Sie sind auf Seite 1von 50

LESSON 25

GENERATOR PROTECTION

OUTLINE OF THE LESSON


1. STATOR WINDING PROTECTION 2. OVERLOAD PROTECTION

3. OVER CURRENT PROTECTION


4. OVER VOLTAGE PROTECTION

STATOR WINDING PROTECTION


The most satisfactory method of protecting an alternator stator is the Merz-Price circulating current technique

Both longitudinal and transverse differential; protection systems are used

LONGITUDINAL DIFFERENTIAL PROTECTION OF DIRECT

CONNECTED GENERATORS

Phase and earth fault protection system

PROTECTION SCHEME FOR

EARTH FAULTS ONLY

FIG

This arrangement is likely to be used only when the individual phases are not
brought out at the neutral end.

Example: A 6600V, 4000KVA star connected alternator has a reactance of 2 ohms/phase and negligible resistance. It is protected by Merz-Price longitudinal differential protection which operates when out of balance current exceeds 30% of the full load current. If Rn= 7.5 ohms, Determine % of winding which remains unprotected. Show that the effect of the generator reactance can be ignored.

The portion of the stator winding

which remains unprotected following


earth fault depends on earthing

resistance and relay setting


Virtually the whole winding is protected against interphase faults since no limiting impedance is included in the fault circuit

Longitudinal differential protection


System does not detect interturn

faults

The earth fault protection schemes

EARTH FAULT PROTECTION FOR THE COMPLETE STATOR WINDING


(percentage bias differential protection
or neutral overcurrent relay or voltage

relay) protect a certain portion of the


winding leaving a part of winding at the

neutral end unprotected.

For large machines there is a requirement for detection of earth fault occurring anywhere in the stator winding

Two different schemes are available for complete protection of the stator winding: 1. Low frequency injection scheme.

1. Third harmonic voltage scheme

LOW FREQUENCY INJECTION SCHEME


In this scheme a sub harmonic voltage is

applied via an injection transformer


connected in series with the neutral earthing

resistance.

A relay which monitors the sub harmonic current is arranged to operate when current increases due to an earth fault on the stator winding.

This scheme provides effective

coverage of the complete stator


winding. However, the cost of the implementation tends to be high due to the cost of the injection equipment.

THIRD HARMONIC VOLTAGE SCHEME


This scheme utilizes the third harmonic

voltage produced by non linearities


within the generator.

Under healthy conditions, this voltage

causes the circulation of third harmonic


capacitive charging currents resulting

in third harmonic voltage appearing


between the neutral of the generator

and ground.

The value of the voltage will depend on 1. The relative values of the impedance of the earthing devices. 2. The capacitance to earth of the stator windings, the capacitance to earth of the busbars, cables and transformer windings connected to the generator.

When fault occurs close to the


neutral of the generator, the third harmonic voltage between the neutral and ground will reduce to near zero-value.

For high resistance earthed generators, measurement of this

voltage provides a clear discrimination


between the faults in the neutral

region of the stator winding and


healthy conditions.

Fig given below shows the variation of


a) The third harmonic voltage during fault and

b) The pre-fault third harmonic voltage as


the function of earth fault position.

Fig.

It may be noted that the pre-fault third

harmonic voltage depends on the


power output of the machines. Fig shows the band over which the prefault voltage may vary.

The third harmonic voltage developed by faults at a distance x to y from the neutral of the generator lies in the same range as produced by pre-fault operating condition.

Thus the location of fault anywhere

from x to y represents a blind zone.


The relay operates if the magnitude

of the third harmonic voltage is


a) Less than OA/or

b) more than OB

Fig.

The problem of blind-zone is overcome by providing two protection system operating simultaneously 1) The one system monitors the fundamental component of the neutral voltage.

2) Monitors the third harmonic


voltage of neutral

The fig. shows relative operation

zones of complementary stator


earth fault relay elements

Fig.

With the combined protection system,


each relay element covers the blind

zone of the other and the combined


protection system will detect earth

faults anywhere on stator winding

INTERTURN FAULT PROTECTION

OF THE
STATOR WINDING

INTER-TURN PROTECTION BY ZERO SEQUENCE VOLTAGE MEASUREMENT


Interturn faults in a generator with a single winding can be detected by observing the zero-sequence voltage across the machine terminals.

Normally, no zero sequence voltage

should exist but a short circuit of


one or more turns on one phase will

cause the generated e.m.f. to contain


such a component

The zero-sequence voltage based interturn fault protection must discriminate against 1. External earth fault will also produce a zero sequence voltage on a directly connected generator.

a) Most of the voltage will be expended on the earthing resistor, the drop on the generator winding being small and the zero-sequence voltage being

limited to one or two percent


b) The zero sequence voltage at the terminals w.r.t. the neutral of the generator rather than w.r.t.

earth

c) This is done by a voltage transformer connected to the line terminals, with the neutral point of

the primary windings connected


to the generator neutral, above the

earthing resistor

d)The voltage transformer has a broken

-delta connected secondary winding


that energizes a relay which therefore

receives a quantity proportional to the


zero-sequence component only

1. The third harmonic component of the e.m.f. is of zero-sequence and is likely to be of a magnitude exceeding the required relay setting. It is therefore necessary to provide a filter to extract the third harmonic component from the VT output and apply it as a relay bias

a) With a direct connected machine it is still possible that a close-up earth fault will produce a zero-sequence voltage drop greater than that produced by the short-circuiting of one-turn.

It is therefore necessary to apply a


short-time delay to tripping outlet

b) An external earth fault cannot


draw zero-sequence current through the generator-transformer unit and hence will produce no residual voltage from the voltage

transformer. NO TIME DELAY IS


REQUIRED IN THIS CASE

OVERLOAD PROTECTION
Overload in terms of current or MVA as distinct from megawatts is possible. It is desirable to provide an overload relay having a suitable time characteristic.

For monitoring the stator winding

temperature embedded thermocouples


or resistance thermometer elements

are provided.
The rotor winding temperature is

checked by measuring the resistance


of the field winding.

OVER CURRENT PROTECTION


It is usual to provide overcurrent relays of the IDMT pattern to generators, as a general back-up feature. These relays are in no way related to the thermal characteristics of the generator and are intended to operate only under fault conditions.

OVER VOLTAGE PROTECTION


Transient overvoltage

Power frequency overvoltage

TRANSIENT OVERVOLTAGE
Surge overvoltages originate largely in the transmission system because of switching and atmospheric

disturbance (lightning)

Surge diverters are provided on the

incoming lines or the station bus


bars

Sometimes surge diverters are


connected also to the generator

terminals.

POWER FREQUENCY OVERVOLTAGE


Overvoltages should not occur on a

machine fitted with a voltage


regulator.

Over voltage may be caused by the following contingencies: 1. Defective operation of the AVR 2. Operation under manual control with the AVR out of service 3. Sudden loss of load (due to line tripping) may cause the hydro

set to over-speed.

Overvoltage protection is not usually provided on attended generators but

maybe required on unattended


automatic hydro stations.

Where applied, it is most effective to


use instantaneous relay with high setting.

Das könnte Ihnen auch gefallen