisive for the insulating capacity, are displayed, temperaturedependent changes in the gas pressure are not. The gas in the measuring box has the same temperature as that in the switchgear. The temperature effect is compensated via the same pressure change in both gas volumes.

HR system (standard)
Verification of safe isolation

from supply phase by phase through insertion in each socket pair


Voltage indicator flashes

if high voltage is present


For continuous operation Safe-to-touch Measuring system and

voltage indicator can be tested


Fixed-mounted capacitive
2

voltage divider in bushings


Without auxiliary power

Mounting of voltage detection systems See Product range pages 10 to 18 Verification of correct terminal-phase connections
Possible by means of a
Control board of a ring-main panel (example) Mounting locations in the control board for 1 Ready-for-service indicator (option) 2 Voltage indicator, HR system, plugged-in (standard)

phase comparison test unit (optional)


Safe-to-touch handling of

R-HA40-088 eps

the phase comparison test unit by inserting it into the capacitive taps (socket pairs) of the switchgear

Voltage indicator, HR system (standard)

HA41-2571 eps

3 Measuring box

3 4 5

4 Magnetic coupling 5 Red indication: not ready for service 6 Green indication: ready for service

6
Stainless-steel vessel filled with SF6 gas, gauge pressure 50 kPa (7.25 psi) at 20 C Ready-forservice indicator

Principle of operation of gas monitoring with ready-for-service indicator

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 25

Components
4MC70 33 cable-type current transformers
Application types CS, CC, CG
For fuse panel
R-HA41-102 eps

For cable panel

types FS, FU Features


According to

ANSI / IEEE C57.13


Designed as a single-pole Only for shielded cables Climate-independent Free of dielectrically
H
R-HA41-024 eps

ring-core current transformer

4MC70 33 cable-type current transformer, 4 different overall heights

stressed cast-resin parts (due to design)


Inductive type Secondary connection by

means of a terminal strip inside the panel Installation


Arranged on the cable at

the panel connection


Transformers mounted on

a supporting plate at the factory; final assembly on the cables at site

4MC70 33 cable-type current transformers on the cable at the panel connection **

Technical data
MC70 33 cable-type current transformer Primary data Max. equipment operating voltage Um Rated current IN Rated short-duration power-frequency withstand voltage (winding test) Rated thermal short-time withstand current Ith Rated continuous thermal current ID Rated peak withstand current Idyn Secondary data Rated current Measuring core Class *** Burden Protection core Dimensions Overall height H Outside diameter Inside diameter For cable diameter mm 50* 100* 170* 285* 145 mm / 5.7 inch 55 mm / 2.2 inch 36 ... 50 mm / 1.4 ... 2.0 inch Class *** 5A 0.3 0.6 1.2 0.60 kV 30 A to 600 A 3 kV 25 kA 1.0 x IN option: 1.2 x IN unlimited

0.2 VA to 1.8 VA C10 ... C200

* Depending on the core data ** Assembly normally under the


panel floor

*** Accuracy class varies according


to CT data

Other values available on request

26 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Components
4MA7 block-type current transformers and 4MR voltage transformers
Application
For metering panel

types MT, MS, MC Features


4MA7 current transformer According to

R-HA41-101 eps

ANSI / IEEE C57.13


Dimensions according to

DIN 42 600-8
Designed as a single-pole

R-HA41-030a eps

indoor block-type current transformer


Cast-resin insulated Secondary connection by

4MA7 blocktype current transformer, single-pole

means of screw-type terminals 4MR voltage transformer


According to

ANSI / IEEE C57.13


Dimensions according to Designed as an indoor
R-HA41-029a eps

DIN 42 600-9 (small model) voltage transformer: Type 4MR, single-pole Option: Type 4MR, two-pole
Cast-resin insulated Secondary connection by

means of screw-type terminals


4MR voltage transformer and 4MA7 block-type current transformer installed in metering panel

4MR14 voltage transformer, single-pole

Technical data
4MA7 single-pole block-type current transf. Primary data Max. equipment operating voltage Um Rated short-duration power-frequency withstand voltage Rated lightning impulse withstand voltage Up Rated current IN 15.5 kV 27.6 kV 34 kV 36 kV 95 kV
1) 2)

4MR single-pole voltage transformer

40 kV

1)

Max. equipment 5.6 kV 9.52 kV operating voltage Um Rated shortduration powerfrequency withstand voltage 16 kV 1) 26 kV 1) 20 kV
2)

15.5 kV 25.5 kV
B

34 kV 1) 40 kV 1) 36 kV 2) 60 kV 2) 95 kV 125 kV

60 kV 2) 125 kV

28 kV 2) 75 kV

50 A to 600 A > 600 A: on request up to 25 kA up to 1.0 x IN option: 1.2 x IN

Rated lightning 60 kV impulse withstand voltage Up

Rated thermal short-time withstand current Ith Rated continuous thermal current ID

R. peak withst. current Idyn max. 2.5 x Ith Secondary data Rated current 5A Rated voltage 100/ 3 V 110/ 3 V 120/ 3 V 100/3 V 110/3 V 120/3 V 25 ... 200 VA 0.3 0.5 1.2

B On request: operating voltage Um > 25.5 kV, e.g. 27.6 kV 1) Acc. to ANSI/IEEE C57.13 (standard) 2) Option: on request 3) Accuracy class varies according to CT data

Measuring core Class 3) Burden Protection core Class 3)

0.3

0.6

1.2

0.2 to 1.8 VA C10 ... C200

Rated voltage for auxiliary winding Burden Class

Other values available on request

Other values available on request

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 27

Components
Cable connection
General features
Cable termination points are

arranged one behind the other


Uniform cable connection

Cable connection (examples)


L3 L2 L1
L3 L2 L1

height per panel (see dimension drawings)


With cable bracket or cable

clamps and grounding points for cable shields


Access to the cable connection

3 4

compartment only when feeder has been grounded Features for cable terminals
For thermoplastic-insulated

cables
For paper-insulated mass-

impregnated cables
For connection cross-

sections (cable size) * up to 300 mm2 (600 kcmil)


Cable bottom entry from

below (standard)
Cable top entry from above

R-HA41-103 eps

Cable switch panel type CS Cable connection compartment as delivered

(optional)

R-HA41-104 eps

Fuse panel type FS Cable connection compartment as delivered Legend 1 As delivered condition for cable termination 2 As delivered condition, prepared for cable termination 3 Cold shrink brand 3M

* Larger connection cross-sections


on request.

28 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

R-HA41-106 eps

R-HA41-105 eps

Cable connection compartment with cable termination

Cable connection compartment with cable termination

4 Cable termination brand 3M or Tyco Electronics Raychem 5 Cable termination brand 3M or Tyco Electronics Raychem (with cold shrink brand 3M)

Components
Selection data for various cable terminations
Panel type CS1 + 2 Cable termination height in mm/inch Top cable entry Main switch or vertical copper bar in upper position (fuse assembly in lower position) Main switch or vertical copper bar in lower position (fuse assembly in upper position) Middle cable connection to top to bottom Bottom cable entry Main switch or vertical copper bar in upper position (fuse assembly in upper position) Main switch or vertical copper bar in upper position (fuse assembly in lower position) not not available available 490/ 19.3 2250/ 88.6 not not available available 490/ 19.3 2250/ 88.6 490/ 19.3 2250/ 88.6 not not available available 490/ 19.3 2250/ 88.6 not not available available 490/ 19.3 2250/ 88.6 not not available available 490/ 19.3 2250/ 88.6 940/ 37 1240/ 48.8 2250/ 88.6 2250/ 88.6 not not available available not not available available 940/ 37 1240/ 48.8 2250/ 88.6 2250/ 88.6 940/ 37 1240/ 48.8 2250/ 88.6 2250/ 88.6 940/ 37 1240/ 48.8 2250/ 88.6 2250/ 88.6 not not available available not not available available 490/ 19.3 2550/ 100.4 490/ 19.3 2550/ 100.4 490/ 19.3 490/ 19.3 2550/ 100.4 2550/ 100.4 490/ 19.3 2550/ 100.4 490/ 19.3 2550/ 100.4 530/ 20.8 2250/ 88.6 Panel height in mm/inch FS1 + 2 + 3 Cable termination height in mm/inch Panel height in mm/inch FU1 + 2 + 3 Cable termination height in mm/inch Panel height in mm/inch CC1 + 2 Cable termination height in mm/inch Panel height in mm/inch CG1 + 2 Cable termination height in mm/inch Panel height in mm/inch MC3 Cable termination height in mm/inch Panel height in mm/inch

not not available available

not not available available

not not available available

not not available available

not not available available

not not available available

Principle of cable connection (dimensions in mm/inch) (e.g. for panel type CS)
125/4.9 125/4.9

L=max. 420/16.5

L=max. 420/16.5

130/5.1

100/3.9

L=max. 420/16.5

130/5.1

HA41-2572 eps

HA41-2573 eps

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 29

HA41-2574 eps

Dimensions
Cable switch panel types CS (dimensions in mm/inch)

2250/88.6

2250/88.6

148 5.8 1240/48.8

370.5/14.6

HA41-2575a eps

187.5 7.4 375/14.8

187.5 7.4

187.5 7.4 50/2 150 5.9

205 8.1

210 8.3

210 8.3

500/19.7

Type CS1

Type CS2

1000/39.4 1230/48.4

148 5.8

2250/88.6

HA41-2576a eps

2250/88.6

443/17.4

940/37

187.5 7.4

187.5 7.4

187.5 7.4

205 8.1

210 8.3

210 8.3

Legend 1 Available mounting depth in the LV niche


375/14.8 500/19.7 50/2 150 5.9 1000/39.4 1230/48.4

Type CS1

Type CS2

30 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Dimensions
Fuse switch panel types FS (dimensions in mm/inch)
2

148 5.8

2250/88.6

2250/88.6

2250/88.6

HA41-2577a eps

187.5 7.4 375/14.8

187.5 7.4 500/19.7

187.5 7.4

187.5 7.4 50/2 150 5.9

205 8.1

210 8.3

210 8.3

750/29.5

Type FS1

Type FS2

Type FS3

1000/39.4 1230/48.4

2250/88.6

2250/88.6

2250/88.6

148 5.8

HA41-2578a eps

187.5 7.4 375/14.8

187.5 7.4

187.5 7.4

187.5 7.4

187.5 7.4 50/2 150 5.9

205 8.1

210 8.3

210 8.3

500/19.7

750/29.5

Type FS1

Type FS2

Type FS3

1000/39.4 1230/48.4

148 5.8 2550/100.4 2550/100.4 2550/100.4

2250/88.6

443/17.4

490/19.3

187.5 7.4

187.5 7.4

187.5 7.4

187.5 = 7.4

187.5 7.4

205 8.1

210 8.3

210 8.3

490/19.3

370.5/14.6

490/19.3

443/17.4

2 1

2 1

Legend 1 Available mounting depth in the LV niche


HA41-2579b eps

2 Screwed-on door (fuse compartment) 3 Top case for cable top entry
375/14.8 500/19.7 750/29.5 50/2 150 5.9 1000/39.4 1230/48.4

Type FS1

Type FS2

Type FS3

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 31

Dimensions
Fuse panel types FU (dimensions in mm/inch)

108/4.3

2250/88.6

2250/88.6

2250/88.6

HA41-2580a eps

187.5 7.4 375/14.8

187.5 7.4

187.5 7.4

187.5 7.4

= 187.5 7.4 50/2 150 5.9

205 8.1

210 8.3

210 8.3

500/19.7

750/29.5

Type FU1

Type FU2

Type FU3

1000/39.4 1230/48.4

108/4.3 2550/100.4 2550/100.4 2550/100.4

HA41-2581b eps

375/14.8

500/19.7

750/29.5

2250/88.6

50/2

Type FU1

Type FU2

Type FU3

150 5.9

1000/39.4 1230/48.4

108/4.3

2250/88.6

2250/88.6

2250/88.6

205 8.1

210 8.3

210 8.3

457/18

457/18

490/19.3

187.5 7.4

187.5 7.4

187.5 7.4

187.5 7.4

= 187.5 7.4

205 8.1

210 8.3

210 8.3

490/19.3

457/18

2 1

2 1

Legend 1 Available mounting depth in the LV niche 2 Screwed-on door (fuse compartment) 3 Top case for cable top entry
375/14.8 500/19.7 750/29.5 50/2 150 5.9 1000/39.4 1230/48.4

HA41-2582a eps

Type FU1

Type FU2

Type FU3

32 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Dimensions
Cable connection panel types CC (dimensions in mm/inch)
2 1
108/4.3

2250/88.6

2250/88.6

457/18 205 8.1 50/2 150 5.9 210 8.3 210 8.3 1000/39.4 1150/45.3

HA41-2583b eps

187.5 7.4 375/14.8

187.5 7.4

187.5 7.4

500/19.7

Type CC1

Type CC2

2
108/4.3 940/37 457/18 187.5 7.4 187.5 7.4 187.5 7.4 205 8.1 210 8.3 210 8.3

2250/88.6

2250/88.6

1240/48.8

HA41-2584b eps

Legend 1 Available mounting depth in the LV niche 2 Screwed-on cover


375/14.8 500/19.7 50/2 150 5.9 1000/39.4 1150/45.3

Type CC1

Type CC2

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 33

Dimensions
Cable grounding panel types CG (dimensions in mm/inch)
2

2250/88.6

2250/88.6

148 5.8

370.5/14.6

1
1240/48.8

HA41-2585b eps

187.5 7.4 375/14.8

187.5 7.4

187.5 7.4 50/2 150 5.9

205 8.1

210 8.3

210 8.3

500/19.7

Type CG1

Type CG2

1000/39.4 1150/45.3

2
148 5.8 940/37 443/17.4 187.5 7.4 187.5 7.4 187.5 7.4 205 8.1 210 8.3 210 8.3

2250/88.6

2250/88.6

HA41-2586b eps

Legend 1 Available mounting depth in the LV niche 2 Screwed-on cover


375/14.8 500/19.7 50/2 150 5.9 1000/39.4 1150/45.3

Type CG1

Type CG2

34 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Dimensions
Metering panel type MT3, metering switch panel types MS (dimensions in mm/inch)
2 1
108/4.3 108/4.3

2 1

457/18

2250/88.6

165 6.5

250 9.8

250 9.8

2250/88.6

165 6.5
HA41-2588b eps

250 9.8

250 9.8

HA41-2587b eps

750/29.5

50/2

150 5.9

Type MT3

1000/39.4 1150/45.3

750/29.5

50/2

150 5.9

Type MT3

1000/39.4 1150/45.3

2 1
108/4.3

2250/88.6

165 6.5

250 9.8

250 9.8

HA41-2589b eps

457/18

Legend 1 Available mounting depth in the LV niche 2 Screwed-on cover


750/29.5 50/2 150 5.9 1000/39.4 1150/45.3

Type MT3

370/14.6

2250/88.6

205 8.1

210 8.3

210 8.3

2250/88.6

148 5.8

205 8.1

210 8.3

210 8.3

148 5.8

165 6.5
HA41-2591b eps

250 9.8

250 9.8
HA41-2590b eps

750/29.5

50/2

150 5.9

1000/39.4 1150/45.3

750/29.5

50/2

150 5.9

1000/39.4 1150/45.3

Type MS2 (with voltage transformer 4MR)

Type MS3 (with control power transformer make ITI)

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 35

370/14.6

457/18

Dimensions
Metering cable panel type MC3 (dimensions in mm/inch)

297.5 11.7

165 6.5

250 9.8

250 9.8

2250/88.6

108/4.3

HA41-2592b eps

750/29.5

50/2

150 5.9

Type MC3

1000/39.4 1150/45.3

108/4.3

2250/88.6

HA41-2593b eps

307.5 12.1 750/29.5

297.5 11.7 50/2

165 6.5

250 9.8

250 9.8

150 5.9

Type MC3

1000/39.4 1150/45.3

297.5 11.7

307.5 12.1

165 6.5

250 9.8

250 9.8

2250/88.6

108/4.3

HA41-2594b eps

457/18

530/20.8

580/22.8

457/18

457/18

530/20.8

Legend 1 Available mounting depth in the LV niche 2 Screwed-on cover

750/29.5

50/2

Type MC3

150 5.9

1000/39.4 1150/45.3

36 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Dimensions
Bus riser panel types BR (dimensions in mm/inch)

2250/88.6

2250/88.6

108/4.3

HA41-2595b eps

375/14.8

500/19.7

50/2

150 5.9

Type BR1

Type BR2

1000/39.4 1150/45.3

108/4.3

2250/88.6

HA41-2596b eps

375/14.8

500/19.7

2250/88.6

50/2

150 5.9

Type BR1

Type BR2

1000/39.4 1150/45.3

2250/88.6

2250/88.6

108/4.3

HA41-2597b eps

457/18

457/18

457/18

2 1

Legend 1 Available mounting depth in the LV niche 2 Screwed-on cover


375/14.8 500/19.7 50/2 150 5.9 1000/39.4 1150/45.3

Type BR1

Type BR2

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 37

Dimensions
Busbar grounding panel type BG1 (dimensions in mm/inch)

2 1
148 5.8 443/17.4 50/2 150 5.9 1000/39.4 1150/45.3

HA41-2598b eps

375/14.8

Type BG1

2250/88.6

1
148 5.8 443/17.4 50/2 150 5.9 1000/39.4 1150/45.3

HA41-2599b eps

375/14.8

Type BG1

2250/88.6

2250/88.6

148 5.8

HA41-2600b eps

370.5/14.6

Legend 1 Available mounting depth in the LV niche 2 Screwed-on cover


375/14.8 50/2 150 5.9 1000/39.4 1150/45.3

Type BG1

38 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Dimensions
Floor openings (dimensions in mm/inch in red) and fixing points
1
150/5.9 50/2
375/14.8 14 x 28/ 0.6 x 1.1 375/14.8 14 x 28/ 0.6 x 1.1

58/2.3

58/2.3

For panel width 375 mm/14.8"

60/2.4

60/2.4

385/15.2 80 20 3.1 0.8

385/15.2 80 20 3.1 0.8

187.5/7.4

Panel type CS1 FS1 FU1 CC1 CG1

150/5.9 50/2

187.5/7.4

Panel type BG1 BR1

1 Wall distance 2 Fixing frame (base) of an individual panel or panel block 3 Floor opening for high-voltage cables and, where applicable, control cables 4 Position of the cables for the feeder 5 Fixing points 6 Floor opening if required for panels without cable connection

2 3 4 5
HA41-2601 eps

1000/39.4 850/33.5

857/33.7

110/4.3 385/15.2

58/ 2.3

HA41-2602 eps

110/4.3 385/15.2

58/ 2.3

18/0.7 169.5/6.7 60/2.4 255/10 500/19.7

28 x 14/ 1.1 x 0.6 14 x 28/ 0.6 x 1.1

18/0.7 169.5/6.7 60/2.4 255/10 500/19.7

857/33.7

28 x 14/ 1.1 x 0.6 14 x 28/ 0.6 x 1.1

1
150/5.9 50/2

For panel width 500 mm/19.7"

58/2.3

58/2.3

60/2.4

385/15.2 80 20 3.1 0.8

2 3 4 5
HA41-2603 eps

1000/39.4 850/33.5

857/33.7

110/4.3 385/15.2

HA41-2604 eps

110/4.3 385/15.2

58/ 2.3

58/ 2.3

18/0.7 232/9.1 60/2.4 380/15 750/29.5

28 x 14/ 1.1 x 0.6 14 x 28/ 0.6 x 1.1

18/0.7 232/9.1 60/2.4 380/15

1
150/5.9 50/2

750/29.5

857/33.7

28 x 14/ 1.1 x 0.6 14 x 28/ 0.6 x 1.1

150/5.9 50/2

1000/39.4 850/33.5

CS2 FS2 FU2 CC2 CG2

385/15.2 80 20 3.1 0.8

250/9.8

250/9.8

60/2.4

Panel type

150/5.9 50/2

1000/39.4 850/33.5

Panel type BR2 MS2

58/2.3

58/2.3

60/2.4

385/15.2 80 20 3.1 0.8

385/15.2 80 20 3.1 0.8

187.5/7.4 375/14.8

187.5/7.4 375/14.8

60/2.4 1000/39.4 850/33.5

Panel type FS3 FU3

Panel type MT3 MS3

2 3 4

1000/39.4 850/33.5

857/33.7

For panel width 750 mm/29.5"

5
HA41-2605 eps

110/4.3 385/15.2

58/ 2.3

HA41-2606 eps

110/4.3 385/15.2

58/ 2.3

18/0.7 169.5/6.7 375/14.8 60/2.4 630/24.8 750/29.5

28 x 14/ 1.1 x 0.6 14 x 28/ 0.6 x 1.1

18/0.7 169.5/6.7 375/14.8 60/2.4 630/24.8

1
150/5.9 50/2

58/2.3

385/15.2 80 20 3.1 0.8

187.5/7.4 375/14.8

60/2.4

Panel type MC3

2 3 4 5
HA41-2607 eps

110/4.3 385/15.2

58/ 2.3

18/0.7 169.5/6.7 375/14.8 60/2.4 630/24.8

28 x 14/ 1.1 x 0.6

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 39

1000/39.4 850/33.5

857/33.7

857/33.7

28 x 14/ 1.1 x 0.6

Standards
Standards, specifications, guidelines
Overview of standards SIMOSEC ANSI switchgear complies with the following relevant standards and specifications as applicable:
ANSI/IEEE Std. C37.20.3-2001 ANSI/IEEE Std. C37.20.4-2001 ANSI/IEEE Std. C37.57-2003 ANSI/IEEE Std. C37.58-2003 ANSI/IEEE Std. 1247-2005 ANSI/IEEE Std. C37.22-1997 CSA C22.2 No. 193-M 1983 CSA C22.2 No. 31-04 EEMAC G11-1

Table Insulating capacity


Rated voltage (rms value) kV 8.25 15 27.6

Insulating capacity
The insulating capacity is veri-

Rated short-duration (1 minute) power-frequency withstand voltage (rms value) Across isolating distances Between phases and to ground kV kV 39.6 36 39.6 36 66 60

Rated lightning impulse withstand voltage (peak value) Across isolating distances Between phases and to ground kV kV 105 95 105 95 138 125

fied by testing the switchgear with rated values of shortduration power-frequency withstand voltage and lightning impulse withstand voltage according to IEC 60 694/ VDE 0670-1000 and ANSI/IEEE C37.20.3.
The rated values are referred

Altitude correction factor Ka


For site altitudes above 1000 m/ 3281 ft, the altitude correction factor Ka is recommended, depending on the actual site altitude above sea level.
Ka 1.50

Altitude correction factor

A 1.40 1.30 1.20 1.10 1.00 1000/ 1500/ 3281 4921

m=1

(measurement of Corona)
IEC 62 271-105

HA40-2037a am eps

to sea level and to normal atmospheric conditions 14.7 PSI, 68 F, 0.00068 lb/ft3 humidity in accordance with IEC 60 071/VDE 0111 and ANSI/IEEE.
The insulating capacity

Third-party listing SIMOSEC ANSI is available for most configurations with UL or C-UL listing. Type of service location SIMOSEC ANSI switchgear can be used as an indoor installation in accordance with NEC (NFPA70)
Outside lockable electrical

2000/ 6562

2500/ 8202

3000/ 9842

3500/ 4000/ 11483 13123

decreases with increasing altitude. For site altitudes above 1000 m/3281 ft (above sea level) the standards do not provide any guidelines for the insulation rating. Instead, special regulations apply to these altitudes. Site altitude
As the altitude increases, the

Site altitude in m/ft above sea level

Rated short-duration power-frequency withstand voltage to be selected W Rated short-duration power-frequency withstand voltage Ka

service locations at places which are not accessible to the public. Enclosures of switchgear can only be removed with tools.
Inside lockable electrical

insulating capacity of insulation in air decreases due to the decreasing air density.
For site altitudes above

Rated lightning impulse withstand voltage to be selected W Rated lightning impulse withstand voltage Ka

service locations. A lockable electrical service location is a place outdoors or indoors that is reserved exclusively for housing electrical equipment and which is kept under lock and key. Access is restricted to authorized personnel and persons who have been properly instructed in electrical engineering. Untrained or unskilled persons may only enter under the supervision of authorized personnel or properly instructed persons. Terms
Make-proof grounding

Example: 3000 m/9842 ft site altitude above sea level 15 kV switchgear rated voltage 95.0 kV rated lightning impulse withstand voltage Rated lightning impulse withstand voltage to be selected 95 kV 1.28 = 122 kV

Result: According to the above table, a switchgear for a rated voltage of 27.6 kV is to be selected.

1000 m/3281 ft a higher insulation level must be selected. This results from the multiplication of the rated insulation level for 0 mm/0 ft to 1000 m/3281 ft (above sea level) with altitude correction factor Ka.

switches are grounding switches with short-circuit making capacity according to IEC 62 271-102
Switch-disconnector corre-

sponds to interrupter switch


HV CL are high-voltage

current limiting fuse links

40 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

Standards
Standards, specifications, guidelines
Cable testing
For switch-disconnector For cable testing

Aseismic capacity (optional) SIMOSEC ANSI switchgear can be upgraded for regions at risk from earthquake. For upgrading, earthquake qualification testing has been carried out in accordance with the following standards as applicable: IEC 60 068-3-3, 1993 IEC 60 068-2-6, 1195 IABG TA13-TM-002/98 (guide) NFPA 5000 and IBC Level Seismic Simulation Within the range of the prevailing earthquake frequencies from 1 to 35 Hz, the required response spectrum to IBC 200 % and 300 % covers the following response spectra: Uniform Building Code zone 4 Seismic Requirements Spec. 9067; Department of Water & Power, Los Angeles GTS-1.1013 ENDES, Chile VDE 0670-111 IABG TA13-TM-002/98 category 2

Switchgear color Light grey No. 61 according to ASTM D1535 97 (Munsell notation 8.3 G6.10/0.54)

feeders
DC voltage test

before the test: Remove or disconnect any voltage transformers at the cable connection in SIMOSEC ANSI switchgear. SIMOSEC ANSI switchgear for rated voltages up to 27.6 kV can be subjected to cable tests at a max. DC test voltage of 70 kV. The voltage at the busbar may be 27.6 kV in this case. Test voltages:
Rated voltage of switchgear DC test voltage, maximum value

the installation and operating instructions of the switchgear the information on manufacturer-dependent cable sealing ends the cable version (e.g. paper-insulated massimpregnated cables, PVC cables or XLPE cables) must be observed.

VLF* test voltage cosine-rectangular waveform rms (peak) voltage kV 22 (22) 33 (33)

VLF* test voltage sinusoidal waveform rms (peak) voltage kV 16 (22) 23 (33)

kV 15 27.6

kV 55 72

Climate and ambient conditions SIMOSEC ANSI switchgear may be used, subject to possible additional measures e.g. panel heaters or floor covers under the following ambient conditions and operating temperatures:
Ambient conditions Natural foreign materials Chemically active pollutants Small animals Operating temperatures

Metal enclosure of switching

devices (e.g. three-position switch) in gas-filled stainlesssteel switchgear vessel


Dry-type bearings in

operating mechanism
Essential parts of the operat-

ing mechanism made of corrosion-proof materials


Use of climate-independent

cable-type current transformers


All contacts (switch discon-

The operating temperatures are classified according to ANSI/IEEE C37.20.3 SIMOSEC ANSI switchgear is largely insensitive to climate and ambient conditions by virtue of the following features:
No cross insulation for

nector and make-proof grounding switch) are maintenance-free


Joints of the energized

copper bars are silver plated


Under indoor operating

conditions, SIMOSEC ANSI requires low maintenance Protection against solid foreign bodies, electric shock and ingress of water SIMOSEC ANSI switchgear fulfills acc. to the standards ANSI/IEEE C37.20.3 the following type of protection: All openings in the enclosure prevent the entrance of a rod with a diameter of 3.2 mm/ 0.13 inch.

isolating distances between phases

* VLF = Very Low Frequency.


Refer to IEEE Standard 400.2-2004 IEEE Guide for Field Testing of Shielded Power Cable Systems Using Very Low Frequency (VLF). For cosine-rectangular waveform, the rms value is taken as equal to the peak value. For sinusoidal waveform, the rms value is 0.707 times the peak value, if distortion is less than 5 %.

Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008 41

Responsible for Technical contents: Siemens AG, Dept. PTD M 2 PPM Erlangen, Germany General editing: Siemens AG, Dept. E CC MCC R Erlangen, Germany
42 Metal-Enclosed Interrupter Switchgear Type SIMOSEC, up to 27.6 kV, ANSI, Air-Insulated, Extendable Siemens HA 41.31 2008

All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy hereof is not guaranteed. Since conditions of use are outside our control, the user should determine the suitability of the product for its intended use and assumes all risk and liability whatsoever in connection herewith.