Sie sind auf Seite 1von 2

ELECTROMAGNETIC FLOWMETER

Technical Specification A) Process Liquid


a) Liquid Type : Raw Water

pH
a) Type b) System c) End Connections d) Flange Rating e) Sensor Electrode material f) Meter Tube g) Sensor Electrode Type h) Lining material i) Connection / Junction Box j) Protection category k) Measuring accuracy l) Coil Housing m) Earthing n) Fluid Conductivity

: 6-8 B) Flow Sensor


: Pulse DC excitation : Separate with cable output : CS, Flanged ends : ANSI #150 : SS 316 : SS 304 (Stainless Steel) : Round head electrodes : Hard Rubber ? : SS 304 : IP67 : +/- 0.5% of Measured value inclusive of Linearity repeatability, Pressure Effect and Hysterics between 0.5 4 m/s velocity. : SS 304 with fully welded construction : Grounding Rings in SS316 : > 20 Siemens/ cm

C) Flow Transmitter / Converter


a) Type b) Display language c) Ambient Temperature d) Display e) Output f) Protection Category g) Enclosure h) Programming i) Power supply j) Cable Gland k) Mounting l) Cable Length : Microprocessor based, Modular Design, Remote mounting : English : -2 deg C + 55 Deg C : Min 2 line back lit LCD for indication of actual rate, forward, reverse, sum totalizes. : 4-20mA : IP 65 : Die Cast Aluminum with polyurethane finish With glass window : Through Key / Keypad on front facia, External Programmer not required. : 230 VAC, 50 Hz : NPT Ni Plated Double compression type) : Wall Mounting : As per the requirement, Maximum Separation Between Sensors & Transmitter should be 200 meters without any Signal booster. : Internal 7 Digit totalizer : Fully interchangeable with all the flow Sensors

m) Flow Totalizer n) Interchangeability

Makes

: Siemens/ Honeywell/Krohne/E&H/Yokogawa

Process Data
Pipe size Service Normal Flow Rate Flow Range Normal Pr. Range Process Temp. : : : : : : 32 (800 mm) Raw water of max. turbidity 1000 ppm, Normal value 50 ppm 2400 T/Hr 0-3000 T/Hr 0.8 to 1.0 Kg/cm2 0-60 oC

All power supply requirement of flow sensors shall be from UPS.

D (Hard Ware and Remote Totaliser )


1. Suitable Expander/ Reducer and associated flanges to achieve (working range) recommended velocity shall be in vendors scope(Smaller diameter flow meter can be
used on bigger diameter pipe with the help of reducers having angle not more than 16 Deg).

2. Suitable canopies for flow meters. 3. Remote totaliser (EPROM protected) shall be in vendors scope.

E( Applicable Standards)

Vendor shall submit calibration certificates conforming to applicable IS/ISO provisions and approved by CPCB/PPCB