"si" and "SiE" type, A and AC class RCCB-ID 10 mA, 30 mA, 100 mA,
Function
300 mA and 500 mA instantaneous Eu rope 100 mAs, 300 mAs, 500 mAs
Residual current circuit breakers ensure: b the control and isolation of electrical circuits b the protection of persons against direct and indirect contacts b the protection of installations against insulation faults. They are conform to both the residual current device standard IEC 61008 and to switch standards IEC 60947-1 and IEC 60947-3. Residual current circuit breakers are used in the housing, tertiary and industrial sectors.
AC class A class
Trippin is ensured for sinusoidal, alternating currents, whether they be quickly applied or slowly increase. Tripping is ensured for sinusoidal, alternating residual currents as well as for pulsed DC residual currents, whether they be quickly applied or slowly increase. Application: loads with electronics, rectifiers, instruments. Reinforced continuity of supply on disturbed networks with: b a high risk of nuisance tripping: v successive lightning strokes v IT earthing system v variable speed controllers, frequency converters v presence of electronic ballasts v presence of switchgear that incorporates interference filters i.e. lighting, microcomputing, etc. b sources of blinding: v presence of harmonics or high frequency rejection v presence of DC components: diodes, thyristors, triacs v law temperature.
si type
SiE type
The RCCB/ID SiE types are particularly suitable for use in humid environments and/or environments polluted by aggressive agents, for example swimming pools, marinas, the food-processing industry, water treatment plants, industrial sites. They also incorporate RCCB/ID si functions.
Instantaneous Selective s
It ensures instantaneous tripping (no time-delay). Total discrimination can be achieved using a non-selective residual current device placed downstream.
Description
The residual current trip unit is electromechanical. It functions without an auxiliary source.
Technical data
b Voltage rating: v 30400 V AC, -15+10 %. b Frequency rating: v AC and A classes: 50/60 Hz v si and SiE types: 50 Hz. b Current rating (Ith) at 40 C: 16100 A. b As in IEC 61008: v breaking and making capacity: - rated residual (IDm): .5 kA - rated (Im): 1.5 kA. b As in IEC 60947-3: v isolation with positive break indication, opening is indicated by a green strip on the device operating handle. This indicator shows that all poles are open. v rated impulse withstand v voltage (Uimp): 6 kV v insulation voltage (Ui): 440 V v utilization category: - AC 3A rating y 63 A - AC B ratings 80 and 100 A v padlocking in the tripped position is possible using the padlocking device (not supplied) (see page 91903/). version: 5.3 90134E.indd
"si" and "SiE" type, A and AC class RCCB-ID 10 mA, 30 mA, 100 mA,
300 mA and 500 mA instantaneous Eu rope 100 mAs, 300 mAs, 500 mAs
b Protected against nuisance tripping due to transient overvoltages (lightning, switchgear operation on the network, etc.). b Impulse withstand level 8/0 s: v AC and A classes: - 50 for instantaneous - 3 k for s v si and SiE type: - 3 k for instantaneous - 5 k for s. b Short-circuit current withstand (IDc = Inc): 10 kA with 100 A fuse upstream b Number of operations (O-C): 0 000. b Trip units with fixed sensitivities for all ratings: v instantaneous trip unit v selective trip unit: total vertical selectivity can be achieved using 30 mA residual v current devices placed downstream. b Indication: v mechanical: earth fault indication on front panel by means of a mechanical indicator v electrical: using auxiliaries (see page 9014/). b Remote tripping: using auxiliaries (see page 9014/). b Environment: v tropicalisation: treatment (relative humidity 95 % at 55 C) v operating temperature: - AC class: -5+40 C - A class, si and SiE type: -5+40 C v storage temperature: -40+60 C v weight (g): Type 2P
30
4P
450
b Connection using tunnel terminals for flexible 35 mm cable or rigid 50 mm cable. b Can be directly connected using comb busbars on P residual current circuit breakers when using the Pclic adapter (see page 90150/). b Conform with standards: v IEC 61008 v IEC 60947-1 v IEC 60947-3.
Catalogue numbers
AC class RCCB-ID residual current circuit breakers
Type Voltage (V AC) Rating (A) Sensitivity (mA) Catalogue number width in mod. of 9 mm 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
2P
N T R N 2 1
30
5
40
63
80
100
10 30 300 500 30 30 g 100 100 g 300 500 30 300 300 s 500 500 s 30 300 300 s 500 500 s 300 300 s
23008 23009 23011 23012 23014 23072 23015 23073 23016 23017 23018 23021 23028 23022 23029 23020 23030 23032 23026 23033 23034 23035
90134E.indd
version: 5.3
"si" and "SiE" type, A and AC class RCCB-ID 10 mA, 30 mA, 100 mA,
Catalogue numbers
AC class RCCB-ID residual current circuit breakers (cont.)
Type Voltage (V AC) Rating (A) Sensitivity (mA) Catalogue number width in mod. of 9 mm 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
300 mA and 500 mA instantaneous E urop 100 mAs, 300 mAs, 500 mAs e
4P
30/400 5
N T R N
5
40
63
80
100
30 300 500 30 30 g 100 100 g 300 300 s 500 500 s 30 30 g 100 100 g 300 300 s 500 500 s 30 300 300 s 500 500 s 300 300 s
23038 23040 23041 23042 23074 23536 23075 23045 23062 23046 23063 23047 23532 15177 23533 23049 23066 23051 23067 23061 23054 23069 23055 23070 23056 23059
40
63
4P
N T R N 2 4 6 1 3 5
80 100 30/400 5
4 4 4 4 4 4 4 4 4 4 4 4 4 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
40
63
80
100
version: 5.3
90134E.indd
"si" and "SiE" type, A and AC class RCCB-ID 10 mA, 30 mA, 100 mA,
Catalogue numbers
si type RCCB-ID residual current circuit breakers
Type Voltage (V AC) Rating (A) Sensitivity (mA) Catalogue number width in mod. of 9 mm 4 4 4 4 4
300 mA and 500 mA instantaneous E urop 100 mAs, 300 mAs, 500 mAs e
2P
30
N T R N
5 40 63 80
30 30 30 300 s 300 s
4P
N T R N 2 4 6 1 3 5
30/400
5 40 63 80
30 30 30 300 s 30 300 s
8 8 8 8 8 8
4P
N T R N 2 4 6 1 3 5
30/400
5 40 63
30 30 300 s 30 300 s
8 8 8 8 8
Additional information
Dimensions: page 90148/ Auxiliaries: page 9014/-90150/ Accessories: page 91900/-91903/
90134E.indd
version: 5.3