Contents:
General description 3 pole: XLP 000 XLP 00 XLP 1 XLP 2 / 3 4 pole: SLP 00 3
4 5 6 7 8 9 10 11
System description
Description of accessories
12 13 14
Technical data
15 16 17
Ordering tables
18 19 20
Dimensional drawings
21 22 23 24 25 26
3
3 - pole: XLP 000 XLP 00 XLP 1 XLP 2 XLP 3 100 Amp 160 Amp 250 Amp 400 Amp 630 Amp
4 - pole: SLP 00 SLP 1 SLP 2 SLP 3 160 Amp 250 Amp 400 Amp 630 Amp
EasyLine 3 pole
XLP 000
XLP 000
100 A
Compact design for NH 000 compact fuses up to 100 A Modern integrated cable clamps for 1,5 -35 mm2 cables Integrated cable shrouds IP 20 Snap on for DIN rail mounting (accessory) Front frames for 1 -3 apparatus (accessory) Micro auxiliary switches, 1 or 2 pcs (accessory) Padlocking facility (accessory) Sealing facility
Sealing facility
EasyLine 3 pole
XLP 00
XLP 00
160A
Kit for double DIN rail mounting Different types of plug - in busbar adapter. 40 to 60 mm busbar distance. Padlocking facility Sealing facility
Electronic fuse monitoring Micro auxilliary switches, 1 or 2 pcs Auxilliary swithes, 1 NO or 1 NC acc. to IEC 60947-5-1 Cable shrouds Wide range of cable terminal clamps (See page 12) Front frames for 1-3 apparatus
Micro auxiliary switch on the sides. Auxiliary switch NO or NC in the front Cable shrouds
EasyLine 3 pole
XLP 1
XLP1
250 A
Electronic fuse monitoring Micro auxiliary switches, 1 or 2 pcs Auxiliary switch, 1 NO or 1NC, acc. to IEC 60947-5-1 Cable shrouds Wide range of cable clamps (See page 12) Front frames for 1 - 2 apparatus Busbar adapter for 60 mm busbar distance Padlocking facility Sealing facility
EasyLine 3 pole
XLP 2 / 3 400 / 630 A
Electronic fuse monitoring Micro auxiliary switches, 1 or 2 pcs Auxiliary switches , 1 NO or 1NC acc. to IEC 60947-5-1 Cable shrouds Wide range of cable clamps (See page 13) Front frame for 1 apparatus Padlocking facility Sealing facility
XLP 2 / 3
XLP 2
XLP 3
EasyLine 4 pole
SLP 4 pole 160 - 630 A
SLP 00-3
The EasyLine range can offer a 4-pole solution by using SLP 4 pole. The Neutral pole can be equiped with a fuse carrier or a neutral link. The SLP 4-pole range : SLP 00 SLP-K 1,2,3 4-pole 4-pole Delivered with 8 bridge clamps Delivered without clamps. Clamps have to be ordered separately
SLP 00 4 pole
SLP K1 4 pole
A 60 - Down A 60 - Up
10
The SF-60 Busbar system features: Busbar width: 12 - 30 mm Busbar thickness: 5 - 10 mm Centre distance between busbars: 60 mm
XLP 00 A60/60
3M10 Up
Apparatus size Axx/yy = A : Adapter xx : Busbardist. yy : Depth mm. 6CC 3BC 3TC 3FC 3M8 3M10 = 6 pcs Cage Clamps = 3 pcs Bridge Clamps = 3 pcs Trippel Clamp = 3 pcs Feeding Clamp = 3 pcs Bolts M8 = 3 pcs bolts M10
10
A 40/95
Cu 12x5 or 12x10 mm. Adapter 75 mm depth to busbars, cable connection below : Adapter 120 mm depth to busbars, cable connection below :
A 40/75 A 40/120
11
Explanations : XLP = Basic Fuse switch disconnector XLP 00 A40/120 3BC
Apparatus size Axx/yy = A : Adapter xx : Busbardist. yy : Depth mm. 6CC 3BC 3TC 3FC 3M8 3M10 = 6 pcs Cage Clamps = 3 pcs Bridge Clamps = 3 pcs Trippel Clamp = 3 pcs Feeding Clamp = 3 pcs Bolts M8 = 3 pcs bolts M10
11
XLP 000 Cage Clamps (CC) XLP 00 Bridge Clamp (BC) Triple Camp (TC) 1,5-35 1,0-10 1,5-16 Single Prism Clamp (SPC) Feeding Clamp (FC) for XLP 00 - 6BC Bolt M8x16 DIN 933 Bolt M8x16 DIN 933 for Cable lug DIN 46234 Bolt M8x16 DIN 933 for Cable lug DIN 46235 XLP 1 Bridge Clamp (BC) Single Prism Clamp (SPC) 95-150 Double Prism Clamp (DPC) Bolt M10x20 DIN933 Bolt M10x20 DIN933 for Cable lug DIN46234 Bolt M10x20 DIN933 for Cable lug DIN46235 10x40 2x70 2x95 95-185 1) 2x70 2x120 95-150 2x70 2x120 10x19 16-70 16-70 16-95 16-95 16-95 16-95 10 1SEP407732R0002 10 1SEP407733R0002 4 x 20 25 - 50 1,5 50 1,0 10 1,5 16 25 70 1,5 50 1,0 10 1,5 16 3,5 25 70 1SEP407732R0001 3,5 3,5 1SEP407733R0001 1SEP407787R0001 1,5-25 1,5 35 1,5 35 3,2 Included in the switch
25-70
25 95
25 95
10
1SEP407811R0001
12
10 - 95
10 95
10 95
10
NHP 400940R0006
16 - 70
16 - 70
16 - 70
10
NHP403631R0001
10-240
10-240
10-240
16
NHP403625R0001
16-240
16-240
16-240
12
XLP 2/3 26x14 Bridge Clamp (BC) 70-240 16-240 Single Prism Clamp (SPC) 25-95 25-70 16-95 2x35 Double Prism Clamp (DPC) 2x35 2x120 2x35 2x150 2x50/ 2x50 2x185 Bolt M12x30 DIN933 Bolt M12x30 DIN933 for Cable lug DIN46234 Bolt M12x30 DIN933 for Cable lug DIN46235 10-240 10-240 10-240 25 16-300 16-300 16-300 NHP403626R0001 50x12 22 1SEP407956R0001 50-185 16-240 50-185 14 16-240 1SEP407954R0001 16-300 16-300 16-300 1SEP407953R0001
13
Type tested according to standard: EN IEC 60947-1 and DIN VDE 0295. Explanations: Flexible: Multi stranded Re: Round solid Se: Sector shaped solid Rm: Round stranded Sm: Sector shaped stranded
1) The Sm (sector shaped stranded) 150 mm2 and 185 mm2 have to be round formed before inserted in the Prism Clamp. *) For correct Torque (Nm) values, please study the installation description delivered with the devices.
13
1. Switch closed : Fuses OK Phases OK Fuses OK 1 Phase loss Fuses OK 2-3 Phases loss Fuses BLOWN Phases OK Fuses BLOWN 1 Phase loss Fuses BLOWN 2-3 Phases loss 2. Switch open : Fuses OK Phases OK Fuses OK Phase loss Fuses BLOWN Phases OK Fuses BLOWN Phase loss
x x (L1)
x (L2,L3) x x x x
x x x x x (L1)
x x x x (L1) x x (L1)
x (L2,L3) x (L2,L3) x x
x x x x x (L2,L3) x
x x x x
x x x x
x x x x
x x x x
14
x (L1): x (L2,L3):
The case if Phase L1 is lost The case if Phase L2 or L3 both are lost
The fuse monitor is connected to the gripping lugs of the fuses. NOTE : Insulated gripping lugs can not be used. The fuse monitor requires that the supply side of the XLP should be on top of the switch. Technical data : Minimum operation voltage: Maximum operation voltage: Uimp over a blown fuse: Uimp between phases: Uimp between main circuit/ relay contacts.: Dielectric test voltage input / output: Electrostatic Discharge: Electrical Fast Transient: Conducted Fast Transient: Connector: Wire size: EMC tested: Relay: Nominal current: Nominal switching capacity: Maximum switching voltage:
400V - 15% 690V - 12% 12,3 kV 9.8 kV 9.8 kV 3.5 kV / 50 Hz / 1 minute EN61000-4-2 +/- 4 kV EN61000-4-4 +/- 2 kV EN61000-4-6 10Vrms / 150kHz 80 MHz MSTB 2,5/4 - ST - 5,08 AWG 22-12 / 0.2-2.5mm2 Yes
14
3 - pole
XLP 000 Fuse size acc. to DIN 43620 / IEC / EN 60269-2-1 Rated operational voltage Ue Rated operational current Ie Thermal current w/fuse link lth Rated insulation voltage Ui Rated impulse withstand voltage Uimp Fuse protected short circuit making Rated making and breaking capacity : Rated frequency Power loss at Ith without fuse-link/phase Electrical durability Mechanical durability Degree of protection from the front acc. to IEC / EN 60529 Open Closed (Hz) (W) AC23B AC22B AC21B AC23B AC22B AC21B AC23B AC22B AC21B AC23B AC22B AC21B AC23B AC22B AC21B 50 / 60 1.4W 300 1700 IP 20 IP 30 50 / 60 3.5W 200 1400 IP 20 IP30 50 / 60 7.5W 200 1400 IP 20 IP 30 50/60 13W 200 800 IP20 IP30 50/60 24W 200 800 IP20 IP30 (V) (A) (A) (V) (V) (kArms) 000 Max Width=21mm 400 500 690 400 500 690 80 100 50 100 690 6000 50 125 160 125 160 1000 8000 50 400 500 690 400 500 690 400 500 690 250 200 250 1000 8000 50 400 315 400 1000 8000 50 630 500 630 1000 8000 50 XLP 00 00 XLP 1 1 XLP 2 2 XLP 3 3
4 - pole
Fuse size acc. to DIN 43620 / IEC / EN 60269-2-1 Rated operational voltage Ue Rated operational current Ie Rated insulation voltage Ui Rated impulse withstand voltage Uimp Fuse protected short circuit making Rated making and breaking capacity: Rated frequency Degree of protection from the front acc. to IEC / EN 60529 SLP 00 00 (V) (A) (V) (V) (kArms) 400VAC (Hz) Open Closed 400 160 1000 8000 50 AC22B 50 / 60 IP 10 IP 30 SLP-K1 1 400 250 1000 8000 50 AC22B 50 / 60 IP 20 IP 30 SLP-K2 2 400 400 1000 8000 50 AC22B 50 / 60 IP 20 IP 30 SLP-K3 3 400 630 1000 8000 50 AC22B 50 / 60 IP 20 IP 30
15
The products are designed and tested in accordance with IEC / EN 60947-3. Additionally, all development and production activities are in compliance with the Quality System Standard EN ISO 9001 and Environmental Standards EN ISO 14001.
15
3-pole
XLP 000 3-POLE 100A Apparatus: 1 1SEP201428R0001
6 Cage Clamps (6 CC)
Switch Including:
Accessories:
2 3 4 5 Front frame for 1 apparatus Front frame for 2 apparatus Front frame for 3 apparatus Micro auxiliary switch Auxiliary switch NC Auxiliary switch NO Padlock device Cable shroud DIN Rail mounting device Cover IP 30 Auxiliary contact b Electronic fusemonitoring kit Cover with fusesurveillance M611 Bridge Clamp Al/Cu Single Prism Clamp 1,5-70 mm2 Al/Cu Triple Clamp 1,0-10 mm2 Al/Cu Feeding Clamp 25-95 mm2 Al/Cu Single cable clamp Al/Cu Double cable clamp Al/Cu ABB Single cable clamp Al/Cu KP Single cable clamp Al/Cu KP Double cable clamp Al/Cu Bolts for cable lug and busbares connection, Al/Cu
1SEP407815R0001 1SEP407815R0002
1SEP407951R0001
6 7 8 9 13
1SEP407740R0001
1SEP407897R0001
14 15 17 18 19 20
21 22
16
23
24
NHP 403631R0001
1SEP407956R0001
25 26
27
28
6,7
16
4-pole
XLP 3 3-POLE 630A 1SEP101975R0002
6 Bridge Clamps (6 BC)
8 ABB Clamps
1)
1)
1)
1SEP407955R0001
17
19
20
NHP 403628R0002 1 pc. 1SEP407956R0001 NHP 403631R0002 1 pc. NHP 403627R0002 1 pc.
17
NHP 403677R0002 1 pc. NHP 403630R0002 1 pc. NHP 403633R0002 1 pc. NHP 403677R0002 1 pc. NHP 403630R0002 1 pc. NHP 403633R0002 1 pc. NHP 403626R0002 1 pc.
21
22
27
1) Clamps, bolts, washers are not included. These have to be ordered separatly.
28 17
Item Description
Type Designation
Order code
XLP 000 Apparatus: XLP 000 -6CC XUP 000-6CC XLP 00 Apparatus: XLP 00 XLP 00-6BC XLP 00-PMNS-3BC XLP 00-EFM-6BC XLP 00-PMNS-EFM-3BC
1SEP201428R0001 1SEP201432R0001
1 1
0,46 0,34
160 A without clamps, bolts 160 A incl. 6 BC 160 A Prepared for MNS adapter incl. 3 BC 160 A incl. El. Fuse Mon. incl 6 BC 160 A Pr. f. MNS Adp. incl. El. Fuse Mon. incl. 3 BC
1 1 1 1 1
XLP 00 with Adapter: XLP 00-A60/60-3BC-Down 160 A incl. A60/60 Adapter incl. 3 BC, cable down XLP 00-A60/60-3BC-Up 160 A incl. A6060 Adapter incl. 3 BC, cable up XLP 00-A40/95-3BC 160 A incl. A40/95 Adapter incl. 3 BC XLP 00-A40/75-3BC 160 A incl. A40/75 Adapter incl. 3 BC XLP 00-A40/75-3M8 160 A incl. A40/75 Adapter incl. 3 M8 bolts XLP 00-A40/120-3BC 160 A incl. A40/120 Adapter incl. 3 BC XLP 00-A40/120-3M8 160 A incl. A40/120 Adapter incl. 3 M8 bolts XLP 1 Apparatus: XLP 1 XLP 1-6BC XUP 1 XUP 1-6BC XLP 1-EFM-6BC XLP 1 with Adapter: XLP 1-A60/85-3BC-Down XLP 1-A60/85-3BC-Up XLP 1-A40/120-3BC XLP 1-A40/120-3M10
1 1 1 1 1 1 1
250 A without clamps 250 A incl. 6 BC 250 A Fuse Base without clamps, bolts 250 A incl. 6 BC 250 A incl. El. Fuse Mon. incl 6 BC
1 1 1 1 1
250 A incl. A60/85 Adapter incl. 3 BC, cable down 230 A incl. A60/85 Adapter incl. 3 BC, cable up 250 A incl. A40/120 Adapter incl. 3 BC 250 A incl. A40/120 Adapter incl. 3 M10 bolts
1 1 1 1
XLP 2 Apparatus: XLP 2 XLP 2-6BC XLP 2-EFM-6BC XLP 3 Apparatus: XLP 3 XLP 3-6BC XLP 3-EFM-6BC
400 A / without clamps , bolts 400 A incl. 6 BC 400 A incl. El. Fuse Monitoring incl 6 BC
1 1 1
630 A / without clamps , bolts 630 A incl. 6 BC 630 A incl. El. Fuse Monitoring incl 6 BC
1 1 1
18
Explanations : XLP XUP = Basic Fuse switch disconnector = Basic Fuse base without front cover
XLP 00-PMNS-EFM-3BC
Apparatus size PMNS = Prepared for MNS adapter Axx/yy = A : Adapter xx : Busbardist. yy : Depth mm. EFM 6CC 3BC 3TC 3FC 3M8 3M10 = Electronic Fuse Monitoring = 6 pcs Cage Clamps = 3 pcs Bridge Clamps = 3 pcs Trippel Clamp = 3 pcs Feeding Clamp = 3 pcs Bolts M8 = 3 pcs Bolts M10 ( XLP 000 )
18
Item Description 1
5 6 7 9 Common Accessories : Micro auxiliary switch Auxiliary switch NC Auxiliary switch NO Padlock device XLP 000 Accessories : XLP 000 Front cover (spare part) XLP 000 DIN rail snap on kit, 1 pc. XLP 000 DIN rail snap on kit, 10 pcs. XLP 000 DIN rail snap on kit, 50 pcs. XLP 000 DIN rail snap on kit, 100 pcs. XLP 000 Front frame f / 1 XLP XLP 000 Front frame f / 2 XLP XLP 000 Front frame f / 3 XLP XLP 00 Accessories : XLP 00 Front cover (spare part) XLP 00 Adapter MNS XLP 00 Adapter A60/60-Down XLP 00 Adapter A60/60-Up XLP 00 Adapter A40/75 XLP 00 Adapter A40/120 XLP 00 Front frame f / 1 XLP XLP 00 Front frame f / 2 XLP XLP 00 Front frame f / 3 XLP XLP 00 Electronic Fuse Monitoring kit XLP 00 Cable shroud XLP 00 Snap on kit for double DIN rail XLP 00 Bridge Clamp (BC) XLP 00 Single Prism Clamp (SPC) XLP 00 Triple Clamp (TC) XLP 00 Feeding Clamp (FC) XLP 00 Bolt M8 x 16 w/ wash XLP 1 Accessories : XLP 1 Front cover (spare part) XLP 1 Adapter A60/85-Down XLP 1 Adapter A60/85-Up 2 3 8 10 11 12 16 15 XLP 1 Front frame f/ 1 XLP XLP 1 Front frame f/ 2 XLP XLP 1 Electronic Fuse Monitoring kit XLP 1 Cable shroud XLP 1 Bridge Clamp (BC) XLP 1 Single Prism Clamp (SPC) XLP 1 Double Prism Clamp (DPC) XLP 1 Bolt M10 x 20 w/ washer XLP 2 Accessories : XLP2 Front cover XLP2 Front frame f/ 1 XLP2 XLP2 Electronic Fuse Monitoring XLP2/3 Cable shroud XLP2/3 Bridge Clamp (BC) XLP2/3 Single Prism Clamp (SPC) XLP2/3 Double Prism Clamp (DPC) XLP2/3 Bolt M12 w/ wash. XLP 3 Accessories : XLP3 Front cover XLP3 Frontframe f/ 1 XLP3 XLP3 Electronic Fuse Monitoring XLP2/3 Cable shroud XLP2/3 Bridge Clamp (BC) XLP2/3 Single Prism Clamp (SPC) XLP2/3 Double Prism Clamp (DPC) XLP2/3 Bolt M12 w/ wash.
Type Designation
Order code
XLP 000, 00, 1, 2 and 3 - 6A / 250V XLP 00, 1, 2 and 3 - 10A / 690V XLP 00, 1, 2 and 3 - 10A / 690V XLP 00, 1, 2 and 3
2 3
2 3 4
1 1 10 50 100 1 1 1
1SEP101873R0001 GLBS500162R0001 For 60 mm busbar distance 5 or 10 mm, cable down For 60 mm busbar distance 5 or 10 mm, cable up 1SEP101915R0001 1SEP101910R0001 1SEP101909R0001 1SEP101909R0002 1SEP407792R0001 1SEP407792R0002 1SEP407792R0003 1SEP304233R0001 1SEP407793R0001 1SEP407897R0001 1SEP407733R0001 1SEP407732R0001 1SEP407787R0001 1SEP407811R0001 NHP400940R0006
1 1 1 1 1 1 1 1 1 1 1 1 3 3 3 3 3
5
NC NO C NO
6,7
2 3 4 8 10 11 12 13 14 15
0,02 0,03 0,04 0,09 0,03 0,24 0,04 0,09 0,15 0,29 0,04
1SEP101883R0001 For 60 mm busbar distance 5 or 10 mm, cable down For 60 mm busbar distance 5 or 10 mm, cable up 1SEP201456R0001 1SEP201451R0001 1SEP407815R0001 1SEP407815R0002 1SEP304279R0001 1SEP407793R0002 1SEP407733R0002 1SEP407732R0002 NHP403631R0001 NHP403625R0001
1 1 1 1 1 1 1 3 3 3 3
0,5 0,74 0,74 0,04 0,06 0,37 0,1 0,11 0,17 0,44 0,09
8 9
10 11
2 8 10 11 12 16 15
1 1 1 1 3 3 3 3
19
12
13
2 8 10 11 12 16 15
14
15
1 1 1 1 3 3 3 3
16
19
SLP 4 Pole SLP 00 4 pole SLP K1 4 pole SLP K2 4 pole SLP K3 4 pole SLP Accessories Cover IP 30 4 pole Cover IP 30 4 pole Cover IP 30 4 pole Cover IP 30 4 pole Auxiliary contact b Auxiliary switch h Front fixing device SLP Cable clamps Single cable clamp, Al/Cu 70-150 mm2 Double cable clamps, Al/Cu 2x(70x150) mm2 Single cable clamp, Al/Cu 16-150 mm2 Single cable clamp, 16 240 mm2 Single cable clamp, Al/Cu 95 - 240 mm2 Double cable clamps, Al/Cu 2x95 240 mm2 Cable lug connection Al/Cu 240mm2 (M10x20) and busbar connection 35 mm2 (M10x20) Cable lug connection Al/Cu 300 mm2 (M12x30)
4 7
NHP 100991P0001 NHP 100993P0001 NHP 100992P0001 NHP 100992P0001 NHPL045270R0001 NHPL045353R0001 NHPL045155R0001
1 1 1 1 1 1 1
SLP-K 1 SLP-K 1 SLP-K 1 SLP-K 2 and SLP-K 3 SLP-K 2 and SLP-K 3 SLP-K 2 and SLP-K 3
10 10 10 20 30 30
NHP 403628R0002 NHP403631R0002 NHP 403627R0002 NHP 403677R0002 NHP 403630R0001 NHP 403633R0001
1 1 1 1 1 1 0,46 0,85
10 8
11
13
25 25
1 1
12
14
Type Designation
5-10 x 12-30 mm 5-10 x 12-30 mm 12-30 x 5 mm 12-30 x 10 mm
Order code
GHV 240849R0001 GHV 240849R0004 GHV 240849R0034 GHV 204849R0036 NHSN320001P0001 NHSN320001P0002
20
20
XLP 00
XLP 1
21
21
XLP 3
22
22
XLP00 A40/120
XLP00 A60/60
23
23
XLP1 A40/120
SF-60 System
24
24
25
25
SLP K1 4 pole
26
26
NHP303408
NHP303599
NHP303398
27
As part of its on-going product improvement, ABB reserves the right to modify the characteristics or the products described in this broschure. The information given is notcontractual. For further details please contact the ABB company marketing these products in your country.
ABB AS Low Voltage Products Automation Technology Products Division P.O. Box 100, Sentrum, N-3701 Skien, Norway Telephone +47 35 58 25 00 Telefax +47 35 58 28 00 e-mail abb.control@no.abb.com www.abb.com