TeSys contactors
Variable composition contactors CV1 B (80 to 1000 A) and CV3 B (80 to 500 A)
Selection
To dene a contactor The criteria required to dene the composition of a contactor are: b the number of N/O and N/C power poles, b the current and power supply voltage, L (note: on a d.c. supply, the time constant ---- of the load must be known in order to R dene the number of poles to be wired in series to break the arc), b the control circuit voltage, b the number of auxiliary contacts. To order a contactor Contactor selectable by code combinations b Use the symbol combination table on page 26218/3. b Check the maximum number of poles in the selection table on page 26218/4. b Check the operational currents possible below (selection restrictions). Contactor not selectable by code combinations b For a composition that cannot be selected using these tables, use order form CF 452, page 26218/5.
Selection restrictions
CV1 BF CV3 BF E M N P Q F Z
CV1 BG CV3 BG Q R G Z
CV1 BH CV3 BH R G H Z
CV1 BJ CV3 BJ S T J Z
CV1 BK CV3 BK U V K Z
CV1 BL K L Z
40 A 50 A 80 A 125 A
10
26218-EN_Ver7.1
TeSys contactors
Variable composition contactors CV1 B (80 to 1000 A) and CV3 B (80 to 500 A)
Reference to be constituted
(see examples on page 26218/4) Type of contactor related to application a 690 V, c 220 V/pole a 1000 V, c 440 V/pole Contactor size AC-1/AC-3 CV1 : 80/80 A CV3 : 80/80 A CV1 : 200/170 A CV3 : 200/200 A CV1 : 300/250 A CV3 : 300/285 A CV1 : 470/350 A CV3 : 320/320 A CV1 : 630/460 A CV3 : 500/460 A CV1 : 1000/700 A Number of poles N/O poles 1 N/O 2 N/O 3 N/O 4 N/O 5 N/O N/C poles 1 N/C 2 N/C 3 N/C No main poles Operational current (determines the blow-out coil size) 11 A 13 A 20 A 40 A 50 A 80 A 125 A 200 A 250 A 300 A 320 A 400 A 470 A 500 A 630 A 1000 A Without breaking Control circuit voltage 24 V 48 V 110 V 120 V 127 V 208 V 220 V 230 V 240 V 380 V 400 V 415 V 440 V 480 V 500 V 600 V Operating frequency 50 Hz 60 Hz 50/60 Hz (rectier + economy resistor) c c + economy resistor Auxiliary contacts (type ZC4 GM) N/O instantaneous CV1 B CV3 B F G H J K L 1 2 3 4 5 1 2 3 0
3
Z E M N P Q F R G S H T U J V K L Z B E F K G L M P U Q V N R T S X 5 6 7 D R 1 2 3 4 1 2 3 4 0 J N
Z E M N P Q F R G S H T U J V K L Z
1 N/O 2 N/O 3 N/O 4 N/O N/C instantaneous 1 N/C 2 N/C 3 N/C 4 N/C No instantaneous auxiliary contacts On-delay 1 C/O Off-delay 1 C/O To check whether the symbol combinations are possible, refer to the selection information and guide on pages 26218/2 and 28218/4. If in doubt, ll out order form CF 452.
10
26218-EN_Ver7.1
Selection
TeSys contactors
Variable composition contactors CV1 B (80 to 1000 A) and CV3 B (80 to 500 A)
2
2 1 2 1 2 1 2 1 2 1
CV1 or CV3 contactors: Maximum number of auxiliary contacts: 4 + 1 time delay if necessary Selection restrictions, according to coil type:
(1) 4-pole with economy resistor. (2) 2-pole with economy resistor.
Examples
b Switching of single-phase capacitor: 400 V - 80 A - 1 N/O main pole. 220 V / 50 Hz control circuit voltage, 1 N/O and 1 N/C auxiliary contacts. Reference: CV1 BF1F0ZM511. b Switching of d.c. heating circuits: 800 V - 150 A - 2 N/O main poles - 48 V c control circuit, instantaneous auxiliary contact 1 N/O + 1 on-delay. Reference: CV3 BG2W0ZED10J.
Other versions
To obtain a composition with more main poles or with more than 4 auxiliary contacts, please use order form CF 452 (see page 26218/5).
10
26218-EN_Ver7.1
TeSys contactors
Variable composition contactors CV1 and CV3
Date of order
Editor
Geog. area
Order n
Job n
/
Company: ................................ Activity sector: ................................ Number of contactors: ....... Type - size or symbol combination: ..........
For devices with symbol combination: Do not ll out the form below
POWER CIRCUIT
Voltage: .......... V
AC DC
...... Hz
Poles
Number of N/O main poles: Rated current: ................... Amp Number of N/C main poles: Rated current: ................... Amp Any special details: ..................................................................................................................... .................................................................................................................................................
Ref: Ref:
CONTROL CIRCUIT
Voltage: .......... V Economy resistor:
Customer marking: ..........
AC DC Yes
...... Hz
No
Electromag: Coil: Coil maint. cont: Rectier: Econ. resist. contact: Econ. Resist.:
No. ZC4GM1 : No. ZC4GM2 :
(N/O) (N/C) (N/C) (N/C+N/O) (N/O+N/O) (ON-Del) (OFF-Del)
GM1:
GM2:
GP4:
GP5:
GP6:
LA1:
No. ZC1GP6 : No. ZC2GG1 : No. ZC2GG5 : No. LA1BNp31 : No. LA1DNpp : No. LApDTp :
If CV1, specif. n:
Note : For mechanical interlocking, a N/C contact must be specied for the interlocking function.
On delay
or
Off delay
MOUNTING
Fixing centres L: Standard Specied Mechanical interlock MI: Yes No With L = ............
Dimensions in catalogue
Vertically mounted reversers xing centres E =.......... mm Upper position contactor: ........................... Lower position contactor: If mechanical interlock specied : Ref: .....................................
Supply linking components for the 2 contactors (Rod, clevis, cranks, lock, etc...) : Yes No
Note : MI components that are part of the contactor such as the bearing, clevis or lock support are factory tted.
* 3 possibilities
1 Device with symbol combination (see drwg 1492177) ) 2) Device n dened on the basis of this form Type/size/order n/year. E.g.: CV1GB000599 3) Reference dened to specication
10
(1) Standard delivery time: 3 weeks, from receipt of order. For faster delivery, please consult your Regional Sales Ofce.
26218-EN_Ver7.1