Sie sind auf Seite 1von 20

Emerson Network Power IntelliSlot 485 Card

Liebert DS

485 Network Settings Menu -------------------------1: Enabled Application Modbus Server 2: Control 3: Server ID enabled 8

4: Communications Rate 9600 5: Supported Data List 430

DSRNPJ 10A VENTA ANGEL RUIZ <ESC>: Cancel menu level

Please select a key ?> 5 =========================================== Entry, Register(Num), Data Label, Unit, Scale, Access

1, 30017(1), Free Cooling Internal Control Mode, , x1, RO 2, 30018(1), Humidity Proportional Control Type, , x1, RO 3, 30019(1), Fan Speed Maximum Set Point, %, x1, RO 4, 30020(1), Supply Air Temperature Set Point, deg C, x10, RO 5, 30021(1), Free Cooling Internal Temperature Delta, deg C, x10, RO 6, 30022(1), Minimum Chilled Water Temp Set Point, deg C, x10, RO

7, 30023(1), Air Temperature Set Point, deg C, x10, RO 8, 30024(1), Air Temperature Proportional Band, deg C, x10, RO 9, 30025(1), Air Temperature Dead Band, deg C, x10, RO 10, 30026(1), Air Temperature Control Integration Time, min, x1, RO 11, 30027(1), Humidity Set Point, % RH, x1, RO 12, 30028(1), Humidity Proportional Band, % RH, x1, RO 13, 30029(1), Humidity Proportional Control Integration Time, min, x1, RO 14, 30030(1), Humidity Dead Band, % RH, x10, RO 15, 30031(1), Auto Restart Delay, sec, x1, RO 16, 30033(1), Air Temperature Control Type, , x1, RO 17, 30045(1), BMS Timeout Period, min, x1, RO 18, 30050(1), Return Air Over Temp Threshold, deg C, x10, RO 19, 30051(1), Return Air Under Temp Threshold, deg C, x10, RO 20, 30052(1), Ext Air Sensor A Over Temp Threshold, deg C, x10, RO 21, 30053(1), Ext Air Sensor A Under Temp Threshold, deg C, x10, RO 22, 30054(1), High Return Humidity Threshold, % RH, x10, RO 23, 30055(1), Low Return Humidity Threshold, % RH, x10, RO 24, 30056(1), Ext Air Sensor A High Humidity Threshold, % RH, x10, RO 25, 30057(1), Ext Air Sensor A Low Humidity Threshold, % RH, x10, RO 26, 30070(1), Fan Hours Threshold, hr, x1, RO 27, 30071(1), Compressor Hours Threshold (Compressor [1]), hr, x1, RO 28, 30072(1), Compressor Hours Threshold (Compressor [2]), hr, x1, RO 29, 30073(1), Humidifier Hours Threshold, hr, x1, RO 30, 30074(1), Dehumidifier Hours Threshold, hr, x1, RO 31, 30075(1), Free Cooling Valve Hours Threshold, hr, x1, RO 32, 30076(1), Electric Reheater Hours Threshold (Electric Reheater [1]), hr,

x1, RO 33, 30077(1), Electric Reheater Hours Threshold (Electric Reheater [2]), hr, x1, RO 34, 30078(1), Electric Reheater Hours Threshold (Electric Reheater [3]), hr, x1, RO 35, 30079(1), Hot Water / Hot Gas Valve Hours Threshold, hr, x1, RO 36, 30100(1), System Operating State, , x1, RO 37, 30102(1), System Status, , x1, RO 38, 30103(1), Fan Speed, %, x1, RO 39, 30104(1), Compressor Utilization, %, x1, RO 40, 30105(1), Free Cooling Valve Open Position, %, x1, RO 41, 30106(1), Reheat Utilization, %, x1, RO 42, 30107(1), Humidifier Utilization, %, x1, RO 43, 30108(1), Dehumidifier Utilization, %, x1, RO 44, 30109(1), Free Cooling Status, , x1, RO 45, 30110(1), Return Air Temperature, deg C, x10, RO 46, 30112(1), Supply Air Temperature, deg C, x10, RO 47, 30113(1), Supply Air Temperature Set Point, deg C, x10, RO 48, 30115(1), Free Cooling Fluid Temperature, deg C, x10, RO 49, 30116(1), Ext Air Sensor A Temperature, deg C, x10, RO 50, 30117(1), Ext Air Sensor B Temperature, deg C, x10, RO

Continue? [Q:Quit, A:All, E:Entry #, any other key: 50 more lines]: a

51, 30118(1), Ext Air Sensor C Temperature, deg C, x10, RO 52, 30119(1), Dig Scroll Comp Discharge Temp (Compressor [1]), deg C, x1, RO

53, 30120(1), Dig Scroll Comp Discharge Temp (Compressor [2]), deg C, x1, RO 54, 30130(1), Return Humidity, % RH, x10, RO 55, 30132(1), Ext Air Sensor A Humidity, % RH, x10, RO 56, 30133(1), Ext Air Sensor B Humidity, % RH, x10, RO 57, 30134(1), Ext Air Sensor C Humidity, % RH, x10, RO 58, 30141(1), Fan Hours, hr, x1, RO 59, 30142(1), Compressor Hours (Compressor [1]), hr, x1, RO 60, 30143(1), Compressor Hours (Compressor [2]), hr, x1, RO 61, 30144(1), Humidifier Hours, hr, x1, RO 62, 30145(1), Dehumidifier Hours, hr, x1, RO 63, 30146(1), Free Cooling Valve Hours, hr, x1, RO 64, 30147(1), Electric Reheater Hours (Electric Reheater [1]), hr, x1, RO 65, 30148(1), Electric Reheater Hours (Electric Reheater [2]), hr, x1, RO 66, 30149(1), Electric Reheater Hours (Electric Reheater [3]), hr, x1, RO 67, 30150(1), Hot Water / Hot Gas Valve Hours, hr, x1, RO 68, 30151(1), Today's High Air Temperature, deg C, x10, RO 69, 30153(1), Today's Low Air Temperature, deg C, x10, RO 70, 30155(1), Today's High Humidity, % RH, x1, RO 71, 30157(1), Today's Low Humidity, % RH, x1, RO 72, 30257(1), Server Class, , x1, RO 73, 30258(2), Today's High Air Temperature Time, , x1, RO 74, 30260(2), Today's Low Air Temperature Time, , x1, RO 75, 30262(1), Supply Air Temperature Sensor Control, , x1, RO 76, 30263(1), Return Air Temperature Set Point, deg C, x10, RO 77, 30264(1), Return Humidity Set Point, % RH, x1, RO 78, 30265(2), Today's High Humidity Time, , x1, RO

79, 30267(2), Today's Low Humidity Time, , x1, RO 80, 30269(1), Compressor State (Compressor [1]), , x1, RO 81, 30270(1), Compressor State (Compressor [2]), , x1, RO 82, 30271(1), Compressor Capacity Control State (Compressor [1]), , x1, RO 83, 30272(1), Compressor Capacity Control State (Compressor [2]), , x1, RO 84, 30273(1), Infrared Humidifier Flush Rate, %, x1, RO 85, 30274(1), Fan Control Mode, , x1, RO 86, 30275(1), Analog Input Reading (Analog Inputs [1]), , x100, RO 87, 30276(1), Analog Input Reading (Analog Inputs [2]), , x100, RO 88, 30277(1), Analog Input Reading (Analog Inputs [3]), , x100, RO 89, 30278(1), Analog Input Reading (Analog Inputs [4]), , x100, RO 90, 30279(1), System Status, , x1, RO 91, 30280(1), System Control Mode, , x1, RO 92, 30281(1), System Operating State Reason, , x1, RO 93, 30282(1), Maintenance Ramp, %, x1, RO 94, 30283(1), Calculated Next Maintenance Month, , x1, RO 95, 30284(1), Calculated Next Maintenance Year, , x1, RO 96, 30285(1), Hot Water / Hot Gas Valve Open Position, %, x1, RO 97, 30286(1), Maintenance Tracking State, , x1, RO 98, 30287(1), Customer Input 1 - Event Control, , x1, RO 99, 30288(1), Customer Input 1 - Event Type, , x1, RO 100, 30289(1), Customer Input 2 - Event Control, , x1, RO 101, 30290(1), Customer Input 2 - Event Type, , x1, RO 102, 30291(1), Customer Input 3 - Event Control, , x1, RO 103, 30292(1), Customer Input 3 - Event Type, , x1, RO 104, 30293(1), Customer Input 4 - Event Control, , x1, RO

105, 30294(1), Customer Input 4 - Event Type, , x1, RO 106, 30295(1), Ext Free Cooling Lockout - Event Control, , x1, RO 107, 30296(1), Ext Free Cooling Lockout - Event Type, , x1, RO 108, 30297(1), Ext Condenser Pump High Water - Event Control, , x1, RO 109, 30298(1), Ext Condenser Pump High Water - Event Type, , x1, RO 110, 30299(1), Ext Standby Glycol Pump On - Event Control, , x1, RO 111, 30300(1), Ext Standby Glycol Pump On - Event Type, , x1, RO 112, 30301(1), Ext Standby Unit On - Event Control, , x1, RO 113, 30302(1), Ext Standby Unit On - Event Type, , x1, RO 114, 30303(1), Ext Humidifier Lockout - Event Control, , x1, RO 115, 30304(1), Ext Humidifier Lockout - Event Type, , x1, RO 116, 30305(1), Ext Loss of Flow - Event Control, , x1, RO 117, 30306(1), Ext Loss of Flow - Event Type, , x1, RO 118, 30307(1), Ext Over Temperature - Event Control, , x1, RO 119, 30308(1), Ext Over Temperature - Event Type, , x1, RO 120, 30309(1), Ext Reheat Lockout - Event Control, , x1, RO 121, 30310(1), Ext Reheat Lockout - Event Type, , x1, RO 122, 30311(1), High Power Shutdown - Event Control, , x1, RO 123, 30312(1), High Power Shutdown - Event Type, , x1, RO 124, 30313(1), Humidifier Issue - Event Control, , x1, RO 125, 30314(1), Humidifier Issue - Event Type, , x1, RO 126, 30315(1), Master Unit Communication Lost - Event Control, , x1, RO 127, 30316(1), Master Unit Communication Lost - Event Type, , x1, RO 128, 30317(1), Service Required - Event Control, , x1, RO 129, 30318(1), Service Required - Event Type, , x1, RO 130, 30319(1), Shutdown - Loss Of Power - Event Control, , x1, RO

131, 30320(1), Shutdown - Loss Of Power - Event Type, , x1, RO 132, 30321(1), Smoke Detected - Event Control, , x1, RO 133, 30322(1), Smoke Detected - Event Type, , x1, RO 134, 30323(1), Water Under Floor - Event Control, , x1, RO 135, 30324(1), Water Under Floor - Event Type, , x1, RO 136, 30325(1), Ext Compressor Lockout - Event Control, , x1, RO 137, 30326(1), Ext Compressor Lockout - Event Type, , x1, RO 138, 30327(1), Clogged Air Filter - Event Control, , x1, RO 139, 30328(1), Clogged Air Filter - Event Type, , x1, RO 140, 30329(1), Ext Loss of Air Blower - Event Control, , x1, RO 141, 30330(1), Ext Loss of Air Blower - Event Type, , x1, RO 142, 30331(1), Compressor High Head Pressure - Event Control (Compressor [1]), , x1, RO 143, 30332(1), Compressor High Head Pressure - Event Control (Compressor [2]), , x1, RO 144, 30333(1), Compressor High Head Pressure - Event Type (Compressor [1]), , x1, RO 145, 30334(1), Compressor High Head Pressure - Event Type (Compressor [2]), , x1, RO 146, 30335(1), Compressor Low Suction Pressure - Event Control (Compressor [1] ), , x1, RO 147, 30336(1), Compressor Low Suction Pressure - Event Control (Compressor [2] ), , x1, RO 148, 30337(1), Compressor Low Suction Pressure - Event Type (Compressor [1]), , x1, RO 149, 30338(1), Compressor Low Suction Pressure - Event Type (Compressor [2]),

, x1, RO 150, 30339(1), Compressor Pump Down Issue - Event Control (Compressor [1]), , x1, RO 151, 30340(1), Compressor Pump Down Issue - Event Control (Compressor [2]), , x1, RO 152, 30341(1), Compressor Pump Down Issue - Event Type (Compressor [1]), , x1, RO 153, 30342(1), Compressor Pump Down Issue - Event Type (Compressor [2]), , x1, RO 154, 30343(1), Compressor Short Cycle - Event Control (Compressor [1]), , x1, RO 155, 30344(1), Compressor Short Cycle - Event Control (Compressor [2]), , x1, RO 156, 30345(1), Compressor Short Cycle - Event Type (Compressor [1]), , x1, RO 157, 30346(1), Compressor Short Cycle - Event Type (Compressor [2]), , x1, RO 158, 30347(1), Compressor Thermal Overload - Event Control (Compressor [1]), , x1, RO 159, 30348(1), Compressor Thermal Overload - Event Control (Compressor [2]), , x1, RO 160, 30349(1), Compressor Thermal Overload - Event Type (Compressor [1]), , x1 , RO 161, 30350(1), Compressor Thermal Overload - Event Type (Compressor [2]), , x1 , RO 162, 30351(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [1 ]), , x1, RO 163, 30352(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [2

]), , x1, RO 164, 30353(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [1 ]), , x1, RO 165, 30354(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [2 ]), , x1, RO 166, 30355(1), Ext Air Sensor A High Humidity - Event Control, , x1, RO 167, 30356(1), Ext Air Sensor A High Humidity - Event Type, , x1, RO 168, 30357(1), Ext Air Sensor A Low Humidity - Event Control, , x1, RO 169, 30358(1), Ext Air Sensor A Low Humidity - Event Type, , x1, RO 170, 30359(1), Ext Air Sensor A Over Temp - Event Control, , x1, RO 171, 30360(1), Ext Air Sensor A Over Temp - Event Type, , x1, RO 172, 30361(1), Ext Air Sensor A Under Temp - Event Control, , x1, RO 173, 30362(1), Ext Air Sensor A Under Temp - Event Type, , x1, RO 174, 30363(1), High Return Humidity - Event Control, , x1, RO 175, 30364(1), High Return Humidity - Event Type, , x1, RO 176, 30365(1), Low Return Humidity - Event Control, , x1, RO 177, 30366(1), Low Return Humidity - Event Type, , x1, RO 178, 30367(1), Return Air Over Temp - Event Control, , x1, RO 179, 30368(1), Return Air Over Temp - Event Type, , x1, RO 180, 30369(1), Return Air Under Temp - Event Control, , x1, RO 181, 30370(1), Return Air Under Temp - Event Type, , x1, RO 182, 30371(1), Fan Hours Exceeded - Event Control, , x1, RO 183, 30372(1), Fan Hours Exceeded - Event Type, , x1, RO 184, 30373(1), Fan Issue - Event Control, , x1, RO 185, 30374(1), Fan Issue - Event Type, , x1, RO 186, 30375(1), Main Fan Overload - Event Control, , x1, RO

187, 30376(1), Main Fan Overload - Event Type, , x1, RO 188, 30377(1), Condenser Issue - Event Control (Condenser [1]), , x1, RO 189, 30378(1), Condenser Issue - Event Control (Condenser [2]), , x1, RO 190, 30379(1), Condenser Issue - Event Type (Condenser [1]), , x1, RO 191, 30380(1), Condenser Issue - Event Type (Condenser [2]), , x1, RO 192, 39998(2), System Date and Time, , x1, RO 193, 40017(1), Free Cooling Internal Control Mode, , x1, WR 194, 40018(1), Humidity Proportional Control Type, , x1, WR 195, 40019(1), Fan Speed Maximum Set Point, %, x1, WR 196, 40020(1), Supply Air Temperature Set Point, deg C, x10, WR 197, 40021(1), Free Cooling Internal Temperature Delta, deg C, x10, WR 198, 40022(1), Minimum Chilled Water Temp Set Point, deg C, x10, WR 199, 40023(1), Air Temperature Set Point, deg C, x10, WR 200, 40024(1), Air Temperature Proportional Band, deg C, x10, WR 201, 40025(1), Air Temperature Dead Band, deg C, x10, WR 202, 40026(1), Air Temperature Control Integration Time, min, x1, WR 203, 40027(1), Humidity Set Point, % RH, x1, WR 204, 40028(1), Humidity Proportional Band, % RH, x1, WR 205, 40029(1), Humidity Proportional Control Integration Time, min, x1, WR 206, 40030(1), Humidity Dead Band, % RH, x10, WR 207, 40031(1), Auto Restart Delay, sec, x1, WR 208, 40033(1), Air Temperature Control Type, , x1, WR 209, 40045(1), BMS Timeout Period, min, x1, WR 210, 40050(1), Return Air Over Temp Threshold, deg C, x10, WR 211, 40051(1), Return Air Under Temp Threshold, deg C, x10, WR 212, 40052(1), Ext Air Sensor A Over Temp Threshold, deg C, x10, WR

213, 40053(1), Ext Air Sensor A Under Temp Threshold, deg C, x10, WR 214, 40054(1), High Return Humidity Threshold, % RH, x10, WR 215, 40055(1), Low Return Humidity Threshold, % RH, x10, WR 216, 40056(1), Ext Air Sensor A High Humidity Threshold, % RH, x10, WR 217, 40057(1), Ext Air Sensor A Low Humidity Threshold, % RH, x10, WR 218, 40070(1), Fan Hours Threshold, hr, x1, WR 219, 40071(1), Compressor Hours Threshold (Compressor [1]), hr, x1, WR 220, 40072(1), Compressor Hours Threshold (Compressor [2]), hr, x1, WR 221, 40073(1), Humidifier Hours Threshold, hr, x1, WR 222, 40074(1), Dehumidifier Hours Threshold, hr, x1, WR 223, 40075(1), Free Cooling Valve Hours Threshold, hr, x1, WR 224, 40076(1), Electric Reheater Hours Threshold (Electric Reheater [1]), hr, x1, WR 225, 40077(1), Electric Reheater Hours Threshold (Electric Reheater [2]), hr, x1, WR 226, 40078(1), Electric Reheater Hours Threshold (Electric Reheater [3]), hr, x1, WR 227, 40079(1), Hot Water / Hot Gas Valve Hours Threshold, hr, x1, WR 228, 40262(1), Supply Air Temperature Sensor Control, , x1, WR 229, 40263(1), Return Air Temperature Set Point, deg C, x10, WR 230, 40264(1), Return Humidity Set Point, % RH, x1, WR 231, 40273(1), Infrared Humidifier Flush Rate, %, x1, WR 232, 40274(1), Fan Control Mode, , x1, WR 233, 40287(1), Customer Input 1 - Event Control, , x1, WR 234, 40288(1), Customer Input 1 - Event Type, , x1, WR 235, 40289(1), Customer Input 2 - Event Control, , x1, WR

236, 40290(1), Customer Input 2 - Event Type, , x1, WR 237, 40291(1), Customer Input 3 - Event Control, , x1, WR 238, 40292(1), Customer Input 3 - Event Type, , x1, WR 239, 40293(1), Customer Input 4 - Event Control, , x1, WR 240, 40294(1), Customer Input 4 - Event Type, , x1, WR 241, 40295(1), Ext Free Cooling Lockout - Event Control, , x1, WR 242, 40296(1), Ext Free Cooling Lockout - Event Type, , x1, WR 243, 40297(1), Ext Condenser Pump High Water - Event Control, , x1, WR 244, 40298(1), Ext Condenser Pump High Water - Event Type, , x1, WR 245, 40299(1), Ext Standby Glycol Pump On - Event Control, , x1, WR 246, 40300(1), Ext Standby Glycol Pump On - Event Type, , x1, WR 247, 40301(1), Ext Standby Unit On - Event Control, , x1, WR 248, 40302(1), Ext Standby Unit On - Event Type, , x1, WR 249, 40303(1), Ext Humidifier Lockout - Event Control, , x1, WR 250, 40304(1), Ext Humidifier Lockout - Event Type, , x1, WR 251, 40305(1), Ext Loss of Flow - Event Control, , x1, WR 252, 40306(1), Ext Loss of Flow - Event Type, , x1, WR 253, 40307(1), Ext Over Temperature - Event Control, , x1, WR 254, 40308(1), Ext Over Temperature - Event Type, , x1, WR 255, 40309(1), Ext Reheat Lockout - Event Control, , x1, WR 256, 40310(1), Ext Reheat Lockout - Event Type, , x1, WR 257, 40311(1), High Power Shutdown - Event Control, , x1, WR 258, 40312(1), High Power Shutdown - Event Type, , x1, WR 259, 40313(1), Humidifier Issue - Event Control, , x1, WR 260, 40314(1), Humidifier Issue - Event Type, , x1, WR 261, 40315(1), Master Unit Communication Lost - Event Control, , x1, WR

262, 40317(1), Service Required - Event Control, , x1, WR 263, 40318(1), Service Required - Event Type, , x1, WR 264, 40320(1), Shutdown - Loss Of Power - Event Type, , x1, WR 265, 40321(1), Smoke Detected - Event Control, , x1, WR 266, 40322(1), Smoke Detected - Event Type, , x1, WR 267, 40323(1), Water Under Floor - Event Control, , x1, WR 268, 40324(1), Water Under Floor - Event Type, , x1, WR 269, 40325(1), Ext Compressor Lockout - Event Control, , x1, WR 270, 40326(1), Ext Compressor Lockout - Event Type, , x1, WR 271, 40327(1), Clogged Air Filter - Event Control, , x1, WR 272, 40328(1), Clogged Air Filter - Event Type, , x1, WR 273, 40329(1), Ext Loss of Air Blower - Event Control, , x1, WR 274, 40330(1), Ext Loss of Air Blower - Event Type, , x1, WR 275, 40331(1), Compressor High Head Pressure - Event Control (Compressor [1]), , x1, WR 276, 40332(1), Compressor High Head Pressure - Event Control (Compressor [2]), , x1, WR 277, 40333(1), Compressor High Head Pressure - Event Type (Compressor [1]), , x1, WR 278, 40334(1), Compressor High Head Pressure - Event Type (Compressor [2]), , x1, WR 279, 40335(1), Compressor Low Suction Pressure - Event Control (Compressor [1] ), , x1, WR 280, 40336(1), Compressor Low Suction Pressure - Event Control (Compressor [2] ), , x1, WR 281, 40337(1), Compressor Low Suction Pressure - Event Type (Compressor [1]),

, x1, WR 282, 40338(1), Compressor Low Suction Pressure - Event Type (Compressor [2]), , x1, WR 283, 40339(1), Compressor Pump Down Issue - Event Control (Compressor [1]), , x1, WR 284, 40340(1), Compressor Pump Down Issue - Event Control (Compressor [2]), , x1, WR 285, 40341(1), Compressor Pump Down Issue - Event Type (Compressor [1]), , x1, WR 286, 40342(1), Compressor Pump Down Issue - Event Type (Compressor [2]), , x1, WR 287, 40343(1), Compressor Short Cycle - Event Control (Compressor [1]), , x1, WR 288, 40344(1), Compressor Short Cycle - Event Control (Compressor [2]), , x1, WR 289, 40345(1), Compressor Short Cycle - Event Type (Compressor [1]), , x1, WR 290, 40346(1), Compressor Short Cycle - Event Type (Compressor [2]), , x1, WR 291, 40347(1), Compressor Thermal Overload - Event Control (Compressor [1]), , x1, WR 292, 40348(1), Compressor Thermal Overload - Event Control (Compressor [2]), , x1, WR 293, 40349(1), Compressor Thermal Overload - Event Type (Compressor [1]), , x1 , WR 294, 40350(1), Compressor Thermal Overload - Event Type (Compressor [2]), , x1 , WR 295, 40351(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [1

]), , x1, WR 296, 40352(1), Dig Scroll Comp Discharge Over Temp - Event Ctrl (Compressor [2 ]), , x1, WR 297, 40353(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [1 ]), , x1, WR 298, 40354(1), Dig Scroll Comp Discharge Over Temp - Event Type (Compressor [2 ]), , x1, WR 299, 40355(1), Ext Air Sensor A High Humidity - Event Control, , x1, WR 300, 40357(1), Ext Air Sensor A Low Humidity - Event Control, , x1, WR 301, 40359(1), Ext Air Sensor A Over Temp - Event Control, , x1, WR 302, 40361(1), Ext Air Sensor A Under Temp - Event Control, , x1, WR 303, 40363(1), High Return Humidity - Event Control, , x1, WR 304, 40365(1), Low Return Humidity - Event Control, , x1, WR 305, 40367(1), Return Air Over Temp - Event Control, , x1, WR 306, 40369(1), Return Air Under Temp - Event Control, , x1, WR 307, 40371(1), Fan Hours Exceeded - Event Control, , x1, WR 308, 40373(1), Fan Issue - Event Control, , x1, WR 309, 40374(1), Fan Issue - Event Type, , x1, WR 310, 40375(1), Main Fan Overload - Event Control, , x1, WR 311, 40376(1), Main Fan Overload - Event Type, , x1, WR 312, 40377(1), Condenser Issue - Event Control (Condenser [1]), , x1, WR 313, 40378(1), Condenser Issue - Event Control (Condenser [2]), , x1, WR 314, 40379(1), Condenser Issue - Event Type (Condenser [1]), , x1, WR 315, 40380(1), Condenser Issue - Event Type (Condenser [2]), , x1, WR 316, 40381(1), System Event Acknowledge/Reset, , x1, WR 317, 49998(2), System Date and Time, , x1, WR

318, 10009(1), Ext Reheat Lockout 319, 10010(1), Ext Humidifier Lockout 320, 10013(1), Minimum Chilled Water Temp Set Point Enable 321, 10019(1), Return Air Sensor Event Control 322, 10020(1), Ext Air Sensor A Event Control 323, 10021(1), Ext Compressor Lockout 324, 10025(1), Fan State 325, 10026(1), Cooling State 326, 10027(1), Free Cooling State 327, 10028(1), Hot Water / Hot Gas State 328, 10029(1), Electric Reheat State 329, 10030(1), Humidifier State 330, 10031(1), Dehumidifier State 331, 10034(1), Main Fan Overload 332, 10035(1), Loss of Air Flow 333, 10036(1), Ext Loss of Flow 334, 10037(1), Compressor High Head Pressure (Compressor [1]) 335, 10038(1), Compressor Low Suction Pressure (Compressor [1]) 336, 10039(1), Compressor Thermal Overload (Compressor [1]) 337, 10040(1), Compressor Pump Down Issue (Compressor [1]) 338, 10041(1), Compressor High Head Pressure (Compressor [2]) 339, 10042(1), Compressor Low Suction Pressure (Compressor [2]) 340, 10043(1), Compressor Thermal Overload (Compressor [2]) 341, 10044(1), Compressor Pump Down Issue (Compressor [2]) 342, 10045(1), Dig Scroll Comp Over Temp (Compressor [1]) 343, 10046(1), Dig Scroll Comp Over Temp (Compressor [2])

344, 10047(1), Smoke Detected 345, 10048(1), Water Under Floor 346, 10049(1), Humidifier Issue 347, 10050(1), Ext Standby Glycol Pump On 348, 10051(1), Ext Standby Unit On 349, 10052(1), Ext Condenser Pump High Water 350, 10053(1), Return Air Sensor Issue 351, 10055(1), Ext Loss of Air Blower 352, 10058(1), Humidifier Low Water 353, 10059(1), Humidifier Over Current 354, 10060(1), Ext Over Temperature 355, 10061(1), Shutdown - Loss Of Power 356, 10065(1), Supply Chilled Water Over Temp 357, 10067(1), Return Air Over Temperature 358, 10068(1), Return Air Under Temperature 359, 10069(1), High Return Humidity 360, 10070(1), Low Return Humidity 361, 10071(1), Ext Air Sensor A Over Temperature 362, 10072(1), Ext Air Sensor A Under Temperature 363, 10073(1), Ext Air Sensor A High Humidity 364, 10074(1), Ext Air Sensor A Low Humidity 365, 10075(1), Supply Chilled Water Loss of Flow 366, 10076(1), Clogged Air Filter 367, 10077(1), Supply Air Sensor Issue 368, 10078(1), Free Cooling Temp Sensor Issue 369, 10079(1), Ext Air Sensor A Issue

370, 10080(1), Fan Hours Exceeded 371, 10081(1), Compressor Hours Exceeded (Compressor [1]) 372, 10082(1), Compressor Hours Exceeded (Compressor [2]) 373, 10083(1), Free Cooling Valve Hours Exceeded 374, 10084(1), Electric Reheater Hours Exceeded (Electric Reheater [1]) 375, 10085(1), Electric Reheater Hours Exceeded (Electric Reheater [2]) 376, 10086(1), Electric Reheater Hours Exceeded (Electric Reheater [3]) 377, 10087(1), Hot Water / Hot Gas Valve Hours Exceeded 378, 10088(1), Humidifier Hours Exceeded 379, 10089(1), Dehumidifier Hours Exceeded 380, 10091(1), Unit Communication Lost 381, 10092(1), Master Unit Communication Lost 382, 10094(1), Unit Code Missing 383, 10098(1), Service Required 384, 10099(1), Humidifier Control Board Not Detected 385, 10104(1), Customer Input 1 386, 10105(1), Customer Input 2 387, 10106(1), Customer Input 3 388, 10107(1), Customer Input 4 389, 10108(1), Dig Scroll Comp Discharge Temp Sensor Issue (Compressor [1]) 390, 10109(1), Dig Scroll Comp Discharge Temp Sensor Issue (Compressor [2]) 391, 10209(1), Supply Air Over Temperature 392, 10210(1), Supply Air Under Temperature 393, 10211(1), Ambient Air Sensor Issue 394, 10212(1), Compressor Short Cycle (Compressor [1]) 395, 10213(1), Compressor Short Cycle (Compressor [2])

396, 10214(1), Ext Free Cooling Lockout 397, 10215(1), Reheater Over Temperature 398, 10216(1), Humidifier Cylinder Worn 399, 10217(1), Humidifier Under Current 400, 10218(1), Fan Issue 401, 10219(1), Condenser TVSS Issue 402, 10220(1), Condenser VFD Issue 403, 10221(1), Condenser Issue (Condenser [1]) 404, 10222(1), Condenser Issue (Condenser [2]) 405, 10223(1), BMS Communications Timeout 406, 10224(1), Digital Output Board Not Detected (iCOM DO Board [1]) 407, 10225(1), Digital Output Board Not Detected (iCOM DO Board [2]) 408, 10226(1), Digital Output Board Not Detected (iCOM DO Board [3]) 409, 10227(1), RAM Battery Issue 410, 10228(1), Water Leakage Detector Sensor Issue 411, 10229(1), External Fire Detected 412, 10230(1), Chilled Water Control Valve Position (Chilled Water Valve [1]) 413, 10231(1), Chilled Water Control Valve Position (Chilled Water Valve [2]) 414, 10232(1), Unit Off 415, 10233(1), Unit On 416, 10234(1), Unit Partial Shutdown 417, 10235(1), Unit Shutdown 418, 10236(1), High Power Shutdown 419, 10237(1), Unit Standby 420, 10238(1), Maintenance Due 421, 10239(1), Maintenance Completed

422, 10240(1), Compressor Low Pressure Transducer Issue (Compressor [1]) 423, 10241(1), Compressor Low Pressure Transducer Issue (Compressor [2]) 424, 10242(1), Compressor High Pressure Transducer Issue (Compressor [1]) 425, 10243(1), Compressor High Pressure Transducer Issue (Compressor [2]) 426, 10244(1), Compressor Capacity Reduced 427, 13(1), Minimum Chilled Water Temp Set Point Enable 428, 19(1), Return Air Sensor Event Control 429, 20(1), Ext Air Sensor A Event Control 430, 25(1), System On/Off Control ===========================================

Das könnte Ihnen auch gefallen