Processor 16 bit, TMS9995 (Texas Instruments) at 12Mhz. Memory 32 Kbytes Program memory (EPROM) 4 x 8 Kbytes - EPROM/EEPROM/RAM Serial Interface - RS232/RS422 (Programmable) Digital Inputs 6 (TTL level), 10 (HCMOS), 7 (24 Volts) Digital Outputs 9 (TTL Level), 14 (HCMOS), 4 (24 Volts) I/O BUS 1 to 16 bits Serial, addressable up to 4096 bits. Analog Inputs - 8 Channels (Bipolar, Programmable as 10V or 50V) Analog Outputs 1 Channel, 10V. Digital Inputs 4 (24 Volts) Digital Outputs 1 (24 Volt) Relay contact Outputs 4 NC / NO Power supply: +5V, 15V, +24V
Measures Generator voltage (7Vdc at 3 x 22Vac(line) input) Measures Generator current (7Vdc at 3 x 5Vac input) (4.2Vdc at 3 x 3Vac input) Measures Sync voltage (7Vdc at 3 x 22Vac(line) input) Conditions Field Current (3Vdc nominal) Generates 12 interrupts per Cycle (sync to R-phase signal) Generates 12 interrupts per 20ms (during free run condition) Monitors frequency and voltage level of actual output. Program execution in CPU is monitored. Interrupt rate is monitored. Internal clock is monitored. Digital Inputs 5 (24 Volt), 6 (HCMOS) Digital Outputs 16 (HCMOS), 2 (24 Volts) Power supply: +5V, 15V, +24V
Digital Inputs 16 (24V) Static inputs. Digital Inputs 16 (24V) Programmable as Pulse/Static inputs. Digital Outputs: 32 (24V) Self monitoring of the module. Module selection through 2 x 6-bit address Switch. (One switch for I/P address and Other for O/P) Power supply: +5V, +24V
Analog inputs - 16 (common mode) or 8 (diff. mode) 0 to +10V or 10V (selectable) 6 channels used as sample and Hold inputs. Analog Outputs 2 (0 to 10V or 10V ; selectable) Module selection through 2 x 6 bit address switch. (One switch for I/P address and Other for O/P) Self checking for functioning of A/D and D/A chips. Power supply: +5V, 15V, +24V
No of Channels 32 (LED indication) Module selection through 6 bit address switch. Module can be used as Master or Slave. Power supply: +5V
Used in Excitation Monitoring system only. Checks for the conduction of the Thyristor within 1 ms time after giving the firing Pulse. Monitors up to 2 Thyristor Bridges. Failure of each Thyrisotr is indicated by lighting a corresponding LED on the Front Panel of the module. Master and Slave operation. Self testing of the firing pulse inputs and internal timing circuit. On failure of any firing pulse or timing circuit, entire monitoring is blocked. Module selection is through 4 bit address switch Power supply: +5V, 15V, +24V
Input : 110Vdc(60V - 156V), 1.7A(3.0A - 1.2A) Output: +5V(5.0V to 5.2V) ,5A, 15V( 14.21V to 15.8V), 1.6A, +24V(22.8V to 26.4V), 4.0A Under Voltage monitoring : 4.7V, 13.9V, 21V (Trips after 10 s) Parallel connection of 2 modules with current balancing.
Input : 220Vdc(100V - 375V), 1.7A(1.8A - 0.5A) Output: +5V(5.0V to 5.2V) ,5A, 15V( 14.21V to 15.8V), 1.6A, +24V(22.8V to 26.4V), 4.0A Under Voltage monitoring : 4.7V, 13.9V, 21V (Trips after 10 s) Parallel connection of 2 modules with current balancing.
Input Voltage: Generator, synchronizing & a spare Rated Input: 3x100Vac .. 120Vac(Generator and synchronizing) 1x100Vac .. 120Vac(spare) Input voltage range: 0 to 130% of rated Input Frequency range: 80 to 120% of rated Input Current: Generator Current, Field Current Rated Input: 3 x 1A or 5A(Generator); 2 x 1A or 5A(Field) Rated Frequency: 50 - 400Hz, Input Current range: 0 to 150% of rated Input Frequency range: 80 to 120% of rated Output Voltage: 3 x 20..24Vac (Generator and Synchronizing) 1 x 20.. 24Vac(Spare) Phase Error input/output <1el Output Current: 3 x 3Vac (Generator) 1 x 3Vdc (Field)
Converts 110Vdc/120Vac into +48Vdc @4A Input voltage: 84Vac to 145Vac (75Vdc to 160Vdc) Output Voltage: +48Vdc rated. Under Voltage Monitoring : <=43Vdc Under Voltage Monitoring Relay: NO contact will be closed.